You are on page 1of 10

This document just gives a not complete description of the ELTEK Flatpack product line

marketed by T-Network Kft. in Hungary and in the surrounding countries. This document is
part of our web page. In case you need more information please contact us.

Flatpack MPSU 3000 system


The Flatpack MPSU 3000 has been specifically designed to meet the demand for higher
capacity and more compact power solutions.

It is suitable for applications needing an expandable, easily serviceable and reliable power
supply, fitting within a minimal space.

The Flatpack MPSU 3000 is a compact power system, controlled by the Flatpack MCU
Monitoring and Control Unit. It can house up to 2 Flatpack 1500 rectifier modules.

Switch mode technology with soft switching and high switching frequency is used to
minimize volume and weight and to obtain fast output voltage regulation.

The system accepts large variations on the input voltage (85-300 VAC) and draws sinusoidal
current with a soft start power-up.

The Flatpack MPSU 3000 will operate in ambient temperatures up to +60°C (+140°F). At
higher temperatures, each rectifier will derate the output power for self-protection.

ELTEK Flatpack Product Line TN_2004.09.23. 1/10 page


FLATPACK MPSU 3000 4U DC OUTPUT
Voltage 48 VDC, 24VDC
Current See Flatpack 1500 48VDC datasheet
SPECIFICATIONS (241114.100.DS3 v.07) or
Flatpack 1500 24VDC datasheet (241114.300.DS3
Max. number of rectifiers 2 v.01) specifications
AC INPUT DC DISTRIBUTION OPTIONS
Voltage 1 phase 230 VAC No. of Load 2 x 125 Amps Siemens MCBs
3 phase 230 VAC ( ∆ ) breakers 11 x Siemens 5SY6 MCBs or
3 phase 400 VAC+N ( Y ) 15 x CBI Q-serie MCBs
No. of Battery 2 of 200 Amps each or
Frequency 45 to 66Hz
fuses 4 of 100 Amps each
Maximum Current See Flatpack 1500 48VDC datasheet Programmable Standard: 1 LVBD (max 250A)
(241114.100.DS3 v.07) or Flatpack LVD Optional: 1 LVLD (max 250A)
1500 24VDC datasheet CONNECTIONS
(241114.300.DS3 v.01) specifications Battery Battery cable, M6 bolts
Protection Soft start connections
Surge protection (varistors) Load MCB 48VDC: Negative, directly in the breakers,
Internal fuses (L & N) connections Positive, common positive bus bars
Disconnect above 312 VAC 24VDC: Positive, directly in the breakers
MONITORING Negative, common negative bus bars
Alarm Plug-in wire connectors rear access
Monitoring Unit Flatpack MCU connections
Local operation Menu driven software via keypads and
LCD or PC (WinPower)
OTHER SPECIFICATIONS
Isolation 3.0 KVAC – input and output
1.5 KVAC – input earth
Remote operation WinPower via modem 1.0 KVDC – output earth
NMS via SNMP-agent Operating Temp -40 to +60°C (-40 to +140°F)
Alarm relays 6 relays are standard Storage Temp -40 to +85°C (-40 to +185°F)
5 extra relays are optional Dimensions 442 x 350 x 178mm (4U) (wxdxh)
Visual indications Green LED – System ON (17.4 x 13.7 x 7’’)
Red LED – Active alarm(s) Weight Approx. 7kg (15.5lbs) excl. rectifiers
LCD – system status APPLICABLE STANDARDS
Digital inputs 4 (for monitoring of external
equipment) Electrical safety EN 60950
Current measurements Battery current UL 60950
Rectifier current EMC ETSI EN 300 386 V.1.3.1
Alarms Load fuse alarm (telecommunication network)
Battery fuse alarm EN 61000-6-3
LVD operated (emission, light industry)
EN 61000-6-2
Low output voltage alarms (2
(immunity, industry)
individual alarm levels)
Environment ETSI EN 300 019-2
High output voltage alarms (2
ETSI EN 300 132-2
individual alarm levels)
Specifications are subject to change without notice.
Low voltage level 1
Low voltage level 2

ORDERING INFORMATION
Part no. Description

MF0200.xxx FLATPACK MPSU 3000 19” 4U 48V


241114.100 FLATPACK 1500 48V 230 VAC rectifier module
351461.003 User manual FLATPACK power system 3U distribution
351461.013 Operational Guide Flatpack 1500 rectifier module 3U distribution
241114.300 FLATPACK 1500 24V 230 VAC rectifier module
MF0200.xxx FLATPACK MPSU 3000 19” 4U 24V

ELTEK Flatpack Product Line TN_2004.09.23. 2/10 page


Rectifier battery charger Flatpack 700 48VDC
The Flatpack 700 48VDC is a battery charger and rectifier
for stand-alone use, or for working in parallel as part of a power rack system controlled
by the Flatpack MCU Monitoring & Control Unit. When connected in parallel, the
rectifiers provide active current sharing, with or without the Monitoring & Control
Unit.

Switch mode technology with soft switching and high switching frequency is used to
minimize volume and weight, and to obtain fast output voltage regulation. The module
accepts large variations on the input voltage and draws sinusoidal current with a soft start
power-up.

The Flatpack 700 48V will operate in ambient temperatures up to +70°C (+158°F). At higher
temperatures, the rectifier will derate the output power and deliver the maximum possible
power until it goes into an over-temperature shutdown.

The rectifier provides 700 W power for universal input voltage range.

ELTEK Flatpack Product Line TN_2004.09.23. 3/10 page


FLATPACK 700 48 V OTHER SPECIFICATIONS
Efficiency > 88% at 110VAC
> 90% at 230VAC
SPECIFICATIONS Isolation 3.0 KVAC – input and output
1.5 KVAC – input earth
INPUT 1.0 KVDC – input earth
Input voltage 85-312 VAC* Rectifier Alarms Mains failure
Module failure
Frequency 45 to 66Hz Overvoltage shutdown
Maximum Current 7.5 Arms maximum at 110VAC Fan failure
3.6 Arms maximum at 230VAC Visual indications Green LED: ON, no faults
Power factor > 0.99 at 50% load or more Red LED: Rectifier failure
Input protection Soft start Yellow LED bargraph: 10 LEDs showing
Surge protection (varistors) load current (0-15A)
Internal fuses (L & N) Operating temp -40 to +70°C (-40 to +158°F)
Disconnect above 312VAC Storage temp -40 to +85°C (-40 to +185°F)
OUTPUT Cooling 2 fans (front to back airflow)
Voltage 48 VDC (range: 44-59 VDC) Brushless w/ magnetic bearing
Fan Speed Temperature regulated
Output power 600 W at 85-99 VAC MTBF > 210,000 hours Telcordia Issue I, method
700 W at 99-312 VAC III (a)
Acoustic Noise < 55dBA (sound pressure)
Maximum current 15 Amps at 48 VDC
Humidity Operating:
Current share ±1.2 Amp from true average current 5% to 95% RH non-condensing
between modules Storage:
Static voltage ±0.5% from 0 to full load 0% to 99% RH non-condensing
regulation Dimensions 214 x 41.5 x 243mm (wxhxd)
(8.43 x 1.64 x 9.57”)
Dynamic voltage ±2% for 10-90% or 90-10% load
Weight 2.8kg (6,17lbs)
regulation variation, regulation time < 10ms
Hold up time 20ms; output voltage > 44 VDC APPLICABLE STANDARDS
Ripple and Noise < 100 mV peak to peak, Electrical safety EN 60950
30 MHz bandwith UL 60950
< 0.96mV rms psophometric EMC ETSI EN 300 386 V.1.3.1
Output Protection Overvoltage shutdown (telecommunication network)
Reverse current blocking EN 61000-6-3
Short circuit proof (emission, light industry)
High temperature protection EN 61000-6-2
(immunity, industry)
Telcordia GR1089 CORE
Harmonics EN 61000-3-2
Environment ETSI EN 300 019-2
ETSI EN 300 132-2
Telcordia GR63 CORE Zone 4
*Above 275 VAC some parameters may vary outside given values. Specifications are subject to change without notice.

ORDERING INFORMATION
Part no. Description
241114.400 FLATPACK 700 48V rectifier module

ELTEK Flatpack Product Line TN_2004.09.23. 4/10 page


Rectifier battery charger Flatpack 1500 48VDC

The Flatpack 1500 48V is a battery charger and rectifier


for stand-alone use, or for working in parallel as part of a power rack system controlled
by the Flatpack MCU Monitoring & Control Unit. When connected in parallel, the
rectifiers provide active current sharing, with or without the Monitoring & Control
Unit.

Switch mode technology with soft switching and high switching frequency is used to
minimize volume and weight, and to obtain fast output voltage regulation. The module
accepts large variations on the input voltage (85-300 VAC) and draws sinusoidal current with
a soft start power-up.

The Flatpack 1500 48V will operate in ambient temperatures up to +70°C (+158°F). At higher
temperatures, the rectifier will derate the output power and deliver the maximum possible
power until it goes into an over-temperature shutdown.

The rectifier provides 1500 W output power at 230 VAC nominal input voltage. The rectifier
provides max. 600 W output power at 48 VDC at 120 VAC nominal input voltage.

ELTEK Flatpack Product Line TN_2004.09.23. 5/10 page


FLATPACK 1500 48 V OTHER SPECIFICATIONS
Efficiency > 90%
Isolation 3.0 KVAC – input and output
SPECIFICATIONS 1.5 KVAC – input earth
1.0 KVDC – input earth
INPUT Rectifier Alarms Mains failure
Input voltage 85-312 VAC Module failure
Overvoltage shutdown
Frequency 45 to 66Hz
Fan failure
Maximum Current 9.2 Arms maximum at 185 VAC and Visual indications Green LED: ON, no faults
1500 W output Red LED: Rectifier failure
Power factor > 0.99 at 50% load or more Yellow LED bargraph: 10 LEDs
Total harmonic showing load current (0-100%)
< 5%
distortion (THD) Operating temp -40 to +70°C (-40 to +158°F)
Input protection Soft start Storage temp -40 to +85°C (-40 to +185°F)
Surge protection (varistors) Cooling 2 fans (front to back airflow)
Internal fuses (L & N) Brushless w/ magnetic bearing
Disconnect above 312VAC Fan Speed Temperature regulated
OUTPUT MTBF > 213,600 hours Telcordia Issue I,
Voltage 48 VDC (range: 44-59 VDC) method III (a)
Acoustic Noise < 55dBA (sound pressure)
Output power 550 W at 85-150 VAC Humidity Operating:
1100 W at 150-185 VAC 5% to 95% RH non-condensing
1500 W at 185-275 VAC Storage:
Maximum current 31.25 Amps at 48 VDC 0% to 99% RH non-condensing
(230 VAC nom.) Dimensions 214 x 41.5 x 243mm (wxhxd)
(8.43 x 1.64 x 9.57”)
Current share ±1 Amp from true average current
Weight 2.8kg (6,17lbs)
between modules
Static voltage regulation ±0.5% from 0 to full load
APPLICABLE STANDARDS
Electrical safety EN 60950
UL 60950
Dynamic voltage ±1.0% for 10-90% or 90-10% load
EMC ETSI EN 300 386 V.1.3.1
regulation variation, regulation time < 10ms
(telecommunication network)
Hold up time 20ms; output voltage > 44 VDC EN 61000-6-3
Ripple and Noise < 100 mV peak to peak, (emission, light industry)
30 MHz bandwith EN 61000-6-2
< 0.96mV rms psophometric (immunity, industry)
Output Protection Overvoltage shutdown Telcordia GR1089 CORE
Blocking diode Harmonics EN 61000-3-2
Short circuit proof Environment ETSI EN 300 019-2
High temperature protection ETSI EN 300 132-2
Telcordia GR63 CORE Zone 4
Specifications are subject to change without notice.

ORDERING INFORMATION
Part no. Description
241114.100 FLATPACK 1500 48V 230VAC rectifier module

ELTEK Flatpack Product Line TN_2004.09.23. 6/10 page


Flatpack MCU
Flatpack MCU Monitoring and Control Unit
The Eltek range of monitoring and control units has been specifically developed
to provide indication and management for DC standby power systems used in
telecommunications and industrial applications

The Flatpack MCU is the Monitoring & Control Unit in Eltek’s Flatpack Power Supply Systems. The
unit allows both local and remote monitoring/control of the Power Supply System via front keypads
and LCD and an RS-232 serial interface.

The Flatpack MCU offers features like

• Front panel LCD and keypad for on-site service (local operation)
• RS-232 interface for PC connection or remote monitoring/control via
modem or SNMP agent
• 6 user programmable relay outputs for traditional remote monitoring
(extendable to 11 relays)
• 5 user programmable inputs for monitoring of other equipment on site
• Battery monitoring and testing without site attendance
• Temperature Compensated Charge Voltage for increased battery
lifetime
• Hot Plug-In
• Modem Callback functionality
• Password protected operator access levels
• Alarm/event log with time and date
• Site Text/ID
• Windows-based PC communication software (WinPower Silver)

ELTEK Flatpack Product Line TN_2004.09.23. 7/10 page


FEATURES
Flatpack MCU • Output Voltage Measurement
• Load Current Measurement (calculated)
Monitoring & Control Unit • Battery Current Measurement
• Rectifier Current Measurement
• Battery Temperature Measurement (optional)
REMOTE MONITORING/CONTROL • Load/Battery Disconnect
• Alarm Level Settings
From a PC running WinPower • Battery Testing (interval and manual)
With the Windows-based “WinPower” • Battery Test Information (2 latest tests)
communication program installed on a remote • Setup of Battery Data
computer, the system can be monitored and • Alarm Log
controlled via modems. • Parameter Calibration
Modem Callback functionality can be used to • Clock and Date adjustment
minimize the traffic on the public telephone • Real Time Clock with Battery Backup
network. • Site Text/ID
• Test of Relay Outputs
From an NMS via Ethernet (SNMP) • Voltage Level Programming
With an external SNMP agent connected to the • Battery Boost Charging
Flatpack MCU, the system can be monitored and • Battery Cable Voltage Drop Compensation
controlled from a Network Management System • Temperature Compensated Charging
through Ethernet on Simple Network Management • Modem Callback
Protocol (SNMP).
AVAILABLE ALARMS
Using alarm relays (voltage free contacts) • High Battery voltage 1 (Level 1)
6 internal failsafe alarm relays provide voltage free • High Battery voltage 2 (level 2)
contacts that can be connected to equipment used • Low Battery voltage 1 (Level 1)
for traditional alarm monitoring. 5 extra relays can • Low Battery voltage 2 (Level 2)
be delivered as an option, providing a total of 11 • Load Disconnect (Voltage or timer)
alarm relays. • Battery Disconnect (Voltage or timer)
• Battery Fuse Alarm
LOCAL MONITORING /CONTROLING • Load Fuse Alarm
• High Battery temp. 1 (level 1)
• High Battery temp. 2 (level 2)
From a PC running WinPower
• Low Battery temp.
WinPower can also communicate with the Flatpack
• Battery Pre Alarm (75% < capacity < 85%)
MCU through an RS-232 C serial cable.
• Battery Failure (capacity < 75%)
• Mains failure
Using front keypads and display
• Rectifier failure (1 module)
Flatpack MCU uses menu driven software to provide
• Critical Rectifier failure (> 1 module)
a user-friendly interface for local operation via a
• Symmetry Failure
keypad and an LCD.
• Battery Test (ongoing test)
• Digital Inputs 1-5 (w. programmable names)
In normal operation, the front LCD will display the
• Rectifier Capacity w. programmable level
output voltage, battery current, rectifier current
• Low temp. w. programmable level
and load current.
• Temperature probe
• Battery discharge
If any alarm is activated, a red LED is lit in the
front panel, the alarm text appears in the LCD and SPECIFICATIONS
the corresponding alarm relay is activated. Input Voltage: Prepared for 24/48/60 VDC
nominal system voltages
Dimensions: 123 x 43 x 177mm (WxHxD)
(4.85 x 1.7 x 6.97”)
Weight: 0.7kg (1.55lbs)

ORDERING INFORMATION
Part no. Description
242072.600 Flatpack MCU
351300.013 Operation Guide, Flatpack MCU

ELTEK Flatpack Product Line TN_2004.09.23. 8/10 page


PRSB 9000 Power Rack System

The Flatpack PRSB 9000 has been specifically designed to meet the demand for higher
capacity and more compact power solutions.

The Flatpack PRSB 9000 is a compact power system, controlled by the Flatpack MCU
Monitoring and Control Unit. It can house up to 6 Flatpack 1500 rectifier modules and
capable of handling up to 250Amps. Switch mode technology with soft switching and high
switching frequency is used to minimize volume and weight and to obtain fast output voltage
regulation.
The system accepts large variations on the input voltage (85-310 VAC) and draws sinusoidal
current with a soft start power-up.

The Flatpack PRSB 9000 will operate at full power in ambient temperatures up to +60°C
(+140°F). At higher temperatures, each rectifier will de-rate its output power and deliver the
maximum possible power at a reduced level until it goes into over-temperature shutdown.

It is suitable for applications needing an expandable (from one to four battery banks), easily
serviceable and reliable power supply, fitting within a minimal space.

ELTEK Flatpack Product Line TN_2004.09.23. 9/10 page


FLATPACK PRSB 9000 CONNECTIONS
Battery Battery cable, M6 bolts
connections
SPECIFICATIONS Load MCB Negative, directly in the breakers,
Max. number of rectifiers 6 connections Positive, 2 common positive bus
bars
AC INPUT Alarm Plug-in wire connectors located in
Voltage 1 phase 230 VAC connections the top-front of the MCU
3 phase 230 VAC ( ∆ )
3 phase 400 VAC+N ( Y ) DISTRIBUTION OPTIONS
Load breakers 2 x 63-125A Siemens MCB’s
Frequency 45 to 66Hz
11 x Siemens 5SY4 MCB’s
Maximum See Flatpack 1500 48VDC datasheet or 15 x CBI, Q-serie MCB’s
Current (241114.100.DS3) Battery fuses 2 of 200 Amps each or
4 of 100 Amps each
Protection Soft start
Programmable Standard: 1 LVBD (max 250A)
Surge protection (varistors)
LVD Optional: 1 LVLD (max 250A)
Internal fuses (L & N)
Disconnect above 310 VAC OTHER SPECIFICATIONS
Isolation 3.0 KVAC – input and output
MONITORING 1.5 KVAC – input earth
Monitoring Unit Flatpack MCU 1.0 KVDC – output earth
Local operation Menu driven software via Operating Temp -40 to +60°C (-40 to +140°F)
keypads and LCD or PC
Storage Temp -40 to +85°C (-40 to +185°F)
(WinPower)
Dimensions 600 x 600 x 630mm (wxdxh)
(23,6 x 23,6 x 24.8”)
Alarm relays 6 relays are standard 600 x 600 x 900mm (wxdxh)
5 extra relays are optional (23,6 x 23,6 x 35.4”)
Visual indications Green LED – System ON 600 x 600 x 1800mm (wxdxh)
Red LED – Active alarm(s) (23,6 x 23,6 x 70.9”)
LCD – system status
Weight 630mm: Approx. 35kg (77lbs)
Digital inputs 5 (for monitoring of external excl. rectifiers
equipment) 900mm: Approx. 40kg (88lbs)
Current readings Battery current, Load excl. rectifiers
Rectifier current 1800mm: Approx. 70kg (154lbs)
Alarms Load fuse alarm excl. rectifiers
Battery fuse alarm
LVD operated
APPLICABLE STANDARDS
Electrical safety EN 60950
Low output voltage alarms
(2 individual alarm levels) EMC ETSI EN 300 386 V.1.3.1
High output voltage alarms (telecommunication network)
(2 individual alarm levels) EN 61000-6-3
(emission, light industry)
DC OUTPUT EN 61000-6-2
Voltage 48 VDC, 24VDC (immunity, industry)
Current See Flatpack 1500 48VDC datasheet Environment ETSI EN 300 019
(241114.100.DS3)

Specifications are subject to change without notice.

ORDERING INFORMATION
Part no. Description
CF0618.01K Flatpack PRSB 9000, 900mm
CF0613.01K Flatpack PRSB 9000, 630mm
CF0638.01K Flatpack PRSB 9000, 1800mm
241114.100 FLATPACK 1500 48V 230VAC rectifier module

ELTEK Flatpack Product Line TN_2004.09.23. 10/10 page

You might also like