You are on page 1of 2

ZXDU68 S/T601 Power System

Intelligent system management:


● Battery temperature charge compensation

● Fast charge

● Battery current limit

● Automatic equalize charge

The power status information system allows the remote


operation center to reduce, prepare, and prioritize site
visits. The system and the rectifiers are fully complying with
international standards.

ZXDU68 S/T601 Application:


● GSM/CDMA center station
Adopting ZXD2400 rectifier module, ZXDU68 S/T601 is a high
frequency switch mode DC power systems designed by ZTE. ● Microwave repeat station

Based on leading proprietary and standard technology, the ● Satellite BSC station
system rectifier is designed with high reliability, high efficiency,
and well electromagnetic compatible and easy to maintain. ● Transmission equipment

The maximum configured capacity is 600A with twelve 50A ● Other middle/large capacity situation
rectifier modules.
Key Features Benefits
● Power efficiency is up to 94% ● Low power consumption of rectifier modules reduces cost for electricity.
● Rectifier module hibernates in rotation and the hibernation ● Highly adaptable to adverse environment saves expenditure for air
power consumption is less than 4W conditioners.
● Wide operating temperature of rectifier modules range from ● Adaptable to various and poor power grids, provides stable power supply
-40 to 70°C
● Minimal interference to equipments on the same commercial power supply.
● Wide input voltage range from 80 to 300Vac
● Save 30% of space than that of the 600mm depth cabinet, save Capex
● THD is less than 2.8%
● Easy maintenance, the system can be positioned next to wall to save space.
● Space efficient cabinet with 400mm depth
● Environmental-friendly
● Front access design 5
● MTBF >2.2 * 10 h
● Noise <55 dBA

System Technical Specifications Rectifier Technical Specifications


Parameters Description Parameters Description
AC input AC input
380 Vac three phase Input mode Single-phase/three-line
Rated input voltage Rated output: 220Vac;
220 Vac single phase (compatible) Input voltage
operating range: 80 ~ 300Vac
Input Voltage range
80 ~ 300 Vac Input frequency 45 Hz - 66 Hz
(phase to neutral)
Input current 16A (maximum)
Maximum input current 100 A
Frequency 45 Hz - 66 Hz Efficiency ≥ 94%
Input power factor ≥ 0.99
Power factor ≥ 0.99 (with full load)
DC output
THD <2.8%
Rated output power: 2400 W;
DC Output Output power
Maximum output power: 3000 W.
-48Vdc nominal; Rated output: -48 Vdc,
Output voltage Output voltage
operating range -42~ -58 Vdc adjustable range: -42 Vdc ~ -58 Vdc
Output current 600 A (full load at >176Vac) Hibernation power
<4W
consumption
Battery input 2*400A breakers
Others
Efficiency ≥ 94% (rated input; full load)
Operating temperature -40~70°C
DC lightning discharge current ≤ 5 kA Dimensions 134 mm × 87 mm × 290 mm (H x W x D)
Protection OCP, OVP, UVP, OTP Weight 3.8 kg
Safety standard IEC60950 standards Applicable standards
Environment Requirement Electrical safety IEC60950-1
Operating temperature –10°C ~ 45°C ETSI EN300
EN61000-6-1
Storage temperature –40°C ~ 70°C
(immunity, light industry)
Relative humidity 10% to 90% EN61000-6-2
Dimensions and weight EMC (immunity, light industry)
Dimensions (ZXDU68 S601) 2000mm×600mm×400mm (H x W x D) EN61000-6-3
(emission, light industry)
Dimensions (ZXDU68 T601) 1600mm×600mm×400mm (H x W x D) EN61000-6-4
Weight (without rectifier) 85kg for S601, 80kg for T601 (immunity, light industry)

For continuous improvement and development, the specifications are subject to change without prior notice.