General
SafeRing is a ring main unit for the secondary distribution network. SafeRing can be supplied
in a number of different configurations suitable for most switching applications in 12/24 kV
distribution networks. When combined with the flexible SafePlus concept, which is ABB’s
extendable, modular compact switchgear, they represent a complete solution for 12/24 kV
secondary distribution networks. SafeRing and SafePlus have identical user interfaces.
SafeRing is a completely sealed system with a stainless steel tank containing all the live parts
and switching functions. A sealed steel tank with constant atmospheric conditions ensures a
high level of reliability as well as personnel safety and a virtually maintenance-free system.
The SafeRing concept offers a choice of either a switch fuse combination or circuit breaker
with relay for protection of the transformer. As the first ring main unit, SafeRing can be
supplied complete with an integral remote control and monitoring unit.
DF CCF CCC
CCCF CCFF
16273-5974 GB-Safering 06.12.01 13:22 Side 4
SafeRing
TRANSFORMER PROTECTION
The SafeRing offers a choice between a switch fuse combination and circuit
a TEST BUSHINGS breaker with relay for transformer protection. The switch fuse combination
SafeRing can be equipped with offers optimal protection against short-circuits, while the circuit breaker with
test bushings for simple cable relay option offers better protection against low overcurrents. Circuit breaker
testing. The test bushings are
with relay is always recommended for larger transformers.
placed on the front of the RMU. If
test bushings and remote control
and monitoring unit are used to-
gether, the remote control and
monitoring unit will be placed on
the top of the RMU.
b CIRCUIT BREAKER
WITH RELAY
When vacuum circuit breakers
are chosen as transformer pro-
tection, the standard relay is ABB
PR521. This system of protection
does not require an external po-
wer supply, as the power is taken
from the current transformers. A
limited choise of other relays are
available on demand.
c FUSES
When switch fuse combinations
are chosen as transformer
protection, the fuse canisters are
positioned behind a separately
interlocked cover in front of the
unit. To facilitate fuse replace-
ment, the operating handle is
used to remove the fuse canister
covers. The fuse tripping system
is located at the front, ensuring
that the entire solution is water-
proof.
16273-5974 GB-Safering 06.12.01 13:23 Side 5
ng RMU
e
g
d VOLTAGE INDICATION
The ring main unit can be equip-
d ped with capacitive voltage
indication. There is a choice
between permanently connected
lamps or plug in type indicators.
The same test sockets are also
used for phase comparison.
e SHORT CIRCUIT
c INDICATORS
In order to facilitate the locating
of faults, the cable switch
modules can be supplied with
short circuit indicators for simple
f fault detection.
f ARC SUPPRESSOR
All SafeRing ring main units can
be supplied with an arc
suppressor which closes auto-
matically on the feeder bushings
if an internal arc fault occurs.
h
g MOTORISED OPERATION
Manually operated mechanisms
for cable and transformer
switches are supplied as
standard. As an option, they can
also be fitted with motor
operation.
h CABLE CONNECTIONS
SafeRing is fitted with standard-
ised bushings that comply with
DIN 47636. All the bushings are
the same height from the ground
and are protected by a cable
cover. The cable covers can be
supplied with interlocking to the
earthing switches. As an option
arc-proof cable covers are
available. It is also possible to
connect parallel cables with a
special double cable cover.
KEY INTERLOCKING
SafeRing can be supplied with
a key interlocking system for
breakers, switches and earthing
switches.
16273-5974 GB-Safering 06.12.01 13:23 Side 6
FUNCTIONS:
• Remote control and position indication for up to 4 switches
• Monitoring of short-circuit indicators
• Monitoring of SF6 gas pressure/density
• Position indication for arc suppressor
ADDITIONAL EQUIPMENT:
• DPI- Direct Process Interface board for:
Monitoring of current on the high-voltage side with ring core transformers.
Monitoring of current and voltage, on the low-voltage side of the distribution transformer. (Power
quality monitoring)
COMMUNICATION:
The unit can be supplied for different types of communication media. External communication
such as radio is connected via an RS232 interface which is supplied as standard.
ns
io
ic at
un
m
m
Co
Control Center
16273-5974 GB-Safering 06.12.01 13:24 Side 7
A
100 765
1365
1248
RMU A B C
2-way 696 622 663
3-way 1021 947 983
4-way 1346 1272 1313
* NB Fixing bracket
Technical specification:
C- module F- module V- module
1) Depending on the current rating of the fuse 2) Limited by High Voltage fuse links
SafePlus is tested according to IEC publications IEC 60265, IEC 60129, IEC 60056, IEC 60420, IEC 60694 and IEC 60298.
Compact secondary Small industries Wind Turbines Hotels, Shopping Light mining appli-
substations Centres, Office cations, Tunnels,
Buildings, Buisness and Underground
Center etc. Railways
ADDITIONAL EQUIPMENT:
• Manometer
• Manometer and signal (1NO) from pressure indicator wired to terminals
• Cable cover with window
• Cable cover for double T
• Emergency trip push button
• Aux. switch for vacuum circuit breaker position 2NO + 2NC
• Aux. switch for disconnected position 2NO + 2NC
• Aux. switch for earth switch position 2NO + 2NC
• Vacuum circuit breaker tripped signal 1NO
• Prepared for relay test equipment
• Aux. switch for load break switch position 2NO + 2NC
• Aux. switch for fuse blown 1NO
• Cable test bushings
• Arc proof cable covers complete incl. Interlocking
• Interlocked cable covers
• Cable support bars
• Cable support bars, non-magnetic
• Extra base frame (h=450 mm)
• Ronis interlocking system,EL 11 AP
• Current measuring
• Arc suppressor
• Integrated control and monitoring (ICMU)
• Trip coil open
• Trip coil open and close
• Motor operation
• Capacitive voltage indication
• Short circuit indicator
Fax: +47 35 52 41 08
www.abb.no
Edition 3 - 0012 - 4000