Flexible AC Transmission Systems


Rahul J. Shimpi Rajendra P. Desale Kunal S. Patil
Lecturer Lecturer Lecturer
Department of Electronics Engg. Department of Electronics Engg. Department of Electronics Engg.
S.S.V.P.S’s College of Engg. Dhule S.S.V.P.S’s College of Engg. Dhule S.S.V.P.S’s College of Engg. Dhule
5 Forest Colony Nagaon Bari Shahu Nagar
Deopur Dhule-05 (India) Deopur Dhule-05 (India) Deopur Dhule-05 (India)

Jaswantsing L. Rajput Shailesh B. Chavan


Lecturer Lecturer
Department of Electronics Engg. Department of Electronics Engg.
S.S.V.P.S’s College of Engg. Dhule S.S.V.P.S’s College of Engg. Dhule
Datta Mandir Chowk Yugondhar Colony
Deopur Dhule-05 (India) Deopur Dhule-05 (India)

ABSTRACT
1. FACTS or "flexible AC transmission systems" is a term that provide control of one or more AC transmission system
has been suggested for the use of solid state devices to control parameters to enhance controllability and increase power
bulk power flow in transmission systems. The Electric Power transfer capability."
Research Institute supported this idea, and many researchers
have invested efforts on the value and potential of FACTS. At FACTS technology:
this time, it appears that the main value of FACTS lies in
improving transmission capability; increasing the flexibility of FACTS could be connected:
power flow control (e.g., for wheeling or for economic • in series with the power system (series compensation)
dispatch); for controlling voltage (and var flow); and possibly • in shunt with the power system (shunt compensation)
additional advantages in lower voltage systems (e.g., • both in series and in shunt with the power system
distributional systems).
2. Flexible AC Transmission Systems (FACTS) controllers Series compensation:
have been used in power systems since the 1970s with the
objective of improving system dynamic performance. Due to the In series compensation, the FACTS is connected in series with
environmental, right-of-way, and cost problems in both bundled the power system. It works as a controllable voltage source.
and unbundled power systems, many transmission lines have Series inductance occurs in long transmission lines, and when a
been forced to operate at almost their full capacities worldwide. large current flow it causes a large voltage drop. To compensate,
FACTS controllers enhance the static performance viz. series capacitors are connected.
increased loading, congestion management, reduced system loss,
economic operation, etc., and dynamic performance viz.
increased stability limits, damping of power system oscillation,
etc. In this paper, an overview of FACTS controllers is
explained. Various FACTS controllers and several devices in
FACTS family are also discussed.

Introduction
Flexible AC transmission system:

Flexible Alternating Current Transmission System (FACTS) is


static equipment used for the AC transmission of electrical
energy. It is meant to enhance controllability and increase power
the transfer capability of the network. It is generally a power Fig a: series compensation
electronics-based device. FACTS is defined by the IEEE as "a
power electronic based system and other static equipment that

54
©2010 International Journal of Computer Applications (0975 - 8887)
Volume 1 – No. 15

Shunt compensation:
In shunt compensation, power system is connected in shunt with In the case of a no-loss line, voltage magnitude at
the FACTS. It works as a controllable source. Shunt receiving end is the same as voltage magnitude at sending end:
compensation is of two types Vs = Vr=V. Transmission results in a phase lag d4that depends
on line reactance X.

VS= V cos (δ/2) + jV sin (δ/2)

Vr= V cos (δ/2) - jV sin (δ/2)

L= (VS - Vr)/ jX = [2Vsin(δ/2)]/X

This is shown in fig


Fig b: shunt compensation

Shunt capacitive compensation:


This method is used improve the power factor. Whenever an
inductive load is connected to the transmission line, power
factor lags because of lagging load current. To compensate, a
shunt capacitor is connected which draws current leading the
source voltage. The net result is improvement in power factor.

Shunt inductive compensation:


This method is used either when charging the transmission line,
or, when there is very low load at the receiving end. Due to very
low, or no load very low current flows through the transmission
line. Shunt capacitance in the transmission line causes voltage
amplification (Ferranti Effect). The receiving end voltage may
become double the sending end voltage. To compensate, shunt As it is a no-loss line, active power P is the same at any point of
inductors are connected across the transmission line. the

Static VAR Compensator:


It helps in keeping steady state and dynamic voltages within Reactive power at sending end is the opposite of reactive power
their limits, but it does not provide any control of active power. at receiving end:
The var output can be varied continuously between the
capacitive and inductive ratings of the equipment. The necessary
reactive power required for the compensation is generated or As dH is very small, active power mainly depends on dH
absorbed by capacitor or reactor banks. Thyristor switches are whereas reactive power mainly depends on voltage magnitude.
only used to control the combined reactive impedance the banks
present to the system. An advanced static compensator has been What are FACTS devices?
recently presented. This device provides control for real and FACTS stand for Flexible AC Transmission Systems. The term
reactive power. “FACTS” covers several power electronics based systems used
for AC power transmission. FACTS solutions are particularly
suitable in applications, which require one or more of the
following qualities:
• Rapid dynamic response
• Ability for frequent variations in output
• Smoothly adjustable output
• Fast implementation to achieve considerable increase in
transmission capacity.

FACTS CONCEPTS SIMILAR TO HVDC


While some of the relevant technology i.e., Static VAR
Compensation is already in wide use, the FACTS concept has
brought to the table a tremendous potential for thyristor based
FACTS theory: controllers which will surely revolutionize the power system.
The technology offers the utilities the ability to:

55
©2010 International Journal of Computer Applications (0975 - 8887)
Volume 1 – No. 15

1. Control power flows on their transmission routes; thyristor is their basic element, just as the transistor is the basic
2. Allow secure loading of transmission lines to their full element for a whole variety of microelectronic circuit. Because
thermal capacity. FACTS technology, while allowing use of all controllers for the flexible transmission system are
transmission to its thermal capacity, does not do away with the applications of similar technology, their use will eventually
need for additional transmission lines or the upgrading of benefit from volume production and further development of
existing lines where thermal limits have been reached or when high-power electronics.
evaluation of losses added to the cost of FACTS technology Electric power networks integrate generation and load centers
shows that new lines or upgrading of existing lines is the most within each utility system and through interconnections among
optimum answer. Often, ac transmission systems are thought of neighboring systems, share power with vast regional grids. The
as being "inflexible". Power flow in ac networks simply follows purpose of this is to take advantage of the diversity of loads,
Ohm's law and ordinarily cannot be made to flow along specific changes in peak demand due to weather and time differences,
desired paths. As a result, ac networks suffer from parallel-path, the availability of different generation reserves in various
or "loop" flows. The power flows from source to load in inverse geographic regions, power sharing arrangements among utilities,
proportion to the relative impedances of the transmission paths. shifts in fuel prices, regulatory changes, and other discrepancies.
Low impedance paths take the largest fraction of flow, but all
lines in the interconnection are a part of the flow path. Thus, Applying Flexibility to the Electric Power
utilities not involved in an interchange power transaction can be
affected. System:
A fundamental notion behind FACTS is that it is possible to The power industry term FACTS (Flexible AC Transmission
continuously vary the apparent impedance of specific Systems) covers a number of technologies that enhance the
transmission lines so as to force power to flow along a "contract security, capacity and flexibility of power transmission systems.
path". This is a brand-new concept for many system planners. FACTS solutions enable power grid owners to increase existing
As illustrated in Figure 1.3, with precise control of the transmission network capacity while maintaining or improving
impedance of transmission lines using FACTS devices, it is the operating margins necessary for grid stability. As a result,
possible to maintain constant power flow along a desired path in more power can reach consumers with a minimum impact on the
the presence of continuous changes of load levels in the external environment, after substantially shorter project implementation
ac network, and to react in a planned way to contingencies. Just times, and at lower investment costs - all compared to the
as in HVDC applications, FACTS controls could be designed to alternative of building new transmission lines or power
enhance the behavior of the uncontrolled systems. generation facilities.
The two main reasons for incorporating FACTS devices in
electric power systems are:
• Raising dynamic stability limits
• Provide better power flow control

Neuro-Control Approach for Flexible AC


Transmission Systems:
A neuro-control approach for flexible AC transmission systems
(FACTS) based on radial basis function neural network
(RBFNN) is presented in this paper. The proposed scheme
consists of a single neuron network whose input is derived from
the active or reactive power or voltage derivation at the power
The flexible system owes its tighter transmission control to its system bus, where the FACTS device (in this case a unified
ability to manage the interrelated parameters that constrain power flow controller) is located.
today's systems, including series impedance, shunt impedance, The performance and usefulness of this approach is tested and
phase angle, and the occurrence of oscillations at various evaluated using both single machine infinite-bus and two-
frequencies below the rated frequency. By adding to in this way, machine power system subjected to various transient
the controllers enable a transmission line to function nearer its disturbances. It was found that the new intelligent controller for
thermal rating. For example, a 500-kV line may have a loading FACTS exhibits a superior dynamic performance in
limit of 1000-2000MW for safe operation, but a thermal limit of compensation to the existing classical control schemes. Its
3000 MW. simple architecture reduces the computational overhead, thereby
It is often not possible both to overcome these constraints and real-time implementation.
maintain the required system reliability by conventional
mechanical means alone, such as tap changers, phase shifters, Benefits of FACTS:
and switched capacitors and reactors (inductors).Granted, When implemented on a broad-scale basis, FACTS technologies
mechanical controllers are on the wholeless expensive, but they deliver the following benefits.
increasingly need to be supplemented by rapidly responding •A Rapidly Implemented Installations: FACTS projects are
power electronics controllers. installed at existing substations and avoid the taking of public or
The new technology is not a single, high-power electronic private lands. They can be completed in less than 12 to 18
controller, but rather a collection of controllers, which can be months a substantially shorter timeframe than the process
applied individually or collectively in a specific power system to required for constructing new transmission lines.
control the five interrelated functions already mentioned. The

56
©2010 International Journal of Computer Applications (0975 - 8887)
Volume 1 – No. 15

•Increased System Capacity: FACTS provide increased capacity California and Texas, as well as in the New England region of
on the existing electrical transmission system infrastructure by the United States and in some areas of Canada. As more
allowing maximum operational efficiency of existing electricity stakeholders recognize the technical and public policy
transmission lines and other advantages that these technologies confer, additional
equipment. applications will emerge. Advancements in the state of the art of
•Enhanced System Reliability: FACTS strengthen the FACTS technologies will continue and will further advance the
operational integrity of transmission networks, allowing greater case for breaking transmission gridlock with these innovative
voltage stability and power flow control, which leads to and proven systems.
enhanced system reliability and security.
•Improved System Controllability: FACTS allow improved REFERENCE
system controllability by building “intelligence” into the Narain G. Hingorani, Laszlo Gyugyi Understanding FACTS:
transmission network via the ability to instantaneously respond Concepts and Technology of Flexible AC Transmission
to system disturbances and gridlock constraints and to enable Systems, Wiley-IEEE Press, December
redirection of power flows.
•Seamless System Interconnections: FACTS, in the form of 1999.
BTB dc-link configurations, can establish “seamless” An Overview of Flexible AC Transmission System--
interconnections within and between regional and local docs.lib.purdue.edu/ecetr/205/ -
networks, allowing controlled power transfer and an increase in A Neuro-Control Approach for Flexible AC Transmission
grid stability. www.actapress.com/PaperInfo.aspx?PaperID=18012-
Flexible AC Transmission system- Wikipedia, the free
encyclopedia--
CONCLUSION http://en.wikepidia.org/wiki/Flexible_AC_transmission_system
Over the past several years, FACTS applications have increased
significantly as compared to the previous decade. There are now
numerous FACTS applications, including recent installations in