ANCHOR BOLT DESIGN

Designed by:
Checked by :

8.0 203.2 203.2 8.0


(in) (mm) (mm) (in) Concrete strength 30 Mpa 4286 psi
type - 1 Anchor bolt material type A307 (A307, A325)
side-2 Anchor bolt diameter 38.1 mm 1.50 in
Minimum edge distance *) 190.5 mm 7.50 in
254 10.0 Minimum edge distance (CSA A23.3 App.D4.2.1)

side-3
(mm) (in) 135.2 mm 5.32 in
edge distance is OK

side-1
406.4 16.0 Minimum embedment length *) 457.2 mm 18.00 in
side-4
(mm) (in) Select embedment length 584.2 mm 23.00 in
embedment length is OK

type - 2 No of anchor bolt type 1 4


No of anchor bolt type 2 0
Bolt Fu 414 Mpa 59 ksi
corrosion allowance 1.59 mm 0.063 in

76.2 (mm) 3.0 (in) *) based on AISC Steel Design Guide Series for Column Base Plates

A A
711.2 mm 28.0 in
B B -127.0 mm -5.0 in

Tensile strength capacity

Total anchor bolt steel capacity 867 kN 194 kips Governing tensile strength capacity 496 kN
Strength based on concrete: 111 kips
Cone diameter at:
section A-A 1168.4 mm 46 in
section B-B 0 mm 0 in

Total projected effective tensile area 794837 mm2 1232 in2


Override the total projected effective tensile area? y (Y/N)
Total projected effective tensile area to be used in this calculation (mm2):
502780
Concrete tensile strength 0.99 Mpa 141 psi CSA A23.3-94 App.D4.1.1
Pull out concrete capacity 496 kN 111 kips
Tensile area calculations

Case 1

Case-1

Total core area of cone base at section A-A 319999 mm2 496.0 in2
At section A-A
cone base side area on side 1 and opp. 165161 mm2 256.0 in2
cone base side area on side 2 and opp. 103226 mm2 160.0 in2
cone base corner areas 206451 mm2 320.0 in2
At section B-B
Cone radius at B-B 0 mm 0.0 in
cone base side area on side 1 and opp. 0 mm2 0.0 in2 0
cone base side area on side 2 and opp. 0 mm2 0.0 in2 0
cone base corner areas 0 mm2 0.0 in2

Total tensile area 794837 mm2 1232.0 in2

Case-2

Total core area of cone base at section A-A 189935 mm2 294.4 in2
At section A-A
cone base side area on side 1 and opp. 474838 mm2 736.0 in2
cone base side area on side 2 and opp. 103226 mm2 160.0 in2
cone base corner areas 206451 mm2 320.0 in2
At section B-B
Cone radius at B-B 0 mm 0.0 in
cone base side area on side 1 and opp. 0 mm2 0.0 in2 0
cone base side area on side 2 and opp. 0 mm2 0.0 in2 0
cone base corner areas 0 mm2 0.0 in2

Total tensile area 974450 mm2 1510.4 in2

Case-3

Total core area of cone base at section A-A 379870 mm2 588.8 in2
At section A-A
cone base side area on side 1 and opp. 165161 mm2 256.0 in2
cone base side area on side 2 and opp. 949676 mm2 1472.0 in2
cone base corner areas 206451 mm2 320.0 in2
At section B-B
Cone radius at B-B 0 mm 0.0 in
cone base side area on side 1 and opp. 0 mm2 0.0 in2 0
cone base side area on side 2 and opp. 0 mm2 0.0 in2 0
cone base corner areas 0 mm2 0.0 in2

Total tensile area 1701158 mm2 2636.8 in2

Case-4

Total core area of cone base at section A-A 1072193 mm2 1661.9 in2
At section A-A
cone base side area on side 1 and opp. 474838 mm2 736.0 in2
cone base side area on side 2 and opp. 949676 mm2 1472.0 in2
cone base corner areas 0 mm2 0.0 in2
At section B-B
Cone radius at B-B 0 mm 0.0 in
cone base side area on side 1 and opp. 0 mm2 0.0 in2 0
cone base side area on side 2 and opp. 0 mm2 0.0 in2 0
cone base corner areas 0 mm2 0.0 in2

Total tensile area 2496706 mm2 3869.9 in2