SBH-15 Hermetically-sealed oil-immersed

amorphous alloy distribution transformer

Product introduction
Hermetically-sealed amorphous alloy distribution
transformer adopts the amorphous alloy iron as its
magnetic material. It is eco-friendly and energy
conservation, which complies with the standard of
China energy conservation outline
issued by National
Economic Committee.

Model designation
43
S (B) H -  -  / 

Voltage class(kV)
Rated capacity(kVA)
Performance level code
Amorphous alloy
LV foil windiing
Three-phase

Normal service condition


a. Altitude should not be over 1000m, indoor type
b. Highest ambient temperature should not over  40; highest daily average temperature should not over  30
c. Highest annual average temperature should not over  20, lowest temperature should not below -25
* We can supply the transformers which operate in special operating conditions according to user's requirements.

Applicable standards
a. GB1094.1~2-1996GB1094.345-1985 Power transformer
b. JB/T10318-2002 Technical parameters and requirements for hermetically-sealed and oil-immersed amorphous alloy
distribution transformer

Character of performance
a. Iron's magnetic material adopts amorphous alloy, which consists of materials such as iron and boron, etc.
b. The iron structure of amorphous alloy transformer adopts three phases and five columns.
c. This kind of transformer has similar body assemblystructure of oil tank, and protection devices with hermetical oil-
immersed transformer.
d. This kind of transformer has same load-loss with S9 series, but the no-load loss of SBH-15 transformers are decreased
by approx. 75% by comparing with S9 series. It can save electricity and decrease the loss cost. Generally, we can take back
the extra investment in four years compared with the silicon-steel iron transformer.
e. Under the normal operation, it does not need to change oil, which decreases the transformer's maintenance cost and
prolongs the service life.
SBH-15 Hermetically-sealed oil-immersed
amorphous alloy distribution transformer

Note for placing order


Transformer type: rated capacity kVA Number of phases: three-phase  single-phase 
High voltage: kV/Low voltage kV Frequency: 50Hz  60Hz 
Tapping range:  4x2.5%   3x2.5%  other  Connection group: Yyn0  Dyn11  other 
Impedance voltage: 4%  6%  other  Cooling method: ONAN  ONAF 
Protecting grade of outer casing: IP00  IP20  IP30  other 

Method of incoming and outgoing line:


1. Incoming line to lower part and outgoing line from upper part 
2. Incoming line to upper part and outgoing line form upper part 
3. Incoming line to lower part and outgoing line from side part  44
4. other 
* If customer has no requirement, the color of outer casing is light grey (the standard color of Delixi), or you should indicate
color code that you want 
45
j~áå= íÉÅÜåáÅ~ä= é~ê~ãÉíÉêë= çÑ= p_eNRJjJPMúNSMMLNM= ëÉêáÉë= çÑ= íê~åëÑçêãÉêë
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

50 43 870 1.3 160 680 950  620  1040 400  550

100 75 1500 1.0 180 880 1060  770  1070 400  550

160 100 2200 0.7 200 1100 1100  830  1200 550  550

200 120 2600 4 0.7 220 1190 1150  850  1250. 550  550

250 6.3 140 3050 0.7 250 1350 1260  870  1200 660  660

315 10 170 3650 0.5 280 1600 1350  910  1250 660  660

 2  2.5 0.4 Dyn11


400 10.5 200 4300 0.5 330 1900 1450  920  1300 660  660

500 11 240 5150 0.5 350 2100 1410  960  1260 660  660

630 320 6200 0.3 420 2460 1900  980  1450 660  660
amorphous alloy distribution transformer
SBH-15 Hermetically-sealed oil-immersed

800 380 7500 0.3 500 2900 1980  1000  1350 820  820

1000 450 10300 0.3 550 3300 2060  1160  1310 820  820
4.5

1250 530 12000 0.2 680 4000 2160  1190  1450 820  820

1600 630 14500 0.2 750 4600 2250  1380  1600 1070  1070
S9-M-30~2500/10
Hermetically-sealed distribution transformer

Production introduction
Installation mode: indoor/outdoor type
Ambient temperature: -25+40 (outdoor)
-5+40 (indoor)
Highest altitude: 1000m
Installation site: in places without corrosive gases
and obvious dusts

Applicable standards
GB1094.1-2-1996 Power Transformer
46
GB1094.3; 5-2003 Power Transformer
GB/T6451-1999 Technical parameters
and requirements for three-phase
oil-immersed power transformer

Model designation

S - M -  / 
Voltage class(kV)
Rated capacity(kVA)
Sealed structure
Performance level code
Three-phase oil-immersed transformer

Performance characteristics
1. A multilayer cylinder structure is used for all high voltage windings in order to improve the voltage impulse distribution of
windings.
2. For the capacity range of low voltage windings is from 30kVA to 2000kVA, the cylinder type or spiral structure is used to
ensure the high mechanical strength, ampere lure distribution, and excellent short-circuits proof performance.
3. The securing structure is set in the transformer body, which is used for ensuring that no displacement will occur during the
transportation; meanwhile, the turnbuckles are mounted in fasteners, which is for assuring that fasteners will not be loose
during the long term operation.
4. Corrugated tanks are used in the transformer for replacing the conservator. The tank enclosure and rim are completely
sealed by welding or bolting up, which prolongs the service life of transformer oil.
5. The transformer surface are painted with primer and finish coats after degreasing, derusting, and phosphorizing; which can
meet the special operation requirements in metallurgic and petrochemical industries, as well as, in moist and dirty places.
6. The press relief valves, signal thermometers, and gas relays are equipped in the oil tank of hermetically sealed transformer
in order to the standard requirements for safe operation. The transformers are attractive and competitive due to the compact
shape, excellent design, and maintenance-free.

Notes for placing orders


Transformer type: rated capacity kVA Number of phases: three-phase  single-phase 
High voltage: kV/ Low voltage: kV Frequency: 50Hz  60Hz 
Tapping range:  2x2.5%   5%  other  Connection group: Yyn0  Dyn11  other 
Impedance voltage: normal  other 
47
Main technical parameters of S9-M-30~2500/10 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Oil Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

30 130 600 2.1 185 80 330 750  530  820 400  400

50 170 870 2.0 240 90 400 830  630  970 400  400

63 200 1040 1.9 260 100 440 830  670  1050 400  400
S9-M-30~2500/10

80 240 1250 1.8 280 105 520 1145  665  1030 550  550

100 290 1500 1.6 325 120 600 1145  665  1055 550  550

125 340 1800 1.5 440 140 700 920  680  1075 550  550

160 400 2200 4.0 1.4 490 140 740 1190  690  1145 550  550

200 480 2600 1.3 500 160 860 1290  765  1165 550  550
Yyno
6
250 5 560 3050 1.2 610 200 1000 1385  815  1180 550  550
0.4 or
6.3
315  2  2.5 670 3650 1.1 740 220 1250 1345  770  1275 550  550
Dynll
10
400 800 4300 1.0 920 240 1400 1430  820  1305 660  660

500 960 5150 1.0 1100 300 1700 1520  870  1380 660  660

630 1200 6200 0.9 1330 390 2100 1650  920  1390 820  820

800 1400 7500 0.8 1560 470 2565 1780  1020  1475 820  820

1700 10300 0.7 1720 420


Hermetically-sealed distribution transformer

1000 4.5 2690 1830  1110  1600 820  820

1250 1950 12000 0.6 1920 510 3110 1870  1120  1685 820  820

1600 2400 14500 0.6 2430 590 3800 1930  1160  1800 1070  1070

2000 2850 17200 0.5 2950 810 4770 2120  1260  1920 1070  1070
5.5
2500 3360 20500 0.5 3250 1040 5370 2240  1320  1950 1070  1070
Main technical parameters of S10-M-30~2500/10 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Oil Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

30 110 600 2.1 185 80 330 750  530  820 400  400

50 150 870 2.0 245 90 390 830  630  970 400  400

63 180 1040 1.9 285 100 490 860  670  1000 400  400

80 200 1250 1.8 295 115 520 890  680  1025 550  550

100 230 1500 1.6 325 140 590 930  690  1060 550  550

125 270 1800 1.5 380 150 730 950  720  1090 550  550

160 310 2200 4.0 1.4 470 170 770 970  740  1180 550  550

200 Yyno 380 2600 1.3 550 205 930 1070  805  1150 550  550
6
5
250 0.4 or 460 3050 1.2 635 225 1060 1410  820  1210 550  550
6.3
 2  2.5
315 Dynll 540 3650 1.1 825 240 1255 1455  830  1260 660  660
10
400 650 4300 1.0 965 280 1525 1530  840  1300 660  660

500 780 5150 1.0 1150 305 1800 1630  930  1390 660  660

630 920 6200 0.9 1360 420 2225 1710  960  1445 660  660

800 1120 7500 0.8 1560 470 2565 1780  1020  1475 820  820

1000 1320 10300 4.5 0.7 1900 540 3070 1850  1130  1600 820  820

1250 1560 12000 0.6 2160 615 3415 1900  1170  1660 820  820

1600 1880 14500 0.6 2575 770 4155 1074  1240  1700 1070  1070

2000 2280 17200 0.5 2840 815 4690 2120  1260  1790 1070  1070
S9-M-30~2500/10
Hermetically-sealed distribution transformer

5.5
2500 2630 20500 0.5 3500 1240 6085 2260  1360  1900 1070  1070
48
49
Main technical parameters of S11-M-30~2500/10 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Oil Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

30 100 600 2.1 165 70 300 800  660  940 400  400

50 130 870 2.0 240 100 450 820  610  1035 400  400

63 150 1040 1.9 270 100 500 830  640  1045 400  400
S9-M-30~2500/10

80 180 1250 1.8 360 113 585 900  675  1140 550  550

100 200 1500 1.6 380 120 590 870  670  1170 550  550

125 240 1800 1.5 430 129 780 1180  670  1130 550  550

160 280 2200 4.0 1.4 550 140 800 1190  690  1195 550  550
Yyno
6
200 5 340 2600 1.3 570 165 940 1290  765  1245 550  550
0.4 or
6.3
250  2  2.5 400 3050 1.2 750 220 1230 1385  790  1330 550  550
Dynll
10
315 480 3650 1.1 790 230 1280 1335  770  1340 550  550

400 570 4300 1.0 1100 280 1670 1430  820  1430 660  660

500 680 5150 1.0 1300 300 1880 1420  790  1510 660  660

630 810 6200 0.9 1440 350 2170 1525  830  1540 660  660

800 980 7500 0.8 1750 355 2453 1550  840  1660 660  660

1150 10300 0.7 1810 470


Hermetically-sealed distribution transformer

1000 4.5 2820 1830  1130  1640 820  820

1250 1360 12000 0.6 2160 520 3340 1870  1130  1680 820  820

1600 1640 14500 0.6 2625 600 3700 1850  1150  1965 1070  1070

2000 1940 17200 5.5 0.5 3100 710 4300 2090  1280  1930 1070  1070
Main technical parameters of S9
S10
S11-2500~6300/10 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Oil Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

S9

2500 6 2970 20700 0.70 3000 1240 6100 2260  1360  1900 1070  1070

3150 6.3 3510 24300 0.70 3630 1510 7800 2460  1400  2600 1070  1070
5 3.15
4000 10 Yd11 4320 28800 5.5 0.60 4350 1770 8100 2700  1900  2800 1475  1070
 2  2.5 6.3
5000 10.5 5130 33000 0.60 5180 2000 9300 3000  2200  2900 1475  1070

6300 11 6120 36900 0.55 6490 2200 10800 3200  2400  3100 1475  1070

S10

2500 6 2640 19550 0.70 3150 1300 6390 2260  1360  1950 1070  1070

3150 6.3 3120 22950 0.70 3800 1590 7360 2460  1400  2650 1070  1070
5 3.15
4000 10 Yd11 3840 27200 5.5 0.60 4560 1860 8500 2700  1900  2850 1475  1070
 2  2.5 6.3
5000 10.5 4560 31170 0.60 5440 2100 9760 3000  2200  2950 1475  1070

6300 11 5440 34850 0.55 6820 2300 11350 3200  2400  3150 1475  1070

S11

2500 6 2310 19550 0.70 3300 1430 6690 2260  1360  2000 1070  1070

3150 6.3 2730 22950 0.70 3990 1660 7750 2460  1400  2700 1070  1070
5 3.15
4000 10 Yd11 3360 27200 5.5 0.60 4780 1950 8900 2700  1900  2900 1475  1070
 2  2.5 6.3
5000 10.5 3990 31170 0.60 5700 2200 10200 3000  2200  3000 1475  1070

6300 11 4760 34850 0.55 7140 2400 11880 3200  2400  3200 1475  1070
S9-M-30~2500/10
Hermetically-sealed distribution transformer

50
S9-50~20000/35 Three-phase oil-immersed
no-excitation voltage-regulating power transformer

Production introduction
The product conforms to the technical parameters
and requirements of China National Standard GB1094
and GB/T6451, and a series of significant innovation is
applied in aspects of material, design and structure. It
has the features of high efficiency and low loss. It can
save a lot of operation cost, and the social benefits are
very significant. In conclusion, it is a nationally promoted
new product and it is deeply favored by customers.
51 Installation type: indoor/outdoor type
Ambient temperature: -25+40
Altitude:  1000m
Installation site: in places without corrosive gases
and obvious dusts.

Applicable standards
GB1094.1-2-1996 Power Transformer
GB1094.3; 5-2003 Power Transformer
GB/T6451-1999 Technical parameters and requirements for three-phase oil-immersed power transformer

Model designation

S  -/
Voltage class(kV)
Rated capacity(kVA)
Performance level code
Three-phase oil-immersed transformer

Performance characteristics
1. The features of this product are high efficiency and low loss. It can save a lot of operation cost, and the social benefits are
very significant.
2. The iron cores are made of the imported high-conduction magnetism, cold-roll, and grain-oriented silicon-steel sheets. The
iron cores and windings adopt the vacuum drying and vacuum oil-filling processes, which make the internal moisture down
to the very low level.
3. The conservator is hermetically sealed, which make the internal running oil to insolate with oxygen and moisture efficiently.
4. The above features guarantee the transformer does not need to replace the oil during the normal operation, greatly
decrease the maintenance cost, and prolong the service life.

Notes for placing orders


Transformer type: rated capacity kVA Number of phases: three-phase  single-phase 
High voltage: kV/ Low voltage: kV Frequency: 50Hz  60Hz 
Tapping range:  4x2.5%   3x2.5%  other  Connection group: Yyn0  Dyn11  other 
Impedance voltage: normal  other 
Main technical parameters of S9-M-50~2500/35 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Oil Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

50 215 1210 2.00 230 320 650 1150  720  1200 550  550

100 305 2020 1.80 380 400 980 1200  740  1300 550  550

125 340 2380 1.75 440 430 1100 1250  780  1380 550  550

160 360 2830 1.65 510 460 1200 1300  800  1400 660  660

200 430 3300 1.55 600 500 1400 1400  840  1500 660  660

250 510 3950 1.40 690 530 1500 1530  860  1580 660  660

315 610 4750 1.40 800 570 1670 1600  890  1630 660  660

35 0.4 YynO 6.5


400 5 735 5750 1.30 930 650 1950 1730  950  1700 660  660

500 870 6900 1.30 1070 710 2300 1800  980  1800 820  820

630 1040 8250 1.25 1300 830 2650 1900  1000  1850 820  820

800 1250 9900 1.05 1600 900 3100 1950  1060  1900 820  820

1000 1480 12150 1.00 1800 1080 3700 1980  1100  1950 820  820

1250 1760 14600 0.90 2100 1150 4000 2010  1160  1980 820  820

1600 2130 17500 0.85 2550 1250 4730 2040  1310  2000 820  820

2000 2500 20680 0.75 3100 1400 5600 2170  1380  2700 1070  1070

2500 2975 24500 0.75 3650 1500 6300 2300  1450  2900 1070  1070
S9-50~20000/35 Three-phase oil-immersed
no-excitation voltage-regulating power transformer

52
53
Main technical parameters of S9-M-800~20000/35 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Oil Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

800 1250 9900 1.05 1680 970 3200 000  1100  1950 820  820

1000 1480 12150 1.00 1800 1100 3570 2100  1200  2100 820  820
3.15
1250 1760 14650 0.90 2060 1200 4040 2150  1250  2150 820  820
35 5 6.3 6.5
1600 2130 17500 0.85 2400 1250 4550 2200  1340  2180 820  820
10.5
2000 2600 19350 0.75 2820 1420 5720 2250  1380  2210 1070  1070
Yd11
2500 3150 20700 0.75 3330 1550 6000 2300  1400  2300 1070  1070

3150 3860 24300 0.70 3800 1670 7060 2480  1900  2450 1070  1070
3.15
4000 4630 28800 7.0 0.70 4500 1830 8200 2800  2250  2500 1070  1070
5 6.3
5000 5480 33000 0.60 5300 2000 9500 3000  2370  2800 1070  1070
10.5
6300 6570 36900 0.60 6550 2300 11280 3200  2520  2900 1070  1070

8000 35 9000 40500 7.5 0.55 8150 2700 14000 3300  2700  3200 1475  1475

10000 38.5 10600 47700 0.55 9600 3050 16250 3400  2800  3400 1475  820
3.15
12500 YNd11 12600 56700 0.50 11000 3660 18800 3500  2930  3500 1475  1070
 2  2.5 6.3
16000 15300 69300 8 0.50 13650 4300 22250 3620  3040  3600 1475  1070
S9-50~20000/35 Three-phase oil-immersed

10.5
20000 18090 83500 0.50 15500 5530 25000 3700  3100  3700 1475  1475
no-excitation voltage-regulating power transformer
SZ9-400~20000/35 Three-phase oil-immersed
on-load voltage-regulating power transformer

Production introduction
The product conforms to the technical parameters
and requirements of China National Standard GB1094
and GB/T6451, and a series of significant innovation is
applied in aspects of material, design and structure. It
has the features of high efficiency and low loss. It can
save a lot of operation cost, and the social benefits are
very significant. In conclusion, it is a nationally promoted
new product and it is deeply favored by customers.
Installation type: indoor/outdoor type 54
Ambient temperature: -25+40
Altitude:  1000m
Installation site: in places without corrosive gases
and obvious dusts.

Applicable standards
GB1094.1-2-1996 Power Transformer
GB1094.3; 5-2003 Power Transformer
GB/T6451-1999 Technical parameters and requirements for three-phase oil-immersed power transformer

Model designation

S  -/
Voltage class(kV)
Rated capacity(kVA)
Performance level code
Three-phase oil-immersed transformer

Performance characteristics
1. The features of this product are high efficiency and low loss. It can save a lot of operation cost, and the social benefits are
very significant.
2. The iron cores are made of the imported high-conduction magnetism, cold-roll, and grain-oriented silicon-steel sheets. The
iron cores and windings adopt the vacuum drying and vacuum oil-filling processes, which make the internal moisture down
to the very low level.
3. The conservator is hermetically sealed, which make the internal running oil to insolate with oxygen and moisture efficiently.
4. The above features guarantee the transformer does not need to replace the oil during the normal operation, greatly
decrease the maintenance cost, and prolong the service life.

Notes for placing orders


Transformer type: rated capacity kVA Number of phases: three-phase  single-phase 
High voltage: kV/ Low voltage: kV Frequency: 50Hz  60Hz 
Tapping range:  4x2.5%   3x2.5%  other  Connection group: Yyn0  Dyn11  other 
Impedance voltage: normal  other 
55
Main technical parameters of SZ9-M-400~2000/10series of transformers
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Oil Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

400 815 4360 1.0 925 320 1610 1810  930  1250 660  660

4.0

500 970 5180 1.0 1150 400 1980 1890  1010  1350 660  660

630 1260 6380 0.9 1360 460 2320 1980  1040  1400 820  820

800 6 Yyno 1500 7800 0.8 1560 520 2670 2030  1100  1425 820  820

6.3  4  2.5 0.4 or


10 Dynll
1000 1740 10720 4.5 0.7 1730 620 3000 2100  1160  1500 820  820

1250 2120 12750 0.6 2020 715 3520 2180  1180  1600 820  820

1600 2700 15200 0.6 2445 890 4345 2280  1260  1720 1070  1070

2000 2790 19170 5.5 0.6 2780 1050 5010 2360  1350  1800 1070  1070
SZ9-400~20000/35 Three-phase oil-immersed
on-load voltage-regulating power transformer

Note:1.Please contact us for the performance parameters,outline dimensions and other importans data for 35kv transformers with bigger capacity.
2.For 8000ka and above,we can also supply transformers with air cooling device according to customer's requirements(SFZ9).
3.The weight and dimensions in table above are only for reference.
Main technical parameters of SZ9-M-2000~20000/35series of transformers
Rated Voltage combination(kV) Vector No-load Load- Short No-load Weight(kg) Overall Gauge(mm)
capacity group loss loss(W) circuit current dimension(mm)
(kVA) High Tapping Low (W) (75) impedance () Body Oil Gross Length  width 
voltage () voltage () weight height
(kV) (kV)

2000 2850 20000 1.00 2780 1650 6140 2750  1410  2800 1070  1070
6.5
2500 3300 21700 1.00 3300 1800 7080 2800  1430  2850 1070  1070

3150 4000 26000 0.90 3700 1910 7300 2690  2020  2940 1070  1070
Yd11
4000 4900 30500 7.0 0.90 4350 2170 8550 3180  2380  3100 1070  1070
6.3
5000 35 5800 35000 0.85 5200 2450 9950 3250  2500  3150 1070  1070
 3  2.5 6.6
6300 38.5 7000 38500 0.85 6500 2740 11800 3370  2600  3290 1070  1070
10.5
8000 9900 42700 7.5 0.75 7770 3320 14500 3420  2740  3350 1475  1360

10000 11700 50500 0.75 9100 3850 16810 3350  2830  3400 1475  1360

12500 YNd11 13770 59800 0.70 10630 4640 19800 3680  2950  3500 1475  1475

16000 16570 72000 8.0 0.70 13300 5360 23300 3800  3080  3600 1475  1475

20000 19580 85000 0.60 17450 7100 30800 4000  3250  3800 1475  1475

Note:1.Please contact us for the performance parameters,outline dimensions and other importans data for 35kv transformers with bigger capacity.
2.For 8000ka and above,we can also supply transformers with air cooling device according to customer's requirements(SFZ9).
3.The weight and dimensions in table above are only for reference.
SZ9-400~20000/35 Three-phase oil-immersed
on-load voltage-regulating power transformer

56
SC(B)9-30~2500/10
Epoxy resin dry-type power transformer

Production introduction
The dry-type transformers are casted with epoxy
resin, which are made of high quality materials by
means of a strict process with advanced production
and testing devices. The product features high reliability
and long service life. In accordance with different
operation environment, it can be equipped with different
protection casings or without casing. It can replace the
oil-immersed transformer and be used in the high
57 buildings, business centers, airports, tunnels, chemical
plants, nuclear power stations and watercrafts etc.

Normal service conditions


1) Altitude should not be over 1000m: indoor type
2) Highest ambient temperature should not over: 40; Highest daily average should not over temperature:  30
3) Highest annual average temperature should not over  20, lowest temperature should not below -5
We can provide transformer operated in special conditions according to user's requirement.

Model designation

S C (B) -  -  / 
Voltage class(kV)
Rated capacity(kVA)
Performance level code
Foil winding
Resin-casting type
Three-phase

Applicable standards
GB6450-1986 Dry-type power transformer
GB4208-1993 Casing protection grade (IP code)
GB/T10228-1997 Technical parameters and requirements for dry-type power transformer

Performance Characteristics
1. The product is safe, fire-proof, pollution free, and can be used in the load center directly.
2. High mechanical strength, strong short-circuit proof capacity, small partial discharge, excellent thermal stability, high
reliability, and long service life.
3. Low loss, low noise, energy saving and maintenance free.
4. Excellent heat dissipation, great overload capacity and a larger operating capacity is available when ONAF is applied.
5. Good humidity resistance, it's suitable for operating in the highly humid and harsh environment.
6. An intelligent signal and temperature control system is adopted, which can automatically monitor and display all working
temperature of the three-phase windings. The blowing fan can give an alarm, switch on and off automatically and conduct
tripping operation to protect the transformer.
7. Due to the structure is compact and weight is light, it can save space and decrease the cost of installation.
SC(B)9-30~2500/10
Epoxy resin dry-type power transformer

Note for placing order


Transformer type: rated capacity kVA Number of phases: three-phase  single-phase 
High voltage: kV/Low voltage kV Frequency: 50Hz  60Hz 
Tapping range:  4x2.5%   3x2.5%  other  Connection group: Yyn0  Dyn11  other 
Impedance voltage: 4%  6%  other  Cooling method: ONAN  ONAF 
Protecting grade of outer casing: IP00  IP20  IP30  other 

Method of incoming and outgoing line:


1. Incoming line to lower part and outgoing line from upper part 
2. Incoming line to upper part and outgoing line form upper part 
3. Incoming line to lower part and outgoing line from side part  58
4. other 
* If customer has no requirement, the color of outer casing is light grey (the standard color of Delixi), or you should indicate
color code that you want 
59
Main technical parameters of SC(B)9-30~2500/10 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Load- Short No-load Noise IP00(no crust) IP20(IP23) High Low voltage
cap- group loss loss loss circuit current level voltage connection
acity High Tapp- Low (W) (W) (W) impe- () (dB) Le- Wi- He- Ga- Gross Len- Wi- Hei- Gross conn- end(mm)
(kVA) voltage ing voltage (120) (75) dance ngth dth ight uge weight gth dth ght weight ection
(kV) () (kV) () (mm) (mm) (mm) (mm) (kg) (mm) (mm) (mm) (kg) end(mm)
30 210 745 650 2.8 45 670 500 700 400 280 1100 1000 1200 380 M10 30  3

50 300 1050 915 2.5 45 720 500 770 400 400 1200 1000 1200 510 M10 30  3

80 410 1460 1275 2.4 46 760 500 950 400 500 1200 1000 1200 650 M10 30  3

100 450 1665 1455 2.2 46 980 600 1060 500 580 1300 1100 1400 820 M10 30  3
SC(B)9-30~2500/10

125 530 1950 1700 2 47 1030 650 1100 500 660 1300 1100 1400 880 M10 30  3

160 610 2250 1965 2 48 1050 650 1130 550 720 1500 1100 1400 940 M10 (a) 40  4
4.0
200 700 2670 2330 1.8 48 1100 650 1150 550 920 1500 1100 1600 1120 M10 (a) 40  4

250 810 2920 2550 1.8 49 1150 760 1200 660 1100 1500 1250 1600 1310 M10 (a) 40  6
6 5 Yyn0
315 990 3670 3205 1.6 49 1210 760 1250 660 1250 1500 1250 1600 1460 M10 (a) 40  6
6.3 2 0.4 or
400 1100 4220 3685 1.6 50 1270 760 1420 660 1600 1700 1250 1800 1850 M10 (b) 60  6
10 2.5 Dyn11
500 1300 5170 4515 1.6 51 1320 760 1500 660 1850 1700 1250 1800 2100 M10 (b) 60  6

630 1500 6220 5430 1.5 52 1360 760 1520 660 2200 1700 1250 1800 2450 M10 (c) 80  8

630 1460 6310 5510 1.5 52 1430 760 1360 660 2100 1700 1250 1800 2350 M10 (c) 80  8
Epoxy resin dry-type power transformer

800 1710 7360 6425 1.5 53 1470 1000 1460 820 2300 1900 1500 1800 3000 M10 (c) 80  8

1000 1990 8600 7510 1.3 54 1540 1000 1560 820 2800 1900 1500 1800 3100 M10 (d)100  10

1250 2350 10260 8955 6 1.3 55 1610 1000 1620 820 3200 1900 1500 2000 3510 M10 (d)100  10

1600 2750 12420 10840 1.3 56 1710 1250 1700 1070 3800 2100 1800 2000 4150 M10 (d)120  10

2000 3735 15300 13355 1.1 56 1830 1250 1930 1070 4800 2100 1800 2200 5180 M16 (e)120  12

2500 4500 18180 15870 1.1 57 1850 1250 1970 1070 5400 2100 1800 2300 5800 M16 (e)120  15
Main technical parameters of SC(B)10-30~2500/10 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Load- Short No-load Noise IP00(no crust) IP20(IP23) High Low voltage
cap- group loss loss loss circuit current level voltage connection
acity High Tapp- Low (W) (W) (W) impe- () (dB) Le- Wi- He- Ga- Gross Len- Wi- Hei- Gross conn- end(mm)
(kVA) voltage ing voltage (120) (75) dance ngth dth ight uge weight gth dth ght weight ection
(kV) () (kV) () (mm) (mm) (mm) (mm) (kg) (mm) (mm) (mm) (kg) end(mm)
30 190 700 610 2.6 44 670 500 700 400 280 1100 1000 1200 380 M10 30  3

50 270 990 865 2.2 44 720 500 770 400 400 1200 1000 1200 510 M10 30  3

80 360 1380 1205 2.0 45 760 500 950 400 500 1200 1000 1200 650 M10 30  3

100 400 1570 1370 2.0 45 980 600 1060 500 580 1300 1100 1400 820 M10 (a)30  3

125 480 1840 1605 1.8 46 1030 650 1100 500 660 1300 1100 1400 880 M10 (a)30  3

160 540 2130 1860 1.8 47 1050 650 1130 550 720 1500 1100 1400 940 M10 (a) 40  4
4.0
200 620 2530 2210 1.6 47 1100 650 1150 550 920 1500 1100 1600 1120 M10 (a) 40  4

250 720 2750 2400 1.6 48 1150 760 1200 660 1100 1500 1250 1600 1310 M10 (a) 40  6
6 5 Yyn0
315 880 3470 3030 1.4 48 1210 760 1250 660 1250 1500 1250 1600 1460 M10 (a) 40  6
6.3 2 0.4 or
400 970 3990 3485 1.4 49 1270 760 1420 660 1600 1700 1250 1800 1850 M10 (b) 60  6
10 2.5 Dyn11
500 1160 4880 4260 1.4 50 1320 760 1500 660 1850 1700 1250 1800 2100 M10 (b) 60  6

630 1340 5870 5125 1.3 51 1360 760 1520 660 2200 1700 1250 1800 2450 M10 (c) 80  8

630 1290 5960 5200 1.3 51 1430 760 1360 660 2100 1700 1250 1800 2350 M10 (c) 80  8

800 1520 6950 6070 1.3 52 1470 1000 1460 820 2300 1900 1500 1800 3000 M10 (c) 80  8

1000 1760 8130 7095 1.1 53 1540 1000 1560 820 2800 1900 1500 1800 3100 M10 (d)100  10

1250 2080 9690 8460 6 1.1 54 1610 1000 1620 820 3200 1900 1500 2000 3510 M10 (d)100  10

1600 2440 11730 10240 1.1 55 1710 1250 1700 1070 3800 2100 1800 2000 4150 M10 (d)120  10

2000 3320 14450 12615 1.0 55 1830 1250 1930 1070 4800 2100 1800 2200 5180 M16 (e)120  12
SC(B)9-30~2500/10
Epoxy resin dry-type power transformer

2500 4000 17170 14990 1.0 56 1850 1250 1970 1070 5400 2100 1800 2300 5800 M16 (e)120  15
60
SG(B)10-100~2500/10
H-class insulation three-phase dry-type transformer

Production introduction
Our company has developed this product by
ourselves. As a high performance, high safety, pollution
free dry-type transformer, it is suitable for the harsh
environments where there is a high fire protection
requirement, the great load fluctuation and the site
where is of filth and moisture. For example: airport,
power plant, metallurgy operation, hospital, high
building, shopping center, densely inhabited area,
61 petrochemical industry, nuclear power station and
nuclear submarine, etc.

Nominal service conditions


1. A unique ceramic type of insulation structure is adopted in H-class high strength insulation cylinders and high-frequency
ceramic cushion blocks are adopted to ensure that no deformation will occur.
2. The high-voltage and low-voltage windings are made of NOMEX wrapped flat copper wires and imported copper foils. And
they are sealed with high strength insulation materials.
3. The iron core is made of laminated imported high-quality silicon-steel sheets of high magnetic conductivity with a 45
stepwise all-bias structure. A flexible fastening unit is adopted to fasten the winding and iron core, which ensures a relatively
low no-load loss and low noise.
4. Outlet terminals are fixed to the top of winding, taps are in the middle of winding, low-voltage line terminal are in plate-type
current-conducting rows for which cold pressure welding is adopted.

Normal service conditions


1) Altitude should not be over 1000m: indoor type
2) Highest ambient temperature should not over: 40; Highest daily average should not over temperature:  30
3) Highest annual average temperature should not over 20, lowest temperature should not below -5 We can provide
transformer operated in special conditions according to user's requirement.

Model designation

S C (B) - 10 -  / 
Voltage class(kV)
Rated capacity(kVA)
Performance level code
Foil winding
Dry-type,air self-cooling
Three-phase
SG(B)10-100~2500/10
H-class insulation three-phase dry-type transformer

Applicable standards
GB6450-1986 Dry-type power transformer
GB/T10228-1997 Technical parameters and requirements for dry-type power transformer
GB/T17211-1998 Guide rules for dry-type power transformer load
GB10237-1998 Insulation level and insulation test for power transformer
GB4208-1993 Casing protection grade (IP code)
JB/10008-1999 6220KV transformer sound level
JB/T56009-1998 Product quality grading for dry-type power transformer

Performance Characteristics 62
1. Excellent heat dissipation, long thermal life, good overload capacity, without forced air-cooling under a long-term 120%
overload and IP45 condition. It can operate for a long time at full load.
2. Extremely high safety fire resistance performance, smoke-free while burning under a temperature as high as 800.
3. Extremely high thermal shock resistance capacity.
4. 100% water-proof, excellent moisture -proof.
5. Unique winding structure and field strength calculation makes partial discharge impossible.
6. Low loss and significant energy saving effect. Compared with SC9 series of dry-type transformers, the no-load loss falls
10% and load loss falls 5% in average.
7. The insulation material and copper conductor can be dismantled easily and recycled after the service life. Therefore, no
pollution will occur.

Note for placing order


Transformer type: rated capacity kVA Number of phases: three-phase  single-phase 
High voltage: kV/Low voltage kV Frequency: 50Hz  60Hz 
Tapping range:  4x2.5%   3x2.5%  other  Connection group: Yyn0  Dyn11  other 
Impedance voltage: 4%  6%  other  Cooling method: ONAN  ONAF 
Protecting grade of outer casing: IP00  IP20  IP30  other 

Method of incoming and outgoing line:


1. Incoming line to lower part and outgoing line from upper part 
2. Incoming line to upper part and outgoing line form upper part 
3. Incoming line to lower part and outgoing line from side part 
4. other 
* If customer has no requirement, the color of outer casing is light grey (the standard color of Delixi), or you should indicate
color code that you want 
63
Main technical parameters of SG(B)10-100~2500/10 series of transformers
Rated Voltage combination(kV) Vector No-load Load- Load- Short No-load Noise IP00(no crust) IP20(IP23) High Low voltage
cap- group loss loss loss circuit current level voltage connection
acity High Tapp- Low (W) (W) (W) impe- () (dB) Le- Wi- He- Ga- Gross Len- Wi- Hei- Gross conn- end(mm)
(kVA) voltage ing voltage (120) (75) dance ngth dth ight uge weight gth dth ght weight ection
(kV) () (kV) () (mm) (mm) (mm) (mm) (kg) (mm) (mm) (mm) (kg) end(mm)
100 405 2165 1765 2.0 40 1000 520 1030 400 720 1300 1000 1400 980 M10 (a) 40  4

125 480 2590 2115 1.8 42 1000 520 1050 400 800 1300 1000 1400 1060 M10 (a) 40  4

160 560 3100 2530 1.8 42 1050 670 1080 550 880 1500 1100 1400 1100 M10 (a) 40  4

200 655 3970 3240 1.6 42 1070 670 1150 550 900 1500 1100 1600 1120 M10 (a) 40  4

250 760 4675 3815 4 1.6 43 1100 670 1200 550 1070 1500 1100 1600 1300 M10 (a) 40  6
SG(B)10-100~2500/10

315 880 5610 4575 1.4 45 1130 780 1220 550  660 1200 1500 1250 1600 1450 M10 (a) 40  6

400 1040 6630 5410 1.4 45 1170 780 1290 660 1350 1500 1250 1600 1600 M10 (b) 60  6

500 1200 7945 6480 1.4 45 1220 780 1355 660 1570 1700 1250 1800 1800 M10 (b) 60  6
6 5 Yyn0
630 1400 9265 7560 1.3 45 1300 780 1380 660 1700 1700 1250 1800 1950 M10 (c) 80  8
6.3 2 0.4 or
630 1345 9775 7975 1.3 45 1380 780 1250 660 1680 1700 1250 1800 1930 M10 (c) 80  8
10 2.5 Dyn11
800 1695 11560 9430 1.3 46 1450 940 1295 660  820 2050 1900 1500 1800 2340 M10 (c) 80  8

1000 1985 13345 10885 1.1 46 1470 940 1380 660  820 2310 1900 1500 1800 2600 M10 (d)100  10

1250 2385 15640 12760 6 1.1 47 1570 940 1515 820 2790 1900 1500 2000 3100 M10 (d)100  10

1600 2735 18105 14770 1.1 48 1660 940 1650 8201070 3500 1900 1500 2000 3830 M10 (d)120  10

2000 3320 21250 17335 1.0 48 1710 1090 1750 8201070 4200 2100 1650 2200 4600 M10 (e)120  12

2500 4000 24735 20180 1.0 49 1750 1190 1815 8201070 4725 2100 1650 2200 5200 M10 (e)120  12
H-class insulation three-phase dry-type transformer
ZGS  -200~1000/10 Combined transformer

Production introduction
1. ZGS 11 combined transformer is one of the high-
tech products developed by our company on the basis
of pad-mounted transformer.
2. Range of capacity: 200-1000KVA. The product
is suitable for the neutral-point insulation system or
small-resistance grounding system in a 10KV
distribution network, or neutral-point solid grounding
system of a three-phase four-wire system in a 400V
distribution network. 64
3. Excellent design, reliable distribution, compact
structure, light in weight, and low noise, etc; it has two
types of cable outlets: ring net type and terminal type.
4. The product can be placed directly into the load
center of 10KV network, thus the line loss is reduced
and power distribution reliability is increased.

Performance characteristics
1. The ZGS11 combined transformer consists of high-voltage and low-voltage chambers and transformer tank in the
operation chambers.
2. H.V. incoming lines in 10KV cross-linked cables are connected to load switch through knuckle connectors, straight plugs
and sleeve sockets.
3. On the high-voltage side, a protection of double fuses (backup current-limiting fuse and plug-in type of fuse are used.
4. There are terminal type and ring net type high-voltage load switches for selection.
They are easy to connect, convert and reliable for power supply.
5. In the low-voltage chamber, a fixed type or drawable type is optional for the low-voltage switch cabinet according to user's
requirement. Various low-voltage apparatus, such as metering and protection instruments are available. (Note: In general
they are customized)
6. The oil tank is fully-sealed by corrugated radiators, which features compact and superior appearance.

Model designation

Z G S 11  / 
Voltage class(kV)
Rated capacity(kVA)
Performance level code
Three phase
Tank-sharing type
Combined transformer
ZGS  -200~1000/10 Combined transformer

Applicable standards
GB1094.1-2-1996 Power Transformer
GB1094.3; 5-2003 Power Transformer
JB/T10318-2002 Technical parameters and requirements for oil-immersed, non-crystal alloy iron core, distribution
transformer

Normal service conditions


Installation type: indoor/outdoor type
Ambient temperature: -25+40
Altitude:  1000m
65
Humidity: daily average value  95%, monthly average value  90%
Installation site: in places without corrosive gases, obvious dusts and water-vapour; the gradient is no more than 3% and
no fierce shock.

Performance Characteristics
1. Compare with type "9" transformer, the product's no-load loss is reduced by 30% and thus the average annual operating
costs can be reduced by 20.03%.
2. The transformer body, high voltage load switch fuses and no-excitation tapping switches are all put into the fully-sealed
oil tank, which make good use of the space. Therefore, the overall size of the product is only 1/3 of that of the similar product.
3. The plug-in and out cable connection is easy for operation.
4. An obstacle protection is of two-stage fuses structure (backup current-limiting fuse and plug-in type fuse) which ensures
a safe and flexible operation and more convenient for replacing of fuse.
5. The oil tank is fully-sealed, in which the oil is totally isolated from the outside. No leakage and maintenance free.
6. Excellent short-circuit proof capacity and high reliability.

Notes for placing orders


Transformer type: rated capacity kVA Number of phases: three-phase  single-phase 
High voltage: kV/ Low voltage: kV Frequency: 50Hz  60Hz 
Tapping range:  2x2.5%   5%  other  Connection group: Yyn0  Dyn11  other 
Impedance voltage: 4%  6%  other 

You might also like