You are on page 1of 2

Ghost voltages – phantom

readings can lead to the


wrong diagnosis
Application Note

Introduction
Ever measured an ac signal on
a branch circuit that you know ON ON

to be dead or even discon-


nected completely? It can be a
real head scratcher. How can a On Off
wire, with no connection at Disconnect A OFF OFF
Disconnect B
either end, have a voltage on
it? What you’re experiencing is
a phenomenon aptly termed
“ghost voltage.” While its
appearance may seem an inde-
cipherable mystery, it usually
can be solved without too
much trouble. 50 - 75 feet
of conduit

The clues
Does the wire, somewhere
along its length, share a run
with many other wires? It’s
not uncommon practice for
electrical contractors to think
ahead for their customers and
pull extra circuits for possible
future expansion of the electri- Is the 60 V
cal system. Or you may have reading real or
just pulled a new wire(s) in a ghost voltage
run with other wires. If so, we
know that our open wire is
?
Motor B
running alongside other circuits
that are connected to the elec-
trical system and are providing
current to real loads such as
lights, motors, computers and
heaters.
Two metal plates (the
Motor A
conductors) separated by the
conductor’s insulation and air
would appear to fit the defini- of ac signal passed through a 1. The surface area of the
tion of a capacitor. We know capacitor is determined by its plates
from basic electrical theory that capacitance and that capaci- 2. The distance between the
ac signals run across a capaci- tance is based on three factors: plates
tor are coupled while dc volt- 3. The make up of the insula-
ages are blocked. The amount tion separating the plates.

From the Fluke Digital Library @ www.fluke.com/library


In our ghost voltage case, When you place your DMM The DMM’s input impedance
the surface area of the plates is leads between the open circuit varies depending on what the
determined by the size of the and the neutral conductor, you input circuitry senses. Initially,
wire and the length of the two effectively complete the circuit the input impedance is on the
conductors that are laying side- through the input of the DMM. order of two kilohms. So, when
by-side. The longer the run, The capacitance between the the leads are placed on the
the larger the surface area and connected and live hot conduc- open circuit that contains a
therefore, the higher the capac- tor and the floating conductor ghost voltage, the low input
itance. Increasing the number forms a voltage divider in con- impedance will cause the ghost
of wires in a conduit will cause junction with the DMM input voltage to dissipate and the
the wires to be packed closer impedance. The DMM then meter will display “OL” with the
together, reducing the distance measures and displays the Ω symbol indicating the meter
between conductors and resulting voltage value. With is still in the resistance function
increasing capacitance. The most DMMs, like the Fluke 170 with no voltage present. When
insulation around the conduc- and 180 Series, the input the leads are placed on a live
tors will stay pretty constant impedance is very high — on circuit however, the input
and won’t change the capaci- the order of 10 megohms. This senses the presence of a “hard”
tance. However, external results in a false reading on the voltage and automatically
factors will change the effec- DMM, which is actually meas- adjusts the input impedance to
tive insulation between the uring voltage coupled into the a much higher value and then
conductors. For instance, while disconnected conductor. displays the actual voltage
pulling the bundle of wires In most cases the amount of present. This variable imped-
through a conduit, the insula- ac coupling between conduc- ance design effectively elimi-
tion may be compressed, tors is very low, so the amount nates reading ghost voltages on
reducing distance between of current that can be pulled open circuits while still making
conductors. In addition, water through this coupling is limited. accurate measurements on live
may get into a conduit and However, these voltages, at power circuits without having
effectively increase the capaci- times, can be significant to change meter settings.
tance as well. Another external enough to cause confusion So remember to put voltage
factor may be carbon between when we are troubleshooting readings in perspective when
conductors where an arc took circuit problems. troubleshooting. If you feel
place some time in the past. there shouldn’t be any voltage
So in an electrical situation, the The solution present, but there is, check for
amount of ac signal coupled To reduce the confusion, and the conditions listed in this
into the disconnected wire is save time troubleshooting an article. The voltage is not an
based on a lot of factors. electrical system, use a DMM apparition, just a result of the
But wait! This wire is open with a low input impedance. physics of electricity.
on both ends! Isn’t Ohms Law Fluke Models 7-600 and 12
still working in this situation? (with VCheck) are designed to
To see voltage, don’t we need respond differently to “ghost
resistance and current flow? voltages” than normal voltages.
Of course you do! This is where
we need to look at another
part of the puzzle: The digital
multimeter (DMM) making the Fluke. Keeping your world
voltage measurement. up and running.

Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
In Canada (800) 36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2003 Fluke Corporation. All rights reserved.
Printed in U.S.A. 8/2003 2105317 A-ENG-N Rev A
2 Fluke Corporation Ghost voltages—phantom readings can lead to the wrong diagnosis

You might also like