You are on page 1of 8

The 2010 International Power Electronics Conference

Opportunities for Power Quality Improvement


through DG-Grid Interfacing Converters
Jinwei He, Md. Shirajum Munir, and Yun Wei Li
Department of Electrical and Computer Engineering
University of Alberta, Alberta, Canada, T6G 2V4
hjinwei@ualberta.ca, mdshiraj@ece.ualberta.ca, yunwei.li@ece.ualberta.ca

Abstract--Power electronics technology is becoming an 250kVA rating must have the provision for monitoring its
increasingly important aspect of today’s power distribution output power and voltage at the point of connection. A
system. It is the key interface to connect distributed energy DG unit should be disconnected from the grid within
resource (DER) to the utility and the local loads. With the 0.16s in a grid voltage quality event (e.g. under grid
increased penetration of power electronics based distributed frequency or voltage variations). Besides the IEEE
generation (DG) systems, the power quality requirements
are becoming more stringent. On the other hand, if
standard for interconnecting the DER with power system,
controlled and regulated properly, the DG-grid interfacing there are also many country-wide DG interconnection
converters are able to improve the system efficiency and standards, which specifies similar requirement regarding
power quality, in addition to the primary function of real the DG current harmonics and the ability to disconnect
power injection. This paper discusses the opportunities for itself from the grid in case of a disturbance.
power quality improvement through the DG-grid On the other hand, with the increasing use of
interfacing converters. While the harmonic voltage unbalanced loads, nonlinear loads and sensitive loads in
compensation is the focus of this paper, a number of other today’s distribution system, maintaining good power
ancillary functions, such as unbalance voltage quality is also a responsibility of the utility. For example,
compensation, voltage sag mitigation and reactive power
compensation, can be realized in a similar manner. Two
IEEE 519 [3] requires that the utility should make sure
alternative DG control methods, namely current controlled the voltage total harmonic distortion (THD) at the point
DG and voltage controlled DG, are considered and the of common coupling (PCC) with each customer be less
associated power quality compensation strategies are than 5%, with individual harmonic voltage less than 3%.
developed. Simulation results and experimental results from While the DG interfacing converters may introduce
a three-phase 5kVA laboratory DG prototype are provided. harmonics into the power system and cause power quality
Index Terms—Distributed generation (DG), distributed concerns, they are also able to improve the system
energy resource (DER), power quality, power converters, efficiency and power quality if designed and controlled
renewable energy. properly. To realize this function of DG, besides the
primary purpose of real power generation, many ancillary
I. INTRODUCTION services, such as power factor compensation, voltage
support [4], flicker mitigation [5], system harmonic
With the increasing concerns on conventional energy
compensation [6-8], unbalance voltage compensation [9],
costs, energy security and greenhouse gas emissions, the
etc. can also be provided through the DGs whenever there
energy industry is experiencing fundamental changes as
is sufficient apparent power rating available.
more and more distributed resource (DER) based
Furthermore, with the recent development of smart grid
distributed generation (DG) units are being connected to
and microgrid concepts, and the associated advancement
the gird. These DG systems are seen as a means for
of communication, instrumentation and control
facilitating climate friendly renewable energy sources
techniques for power electronics interfaced DG systems,
(RES) and to enable efficient use of electricity. Most of
systematically controlling the DGs to improve the
these DG systems are connected to the grid through the
distribution system power quality is becoming be a very
power electronic interfaces.
promising topic.
This increased penetration of DG introduced a number
Most of the power electronics interfaced DG systems
of challenges, such as harmonics, protection interference,
use voltage source inverters (VSI) as the interfacing
voltage regulation problems, etc [1]. As a result, the
inverter. The control mechanism of the VSI is mainly of
power quality as well as power regulation requirements
two types, namely current control method (CCM) and
are becoming more stringent as have already been
voltage control method (VCM). In this paper, both
reflected in a few grid codes. IEEE 1547 [2] and its
control methods are considered and the associated power
recent series of application guidelines require that the
quality compensation strategies are developed. A detailed
total demand distortion (TDD) of harmonic current
comparison of these two methods for power quality
injection by the DG into the grid should be less than 5%
improvement is also carried out. Note that although
(individual harmonic lower than 11th should be less than
harmonic compensation is the focus in this paper, the
4% and the even order harmonics should be even lower
proposed control strategy can be extended for voltage
than half of this number). A DG unit of more than
flicker and unbalance compensation. Finally, simulation
and experimental results are presented to confirm and
This work was supported by Natural Science and Engineering
Research Council of Canada (NSERC).
validate the analysis.

978-1-4244-5393-1/10/$26.00 ©2010 IEEE 1657


The 2010 International Power Electronics Conference

Power electronic interfaced DG PCC


ZGRID VG 2
VG ,h
ZDG
Energy LC Grid
+
+
+
+ × N
source Filter
VDC
VG z−N −1 j 2π k z −1
PWM modulator Nonlinear e N

load
IL ×
Multi-loop
current control SDFT Fig. 2. SDFT for fundamental and harmonic component extraction.
IDG VG_h VG_f
-
+ For synchronization *
2Kihωch s IL
*
I αβ
IDG*
+
-
Ih* 1 P Q +

KP + ¦ s + 2ωch s + ω
2 2 +

KC αβ PWM
abc modulator
Rh
I DG _ αβ h =1,5,7.... h

If* Real and P *


reactive
power control Q*
I L _ αβ
Fig. 1. Interfacing inverter control scheme for current controlled DG.
Fig. 3. Closed-loop current control diagram.

Traditionally, the harmonic components and


II. CURRENT CONTROLLED DG fundamental component are separated by using low pass
Many grid-connected DG systems (such as PV or high pass filters in either the stationary or synchronous
systems) adopt the current control method (CCM) for the frames [11]. However, this filtering will introduce
interfacing inverter, where the DG output current is magnitude and phase errors in the extracted signals,
synchronized with the grid voltage, and the current which will subsequently lead to inaccurate compensation
magnitude is generated through the output power control. performance. On the other hand, it is also important to
The idea of PCC voltage quality improvement using avoid high order harmonic tracking due to limited current
the current controlled grid-connected inverter has been control bandwidth (usually, tracking of harmonics higher
reported in [7, 8]. Basically, this method functions by than 13th is difficult with an inverter operated at around
controlling the DG as a shunt active power filter (APF), 10kHz switching frequency). The inaccurate control may
and the DG will absorb the harmonic current from the introduce amplification of these harmonics, or even lead
nonlinear load, leaving an improved source current and to instability of the system. With the above
PCC voltage with low THD. One way to achieve this is to considerations, selected compensation of the most
control each DG as an R-APF [10], where the grid side significant low order harmonics in a system (such as 5th,
voltage is measured and the harmonic components are 7th, 11th) would be more appropriate.
extracted to produce the reference harmonic current for a To selectively extract the harmonics, resonant filters
*
DG ( I h = VG _ h Rh ), and therefore the DG will act as a are used in [8]. However, the resonant filter has sudden
change of phase angle at the resonant frequencies, which
small resistance (Rh) only at the harmonic frequencies. means that slight variation of the resonant frequency may
The block diagram of the power quality improvement introduce substantial phase error in the extracted signals.
method with current controlled interfacing inverter is To accurately extract the harmonics, the sliding discrete
shown in Fig. 1. As illustrated, the fundamental reference Fourier transform (SDFT) is used in this work [12]. The
current magnitude (If*) is obtained from the power control SDFT features very simple structure with a sliding
loop, where the real power reference can be produced window and can be easily implemented in a DSP for real
from the maximum power point tracking (MPPT) like in time calculation. The z-domain transfer function for the
a wind or PV system, the maximum system efficiency hth harmonic can be descried as:
control like in a fuel cell system or from the command
−N
value of the energy management center. The reactive G SDFT = 1 − Z (1)
power command can be produced from the voltage 1 − e j2ʌh/N Z −1
support or load power factor compensation algorithms. If where N is the number of samples in one fundamental
unity power factor injection from a DG is desired, this period, and h is the harmonic order. The implementation
reactive power demand can be simply set to zero. To diagram of the SDFT is illustrated in Fig. 2. Note that
improve the transient performance, a current magnitude with SDFT, the grid voltage fundamental component
feedforward loop can be added, where the feedforward (h=1) can also be extracted and it is used for the grid
current is calculated from the reference power and grid synchronization of the current control scheme.
side voltage magnitude. With the grid voltage angle Once the harmonic voltage is obtained, the harmonic
information from a phase-locked-loop (PLL), the current reference can be produced by using the desired
reference inverter output current synchronized to the virtual resistance Rh. Note that the value of Rh will affect
fundamental grid voltage can be obtained. In order to the compensation performance. Generally, a smaller Rh
properly compensate the grid side voltage harmonics, and gives better compensation, but tends to reduce the system
at the same time to avoid any conflicts with the primary stability. Additionally, the value of Rh should also be
function of real power injection of a DG system, the determined according to the available rating of a DG, to
reference harmonic current generation and the current avoid any conflict of the primary function of real power
control loop need to be carefully designed. generation. This control of the Rh according to the DG’s

1658
The 2010 International Power Electronics Conference

available rating can be realized through an adaptive VG


control algorithm [7] or simply by an integral controller. ZDG (s) ZGRID (s)
Finally, the DG reference current can be obtained by
VDG (s)
adding the fundamental reference from power control VGrid (s)
ILoad (s)
loop and the harmonic current reference. The DG output ZLoad (s)
current closed-loop control scheme is shown in Fig. 3,
where I*Įȕ, IDG_Įȕ are the Į-ȕ frame DG reference and
feedback currents respectively. For good fundamental DG PCC Load Grid
current tracking and harmonic current control, a current Fig. 4. Equivalent circuit of DG-grid system with voltage control.
controller based on parallel P+Resonant controllers (at
fundamental frequency and the harmonic frequencies of Power electronic interfaced DG PCC
interest) and used [13, 14]: Energy LC
ZDG ZGRID
Grid
source Filter
2 K ω ch s VDC
¦
VG
G =K + (2)
ih

PWM modulator Nonlinear


C P 2
s + 2ω ch s + ω
2

h =1,5,7.... h IDG load


Multi-loop IL
voltage control SDFT
where Ȧh is system fundamental and harmonic frequency, VDG VG_h VG_f
Ȧch is the cut-off bandwidth at each frequency, Kih is the +
-
For synchronization
VDG* Vh* Active
integral gain at each frequency, and Kp is the proportional +
- harmonic P Q
control gain at all frequencies. To further improve the control
Vf* Real and P*
dynamic response and stability of the control loop, an reactive
power control Q*
inner filter inductor current feedback loop with
proportional controller is also added as shown in Fig. 3. Fig. 5. Proposed control strategy for the voltage controlled DG.
Finally, it is noted that if the distributed line
From the above analysis, it is obvious that by properly
impedance is very small, and DG is connected to the grid
controlling the DG output voltage with a feedback gain of
with an LCL filter (or with a coupling transformer), the
G, the harmonic impedance at DG side can be scaled
grid side voltage (VG) measured for harmonic
down by a factor of (1+G) and therefore it can be
compensation is very close to PCC voltage, and therefore
substantially lower than that at the grid side. As a result
remote measurement is not necessary for this
most of the nonlinear load current can be absorbed by the
compensation scheme.
DG, leaving an improved grid current and the PCC
voltage. Obviously, a higher G value will further reduce
III. VOLTAGE CONTROLLED DG the PCC voltage harmonics. With G=0, the DG will be a
While the current controlled DG is mostly employed standard voltage controlled DG unit without any
for grid connected inverters, the voltage controlled DG compensation. This is in contrast to the current controlled
can also be used [15-17]. The voltage control method method, where the whole DG system is controlled as a
(VCM) will produce seamless transient if a DG is to be resistor Rh at the harmonic frequencies.
operated in intentional islanding mode, as VCM is Furthermore, if desired, this method can also control
necessary in the islanding operation to provide voltage the DG output current with low harmonics and better
and frequency support for the microgrid. To the authors’ THD. This can be done by using a negative feedback gain
knowledge, the grid power quality improvement using the (-1<G<0), and therefore the DG output impedance will be
VCM has not been addressed in the literature so far. increased at the harmonic frequencies. As a result, the
PCC harmonic voltage will be amplified comparing with
A. Proposed Compensation Strategy
conventional voltage controlled mode. Actually, if DG
The equivalent circuit of a DG-grid system with VCM harmonic current can be properly attenuated with a
is shown in Fig. 4, where the DG is described as a negative G, the performance will be the same as current
controlled voltage source VDG and a DG impedance ZDG, controlled DG unit. Therefore, with different system
and the grid is represented as a voltage VGrid and a grid compensation requirements or DG operation objectives,
impedance ZGrid. The PCC nonlinear load is shown in the the value of G can be controlled adaptively (with a
middle as a harmonic current source and passive loads. If theoretical range from -1 to ’). Since a high value of G
the DG harmonic voltage is controlled as: tends to make the system unstable, a practical top limit of
VDG ( s) = −G ⋅VG ( s) (3) G is around 10-20. Finally, it is important to note that G
should not be less than -1, as this will introduce
the equivalent harmonic impedance can be accordingly capacitive equivalent impedance, which may induce some
expressed as: system resonance.
In this work, G>0 is named harmonic compensation
Z DG ,eq = Z DG / (1 + G ) (4) mode and G<0 is named as harmonic rejection mode.
The proposed control strategy is implemented as
where VG(s) is measured voltage after the DG impedance shown in Fig. 5. Similarly, a SDFT block first separates
ZDG(s). Similarly, considering the low line impedance, it the fundamental and the harmonic components of the
is valid to assume that VG(s) is the PCC voltage. PCC voltage. The fundamental voltage is used for grid

1659
The 2010 International Power Electronics Conference

Uncontrolled
0 200

Magnitude (%)
150
VG _ h
*
Rejection Compensation Vh
− ¦ Vh mode
100

h selection 50

500 1000 1500 2000


K ¦ Gh Vh
h
Compensation

Phase(deg)
I DG
100

50

I Rated 0

0 500 1000 1500


Fig. 6. Active harmonic control algorithm. Frequency (Hz)
(a)
* *
VDG _ αβ 2Kihωch s IL
+ KP + ¦ + KC αβ PWM 280

Magnitude (%)
s + 2ωch s + ω
2 2 −
− abc modulator
VDG _ αβ h =1,5,7.... h 260
240
220
200
I L _ αβ 180
160
Fig. 7. Muli-loop voltage control diagram. 200 400 600 800 1000 1200 1400 1600 1800

voltage synchronization and DG output real and reactive 0


power calculation, while the harmonic components are
Phase(deg)
-20
used for the inverter reference harmonic voltage -40
generation. In the control scheme, the real and reactive -60
power control block produces the fundamental reference
500 1000 1500 2000
of DG voltage while the active harmonic control block Frequency (Hz)
generates the reference harmonic voltages. The power (b)
control can be realized by using the droop control as Fig. 8. PCC harmonic voltage compensation: (a) PCC harmonic voltage,
discussed in [15-17], where the reactive power control (b) DG harmonic current. (Black: G=15, Red: G=7.5, Blue: G=3)
should be updated by using a PI controller to remove any
control errors [16, 17]. 1 1 1 1
= + + (6)
The active harmonic control is illustrated in Fig. 6. As Z Parllel Z DG ( s ) ZGrid ( s ) Z Load ( s )
discussed before, this control block can operate at
compensation, rejection or uncontrolled mode. To avoid Considering ZLoad(s) is much higher than ZGrid(s) and
over-rating operation and possible conflict with the ZDG(s), and VGrid ( s ) ≈ 0 at the harmonic frequencies,
primary function of power control, a control algorithm
PCC voltage and DG current harmonic attenuation ratio
named “available DG rating detection and compensation
after the active harmonic compensation can be obtained
gain adjustment” is added. By using either the adaptive
as in (7), (8):
controller [7] or a simple integral controller [8], this
algorithm adjusts the value of K, which subsequently VG , Active ( s ) Z DG ( s ) + Z Grid ( s )
changes the effective gain used for each harmonic. To ≈ (7)
VG ( s ) Z DG ( s ) + (1 + G ) ⋅ Z Grid ( s )
achieve optimal compensation, the feedback gain Gh for
each harmonic components is not necessarily to be the
same. Generally, Gh is lower for high order harmonics. I DG , Active ( s ) ( Z DG ( s ) + Z Grid ( s )) ⋅ (1 + G )
≈ (8)
Note that for harmonic rejection mode, Gh=-1 for all the I DG ( s ) Z DG ( s ) + (1 + G ) ⋅ Z Grid ( s )
harmonics.
The final multi-loop DG voltage control block is If the dynamics of voltage control loop is considered,
shown in Fig. 7, where the parallel P+Resonant controller the equivalent DG harmonic impedance becomes:
for fundamental and different harmonic components are
Z DG + Z DG ,out ( s ) (9)
used as the outer loop voltage controller, and the inner Z DG ,eq =
current loop uses the filter inductor current feedback and 1 + G ⋅ K DG ,out ( s )
a proportional controller (Kc).
where
B. Analysis of the Proposed Control Strategy N ( s )(1 + K C M ( s ))
Z DG ,out ( s ) =
In the equivalent circuit of Fig. 4, (5) and (6) can be 1 + M ( s ) N ( s ) + GV ( s ) K C M ( s ) N ( s ) + M ( s ) K C
obtained: GV ( s ) K C M ( s ) N ( s )
K DG ,out ( s ) =
VG ( s ) V ( s ) VGrid ( s ) 1 + M ( s ) N ( s ) + GV ( s ) K C M ( s ) N ( s ) + M ( s ) K C
+ I Load ( s ) + G + =0 (5)
Z Parllel Z DG ( s ) Z G ( s ) 2 K ihω ch s , h=1, 5, 7, 11.
GV ( s ) = K P + ¦
s + 2ω ch s + ω
2 2
h h

1660
The 2010 International Power Electronics Conference

350
more rejection effects are achieved. As shown in Fig.
Magnitude (%) 300 9(b), with G=-1, the DG output current contained no 5th,
250
7th and 11th harmonics. This harmonic rejection mode has
200
150 very similar performance compared to the current
100 controlled inverter.
50
0 500 1000 1500 2000

50
IV. COMPARISON BETWEEN CCM AND DCM
While both methods can effectively control the DG
Phase(deg)

0
output real and reactive power and compensate the PCC
-50 harmonic voltage, a further comparison of both methods
-100
gives the following conclusions:
0 500 1000 1500 2000
Frequency (Hz) • Without harmonic compensation, CCM pushes all
(a) the harmonic currents to the grid side. Leading to
500 polluted PCC voltage due to harmonic voltage drops
on source impedance. To the contrary, even without
Magnitude (%)

400

300
harmonic compensation, the voltage controlled DG
200
shares the nonlinear load current with the source
100

0
according to their respective impedance. This leads
0 500 1000 1500 2000
to better PCC voltage compared to CCM.
200 • With PCC harmonic compensation, the CCM works
150 as a shunt low resistance (R-APF) to absorb the
Phase(deg)

100
50
harmonic currents. In case of multiple DG systems,
0 this method ensures that the harmonic current
-50
-100
flowing to each DG is of the same phase angle even
0 500 1000 1500 2000 different Rh is used for different DG units, meaning
Frequency (Hz)
that no circulating current exist among DG units.
(b)
Fig. 9. DG harmonic current rejection mode: (a) PCC harmonic voltage, However, harmonic components extraction without
(b) DG harmonic current. (Red: G=-0.5, Black: G=-0.8, Blue: G=-1) phase shift is very important here, as any phase error
(such as those can be introduced by the resonant
and M ( s) = 1/ ( LF s + RF ) , N ( s) = 1/ (CF s) are the filters) will lead to inductive or capacitive
transfer functions related to the LC filter (LF, RF and CF impedance in series with Rh, causing the circulating
are the filter inductance, stray resistance, and filter current among DG systems.
capacitance respectively). • When VCM is used for multiple DG systems, since
Therefore, PCC voltage and DG current attenuation in each DG will act as an impedance of ZDG/(1+G), the
(7) and (8) can be be re-expressed as (10) and (11): harmonic current flowing into each DG is related to
ZDG and G for each DG unit. Seemingly causing
VG , Active ( s ) Z DG ( s ) + Z DG , out ( s ) + Z Grid ( s ) (10) circulating current among DGs, a further look into
=
VG ( s ) Z DG ( s ) + Z DG ,out ( s ) + (1 + G ⋅ K DG , out ( s )) ⋅ Z Grid ( s ) this issue reveals that the harmonic impedance ZDG
is mainly inductive (even for directly coupled DG
I DG, Active ( s ) ( ZDG ( s ) + ZDG,out ( s ) + ZGrid ( s)) ⋅ (1 + G ⋅ K DG,out ( s)) (11) without grid side inductance, the line impedance

I DG ( s) ZDG ( s) + ZDG,out ( s) + (1 + G ⋅ K DG,out ( s)) ⋅ ZGrid ( s) will be inductive at harmonic frequencies). As a
result, the harmonic current circulation among DG
With (10) and (11), the PCC voltage and DG output unit is not a real issue with VCM, as long as the
current harmonic attenuation ratio is plotted in Figs. 8 harmonic reference can be generated without phase
and 9 respectively, where the 5th, 7th and 11th harmonics error.
(300Hz, 420Hz and 660Hz) are compensated. It can be • Considering that a DG system may operate in grid
seen from Fig. 8 (a) that with a positive G, the harmonics connected mode and intentional islanding mode (to
at PCC can be effectively reduced, and the harmonic form a self contained microgrid), the VCM has the
phase angle is almost not changed at the compensated advantages of seamless control transition, since the
frequencies. Also the further reduction of harmonics same control scheme can be used for both operation
associated with a higher G is obviously shown in Fig. 8 modes. In contrast, the CCM has difficulties in
(b). To compensate the PCC harmonic voltage, the DG islanding operation, as it is not directly controlling
output current contains most of the nonlinear load the load voltage and frequency.
current. As a result, the DG current harmonics are • The VCM is more flexible with compensation,
amplified at the 5th, 7th, 11th harmonics. rejection and uncontrolled modes, where the
For the harmonic rejection mode, when a negative G is harmonic reject operation essentially gives similar
used, the PCC voltage harmonics are amplified as shown performance as the current control method.
in Fig. 9 (a). As expected, when G is closer to -1, the DG
harmonic impedance is approaching ’, and therefore the

1661
The 2010 International Power Electronics Conference

100
TABLE I. SYSTEM PARAMETERS IN SIMULATION AND EXPERIMENT.
Parameters Simulations Experiments (a) 0

V
Grid voltage 104V, 60Hz (3 phase) 104V, 60Hz (3 phase) -100
DC link voltage 260V 260V 0.16 0.18 0.2 0.22 0.24
DC link capacitance Ideal DC source 1900uF 5
LC filter L = 2.5mH, C = 40µF L = 2.5mH, C = 40µF (b) 0

A
DG Impedance R = 1Ÿ, L = 2.5mH R = 1Ÿ, L = 5mH -5
Grid impedance R = 1Ÿ, L = 2.5mH R = 1Ÿ, L = 5mH 0.16 0.18 0.2 0.22 0.24
Switching frequency 12kHz 12kHz 5
Power reference P*=300W, Q*=125Var P*=120W, Q*=75Var (c) 0

A
-5
0.16 0.18 0.2 0.22 0.24
Time (s)
V. SIMULATION AND EXPERIMENTAL RESULTS
Fig. 10. Current controlled method without harmonic compensation: (a)
The proposed harmonic compensation strategies are PCC phase voltage, (b) grid current, (c) DG current.
verified through Matlab/Simulink simulation and
10

Mag (% of Fundamental)
experimentally on a 5kVA grid connected DG system.
The system parameters used in the simulation and
experiments are almost identical and are listed in Table 1.
5
In the simulation and experiment, the nonlinear load at
PCC is a diode rectifier with parallel connected capacitor
(1000uF) and resistor (25ȍ) at the dc side.
0
0 5 10 15 20 25 30
A. Current Control Method Harmonic order
The current controlled interfacing inverter is first Fig. 11. Harmonic analysis of PCC voltage under current controlled DG
tested in the simulation with the 5th and 7th harmonic without harmonic compensation (THD =10.22%)
compensated. Figs. 10 and 11 show the performance of
current controlled DG without implementation of the 100
PCC voltage harmonic compensation. As can be seen (a) 0
V

from Fig. 10, the DG output current has no harmonics (as -100
0.14 0.16 0.18 0.2 0.22 0.24
it is only controlled to produce real and reactive power),
5
and the nonlinear load current is supplied through the
(b) 0
A

grid. As a result, the PCC voltage is distorted due to the -5


harmonic voltage drop on the grid impedance. As 0.14 0.16 0.18 0.2 0.22 0.24
illustrated in Fig. 11, the PCC voltage has a THD of 5
10.22%. (c) 0
A

-5
The situation with PCC voltage harmonic 0.14 0.16 0.18 0.2 0.22 0.24
compensation is shown in Figs. 12 and 13. As expected, Time (s)
by acting as a low resistance Rh at the harmonic Fig. 12. Current control method with harmonic compensation: (a) PCC
frequencies, the DG unit absorbed most of the nonlinear phase voltage, (b) grid current, (c) DG current.
load currents, leading to an improved grid current and
PCC voltage as shown in Fig. 12 (a) and (b). As shown in
Mag (% of Fundamental)

10
Fig. 13, the low order harmonics of PCC voltage are
significantly reduced, which results in a THD of 2.5%.
5
B. Voltage Control Method
The voltage controlled DG and different compensation
modes are also tested in the simulation, and the results 0
0 5 10 15 20 25 30
are shown in Figs. 14-19. Harmonic order
Figs. 14 and 15 show the results without any harmonic Fig. 13. Harmonic analysis of PCC voltage under current controlled DG
compensation, i.e. the DG unit is controlled with pure with harmonic compensation (THD =2.50%)
sinusoidal output voltage (see Fig. 14 (b)). In this case, voltage are improved. As shown in Fig. 17, the 5th
the DG and grid equally share the nonlinear load current harmonic voltage at PCC is reduced to about 1.5% and
as seen from Fig. 14 (c) and (d). As a result, the PCC the THD is reduced to 2.42%.
voltage is distorted due to the nonlinear current flow on Finally, the harmonic rejection mode is tested and the
the grid impedance. Fig. 15 shows that the PCC voltage results are shown in Figs. 18-19. As expected, with G=-1,
has almost 6% 5th harmonic and the THD is 6.72%. the DG output current is controlled to be sinusoidal (see
To improve the PCC voltage, the harmonic Fig. 18(d)) due to the very high DG impedance at
compensation is implemented (with G5=12, G7=12, harmonic frequencies. In this case, the grid will provide
G11=5). As the DG output impedance at harmonics all the nonlinear load current, and therefore the grid
frequencies is reduced by a factor of (1+Gh), the DG unit current and voltage are further distorted. The PCC
absorbs most of the load nonlinear current as can be seen voltage has 8% 5th harmonic, and the THD is 10.08%. As
in Fig. 16 (d). As a result, the grid current and PCC

1662
The 2010 International Power Electronics Conference

100 100

(a) 0 (a) 0

V
V
-100 -100
0.7 0.72 0.74 0.76 0.78 0.8 2.3 2.32 2.34 2.36 2.38 2.4
100 100

(b) (b) 0

V
0
V

-100 -100
0.7 0.72 0.74 0.76 0.78 0.8 2.3 2.32 2.34 2.36 2.38 2.4
5 5

(c) 0 (c) 0

A
A

-5 -5
0.7 0.72 0.74 0.76 0.78 0.8 2.3 2.32 2.34 2.36 2.38 2.4
5 5

(d) (d)

A
0 0
A

-5 -5
0.7 0.72 0.74 0.76 0.78 0.8 2.3 2.32 2.34 2.36 2.38 2.4
Time (S) Time (S)
Fig. 14. Voltage control method without compensation: (a) PCC phase Fig. 16. Voltage control method with harmonic compensation: (a) PCC
voltage, (b) DG phase voltage, (c) grid current, (d) DG current. phase voltage, (b) DG phase voltage, (c) grid current, (d) DG current.

10 10

Mag (% of Fundamental)
Mag (% of Fundamental)

8 8

6 6

4 4

2 2

0 0
0 5 10 15 20 25 30 0 5 10 15 20 25 30
Harmonic order Harmonic order

Fig. 15. Harmonic analysis of PCC phase voltage under voltage Fig. 17. Harmonic analysis of PCC voltage under voltage controlled DG
controlled DG without harmonic compensation (THD =6.72%) with harmonic compensation (THD =2.42%)

expected, this performance is similar to the current current is 15.3% and 26.3% respectively.
control mode without PCC harmonic compensation. Note that the increase of harmonics compared to
simulations is introduced by using higher DG and grid
C. Experimental Verifications impedance in the experiment.
Experiments are also conducted on a 5kVA grid
connected DG system to verify the voltage control VI. CONCLUSIONS
method. In the experiment, a three-phase programmable
This paper investigates the opportunities of
power supply is used to represent the grid, and the three-
distribution system power quality improvement using the
phase DG system is control with a DSP-FPGA system. In
DG interfacing inverters. Both the current controlled
the experiment, the 5th and 7th harmonics are
method and the voltage controlled method are considered
compensated. The experimental parameters are listed in
and their associated power quality compensation schemes
Table 1, and the results are shown in Figs. 20-22.
are developed. Specifically, the voltage controlled DG
The performance of uncontrolled mode (without
can be operated with compensation, rejection and
harmonic compensation) is shown in Fig. 20, where it can
uncontrolled mode, where the harmonic compensation
be seen that the DG and grid share the nonlinear load
and rejection modes produce similar performance as with
current. Since the DG real and reactive power references
the current controlled DG. The proposed control
is smaller in the experiment (see Table 1), the grid current
strategies have been verified in both simulation and
contains higher fundamental current. Without harmonic
experiments. Note that although the paper focuses on the
compensation, the THD of PCC voltage and grid current
PCC voltage harmonic compensation, it can be extended
is 10.5% and 16.9% respectively.
for flicker and unbalance compensation as well.
When PCC harmonic compensation is implemented,
the DG absorbs the nonlinear load current and as a result,
both the source current and PCC voltage are improved as REFERENCES
shown in Fig. 21. In this case, the THD of PCC voltage [1] I. El-Samahy and E. El-Saadany, “The effect of DG on
and grid current is improved to 5.2% and 7% power quality in a deregulated environment,” Proc. IEEE
respectively. PESGM - 2005, pp. 2969- 2976.
[2] IEEE Standard for Interconnecting Distributed Resources
Finally, for the harmonic rejection mode, the DG
with Electric Power Systems, IEEE Std. 1547, 2003.
output current is controlled to contain very few [3] IEEE Recommended Practices and Requirements for
harmonics as the DG output impedance is increased Harmonic Control in Electrical Power Systems, IEEE Std
significantly at harmonic frequencies. As a result, most of 519-1992, Apr. 1993.
the nonlinear load current is supplied through the source [4] M. Triggianese, F. Liccardo, and P. Marino, “Ancillary
and the PCC voltage is further deteriorated. With Services performed by Distributed Generation in grid
harmonic rejection, the THD of PCC voltage and grid

1663
The 2010 International Power Electronics Conference

100

(a) 0
V
-100
1.5 1.52 1.54 1.56 1.58 1.6
100

(b) 0
V

-100
1.5 1.52 1.54 1.56 1.58 1.6
5
(c) 0
A

-5
1.5 1.52 1.54 1.56 1.58 1.6
5
(d) 0
A

-5
Fig. 20. Voltage control method without harmonic compensation: (a)
1.5 1.52 1.54 1.56 1.58 1.6 DG line voltage (200V/div), (b) PCC line voltage (250V/div), (c) grid
Time (S) current (5A/div), (d) DG current (5A/div).
Fig. 18. Voltage control method with harmonic rejection: (a) PCC phase
voltage, (b) DG phase voltage, (c) grid current, (d) DG current.

10
Mag (% of Fundamental)

0
0 5 10 15 20 25 30
Harmonic order
Fig. 21. Voltage control method with harmonic compensation: : (a) DG
Fig. 19. Harmonic analysis of PCC voltage under voltage controlled DG line voltage (200V/div), (b) PCC line voltage (250V/div), (c) grid
with harmonic rejection (THD =10.08 %) current (5A/div), (d) DG current (5A/div).
integration,” Proc. IEEE International Conference on
Clean Electrical Power, 2007, pp. 164–170.
[5] M.I. Marei, T.K. Abdel-Galil, E.F. El-Saadany, and
M.M.A. Salama, “Hilbert transform based control
algorithm of the DG interface for voltage flicker
mitigation,” IEEE Trans. Power Delivery, vol. 20, pp.
1129- 1133, April 2005.
[6] M. Prodanovic, K. De Brabandere, J. Van Den Keybus, T.
Green, and J. Driesen, “Harmonic and reactive power
compensation as ancillary services in inverter-based
distributed generation,” IEE Proc. Gener. Transm.
Distrib., vol.1, pp.432-438, May 2007
[7] N. Pogaku and T.C. Green, “Harmonic mitigation Fig. 22. Voltage control method with harmonic rejection: : (a) DG line
throughout a distribution system: a distributed-generator- voltage (200V/div), (b) PCC line voltage (250V/div), (c) grid current
based solution,” IEE Proc. Gener. Transm. Distrib., vol. (5A/div), (d) DG current (5A/div).
153, no. 3, pp. 350- 358, 11 May 2006.
[8] C.J. Gajanayake, D.M. Vilathgamuwa, P. C. Loh, R. [13] D. N. Zmood, D. G. Holmes and G. H. Bode, “Stationary
Teodorescu, and F. Blaabjerg, “Z-Source-Inverter-Based frame current regulation of PWM inverters with zero
Flexible Distributed Generation System Solution for Grid steady-state error,” IEEE Trans. Power Electron., vol. 18,
Power Quality Improvement,” IEEE Trans. Energy pp. 814–822, Mar. 2003.
Conversion, vol.24, pp.695-704, Sept. 2009. [14] P. Mattavelli, “Synchronous-frame harmonic control for
[9] Y. W. Li, D. M. Vilathgamuwa and P. C. Loh, “Microgrid high-performance AC power supplies,” IEEE Trans. Ind.
Power Quality Enhancement Using A Three-Phase Four- Applicat., vol. 37, pp. 864–872, May/Jun. 2001.
Wire Grid-Interfacing Compensator,” IEEE Trans. Ind. [15] R. Lasseter, “Microgrids,” Proc. IEEE Power Engineering
Applicat., vol. 41, pp. 1707-1719, Nov-Dec. 2005. Society Winter Meeting, 2002, pp. 305–308.
[10] P. Jintakosonwit, H. Akagi, H. Fujita, and S. Ogasawara, [16] Y. W. Li, D. M. Vilathgamuwa, and P. C. Loh, “Design,
“Implementation and performance of automatic gain Analysis and Real-Time Testing of Controllers for Multi-
adjustment in a shunt-active filter for harmonic damping Bus Microgrid System,” IEEE Trans. Power Electron.,
throughout a power distribution system,” IEEE Trans. vol. 19, pp. 1195-1204, Sep. 2004.
Power Electron., vol.17, pp. 438-447, May 2002. [17] Y. W. Li and C. N. Kao, “An Accurate Power Control
[11] L. Asiminoaei, F. Blaabjerg, and S. Hansen, “Evaluation of Strategy for Power-Electronics-Interfaced Distributed
harmonic detection methods for active power filter Generation Units Operating in a Low-Voltage Multibus
applications,” IEEE APEC- 2005, pp. 635- 641. Microgrid,” IEEE Trans. Power Electron., vol. 24, pp.
[12] E. Jacobsen and R. Lyons, “The Sliding DFT,” IEEE 2977-2988, Dec. 2009.
Signal Processing Magazine, vol 20, pp. 74-80, Mar. 2003.

1664

You might also like