Professional Documents
Culture Documents
Abstract--Power electronics technology is becoming an 250kVA rating must have the provision for monitoring its
increasingly important aspect of today’s power distribution output power and voltage at the point of connection. A
system. It is the key interface to connect distributed energy DG unit should be disconnected from the grid within
resource (DER) to the utility and the local loads. With the 0.16s in a grid voltage quality event (e.g. under grid
increased penetration of power electronics based distributed frequency or voltage variations). Besides the IEEE
generation (DG) systems, the power quality requirements
are becoming more stringent. On the other hand, if
standard for interconnecting the DER with power system,
controlled and regulated properly, the DG-grid interfacing there are also many country-wide DG interconnection
converters are able to improve the system efficiency and standards, which specifies similar requirement regarding
power quality, in addition to the primary function of real the DG current harmonics and the ability to disconnect
power injection. This paper discusses the opportunities for itself from the grid in case of a disturbance.
power quality improvement through the DG-grid On the other hand, with the increasing use of
interfacing converters. While the harmonic voltage unbalanced loads, nonlinear loads and sensitive loads in
compensation is the focus of this paper, a number of other today’s distribution system, maintaining good power
ancillary functions, such as unbalance voltage quality is also a responsibility of the utility. For example,
compensation, voltage sag mitigation and reactive power
compensation, can be realized in a similar manner. Two
IEEE 519 [3] requires that the utility should make sure
alternative DG control methods, namely current controlled the voltage total harmonic distortion (THD) at the point
DG and voltage controlled DG, are considered and the of common coupling (PCC) with each customer be less
associated power quality compensation strategies are than 5%, with individual harmonic voltage less than 3%.
developed. Simulation results and experimental results from While the DG interfacing converters may introduce
a three-phase 5kVA laboratory DG prototype are provided. harmonics into the power system and cause power quality
Index Terms—Distributed generation (DG), distributed concerns, they are also able to improve the system
energy resource (DER), power quality, power converters, efficiency and power quality if designed and controlled
renewable energy. properly. To realize this function of DG, besides the
primary purpose of real power generation, many ancillary
I. INTRODUCTION services, such as power factor compensation, voltage
support [4], flicker mitigation [5], system harmonic
With the increasing concerns on conventional energy
compensation [6-8], unbalance voltage compensation [9],
costs, energy security and greenhouse gas emissions, the
etc. can also be provided through the DGs whenever there
energy industry is experiencing fundamental changes as
is sufficient apparent power rating available.
more and more distributed resource (DER) based
Furthermore, with the recent development of smart grid
distributed generation (DG) units are being connected to
and microgrid concepts, and the associated advancement
the gird. These DG systems are seen as a means for
of communication, instrumentation and control
facilitating climate friendly renewable energy sources
techniques for power electronics interfaced DG systems,
(RES) and to enable efficient use of electricity. Most of
systematically controlling the DGs to improve the
these DG systems are connected to the grid through the
distribution system power quality is becoming be a very
power electronic interfaces.
promising topic.
This increased penetration of DG introduced a number
Most of the power electronics interfaced DG systems
of challenges, such as harmonics, protection interference,
use voltage source inverters (VSI) as the interfacing
voltage regulation problems, etc [1]. As a result, the
inverter. The control mechanism of the VSI is mainly of
power quality as well as power regulation requirements
two types, namely current control method (CCM) and
are becoming more stringent as have already been
voltage control method (VCM). In this paper, both
reflected in a few grid codes. IEEE 1547 [2] and its
control methods are considered and the associated power
recent series of application guidelines require that the
quality compensation strategies are developed. A detailed
total demand distortion (TDD) of harmonic current
comparison of these two methods for power quality
injection by the DG into the grid should be less than 5%
improvement is also carried out. Note that although
(individual harmonic lower than 11th should be less than
harmonic compensation is the focus in this paper, the
4% and the even order harmonics should be even lower
proposed control strategy can be extended for voltage
than half of this number). A DG unit of more than
flicker and unbalance compensation. Finally, simulation
and experimental results are presented to confirm and
This work was supported by Natural Science and Engineering
Research Council of Canada (NSERC).
validate the analysis.
load
IL ×
Multi-loop
current control SDFT Fig. 2. SDFT for fundamental and harmonic component extraction.
IDG VG_h VG_f
-
+ For synchronization *
2Kihωch s IL
*
I αβ
IDG*
+
-
Ih* 1 P Q +
−
KP + ¦ s + 2ωch s + ω
2 2 +
−
KC αβ PWM
abc modulator
Rh
I DG _ αβ h =1,5,7.... h
1658
The 2010 International Power Electronics Conference
1659
The 2010 International Power Electronics Conference
Uncontrolled
0 200
Magnitude (%)
150
VG _ h
*
Rejection Compensation Vh
− ¦ Vh mode
100
h selection 50
Phase(deg)
I DG
100
50
I Rated 0
Magnitude (%)
s + 2ωch s + ω
2 2 −
− abc modulator
VDG _ αβ h =1,5,7.... h 260
240
220
200
I L _ αβ 180
160
Fig. 7. Muli-loop voltage control diagram. 200 400 600 800 1000 1200 1400 1600 1800
1660
The 2010 International Power Electronics Conference
350
more rejection effects are achieved. As shown in Fig.
Magnitude (%) 300 9(b), with G=-1, the DG output current contained no 5th,
250
7th and 11th harmonics. This harmonic rejection mode has
200
150 very similar performance compared to the current
100 controlled inverter.
50
0 500 1000 1500 2000
50
IV. COMPARISON BETWEEN CCM AND DCM
While both methods can effectively control the DG
Phase(deg)
0
output real and reactive power and compensate the PCC
-50 harmonic voltage, a further comparison of both methods
-100
gives the following conclusions:
0 500 1000 1500 2000
Frequency (Hz) • Without harmonic compensation, CCM pushes all
(a) the harmonic currents to the grid side. Leading to
500 polluted PCC voltage due to harmonic voltage drops
on source impedance. To the contrary, even without
Magnitude (%)
400
300
harmonic compensation, the voltage controlled DG
200
shares the nonlinear load current with the source
100
0
according to their respective impedance. This leads
0 500 1000 1500 2000
to better PCC voltage compared to CCM.
200 • With PCC harmonic compensation, the CCM works
150 as a shunt low resistance (R-APF) to absorb the
Phase(deg)
100
50
harmonic currents. In case of multiple DG systems,
0 this method ensures that the harmonic current
-50
-100
flowing to each DG is of the same phase angle even
0 500 1000 1500 2000 different Rh is used for different DG units, meaning
Frequency (Hz)
that no circulating current exist among DG units.
(b)
Fig. 9. DG harmonic current rejection mode: (a) PCC harmonic voltage, However, harmonic components extraction without
(b) DG harmonic current. (Red: G=-0.5, Black: G=-0.8, Blue: G=-1) phase shift is very important here, as any phase error
(such as those can be introduced by the resonant
and M ( s) = 1/ ( LF s + RF ) , N ( s) = 1/ (CF s) are the filters) will lead to inductive or capacitive
transfer functions related to the LC filter (LF, RF and CF impedance in series with Rh, causing the circulating
are the filter inductance, stray resistance, and filter current among DG systems.
capacitance respectively). • When VCM is used for multiple DG systems, since
Therefore, PCC voltage and DG current attenuation in each DG will act as an impedance of ZDG/(1+G), the
(7) and (8) can be be re-expressed as (10) and (11): harmonic current flowing into each DG is related to
ZDG and G for each DG unit. Seemingly causing
VG , Active ( s ) Z DG ( s ) + Z DG , out ( s ) + Z Grid ( s ) (10) circulating current among DGs, a further look into
=
VG ( s ) Z DG ( s ) + Z DG ,out ( s ) + (1 + G ⋅ K DG , out ( s )) ⋅ Z Grid ( s ) this issue reveals that the harmonic impedance ZDG
is mainly inductive (even for directly coupled DG
I DG, Active ( s ) ( ZDG ( s ) + ZDG,out ( s ) + ZGrid ( s)) ⋅ (1 + G ⋅ K DG,out ( s)) (11) without grid side inductance, the line impedance
≈
I DG ( s) ZDG ( s) + ZDG,out ( s) + (1 + G ⋅ K DG,out ( s)) ⋅ ZGrid ( s) will be inductive at harmonic frequencies). As a
result, the harmonic current circulation among DG
With (10) and (11), the PCC voltage and DG output unit is not a real issue with VCM, as long as the
current harmonic attenuation ratio is plotted in Figs. 8 harmonic reference can be generated without phase
and 9 respectively, where the 5th, 7th and 11th harmonics error.
(300Hz, 420Hz and 660Hz) are compensated. It can be • Considering that a DG system may operate in grid
seen from Fig. 8 (a) that with a positive G, the harmonics connected mode and intentional islanding mode (to
at PCC can be effectively reduced, and the harmonic form a self contained microgrid), the VCM has the
phase angle is almost not changed at the compensated advantages of seamless control transition, since the
frequencies. Also the further reduction of harmonics same control scheme can be used for both operation
associated with a higher G is obviously shown in Fig. 8 modes. In contrast, the CCM has difficulties in
(b). To compensate the PCC harmonic voltage, the DG islanding operation, as it is not directly controlling
output current contains most of the nonlinear load the load voltage and frequency.
current. As a result, the DG current harmonics are • The VCM is more flexible with compensation,
amplified at the 5th, 7th, 11th harmonics. rejection and uncontrolled modes, where the
For the harmonic rejection mode, when a negative G is harmonic reject operation essentially gives similar
used, the PCC voltage harmonics are amplified as shown performance as the current control method.
in Fig. 9 (a). As expected, when G is closer to -1, the DG
harmonic impedance is approaching , and therefore the
1661
The 2010 International Power Electronics Conference
100
TABLE I. SYSTEM PARAMETERS IN SIMULATION AND EXPERIMENT.
Parameters Simulations Experiments (a) 0
V
Grid voltage 104V, 60Hz (3 phase) 104V, 60Hz (3 phase) -100
DC link voltage 260V 260V 0.16 0.18 0.2 0.22 0.24
DC link capacitance Ideal DC source 1900uF 5
LC filter L = 2.5mH, C = 40µF L = 2.5mH, C = 40µF (b) 0
A
DG Impedance R = 1, L = 2.5mH R = 1, L = 5mH -5
Grid impedance R = 1, L = 2.5mH R = 1, L = 5mH 0.16 0.18 0.2 0.22 0.24
Switching frequency 12kHz 12kHz 5
Power reference P*=300W, Q*=125Var P*=120W, Q*=75Var (c) 0
A
-5
0.16 0.18 0.2 0.22 0.24
Time (s)
V. SIMULATION AND EXPERIMENTAL RESULTS
Fig. 10. Current controlled method without harmonic compensation: (a)
The proposed harmonic compensation strategies are PCC phase voltage, (b) grid current, (c) DG current.
verified through Matlab/Simulink simulation and
10
Mag (% of Fundamental)
experimentally on a 5kVA grid connected DG system.
The system parameters used in the simulation and
experiments are almost identical and are listed in Table 1.
5
In the simulation and experiment, the nonlinear load at
PCC is a diode rectifier with parallel connected capacitor
(1000uF) and resistor (25ȍ) at the dc side.
0
0 5 10 15 20 25 30
A. Current Control Method Harmonic order
The current controlled interfacing inverter is first Fig. 11. Harmonic analysis of PCC voltage under current controlled DG
tested in the simulation with the 5th and 7th harmonic without harmonic compensation (THD =10.22%)
compensated. Figs. 10 and 11 show the performance of
current controlled DG without implementation of the 100
PCC voltage harmonic compensation. As can be seen (a) 0
V
from Fig. 10, the DG output current has no harmonics (as -100
0.14 0.16 0.18 0.2 0.22 0.24
it is only controlled to produce real and reactive power),
5
and the nonlinear load current is supplied through the
(b) 0
A
-5
The situation with PCC voltage harmonic 0.14 0.16 0.18 0.2 0.22 0.24
compensation is shown in Figs. 12 and 13. As expected, Time (s)
by acting as a low resistance Rh at the harmonic Fig. 12. Current control method with harmonic compensation: (a) PCC
frequencies, the DG unit absorbed most of the nonlinear phase voltage, (b) grid current, (c) DG current.
load currents, leading to an improved grid current and
PCC voltage as shown in Fig. 12 (a) and (b). As shown in
Mag (% of Fundamental)
10
Fig. 13, the low order harmonics of PCC voltage are
significantly reduced, which results in a THD of 2.5%.
5
B. Voltage Control Method
The voltage controlled DG and different compensation
modes are also tested in the simulation, and the results 0
0 5 10 15 20 25 30
are shown in Figs. 14-19. Harmonic order
Figs. 14 and 15 show the results without any harmonic Fig. 13. Harmonic analysis of PCC voltage under current controlled DG
compensation, i.e. the DG unit is controlled with pure with harmonic compensation (THD =2.50%)
sinusoidal output voltage (see Fig. 14 (b)). In this case, voltage are improved. As shown in Fig. 17, the 5th
the DG and grid equally share the nonlinear load current harmonic voltage at PCC is reduced to about 1.5% and
as seen from Fig. 14 (c) and (d). As a result, the PCC the THD is reduced to 2.42%.
voltage is distorted due to the nonlinear current flow on Finally, the harmonic rejection mode is tested and the
the grid impedance. Fig. 15 shows that the PCC voltage results are shown in Figs. 18-19. As expected, with G=-1,
has almost 6% 5th harmonic and the THD is 6.72%. the DG output current is controlled to be sinusoidal (see
To improve the PCC voltage, the harmonic Fig. 18(d)) due to the very high DG impedance at
compensation is implemented (with G5=12, G7=12, harmonic frequencies. In this case, the grid will provide
G11=5). As the DG output impedance at harmonics all the nonlinear load current, and therefore the grid
frequencies is reduced by a factor of (1+Gh), the DG unit current and voltage are further distorted. The PCC
absorbs most of the load nonlinear current as can be seen voltage has 8% 5th harmonic, and the THD is 10.08%. As
in Fig. 16 (d). As a result, the grid current and PCC
1662
The 2010 International Power Electronics Conference
100 100
(a) 0 (a) 0
V
V
-100 -100
0.7 0.72 0.74 0.76 0.78 0.8 2.3 2.32 2.34 2.36 2.38 2.4
100 100
(b) (b) 0
V
0
V
-100 -100
0.7 0.72 0.74 0.76 0.78 0.8 2.3 2.32 2.34 2.36 2.38 2.4
5 5
(c) 0 (c) 0
A
A
-5 -5
0.7 0.72 0.74 0.76 0.78 0.8 2.3 2.32 2.34 2.36 2.38 2.4
5 5
(d) (d)
A
0 0
A
-5 -5
0.7 0.72 0.74 0.76 0.78 0.8 2.3 2.32 2.34 2.36 2.38 2.4
Time (S) Time (S)
Fig. 14. Voltage control method without compensation: (a) PCC phase Fig. 16. Voltage control method with harmonic compensation: (a) PCC
voltage, (b) DG phase voltage, (c) grid current, (d) DG current. phase voltage, (b) DG phase voltage, (c) grid current, (d) DG current.
10 10
Mag (% of Fundamental)
Mag (% of Fundamental)
8 8
6 6
4 4
2 2
0 0
0 5 10 15 20 25 30 0 5 10 15 20 25 30
Harmonic order Harmonic order
Fig. 15. Harmonic analysis of PCC phase voltage under voltage Fig. 17. Harmonic analysis of PCC voltage under voltage controlled DG
controlled DG without harmonic compensation (THD =6.72%) with harmonic compensation (THD =2.42%)
expected, this performance is similar to the current current is 15.3% and 26.3% respectively.
control mode without PCC harmonic compensation. Note that the increase of harmonics compared to
simulations is introduced by using higher DG and grid
C. Experimental Verifications impedance in the experiment.
Experiments are also conducted on a 5kVA grid
connected DG system to verify the voltage control VI. CONCLUSIONS
method. In the experiment, a three-phase programmable
This paper investigates the opportunities of
power supply is used to represent the grid, and the three-
distribution system power quality improvement using the
phase DG system is control with a DSP-FPGA system. In
DG interfacing inverters. Both the current controlled
the experiment, the 5th and 7th harmonics are
method and the voltage controlled method are considered
compensated. The experimental parameters are listed in
and their associated power quality compensation schemes
Table 1, and the results are shown in Figs. 20-22.
are developed. Specifically, the voltage controlled DG
The performance of uncontrolled mode (without
can be operated with compensation, rejection and
harmonic compensation) is shown in Fig. 20, where it can
uncontrolled mode, where the harmonic compensation
be seen that the DG and grid share the nonlinear load
and rejection modes produce similar performance as with
current. Since the DG real and reactive power references
the current controlled DG. The proposed control
is smaller in the experiment (see Table 1), the grid current
strategies have been verified in both simulation and
contains higher fundamental current. Without harmonic
experiments. Note that although the paper focuses on the
compensation, the THD of PCC voltage and grid current
PCC voltage harmonic compensation, it can be extended
is 10.5% and 16.9% respectively.
for flicker and unbalance compensation as well.
When PCC harmonic compensation is implemented,
the DG absorbs the nonlinear load current and as a result,
both the source current and PCC voltage are improved as REFERENCES
shown in Fig. 21. In this case, the THD of PCC voltage [1] I. El-Samahy and E. El-Saadany, “The effect of DG on
and grid current is improved to 5.2% and 7% power quality in a deregulated environment,” Proc. IEEE
respectively. PESGM - 2005, pp. 2969- 2976.
[2] IEEE Standard for Interconnecting Distributed Resources
Finally, for the harmonic rejection mode, the DG
with Electric Power Systems, IEEE Std. 1547, 2003.
output current is controlled to contain very few [3] IEEE Recommended Practices and Requirements for
harmonics as the DG output impedance is increased Harmonic Control in Electrical Power Systems, IEEE Std
significantly at harmonic frequencies. As a result, most of 519-1992, Apr. 1993.
the nonlinear load current is supplied through the source [4] M. Triggianese, F. Liccardo, and P. Marino, “Ancillary
and the PCC voltage is further deteriorated. With Services performed by Distributed Generation in grid
harmonic rejection, the THD of PCC voltage and grid
1663
The 2010 International Power Electronics Conference
100
(a) 0
V
-100
1.5 1.52 1.54 1.56 1.58 1.6
100
(b) 0
V
-100
1.5 1.52 1.54 1.56 1.58 1.6
5
(c) 0
A
-5
1.5 1.52 1.54 1.56 1.58 1.6
5
(d) 0
A
-5
Fig. 20. Voltage control method without harmonic compensation: (a)
1.5 1.52 1.54 1.56 1.58 1.6 DG line voltage (200V/div), (b) PCC line voltage (250V/div), (c) grid
Time (S) current (5A/div), (d) DG current (5A/div).
Fig. 18. Voltage control method with harmonic rejection: (a) PCC phase
voltage, (b) DG phase voltage, (c) grid current, (d) DG current.
10
Mag (% of Fundamental)
0
0 5 10 15 20 25 30
Harmonic order
Fig. 21. Voltage control method with harmonic compensation: : (a) DG
Fig. 19. Harmonic analysis of PCC voltage under voltage controlled DG line voltage (200V/div), (b) PCC line voltage (250V/div), (c) grid
with harmonic rejection (THD =10.08 %) current (5A/div), (d) DG current (5A/div).
integration,” Proc. IEEE International Conference on
Clean Electrical Power, 2007, pp. 164–170.
[5] M.I. Marei, T.K. Abdel-Galil, E.F. El-Saadany, and
M.M.A. Salama, “Hilbert transform based control
algorithm of the DG interface for voltage flicker
mitigation,” IEEE Trans. Power Delivery, vol. 20, pp.
1129- 1133, April 2005.
[6] M. Prodanovic, K. De Brabandere, J. Van Den Keybus, T.
Green, and J. Driesen, “Harmonic and reactive power
compensation as ancillary services in inverter-based
distributed generation,” IEE Proc. Gener. Transm.
Distrib., vol.1, pp.432-438, May 2007
[7] N. Pogaku and T.C. Green, “Harmonic mitigation Fig. 22. Voltage control method with harmonic rejection: : (a) DG line
throughout a distribution system: a distributed-generator- voltage (200V/div), (b) PCC line voltage (250V/div), (c) grid current
based solution,” IEE Proc. Gener. Transm. Distrib., vol. (5A/div), (d) DG current (5A/div).
153, no. 3, pp. 350- 358, 11 May 2006.
[8] C.J. Gajanayake, D.M. Vilathgamuwa, P. C. Loh, R. [13] D. N. Zmood, D. G. Holmes and G. H. Bode, “Stationary
Teodorescu, and F. Blaabjerg, “Z-Source-Inverter-Based frame current regulation of PWM inverters with zero
Flexible Distributed Generation System Solution for Grid steady-state error,” IEEE Trans. Power Electron., vol. 18,
Power Quality Improvement,” IEEE Trans. Energy pp. 814–822, Mar. 2003.
Conversion, vol.24, pp.695-704, Sept. 2009. [14] P. Mattavelli, “Synchronous-frame harmonic control for
[9] Y. W. Li, D. M. Vilathgamuwa and P. C. Loh, “Microgrid high-performance AC power supplies,” IEEE Trans. Ind.
Power Quality Enhancement Using A Three-Phase Four- Applicat., vol. 37, pp. 864–872, May/Jun. 2001.
Wire Grid-Interfacing Compensator,” IEEE Trans. Ind. [15] R. Lasseter, “Microgrids,” Proc. IEEE Power Engineering
Applicat., vol. 41, pp. 1707-1719, Nov-Dec. 2005. Society Winter Meeting, 2002, pp. 305–308.
[10] P. Jintakosonwit, H. Akagi, H. Fujita, and S. Ogasawara, [16] Y. W. Li, D. M. Vilathgamuwa, and P. C. Loh, “Design,
“Implementation and performance of automatic gain Analysis and Real-Time Testing of Controllers for Multi-
adjustment in a shunt-active filter for harmonic damping Bus Microgrid System,” IEEE Trans. Power Electron.,
throughout a power distribution system,” IEEE Trans. vol. 19, pp. 1195-1204, Sep. 2004.
Power Electron., vol.17, pp. 438-447, May 2002. [17] Y. W. Li and C. N. Kao, “An Accurate Power Control
[11] L. Asiminoaei, F. Blaabjerg, and S. Hansen, “Evaluation of Strategy for Power-Electronics-Interfaced Distributed
harmonic detection methods for active power filter Generation Units Operating in a Low-Voltage Multibus
applications,” IEEE APEC- 2005, pp. 635- 641. Microgrid,” IEEE Trans. Power Electron., vol. 24, pp.
[12] E. Jacobsen and R. Lyons, “The Sliding DFT,” IEEE 2977-2988, Dec. 2009.
Signal Processing Magazine, vol 20, pp. 74-80, Mar. 2003.
1664