You are on page 1of 17

Image courtesy of the Taiwan Tourism Bureau

王中平,
王中平, 高雄電機技師公會,
高雄電機技師公會, 2010/03/31

Protection Relay for Transmission


IED 670 Series

© ABB Group
March 31, 2010 | Slide 1

The Relion® product family


From intercontinental transmission grids to secondary
distribution kiosks

 670 series - optimized for  650 series – your best


transmission applications choice for sub-transmission
applications
 630 series - optimized for
advanced distribution  615 series - standard
applications configurations for
distribution applications
 610 series - for dedicated
distribution applications  60_ series - for secondary
distribution applications
© ABB Group
March 31, 2010 | Slide 2

1
IED670 670 vs 500 series; Evolution not Revolution
 Same
 mechanical 19” design
 internal CAN bus & I/O cards
 Principle algorithms & logic
 Extended modular hardware
 Max 24 Analogue Inputs
 Max 14 I/O boards (i.e..224BI / Max 4 BOM = 98BO)
 More powerful CPU & memory capacity
 600 MHz, 256 Mb DRAM + 64 Mb Flash
 Extended functional library (IEC 61850 nodes)
 Disturbance Recorder (100 x 3.4 s; 40 A + 96B)
 Extended communication facilities
 Multiple SA protocols
 Multiple differential communication channels
 Graphical HMI
 Engineering tool; PCM 600
 Signal matrix
 IEC 61850 configuration

© ABB Group
March 31, 2010 | Slide 3

IED670 Robust design for HMI, communication, AI and I/O

© ABB Group
March 31, 2010 | Slide 4

2
IED670 Select your perfect hardware

© ABB Group
March 31, 2010 | Slide 5

IED670 Available I/O-modules 1/1 19” case

MIM
(max 4st)

IOM
(max 6st)
6 Transducer inputs,
setting range + 20 mA
BOM
(max 4st)
12 binary outputs
and 8 binary inputs
BIM
(max 11/14st)
24 binary outputs

16 binary inputs

 Up to 24 analog inputs per IED permit integration of main and back-up protection in one IED
and/or additional objects

© ABB Group
March 31, 2010 | Slide 6

3
IED670 670 Series Hardware Platform
 Transformer Input Module TRM
6I + 6U, 9I+3U or 12I
 One or two - TRM1 & TRM2 for 12 or 24 analogue CT
or VT inputs
 Analog Digital Conversion module ADM1 and ADM2 for
TRM inputs
 Central Processing Unit NUM
 GPS time synchronization module GSM (option)
 Time synchronization via binary signal and
communication ports IRIG-B
 Binary Input / Output modules BIM, SOM, BOM, IOM,
MIM
 Power supply module PSM

© ABB Group
March 31, 2010 | Slide 7

IED670 670 Series Hardware Platform


ABB IED 670
Analogue A/D Main GPS Binary Binary Binary Binary Binary mA Power
Input Conversion Processing Synch I/O I/O I/O I/O I/O Input Supply
Module Module Module Module Module Module Module Module Module Module Module
TRM AD1 NUM GSM BIM BIM BIM BOM BOM MIM PSM
3
PCU

3
Logics CAN
3 1Mbit/s
6I
A/D
6U
3
OEM
~
~ ~
~
LDCM
Comm-
uni-
cation

I/O I/O I/O I/O I/O mA

© ABB Group
March 31, 2010 | Slide 8

4
IED670 Standardized Transformer Modules

Transformer module (TRM 12) 1A 5A 110/220 V


6I and 6U 6 6
6I and 6U 6 6
9I + 3U 9 3
9I + 3U 9 3
9I + 3U 5 4 3
12I 12
12I 12
6I 6
5I + 5U 5 5

© ABB Group
March 31, 2010 | Slide 9

IED670 Available I/O-modules 1/1 19” case


 GPS time synch module (GSM)
1/
1 19” rack, 6U high  IRIG-B time synch
 Up to 4 Protection Communication Modules for multi terminal
line differential (LDCM)
 Optical Communication modules
 OEM IEC 61850-8-1 Ethernet
 OEM IEC 61850-9-2 Ethernet (restricted)
 SLM LON(1); SPA or IEC103
 RS485 DNP 3.0 module
½ 19” rack, 6U high  Static binary output module (SOM)

© ABB Group
March 31, 2010 | Slide 10

5
IED670 Communication
 IED 670s are designed to communicate with substation
automation systems
 IEC 61850-8-1
4 x 4 analog channels  verified by independent test institution
4 x 8 binary signals  IEC 60870-5-103
remote communication  LON
 SPA
 DNP 3.0
IEC 61850 8-1  TCP/IP communication to the
PCM 600 tool
or LON
IEC 60870-5-103
or SPA  IEC 61850-9-2 for process bus
 ANSI C37.94 for teleprotection

192 binary
signals remote
communication

PC Ethernet connection

© ABB Group
March 31, 2010 | Slide 11

IED670 ALL IED670 include GOOSE

GOOSE = Generic Object Oriented System-wide Events

Data to be sent to other IEDs are


defined in the engineering tool

GOOSE

Control Protection Control & Control Protection


Protection

 Peer to peer communication


 An IED sends information by multicasting
 Only IEDs which are defined to listen (subscribers) receive this message

© ABB Group
March 31, 2010 | Slide 12

6
IED670 Powerful Information Management
 Protection and Control IED Manager for the 600 series
 PCM600
 PCM 600 consists of following tools:
 Application Configuration(CAP531)
 Signal Matrix (SMT)
Configuration of:
I/O cards,
Analog Input Cards
GOOSE
64 kbit communication
 Parameter Setting (PST)
 Disturbance Handling
 Graphic Display Editor (SLD Editor)
 Time scheduler
 Signal Monitoring
 Event Viewer
 User Management

© ABB Group
March 31, 2010 | Slide 13

IED670 One Common Tool

© ABB Group
March 31, 2010 | Slide 14

7
IED670 PCM600 Parameter Setting

© ABB Group
March 31, 2010 | Slide 15

IED670 Full Control Over Parameter Settings

 All parameters set in primary quantities within


the pre-defined setting ranges
 Clear overview of parameter settings
uploaded from an IED and settings entered in
PCM 600
 Versatile filtering functions:
 Basic and advanced parameters
 Visible and hidden parameters
 Changed parameters
 Parameter value in IED differs from
the parameter value in PCM 600 and
invalid parameters

© ABB Group
March 31, 2010 | Slide 16

8
IED670 PCM600 Graphical Configuration of IED HMI

 Easy to instantiate the power


system object into the display page
and assign it to its switching
function
 Easy to include on-line
measurement in the IED HMI
 Easy to set node attributes like
name, name position and sort index
 Extensive IEC and ANSI symbol
library

© ABB Group
March 31, 2010 | Slide 17

IED670 Monitoring

 Signal monitoring for on-line information about


the measured quantities and status of binary
input and output signals
 All signals can be monitored in a signal list
 A report can be generated, printed and
exported to Excel

 Event viewer for viewing process events and


internal system events on-line

© ABB Group
March 31, 2010 | Slide 18

9
IED670 Signal Matrix Tool (SMT)

© ABB Group
March 31, 2010 | Slide 19

IED670 Signal Matrix Tool (SMT)

© ABB Group
March 31, 2010 | Slide 20

10
IED670 SMT: Virtual and Real Binary Inputs
HARDWARE: Binary Input Card

© ABB Group
March 31, 2010 | Slide 21

IED670 The role of SMT for Binary Outputs

© ABB Group
March 31, 2010 | Slide 22

11
IED670 Analog Input Configuration

© ABB Group
March 31, 2010 | Slide 23

IED670 Disturbance Recorder – Inputs


 40 analog channels
 flexible analog configuration
 voltages and/or currents (30 channels via AIM, LDCM or Σ-block)
 derived analog signals (10 channels)
 setting possibilities:
 be recorded or not
 trig disturbance recording
 96 binary channels
 any internal or external (via BIM) binary signal
 these 96 signals are logged into IED internal Event List
 setting possibilities:
 be recorded or not
 trig disturbance recording and trigger mode
 be included in Indications
 activate local HMI LED

© ABB Group
March 31, 2010 | Slide 24

12
IED670 PCM 600 - Disturbance Report Tool
TOTAL RECORDING

Visualisation of the full disturbance: analog and binary signals.


© ABB Group
March 31, 2010 | Slide 25

IED670 Event List Handling

Even t s \ Even t Li st  The event buffer can store and show on display
2004 - 12 - 15
up to 1000 events on a FIFO principle
12 : 17 : 54 . 711 054 TR I P - T R L 1 on
53 . 611 012
. 611 066
TR I P - T R I P
ZM3 - S T L 1
on
on
 The events are time tagged with a resolution of
. 611 079 CB 1 - C L OSE on 1 ms
12 : 16 : 58 . 711 096 ZCOM - CS of f
57 . 611 012 TR I P - T R I P on
. 611 011 TOC 1 - T R I P on  The user can choose in having the last event on
2004 - 12 - 14
12 : 17 : 56 . 711 054 TR I P - T R L 1 on
top or the last event on bottom
55 . 611 012 TR I P - T R I P on
. 611 066
. 611 079
ZM3 - S T L 1
CB 1 - C L OSE
on
on
 Events can be defined as a part of the
12 : 16 : 58 . 711 096 ZCOM - CS of f Disturbance Report
57 . 611 012 TR I P - T R I P on
. 611 011 TOC 1 - T R I P on
2004 - 12 - 13  Upload event list to PC
12 : 17 : 56 . 711 054 TR I P - T R L 1 on
55 . 611 012
. 611 066
TR I P - T R I P
ZM3 - S T L 1
on
on
 Event list sorting facility
. 611 079 CB 1 - C L OSE on
12 : 16 : 58 . 711 096 ZCOM - CS of f
57 . 611 012 TR I P - T R I P on
. 611 011 TOC 1 - T R I P on
2004 - 12 - 12
12 : 17 : 56 . 711 054 TR I P - T R L 1 on
55 . 611 012 TR I P - T R I P on
. 611 066 ZM3 - S T L 1 on
. 611 079 CB 1 - C L OSE on
2004 - 12 - 17 08 : 37 No r t h Co n n e c t i o n

© ABB Group
March 31, 2010 | Slide 26

13
IED670 IED670 Operation introduction

© ABB Group
March 31, 2010 | Slide 27

IED670 Fast Access to Information


Status indication
 Green
Steady: In service
Flashing: Internal failure
Dark : No power supply
 Yellow:
Steady: Disturbance recorder triggered
Flashing: IED in test mode
 Red:
Steady: Trip command issued
Flashing: IED blocked
Measurements
 Single line diagram presents measurements
 Selected measurements
 Selected calculated values

© ABB Group
March 31, 2010 | Slide 28

14
IED670 Main Basic Functions in IED 670
 Service Value Measurement
(I, U, P, Q, S, f)
 Configurable logic and event counter
 Signal and Tripping matrix
 Remote communication
(requires LDCM)
 Event list (1000 signals)
 Disturbance recorder for 40 analogue & 96 digital channels
 100 disturbances
 Trip value & internal signals report
 Supervision of I, U and mA inputs
 Real time clock with external synchronization
 1 ms time tagging resolution
 6 setting groups
 >< U, I, I1 , I2 , 3I0 , f, Z configurable functions
 Self supervision & diagnostics

© ABB Group
March 31, 2010 | Slide 29

IED670 Main Application Functions in IED670


 Five Zone full scheme distance protection
 Five terminal line differential protection
 Six input transformer differential protection
 Generator differantial/block differential
 High impedance and restricted EF differential
 Ultra High Speed bus differential protection
 Phase segregated directional comparison
 Adaptive Breaker Failure Protection
 Four step Dir/Undir overcurrent protection
 Four step Dir/Undir earthfault protection
 Over Excitation & Over Load Protection
 Multi purpose protection (E.g. Generators, Mho)
 Multi bay & Multi breaker Control, AR & SC
 Multi input measurement (24 AI)
 High accuracy fault locator

© ABB Group
March 31, 2010 | Slide 30

15
IED670
IED670 – Application areas
REL670
RED670

RET670 REC670

REB670 REG670  Generator protection IED for

 Busbar protection IED for  small to medium sized generators

 Autotransformers
 Shunt Reactors

 Shunt Capacitors
© ABB Group
March 31, 2010 | Slide 31

IED670 ABB Substation Automation Web Site

© ABB Group
March 31, 2010 | Slide 32

16
IED670 ABB Substation Automation Web Site

 Our Web Site


www.abb.com/substationautomation

www.abb.com/relion

www.abb.com.tw

 聯絡人:
王中平 0935-080-880
李聖彬 0922-882-906
E-mail: rick.lee@tw.abb.com

© ABB Group
March 31, 2010 | Slide 33

17

You might also like