MDVS System Guide DRYER VENTING SYSTEMS

Better Drying with Better Venting

Clothes Dryer Exhaust

EXSTREAM
PERFORMANCE
DEVELOPED AND MANUFACTURED BY EXHAUSTO
Can Your Clothes Dryers Breathe?
Create the Ultimate Design - Feel the Difference Forever...

A Better Climate for Clothes Dryers


Clothes dryers will make or break a laundry facility. If the user thinks the clothes have been in the
dryer long enough and they are still not dry, the clothes dryer will get the blame.

Extensive drying times are typically caused by bad exhaust design, reduced duct sizes and
insufficient make-up air. You are probably concerned about duct runs that cause your dryers to
experience too much back-pressure and violate building codes – only then to install a booster fan
that does not live up to your standards?

The MDVS Mechanical Dryer Venting System™ is the benchmark for dryer venting. The fully
modulating MDVS system maintains the proper flow in ducts serving multiple Type 1 and Type 2
clothes dryers.
Reduce Operating Cost
Advantages
The MDVS provides a wealth of advantages. Ducts can be
configured the most efficient and cost-effective way and still
meet code requirements. Aesthetics can be enhanced as the
MDVS reduces the number of required ducts and roof or
wall openings.

Even the make-up air can be provided with the assistance


of the MDVS system, which can also operate and control
a make-up air fan. Insufficient make-up air is the biggest
problem faced by the laundry industry today.

If dryers are not vented properly, lint will accumulate in the


dryers and the ductwork. This is not only dangerous, but will
also affect drying ability.

Proper Airflow Saves Money & Energy


The improved flow control maximizes the clothes dryer’s
operating efficiency and improves drying times. The
modulating flow control system reduces energy
consumption dramatically compared to a constant speed
flow control system with a single speed fan. The savings can
be dramatic:
When dryers don’t get the air they need or the proper
20 Dryer Multistory Apartment exhaust, the dryers short-cycle and can’t achieve a proper
MDVS Single Speed Fan Savings burn pattern. It takes longer to dry, which affects the bot-
4,368
tom line.Improved drying time translates into additional
Fan Power 41 kW/yr $4/yr $437/yr $433/yr
kW/yr energy savings. An inefficient dryer will make a user add
Loss of drying time or a complete cycle. Operating savings of
1,454 155,520
Heated
kBtu/yr
$15/yr
kBtu/yr
$1,555/yr $1,540/yr 20-30% are realistic.
Air

Loss of Installation is also less expensive. There are virtually no duct


Cooled Air 824 88,128
(sensible (kBtu/yr)
$5/yr
kBtu/yr
$557/yr $552/yr length limitations and a common duct can be used for
only) venting in lieu of multiple ducts that also require multiple
Total Annual Savings = $2,525 roof or wall penetrations.
Location = Atlanta, GA (3000DDH 1700DDC)
Power = $0.10/kW, Heating = $1.00 per therm, A/C = 0.75 kW/ton x $0.10 per kW/h


Code Compliance & Design
The MDVS system is listed and approved for removal of lint-laden
air and our designs comply with NFPA and ICC Building and
Fuel Gas Codes. We have decades of experience in the field of
mechanical dryer venting and have exhausted dryers from ADC
to Whirlpool and almost every manufacturer in between.

EXHAUSTO assists with design and layout of dryer venting


Enhance Flow for Reduce Energy Cost systems. We have many years of experience dealing with
Efficient Operation fire-rated shafts, diversity factors, lint issues, velocities and
acceptable pressure differentials.

EXHAUSTO wrote the book on mechanical dryer venting!

EXHAUSTO MDVS Mechanical Dryer Venting


System™
EXHAUSTO’s MDVS systems for multistory and multifamily
dwellings and central laundry facilities, or coin-laundries used
with the recommended EXHAUSTO products, always provide
modern, efficient and energy-saving dryer venting. We guarantee
that our products are made to work together effectively and that
our systems comply with and are listed with all relevant codes
and listing standards.

Detailed descriptions of our systems are provided on the


following pages.


MDVS - Multistory Venting Systems
with “on-demand” Control
EXSTREAM
PERFORMANCE
DEVELOPED AND MANUFACTURED BY EXHAUSTO

The MDVS, Mechanical Dryer Venting System™ is used to


extract lint-laden air from Type 1 clothes dryers in multistory
residential dwellings. It features “on-demand” control that
maintains a precise exhaust condition for the dryers by
constantly adjusting the exhaust rate to meet current needs.

The concept assures that dryers are never over- or under-


drafted and optimal dryer times are achieved at the lowest
possible use of energy. It assures optimal performance and
control.

• Full modulation and 100% pressure control


• Bearing Cycle Activation.
• Easy programming of essential functions – 80
parameters are programmable for customized solutions.
• Spark-resistant construction with TEF-motor with direct
drive and true variable speed (inverter duty).
• System and control are listed to UL705 Standard for
Power Ventilators with special consideration to
exhausting lint-laden air from clothes dryers.


Exhaust Unit: Option 1:
BESB Box Ventilator

Option 2:
RSV Fan

Control System: EBC 12 – integrated control
with constant pressure
modulation.

Speed Control: For 1-phase fans the speed


control is provided directly
by the EBC control. For
3-phase fans the speed
control is provided by the
EBC control via a VFD.

ERTEK
INT

CM

C US
LISTED


MDVS - Laundry Room Venting Systems
with “on-demand” Control

EXSTREAM
PERFORMANCE
DEVELOPED AND MANUFACTURED BY EXHAUSTO

The MDVS, Mechanical Dryer Venting System™ is used to


extract lint-laden air from Type 1 or 2 clothes dryers in
residential or commercial laundry facilities and
coin-laundries. It features “on-demand” control that
maintains a precise exhaust condition for the dryers by
constantly adjusting the exhaust rate to meet current needs.

The concept assures that dryers are never over- or under-


drafted and optimal dryer times are achieved at the lowest
possible use of energy. It assures optimal performance and
control.

An optional make-up air solution is available as the control


can monitor and control the supply of make-up air via a
fan. It eliminates the need for louvers to provide air for the
dryers.
• Full modulation and 100% pressure control
• Bearing Cycle Activation.
• Easy programming of essential functions – 80
parameters are programmable for customized solutions.
• Spark-resistant construction with TEF-motor with direct
drive and true variable speed (inverter duty).
• System and control are listed to UL705 Standard for
Power Ventilators with special consideration to
exhausting lint-laden air from clothes dryers.


Exhaust Unit: Option 1:
BESB Box Ventilator

Option 2:
RSV Fan

Control System: Option 1:
EBC 12 – integrated control
with constant pressure
modulation.

Option 2:
EBC 30 - integrated control
with constant pressure
regulation of both exhaust
and supply air.

Speed Control: For 1-phase fans the speed


control is provided directly by
the EBC control. For 3-phase fans INT
ERTEK

the speed control is provided by CM

the EBC control via a VFD. C


LISTED
US


Choose the Right Components!

BESB Low Energy Fan MDVS



• Low energy fan in compact design
• High efficiency aluminum impeller guaranteeing EXstream performance
• Made from corrosion resistant material (indoor or outdoor installation)
• Insulated housing and quiet operation
EXSTREAM
PERFORMANCE
• Variable-speed class A motor (inverter duty)
DEVELOPED AND MANUFACTURED BY EXHAUSTO
• Access with 180° opening angle and full duct access
• 4 sizes available, ETL and ETLc Listed

RSV Low Energy Fan MDVS

• Vertical exhaust in small compact design


• High efficiency aluminum impeller guaranteeing EXstream performance
• Made from corrosion resistant material (indoor or outdoor installation)
• Quiet Operation
EXSTREAM
PERFORMANCE • Variable speed, class H motor (inverter duty)
• Clam shell design opens 90° for full duct access
DEVELOPED AND MANUFACTURED BY EXHAUSTO

• 4 sizes available, ETL and ETLc Listed

EBC 30 Fan Speed Control MDVS

• Constant pressure control for fans


• Used where constant pressure is needed in the exhaust duct or in the
laundry room for “on-demand” control
• Helps keep power consumption down
• “Plug-and-Play” design for easy operation
• Can control exhaust rate and make-up air supply rates.

EBC 12 Fan Speed Control MDVS

• Constant pressure control for fans


• Used where constant pressure is needed in the exhaust duct for
“on-demand” control
• Helps keep power consumption down
• Easy to operate

Danfoss VLT2800 Variable Frequency Drive MDVS

• Pre-wired for easy installation with EBC 12 or EBC 30


• Pre-programmed from factory - no field programming needed.


MDVS, Mechanical Dryer Venting System™
System Components and Specifications

EBC 12,
incl. XTP
and stack
probe


Support Services

Project and Design Support


EXHAUSTO solutions are so much more than just
products and systems. We provide pre-sale analysis,
system design and implementation recommendations.
During this process we use state-of-the-art design
software, developed by EXHAUSTO, which enables us
to design any system with great accuracy and speed.
The design software, FanCalc, integrates a database
of clothes dryers complete with operating data and
requirements, such as exhaust requirements, exhaust
temperatures, efficiency and much more – something
that nobody else has. The database also includes data
on ducts with k-values, resistance factors, insulation-
factors, etc.
Engineering and Installation Support
FanCalc allows EXHAUSTO’s experienced engineers to
design complete venting systems fast, accurate and Systems designed by EXHAUSTO come complete with
efficiently, while providing engineers with sizing reports, AutoCAD installation instructions and wiring diagrams
code violation warnings as well as design alternatives. for the specific job. They are not generic diagrams but
EXHAUSTO has venting design capabilities that not drawings showing where components are installed
many fan or venting manufacturer can match. In and exactly how they are wired together so potential
addition to creating venting system designs, FanCalc problems in the field are resolved before they occur. A
checks for code violations. It calculates and checks for customized installation
proper vent type application, operating temperatures, and wiring package is
pressure losses in each venting component, risk of part of the delivery. FanCalc Ver. 2.0
FanCalc Ver
. 2.0
EXHAUSTO
: F-02808 Job #

condensation and provides system specific wiring


EXHAUSTO Job #

EXHAUSTO offers
Job/Project : F-02808
: Jackson Twp School Name w Pkwy
Job/Project Name City/State : Jackson 1200 Northmeado
: Ocean City, NJ Twp STE 180
City/State : Ocean City, School
Prepared NJ Roswell, GA 30076
: Tom Haddad for
Tel: (800) 255-2923
Prepared for Compa
Co. ny : Tom Haddad
: Energy Products Fax: (770) 587-4731
Company City/State : Energy
: Broomall, PA Products Co.
us.exhausto.com

diagrams.
1200 Northm

telephone engineering
City/State : Brooma eadow
ll, PA Pkwy
Prepared
: Steen Hagensen by STE 180
Prepared by E-mail : Steen Hagens Roswell, GA
: steenh@exhausto.com
E-mail Phone Ext. : steenh@exha en Tel: (800)
30076
: 2501 usto.com 255-2923
Phone Ext. : 2501 Fax: (770)
Fan Syste 587-47
m Data: us.exhausto.co31
Fan System Data: : 2-CBs and 2-PVIs

and installation
m
System Type Description
: CASV
System Type : CASV

As EXHAUSTO usually designs the entire venting


Location
Data: Description
Location Data: : 60 °F
Local Altitude Ambient Temperature : 2-CBs and
2-PVIs
: 0 ft A.S.L.Barome : 0 ft A.S.L.
Local Altitude

support. All designs are


: 29.92 in. Hg tric Pressu
Barometric Pressure re : 29.92 in.
Hg Ambient Tempe
Equipment

system, we also take full responsibility for its operation.


rature
Data: : 60 °F
Equipment Data: Temp. Barometric
Input CO2%
Fuel Rise, °F Damper
Appl. Category MBH
Model Manufa
Appl. Manufacture r No. cturer
Model 360 NO
2510 9.00
No. Natural Gas Catego 360 NO
1 III 9.00
ry

stored electronically,
CBH-60 Cleaver-Brooks Natural Gas 2510 NO
Cleaver-Brooks 2 III 5.30 300Fuel
1 CBH-60 Cleaver-Brooks CBH-60Gas
Natural
270 NOInput CO2%
2 Cleaver-Brooks 3 I - Draft Hood 270 III 5.30
300 MBH Temp.

This is part of EXHAUSTO’s “Performance Guarantee”.


27-G PVI Industrie CBH-60Gas
Natural Barometric
3 PVI Industries 4
27-G I - DraftsHood
PVI Industrie 27-G III
Natural Gas Rise, °F
Damper
s Natural Gas 2510
4 PVI Industries I - Draft Hood 9.00
27-G 2510 360
Vent Syste I - Draft Hood Natural Gas 9.00 NO
360
m Data: 270
Vent System Data:
Natural Gas 5.30 NO
Temp. Fitting(s) 270 300
Velocity 5.30 NO

so our engineers and


Section Horiz. Mass Flow
Size Vert. Model °F 300
Model StackNo. lb/h FPM NO
Section ft ft Stack Size Vert.
in. 376 None
No. 5609in. 1116 Horiz. Mass
1 18 - 90°T
Flow Velocity
18ø Pressure
Stack 979ft ft 401
1 Pressure Stack 2 2
Pressure - 4778
18ø 407 90°T, (2) 45°L
lb/h Temp.
Fitting(s)
18ø Stack 986
18 FPM

All calculations and system recommendations provided


2 Pressure Stack 3 -
Pressure 12 4778
18ø - 415 5609 WYE, 90°L °F
18ø Stack 1611
2
3 Pressure Stack 4 2
Pressure 8 2389
18ø - 415 4778 WYE, 90°L 1116
10ø Stack 1611
- 376
4 Pressure Stack 5 2 8 2389
10ø 12 286 90°T 979 None

technicians know
10ø Pressure 4778 401
Pressure Stack 6 Stack
32 831 2478 8 323 2389 90°L 986 90°T
5 10ø Pressure- 10ø 407
Pressure Stack 7 Stack
16 831 2 501 8 45°T, 90°L1611 90°T, (2) 45°L
6 10ø -
Pressure 10ø 349 2389 415
Pressure Stack Stack 415 - 405 WYE, 90°L
7 8
8ø Pressure3 5 10ø 32 349 83145°T, 90°L 1611
415
Pressure Stack 9 Stack 5 415 - 405 16 478 WYE, 90°L
8 3
8ø Pressure 8ø 831 286
Stack 3

by EXHAUSTO are performed in accordance with


Pressure Stack 5 501 90°T
9 8ø 415 323
3 90°L
Results: 5
415
405
349
405 45°T, 90°L
in. W.C.

exactly what a system


Results: : 0.198 349
Max. Pressure Loss
45°T, 90°L
Mass Flow : -0.124 in. W.C.
: 5609 lb/h Rate Theoretical Draft
Mass Flow Rate Max. Temp : 5609 lb/h : 0.074 in. W.C.
: 370 °F @ inlet Avaliable Draft
Max. Temp @ inlet Max. 3.283
k value : 370 °F : 0.134 in. W.C.
:
Volume : 3.283 Max. Inlet Pressure Max. Pressure Loss

approved engineering methods. They present an


Max. k value tric Flow Theoretical : 0.198 in.
: 1971 CFM : 1971 CFM Draft W.C.
Volumetric Flow Avaliable Draft : -0.124 in.
Fan Selec W.C.

looks like and what it


tion: Max. Inlet : 0.074 in.
Fan Selection: Pressure
: 0.134 in.
W.C.
RSV400 W.C.
AM
RSV400 10/16/2002, 11:19
Page 1

appropriate “Approved Method” of vent design and includes. 10/16/2002,


11:19 AM
Page 1

sizing as defined in national standards, such as the


National Fuel Gas Code ANSI Z223.1, NFPA 54, IFGC
and others.
Please notice that “the equivalent length method” is
not an approved engineering method for vent sizing.