You are on page 1of 4

1 Product Selection

Relay Functions

1 –

Pilot wire differential


Line differential

Overcurrent

Differential
Distance

7SD600

7SD610

7UT512
7UT513
7UT612
7UT613
7SA513
7SA522

7SJ600
7SJ602

7VH60

7UT63
7SS60
7SS52
7SJ45
7SJ46

7SJ61
7SJ62
7SJ63
7SJ64
7SD5
7SA6

Protection functions Type


ANSI No.* Description –
14 Locked rotor protection – – – – – – – – – – l l l l – – – – – – – –
21 Distance protection, phase n n n – l – – – – – – – – – – – – – – – – –
21N Distance protection, earth (ground) n n n – l – – – – – – – – – – – – – – – – –
21FL Fault locator n n n – l – – – – – – l l l – – – – – – – –
24 Overfluxing (V/f protection) – – – – – – – – – – – – – – – – – – l l – –
25 Synchronizing, synchronism check l l l – l – – – – – – – – l – – – – – – – –
27 Undervoltage – l l – l – – – – – – l l l – – – – – – – –
27/34 Stator earth fault 3rd harmonic – – – – – – – – – – – – – – – – – – – – – –
32 Directional power – – – – – – – – – – – – – l – – – – – – – –
32F Forward power – – – – – – – – – – – – – l – – – – – – – –
32R Reverse power – – – – – – – – – – – – – l – – – – – – – –
37 Undercurrent or underpower – – – – – – – – – l n n n n – – – – – – – –
40 Loss of field – – – – – – – – – – – – – – – – – – – – – –
46 Load unbalance, negative phase- – – – – – – – – n n n n n n – – – l – l – –
sequence overcurrent
47 Phase-sequence voltage n n n – n – – – – – – n n n – – – – – – – –
48 Motor starting protection – – – – – – – – n l l l l l – – – – – – – –
49 Thermal overload – – l – n n – – n n n n n n – n n n n n – –
49R Rotor thermal protection – – – – – – – – n n n n n n – – – – – – – –
49S Stator thermal protection – – – – – – – – n n n n n n – – – – – – – –
50 Instantaneous overcurrent n n n n n n n n n n n n n n – n n n n n – l

50N Instantaneous earth n n n – n n – – n n n n n n – – l n n n – l

fault overcurrent
50BF Breaker failure n l l – n l – – – n n n n n – – – l l l – n

51GN Zero speed and underspeed device – – – – – – – – – – – – – – – – – – – – – –


51 Overcurrent-time relay, phase n n n n n n n n n n n n n n – n n n n n – l

51N Overcurrent-time relay, earth n n n – n n n n n n n n n n – – – n n n – l

51V Overcurrent-time relay, – – – – – – – – – – – – – – – – – – – – – –


voltage controlled
59 Overvoltage n l l – l – – – – – – l l l – – – – – – – –
59N Residual voltage earth l l l – l – – – – n – n n n – – – – – – – –
fault protection
59GN Stator earth-fault protection – – – – – – – – – – – – – – – – – – – – – –
64 100 % Stator earth-fault protection – – – – – – – – – – – – – – – – – – – – – –
(20 Hz)
64R Rotor earth fault – – – – – – – – – – – – – – – – – – – – – –

n Standard function
l Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers

1/2 Siemens SIP · 2004


1 Product Selection

Breaker management
Generator protection

synchronism check

Voltage, frequency
motor protection

Auto-reclosure +
Generator and

Breaker failure
Synchronizing
7UM511
7UM512
7UM515
7UM516

7RW600
7VK512

7SV512
7SV600
7UM61
7UM62

7VK61

7VE51
7VE6
Protection functions Type
ANSI No.* Description –
14 Locked rotor protection – – – – n n – – – – – – –
21 Distance protection, phase – – – n n n – – – – – – –
21N Distance protection, earth – – – – – – – – – – – – –
21FL Fault locator – – – – – – – – – – – – –
24 Overfluxing (V/f protection) – – n – n n – – – – – – n

25 Synchronizing, synchronism check – – – – – – n n n n – – –


27 Undervoltage n – n – n n l – – l – – n

27/34 Stator earth fault 3rd harmonic – n – – n n – – – – – – –


32 Directional power n n – – – n – – – – – – –
32F Forward power – – – n l n – – – – – – –
32R Reverse power – – – n n n – – – – – – –
37 Undercurrent or underpower – n – – – n – – – – – – –
40 Loss of field n n – n l n – – – – – – –
46 Load unbalance, negative phase- n n – n l l – – – – – – –
sequence overcurrent
47 Phase-sequence voltage – – – – n n – – – – – – –
48 Incomplete sequence, locked rotor – – – – l l – – – – – – –
49 Thermal overload n – – – n n – – – – – –
49R Rotor thermal protection – – – – – – – – – – – – –
49S Stator thermal protection n – – – n n – – – – – – –
50 Instantaneous overcurrent – – – – n n – – – – – – –
50N Instantaneous earth-fault – – – – n n – – – – – – –
overcurrent
50BF Breaker failure – – – – n n – – – – n n –
51GN Zero speed and underspeed dev. – – – – – n – – – – – – –
51 Overcurrent-time relay, phase n n – – n n – – – – – – –
51N Overcurrent-time relay, earth – – – – n n – – – – – – –
51V Overcurrent-time relay, n n – – n n – – – – – – –
voltage controlled
59 Overvoltage n n n – n n l – – l – – n

59N Residual voltage earth- n – – – n n – – – – – – –


fault protection
59GN Stator earth-fault protection – n n – n n – – – – – – –
64 100 % Stator earth-fault protection – n n – – l – – – – – – –
(20 Hz)
64R Rotor earth fault – n n – n n – – – – – – –

n Standard function
l Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers

Siemens SIP · 2004 1/3


1 Product Selection

Relay Functions

Pilot wire differential


Line differential

Overcurrent

Differential
Distance

7SD600

7SD610

7UT512
7UT513
7UT612
7UT613
7SA513
7SA522

7SJ600
7SJ602

7VH60

7UT63
7SS60
7SS52
7SJ45
7SJ46

7SJ61
7SJ62
7SJ63
7SJ64
7SD5
7SA6

Protection functions Type


ANSI No.* Description –
67 Directional overcurrent – – – – – – – – – – – n n n – – – – – – – –
67N Directional earth-fault overcurrent l l l – l – – – – n – n n n – – – – – – – –
67G Stator earth-fault – – – – – – – – – – – – – – – – – – – – – –
directional overcurrent
68 Out-of-step protection n l l – l – – – – – – – – – – – – – – – – –
74TC Trip circuit supervision – n n – n n – – n n n n n n – – – l l l – –
78 Out-of-step protection – – – – – – – – – – – – – – – – – – – – – –
79 Auto-reclosure l l l – l l – – l l l l l l – – – – – – – –
81 Frequency protection – n n – l – – – – – – l l l – – – – – – – –
81R Rate of frequency change protection – – – – – – – – – – – – – – – – – – – – – –
Vector jump supervision – – – – – – – – – – – – – – – – – – – – – –
85 Carrier interface/remote trip n n n l n n – – – – – – – – – – – – – – – n

86 Lockout function – n n n n n – – – – n n n n – – – n n n n –
87G Differential protection generator – – – – – – – – – – – – – – – n n n n n – –
87T Differential protection transformer – – – n l l – – – – – – – – n n n n n n – –
87BB Differential protection busbar – – – – – – – – – – – – – – – – – n n n n n

87M Differential protection motor – – – – – – – – – – – – – – – n n n n n – –


87L Differential protection line – – – n n n – – – – – – – – – – – n n n – –
87N Restricted earth-fault protection – – – – – – – – – – n n n n n – n l l l – –

n Standard function
l Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers
1/4 Siemens SIP · 2004
1 Product Selection

Breaker management
Generator protection

synchronism check

Voltage, frequency
motor protection

Auto-reclosure +
Generator and

Breaker failure
Synchronizing
7UM511
7UM512
7UM515
7UM516

7RW600
7VK512

7SV512
7SV600
7UM61
7UM62

7VK61

7VE51
7VE6
Protection functions Type
ANSI No.* Description –
67 Directional overcurrent – – – – n n – – – – – – –
67N Directional earth-fault overcurrent – – – – n n – – – – – – –
67G Stator earth-fault – – – – n n – – – – – – –
directional overcurrent
68 Out-of-step protection – – – n – l – – – – – – –
74TC Trip circuit supervision – – – – n n n – – – – – –
78 Out-of-step protection – – – n – n – – – – – – –
79 Auto-reclosure – – – – – – n n – – – – –
81 Frequency protection n n n – n n – – – l – – n

81R Rate of frequency change protection – – – – l l – – – l – – l

Vector jump supervision – – – – l l – – – l – – –


85 Carrier interface/remote trip – – – – – – – – – – – – –
86 Lockout function – – – – n n n – – l – – –
87G Differential protection generator – – – – – n – – – – – – –
87T Differential protection transformer – – – – – n – – – – – – –
87BB Differential protection busbar – – – – – – – – – – – – –
87M Differential protection motor – – – – – n – – – – – – –
87L Differential protection line – – – – – – – – – – – – –
87N Restricted earth-fault protection – – – – – l – – – – – – –

n Standard function
l Option
* ANSI/EEE C 37.2: IEEE Standard Electrical Power System Device Function Numbers

Siemens SIP · 2004 1/5

You might also like