You are on page 1of 67

website http://www.lgservice.

com

LG
LG
Multi Type Air Conditioner
SERVICE MANUAL
MODEL
• Indoor Unit: Room Type Art Cool Deluxe Type
LMNC096LRL0 LMNC096DUR0
LMNC126LRL0 LMNC126DUR0
LMNC186LTL0 LMNC186D3R0

Floor Standing Type


LMNC246PRC2
LMNC286PRC2
LMNC366PRC2

• Outdoor Unit: L4UC488FA0

CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Multi Air Conditioner Service Manual

TABLE OF CONTENTS
Safety Precautions......................................................................................................................................3

Details of LG Model Name..........................................................................................................................7

Product Specifications ...............................................................................................................................8

Combination Table ....................................................................................................................................10

Dimensions................................................................................................................................................11

Refrigeration Cycle Diagram....................................................................................................................14

Wiring Diagram..........................................................................................................................................15

Electronic Control Device.........................................................................................................................18

Schematic Diagram...................................................................................................................................22

Functions ...................................................................................................................................................26

Operation Details ......................................................................................................................................30

2-way, 3-way Valve ....................................................................................................................................35

Cycle Troubleshooting Guide ..................................................................................................................39

Electronic Parts Troubleshooting Guide.................................................................................................41

Exploded View & Replacement Parts List ..............................................................................................56

2 Free Joint Multi Air Conditioner


Safety Precautions

Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.

WARNING This symbol indicates the possibility of death or serious injury.

CAUTION This symbol indicates the possibility of injury or damage.


■ Meanings of symbol used in this manual are as shown below.

Be sure not to do.

Be sure to follow the instruction.

WARNING
■ Installation
Do not use a defective or Do not let the air conditioner Always ground the product.
underrated circuit breaker. run for a long time when the
Use this appliance on a dedi- humidity is very high and a
cated circuit. door or a window is left open.
• There is risk of fire or electric shock. • Moisture may condense and wet or • There is risk of fire or electric shock.
damage furniture.

Install the panel and the cover Always install a dedicated cir- Use the correctly rated break-
of control box securely. cuit and breaker. er or fuse.
• There is risk of fire or electric shock. • Improper wiring or installation may • There is risk of fire or electric shock.
cause fire or electric shock

Service Manual 3
Safety Precautions

Do not modify or extend the Do not install, remove, or re- Be cautious when unpacking
power cable. install the unit by yourself and installing the product.
(customer).
• There is risk of fire or electric shock. • There is risk of fire, electric shock, • Sharp edges could cause injury. Be
explosion, or injury. especially careful of the case edges
and the fins on the condenser and
evaporator.

For installation, always con- Do not install the product on a Be sure the installation area
tact the dealer or an defective installation stand. does not deteriorate with age.
Authorized Service Center.
• There is risk of fire, electric shock, • It may cause injury, accident, or dam- • If the base collapses, the air condition-
explosion, or injury. age to the product. er could fall with it, causing property
damage, product failure, and personal
injury.

■ Operational
Do not touch(operate) the Do not place a heater or other Do not allow water to run into
product with wet hands. appliances near the power electric parts.
cable.

• There is risk of fire or electrical shock. • There is risk of fire and electric shock. • It may cause There is risk of fire, fail-
ure of the product, or electric shock.

4 Free Joint Multi Air Conditioner


Safety Precautions

Do not store or use flammable gas or com- If strange sounds, or smell or smoke comes
bustibles near the product. from product. Turn the breaker off or discon-
nect the power supply cable.
• There is risk of fire or failure of product. • There is risk of electric shock or fire.

Gasolin

Do not open the inlet grille of the product dur- Be cautious that water could not enter the
ing operation. (Do not touch the electrostatic product.
filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product fail- • There is risk of fire, electric shock, or product damage.
ure.

Service Manual 5
Safety Precautions

CAUTION
■ Installation
check for gas (refrigerant) Install the drain hose to Keep level even when
leakage after installation or ensure that water is drained installing the product.
repair of product. away properly.
• Low refrigerant levels may cause fail- • A bad connection may cause water • To avoid vibration or water leakage.
ure of product. leakage.

90˚

■ Operational
Use two or more people to lift Use a soft cloth to clean. Do Do not touch the metal parts
and transport the product. not use harsh detergents, sol- of the product when removing
vents, etc. the air filter. They are very
sharp!
• Avoid personal injury. • There is risk of fire, electric shock, or • There is risk of personal injury.
damage to the plastic parts of the prod-
uct.

x
Wa Thinner

Do not step on or put anyting on the product. Do not insert hands or other objects through
(outdoor units) the air inlet or outlet while the product is oper-
ated.
• There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause personal
injury.

6 Free Joint Multi Air Conditioner


Details of LG Model Name

Details of LG Model Name


Indoor Unit
LMN C 12 6 L R L 0

Serial Number
Function
A : Basic, L : Nano Plasma + Auto Clean(Wall Mounted)
C: Plasma(Ceiling Cassette), G: Low Static Motor
Art Cool Deluxe Type Front Panel Color
B: Blue, D: Wood, M: Metal, R: Mirror, W: White

Chassis Name

Indoor Unit Type


L : Wall Mounted T : Ceiling Cassette
B : Ceiling Concealed Duct D : Art Cool Deluxe
P : Floor Standing

Electrical Rating
6: 1Ø, 220~240V, 50Hz

Nominal Heating or Cooling Capacity in Btu/h


Ex) 12,000 Btu/h '12', 18,000Btu/h '18'
Model Type
C : Cooling Only

MPS Variable Multi System Indoor Unit

Outdoor Unit
L4U C 48 8 F A 0

0 : right type, 1 : left type

Function
A : Basic

Multi Type
F : Free Joint Multi Type

Electrical Ratings
8 : 3Ø, 220V, 50Hz

Nominal Cooling Capacity in Btu/h


Ex) 48,000 Btu/h '48'

Model Type
C : Cooling Only

R22 MPS Variable Multi System Outdoor Unit.


And No. of Connectable Indoor Units
Ex) L4U : Connectable max. 4 Indoor Units

Service Manual 7
Product Specifications

Product Specifications
1. Outdoor
Model L4UC488FA0
Cooling Capacity ★ Btu/hr 48,000
W 14,067
kcal/hr 12,096
Input ★ Cooling/Heating W 5,000
Running Current ★ Cooling/Heating A 10
Starting Current ★ Cooling/Heating A 14
Power Supply Ø,V,Hz 3,380~415,50
Compressor Type Rotary
O.L.P Type(model name) internal
Refrigerant charge Charge g(oz) 4000(141.1) "at 7.5m"
Type R22
Control L.E.V
Coil Tube Size (OD) inch(mm) 0.276(7.0)
Fins per inch 18
No. of Rows & Column/No. 2R,52C
Fan motor Model IC28640LG28J
Output W 120 * 2
Capacitor µF/Vac 6/370
Air Circulation Outdoor CMM(CFM) 53(1872) *2
Noise Level(H/L) Sound Press,1m dB(A)±1 58/54
SVC Valve Liquid inch(mm) 1/4 (6.35)*4EA
Gas 3/8 (12.7)*4EA
Dimensions W*H*D inch(mm) 35.4*45.8*14.5 (900*1,165*370)
Net Weight Outdoor kg(lbs) 105(231)
Power Supply Cable No.* mm2 4*5.0
Interunit Cable No.* mm2 4*0.75 (Includes earth)

Notes:-
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notification.
4. ★ : See the page "Combination Table"

8 Free Joint Multi Air Conditioner


Product Specifications

2. Indoor
Indoor Unit Type Wall Mounted Art Cool
Model LMNC096LRL0 LMNC126LRL0 LMNC186LTL0 LMNC096DUR0 LMNC126DUR0 LMNC186D3R0
kcal/hr(W) 2267(2638) 3024(3517) 4536(5275) 2267(2638) 3024(3517) 4536(5275)
Nominal Cooling Capacity ★
Btu/hr 9,000 12,000 18,000 9,000 12,000 18,000
Air Circulation H/M/L CMM(CFM) 8.5(300) 9.0(318) 13(460) 8.5(300) 9.0(318) 13(460)
Setting temperature range(cool) °C 18~30 18~30 18~30 18~30 18~30 18~30
Output W 14.4 14.4 22 7.8 7.8 25.6
Fan motor
Capacitor µF/Vac 0.9/400 0.9/400 2.0/370 0.9/400 0.9/400 2/370
Noise Level
H/M/L dBA 35/33/31 39/36/34 42/39/36 36/32/29 37/33/31 40/38/36
(Sound Press,1.5m)
Temperature controller Thermistor Thermistor Thermistor Thermistor Thermistor Thermistor
Dehumidification Rate l/h 1.4 1.8 2 1.2 1.5 2
Dimensions (W*H*D) Body inch(mm) 35.4*11.2*6.1(900*285*156) 35.4*11.2*6.1(900*285*156) 42.9*12.4*6.8(1090*314*172) 40.6*11.4*6.0(1030*290*153) 40.6*11.4*6.0(1030*290*153) 46.1*24.4*6.81(1170*315*173)
Net Weight Body kg(lbs) 8(17.6) 8(17.6) 12(26.5) 9.5(20.9) 9.5(20.9) 13(28.7)
Liquid inch(mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)
Piping Connection Gas inch(mm) 3/8 (9.52) 1/2 (12.7) 1/2 (12.7) 3/8 (9.52) 1/2 (12.7) 1/2 (12.7)
Drain hose (ID Ø) mm 20 20 20 20 20 20

Indoor Unit Type PAC


Model LMNC246PRC2 LMNC286PRC2 LMNC346PRC2
kcal/hr(W) 6048(7034) 7056(8260) 8568(9964)
Nominal Cooling Capacity
Btu/hr 24,000 28,000 34,000
Air Circulation H/M/L CMM(CFM) 18.5/14/12/8(653/494/424) 20/16.5/13/8(706/583/459/283) 21/18/15.5/6(742/636/547/212)
Setting temperature range(cool) °C 18~30 18~30 18~30
Output W 47.4 102 82.8
Fan motor
Capacitor µF/Vac 2.5/440 4/450 2.5/440
Noise Level
H/M/L dBA 46/45/44 48/47/46 50/49/48
(Sound Press,1.5m)
Temperature controller Thermistor Thermistor Thermistor
Dehumidification Rate l/h 2.1 3.2 3.8
Dimensions (W*H*D) Body inch(mm) 22.4*71.7*12.5(570*1,820*317) 22.4*71.7*12.5(570*1,820*317) 22.4*71.7*12.5(570*1,820*317)
Net Weight Body kg(lbs) 36(79) 36(79) 36(79)
Liquid inch(mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)
Piping Connection Gas inch(mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Drain hose (ID Ø) mm 16 16 16

Notes:-
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notification.
4. ★ : See the page "Combination Table"

Service Manual 9
Combination Table

Combination Table
L4UC488FA0

Cooling
Operation Combimation of Indoor unit(k Btu/h)
Each Capacity Input Current
Unit Unit-A Unit-B Unit-C Unit-D Total Unit-A Unit-B Unit-C Unit-D Total (W) (A)
9 9 10 10 2200 4.1
12 12 12 12 2300 4.2
18 18 18 18 2400 4.4
1 UNIT 24 24 24 24 2500 4.5
28 28 28 28 4600 8.3
34 34 34 34 4600 8.4
9 9 18 9 9 18 2400 4.5
9 12 21 9 12 21 2500 4.6
12 12 24 12 12 24 2600 4.7
9 18 27 9 18 27 4500 8.5
12 18 30 12 18 30 4700 8.6
9 24 33 9 24 33 4700 8.6
12 24 36 12 24 36 4800 8.6
18 18 36 18 18 36 4800 8.8
2 UNIT 9 28 37 9 28 37 4800 8.6
12 28 40 12 28 40 4900 8.7
18 24 42 18 24 42 4900 8.9
9 34 43 9 34 43 4900 8.6
12 34 46 12 34 46 4900 8.7
18 28 46 18 28 46 5000 8.9
24 24 48 24 24 48 5000 8.9
18 34 52 18 34 52 5100 8.9
24 28 52 24 28 52 5100 9.0
9 9 9 27 9 9 9 27 4600 8.6
9 9 12 30 9 9 12 30 4700 8.7
9 12 12 33 9 12 12 33 4800 8.8
9 9 18 36 9 9 18 36 4800 8.9
12 12 12 36 12 12 12 36 4900 8.9
9 12 18 39 9 12 18 39 4900 9.0
9 9 24 42 9 9 24 42 4900 9.0
12 12 18 42 12 12 18 42 5000 9.1
9 12 24 45 9 12 24 45 5000 9.1
3 UNIT 9 18 18 45 9 18 18 45 5000 9.2
9 9 28 46 9 9 28 46 5000 9.1
12 12 24 48 12 12 24 48 5100 9.1
12 18 18 48 12 18 18 48 5200 9.2
9 12 28 49 9 12 28 49 5100 9.1
9 18 24 51 9 18 24 51 5100 9.3
9 9 34 52 9 9 34 52 5100 9.2
12 12 28 52 12 12 28 52 5200 9.3
12 18 24 54 12 18 24 54 5200 9.4
18 18 18 54 18 18 18 54 5200 9.5
9 9 9 9 36 9 9 9 9 36 4800 9.0
9 9 9 12 39 9 9 9 12 39 4900 9.1
9 9 12 12 42 9 9 12 12 42 5000 9.2
9 9 9 18 45 9 9 9 18 45 5000 9.3
9 12 12 12 45 9 12 12 12 45 5100 9.3
4 UNIT 9 9 12 18 48 9 9 12 18 48 5100 9.4
12 12 12 12 48 12 12 12 12 48 5100 9.2
9 9 9 24 51 9 9 9 24 51 5100 9.4
9 12 12 18 51 9 12 12 18 51 5200 9.5
9 9 12 24 54 9 9 12 24 54 5200 9.5
12 12 12 18 54 12 12 12 18 54 5300 9.6

10 Free Joint Multi Air Conditioner


Dimensions

Dimensions
1. Indoor Unit
• RAC
H

D
W

Installation plate

Capacity W H D
SQ Ch. 7K/9K 824 260 156
SR Ch. 12K 900 285 156
ST Ch. 18K/24K 1080 314 182

• DCR
H

Installation plate

Pipe See Note


Drain Hose

Model W H D
LMN096DUR0
1030 290 153
LMNC126DUR0
LMNC186D3R0 1170 315 173

Service Manual 11
Dimensions

• PAC

1
1,820

570 311

No. Items
1 Control Display
2 Air outlet vent
3 Air inlet vent
4 Sliding Clean Door

12 Free Joint Multi Air Conditioner


Dimensions

2. Outdoor Unit
L4UC488FA0

L2

L1
D
L3
L10 L11 L11 L11 L11 L11 L11 L11
H

L4

Gas side
3-way valve

Liquid side
2-way valve

L9
L5

L7 L6 L8

MODEL
L4UC488FA0
DIM
W mm 870

H mm 1038

D mm 320
L1 mm 360

L2 mm 340

L3 mm 25

L4 mm 1035

L5 mm 25

L6 mm 546

L7 mm 160

L8 mm 160

L9 mm 44

L10 mm 64.5

L11 mm 50

Service Manual 13
Refrigeration Cycle Diagram

Refrigeration Cycle Diagram


L4UC488FA0

Indoor Side Outdoor Side

D C B A

Accum.
COMP A COMP B

ex) Capillary
Solenoid Valve
L.E.V
3-Way Valve
2-Way Valve

14 Free Joint Multi Air Conditioner


Wiring Diagram

Wiring Diagram
Indoor Unit
1. LMNC096LRL0, LMNC126LRL0, LMNC186LTL0

AC PCB ASM DC PCB ASM

CN-U/D CN-TH1 CN-TH2


THERMISTOR(OUT-PIPE)

CN-MOTOR
THERMISTOR(IN-PIPE)
THERMISTOR(ROOM)

ZNR

FUSE
250V 2A
CN-POWER

3854A20135W

2. LMNC096DUR0, LMNC126DUR0, LMNC186D3R0

Service Manual 15
Wiring Diagram

3. LMNC246PRC2,LMNC286PRC2,LMNC366PRC2

16 Free Joint Multi Air Conditioner


Wiring Diagram

Outdoor Unit
1. L4UC488FA0

Service Manual 17
Electronic Control Device

Electronic Control Device


Indoor Unit
LMNC096LRL0, LMNC126LRL0, LMNC186LTL0

• MAIN P.C.B AC ASM

18 Free Joint Multi Air Conditioner


Electronic Control Device

LMNC096DUR0, LMNC126DUR0, LMNC186D3R0


• MAIN PCB ASM - TOP VIEW
C03J JP32

CN_MOTOR
C04J CN_TH2
CN_L/R(BL)

JP33
JP1 CN
_U
/D
(W

JP34
7
R01J H)
4
CN_CC
FUSE 250V/T2A
SMPS
CN
_S
UC
(W
H)

JP28
CN_POWER

1 3
JP43 CN
_H

D07D
EARTH VB
(B
C05J L1 C06D L)
JP29
C06J CN
_T
H1
ZNR01J

JP58
JP40
JP39

JP44
C01J
NF02J C04D CN

JP45
_V
JP35 FD
(W
R05K H)
SD01D
D02K

JP11
C09D IC04D
C01E
NF01J JP30 NTC JP46
D01K

PCB : 6870A90120C

JP48
ZNR02J

ASM : 6871A10111
JP47
C01D

CN_CON(BL)
BZ01E

JP42
JP41
R03J

TR01J
R02J

D05D

JP49
JP31

IC01D OSC01B
Q01V
~ ~
C02A IC01A
D02D

JP56
JP12
IC1

JP55
C05D
+ -

ZD02D

JP19
IC01K IC02K

JP51
JP38

JP52

JP54
BD01D

JP53
IC02D JP50
IC01J
Q01C
IC03D

• MAIN PCB ASM - BOTTOM VIEW

JP20
R04H
C03H
R03H

JP32
CN-L/R(BL)
CN-MOTOR

C03J

CN-CH2
JP33

H) C04J
(W
/D
-U
CN
JP27

JP1
CN-CC
JP5

R01J
JP34

R24G

R23G

R22G

R21G

IC01M IC04M
H)
(W
UC
-S FUSE
L) CN
B(B
JP57

V 250V/T2A
-H
JP28

CN
IC02M
CN-POWER

EARTH
C01F

JP43
D07D

C06J
H1 SMPS C05J
-T
CN
L1
JP4

C06D JP29
R02F
R01F

C10D

ZNR01J
H)
JP58

(W
FD
JP44

-V
JP39

CN JP35
JP40

C01J
JP45

C07D

NF02J
C04V

C04D
R04V
JP3

MICOM SD01D
D02K

C03V C01E
JP30
50
R02H
R01H
R05H
R03V

45

C08D
JP16

ZNR02J
IC04D

C01D
55

NTC
JP48

40

Q02E
R03E

JP46 C09D

JP47
C02H
Q03E

Q01E
C01L R01E
R02E
R02L
JP25

NF01J
R06H
C01H

R03K
R21H
R23H
R22H
CN-CON(BL)

D01K

TR01J
JP9
JP2
1

R03J
30
JP49

R02J
R04E
JP24

JP26

D05D
C02D
R01B

JP31

IC01D
25

R01L
10
OR1H
OR3H

JP8
R02G

R05V
R06V
20

JP18

JP15

R05K
15

R01A C01A
JP41

JP10

OR2H
R05D

IC02K
JP42

IC01K
BC01D
Q01V

JP17

R04J

C05D
Q01K
C01G
R01G

IC01J
D02D
C01X

JP19

Q02V

JP37
R08D

IC02D
L02X
JP12

JP56

L01X

IC01A R01P IC03D


R06D

JP14 R02A
JP55

R03D
R02D

JP50
R02K
R04K
ZD02D
Q01C
R07D

IC1
JP38

JP36
JP21

JP22
JP54

JP53

JP23
JP51
JP52

R04D JP13 JP7 JP6 C01K R01K

Service Manual 19
Electronic Control Device

LMNC246PRC2, LMNC286PRC2, LMNC366PRC2


• MAIN PCB ASM

20 Free Joint Multi Air Conditioner


Electronic Control Device

Outdoor Unit
L4UC488FA0
• MAIN P.C.B ASM

All of M/S SW 1, 2, 3, 4 must be on 'M'

Display P.C.B ASM

Art Cool Deluxe Type


TOP VIEW
SEJIN ELECTRON INC. SVM-GP1119AI P/N 3210018043 REV1 R7
R8 R17 R9 Q2

R5
D1 C18 1
C13 TP1
C20

C8 R10 Q1
C9 R13

M43 TP2
C19
TP3
TP4
R3 R4
C7 R18
C21
M44 M42 TP5
M45 R19
R2 R6 TP6

C15 C14

BOTTOM VIEW

TP1
TP2

TP3
TP4

TP7
TP8

Service Manual 21
Schematic Diagram

Schematic Diagram
Indoor Unit
1. LMNC096LRL0, LMNC126LRL0, LMNC186LTL0

22 Free Joint Multi Air Conditioner


Schematic Diagram

2. LMNC096DUR0, LMNC126DUR0, LMNC186D3R0

Service Manual 23
Schematic Diagram

3. LMNC246PR30, LMNC286PR30, LMNC366PR30

24 Free Joint Multi Air Conditioner


Schematic Diagram

Outdoor Unit
• L4UC488FA0

Service Manual 25
Functions

Functions
Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature


• Room temperature sensor. (THERMISTOR)

Room temperature control

• Maintains the room temperature in accordance with the Setting Temp.

Starting Current Control


• Indoor fan is delayed for 5 sec at the starting.

Time Delay Safety Control

• Restarting is inhibited for approx. 3 minutes.

Indoor Fan Speed Control


• High, Med, Low, CHAOS, JET COOL

Operation indication Lamps (LED)

• Refer to 37 page signal receptor.

Soft Dry Operation Mode


PLASMA
• Intermittent operation of fan at low speed.
• The function will be operated while in any
Sleep Mode Auto Control operation mode with selecting the function.
• The function is to be stopped while it is
• The fan is switched to low(Cooling), med(Heating) speed. operating with selecting the function.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic
• Both the indoor and outdoor fan stops dur-
• The fan is switched to intermittent or irregular operation ing defrosting.
• The fan speed is automatically switched from high to low speed.
Hot-start Control (Heating)
Airflow Direction Control
• The indoor fan stops until the
• The louver can be set at the desired position or swing evaporator pipe temperature will be reached
up and down automatically. at 28°C.

26 Free Joint Multi Air Conditioner


Functions

Remote Controller

Operation ON/OFF

Operation Mode Selection


Cooling Operation Mode.( ) Auto Operation Mode.( )
(Cooling
model only) Healthy Dehumidification Operation Mode.( )

Fan Speed Selection

(Low) (Med) (High) (CHAOS)

Room, Temperature Display


: (High: 39°C LOW : 11°C)

Temperature Setting
TEMPERATURE HIGH LOW Down to 18°C
Cooling
Up to 30°C

JET COOL

Setting the Time or Timer

Timer Selection
ON OFF
: OFF, ON, OFF ON

Timer Setting
SET

Timer Cancel
CANCEL
: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation
: 1, 2, 3, 4, 5, 6, 7, Off Timer

Airflow Direction Control

Fan Operation Mode

: Fan Operates without cooling or heating.

Reset

Service Manual 27
Functions

Art Cool Deluxe Type Remote Controller

Operation ON/OFF

Operation Mode Selection


Cooling Operation Mode.( ) Auto Operation Mode.( )
(Cooling
model only) Healthy Dehumidification Operation Mode.( )
Fan Speed Selection

(Low) (Med) (High)

Room, Temperature Checking


: (High:39°C Low:11°C)
Temperature Setting
TEMPERATURE LOW HIGH

Cooling Down to 18°C Heating Down to 16°C


Up to 30°C Up to 30°C
JET COOL

Setting the Time or Timer

Timer Selection
: OFF, ON, OFF ON
ON OFF

Timer Setting

SET

Timer Cancel
CANCEL
: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation
: 1, 2, 3, 4, 5, 6, 7, Off Timer

Airflow Direction Control


2nd F

Air Circulation
Reset
: Fan Operates without cooling or heating.
Horizontal Airflow Direction Control Button(Optional)

28 Free Joint Multi Air Conditioner


Functions

Floor Standing Type Remote Controller

1. START/STOP BUTTON
Operation starts when this button is pressed
and stops when the button is pressed again.
2. ROOM TEMPERATURE SETTING
BUTTONS
Used to select the room temperature.
3. INDOOR FAN SPEED SELECTOR
Used to select fan speed in three steps low,
high, super high.
4 5 4. TURBO-Z
Used to start or stop the speed
3 1 cooling. (Speed cooling operates
2 super high fan speed in cooling mode.)
ON OFF 5. PLASMA AIRPURIFYING BUTTON
6 9 6. ON/OFF TIMER BUTTONS
7 10 Used to set the time of starting and stopping
SET CANCEL
operation.
8
7. TIME SETTING BUTTONS
13 12 Used to adjust the time.
14 8. TIMER SET/CANCEL BUTTONS
11
Used to set the timer when the desired time is
obtained and to cancel the Timer operation.
9. SIMPLE OFF TIMER SET BUTTON
Each time the button is pressed, the mode is
Flip-up door
changed in the following process.
(closed)
Time set (0, 1, 2, 3, 4, 5, 6, 7 hrs)
If you select "0", Timer function will be Cancel.
Cooling Operation
10. ENERGY SAVING OPERATION BUTTON
11. RESET BUTTON
Used prior to resetting time or after replacing
Auto Operation
batteries.
12. AUTO AIRFLOW DIRECTION CONTROL
Soft dry operation
BUTTON
The horizontal louvers swing up and down.
13. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
Cooling,Auto-operation,Soft dry Operation
14. AUTO AIRFLOW DIRECTION CONTROL
BUTTON
The vertical louvers swing right and left.

Service Manual 29
Operation Details

Operation Details
Main Unit Function
1) C/O Model
Operation Indicator
• On while in appliance operation, off while in appliance pause
• Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)

Sleep Timer Indicator


• On while in sleep timer mode, off when sleep timer cancel or appliance operation pause

Timer Indicator
• On while in timer mode (on/off), off when timer mode is completed or canceled.

Comp. Running Incidator


• While in appliance operation, on while in outdoor unit compressor running, off while in compressor off

■ Cooling Mode Operation


• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp ➲ Setting Temp+0.5°C
Compressor OFF Temp ➲ Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While in compressor
not running, operating with the low airflow speed regardless of the setting.

■ Healthy Dehumidification Mode


• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp ➲ 25°C
24°C ≤ Intake Intake Air Temp<26°C ➲ Intake Air Temp-1°C
18°C ≤ Intake Intake Air Temp<24°C ➲ Intake Air Temp-0.5°C
Intake Air Temp<18°C ➲ 18°C

• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp. ➲ Setting Temp+0.5°C
Compressor OFF Temp. ➲ Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

30 Free Joint Multi Air Conditioner


Operation Details

■ Fuzzy Operation (C/O Model)


• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C
Compressor OFF Temp ➲ Setting Temp + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp ➲ 25°C
24°C ≤ Intake Air Temp < 26°C ➲ Intake Air Temp + 1°C
22°C ≤ Intake Air Temp < 24°C ➲ Intake Air Temp + 0.5°C
18°C ≤ Intake Air Temp < 22°C ➲ Intake Air Temp
Intake Air Temp<18°C ➲ 18°C

• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the
temperature.

3. Display Ass'y

Service Manual 31
Operation Details

■ Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

■ Off-Timer ↔ On-Timer Operation


• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.

■ Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli-
ance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C. After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.

■ Chaos Swing Mode


• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are
fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.

< Cooling Mode >


CLOSED

OPEN

■ Chaos Natural Wind Mode


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.

32 Free Joint Multi Air Conditioner


Operation Details

■ Jet Cool Mode Operation (C/O Model)


• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

■ Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.

Cooling Model

Operating mode Cooling


Indoor FAN Speed High
Setting Temperature 22°C

• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.

■ Test operation
• During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-
perature and resets in 18±1 minutes.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, open the front panel upward and Press the power button let it be pressed for
about 3 seconds.
• If you want to stop the operation, re-press the button.
■ Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.

■ Air Cleaner Operation


• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.

Service Manual 33
Operation Details

■ Remote Control Operation Mode


• When the remote control is selected by the slide switch on the main unit, the appliance operates according to
the input by the remote control.

■ Protection of the evaporator pipe from frosting


• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool-
ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor
evaporator pipe from frosting.
• When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the
outdoor fan is turned on according to the condition of the room temperature.

■ Buzzer Sounding Operation


• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
• When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the
remote control signal cannot be received.

34 Free Joint Multi Air Conditioner


2-way, 3-way Valve

2-way, 3-way Valve


2-way Valve (Liquid Side) 3-way Valve (Gas Side)

Valve cap
Hexagonal wrench
(4mm) Open position
Flare nut Flare nut Closed position
Open position
Closed position Pin

To To
piping piping Service Service
connection connection port cap port
To outdoor unit To outdoor unit

Works Shaft position Shaft position Service port

Closed Closed Closed


Shipping
(with valve cap) (with valve cap) (with valve cap)

Pumping down Closed Open Open


1.
(Transfering) (clockwise) (counter-clockwise) (connected manifold gauge)

Evacuation Open
2. Open Open
(Servicing) (with charging cylinder)

Gas charging Open


3. Open Open
(Servicing) (with charging cylinder)

Pressure check Open


4. Open Open
(Servicing) (with charging cylinder)

Gas releasing Open


5. Open Open
(Servicing) (with charging cylinder)

Service Manual 35
2-way, 3-way Valve

(1) Pumping down

Indoor unit Liquid side

Close Outdoor unit


2-Way
valve

Gas side

Open
3-Way
valve

Indoor unit Liquid side

Close
2-Way
valve

Gas side

Open
3-Way
valve

manifold gauge

Low-
handle
(CLOSE) Hi- handle
(CLOSE)

• Procedure
1. Confirm that both the gas side and liquid side 6. Operate the air conditioner at the cooling cycle
valves are set to the open position. and stop it when the gauge indicates 1kg/cm g.
2

- Remove the valve stem caps and confirm that 7. Immediately set the gas side valve to the closed
the valve stems are in the raised position. position.
- Be sure to use a hexagonal wrench to operate - Do this quickly so that the gauge ends up indi-
the valve stems. cating 1kg/ g.
2. Operate the unit for 10 to 15 minutes. 8. Disconnect the charge set, and mount the liquid
side and gas side valve caps and the service
3. Stop operation and wait for 3 minutes, then con-
port nut.
nect the manifold gauge to the service port of
- Use torque wrench to tighten the service port
the gas side valve.
nut to a torque of 1.8kg.m.(4.2kg*m/5.5kg*m)
- Connect the hose of the gauge with the push
pin to the service port. - Be sure to check for gas leakage.
4. Air purging of the charge hose.
- Open the Low-handle valve on the gauge
slightly to air purge from the hose.
5. Set the liquid side valve to the closed position.

36 Free Joint Multi Air Conditioner


2-way, 3-way Valve

(2) Evacuation
(All amount of refrigerant leaked)

Indoor unit Liquid side

Open Outdoor unit


2-Way
valve

Gas side

Open
3-Way
valve

Indoor unit Liquid side

Open
2-Way
valve

Gas side

Open
3-Way
valve

manifold gauge

Vacuum pump
Low-
handle
(OPEN) Hi- handle
(OPEN)

• Procedure
1. Confirm that both the liguid side valve and gas 7. Disconnect the charge hose from the vacuum
side valve are set to the opened position. pump.
- Vacuum pump oil.
2. Connect the vaccum pump to the center hose of If the vacuum pump oil becomes dirty or deplet-
the manifold gauge. ed,replenish as needed.
3. Connect the service port of the gas side valve to 8. Mount the valve caps and the service port caps.
the low side of the gauge.
4. Connect power supply to outdoor unit.
5. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved
toward-76 cmHg (vacuum of 4 mmHg or less).
6. Close the Low handle of the gauge turn off the
vacuum pump, and confirm that the gauge nee-
dle does not move(approximately 5 minutes
after turning off the vacuum pump).

Service Manual 37
2-way, 3-way Valve

(3) Gas Charging


(After Evacuation)

Indoor unit Liquid side

Open Outdoor unit


2-Way
valve

Gas side

Open
3-Way
valve

Indoor unit Liquid side

Open
2-Way
valve

Gas side

Open
3-Way
valve

Charging manifold gauge


cylinder

Low-handle
Check valve (OPEN) Hi- handle
(OPEN)

• Procedure
1. Connect the gauge to the charging cylinder. 4. Immediately disconnect the charge hose from
- Connect the charge hose which you disconnect- the gas side valve's service port.
ed from the vacuum pump to the valve at the
This is different from previous procedures.
bottom of the cylinder.
Because you are charging with liquid refrigerant
- If you are using a gas cylinder, also use a scale
from the gas side, absolutely do not attempt to
and reverse the cylinder so that the system can
charge with larger amounts of liquid refrigerant
be charged with liquid.
while operating the air conditioner.
2. Purge the air from the charge hose.
- Open the valve at the bottom of the cylinder and - Stopping partway will allow the gas to be dis-
press the check valve on the charge set to purge charged.
the air. (Be careful of the liquid refrigerant). The - If the system has been charged with liquid
procedure is the same if using a gas cylinder. refrigerant while operating the air conditioner
3. Open the low handle on the gauge and charge turn off the air conditioner before disconnecting
the system with liquid refrigerant. the hose.
- If the system can not be charged with the speci- 5. Mount the valve stem nuts and the service port
fied amount of refrigerant, it can be charged nut.
with a little at a time (approximately 150g each - Use torque wrench to tighten the service port
time) while operating the air conditioner in the nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
cooling cycle; however, one time is not suffi- - Be sure to check for gas leakage.
cient, wait approximately 1 minute and then
repeat the procedure(pumping down-pin).

38 Free Joint Multi Air Conditioner


Cycle Troubleshooting Guide

Cycle Troubleshooting Guide


Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current.

Temp. difference : approx. 0°C All amount of refrigerant leaked out.


Current : less than 80% of Check refrigeration cycle.
rated current

Temp. Difference
Temp. difference : approx. 8°C Refrigerant leakage
Current : less than 80% of Clog of refrigeration cycle
rated current Defective compressor

Operating Current
Temp. difference : less than 8°C
Excessive amount of refrigerant
Current : near the rated
current

Temp. difference : over 8°C Normal

Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.

2. Check temperature and pressure of refrigeration cycle.

Suction pressure Temperature


(Compared with (Compared with Cause of Trouble Description
the normal value) the normal value)

High Defective compressor Current is low.


Higher
Excessive amount of High pressure does not quickly
Normal
refrigerant rise at the beginning of operation.

Insufficient amount of
Lower Higher refrigerant(Leakage) Current is low.
Clogging

Notice:
1. The suction pressure is usually 8~12 kg/cm G at normal condition.
2

2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.

Service Manual 39
Cycle Troubleshooting Guide

1) Comp basic step.

Free joint outdoor unit has two compressor (MPS: Multi power system)

Step Step 0 Step 1 Step 2 Step 3 Step 4


Operating Comp. Off 1 1 2 2
By-pass Off On Off On Off

If overload Max. capacity, display error code in indoor unit.

2) Capacity Vs Step
Q2 = 0 Q2 ≤ 12k Q2 ≤ 24k Q2 ≤ 36k 36k < Qs
Step Step 0 Step 1 Step 2 Step 3 Step 4
cf) Max. Capacity : 54k

40 Free Joint Multi Air Conditioner


Electronic Parts Troubleshooting Guide

Electronic Parts Troubleshooting Guide


1. The Outdoor Unit does not operate at all

NO
Does the Operating LED of indoor unit blink
Refer to the self-diagnosis function.
when Operation’s ON?

NO

NO
Is the Connection between CN-Power of indoor
Check the connecting state of connector
unit and terminal block?

YES

NO
Indoor Outdoor
Is the connection of cable between indoor and
outdoor unit ringht? 1(L)(Brown) 1(L)(Brown)
2(N)(Blue) 2(N)(Blue)
(Green/YL) (Green/YL)
YES
3(Red) 3(Red)

NO
Is the voltage of CN-POWER in outdoor
Check the main power
PCB Ass’y about AC220V / 240V?

YES

Check the Fuse of outdoor PCB Ass’y.


Chek the connecting state of wires

NO

Replace the PCB Ass’y.

* TPS units start at three minutes after main power turning on.

Service Manual 41
Electronic Parts Troubleshooting Guide

2. The product is not operate with the remote controller.

Turn on Main Power

While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.

When the compressor stopped Indoor Fan is driven by a low speed.


At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the
low speed by force.)

Caused by the remote controller Caused by other parts except the remote controller

When the mark( ) is displayed in LCD screen, replace


Check the contact of CN-DISP1 connector.
battery.

When the detect switch(double key) inside the remote


Check DISP PWB Ass'y
controller door is fault, it is impossible to operate
- Voltage between CN DISP1 - : DC +5V
temperature regulating( / ) and wind speed selecting.

Replace remote controller Check point

• Check the connecting circuit between PIN -


R01L(1K) - C01L(680PF) - MICOM PIN
• Check Receiver Ass'y

42 Free Joint Multi Air Conditioner


Electronic Parts Troubleshooting Guide

3. When cooling does not operate

Turn on Main Power

Operate "Cooling Mode( )" by setting the desired temperature of the


remote controller is less than one of the indoor temperature by 1°C at least.

When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.

Check the sensor for indoor temperature is attached as close as to be


effected by the temperature of Heat Exchanger(EVA).

When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.

• Check the indoor temperature sensor is disconnected or not(About 10kΩ / at 25°C).

Check Relay(RY - COMP) for driving compressor.

• When the power(About AC220V/240V) is applied to the connecting wire


terminal support transferred to compressor, PWB Ass'y is normal.
• Check the circuit related to the relay.
Check point COMP ON COMP OFF

Between two pin of DC Below DC 1V


part in relay for COMP About DC12V
(app)

Service Manual 43
Electronic Parts Troubleshooting Guide

4. When indoor Fan does not operate

Turn off Main power

Check the connection of CN-FAN or CN-MOTOR

Check the Fan Motor

Check the Fuse(AC250V/T2A)

Check the related circuit of indoor Fan Motor.

• The pin of Micom, and the part for driving SSR


• Check the pattern
• Check the SSR
- SSR Open: Indoor Fan Motor never operate
- SSR short: Indoor Fan Motor always operates in case of ON or OFF.

Turn ON Main Power

Check the SSR high speed operation by remote control.


(The Indoor Fan Motor is connected)

The voltage of PIN NO 1(blue) and 3(yellow) of CN-FAN or CN-MOTOR.

About AC 160V over About AC 50V over

SSR is not damaged SSR Check

44 Free Joint Multi Air Conditioner


Electronic Parts Troubleshooting Guide

5. When Vertical Louver does not operate


• Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands Normal

• Check the connecting condition of CN-U/D Connector


• Check the soldering condition(on PWB) of CN-U/D Connector

Check the operating circuit of the Vertical Louver

• Confirm that there is DC +12V between pin (RED) of CN-U/D and


GND.

If there are no problems after above checks

• Confirm the assembly conditions that are catching and interfering parts
in the rotation radial of the Vertical Louver

Service Manual 45
Troubleshooting Guide

Self-diagnosis Function
■ Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
Indoor Error
MPS LED 1 LED 2 Indoor
Error code Description Variable (Red) (Green) Status
00 No Error ON
01 Indoor Room themistor error 1time OFF
02 Indoor in-piping sensor error 2times OFF
03 Remote controller error 3times OFF
04 Drain Pump error 4times OFF
05 Communcation error between in and out 5times OFF
06 Indoor Out-Piping sensor error 6times OFF
07 Differnt mode operation 7times OFF

Outdoor Error
MPS LED 1 LED 2 Indoor
Error Code Description Variable (Red) (Green) Status
21 DC Peak (IPM Fault) 2times 1time OFF
22 CT 2(Max CT) 2times 2times OFF
23 DC Link Low Volt. 2times 3times OFF
24 L_P/Heater Sink 2times 4times OFF
25 Low voltage / Over voltage 2times 5times OFF
26 DC Comp Position Error 2times 6times OFF
27 PSC Fault Error 2times 7times OFF
28 DC Link High Volt 2times 8times OFF
32 D-Pipe High (INV) 3times 2times OFF
33 D-Pipe High (Normal) 3times 3times OFF
40 CT Sensor (Open/Short) 4times O OFF
41 INV. D-PipeTh Error(Open/Short) 4times 1time OFF
44 Outdoor air Th Error(Open/Short) 4times 4times OFF
45 Cond. Pipe Th Error(Open/Short) 4times 5times OFF
46 Suction Pipe Error(Open/Short) 4times 6times OFF
47 Const D-pipe Th Error(Open/Short) 4times 7times OFF
51 Capacity over 5times 1time OFF
54 Riversed phase 5times 3times OFF
60 EEPROM Check Sum Error 6times O OFF
61 Cond. Pipe High 6times 1time OFF
62 Heatsink High 6times 2times OFF
63 Cond. Pipe Low 6times 3times OFF
65 Heatsoml Th error (Open/Short) 6times 5times OFF

46 Multi type Air Conditioner


Troubleshooting Guide

General Information
■ Error Indicator (Indoor)
• The function is to self-diagnosis air conditioner and express the troubles if there is any trouble.
• Error mark is displayed on display window of indoor units and wired-remote controller, and LED of outdoor unit
control board.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurs, if error is released, error LED is also released simultaneously.

1 digit 10 digit

■ Indoor Error

Error Indoor
Contents Case of error
code Status
01 Air sensor (open/short) Open / Short Off
02 Inlet pipe sensor Open / Short Off
03 Communication(Indoor ↔ Wired R/Control) Communication Poorly Off
04 Drain pump/ Float switch Float switch Open Off
05 Communication(Indoor ↔ Outdoor) Communication Poorly Off
06 Outlet pipe sensor Open / Short Off
07 Different operation mode Different operation mode Off

Service Manual 47
Troubleshooting Guide

■ Error Indicator (Outdoor)


Outdoor Error

Error LED01G LED02G Outdoor


Contents (Green) Case of error Status
code (Red)
33 Discharge Pipe Temp. High(cons.) 3 times 3 times Off Off

44 Air sensor (open/ short) 4 times 4 times Open / Short Off

45 Cond. Pipe sensor (open/ short) 4 times 5 times Open / Short Off

46 Suction pipe sensor (open/ short) 4 times 6 times Open / Short Off

47 D-pipe sensor Cons. (open/ short) 4 times 7 times Open / Short Off

51 Over capacity 5 times 1 times Over load combination Off

54 Reiversed phase (Voltage) 5 times 4 times Off Off

48 Multi type Air Conditioner


Troubleshooting Guide

1) Troubleshooting CH01, CH02, CH06

Display
Title Cause of error Check point & Normal condition
code
• Open / Short
Indoor air sensor • Soldered poorly Normal resistor : 10KΩ/ at 25°C (Unplugged)
01
• Internal circuit error Normal voltage : 2.5Vdc / at 25°C (plugged)

• Open / Short
Normal resistor : 5KΩ/ at 25°C (Unplugged)
02 Indoor inlet pipe sensor • Soldered poorly
Normal voltage : 2.5Vdc / at 25°C (plugged)
• Internal circuit error

• Open / Short
Normal resistor : 5KΩ/ at 25°C (Unplugged)
06 Indoor outlet pipe sensor • Soldered poorly
Normal voltage : 2.5Vdc / at 25°C (plugged)
• Internal circuit error

10kΩ 2.5Vdc

Ω V

Check the resistance Check the voltage

Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10KΩ/ 5KΩ at 25°C, then sensor is normal.
4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. → Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25°C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. → Repair or Change the PCB.

Service Manual 49
Troubleshooting Guide

2) Troubleshooting CH03

Display
Title Cause of error Check point & Normal condition
code
• Connection of wire
Communication • Open / Short • Main PCB Volt. DC12V
03
Wired R/C • Wrong connection • Noise interference

Wired R/C Indoor Unit


CN-REMO
12V S GND 12V S GND

12Vdc 12Vdc

V V

Check the Volt. Check the Volt.

Check Point
1. Check the wire connection. (Open / Short) → Repair the connection
2. Check the soldering state of connector. (Soldered poorly) → Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V, DC 5V) → Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) → Adjust the state of installation

50 Multi type Air Conditioner


Troubleshooting Guide

3) Troubleshooting CH04

Display
Title Cause of error Check point & Normal condition
code
• The connection of wire(Drain pump/ Float switch)
Drain pump • Float switch Open. • Drain pump power input. (220V)
04
/ Float switch (Normal : short) • Drain tube installation.
• Indoor unit installation. (Inclination)

CN Float

CN-D/PUMP
CN-Float
0Ω

Check the resistance

Check Point
1. Check the wire connection. (Open, Soldered poorly) → Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) → Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) → Repair or Change the main PCB.

Service Manual 51
Troubleshooting Guide

4) Troubleshooting CH05

Display
Title Cause of error Check point & Normal condition
code
• Power input AC 220V. (Outdoor, Indoor)
• The connector for transmission is disconnected.
• The connecting wires are misconnected.
05 Communication
• Communication poorly • The GND1,2 is not connected at main GND.
(Indoor → Outdoor)
• The communication line is shorted at GND.
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.

05 M/S Switch(Outdoor PCB) • PCB • Refer 21

Check Point
1. Check the input power AC380~450V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
→ Adjust the connection of wire
→ Confirm the wire of “Live”, “Neutral”
3. Check the resistance between communication line and GND.
(Normal : Over 2MΩ)
4. Check the connector for communication is correctly
connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no
problem.
→ Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor
unit.

52 Multi type Air Conditioner


Troubleshooting Guide

5) Troubleshooting CH33

Display
Title Cause of error Check point & Normal condition
code

• Check the discharge pipe sensor for Cons.


D-pipe (Constant) • Discharge sensor
33 • Check the install condition for over load.
temp. high (Cons.) temp. high • Check the leakage of refrigerant.
(105°C )
• Check the SVC V/V open.

D-Pipe temp.

Toff(105) °C

T2(95) °C
T1(90) °C

COMP Frequency
Normal Normal OFF
(Hz)
LEV Openness Normal Normal OFF Control
(Pulse)

Check Point
• CH 33
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerant.
4. Check the constant compressor. (same with CH21)

Service Manual 53
Troubleshooting Guide

6) Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65

Display
Title Cause of error Check point & Normal condition
code
• Open / Short
44 • Normal resistor : 10KΩ / at 25°C (Unplugged)
Air sensor • Soldered poorly
• Normal voltage : 2.5Vdc / at 25°C (plugged)
• Internal circuit error

• Open / Short
45 Condenser Pipe sensor • Soldered poorly • Normal resistor : 5KΩ / at 25°C (Unplugged)
• Internal circuit error • Normal voltage : 2.5Vdc / at 25°C (plugged)

• Open / Short
Suction Pipe sensor • Soldered poorly • Normal resistor : 5KΩ / at 25°C (Unplugged)
46
• Internal circuit error • Normal voltage : 2.5Vdc / at 25°C (plugged)

• Open / Short
D-pipe sensor (Constant) • Soldered poorly • Normal resistor : 200KΩ / at 25°C (Unplugged)
47
• Internal circuit error • Normal voltage : 4.5Vdc / at 25°C (plugged)

Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance of the sensor is 0 kΩ or ∞, then sensor is abnormal.
Ω If the voltage of the sensor is 0 V or 5Vdc, then sensor is abnormal.

54 Multi type Air Conditioner


Troubleshooting Guide

7) Troubleshooting CH51, CH60

Display
Title Cause of error Check point & Normal condition
code

51 • Over capacity • Check the indoor unit capacity.


Over capacity
Combination • Check the combination table.

Check Point
• CH 51
1. Check the indoor unit capacity.

Service Manual 55
Exploded View & Replacement Parts List

Exploded View & Replacement Parts List


1. Indoor Unit
SR Chassis
135316

152313
135314

152302

131410 733010

359011

342800
159830

354210

135316

352115
159901 352116

268712
35211B 346810
263230-2 135516

352150 263230-1
135311

146811

266090 268716
267110 268715

249951 W0CZZ

56 Free Joint Multi Air Conditioner


Exploded View & Replacement Parts List

Parts List(SR chassis)

LOCATION PART No.


DESCRIPTION REMARKS
No. LMNC096LRL0 LMNC126LRL0
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006A R
135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10127A 3531A10127A R
135314 GRILLE ASSEMBLY,INLET SUB 3531A20100B 3531A20100A R
135316 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A20187M 3531A20187Q R
135516 COVER ASSEMBLY,MOTOR 3551A20050P 3551A20050P R
146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A R
152302 FILTER(MECH),A/C 5230A10005A 5230A10005A R
152313 FILTER ASSEMBLY,DEODORIZER 5231A20032C 5231A20032C R
159830 AIR CLEANER ASSEMBLY 5983A10009V 5983A10009V R
159901 VANE,HORIZONTAL 5990A10005A 5990A10005A R
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20361A 4995A20361G R
263230-1 THERMISTOR ASSEMBLY 6323AQ3226T 6323AQ3226T R
263230-2 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A R
266090 H.V ASSEMBLY 6609A10003J 6609A10003J R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20067J 6711A20067H R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20194A 6871A20194A R
268715 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20267B 6871A20267B R
268716 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20440A 6871A20440G R
342800 BEARING 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY,INDOOR 4681A20062A 4681A20062A R
35211B TUBE ASSEMBLY,TUBING 5211AR7066P 5211AR7066P R
352115 TUBE ASSEMBLY,EVAPORATOR IN 5211A20470J 5211A20470J R
352116 TUBE ASSEMBLY,EVAPORATOR OUT 5211A20471D 5211A20471D R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F R
354210 EVAPORATOR ASSEMBLY,FIRST 5421A10024A 5421A10024A R
359011 FAN ASSEMBLY,CROSS FLOW 5901A20007B 5901A20007B R
733010 PLATE ASSEMBLY,INSTALL 3301A10003A 3301A10003A R
W0CZZ CAPACITOR,DRAWING 3H01487A 3H01487A R

Service Manual 57
Exploded View & Replacement Parts List

ST Chassis

135316
267110

152313
135314

152302

131410 733010

359011

342800

159830
135311 352111

135316
159901-1
352115
159901-2 352116

268712
35211B 346810
263230-2 135516

352150 263230-1
268715
146811

249951
266090 268716

W0CZZ

58 Free Joint Multi Air Conditioner


Exploded View & Replacement Parts List

Parts List(ST chassis)


LOCATION PART No. SVC
DESCRIPTION
No. LMNC186LTL0 AMNC186LTL0 AMNH246LTL0 AMNH246LTA0 AMNC246LTL0 CODE
131410 CHASSIS ASSEMBLY 3141A10002A 3141A10002A 3141A10002A 3141A10002A 3141A10002A R
135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10116A 3531A10116A 3531A10116A 3531A10116A 3531A10116A R
135314 GRILLE ASSEMBLY,INLET SUB 3531A20107W 3531A20107V 3531A20107W - 3531A20107V R
135316 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A20207E 3531A20207F 3531A20207E 3531A24010F 3531A20207F R
135516 COVER ASSEMBLY,MOTOR 3551A20099C 3551A20099C 3551A20099C 3551A20099C 3551A20099C R
146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH),A/C 5230A20001A 5230A20001A 5230A20001A 5230A20001A 5230A20001A R
159830 AIR CLEANER ASSEMBLY 5983A10006T 5983A10006T 5983A10006T - 5983A10006T R
159901-1 VANE,HORIZONTAL 5990A20008A 5990A20008A 5990A20008A 4995A11004D 5990A20008A R
159901-2 VANE,HORIZONTAL 5990A20009A 5990A20009A 5990A20009A 5990A20009A 5990A20009A R
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20361E 4995A20361K 4995A20361F 4995A20361F 4995A20361L R
263230-1 THERMISTOR ASSEMBLY 6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T R
263230-2 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004A 6323A20004A 6323A20004A R
266090 H.V ASSEMBLY 6609A10003L 6609A10003L 6609A10003L - 6609A10003L R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20067J 6711A20067H 6711A20067J 6711A20083F 6711A20067H R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20194B 6871A20194B 6871A20194B 6871A20194B 6871A20194B R
268715 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20267B 6871A20267B 6871A20267B 6871A20267B 6871A20267B R
268716 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20440E 6871A20440L 6871A20440F 6871A20440F 6871A20440M R
342800 BEARING 4280A20004A 4280A20004A 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY,INDOOR 4681A20003D 4681A20003D 4681A20067A 4681A20067A 4681A20067A R
352111 TUBE ASSEMBLY,CONNECTOR 5211A20514B 5211A20514B 5211A20514B 5211A20514B 5211A20514B R
352115 TUBE ASSEMBLY,EVAPORATOR IN 5211A30058H 5211A30058H 5211A30097J 5211A30097J 5211A30097J R
352116 TUBE ASSEMBLY,EVAPORATOR OUT 5211A30057D 5211A30057D 5211A30098G 5211A30098G 5211A30098G R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F 5251AR2575F R
359011 FAN ASSEMBLY,CROSS FLOW 5901A20008A 5901A20008B 5901A20008A 5901A20008A 5901A20008B R
733010 PLATE ASSEMBLY,INSTALL 3301A10002A 3301A10002A 3301A10002A 3301A10002A 3301A10002A R
35211B TUBE ASSEMBLY,TUBING 5211A30439E 5211A30439E 5211A30439J 5211A30439J 5211A30439J R
W0CZZ CAPACITOR,DRAWING 3H01487G 3H01487G 3H01487G 3H01487G 3H01487G R

Service Manual 59
Exploded View & Replacement Parts List

SU, SZ, S3 chassis(Art Cool Deluxe Type)

146811 135316

152302
668713-1
146811-1

145200

668713-2

135080-1
135313 135511
263020

135080-2
263230-2 263230-1

733010

267110 359011

159830

266090 342800

352111
131410

346810

352150
352114 249951
352118
W0CZZ
35211B 266090

146811

159901
135311
268714 249941

60 Multi type Air Conditioner


Exploded View & Replacement Parts List
Parts List(Art cool Deluxe Type)

LOCATION PART No. SVC


DESCRIPTION
No. LMNC096DU*0 LMNC126DU*0 LMNC186D3*0 CODE
131410 CHASSIS ASSEMBLY 3141A20007B 3141A20007B 3141A20012A R
135080-1 DECORATION (TOP) 3508A20034E 3508A20034E - R
135080-2 DECORATION (BOTTOM) 3508A20034F 3508A20034F - R
135311 GRILLE ASSEMBLY, DISCHARGE 3531A20137B 3531A20137B 3531A20231C R
135313 GRILLE ASSEMBLY, INLET W: White - - - R
M: Metal - - - R
R: Mirror 3531A21010E 3531A21010E 3531A20232B R
B: Blue - - - R
D: Wood - - - R
C: Cherry - - - R
135316 GRILLE ASSEMBLY, FRONT W: White - - - R
M: Metal - - - R
R: Mirror 3531A21027L 3531A21027L 3531A10341A R
B: Blue - - - R
D: Wood - - - R
C: Cherry - - - R
146811 MOTOR ASSEMBLY, STEP (Vane) 4681A20055A 4681A20055A 4681A20055A R
146811-1 MOTOR ASSEMBLY, STEP (Door) 4681A20055B 4681A20055B 4681A20055D R
159830 AIR CLEANER ASSEMBLY 5983A10006T 5983A10006T 5983A10006T R
152302 FILTER (MECH), A/C 5230A20022A 5230A20022A 5230A20047A R
159901 VANE, HORIZONTAL 5990A20015B 5990A20015B 5990A20042B R
249951 CONTROL BOX ASSEMBLY 6994A20375U 6994A20375V 6994A20375W R
249941 CONTROL BOX, INDOOR 4994A20067A 4994A20067A 4994A20067A R
263020 PWB(PCB) ASSEMBLY W: White - - - R
M: Metal - - - R
R: Mirror 6871A20463P 6871A20463P 6871A20656A R
B: Blue - - - R
D: Wood - - - R
C: Cherry - - - R
263230-1 THERMISTOR ASSEMBLY (Out) 6323AQ2226T 6323AQ2226T 6323AQ3226T R
263230-2 THERMISTOR ASSEMBLY (Room, in) 6323A20004A 6323A20004A 6323A20004A R
266090 H.V ASSEMBLY 6609A10005A 6609A10005A 6609A10005D R
267110 REMOE CONTROLLER ASSEMBLY 6711A20077U 6711A20077U 6711A20077U R
268714 PWB(PCB) ASSEMBLY, MAIN 6871A20684E 6871A20684N 6871A20684P R
342800 BEARING 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY, INDOOR 4681A20048A 4681A20048A 4681A20067C R
352114 TUBE ASSEMBLY, DISTRIBUTOR 5211A202569D 5211A202569D 5211A14007A R
352118 TUBE ASSEMBLY MANIFOLD 5211A20605B 5211A20605B 5211A10474D R
35211B TUBE ASSEMBLY, TUBING 5211AR7066L 5211AR7066L 5211A30038Z R
352150 HOSE ASEMBLY, DRAIN 5251AR1222R 5251AR1222R 5251AR1222R R
354212 EVAPORATOR ASSEBLY, FINAL 5421A20105H 5421A20105H 5421A21004T R
359011 FAN ASSEMBLY, CROSS FLOW 5901A20016J 5901A20016J 5901A20017C R
668713 PWB ASSEMBLY, SUB 6871A20258B 6871A20258B 6871A20258B R
668713 PWB ASSEMBLY, SUB 6871A20259A 6871A20259A 6871A20259A R
733010 PLATE 1H00843A 1H00843A 3301A10002A R
W0CZZ CAPACITOR, DRAWING 3H01487A 3H01487A 3H01487G R

Service Manual 61
Exploded View & Replacement Parts List

PR3 chassis (Floor Standing Type)

137211

235811-1

132111

235512

235811-2

249941 267110

W0CZZ

268715 135515-2

668713

237201

135515-1

62 Free Joint Multi Air Conditioner


Exploded View & Replacement Parts List

W52103

354212 W4811-2
W4810-2

354210
W4811-1

435512

269310

35211A
35211C

130911
336610
336600 266000

352150
W4810-1

349480

337000 159830

W50400

346810

140570
W1WS 359012

W1NHA 730400

Service Manual 63
Exploded View & Replacement Parts List

Parts List(Floor Standing Type)

LOCATION PART No.


DESCRIPTION REMARKS
No. LMNC246PRC2 LMNC286PRC2 LMNC366PRC2
132111 FRAME ASSEMBLY 3210A20046A 3210A20046A 3210A20046A
135515-1 GRILLE ASSEMBLY, INLET 3531A10203R 3531A10203R 3531A10203R
153315-2 GRILLE ASSEMBLY, INLET 3531A10203S 3531A10203S 3531A10203S
435512 COVER ASSEMBLY, TOP(INDOOR) 3551A10022A 3551A10022A 3551A10022A
137211 PANEL ASSEMBLY, FRONT(INDOOR) 3721A10190A 3721A10190B 3721A10190L
140570 LOCKER ASSEMBLY 4A01405C 4A01405C 4A01405C
159830 AIR CLEANER ASSEMBLY 5983A10004S 5983A10004S 5983A10004S
235512 COVER ASSEMBLY, DISPLAY 3551A20135P 3551A20135P 3551A20135P
235811-1 DOOR ASSEMBLY, CLEAN 3581A20005V 3581A20005V 3581A20005V
235811-2 DOOR ASSEMBLY, CLEAN 3581A20006M 3581A20006M 3581A20006M
237201 PANEL, BASE 3720A10105H 3720A10105H 3720A10105H
249941 CONTROL BOX, INDOOR 4994A10042A 4994A10042A 4994A10042A
266000 SWITCH, PUSH 6600AP2059A 6600AP2059A 6600AP2059A
267110 REMOTE CONTROLLER 6711A20060A 6711A20060A 6711A20060A
268715 PWB(PCB) ASSEMBLY, MAIN(AC) 6871A10136X 6871A10136Y 6871A10136Z
269310 THERMISTOR ASSEMBLY 6323A20016A 6323A20016A 6323A20016A
336600 HOUSING (MECH), WRAPPER 3660A20023J 3660A20023J 3660A20023J
336610 HOUSING ASSEMBLY (MECH) 3661A20017S 3661A20017S 3661A20017S
337000 NET, STEEL 3700A30001A 3700A30001A 3700A30001A
346810 MOTOR ASSEMBLY, INDOOR 4681A20183A 4681A20134A 4681A20134A
349480 ORIFICE 4948A20008B 4948A20008B 4948A20008B
352150 HOSE ASSY, DRAIN 5251AR1222X 5251AR1222X 5251AR1222X
35211C TUBE ASSY, DISCHARGE (INDOOR) 5211A20854C 5211A20854C 5211A20854C
354210 EVAPORATOR ASSEMBLY, FIRST 5421A20039Q 5421A20039Q 5421A20039Q
359012 FAN ASSEMBLY, TURBO 5901A20021A 5901A20021A 5901A20021A
668713 PWB(PCB) ASSEMBLY, SUB 6871AQ3212D 6871AQ3212D 6871AQ3212D
730400 BASE, INSTALL 3040A20067B 3040A20067B 3040A20067B
753010 HEATER ASSEMBLY, ELECTRIC - - -
W0CZZ CAPACITOR, DRAWING 3H00660N 3H00660N 3H00660N
W1NHA NUT, HEXAGON 1NHA0801206 1NHA0801206 1NHA0801206
W1WS WASHER, SPRING LOCK 1WSD0800030 1WSD0800030 1WSD0800030
W4810-1 BRACKET 4810A20142A 4810A20142A 4810A20142A
W4810-2 BRACKET 4810A10008A 4810A10008A 4810A10008A
W4811-1 BRACKET ASSEMBLY 4811A30011B 4811A30011B 4811A30011B
W4811-2 BRACKET ASSEMBLY 4811A30021A 4811A30021A 4811A30021A
W50400 RUBBER 5040A30031A 5040A30031A 5040A30031A
W52103 TUBE, DISTRIBUTOR 2H00351T 2H00351T 2H00351T
35211A TUBE ASSEMBLY, SUCTION INDOOR 5211A20851C 5211A20851C 5211A20851C

64 Free Joint Multi Air Conditioner


Exploded View & Replacement Parts List

Service Manual 65
435512 658740
668711 649950 263230-1
546810
W0CCZ-1
W0CCZ-2 263230-2
669200
437212
559010
437210 447910
435301 546810
548490 554031
554160-2
552113
561411-1
554160-1
561411-2
561411-3
561411-4 352112
435511
552203-1 552114
237204 552203-2
2. Outdoor Unit

430410
552115-2
552115-1
L4UC488FA0
Exploded View & Replacement Parts List

Parts List(L4UC488FA0)

LOCATION PART No.


DESCRIPTION REMARKS
No. L4UC488FA0
430410 BASE ASSEMBLY,WELD[OUTDOOR] 3041A20047F R
554031 CONDENSER ASSEMBLY,BENT 5403A20230B R
554160-1 COMPRESSOR 2520UHLT2BA R
554160-2 COMPRESSOR - R
552112 TUBE ASSEMBLY,CONDENSER IN 5211A15004A R
552113 TUBE ASSEMBLY,CONDENSER OUT 5211A15005A R
552203-1 VALVE,SERVICE 2H02479B R
552203-2 VALVE,SERVICE 2H01890W R
552203-3 VALVE,SERVICE - R
561411 COIL ASSEMBLY,EXPANSION 6140A90001P R
263230-1 THERMISTOR ASSEMBLY 6323A20020A R
263230-2 THERMISTOR ASSEMBLY 6323A20039A R
548490 ACCUMULATOR ASSEMBLY(MECH) 4949A10048B R
552114 TUBE ASSEMBLY,DISCHARGE (OUTDOOR) 5211A16005A R
447910 BARRIER ASSEMBLY,OUTDOOR 4760AP1216L R
561411-1 COIL ASSEMBLY,EXPANSION 6141A20037A R
561411-2 COIL ASSEMBLY,EXPANSION 6141A20037B R
561411-3 COIL ASSEMBLY,EXPANSION 6141A20037C R
561411-4 COIL ASSEMBLY,EXPANSION 6141A20037D R
561411-5 COIL ASSEMBLY,EXPANSION - R
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995A20166M R
668711 PWB(PCB) ASSEMBLY,MAIN(OUTDOOR) 6871A20583U R
W0CZZ-1 CAPACITOR,DRAWING 2A00986D R
W0CZZ-2 CAPACITOR,DRAWING - R
546810 MOTOR ASSEMBLY,OUTDOOR 4681A20028J R
559010 FAN ASSEMBLY,PROPELLER 5901A10032A R
435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 3A01293X R
435512 COVER ASSEMBLY,TOP(OUTDOOR) 3550AP1213B R
437212 PANEL ASSEMBLY, REAR(OUTDOOR) 3720AP1202L R
137213-1 PANEL ASSEMBLY,SIDE - R
137213-2 PANEL ASSEMBLY,SIDE 3720AP1215E R
437214 PANEL ASSEMBLY,FRONT(OUTDOOR) - R
437210 PANEL ASSEMBLY,FRONT(OUTDOOR) 3720A1212B R
435301 GRILLE,DISCHARGE 3530AP1225D R
W49810 SUPPORTER ASSEMBLY 4981A11008A R
552115-1 TUBE ASSEMBLY,MENIFOLD(OUTDOOR) - R
552115-2 TUBE ASSEMBLY,MENIFOLD(OUTDOOR) - R

66 Free Joint Multi Air Conditioner


July, 2005
Printed in Korea
P/No.: 3828A22020B

You might also like