POWER GRID CORPORATION OF INDIA LIMITED Doc. No.

: MR/CF/CVT/02/R-2 DATED 01/04/08


CORPORATE OPERATION SERVICES Sub station: khadoli
PRE-COMMISSIONING OF POTENTIAL Bay No.: 66 kv BUS
TRANSFORMER
COMMISSIONING FORMATS Equipment Identification No.: BUS PT
Date of Testing: 19.09.2010

_____________________________________________________________________________
_

I. Region: WR-II

II. Date of Erection:09.06.2010 III. Date of Energisation: 04.10.2010

IV. Details of Equipment:

LOA No : C-32029-S248-3/LOA-1/2557 dated 19.06.2008

Make : MEHRU

Type : Out door oil cooled

Sl. No. : R-Phase: OP 2561/2/1/09 Y-Phase:OP2561/2/2/09


B-Phase:OP2561/2/3/09

Year of manufacture : R-Phase: 2009 Y-Phase: 2009 B-Phase: 2009

V. Feeder Name: 66kV BUS

VI. Primary Voltage: 66kV

VII. Secondary Details:

Winding 1 Winding 2 Winding 3


Voltage 110/√3 110/√3 110/√3 Volts
VA Burden 50 50 50 VA
Class 3P 3P 0.5
Purpose Protection Protection Metering

VIII. Details of checklist:

S. No. Description Status Remarks, Record


Yes No discrepancies, if any
1. Equipment is cleaned and free from Yes
dust / dirt, foreign materials etc.
2. Equipment is free from all visible Yes
defects on physical inspection
3. Check CVT tank has been provided Yes
with double earthing
4. Check that CVT marshalling box is Yes
earthed
5. All nuts and bolts are tightened Yes
Page 1 of 6

CAPACITIVE VOLTAGE TRANSFORMER


POWER GRID CORPORATION OF INDIA LIMITED Doc. No.: MR/CF/CVT/02/R-2 DATED 01/04/08
CORPORATE OPERATION SERVICES Sub station: khadoli
PRE-COMMISSIONING OF POTENTIAL Bay No.: 66 kv BUS
TRANSFORMER
COMMISSIONING FORMATS Equipment Identification No.: BUS PT
Date of Testing: 19.09.2010

correctly as per specified torque


6. Check tightness of terminal Yes
connector
7. All fittings as per out line general Yes
arrangement drawing
8. Labelling and identification marking Yes
is carried out
9. Levelling and alignment of structure Yes
and base frame is checked
10. Erection completion certificate along Yes
with list of outstanding activities
reviewed
11. Any paint removed / scratched in Yes
transit has been touched up
12. Sl. No. of HV capacitor identical to NA
the Sl. No. mentioned on rating plate
& Diagram plate
13. Ensure brass vent plug between NA
stacks of CVT is removed
14. Check the oil level and leakage Yes
through any joints / terminals
15. Check oil drain valve is properly Yes
closed and locked
16. Oil level on tank gauge glass Yes
17. BDV of oil sample taken from tank NA
bottom drain valve
18. Check secondary cable end box is Yes
properly fixed and ensure cable entry
at the bottom
19. Ensure HF terminal of unused phases NA
has been earthed and no load on HF
terminal bushing
20. Check rating / healthiness of fuses at Yes
CVT MB and CVT terminal box
21. Check that the neutral point is Yes
earthed
22.. Ensure interpole cabling is Yes
completed and check the continuity
23. Check the IR value of secondary Yes
cables
(> 50M Ω for control cables)
24. Check external cabling from junction Yes
box to relay / control panel
completed
25. All the cable identification tags Yes
Page 2 of 6

CAPACITIVE VOLTAGE TRANSFORMER


POWER GRID CORPORATION OF INDIA LIMITED Doc. No.: MR/CF/CVT/02/R-2 DATED 01/04/08
CORPORATE OPERATION SERVICES Sub station: khadoli
PRE-COMMISSIONING OF POTENTIAL Bay No.: 66 kv BUS
TRANSFORMER
COMMISSIONING FORMATS Equipment Identification No.: BUS PT
Date of Testing: 19.09.2010

provided and all cores are provided


with identification ferrules at MB

IX. Continuity of winding (after removing earth link, 1, 2, 3)

A Between terminals 1a – 1n OK
B Between terminals 2a – 1n OK
C Between terminals 3a – 1n OK

X. Insulation resistance measurement using 5 kV Megger: Min: 1000MOHMS

Core Phase
R- Phase Y- Phase B-Phase
GΩ Primary – Core – I 2.1 4.2 3.1
GΩ Primary – Core – II 3.5 3.6 3.7
GΩ Primary – Core – III 2.2 2.9 4.0
GΩ Primary – Earth 3.1 2.7 4.3

XI. Secondary winding resistance in Ω:

Phas Core 1 Core 2 Core 3 Remarks


e Factor Site Factor Site Factor Site
y y y
1a1- 1a2- 2a1- 2a2- 3a1- 3a2-
1n 1n 2n 2n 3n 3n
R NA 0.1 NA NA 0.1 NA NA 0.2 NA
Y NA 0.2 NA NA 0.1 NA NA 0.1 NA
B NA 0.1 NA NA 0.2 NA NA 0.1 NA
All values at 75 oC

XII. Insulation resistance measurement using 500 V Megger: Min: 50MOHMS

Core Phase
R- Phase Y- Phase B-Phase
GΩ Secondary Core I - Earth 1 1 1
GΩ Secondary Core II - Earth 1 1 1
GΩ Secondary Core III - Earth 1 1 1
GΩ Core I- Core II 1 1 1
GΩ Core I – Core III 1 1 1
GΩ. Core II – Core III 1 1 1

Page 3 of 6

CAPACITIVE VOLTAGE TRANSFORMER


POWER GRID CORPORATION OF INDIA LIMITED Doc. No.: MR/CF/CVT/02/R-2 DATED 01/04/08
CORPORATE OPERATION SERVICES Sub station: khadoli
PRE-COMMISSIONING OF POTENTIAL Bay No.: 66 kv BUS
TRANSFORMER
COMMISSIONING FORMATS Equipment Identification No.: BUS PT
Date of Testing: 19.09.2010

XIII. Voltage Ratio Test:


Phase Primary Secondary Voltage Theoretical Actual ratio % Error
Voltage Between Value ratio Factory Site
R 2400.00 1a-1n 4.003 600 599.55 -0.07%
R 2400.00 2a-2n 4.005 600 599.25 -0.12%
R 2400.00 3a-3n 4.021 600 596.87 -0.52%
Y 2400.00 1a-1n 4.002 600 599.70 -0.05%
Y 2400.00 2a-2n 4.034 600 594.94 -0.84%
Y 2400.00 3a-3n 3.995 600 600.75 0.13%
B 2400.00 1a-1n 4.005 600 599.33 -0.11%
B 2400.00 2a-2n 4.009 600 598.65 -0.22%
B 2400.00 3a-3n 4.007 600 598.95 -0.17%

Apply 415 Volts, 3 Phase across line capacitor (Top flange) to earth tank. Ensure all earthing
leads connected.

XIV. All terminal blocks closed in the secondary after all testing

Yes

XV. Phasing of CVT by measuring voltage between R-Phase, Y-Phase and B-Phase at
incoming terminal in control cubicle for one circuit of the checked CVT and output
terminals R-Phase, Y-Phase and B-Phase of a reference circuit (Existing CVT) with
known phasing

Reference Measured Value


circuit R-Phase Y-Phase B-Phase
R-Phase OK OK OK
Y-Phase OK OK OK
B-Phase OK OK OK

XVI. Tan delta and capacitance measurement: NA

Details of Test Kit: Make:


Page 4 of 6

CAPACITIVE VOLTAGE TRANSFORMER


POWER GRID CORPORATION OF INDIA LIMITED Doc. No.: MR/CF/CVT/02/R-2 DATED 01/04/08
CORPORATE OPERATION SERVICES Sub station: khadoli
PRE-COMMISSIONING OF POTENTIAL Bay No.: 66 kv BUS
TRANSFORMER
COMMISSIONING FORMATS Equipment Identification No.: BUS PT
Date of Testing: 19.09.2010

Across Stack Pre Commissioning Values


CAPACITANCE TAN DELTA
R-Phase Y-Phase B-Phase R-Phase Y-Phase B-
Phase
ALL STACK (2kV) NA NA NA NA NA NA
ALL STACK(10kV) NA NA NA NA NA NA

Factory Values
CAPACITANCE TAN DELTA
R-Phase Y-Phase B-Phase R-Phase Y-Phase B-
Phase
ALL STACK (2kV) NA NA NA NA NA NA
ALL STACK NA NA NA NA NA NA
(10kV)

Factory Test Report ref. No.:

XVII. Final documentation review:

A. Final document of pre-commissioning checks reviewed YES


and approved
B. Document regarding spares, equipment, O & M YES
manuals etc. available at site for O & M purpose
After modification, if any, “As built drawings “ are available at NA
site

Signature: Signature: Signature:


Name : Name: Name:
Designation: Designation: Designation:
Organisation: Organisation:
(Supplier Rep.) (Erection Agency) (Power Grid Site I/C)

Signature: Signature:
Name : Name:
Designation: Designation:
Page 5 of 6

CAPACITIVE VOLTAGE TRANSFORMER


POWER GRID CORPORATION OF INDIA LIMITED Doc. No.: MR/CF/CVT/02/R-2 DATED 01/04/08
CORPORATE OPERATION SERVICES Sub station: khadoli
PRE-COMMISSIONING OF POTENTIAL Bay No.: 66 kv BUS
TRANSFORMER
COMMISSIONING FORMATS Equipment Identification No.: BUS PT
Date of Testing: 19.09.2010

Organisation:
(Testing Agency) (Power Grid Commissioning Team)

Page 6 of 6