Professional Documents
Culture Documents
POI,tJER $
Abstract
The voltage stability problem of a power system is associated with a rapid voltage drop due to heavy system load, and it occurs
because of inadequate reactive power support at some critical buses. One of the serious consequences of the voltage stability
problem is a system blackout, and this problem has received much attention in recent years. This paper proposes a fast method
for finding the maximum load, especially the reactive power demand, at a particular load bus before reaching the voltage stability
limit. The method uses the base-case system information to find special two-bus equivalents of the system for analyzing the voltage
stability problem. The method was tested on the IEEE 14-, 30-, and 118-bus systems and the results obtained were compared with
those found by some other methods.
Pm- 2X 2 (8a)
/ / / /
i/,,/ //
,~.I ]
= (8b)
,¢¢'+
O*O I I I I i i i i i [ ~ i i i i i i i i i i i i i i i i 4 i i i i i i i i i i i I
Similarly, the maximum reactive power loading Qm at
0.0 2.0 4.0 6.0 8.0 lagging PF (with P = 0) and the corresponding voltage
Load apparent power, pu
can be written as (by setting 0 = 90 °)
Fig. 2. Variation of load voltage against the load apparent power for
various power factors. VI2(Z - X)
Qm - 2R 2 (9a)
Typical variations of load voltage against the load
Vcr = ( V'2 --~2QmX) '/z (9b)
apparent power for various power factors (PFs) are
shown in Fig. 2. The figure is plotted for V1 = 1.0 p.u.,
R = 0.01 p.u. and X = 0.1 p.u. The high-voltage or sta- It can also be noticed in Fig. 2 that the critical voltage
ble solution is represented by full curves while the for unity and lagging PF loads is significantly less than
low-voltage or unstable solution is represented by bro- the nominal value of 1.0 p.u. and it may not be accept-
ken curves. These two curves or voltages meet at the able in practice. In power system operation, it may be
critical point (marked by "< in the figure). It can be necessary to know the maximum load at which the load
observed in the figure that both the maximum load voltage should not drop below a specified value V2sp
apparent power and critical voltage increase as the load ( > Vor). The corresponding load Ssp can be obtained
PF changes from lagging to leading. The objective is to from Eq. (1) by setting V2 = Vzsp. This involves the
find the maximum load apparent power and the corre- solution of the following quadratic equation:
sponding voltage. Obviously, the condition of the max- a3Ssp 2 -}- b 3 S s p -F C3 : 0 10)
imum load apparent power (Sin) can be obtained by
setting the value of d in Eq. (4) to zero. This gives the where
following quadratic equation: a3= R 2 _]_ X2
a2 Sm 2 _L b2 Sm + C2 = 0 (5)
b 3 = 2 V2w2(R cos 0 + X sin O)
where
C3 = V2sp4-- V 12 V2sp2
a 2 = 4[RX sin(20) - R 2 sin20 - X 2 cos20]
Typical variations of load apparent power S+p against
b2 = - 4 V ~ ( R cos 0 -- X sin 0) the load PF angle for various specified load voltages are
shown in Fig. 3. It can be seen in the figure that the
C2= V14
load apparent power decreases as the lagging PF angle
In deriving Eq. (5), it is considered that P = S cos 0 is increased. For a given PF, the load apparent power
and Q = S sin 0, where 0 is the PF angle. The value of increases as the specified load voltage is decreased.
Sm can be obtained from the solution of Eq. (5):
Vt 2 Z - (R cos 0 + X sin 0)
Sin- 2 (R sin 0 + X c o s 0) 2 (6) 3. Voltage stability limit of a general power system
Here Z = (R2+ X 2) ~/2. Note that the other solution of In general, the determination of the voltage stability
Eq. (5) is not feasible because of its negative value. limit of a general power system is a very difficult task.
Once the value of Sm is known, the corresponding A quicker way to find the voltage stability limit of a
critical voltage Vcr can be obtained from either Eq. (3a) power system is through the two-bus or Th6venin
or (3b) by setting d = 0 and evaluating the coefficient bl equivalent circuit of the system. Note that the operating
at the maximum load apparent power Sin. This gives point of the generators at the verge of voltage stability
38 M.H. Haque /Electric' Power Systems Research 32 (1995) 35 43
5.0
jx,~
m
~4.0
Q)
0
~.3.0
JXgl
V=0.75 pu
m+l
~2.0 V=0.80 pu
1.0
V=0,85
V=0.90
V=0.95
pu
pu
pu
~ Es~
(a)
0.0 ''''''''ll'''l'l'llllll'l'l'lll'~ll,,,,ll,,,lllll ]
0 10 20 30 40 50
Lagging pf angle, degree
Fig. 3. Variation of load apparent power against the load PF angle
for various specified values of load voltage. jXs. - 0
ggm
m n---~
may differ significantly from the base-case operating
point. Thus, the Th6venin equivalent circuit obtained at k
the base case with a conventional generator model may
not represent a good equivalent circuit to determine the jX¢I = 0 Vc,
voltage stability limit unless some special care is taken m+l
in modeling the generators. Chebbo et al. [13] overcome
this problem first by finding an equivalent circuit at the
I
base case and predicting the maximum loading capabil-
ity of a particular load bus in the equivalent circuit. The
load of that bus is then increased to the predicted value
and a second equivalent circuit is obtained for the new (b)
operating point. The process is repeated until the load Fig. 4. Generator model in a power system.
flow solution of the original network for the predicted
load fails to converge. The method ultimately produces
an equivalent circuit that has been obtained for a load to maintain constant terminal voltages Vg as long as the
condition which is very close to the voltage stability reactive power generation of the generators is within
limit. The repetitive computations in this method seem the limits. Because of the variable nature of Eg, the
to be very time consuming. In this paper special atten- Th6venin equivalent circuit obtained for a given operat-
tion has been given in modeling the generators to avoid ing point, with the above generator model, may not be
these repetitive computations and the Th6venin equiva- used for a different operating point unless they are
lent circuits obtained at the base-case operating point very close. However, the voltage instability point is, in
may be faithfully used to determine the voltage stability general, far away from the base-case operating point.
limit. Some researchers have modeled the generators by
constant impedances with an appropriate sign. Those
3.1. Generator model impedances are again obtained from the base-case load
flow solution. A better generator model for the analysis
Consider a general power system as shown in Fig. of the voltage stability problem is proposed in the
4(a). Buses 1 to m are the generator buses where the following.
voltage magnitudes are kept constant. Buses m -4- 1 to n As mentioned earlier, the generator internal voltages
are the load buses. The aim is to find the maximum Eg are adjusted with the system load to maintain con-
loading capability of a particular load bus k within the stant terminal voltages Vg. The difference between Eg
voltage stability limit. In general, the generators in a and Vg is the voltage drop across Xg. With this in mind,
power system are modeled by internal voltage sources the generators can be considered as Eg = Vg = constant
Eg with series reactances Xg, as shown in the figure. with Xg~-0, as shown in Fig. 4(b). When reactive
When the system load or operating point changes, the power generation is changed due to the change in
generator internal voltages Eg are adjusted accordingly reactive power demand in the system, the angle of Vg
M.H. Haque /Electric Power Systems Research 32 (1995) 35 43 39
The no-load or Th6venin equivalent voltage Vth of 3.2.1. Determination of the Thkvenin impedance
load bus k can be obtained from the load flow solution. Let Zkk be the kth diagonal element of the Z matrix
The load flow solution is to be determined by consider- when all loads are considered. Our aim is to find the
ing all loads in the system except at bus k. The Th6v- Th6venin impedance Zth of bus k when its load is
enin equivalent impedance Zth of bus k is the kth ignored. These two impedances (Zkk and Zth) are
diagonal element of the Z matrix. In calculating the Z shown in Fig. 5. It can be observed in the figure that
matrix, loads of all buses (except at bus k) are to be L
replaced by constant impedances and the generators are Zk Z,~ (12)
= z#.llZ,,, z#. + z,,,
to be replaced by negligible reactances. The relationship
-
between the voltage, impedance and load of bus i is Here Z~ is the load impedance of bus k Thus, the
Th6venin impedance Z,h can readily be written as
Iv'12 (ll)
P, - JQi Zth = 2~ (13)
k
Note that, at the verge of voltage stability, the con-
stant-impedance load model may represent less load 3.2.2. Determination of the Thkvenin voltage
than it should because of voltage reduction at some Let Vx. be the voltage at bus k obtained from the
buses. Thus, the Th6venin equivalent circuit with the load flow solution when all loads in the system are
above load model may provide pessimistic results at the considered. The objective is to find the Th+venin
verge of voltage stability. However, the error is not voltage V~h of bus k when its load is ignored. Fig. 6(a)
significant because the load impedances are, in general, and (b) shows the Thavenin equivalent circuits of Fig. 5
much higher than the line impedances or generator at points aa' and bb', respectively. By comparing Fig.
impedances (Xg ~ 0). Thus, the load impedances have 6(a) and (b), the value of Vth can readily be written as
very little effect on the diagonal element of the Z matrix
or the Th6venin impedance. In order to find the Th6v- Z~h\
V,h= l+~y|Vk (14)
enin equivalent circuit behind a different bus, the entire Z, /
40 M.H. Haque /Electrie Power Systems Research 32 (1995) 35-43
Z~ Z~ Table 1
a a
I I /------] M a x i m u m reactive power loading of the IEEE 14-bus system
Proposed NR
method method
a'
4 0.5156 622 615-620 1.1
(a) (b) 5 0.5144 611 600 605 1.8
Fig. 6. Th~venin equivalent circuits of load bus k. 7 0.5316 348 335 340 3.9
9 0.5421 262 255 260 2.7
10 0.5375 193 185 190 4.3
Fig. 6(b) represents the Th6venin equivalent circuit of
11 0.5416 201 195-200 3.1
bus k and the maximum loading capability of this bus 12 0.5531 180 175-180 2.9
can be determined by varying the load impedance Z~. 13 0.5476 295 290 295 1.7
When the Th6venin equivalent circuit of a general 14 0.5410 127 125 130 1.6
power network behind a particular load bus is ob-
tained, all the equations derived in Section 2 can be
used to analyze the voltage stability problem associated
system was determined through the Th6venin equiva-
with that bus.
lent circuit as described in Section 3. Values of Qm and
Vcr obtained from Eqs. (9a) and (9b), respectively, are
4. Simulation results given in Table 1. The maximum reactive power load-
ings, for these buses, obtained by the NR method are
The proposed method of determining the maximum also given in Table 1. The limit on the reactive power
reactive power loading of a load bus in a general power generation of the voltage control buses was not consid-
system has been vigorously tested on the following ered in both the proposed and the NR method. It can
three power systems: the IEEE 14-bus system, the IEEE be observed in Table 1 that the maximum reactive
30-bus system, and the IEEE 118-bus system. power loading obtained by the proposed method is
The results obtained by the proposed method were slightly higher, as expected, then the corresponding
compared with those found by the NR method. In the value found by the NR method. The maximum error
NR method, the maximum reactive power loading of a (less than 4.5%) was observed at bus 10. For this bus,
load bus is determined by gradually increasing the the maximum reactive power loading obtained by the
reactive power demand at the candidate bus in the NR method was between 185 and 190 MVAr. That is,
original unreduced system until the method fails to the method converged for 185 MVAr and it failed to
converge in solving the load flow problem. The actual converge for 190 MVAr. The corresponding value
maximum reactive power demand should not be less found by the proposed method was 193 MVAr.
than the value obtained by the NR method because of It was observed from the load flow solution of the
the numerical problems of the method in the vicinity of original system that the reactive power generation of all
the voltage instability point. As mentioned earlier, the voltage control buses exceeded the limits. This hap-
maximum loading capability of a bus estimated by the pened at Qm for all load buses. In order to consider the
proposed method is slightly higher than the correspond- limits on the reactive power generation, all voltage
ing actual value because of the constant-impedance control buses (except the swing bus) were considered as
load model. Thus, the results obtained by the proposed
and NR methods and the actual value can be ranked as
Table 2
follows: M a x i m u m reactive power loading of the IEEE 14-bus system when
Result obtained Actual Result estimated by the reactive power generation limits are considered
< <
by NR method value proposed method Bus no. Vcr (p.u.) Qm (MVAr) obtained Error (%)
The actual error involved in the proposed method is
Proposed NR
less than that obtained by comparing the results of the
method method
proposed and NR methods.
9 0.5861 135 128 130 5.5
4.1. The I E E E 14-bus system 10 0.5694 110 97 99 13.4
11 0.5676 97 86--88 12.8
12 0.5745 80 73---75 9.6
The single-line diagram and data of the IEEE 14-bus
13 0.5767 99 92 94 7.6
system are obtained from Ref. [16]. The maximum 14 0.5723 84 77-79 9.1
reactive power loading Qm of all load buses in the
M.H. Haque ~Electric Power Systems Research 32 (1995) 35 43 41
Table 3 Table 4
Maximum apparent power loading (at PF =0.8 lagging) of the Maximum reactive power loading of the IEEE 30-bus system
14-bus system
Bus no. V~ (p.u.) Qm (MVAr) obtained Error (%)
Bus no. V~, (p.u.) Sm (MVA) obtained Error (%)
Proposed NR
Proposed NR method method
method method
7 0.5139 452 445 450 1.6
9 0.5797 299 275 280 8.7 14 0.5390 127 120 125 5;.8
II 0.5494 206 200 205 3.0 21 0.5323 189 180 185 5.0
14 0.5480 131 125 130 4.8 28 0.5089 446 435 440 2.5
30 0.5251 38.7 3738 4.6