Professional Documents
Culture Documents
ZAE Bayern, Center for Applied Energy Research, Munich, Germany, Tel: 089/356250-17, Fax: 089/356250-23
Heated Building area 135 m² There are two modes of operation for an adsorption heat
Air Exchange rate 0.5 (ca. 140 m³/h) pump: Desorption and adsorption. The high temperature
Maximum Heat Load energy input from the gas burner takes place during
Transmission Losses 25 W/m² desorption, low temperature energy input during ad-
Ventilation Losses 16 W/m² sorption. Heat can be delivered to the heating system
Averaged Heat Load 75 kWh/m² a over the whole de- and adsorption cycle. In the follow-
Heating System ing example an ambient temperature of -5°C and a dew-
Inlet/outlet Temperature 60 °C/ 40°C point of -5°C are assumed.
Max. Heating Power 5.5 kW
The example is calculated by a experimentally validated
Table 1: Building and heating system data simulation program for sorption processes in packed
beds. All data of the zeolite and the column are taken
Zeolite Experiments with 20 kg zeolite 13X showed a into account.
heating power of about 1 kW. In the application dis-
cussed here the heat pump contains 110 kg of zeolite Desorption For desorption 20 m³/h of ambient air are
13X. The packed bed of zeolite pellets is located inside blown through the heat recovery heat exchanger. This
a double walled steel column. The space between the leads to a temperature rise of about 40 K. The gas
two walls is evacuated and filled with glass fiber burner brings the preheated air up to a temperature of
boards. Using this new insulation technique, the heat 1000 °C and a dewpoint of 45 °C. By mixing this air
losses are reduced by a factor of ten and the parasitic with 150 m³/h of saturated air at 45 °C desorption con-
heat capacity is four times smaller compared to conven- ditions of 300 °C temperature and of 45 °C dewpoint
tional insulation. The cylindrical tube has a diameter of are reached.
0.4 m and a height of 1 m.
With a temperature of 300 °C zeolite can be completely
Condensing Heat Exchanger For a compact construc- dried to a residual water content below 1% of its dry
tion the condensing heat exchanger is located at the side weight. Air leaves the packed bed almost saturated at
of the zeolite column and the humidifier. It is a counter- about 60 °C.
current flow heat exchanger with a length of 1.3 m (like
the zeolite column plus the humidifier). This length is
necessary in order to get maximum temperature change 60/59 water
60°C
in the air and the condensed water. The vertical position air
allows the condensed water to transfer heat to the ex-
changer fluid while running down and finally flowing Zeo
into the connected tank or directly into the hot water 40°C
storage of the solar system.
45/45
condensate
Gas Burner A standard, modern gas burner is used. 150 m³/h 300/45
40°C
Maximum heating power is 10 kW. Maximum tempera- 1000/45
ture of the combustion gases in case of complete com- 20 m³/h
bustion (at air rate 10 m³/h) is 1900 °C. In this applica- 40/40 35/-5
tion the gas burner is operated with an air surplus. With
an air rate of 20 m³/h this leads to a temperature of 1000 -5/-5
°C.
Figure 2: Desorption mode of the heat pump
Humidifier The humidifier is located directly under
(35/-5: temperature 35 °C, dewpoint -5 °C)
the zeolite column. A spray nozzle distributes water
over a packed bed of Raschig rings. Up to 400 l/h are
The latent and sensible heat of the 170 m³/h air stream
pumped through the nozzle. The packed bed of rings
can be used. They are transported to the heating system
has a diameter of 0.4 m and a height of 0.2 m, which
via the condensing heat exchanger. Condensed water at
leads to an exchange surface of the rings of about 20
about 40 °C leaves the desorption process and can be packed bed. Low temperature energy as well as latent
stored in the hot water tank. heat from the building is used for humidification.
20 m³/h of saturated air are blown through the heat 140 m³/h of preheated air at 30 °C and a dewpoint of -5
recovery device heating up the incoming air, while 150 °C are blown through the building. It leaves the build-
m³/h are mixing down the combustion gases to 300 °C ing at 20 °C, but with a dewpoint of 7 °C. The energy
again. The desorption process is schematically shown in balance of the building is not influenced by this ventila-
figure 2. tion process. The dewpoint increment is equivalent to
the moisture production within the building.
Zeolite
40°C
30°C
humidifier 23°C
45/-40
20 m³/h 23/5
140 m³/h 20/7
building
30/-5
10/-40
Enthalpy of
air leaving the system
Qair des
Energy input
to heat up and
Heating
desorb zeolite
energy
Figure 6: : Adsorption inlet/outlet air temperature Gas
burner Zeo
Figure 6 and 7 show temperatures (in/out) and water Qcap Qheat des
contents (in/out). The adsorption shown here starts Qdes
immediately after desorption. Therefore high tempera-
tures (up to 300 °C) for the first hour due to the thermal
Energy of condensed water
capacity of the desorbed zeolite are observed. The ad- Qcond
sorption process itself starts after about 45 minutes and
lasts for 5.25 hours. Out let temperature is constant
Figure 8: Desorption heat fluxes
during the adsorption process at about 140 °C. In this
phase the adsorption front is moving through the packed
bed. Adsorption stops, when the air temperature drops
below 75 °C. Enthalpy of
air leaving the system
Qair ads
Energy for
humidification Heating
energy
Gas
burner Zeo
The COP is defined as the fraction of energy output, .Since Qcond can be stored (see „Desorption“) it can
which is the heating energy during de- and adsorption substitute part of the low temperature energy demand.
(Qheat ads and Qheat des), to energy input during desorption This leads to:
(Qdes) plus not usable output (enthalpy of air blown into
Qheat ads + Qheat des + Qcap Auxiliary energy for ventilation is 1.64 kWh for a com-
COP =
Qdes + Qair ads + Qair des + (Qlt − Qcond ) + Qcap
plete de- and adsorption cycle (assuming a 50% effi-
ciency for the fan). This is about 3% of the usable heat-
ing energy output per cycle. Energy demand for the gas
An experimental set-up with 20 kg zeolite 13X was burner fan and water pump for the humidifier are about
built [1]. An electric air heater supplied desorption and 2%.
low temperature energy to the heat pump. The thermal
COP for the experimental de- and adsorption cycle was 5. Adsorption heat pump as Desiccant Cooling Sys-
1.48 ± 0.03. In this experiment the entire low tempera- tem
ture energy demand was supplied electrically.
In a desiccant cooling system dry air is cooled down by
Looking at the gas driven adsorption heat pump in con- humidification. The desorbed zeolite is able to dry an
nection with the building, there are two differences to air stream very effectively by adsorption. The humidi-
the experiments: Water vapor from the building can be fier can cool it to temperatures suitable for air condi-
used for humidification and water vapor from the gas tioning systems. Cooling is only possible in the adsorp-
combustion increases the usable latent heat during de- tion mode.
sorption. Because of these two effects, a higher COP is
to be expected. The driving energy has to be delivered by the solar
surplus in periods of high irradiation. Solar energy out
If low temperature energy is supplied by a solar system, of the hot water storage is brought into the system by
it is not always available (in the heating period). Figure the condensing heat exchanger. Solar desorption takes
8 shows how the COP depends on this availability. If place at temperatures of 70 - 80 °C. Using these tem-
there is no low temperature energy at all (that means it peratures only about 35% of the water in the zeolite can
has to be delivered by the gas burner), a COP of 1.05 is be desorbed. Figure 9 shows the solar desorption.
obtained. It is above 1.0 because of the transformation
of latent heat from the building and the gas combustion For the cooling operation during adsorption a change in
into usable heat for the heating system. If low tempera- the construction and an additional component are neces-
ture energy is fully available a COP of 1.63 can be sary: The humidifier has to be switched to another posi-
reached. tion just under the condensing heat exchanger (see fig-
ure 10) and a very simple supplementary humidifier
(Hum 2) has to be installed. This one has to cool the
ventilation outlet air from the building by humidifica-
tion.
water
air
Zeo
70-80°C
160 m³/h
6. Outlook