You are on page 1of 7

9

LABORATORY INVESTIGATIONS AND METHODS FOR EVALUATING THE FLASHOVER


PERFORMANCE OF OUTDOOR INSULATORS ON A LARGE SCALE

Masoud FARZANEH 1 , Jean-Francois DRAPEAU2 , Changiz TAVAKOLI1 , Michel J. ROY3

1 2 3
NSERC/ Hydro -Quebec /UQAC Institut de recherche TransEnergie (Hydro-Quebec)
Industrial Chair on Atmospheric d’Hydro -Québec (IREQ) (Montreal, Canada)
Icing of Power Network (Varennes, Canada)
Equipment (CIGELE)
(Chicoutimi, Canada)

Abstract - This paper presents the new facilities of air gaps, i.e. the zones on the insulators without ice or
the University of Québec at Chicoutimi designed snow. These air gaps are normally created near the
for large-scale evaluation of the electrical electrodes by the melting process caused by the heating
performance of insulators under atmospheric icing effects of partial arcs active in these areas, as the voltage
conditions. It also reports on the test method used drops are relatively high [5, 20, 30]. Air gaps could also
for evaluating the maximum withstand voltage of be created by snow or ice shedding during or after
a 735-kV station post insulator type with a accretion.
standard shed design. The tests were carried out A relatively large number of laboratory investigations
under wet-grown ice, during a melting period, on and theoretical studies have been carried out to quantify
a portion of insulator with a dry arcing distance of the effects of individual parameters of ice and snow on
about 2 m, corresponding to 50% of full scale. the critical flashover voltage of insulators. Reviews of
The ice was produced at an air temperature of most of these investigations have been reported in
-12 o C from supercooled droplets impinging on the previous work [14, 16] and recent papers by a CIGRE
vertically installed insulator in the climatic task force [2, 3]. These reviews have shown the need
chamber. The results are highly meaningful as for more substantial studies in this field and, especially,
they are used as the reference for ranking several the necessity to establish standard methods for
other station post insulator types and evaluating the electrical performance of insulators under
configurations in order to choose the adequate one icing conditions. The reviews also revealed that, in
for a new Hydro-Québec 735-kV substation spite of many worthwhile studies, the role of many
planned for construction. major insulator parameters such as shed profile,
diameter and spacing, material covering the insulator
1. INTRODUCTION surfaces as well as the relation between the dry arcing
distance and flashover voltage, have not yet been clearly
Insulator flashover under ice and snow conditions still determined. More recently, a new IEEE task force on
constitutes a challenging problem for overhead insulator icing problems was created and a position
electrical power transmission systems experiencing paper was prepared [13]. The main purpose of this
atmospheric ice accretion. Reports from several utilities paper is to positively respond to at least one of these
demonstrate that the flashover phenomenon can occur preoccupations, namely the establishment of methods
on most line and post type insulators during or after ice for evaluating the electrical performance of insulators
and snow accretion followed by a period of warming under atmospheric conditions including ice, snow and
[4, 5, 18, 21, 22, 26-28, 31]. In Canada, most of the cold fog.
significant insulator flashovers are reported to occur The need for more research and development in the field
during the melting period on station post insulators of atmospheric icing of power network equipment,
covered with snow or ice [4, 5, 18]. including insulators, led the CIGELE researchers of the
Ice and snow have 2 significant roles in reducing the University of Québec at Chicoutimi (UQAC) to design
flashover voltage of outdoor insulators [8]. First, the and construct a world-renowned and unique laboratory
leakage distance is reduced to approximately the dry with state-of-the-art equipment on the university
arcing distance if the shed spaces are completely campus. Such a project, in the framework of the
bridged. Second, the water present in the snow or on Canada Foundation projects, was made possible thanks
the surface of the accreted ice is highly conductive in to major financial support granted to Professor
general, causing relatively high voltage drops along the Farzaneh’s research team by the Québec and Canadian
governments, Hydro-Québec and UQAC.

1
Using part of this infrastructure, namely a specially conditions and with a potential for further research
designed climatic chamber and a 350-kV AC system, under ice and contamination, this system with its 2 tap
the performance of several types and configurations of switches has a minimum short-circuit current of 10 A at
735-kV station post insulators was evaluated in a 130 kV, a maximum of 42 A at 240 kV and 32 A at
project undertaken in collaboration with Hydro-Québec. 350 kV. For voltages lower than 130 kV, a second
The primary objective of the overall project was to rank transformer of 120 kV, 240 kVA with a maximum
the insulators on the basis of their maximum withstand short-circuit current of 28 A is used.
voltage (VWS) under various icing conditions in order to
select the most adequate insulators and configurations.
In a first, exploratory, stage of the project, several 3
solutions were tested on very short portions (0.6 m) of
insulators [6, 7, 10]. In the present stage, the new
insulator types and configurations are being more
thoroughly investigated on a larger scale, with dry
arcing distances of about 2m. These insulators are 1
planned to be implemented in a new Hydro-Québec
735-kV substation. The main purpose of this paper is to
present the set-up and describe the methods used for 2
evaluating the maximum withstand voltage of ice-
covered insulators. In addition, the results obtained on a
profile of one of the standard sheds, used as reference,
are presented.

2. FACILITIES AND PROCEDURE 1 Water droplet generator


2 Insulator under test
2.1. Facilities 3 HV Bushing
The tests were performed in a uniquely designed
climatic chamber at the University of Québec at Fig. 1: Inside of the UQAC climate room used in this
Chicoutimi (UQAC) in close collaboration with Hydro- study
Québec. This chamber, 6 m (w) x 6 m (l) x 9 m (h), has
a roof designed to open, allowing for the collection of
natural precipitation, especially snow. It is also
equipped with a HV SF6 composite bushing as well as a
sophisticated water droplet generator for physical
simulations of cold precipitation. The ammonia cooling
system and computer-controlled regulators allow a
desired air temperature as low as –30°C ± .2°C to be
obtained very rapidly.
The water droplet generator comprises a system of
6 oscillating pneumatic nozzles located in front of a
diffusing honeycombed panel. Behind the panel, a series
of fans are placed in a tapering box. The fans can be
mounted in a single- or double-stage arrangement,
depending on the desired wind velocity. The specific Fig. 2: UQAC 350 kV alternating high-voltage system
design of the water droplet generator enables its position
to be changed for the formation of a very uniform ice on The test data, including the temperature, voltage and
the test object mounted in any position (horizontal, current, is monitored by commercial software integrated
vertical or transversal). The system is also able to into a PC-compatible computer. The results are
produce the ice on a large-surface test object, as the presented in MS Excel Table formats for further
wind generation system is composed of 24 fans treatment and analysis. Considering the long duration
uniformly distributed on a large panel in the climatic of each evaluation test, only the peak values of the
chamber. leakage-current data during positive and negative half-
Figure 1 shows the inside of the chamber featuring the cycles is monitored.
water droplet generator (1), the insulators under test (2)
and the HV bushing (3).
2.2. Insulator tested
The high-voltage system is composed of a newly
designed 350-kV, 700-kVA transformer and its Different 735-kV station post insulator types and
associated voltage regulator (Fig. 2). Specially configurations were tested under various icing
designed for flashover tests on insulators under icing conditions. For the purpose of the present paper, the

2
results are presented for just one insulator, which serves substations. This type of ice is considered the most
mainly as a reference. This insulator is a normal glazed dangerous, since it is associated with the highest
porcelain type with a standard shed profile and is typical probability of flashover [15, 17].
of those used in Hydro-Québec 735-kV substations. The density of ice accumulated on the insulators was
Figure 3 shows one unit of the tested insulator and some determined by weight and volume measurements. The
of its characteristics. A dry arcing distance of about 2 m volume was obtained by immersing an ice sample in
of these insulators, corresponding to 50% of full scale, light mineral oil. The conductivity of the water feeding
is tested in this study. the nozzles was adjusted to a desired value by adding
sodium chloride to de-ionized water. The median
volume diameter of the supercooled droplets impinging
on the insulators at an average angle of about 53o ,
compared to the vertical axis of the insulators, was
measured by exposing a glass slide coated with a
solution of Collargol to the flow of water droplets for a
short period [23]. The samples were then examined
under a microscope and the median volume diameter of
these droplets was determined from the average
diameter of approximately 1000 droplets. The intensity
of the precipitation was determined from measurements
of horizontal and vertical spray intensities using a
pluviometer designed for standard tests [24]. This
device is fitted with a divided collecting vessel, one
horizontal and one vertical, the latter facing the spray.
Lastly, the thickness of ice accumulated on the insulator
was controlled by a monitoring cylinder [11], 3.8 cm in
diameter rotating at 1 rpm.
Table 1 summarizes the test parameters during the ice
Without ice With ice (15 mm) accretion sequence.
Height 1540 mm Table 1: Test parameters for the ice accretion sequence
Arc distance 1360 mm
Leakage path 3500 mm Test parameters Parameters values
Higher part Air temperature -12°C (± 0.2°C)
Interior diam. 154 mm Droplet size 80 µm
Exterior diam. 246 mm
Freezing water conductivity 30 µS/cm at 20°C
Middle part
Interior diam. 168 mm Precipitation intensity 34 mm/h (± 7 mm/h)
Exterior diam. 262 mm Incidence angle 53° (± 5°)
Skirts Wind velocity 3.3 m/s
Number 26 Ice thickness on monitoring 15 mm
Spacing 50 mm cylinder
Upper angle 24.5 ° Voltage gradient 105 kV/m
Lower angle 6.0 ° (service voltage gradient)

Once the desired ice thickness on the monitoring


Fig. 3: 735 kV porcelain station post insulator with cylinder is reached, 15 mm in this case, the water
normal glaze and standard shed profile spraying system and the voltage applied to the insulator
are turned off while the wind continues to blow at the
same velocity of 3.3 m/s, whereupon the curing
2.3. Test procedure sequence begins.
The test procedure for evaluating insulators under icing
2.3.2: Curing sequence
conditions includes 4 basic sequences: ice accretion,
curing, melting and, lastly, evaluation of the maximum During this sequence, the temperature in the climatic
flashover voltage. chamber is maintained at –12o C and the wind kept
blowing at 3.3 m/s for a period of 20 min to ensure that
2.3.1: Ice accretion sequence the liquid water present on the ice surface, inside the ice
In this sequence and for the purpose of the tests reported and at the ice/insulator interface, is completely frozen.
here, wet-grown ice is built up on the vertically installed At the same time, it ensures a better adherence of the ice
insulators energized at approximately the equivalent on the insulator surface. This curing period has
service voltage as used in Hydro-Québec’s 735-kV provenparticularly relevant in the case of semi-

3
conducting glazed insulators (not presented here) [9] as test, the insulators were kept at the test voltage for a
it allows the water film at the of ice/insulator interface, period of at least 15 min to ensure that no flashover
created by the resistive current of about 1mA at the occurred during this period.
insulator surface, to freeze, thus ensuring the good Figure 4 summarizes the different sequences of the test
adherence of ice to the insulator surface for the normal procedure for evaluating the VWS of the insulators.
duration of the melting sequence (described below). In
addition, the curing sequence is highly representative of
many icing episodes in natural conditions where cold Ice Accretion Curing Melting Evaluating
periods occur between ice accumulation and subsequent
Voltage
warm-up of the air temperature. ∆V
Once this sequence is completed, the fans and the
cooling system are turned off and the insulators are
energized again at the same service voltage. This is
followed by the melting sequence. ∆ ta ∆ tc ∆ tm Ti

2.3.3: Melting sequence


The melting sequence consists in raising the chamber -12 Temperature
temperature from sub-zero temperatures to a °C
temperature near the melting point. The rate of increase
in air temperature is a particularly important parameter
and should be carefully controlled. In general, a low Fig. 4: Different sequences of test procedure
rate is associated with the worst conditions, since it
promotes the formation of a highly conductive water 3. EXPERIMENTAL RESULTS
film at the ice surface with a relatively long duration
[8, 19]. In the case of a high rate of increase (i.e. much Figure 5 shows the results of the test performed on a
faster than 1°C/h), the highly conductive water film portion of the standard station post insulator with a dry
caused by melting quickly drips off, thus decreasing the arcing distance of approximately 2 m, tested under
ice surface conductivity and consequently raising the 15 mm of wet-grown ice. This quantity of ice was
critical flashover voltage. In the present study, the air selected for the present experiment in order to provide
temperature in the climatic chamber was increased in icing conditions severe enough to induce flashovers on a
2 steps by combining the opening of the door with an standard insulator at normal operating voltage.
electrical heating system [9]. In the 1st step, the Actually, based on Hydro-Québec’s service experience,
temperature was raised from –12o C to –2o C at a rate of the visual aspect of ice accretions as observed in
about 14°C/h and, in the 2nd step, from –2°C to +2.5°C laboratory for 15 mm corresponds to some of the most
at a rate of about 3.5°C/h. Even though this rate is severe cases observed in the field.
higher than 1°C/h, it was considered severe enough.for It may be observed that the maximum withstand voltage
the purpose of the present study. (VWS) is 195 kVrms . Compared to the service voltage of
2.3.4: Evaluating sequence the insulator (~210 kVrms ), VWS is equal to 0.93 p.u.,
indicating that the maximum withstand voltage of the
This sequence consists in determining the maximum insulators under the test conditions is lower than the
withstand voltage (VWS) of the insulators under a given service voltage by about 7%. It provides evidence that
ice thickness during the melting period, based on the the ice severity was properly selected in accordance
method described in IEC 60507 [25], established for with the test philosophy described above.
evaluating the electrical performance of polluted
insulators, and on the processes developed in previous Under such icing conditions, the shed spacings are
completely bridged with icicles and the leakage distance
work [1, 8, 10, 29]. The moment at which the voltage
is dramatically decreased to approximately that of the
should be applied to the insulator is of great importance
and should correspond to the critical moment when the dry arcing distance. Naturally, insulator parameters
such as shed spacing and diameter, as well as the
probability of flashover is highest. This critical moment
material covering the surface of the insulators, are
typically coincides with the development of a water film
at the ice surface. The brightness of the ice surface, the among the other parameters that influence the VWS of
this insulator. The investigation of these insulator
presence of water droplets at the tip of the icicles and/or
parameters constitutes a challenge in our on-going
the steady increase in peak values of the leakage current
over 15 mA are all indications that the critical moment project for selecting the most adequate insulators and
configurations to be used in Hydro-Québec substations.
at which to apply the flashover test voltage has been
reached. Each flashover test was performed for one
instance of ice accumulation on the insulators. The
maximum withstand voltage was considered the
maximum level of applied voltage at which flashover
did not occur for a minimum of 3 tests out of 4, under
similar experimental conditions. For each withstand

4
of Canada and the University of Québec in Chicoutimi.
225 VWS= 195 kV The authors would like to thank Dr. S. Brettschneider
Test voltage (kV)

Flashover
for his active participation in laboratory tests at UQAC,
210 Withstand and also S. Desgagnés and P. Camirand for technical
assistance.
195
6. REFERENCES
180
1 2 3 4 5 6 1. Chaarani R.: Détermination de la tension de tenue
Test number maximale des isolateurs composites en EPDM.
M.Sc. Thesis, UQAC, Fall 1996, 121 p.
Service voltage: 195 kV
2. CIGRE TF 33 04 09: Influence of Ice and Snow on
Conductivity: 30 µS/cm the Flashover Performance of Outdoor Insulators –
Part I :Effects of Ice, Electra no. 187, 1999, pp. 91-
Fig. 5: Test results obtained on an arcing distance of 111.
2 m on a std station post insulator under an ice
thickness of 15 mm 3. CIGRE TF 33 04 09: Influence of Ice and Snow on
the Flashover Performance of Outdoor Insulators –
Part II : Effects of Snow, Electra no. 188, 2000,
4. CONCLUSIONS
pp. 55-69.
4. Chisholm W.A. et al.: The Cold-Fog Test. IEEE
1- The new infrastructure of UQAC used for a project
Trans. on Power Delivery, vol. 11, no. 4, 1996, pp.
in collaboration with Hydro-Québec for evaluating
1874-1880.
the electrical performance of insulators under
atmospheric icing conditions was presented. This 5. Drapeau J.F., Beauchemin R., Laflamme J., Martin
infrastructure offers great potential and flexibility for R., Roy M.: Tenue sous verglas de l'isolation
icing tests on a large scale. externe - Rapport #1 : Risques de contournements
en conditions de verglas et impacts des pertes
2. The electrical performance of a portion of a standard
d'équipements associées. Hydro-Québec Working
735-kV station post insulator with an arcing distance
Group: "Tenue sous verglas" (confidential), Nov.
of about 2 m (50% of full scale) was evaluated under
1996.
severe icing conditions. The method used
comprises an icing sequence at service voltage, a 6. Drapeau, J.F., Farzaneh, M., Roy, M.J., Chaarani,
curing sequence in the absence of HV but in the R., Zhang, J.: An Experimental Study of Flashover
presence of wind, a melting sequence and, lastly, an Performance of Various Post Insulators under Icing
evaluation sequence consisting in determining the Conditions. 2000 Annual Report of IEEE
maximum withstand voltage (VWS). The latter is Conference on Electrical Insulation and Dielectric
determined according to the method described in Phenomena (CEIDP), Victoria, B.C., Canada,
IEC 60507 for evaluating the VWS of polluted Oct. 2000, #00CH37132, pp. 359-364.
insulators. 7. Drapeau, J.F., Farzaneh, M., Roy, M.J., Chaarani,
3. Under wet-grown ice, known as the most dangerous R., Zhang, J.: An Exploratory Study for Ranking
type associated with the highest probability of Various Solutions for Improving Ice Flashover
flashover, and with an ice thickness of 15 mm Performance of Station Post Insulators..
measured on a monitoring cylinder, the VWS of the Proceedings of the 10th International Workshop on
portion tested was about 7% less than the service Atmospheric Icing of Structures, Brno, Czech
voltage. This confirms that the experimental Republic, June 2002, 6 p.
conditions selected for this study are in the range of 8. Farzaneh M.: Ice Accretion on H.V. Conductors and
the most severe cases to be encountered on the Insulators and Related Phenomena. Invited article,
Hydro-Québec transmission system. The results Philosophical Transactions, The Royal Society,
provide a solid basis for assessing new solutions London, no. 358, 2000, pp. 1-35.
aimed to improve electrical performances under 9. Farzaneh M., Brettschneider S.: Étude de la
icing conditions. tension de tenue des isolateurs de postes en
présence de glace atmosphérique en vue d’un
choix approprié de type et configuration
5. ACKNOWLEDGEMENTS d’isolateurs de postes à 735 kV, Volume 1 : Étude
en vue du choix d’isolateurs pour le futur poste
Montérégie. Presented to IREQ. Industrial Chair
This study has been carried out within the framework of
NSERC/Hydro-Québec/UQAC on Atmospheric
a joint research and development (CRD) project with
Icing of Power Network Equipment (CIGELE),
financial support from Hydro-Québec, the Natural
September 2001.
Sciences and Engineering Research Council (NSERC)

5
10. Farzaneh M., Chaarani R.: Performances 22. Fujimura T., Naito K., Hasegawa Y., Kawaguchi
électriques de divers types et configurations K.: Performance of Insulators Covered with Snow
d’isolateurs sous conditions de glace or Ice. IEEE Trans. on Power Apparatus &
atmosphérique artificielle. Report for Hydro- Systems, vol. PAS-98, 1979, pp. 1621-1631.
Québec, April 1999, 44 p. 23. Godard S.: Mesure des gouttelettes de nuage avec
11. Farzaneh M, Drapeau J.F.: AC Flashover un film de Collargol. Bulletin de l’Observatoire du
Performance of Insulators Covered with Artificial Puy de Dôme, no. 2, 1960, pp.41-46.
Ice. IEEE Transactions on Power Delivery, vol. 10, 24. IEEE Standard Techniques for High-Voltage
no. 2, April 1995, pp. 1038-1051. Testing, IEEE Std 4, IEEE Publication, October
12. Farzaneh M., Drapeau J.F., Brettschneider S., Roy 1995, p.129.
M.: Étude comparative de performance électrique 25. International Electrotechnical Commission:
des isolateurs externes dans des conditions de glace Artificial Pollution Tests on High Voltage
atmosphérique en vue du choix adéquat d’isolateurs Insulators to be Used on AC Systems. International
de postes à 735 kV. Colloquium on Icing, ACFAS Standard IEC 60507, 1991.
Conference, University of Sherbrooke, Canada,
26. Kannus K., Lahti K.: Electrical Behaviour of High
2001, http://icevolt.uqac.ca/cigele
Voltage Insulator Strings under Rime Ice.
(see “Actualités”).
Proceedings of the 9th International Workshop on
13. Farzaneh M. et al: Insulator Icing Test Methods and Atmospheric Icing of Structures, Chester, United
Procedure. A position paper prepared by the IEEE Kingdom, 2000, 8 p.
Task Force on Insulator Icing Test Methods. To be
27. Schneider H.M.: Artificial Ice Tests on
submitted in IEEE Power Delivery, April 2002.
Transmission Line Insulators – A Progress Report.
14. Farzaneh M., Kiernicki J.: Flashover Performance IEEE/PES Summer Meeting, San Francisco, USA,
of Ice-Covered Insulators. IEEE Canadian Journal paper A75-491-1, 1975, pp. 347-353.
of Electrical and Computer Engineering, vol. 22,
28. Shu L., Sun C., Zhang J., Gu L.: AC Flashover
no. 3, 1997, pp. 95-109.
Performance on Iced and Polluted Insulators for
15. Farzaneh M., Kiernicki J.: Flashhover Performance High Altitude Regions. Proceeding of the 7th
of IEEE Standard Insulators under Ice Conditions. International Symposium on High Voltage
IEEE Transactions on Power Delivery , vol. 12, Engineering, Dresden, Germany, vol. 4, paper
no. 4, October 1997, pp. 1602-1613. 43.13, 1991, pp. 303-306.
16. Farzaneh M., Kiernicki J.: Flashover Problems 29. Soucy L.: Effet de la fonte et de la pollution sur la
Caused by Ice Build-up on Insulators. IEEE tension de tenue maximale des isolateurs recouverts
Electrical Insulation Magazine, vol. 11, no. 2, 1995, de glace. M.Sc. Thesis, UQAC, October 1996, 132
pp. 5-17. p.
17. Farzaneh M., Kiernicki J., Drapeau J.F.: Ice 30. Volat C., Farzaneh M., Gakwaya A.: 3-D Modelling
Accretion on Energized Ice Insulators. of Potential and Electric Field Distributions around
International Journal of Offshore and Polar an Ice-covered Insulator. The Proceedings of the
Engineering. vol. 2, no. 3, September 1992, pp. 58th Annual Eastern Snow Conference, Ottawa,
228-233. Ontario, May 2001, 9 p.
18. Farzaneh M., Melo O.T.: Flashover Performance of 31. Yasui M., Naito K., Hasegawa Y.: AC Withstand
Insulators in the Presence of Short Icicles. Voltage Characteristics of Insulator String Covered
International Journal of Offshore and Polar with Snow. IEEE Trans. on Power Delivery, vol. 3,
Engineering, vol. 4, no. 2, 1994, pp. 112-118. no. 2, 1988.
19. Farzaneh M., Melo O.T.: Properties and Effect of
Freezing and Winter Fog on Outline Insulators. Mailing addresses :
Journal of Cold Regions Science and Technology,
Masoud Farzaneh
no. 19, February 1990, pp. 33-46.
NSERC/Hydro-Quebec /UQAC Industrial Chair
20. Farzaneh M., Volat C., Gakwaya A.: Electric Field on Atmospheric Icing of Power Network Equipment
Calculation around Ice-covered Insulator Using 555, boul. de l’Universite
Boundary Element Method. IEEE International Chicoutimi (Quebec) G7H 2B1 CANADA
Symposium on Electrical Insulation, Anaheim, Phone : +1 418 545-5044 Fax : +1 418 545 5032
California, April 2000, pp. 349-355. E-mail : farzaneh@uqac.ca
Jean-François Drapeau
21. Fikke S.M.,. Hanssen J.E, Rolfseng L.: Long Range
Institut de recherche d’Hydro-Quebec (IREQ)
Transported Pollution and Conductivity on 1800, boul. Lionel-Boulet
Atmospheric Ice on Insulators. IEEE Trans. on Varennes (Quebec) J3X 1S1 CANADA
Power Delivery, vol. 8, no. 3, 1993, pp. 1311-1321. Phone : +1 450 652-8323 Fax : +1 450 652 8181
E-mail : drapeau@ireq.ca

6
Changiz Tavakoli
NSERC/Hydro-Quebec /UQAC Industrial Chair
on Atmospheric Icing of Power Network Equipment
555, boul. de l’Universite
Chicoutimi (Quebec) G7H 2B1 CANADA
Phone : +1 418 545-5011 ext. 2192
Fax : +1 418 545 5032
E-mail : ctavakol@uqac.ca
Michel J. Roy
TransEnergie (Hydro-Quebec)
800, de Maisonneuve Est, 12e etage
Montreal (Quebec) H2L 4M8 CANADA
Phone : +1 514 840-3000 #5027 Fax : +1 514 840 5261
E-mail : roy.michel.j@hydro.qc.ca

You might also like