Description: MSB A1
Date: 12/8/2021
System voltage : 415 Volts Total net effective kVAr at 415V, Nc: 298.9 kVAr
Capacitor voltage : 525 Volts Total connected kVAr at 525V, Qc : 478.4 kVAr
** MD -- Maximum demand 1 1: 1: 1: 1: 1: 1 1 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
2 1: 1: 2: 2: 2: 2 2 1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
MCCB & contactors recommended ratings 3 1: 1: 2: 2: 4: 4 3 1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
4 1: 1: 2: 3: 3: 3 4 1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
kVAr Capacitance Capacitor MCCB Contactor 5 1: 1: 2: 4: 4: 4 5 1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
525 V uF current, A 25kA, A AC3, A 6 1: 1: 2: 4: 8: 8 6 1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
5 3* 19.3 4 10 9 7 1: 2: 2: 2: 2: 2 7 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
10 3* 38.5 9 15 12 8 1: 2: 3: 3: 3: 3 8 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
15 3* 57.7 13 20 22 9 1: 2: 3: 4: 4: 4 9 1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
20 3* 77.0 17 30 30 10 1: 2: 3: 6: 6: 6 10 1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
25 3* 96.2 22 30 30 11 1: 2: 4: 4: 4: 4 11 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
30 3* 115.5 26 40 40 12 1: 2: 4: 8: 8: 8 12 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8
40 3* 154.0 35 50 50
50 3* 192.5 43 60 65 Typical example for configuration of capacitor steps using above swicthing programs
60 3* 230.9 52 75 80
75 3* 288.7 65 100 105 Assuming total capacitor output required = 250kVAr, 525V
80 3* 307.9 70 100 105
100 3* 384.9 87 125 120 option 1:
120 3* 461.9 104 150 150 If a 6-step regulator is used, switching program no.2 can be selected :
150 3* 577.4 130 200 220 Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
160 3* 615.9 139 200 220
200 3* 769.8 174 250 250 option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Main MCCB, 25kA : 624 A Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare
REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.
-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
Counter check 623.81
easy way
mccb = KVAR * .625 * 2.1
PROJECT: 5290-RIANA GREEN EAST
Description: MSB-A2
Date: 12/8/2021
System voltage : 415 Volts Total net effective kVAr at 415V, Nc: 274.7 kVAr
Capacitor voltage : 525 Volts Total connected kVAr at 525V, Qc : 439.6 kVAr
** MD -- Maximum demand 1 1: 1: 1: 1: 1: 1 1 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
2 1: 1: 2: 2: 2: 2 2 1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
MCCB & contactors recommended ratings 3 1: 1: 2: 2: 4: 4 3 1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
4 1: 1: 2: 3: 3: 3 4 1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
kVAr Capacitance Capacitor MCCB Contactor 5 1: 1: 2: 4: 4: 4 5 1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
525 V uF current, A 25kA, A AC3, A 6 1: 1: 2: 4: 8: 8 6 1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
5 3* 19.3 4 10 9 7 1: 2: 2: 2: 2: 2 7 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
10 3* 38.5 9 15 12 8 1: 2: 3: 3: 3: 3 8 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
15 3* 57.7 13 20 22 9 1: 2: 3: 4: 4: 4 9 1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
20 3* 77.0 17 30 30 10 1: 2: 3: 6: 6: 6 10 1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
25 3* 96.2 22 30 30 11 1: 2: 4: 4: 4: 4 11 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
30 3* 115.5 26 40 40 12 1: 2: 4: 8: 8: 8 12 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8
40 3* 154.0 35 50 50
50 3* 192.5 43 60 65 Typical example for configuration of capacitor steps using above swicthing programs
60 3* 230.9 52 75 80
75 3* 288.7 65 100 105 Assuming total capacitor output required = 250kVAr, 525V
80 3* 307.9 70 100 105
100 3* 384.9 87 125 120 option 1:
120 3* 461.9 104 150 150 If a 6-step regulator is used, switching program no.2 can be selected :
150 3* 577.4 130 200 220 Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
160 3* 615.9 139 200 220
200 3* 769.8 174 250 250 option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Main MCCB, 25kA : 573 A Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare
REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.
-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
Counter check 573.22
easy way
mccb = KVAR * .625 * 2.1
PROJECT: 5290-RIANA GREEN EAST
Description: MSB-BC1
Date: 12/8/2021
System voltage : 415 Volts Total net effective kVAr at 415V, Nc: 210.5 kVAr
Capacitor voltage : 525 Volts Total connected kVAr at 525V, Qc : 336.9 kVAr
** MD -- Maximum demand 1 1: 1: 1: 1: 1: 1 1 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
2 1: 1: 2: 2: 2: 2 2 1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
MCCB & contactors recommended ratings 3 1: 1: 2: 2: 4: 4 3 1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
4 1: 1: 2: 3: 3: 3 4 1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
kVAr Capacitance Capacitor MCCB Contactor 5 1: 1: 2: 4: 4: 4 5 1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
525 V uF current, A 25kA, A AC3, A 6 1: 1: 2: 4: 8: 8 6 1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
5 3* 19.3 4 10 9 7 1: 2: 2: 2: 2: 2 7 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
10 3* 38.5 9 15 12 8 1: 2: 3: 3: 3: 3 8 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
15 3* 57.7 13 20 22 9 1: 2: 3: 4: 4: 4 9 1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
20 3* 77.0 17 30 30 10 1: 2: 3: 6: 6: 6 10 1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
25 3* 96.2 22 30 30 11 1: 2: 4: 4: 4: 4 11 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
30 3* 115.5 26 40 40 12 1: 2: 4: 8: 8: 8 12 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8
40 3* 154.0 35 50 50
50 3* 192.5 43 60 65 Typical example for configuration of capacitor steps using above swicthing programs
60 3* 230.9 52 75 80
75 3* 288.7 65 100 105 Assuming total capacitor output required = 250kVAr, 525V
80 3* 307.9 70 100 105
100 3* 384.9 87 125 120 option 1:
120 3* 461.9 104 150 150 If a 6-step regulator is used, switching program no.2 can be selected :
150 3* 577.4 130 200 220 Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
160 3* 615.9 139 200 220
200 3* 769.8 174 250 250 option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Main MCCB, 25kA : 439 A Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare
REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.
-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
Counter check 439.30
easy way
mccb = KVAR * .625 * 2.1
PROJECT: 5290-RIANA GREEN EAST
Description: MSB-BC2
Date: 12/8/2021
System voltage : 415 Volts Total net effective kVAr at 415V, Nc: 212.8 kVAr
Capacitor voltage : 525 Volts Total connected kVAr at 525V, Qc : 340.6 kVAr
** MD -- Maximum demand 1 1: 1: 1: 1: 1: 1 1 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
2 1: 1: 2: 2: 2: 2 2 1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
MCCB & contactors recommended ratings 3 1: 1: 2: 2: 4: 4 3 1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
4 1: 1: 2: 3: 3: 3 4 1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
kVAr Capacitance Capacitor MCCB Contactor 5 1: 1: 2: 4: 4: 4 5 1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
525 V uF current, A 25kA, A AC3, A 6 1: 1: 2: 4: 8: 8 6 1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
5 3* 19.3 4 10 9 7 1: 2: 2: 2: 2: 2 7 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
10 3* 38.5 9 15 12 8 1: 2: 3: 3: 3: 3 8 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
15 3* 57.7 13 20 22 9 1: 2: 3: 4: 4: 4 9 1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
20 3* 77.0 17 30 30 10 1: 2: 3: 6: 6: 6 10 1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
25 3* 96.2 22 30 30 11 1: 2: 4: 4: 4: 4 11 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
30 3* 115.5 26 40 40 12 1: 2: 4: 8: 8: 8 12 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8
40 3* 154.0 35 50 50
50 3* 192.5 43 60 65 Typical example for configuration of capacitor steps using above swicthing programs
60 3* 230.9 52 75 80
75 3* 288.7 65 100 105 Assuming total capacitor output required = 250kVAr, 525V
80 3* 307.9 70 100 105
100 3* 384.9 87 125 120 option 1:
120 3* 461.9 104 150 150 If a 6-step regulator is used, switching program no.2 can be selected :
150 3* 577.4 130 200 220 Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
160 3* 615.9 139 200 220
200 3* 769.8 174 250 250 option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Main MCCB, 25kA : 444 A Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare
REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.
-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
Counter check 444.12
easy way
mccb = KVAR * .625 * 2.1
PROJECT: 5290-RIANA GREEN EAST
Description: MSB-D
Date: 12/8/2021
System voltage : 415 Volts Total net effective kVAr at 415V, Nc: 174.2 kVAr
Capacitor voltage : 525 Volts Total connected kVAr at 525V, Qc : 278.8 kVAr
** MD -- Maximum demand 1 1: 1: 1: 1: 1: 1 1 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1: 1
2 1: 1: 2: 2: 2: 2 2 1: 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
MCCB & contactors recommended ratings 3 1: 1: 2: 2: 4: 4 3 1: 1: 2: 2: 4: 4: 4: 4: 4: 4: 4: 4
4 1: 1: 2: 3: 3: 3 4 1: 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3
kVAr Capacitance Capacitor MCCB Contactor 5 1: 1: 2: 4: 4: 4 5 1: 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4
525 V uF current, A 25kA, A AC3, A 6 1: 1: 2: 4: 8: 8 6 1: 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8
5 3* 19.3 4 10 9 7 1: 2: 2: 2: 2: 2 7 1: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2: 2
10 3* 38.5 9 15 12 8 1: 2: 3: 3: 3: 3 8 1: 2: 3: 3: 3: 3: 3: 3: 3: 3: 3: 3
15 3* 57.7 13 20 22 9 1: 2: 3: 4: 4: 4 9 1: 2: 3: 4: 4: 4: 4: 4: 4: 4: 4: 4
20 3* 77.0 17 30 30 10 1: 2: 3: 6: 6: 6 10 1: 2: 3: 6: 6: 6: 6: 6: 6: 6: 6: 6
25 3* 96.2 22 30 30 11 1: 2: 4: 4: 4: 4 11 1: 2: 4: 4: 4: 4: 4: 4: 4: 4: 4: 4
30 3* 115.5 26 40 40 12 1: 2: 4: 8: 8: 8 12 1: 2: 4: 8: 8: 8: 8: 8: 8: 8: 8: 8
40 3* 154.0 35 50 50
50 3* 192.5 43 60 65 Typical example for configuration of capacitor steps using above swicthing programs
60 3* 230.9 52 75 80
75 3* 288.7 65 100 105 Assuming total capacitor output required = 250kVAr, 525V
80 3* 307.9 70 100 105
100 3* 384.9 87 125 120 option 1:
120 3* 461.9 104 150 150 If a 6-step regulator is used, switching program no.2 can be selected :
150 3* 577.4 130 200 220 Capacitor bank : 25: 25: 50: 50: 50: 50 kVAR -- 6 steps, 250 kVAr
160 3* 615.9 139 200 220
200 3* 769.8 174 250 250 option 2:
If a 12-step regulator is used, switching program no. 4 can be selected :
Main MCCB, 25kA : 364 A Capacitor bank : 10: 10: 20: 30: 30: 30: 30: 30: 30: 30 -- 10 steps, 250kVAr, 2 steps spare
REMARK
-- If above rating does not match to normal MCCB rating, select a type with rating slightly higher than the above.
-- Contactor ratings recommended above are based on common ranges available in the market. Other ranges closest
to recommended ratings are acceptable. Minimum requirement is 1.5 times rated capacitor current, AC3 rating.
Counter check 363.54
easy way
mccb = KVAR * .625 * 2.1