80 Masterpact Schneider Electric

Masterpact Electrical diagrams

Presentation 1
Functions and characteristics 9
Dimensions and connection 53

Masterpact NT06 to NT16 82


Masterpact NW08 to NW63 84
Masterpact NT and NW 86

Installation recommendations 91
Additional characteristics 115
References 121

81 Masterpact Schneider Electric


Electrical diagrams Masterpact NT06 to NT16
Fixed and drawout devices

The diagram is shown with circuits


de-energised, all devices open, connected
and charged and relays in normal position.

Power Control unit Remote operation


power upstream cb downstream cb

to-close

charged
ready-
N L1 L2 L3

fault

fault
Z1
Z2

Z3

Z4
Z5
Z1
Z2

Z3

Z4

Z5
AT BPF
M6C
BPO

C12
474

484

182

184

252
254
Q1
Q2
Q3

A2
A3
VN

C2
C3
D2
V1
V2
V3

K2
Z1
Z2
Z3
Z4
Z5

B3
B2
82

84
Q MCH

I MX1 XF
S1 S2 SDE2 SDE1 MN MX2
Micrologic PF CH
U
Res
M2C M6C or
or
or
E46133

E46136A
E46135A

E46137A

E46139A
E46138A
E46132A

471
E46555B

D1

C11

C1

A1

B1
181

K1

251
81
F2+
M1
M2
M3

T1
T2
T3
T4
F1
SG1
SG2

24 V DC
X1

X2

Control unit Remote operation


Terminal block marking Com UC1 UC2 UC3 UC4 / M2C / M6C SDE2 / Res SDE1 MN / MX2 MX1 XF PF MCH

E5 E6 Z5 M1 M2 M3 F2+ V3 / 484 / Q3 184 / K2 84 D2 / C12 C2 A2 254 B2

E3 E4 Z3 Z4 T3 T4 VN V2 / 474 / Q2 182 82 C3 A3 252 B3

E1 E2 Z1 Z2 T1 T2 F1 – V1 / 471 / Q1 181 / K1 81 D1 / C11 C1 A1 251 B1

A P H Control unit Remote operation

c c c Com: E1-E6 communication SDE2: Fault-trip indication contact


or
c c c UC1 : Z1-Z5 zone selective interlocking; Res : Remote reset
Z1 = ZSI OUT SOURCE
Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE SDE1: Fault-trip indication contact (supplied as standard)
Z4 = ZSI IN ST (short time)
Z5 = ZSI IN GF (earth fault) MN : Undervoltage release
c c c M1 = Vigi module input (Micrologic 7) or
MX2 : Shunt release
c c c UC2 : T1, T2, T3, T4 = external neutral;
c c c M2, M3 = Vigi module input MX1 : Shunt release (standard or communicating)
(Micrologic 7)
XF : Closing release (standard or communicating)
c c c UC3 : F2+, F1– external 24 DC power
supply PF : Ready-to-close contact
c c VN external voltage connector (optional)
MCH: electric motor
c c UC4 : optional external voltage connector
or
c c M2C : 2 programmable contacts (internal relay); Note:
When communicating MX or XF releases are used, the third wire
ext. 24V DC power supply required (C3,A3) must be connected even if the communication module is
or
not installed.
c c M6C : 6 programmable contacts (external relay);
ext. 24V DC power supply required.

A : Digital ammeter
P: A + power meter + additional protection
H: P + harmonics

82 Masterpact Schneider Electric


Indication contacts Craddle contacts

open closed disconnected connected Test

822
824
812
814

332
334
322

324
312

314

914
912
42

32

22

12
44

34

24

14

OF4 OF3 OF2 OF1 CT1


CD2 CD1 CE3 CE2 CE1

E47074A
E46134A
E47075A
E46141A

321
331
41

31

21

821

311
11

811

911
Indication contacts Craddle contacts
OF4 OF3 OF2 OF1 CD2 CD1 CE3 CE2 CE1 CT1

44 34 24 14 824 814 334 324 314 914

42 32 22 12 822 812 332 322 312 912

41 31 21 11
821 811 331 321 311 911

Indication contacts Craddle contacts


OF4 / OF3 / OF2 / OF1 : ON/OFF indication contacts CD2: Disconnected CE3: Connected CT1: Test
CD1 position CE2 position position
contacts CE1 contacts contacts
(*) Spring charging motor 440/480 V AC
(380 V motor + additional resistor)

CN1 - 440/480 V
E47484

9 11
“spring
charged“ R
light
440/480 V
B3 B2

MCH
380V

CH

B1
key:
CN2 - 440/480 V Drawout device only

XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard

Interconnected connections
(only one wire per connection point)

83 Masterpact Schneider Electric


Electrical diagrams Masterpact NW08 to NW63
Fixed and drawout devices

The diagram is shown with circuits


de-energised, all devices open, connected
and charged and relays in normal position.

Power Control unit Remote operation


power upstream cb downstream cb

to-close

charged
ready-
N L1 L2 L3

fault

fault
Z1
Z2

Z3

Z4
Z5
Z1
Z2

Z3

Z4

Z5
AT BPF
M6C
BPO

C12
474

484

182

184

252
254
VN

Q1
Q2
Q3

A2
A3
C2
C3
D2
V1
V2
V3

Z1
Z2
Z3
Z4
Z5

K2
82

84

B3
B2
Q MCH

I SDE1 MN MX2 MX1 XF


S1 S2 SDE2
Micrologic PF CH
U
Res
M2C M6C or
or
ou E46133

E46136A
E46135A

E46137A

E46139A
E46138A
E46132A

471

D1

C11

C1

A1
181

K1

251
81

B1
F2+
M1
M2
M3

T1
T2
T3
T4
F1
SG1
SG2

24 V DC
X1

X2
E46555B

Control unit Remote operation


Terminal block marking Com UC1 UC2 UC3 UC4 M2C / M6C SDE2 / Res SDE1 MN / MX2 MX1 XF PF MCH

E5 E6 Z5 M1 M2 M3 F2+ V3 484 / Q3 184 / K2 84 D2 / C12 C2 A2 254 B2

E3 E4 Z3 Z4 T3 T4 VN V2 474 / Q2 182 82 C3 A3 252 B3

E1 E2 Z1 Z2 T1 T2 F1 – V1 471 / Q1 181 / K1 81 D1 / C11 C1 A1 251 B1

A P H Control unit Remote operation

c c c Com: E1-E6 communication SDE2: Fault-trip indication contact


UC1 : Z1-Z5 zone selective interlocking; or
c c c
Z1 = ZSI OUT SOURCE Res : Remote reset
Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE
Z4 = ZSI IN ST (short time) SDE1: Fault-trip indication contact (supplied as standard)
Z5 = ZSI IN GF (earth fault)
c c c M1 = Vigi module input (Micrologic 7) MN : Undervoltage release
or
c c c UC2 : T1, T2, T3, T4 = external neutral; MX2 : Shunt release
c c c M2, M3 = Vigi module input
(Micrologic 7) MX1 : Shunt release (standard or communicating)

c c c UC3 : F2+, F1– external 24 DC power XF : Closing release (standard or communicating)


supply
c c VN external voltage connector (optional) PF : Ready-to-close contact
c c UC4 : V1, V2, V3 optional external voltage
MCH: electric motor
connector
c c M2C : 2 programmable contacts (internal relay);
ext. 24V DC power supply required Note:
or When communicating MX or XF releases are used, the third wire
(C3,A3) must be connected even if the communication module is
c c M6C : 6 programmable contacts not installed.
(to be connected to the external module
M6C);
ext. 24V DC power supply required

A : Digital ammeter
P: A + power meter + additional protection
H: P + harmonics

84 Masterpact Schneider Electric


Indication contacts Craddle contacts

not
connected
open closed closed or connected disconnected connected Test
connected and closed
and open

832
834
822
824
812
814
332
334
322

324
312

314

934

924

914
932

922

912
..2

..4

..8
..6
42

32

22

12
44

34

24

14

EF . .
OF4 OF3 OF2 OF1 OF . . OF CT3 CT2 CT1
CD3 CD2 CD1 CE3 CE2 CE1

or

CE
E46140

E46142A
E46134A
E46141A

E46131A

321
331
41

31

21

311
11

831

821
..1

..5

911
931

921
811
Indication contacts Craddle contacts
OF4 OF3 OF2 OF1 OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 CD3 CD2 CD1 CE3 CE2 CE1 CT3 CT2 CT1

44 34 24 14 244 234 224 214 144 134 124 114 834 824 814 334 324 314 934 924 914

42 32 22 12 242 232 222 212 142 132 122 112 832 822 812 332 322 312 932 922 912

41 31 21 11 241 231 221 211 141 131 121 111 831 821 811 331 321 311 931 921 911
or or or or or or or or or or
EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CE6 CE5 CE4 CE9 CE8 CE7

248 238 228 218 148 138 128 118 364 354 344 394 384 374

246 236 226 216 146 136 126 116 362 352 342 392 382 372

245 235 225 215 145 135 125 115 361 351 341 391 381 371

Indication contacts Craddle contacts

OF4 : ON/OFF OF24 : ON/OFF CD3: Disconnected CE3: Connected CT3: Test
OF3 indication or indication contacts CD2 position CE2 position CT2 position
OF2 contacts EF24 Combined “ connected-deconnected” CD1 contacts CE1 contacts CT1 contacts
OF1 indication contacts
or or
OF23 or
EF23
CE6: Connected CE9:Connected
OF22 or CE5 position CE8 position
EF22 CE4 contacts CE7 contacts
OF21 or
EF21 or

OF14 or CD6:Disconnected
EF14 CD5 position
OF13 or key: CD4 contacts
EF13 Drawout device only

OF12 or XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard


EF12
OF11 or Interconnected connections
EF11 (only one wire per connection point)

85 Masterpact Schneider Electric


Electrical diagrams Masterpact NT and NW
Communications option
24 VDC external power supply

Connection of the communications option


E47593

914 812 314 912 812 312


N L1 L2 L3
microswitch
built into
COM module
OF

SDE MX1
VN
V1
V2
V3

Z1
Z2
Z3
Z4
Z5
com
911 811 311 911 811 311
PF

CH XF
com CT CD CE CT CD CE
+ +
Q B'
A'
Modbus Digipact
I device B COM craddle COM craddle
Micrologic communication A BB
U module BB
+

shield

BB
BB
B' A' B A +

CCP 303
(2)
F2+

E1
E2
E3
E4
E5
E6
M1
M2
M3

T1
T2
T3
T4

CCP 303
F1

5
H1 H2
4

BAT
module
3 Modbus Digipact
junction junction
(1) 2
H3 H4 block block
1 CJB306
(2)
G1 G2 0
yellow

24 V
brown

AD
black

white

0V
blue

module
red

L3 L4 E1 E2 E3 E4 E5 E6 0V 24 V
+ A B A' B' Modbus 24 VDC 24 VDC
communication
+ / / BB BB + Digipact 1A
power supply
DC 150

110/240 V AC E3 / E4 twisted pair


24/125 V DC E5 / E6 twisted pair

None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power-supply (AD module) is
required for certain operating configurations as indicated in the table below.
circuit breaker closed open
voltage measurement inputs powered powered not powered
M2C, M6C programmable contacts option yes yes yes
Protection function no no no
Display function no (3) no (4) yes
Time-stamping function no no yes (5)
Circuit-breaker status indications and no no no
control via communications bus
Identification, settings, operation and no (3) no (4) yes
maintenance aids via communications bus

The communications bus requires its own 24 V DC power source (E1, E2). This source
is not the same as the 24 V DC external power-supply module (F1-, F2+).
In case of using the 24 VDC external power supply (AD module), maximum cable length
between 24 VDC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.
The BAT battery module, mounted in series upstream of the AD module, ensures an
uninterrupted supply of power if the AD module power supply fails.
The voltage measurement inputs are standard equipment on the downstream
connectors of the circuit breaker.
External connections are possible using the PTE external voltage measurement input
option. With this option, the internal voltage measurement inputs are disconnected and
terminals VN, V1 and V2 are connected only to the control unit (Micrologic P and H only).
(1) draw-out device equipped with Modbus craddle COM. The PTE option is required for voltages less than 100 V and greater than 690 V (in which
(2) draw-out device equipped with Digipact craddle COM. case a voltage transformer is compulsory). For three-pole devices, the system is
(3) except for Micrologic A control units (if current < 20% In). supplied with terminal VN connected only to the control unit (Micrologic P and H).
(4) except for Micrologic A control units. When the PTE option is implemented, the voltage measurement input must be protected
(5) time setting is manual and can be carried out against short-circuits. Installed as close as possible to the busbars, this protection
automatically by the supervisor via the communications bus. function is ensured by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat.
no. 21104 and 21117). This voltage measurement input is reserved exclusively for the
control unit and must not ever be used to supply other circuits outside the switchboard.

86 Masterpact Schneider Electric


Examples using the COM communications option

Switchboard display unit CDM303 + CSD309


This architecture provides remote display of the d < 1 km

E47976
variables managed by Micrologic control units DMB300 5 CCP303
equipped with the eco COM Modbus module. 1
4
c I (Micrologic A) 2
c I, U, P, E (Micrologic P) 3
3
c I, U, P, E, THD (Micrologic H) 4 I U P ?

No programming is required. switchboard 2


display unit
For Micrologic A control unit (if current < 20% In), it is 1
recommended to use the 24 VDC external power 0
supply (AD module).
24 V
0V
Modbus power circuit
junction 24 VDC breaker
block 1A
CJB 306

Communicating switchboard
This configuration provides remote display and control
of Masterpacts equipped with the Modbus or Digipact
COM module. The Digipact bus can be combined with
the Modbus bus.
E47977

Software PC running PC running


Micrologic utilities Micrologic utilities
SMS SMS
PLC PLC

TCP/IP

Communication
interface
RS 232C Ethernet
RS 485 RS 485

Bus Modbus Bus Modbus

communication
Bus
Data
concentrator DC150

Device

UA150 SC150 PM150 Masterpact Masterpact PM300


measure Sepam Vigilohm Altivar
source contraf measure COM Digipact COM Modbus
change-ower interface

Digipact Bus Modbus Bus

87 Masterpact Schneider Electric


Electrical diagrams Masterpact NT and NW
Earth-fault and earth-leakage protection
Neutral protection
Zone selective interlocking
External sensor (CT) for residual earth-fault protection

Connection of current-transformer secondary N L1 L2 L3

E47591B
circuit for external neutral

VN
V1
V2
V3

Z1
Z2
Z3
Z4
Z5
Masterpact equipped with a Micrologic 6 A/P/H:
c shielded cable with 2 twisted pairs
c SG1 twisted with SG2
c X1 twisted with X2
c shielding connected to GND on one end only
c maximum length 5 meters
c cable cross-sectional area 0.4 to 1.5 mm2
c recommended cable: Belden 9552 or equivalent.
Q
If supply is via the top, follow the shematics.
If supply is via the bottom, control wiring is identical; I
for the power wiring, H1 is connected to the source Micrologic 6
side, H2 to the load side. U

For four-pole versions, for residual earth-fault


protection, the current transformer for the external
neutral is not necessary.
If the 2000/6300 current transformer is used:
c signals SG1 and SG2 must be wired in series

F2+
M1
M2
M3

T1
T2
T3
T4
F1
c signals X1 and X2 must be wired in parallel.
VN
Connection for signal VN is required only for power H2 SG1
measurements (3 Ø, 4 wires, 4CTs). SG2
X1

X2
H1
GND

External transformer for source ground return (SGR) earth-fault protection

Connection of the secondary circuit


Masterpact equipped with a Micrologic 6 A/P/H:
c unshielded cable with 1 twisted pair
c maximum length 150 meters
VN
V1
V2
V3

Z1
Z2
Z3
Z4
Z5
c cable cross-sectional area 0.4 to 1.5 mm2
c terminals 5 and 6 may not be used at the same time
c use terminal 5 for NW08 to 40
c use terminal 6 for NW40b to 63
c recommended cable: Belden 9409 or equivalent.

I
Micrologic 6
U
F2+
M1

M2
M3

T1
T2
T3
T4
F1

or

H1 X1 12 5 6 7 10 11
1 MDGF module 9
8
E47592

H2 X2 3 13 14
PE

88 Masterpact Schneider Electric


Earth-leakage protection

Connection of the rectangular-sensor secondary N L1 L2 L3

E47974B
circuit
Masterpact equipped with a Micrologic 7 A/P/H:

VN
c unshielded cable with 3 twisted conductors:

V1
V2
V3

Z1
Z2
Z3
Z4
Z5
v M1, M2, M3 twisted together
c maximum length 4 metres
c cable cross-sectional area 0.4 to 1.5 mm2
c recommended cable: Belden 9493 or equivalent.

I
Micrologic 7
U

F2+
M1

M2
M3

T1
T2
T3
T4
F1
M1
M2

M3

Neutral protection

c Three pole breaker:


v Masterpact equipped with Micrologic P or H
v the current transformer for external neutral is
necessary (the wiring diagram is identical to the one
used for the residual earth-fault protection).
c Four pole breaker:
v Masterpact equipped with Micrologic A, P or H
v the current transformer for external neutral is not
necessary.

Zone selective interlocking


E47975B

A pilot wire interconnects a number of circuit breakers


equipped with Micrologic A/P/H control units, as illustrated upstream A Z1
circuit breaker Z2 tsd = 0,3
in the diagram above.
The control unit detecting a fault sends a signal upstream Z3
and checks for a signal arriving from downstream. If there Z4
is a signal from downstream, the circuit breaker remains Z5
closed for the full duration of its tripping delay. If there is
no signal from downstream, the circuit breaker opens fault 1
immediately, whatever the tripping-delay setting.
Fault 1.
Only circuit breaker A detects the fault. Because it
receives no signal from downstream, it immediately opens
in spite of its tripping delay set to 0.3. B Z1
Z2
Fault 2. tsd = 0,2
Z3
Circuit breakers A and B detect the fault. Circuit breaker A
Z4
receives a signal from B and remains closed for the full
duration of its tripping delay set to 0.3. Circuit breaker B Z5
does not receive a signal from downstream and opens
immediately, in spite of its tripping delay set to 0.2. fault 2

Z1 downstream Z1
Z2 circuit breaker Z2
Z3 Z3
Z4 Z4
Z5 Z5
Note: the maximum permissible distance between
two devices is 3000 m and the maximum number
of devices is 100.

89 Masterpact Schneider Electric