Tuning power plant controls takes nerves of steel and an intimate knowledge of plant systems gained
only by experience. Tuning controls also requires equal parts art and science, which probably is why
there are so few tuning experts in the power industry. In Part I of a two-part series, we explore a mix of the
theoretical and practical aspects of tuning boiler controls.

On my first project as a combustion control engineer, I was responsible for loop checks and for watching the
experts tune the system controls. The first loop I tried to tune solo was the drum level control. At that time the
trend-tune program defaulted to a 2-minute window, and no one bothered to mention to me that the proper time
span to tune drum level control to is 20 to 30 minutes. I also zoomed in on the drum level, which has a normal
range of ±15 inches, though my trend range was ±3 inches. Finally, I did not know that drum level can be a very
“noisy” signal, so the hours I spent trying to tune out that noise were wasted.

Eventually, I got the bright idea to add a little derivative to the loop control. In the time it took to program 0.01 as
the derivative gain and then immediately remove it, the boiler tripped. Thus began my career in boiler tuning.

In the 20-plus years since my inauspicious debut, I’ve had the opportunity to successfully tune hundreds of
boilers, new and old, that needed either a control loop tweak or a complete overhaul.

Many inexperienced engineers and technicians approach boiler tuning with a heavy hand and little insight into the
inner workings of individual control loops, how highly interconnected they are with other loops in the boiler system,
or what change should be expected from the physical equipment the loops are to control. My purpose in writing
this article is to explore these fundamentals and share my experiences. I trust these insights will be of value to the
power industry and specifically to those who want to tune boilers for rock-solid stability yet agility when responding
to process changes.

What Constitutes Good Control?


Every boiler ever built has its own set of peculiarities. Even two boilers built at the same plant at the same time to
the same drawings will have unique quirks and special tuning issues. I begin with a description of the various
boiler and subsystem control loops before moving to good boiler-tuning practices that are sufficiently robust to
accommodate even minute differences between what should be identical boilers.

From a pure controls perspective, the most important goal is to tune for repeatability of a value, not the actual
value itself. We do not care that there are exactly 352,576.5 pph of fuel going into the furnace; we only care that,
for a given fuel master demand, we get the same amount every time. There will be process variation, of course,
but the goal is to tune the controls to keep that variation as small as possible and then tune for accuracy.

Boiler control processes are where I will begin. Additional control functions outside the furnace will be explored in
Part II in a future issue of POWER.

Operator Controls
The operator’s window into the control system is referred to as a master or as a hand/auto station, control station,
or operator station. The station is the operator interface to a given control loop and is typically a switch located on
the control panel in older plants or accessible from the operator’s keyboard in those equipped with all-digital
controls. Typically, the control station allows the operator to move between manual and automatic modes of
operation. All of the control loops discussed in this article combine to form the set of controls that manage the key
boiler operating functions.

When a control loop is placed in manual mode, the operator will have direct control of the output. In automatic
mode the output is modulated by the proportional-integralderivative (PID) controller. In automatic mode the
operator usually has some control over the set point or operating point of the process, either directly or through
the use of a bias signal. Occasionally, as in primary airflow control, the set point is displayed either on the
controller located on the control panel or on the computer screen graphic display. Cascade mode is a subset of
the automatic mode in which the operator turns over control of the set point to the master, whose internal logic
generates the set point.

Usually, there is some digital logic that requires the station to be interlocked to manual, as well as control output
tracking and set point tracking.

http://powerservices.lakho.com/2009/04/06/boiler-tuning-basics-part-i/ 2/19/2011
Boiler-Tuning Basics, Part I | Power Industry News Page 2 of 7

Furnace Pressure Control


Furnace pressure control is a fairly simple loop, but it’s also one that has important safety implications. The
National Fire Protection Association (NFPA) codes, such as NFPA 85: Boiler and Combustion Systems Hazards
Code, are dedicated to fire and furnace explosion and implosion protection. Before you begin tuning a boiler, you
must
read and understand the NFPA codes that apply to your boiler.

Balanced draft boilers use induced draft (ID) fans and/or their inlet dampers to control boiler furnace pressure.
The typical control system has one controller that compares the difference between the furnace pressure and the
furnace pressure set point that uses a feedforward signal usually based on forced draft (FD) fan master output.
The output from the controller typically is fed through an ID fan master control station. Smaller units may have a
single ID fan, but larger units usually have two or more ID fans. The most I have seen is eight ID fans for a single
unit. In this case, the output from the control loop or master is distributed to the individual fan control stations.

The NFPA also requires some additional logic for the furnace pressure control loop to ensure adequate operating
safety margins. There should be high and low furnace pressure logic to block the ID fan from increasing or
decreasing speed, as is appropriate. For example, because this fan sucks flue gas out of the furnace, on a high
furnace pressure signal the fan should be blocked from decreasing speed and on a low furnace pressure signal it
should be blocked from increasing speed. On a very negative furnace pressure signal, there should be an
override that closes the ID inlet damper or decreases ID fan speed. The settings of these signals are determined
by the boiler and fan supplier during the design of the plant.

blowing-hot-air

1. Blowing hot air. Induced draft fans are used to control furnace pressure and primary combustion
airflow. In this test, induced draft fan and furnace pressure respond to a step increase in furnace pressure
set point.

favorite-trend

http://powerservices.lakho.com/2009/04/06/boiler-tuning-basics-part-i/ 2/19/2011
Boiler-Tuning Basics, Part I | Power Industry News Page 3 of 7

2. Favorite trend. I typically monitor airflow, O2 content in the flue gas, and furnace pressure control when
I tune airflow. The particular response of those variables was observed after a 20% load increase in
coordinated control mode.

Also, on a main fuel trip (MFT) there should be MFT kicker logic. An MFT occurs when the burner management
system detects a dangerous condition and shuts down the boiler by securing the fuel per NFPA and boiler
manufacturer requirements. When fuel is removed, the flame within the furnace collapses violently, which can
cause a lot of wear and tear on the boiler and related boiler equipment. It also presents the very real danger of an
implosion. The MFT kicker should immediately reduce the control output to the fan(s) proportional to the load
being carried at the time of the MFT and then release the device back to normal operation.

I am constantly amazed at how well furnace pressure can be controlled, especially when you consider the amount
of fuel and air being injected into a ball of fire many stories tall and the ferocious and chaotic environment inside a
boiler. The fact that a welltuned system can maintain furnace pressure to –0.5 inches H2O is remarkable.

A typical mistake made by boilers tuners is the use of very fast integral action to the furnace pressure controller.
Furnace pressure changes quickly, but not instantaneously, so consider the size of your furnace and the amount
of duct work between the furnace and the fans as capacitance in the system, because air is compressible. I
recommend restraint when tuning furnace pressure when it comes to adding integral gain. Interestingly, the
feedforward for almost every boiler is on the order of 0% to 100% in, and 0% to 80% out.

The trends in the following figures show what you should expect to see from your furnace pressure control. The
plant from which these data were taken uses both fan inlet damper position and fan speed to control furnace
pressure. Figure 1 illustrates an ID fan tuning trend and the reaction of the ID fans and the furnace pressure to a
change in set point.

Airflow and Oxygen Trim Forced draft fans are typically placed in automatic after the ID fan master is placed in
automatic. Usually, the FD fan master is only controlling airflow; however, some boilers are designed with
secondary airflow dampers that control the airflow. In this case the FD fan will control the secondary air duct
pressure to the dampers (Figure 2).

extra-air 3. Extra air is a good thing. A typical O2 set point curve for a
coal-fired plant is a function of boiler firing rate or boiler
demand. Minimum levels of air are required so that reducing
conditions in the furnace never occur.

Air and, consequently, O2 control are critical to the safe and


efficient operation of a boiler. The airflow signal is normally
measured in terms of a percentage and is usually not available in
volumetric or mass flow units. The obvious question is,
“Percentage of what?” The answer is the percentage of airflow that
is available from a given fan or system of fans. The actual
measured pounds per hour of air does not matter, because air is
free, and the final arbiter of proper airflow is the O2 content in the
flue gas (gases leaving the furnace). Because of variations in coal
heat content, air temperature, and combustion conditions inside a
boiler, we ensure proper burning by measuring the amount of
oxygen content in the flue gas, commonly referred to simply as O2.

Pulverized coal has an interesting property: Under certain


conditions of heat in a low-oxygen atmosphere, coal can self-ignite
or even explode. Therefore, personnel safety and equipment protection require boiler operators to maintain
excess O2 in the flue gas. The amount of excess O2 is determined by the load on the plant and the type and
design of boiler. Typically, the load signal used is steam flow. In any coal-fired boiler, airflow demand is a function
of the boiler firing rate or boiler demand (Figure 3). Gas- and oilfired boilers have lower O2 requirements at higher
loads.

The term cross-limiting refers to the function of fuel flow that limits the decrease in air demand and the function of
airflow that limits the increase in fuel demand. When decreasing load, the air demand follows its lag function and
the fuel demand follows the boiler demand to ensure that there is always more air than fuel going into a furnace

http://powerservices.lakho.com/2009/04/06/boiler-tuning-basics-part-i/ 2/19/2011
Boiler-Tuning Basics, Part I | Power Industry News Page 4 of 7

so explosive conditions never develop inside the furnace. When increasing load, the opposite is true. This is truly
an elegant piece of logic.

The output from the boiler master is the boiler demand. Cross-limited air demand is developed by choosing the
highest of four calculated values: boiler demand function, the lag of the boiler demand signal, a minimum value
(per the boiler manufacturer under the NFPA codes), and a function of the actual fuel flow. The cross-limited fuel
demand is selected from the least of three signals: boiler demand function, a lag of boiler demand, and a function
of actual airflow. When load is increased, air demand follows the function of the boiler demand and the fuel
demand follows its lag of the boiler demand.

To develop the air demand for your boiler, hold your O2 trim controller in manual at 50% output. At a low, medium,
and high load, place your FD fan master, or secondary airflow dampers (if the boiler is so equipped), and your fuel
master in manual. Then manipulate the airflow until you find the amount that satisfies your O2 set point
requirement, using stack opacity as a reality check on the O2 set point. Next, manipulate the airflow
characterization curve as required to allow the air demand to equal or slightly exceed the fuel flow or boiler
demand. Record the airflow required for that fuel flow and then move on to another fuel flow setting. Three points
should be sufficient for a good airflow curve.

Typically, the airflow measurement is a differential pressure taken in air ductwork and requires a square root in
order to make it linear. Ensure that your signal is also temperature-compensated. Each boiler should have an
airflow characterization curve that should be a virtual straight line. If it isn’t, I would be concerned about
unexplained “correction factors” or “magic numbers” that should not be necessary.

Next, the characterized airflow is multiplied against a function of the O2 trim controller. The O2 trim control loop
uses the set point curve, discussed above, plus an operator bias to calculate an O2 set point for various loads.
This set point is compared with the O2 content of the flue gas used by the control system. It is best to have
several O2 measurements because of striations or variations of temperature and oxygen that are present across
the stack cross-section.

Different plants use different measurement schemes, selecting the average, the median, or the lowest
measurement to control. O2 trim is designed to be a steady state trim of the airflow. If you, or your tuner, are trying
to control airflow with the trim controller, stop it. The O2 trim controller should be mostly integral action with very
little proportional and no derivative gain. Your time is better spent reworking your air demand curves or airflow
characterization than attempting to tune the airflow using the O2 controls.

The output from the O2 trim control station then goes through a function generator such that a 0% to 100% input
signal equals a 0.8 to 1.2 output signal. This value is then multiplied against the characterized airflow. This means
that the O2 trim controller can adjust the airflow ±20%. In some extreme cases this amount can be varied, but for
most boilers ±20% is more than sufficient. The final result is a signal referred to as “O2 trimmed airflow.” This
value is then used by the airflow controller to modulate the ID fans or dampers.

Because O2 trim control uses a primarily integral-only controller, it does not have the dynamic capabilities of most
controllers. As a result, there are times when the controller should not be allowed the full range of control. At low
loads, typically less than 30% to 35%, output from the O2 trim controller should not be allowed to go below 50%
but should be limited to some minimum setting so that an air-rich atmosphere is always maintained in the furnace.

Also, when the lag function in the crosslimited air demand is driving air demand, airflow will lag behind. That is,
the air will remain elevated for a period of time as the load, and the fuel flow, decreases. As a result, oxygen in the
flue gas will spike up. If the O2 trim controller is not limited, the controls would see the O2 go higher than the set
point and start cranking, cranking, cranking down. Then, when the load gets to where the operators have set it
and the fuel flow is no longer decreasing, airflow demand will catch up with the boiler demand, and the O2 will
quickly begin to fall. The controller will see the O2 falling and begin to crank up. But because there is very little, or
no, proportional gain, it will take a long time to bring the air back. This can result in an unsafe or, at the least, a
nerve-wracking condition.

The NFPA requires some additional logic for the airflow control loop. There should be high and low furnace
pressure logic to block the airflow from increasing or decreasing, as is appropriate. Because this fan forces air into
the furnace, on high furnace pressure, the fan should be blocked from increasing speed; on a low furnace
pressure signal, it should be blocked from decreasing.

http://powerservices.lakho.com/2009/04/06/boiler-tuning-basics-part-i/ 2/19/2011
Boiler-Tuning Basics, Part I | Power Industry News Page 5 of 7

Also, on an MFT there are NFPA and boiler manufacturer requirements that must be considered. One important
consideration is the need to hold the air in place for a time after an MFT or if the airflow should drop very low
during or just after a trip. The dampers should go to a full open position shortly after the loss of all FD or ID fans
(providing a natural draft air path). Moreover, in the typical boiler air control system, if the ID fan is placed in
manual, then the FD fan is normally forced to manual. If the FD fan is in manual, then O2 trim is forced to manual.

Drum Level and Feedwater Control


Feedwater is fed into the drum in a typical subcritical pulverized coal–fired drum boiler via either a series of valves
in parallel with a series of constant-pressure feedwater pumps or a battery of variable-speed feedwater pumps. If
the feedwater level in the drum goes too high, water can become entrained in the steam going to the turbine and
can cause catastrophic results. If the drum feedwater level goes too low, the drum itself can become overheated,
possibly resulting in catastrophe.

Feedwater (and drum level) control has two modes of automatic operation: singleand three-element control. The
drum level set point for both modes is set by the operator. In single-element control the difference between the
drum level and the drum level set point provides the error signal that is used by the single-element controller to
control the rate of water entering the drum by modulating the feedwater flow control valve. Three-element control
governs the three variables, or elements, that are used in this control scheme: drum level, steam flow, and
feedwater flow.

Drum level control uses a cascaded controller scheme consisting of an outer and an inner controller. Steam flow
is an indication of the rate at which water is being removed from the drum. A function of steam flow is used as a
feedforward to the outer controller. The drum level error is then operated on by the outer controller. The output of
this controller is the feedwater flow set point. The difference between this set point and the feedwater flow is then
operated on by the inner controller. The output from this controller is then used to modulate the feedwater flow
control valve.

Three-element control is much more stable and robust than single-element control. The reason that we use single
-element control at all has to do with the nature of the instrumentation. Typically, feedwater flow, and occasionally
steam flow, is developed by using a flow-measuring device like an orifice plate or a flow nozzle, where flow rate is
proportional to differential pressure. However, a problem occurs at low flow rates (low boiler load), where
differential pressures are not as solidly proportional as we would like and therefore untrustworthy for boiler control.
Consequently, single-element control is used at low loads.

A well-tuned drum level control can be placed in automatic as soon as a pump is started. By the time steam flow
has passed 25% of the total range, we can consider steam flow signals to be reliable. That is a good point at
which to switch to three-element control.

There really is not much in the way of manual interlocks or control tracking when it comes to the drum level loop.
If the drum level signal or the feedwater flow valve control output goes out of range, or no pump is running, this
station is normally locked to manual mode. That’s about it.

rapid-responder

http://powerservices.lakho.com/2009/04/06/boiler-tuning-basics-part-i/ 2/19/2011
Boiler-Tuning Basics, Part I | Power Industry News Page 6 of 7

rapid-responder_2

4. Rapid responder. A typical coal-fire boiler with a properly tuned drum level control will respond very
quickly to a substantial load increase (top) or load decrease (bottom). The dynamic response of other key
variables in boiler drum level control system is also illustrated.

small-is-big

5. Small is big. A small increase in the feedforward signal added more stability to the drum level controls.
Only very small incremental changes in feedforward should be made when tuning drum level controls.

Normally, tuning for the single-element controller consists of big proportional and very small integral gain settings.
Tuning for the three-element controller has some additional requirements. As in any cascaded loop, it is
absolutely crucial that the inner controller be tuned as tightly as time will allow. The inner controller, the feedwater
controller in this case, must have an integral action that is faster than that of the outer, or drum level, controller
(Figure 4). This is true for all cascade loops.

You may notice that as the load decreases, the drum level sags downward, and as the load increases, the drum
level is slightly elevated. This means that the steam flow feedforward is just a tad too strong. A minute adjustment
to the feedforward signal can add stability to the control loop (Figure 5).

Superheat Temperature Control


Superheated steam temperature control is very straightforward. Normally, steam leaves the drum and travels
through a primary superheater(s) before entering the desuperheater, where attemperating water is mixed with the
steam to modulate its temperature before it enters the next superheater section. After the steam passes through
that superheater, the outlet temperature is measured.

If the inlet temperature to the superheater is a measured variable, the preferred method of control is a cascaded
loop. In this case the outer controller uses the superheater outlet temperature as the process variable. The output

http://powerservices.lakho.com/2009/04/06/boiler-tuning-basics-part-i/ 2/19/2011
Boiler-Tuning Basics, Part I | Power Industry News Page 7 of 7

from the outer controller is the inlet temperature set point. The output from the inner controller is spray water
demand. If the superheater outlet temperature is the only available measurement, then we are forced to use a
single-element control loop. In either case, it is important that the controls are equipped with a feedforward signal.

A variety of signals can be used for the superheater temperature control feedforward. Usually, the boiler demand
is a good starting point for the feedforward because this signal anticipates the measured temperature signals. My
experience is that the boiler demand usu-ally has a well-defined relationship with the superheater temperature.

deaerator-level-control Other measured variables are available to supply the feedforward


signal. Throttle pressure is usually used in tandem with the throttle
pressure set point as an indication of over- or underfiring of the
boiler, but throttle pressure is transient in nature. Airflow versus fuel
flow or steam flow may be used in the same way. The ratio of fuel
flow to the top mill versus the other mills is a good indicator of the
changing dynamics in the boiler, especially if the boiler is large and
has many burner levels. In this case it is a good rule of thumb to
think of the top elevations as affecting temperature more than
pressure, and the lower elevations as affecting steam pressure
more than temperature. Finally, the reheater temperature control
affects the superheater temperature to a greater or lesser degree,
depending on the type of boiler manufacturer and its method of
control.

The feedforward signal development may include both static and


dynamic functionality. The static cases are basically a function of
the variable that you are using. Dynamic feedforward refers to a
derivative kick based on the movement of the chosen variable. For
example, the ratio of airflow to steam flow might be used as an indicator of the boiler’s movement up or down, and
the feedforward then can be manipulated accordingly.

Patience is a virtue when tuning these feedforwards, because steam temperature processes may have long time
constants.

Reheat Temperature Control


It is an interesting fact that superheater spray adds to the efficiency of a unit but reheater spray flow decreases
the unit’s efficiency. Maximum boiler efficiency is always the goal, so boiler manufacturers have developed
alternative approaches to control reheat steam temperature.

Babcock & Wilcox uses a gas recirculation fan to move flue gas from the outlet of the boiler back into the furnace,
either directly or through the secondary air wind box. More recirculation yields higher furnace temperature and,
therefore, higher steam temperatures. Combustion Engineering, now Alstom Power, is famous for its tangential,
tilting burner design that can move the furnace fireball vertically to control steam temperatures. Foster Wheeler
boilers use a superheat/reheat gas bypass damper to shunt flue gas to the appropriate gas pass ducts to control
reheat temperature. Spray valves are also used in each design, although the reheat temperature set point to the
spray valve controller is usually several degrees higher to keep the reheater spray to a minimum.

The setup for the reheat temperature spray valve control is the same as that for the superheat temperature
control: two valves (modulating valve and block valve), an attemperator or desuperheater, and a reheater section.
However, reheat steam temperature control is not normally a cascaded loop. Assuming that the primary method
of control (gas recirculating fan, tilting burners, or bypass damper) is operating, the sprays are held in reserve.
The operator-adjustable set point is used directly by the primary control mechanism. A sliding bias is added to the
set point before it is sent to the spray controller. Usually, the spray set point is set higher than the primary reheat
temperature control set point before the sprays are enabled, to reduce the reheater spray flow.

Part II will look at fuel flow control, pulverizer air control, and overall plant control options such as boiler- and
turbine-following modes and plant coordinated control.