Professional Documents
Culture Documents
● Worldwide in service
A short-circuit downstream from an outgoing feeder The course of the current through the I S-limiter
breaker is assumed. The oscillogram shown below in such an event is shown below as current i2.
indicates the course of the short-circuit currents in the It can be seen that the I S-limiter is operating so
first half wave. rapidly, that there is no contribution via the trans-
A short-circuit current of 31.5 kA can flow to the fault former T2 to the total peak short-circuit current
location through each transformer. This would result (i1 + i2). Therefore, a switchgear with a rating of
in a total short-circuit current of 63 kA, which is twice 31.5 kA is suitable for this application.
as much as the switchgear capability.
k 31.5 kA k 31.5 kA
Single line
diagram of a bus
k perm. 31.5 kA tie for a system
with
I”k = 31.5 kA
and with an
IS-limiter
1. What is the peak short-circuit current? 3. How can switchboards which are only
dimensioned for 2 x IK be operated
with four transformers infeeds and
The peak short-circuit current ipeak is the
a total short-circuit current of 4 x IK
maximum instantaneous value of the
without any risk of overload and with-
current after the short-circuit occurs.
out losses?
Due to the peak short-circuit
current the electrical system
is subjected to the maximum
mechanical stress created by
magnetic forces. 2 3
1 4
Ik Ik Ik Ik
peak
Ik
4
3
2
1
t
Transformers: 1 1+2 1+2+3 1+2+3 +4
1
3
2
1. Current transformer
(detects the short-circuit current)
2. Measuring and tripping device
(measures the current and provides
the triggering energy)
3. Pulse transformer (converts the
tripping pulse to the busbar
potential)
4. Insert holder with insert (carries the
rated normal current and limits the
short-circuit current)
Short-circuit
current limited by
the fuse element
di
The rate of current rise ( dt )
– is high with high short-circuit currents
– is low with low short-circuit currents
10. What experience is available with the 12. Which short-circuit current the
operation of IS-limiters? IS-limiter can interrupt?
The rising demand for energy uneconomical for the user. The In comparison with complex
world-wide requires more use of I S-limiters reduces the conventional solutions, the
powerful or additional transfor- short-circuit current in new IS-limiter has both technical and
mers and generators, and an systems and expansions to economic advantages when
increasing interconnection of existing systems, thus saving used in transformer or genera-
the individual supply networks. cost. tor feeders, in switchgear sectio-
This can lead to the permissible Circuit-breakers cannot provide nalizing and connected in
short-circuit currents for the any protection against unduly parallel with reactors.
equipment being exceeded and high peak short-circuit currents, The I S-limiter is in every regard
thus parts of the equipment as they are too slow. Only the the ideal switching device to
being dynamically or thermally I S-limiter is capable of detecting solve the short-circuit problems
destroyed. and limiting a short-circuit for switchgear in power stati-
The replacement of existing current at the first rise, i.e. in ons, in heavy industry and at
switchgear and cable connec- less than 1 ms. The maximum utilities.
tions by new equipment with instantaneous current occurring
higher short-circuit strength is remains well below the level of
often technically impossible or the peak short-circuit current.
I S-limiters for three-phase sy- The operation of the clamping ensures electrical isolation of
stems basically consist of: device will be done with two the tripping device from the
• three I S-limiter insert holders, levers. Only for insert holders charge which is on busbar
• three I S-limiter inserts, Ir ≥ 2500 A and 12 kV/17.5 kV potential.
• three tripping current trans- the inserts are fixed with two
IS-limiter insert
formers, bolts.
• a measuring and tripping The I S-limiter insert is the swit-
Pulse transformer
device. ching element. In a sturdy
The location of the pulse trans- insulating tube 8, the insert
IS-limiter insert holders
former depends on the rated contains the main conductor,
The I S-limiter insert holder voltage: designed as a bursting bridge 9,
comprises: • for ≤ 17.5 kV, in the lower which encloses a charge 10. On
• base plate 1, insulator 6 only, tripping, this charge is triggered
• insulator 2, • for 24/36 kV, in the upper and the main conductor opens
• insulator with pulse trans- and lower insulators. at the rupture point.
former 6 and telescopic The pulse transformer transmits
contact 5, the tripping pulse from the
• pole heads with clamping tripping device (Figure 3) to
device 3 for the reception the charge 10 in the I S-limiter
of the I S-limiter insert. insert, and at the same time
1 7
2
3
9
4
10
11
5
4
12
The I S-limiter consists in prin- current, this device decides contribute to the peak short-
ciple of an extremely fast whether tripping of the circuit current.
switch, able to carry a high I S-limiter is necessary. In order
Power unit
rated current but having a low to reach this decision, the
switching capacity, and a high instantaneous current and rate A DC voltage of 150 V gener-
rupturing capacity (HRC) fuse of current rise at the I S-limiter ated in the power unit is used as
arranged in parallel. In order to are constantly measured and the charging voltage for the
achieve the desired short open- evaluated. When the setpoints tripping capacitors and at the
ing time, a small charge is used are simultaneously reached or same time as the supply voltage
as the energy store for opening ex-ceeded, the I S-limiter trips. for the electronics. As far as
of the switch (main conductor). The three phases are operated necessary, the supply voltage is
When the main conductor is independently of one another. divided and stabilized within
opened, the current continues The loss-free conduction of a the individual assemblies. A
to flow through the parallel high operating current on the watchdog module in the power
fuse, where it is limited within one hand and the limitation of unit constantly monitors the
0.5 ms and then finally inter- the short-circuit current at the most important functions of the
rupted at the next voltage zero first current rise on the other three tripping units.
passage. hand are made possible by
The current flowing through distributing these two functions
the I S-limiter is monitored by an of the I S-limiter between two
electronic measuring and conductors. In comparison with
tripping device. At the very reactors, the I S-limiter avoids
first rise of a short-circuit voltage drops and does not
11
12
As with every other protective The test plug is used to check During testing, the I S-limiter
device, I S-limiters should also be the voltages and the functions insert is replaced by the test
checked at regular intervals. of the tripping system. insert. The test insert contains
There are special testing sets The user friendly test equip- a neon lamp as an indicator,
available for those tests which ment facilitates further tests which lights up when a trip-
can be performed by the opera- such as determination of the ping pulse is received.
tor or by ABB AG. These test response voltages of the measu-
sets consist of a test equipment ring elements, and testing and
and a test insert or a test plug setting of the modules of the
and a test insert. measuring circuits.
Figure 6: IS-limiter insert holder with test insert Figure 7: Test plug
H
D
W
13
transformers, H
• one measuring and trip-
▼
W
ping device (Figure 3). ▼ ▼
▼
D
▼
Technical data
Rated voltage V 690 12000 12000
Rated power-frequency
withstand voltage kV 3 28 28
Interrupting
current kARMS up to 140 up to 210 up to 210
IS-limiter
insert holder kg 10.5 23/27.5 65
IS-limiter
insert kg 17.0 12/12.5 15.5
1)
With cooling fan
Frequency: 50/60 Hz
For higher rated currents, insert holders with inserts are connected in parallel.
14
38 38 50 75
95 95 125 200
23/27.5 65 27/31.5/33 60
15
16
2000
2500
3000 1)
3000 1350
4000 1) 1350
2000
3000 1)
3000 1350
4000 1) 1350
1600
2000
2500 1)
1)
With cooling fan.
For higher currents, insert holders with inserts are connected in parallel.
C. Fixed mounted IS-limiter in a switchgear panel The I S-limiter (fixed mounted) for 36 kV/40.5 kV
is available in a metal-enclosed switchgear panel.
The I S-limiters for low voltage, 12 kV, 17.5 kV and
Same as for loose equipment supply, the measuring
24 kV are also available as fixed mounted equip-
and tripping device is installed in a separate sheet
ment in a metal-enclosed switchgear panel.
steel cabinet (Figure 3).
The three I S-limiter insert holders with the I S-limiter
inserts and the three tripping current transformers
For all fixed mounted I S-limiters the electrical data
are fixed mounted in the panel.
are the same as for loose equipment supply.
The measuring and tripping device is mounted in
Dimensions and weights on request.
the low voltage compartment.
17
18
I"kT = 15 kA
10 kV
3 ~ 50 Hz I"k perm = 25 kA
Figure 10: IS-limiter in connecting point with Figure 11: IS-limiter in parallel with a reactor in
a public supply network a generator feeder
19
20
Sender:
ABB AG
Calor Emag Medium Voltage Products
Postfach 101220
D-40472 Ratingen
21
7. We are able to deliver the IS-limiter in different 9. Remarks:
designs. Which design do you need?
IS-limiter as loose delivered components for
installation in a cubicle of your own design
IS-limiter in a cubicle type ZS1, truck
mounted (up to 24 kV)
IS-limiter in a cubicle type ZS1, fixed
mounted (up to 24 kV)
IS-limiter in a cubicle type ZS, fixed
mounted (25 to 40.5 kV)
as main supply:
………V ………Hz
as stand-by supply:
………V ………Hz
22
Remarks (continuation):
23
Contact us
ABB AG Note: