Lynn G. Bellenger, PE
ASHRAE Fellow
Pathfinder Engineers LLP
continued . . .
Ventilation Rate Procedure
Particulate Matter
§ If national standard for PM10 exceeded
§ Particulate filters or air cleaning devices
§ MERV 6 or higher*
§ Rated per ASHRAE Standard 52.2-1999
Ozone
§ If second-highest daily maximum one hour
concentration exceeds 0.160 ppm
§ Requires air cleaning devices
§ Minimum removal efficiency of 40%
§ Operate when > 0.160 ppm forecast
§ When Air Quality Index forecast > 151
Outdoor Air Treatment
Ozone
§ Exception: if the minimum system design
outdoor intake flow results in 1.5 air
changes per hour or less
§ Exempts most office, retail space, but not
classrooms
Air Data for PM10
Design Steps
§ Determine breathing zone outdoor airflow
§ Determine zone air distribution
effectiveness
§ Determine zone outdoor airflow
§ Determine system outdoor air intake flow
Outdoor Air Intake Flow
Conference Rm 5 0.06 50 6 20
Classroom** 10 0.12 35 13 15
Design Steps
ü Determine breathing zone outdoor airflow
§ Determine zone air distribution
effectiveness
• Table 6.2
• Supply air temperature v. space
• Supply diffuser location
• Return grille location
Zone Air Distribution Effectiveness
Design Steps
ü Determine breathing zone outdoor airflow
ü Determine zone air distribution
effectiveness
§ Determine zone outdoor airflow
Voz = V bz/Ez
Zone Outdoor Airflow
Voz = Vbz/Ez
Design Steps
ü Determine breathing zone outdoor airflow
ü Determine zone air distribution
effectiveness
ü Determine zone outdoor airflow
§ Determine system outdoor air intake flow
Outdoor Air Intake Flow
§ Single-Zone Systems
Vot = V oz