You are on page 1of 52

Medium Voltage Products

HD4 according to IEC and GOST standards


Gas insulated MV circuit-breakers
12...40.5 kV - 630...3600 A - 16...50 kA
1
DESCRIPTION 2

2
CIRCUIT-BREAKER SELECTION AND ORDERING 8

3
SPECIFIC PRODUCT CHARACTERISTICS 22

4
OVERALL DIMENSIONS 24

5
ELECTRICAL CIRCUIT DIAGRAM 43
1 DESCRIPTION

Autopuffer breaking technique


Electric arc extinction without chopped
current
No restriking after breaking
Rapid recovery of the dielectric properties
of the means of extinction
Withstand insulation voltage even at zero
relative pressure (*)
Breaking up to 30% of the rated breaking
capacity even at zero relative pressure (*)
Sealed-for-life poles
Test for checking gas tightness carried out
three times on each piece of apparatus
General information Compact dimensions
HD4 medium voltage circuit-breakers use sulphur
hexafluoride gas (SF6) to extinguish the electric arc Fixed and withdrawable version
and as the insulating medium.
Stored energy operating mechanism with
Breaking in SF6 gas takes place without any arc
chopping and without generation of overvoltages. anti-pumping device as standard common
These characteristics ensure long electrical life of
to the whole circuit-breaker series
the circuit-breaker and limited dynamic, dielectric
and thermal stresses on the installation. Mechanical safety locks against incorrect
The circuit-breaker poles, which make up the
operations
breaking part, are systems with lifelong sealed
pressure (IEC 62271-100 and CEI 17-1 Standards) Simple personalisation thanks to a com-
and are maintenance-free.
plete range of accessories
The ESH type mechanical operating mechanism,
with stored energy has free release and allows Maintenance-free
opening and closing operations independently of
the operator’s actions. SF6 gas pressure control device (on
The operating mechanism and the poles are fixed request).
to the metal structure which also acts as a support
for the kinetics for operating the moving contacts.
Circuit-breakers in the withdrawable version are (*) Up to 24 kV.
fitted with a truck to allow racking in and racking out
of the switchboard or enclosure.
The light and compact structure of the circuit-breaker
ensures great sturdiness and excellent mechanical
reliability. Fields of application
HD4 circuit-breakers are used in power distribution
Available versions to control and protect lines, transformer and
HD4 circuit-breakers are available in the fixed and distribution substations, motors, transformers,
withdrawable version with front operating mecha- capacitor banks, etc.
nism. Thanks to the SF6 autopuffer breaking technique,
The withdrawable version is available for: CBE the HD4 circuit-breakers do not generate operating
enclosures, CBF fixed parts, PowerCube modules overvoltages, and are therefore also highly suitable
and UniGear type ZS1 switchboards. for retrofitting, upgrading and enlarging older installa-

2
1

7 3

6 4

5 Circuit-breaker Main contact Arcing contact Circuit-breaker


closed separation separation open

1
Main contact separation
No electric arc strikes as the current flows through the arcing contacts.
During its run downwards, the moving part compresses the gas contained in the lower chamber.
The compressed gas flows out of the lower chamber into the upper chamber, taking them both to
8 the same pressure.

Arcing contact separation


The current flows thanks to the electric arc which has struck between the arcing contacts.
The gas cannot get out through the nozzle because the hole is still closed by the fixed arcing
contact and cannot get out through the inside of the moving arcing contact either because the
electric arc closes this (clogging effect).
• with low currents, when the current passes through natural zero and the arc is quenched,
the gas flows through the contacts. The low pressure reached cannot chop the current and
the modest amount of compressed gas is sufficient to restore dielectric resistance between
the two contacts, preventing restriking on the rising front of the return voltage.
2 • with high short-circuit currents, the pressure wave generated by the electric arc closes the
valve between the two chambers so that the circuit-breaker starts to operate as a “pure self-
blast”. The pressure increases in the upper volume thanks to heating of the gas and molecular
9 disassociation due to the high temperature. The increase in pressure generated is propor-
tional to the arc current and ensures quenching on first passage through current zero.

1 Terminal 6 Fixed arcing contact Circuit-breaker open


2 Insulating case 7 Fixed contact The arc has been interrupted, the self-generated pressure in the upper volume is reduced be-
3 Blasting nozzle 8 Insulating tie-rod cause the gas is flowing through the contacts. The valve re-opens and so a new flow of fresh
4 Moving arcing contact 9 Anti-explosion valve gas comes into the breaking chamber. The apparatus is therefore immediately ready to close
5 Moving contact and trip again up to its maximum breaking capacity.

tions where the motor, cable, etc. insulating materials operating overvoltages.
may be particularly sensitive to dielectric stresses. The HD4 series brings to medium voltage the
advantages of the “autopuffer” breaking technique
Breaking technique already used in high voltage.
The breaking technique of HD4 circuit-breakers is
based on compression and self-blast techniques to
obtain top performances at all service current
values, with minimum arc times, gradual arc
extinction without chopping, and no restriking or

3
1 DESCRIPTION

Standards and approvals


HD4 circuit-breakers comply with IEC 62271-100,
CEI 17-1 file 1375 Standards and with those of
major industrialised countries.
They have undergone the following tests and
guarantee safety and reliability of the apparatus in
service in all installations.
• Type tests: heating, withstand insulation at
industrial and impulse frequency, short-time and
peak withstand current, mechanical duration,
making and breaking of short-circuit currents;
• Individual tests: insulation with voltage at
industrial frequency in the main circuits and
insulation of the auxiliary and control circuits,
measurement of the main circuit resistance,
mechanical and electrical operation.
The HD4 circuit-breakers are tested according to
the requirements of the IEC 62271-100 Standard
(class E2 - table 21) and guarantee suitability for
use in overhead lines, with rapid reclosing cycle.
Versions approved according to the GOST Stand-
ard are also available.

Service safety
Thanks to the availability of a complete range of
mechanical and electrical locks (on request), safe
distribution switchboards can be constructed using

The terminals and isolating The withdrawable circuit- The nameplate, located on All the control and signalling devices are located on the
contacts are silver-plated. breakers feature a device the front panel, enables all front of the circuit-breaker.
enabling them to be racked the circuit-breaker Suitable locks prevent incorrect operations.
in/out with the door closed. characteristics to be The antipumping device is always provided on the actuator.
identified.

4
HD4 circuit-breakers. The locking devices have been designed to Technical documentation
prevent incorrect operations and to carry out inspection of the To obtain in-depth knowledge of technical and application
installation, ensuring maximum operator safety. aspects of the HD4 circuit-breakers please ask for the following
publications:
– PowerCube modules
Accessories
– UniGear ZS1 type switchboards
HD4 circuit-breakers have a complete range of accessories
– ZS3.2/PowerBloc switchboards
which fulfil all installation requirements.
The operating mechanism is the same type for the whole series – REF542plus unit
and has a standardized range of accessories and spare parts – PR512 protection device.
which are easy to identify and order.
Apparatus use, maintenance and service have been simplified
and require less use of resources. Quality System
Complies with ISO 9001 Standards,
certified by an independent
ESH operating mechanism organisation.
• Just one device for the whole series.
• The same set of accessories for all the types of HD4 circuit-
breaker.
• Fixed strikers to facilitate assembly or replacement of accesso- Test Laboratory
ries. Complies with UNI CEI EN ISO/IEC
• Accessory cabling with socket and plug. 17025 Standards, accredited by an
independent organisation.

Environmental Management
System
Complies with ISO 14001 Standards,
certified by an independent
organisation.

Health and Safety Management


System
Complies with OHSAS 18001
Standards, certified by an
independent organisation.

The self-supplied PR512 switchboard release is available for protection of


the installations.
In its basic version, the PR512 carries out the following functions:
• 50-51-50N-51N protection
• current measurement with display of the maximum value between
phases
• dialogue.
For further information about the PR512 release, please consult technical
catalogue 649092.

5
2 CIRCUIT-BREAKER SELECTION AND ORDERING

General characteristics of fixed circuit-breakers (12 - 17.5 - 24 kV)

Circuit-breaker HD4/GT 12
Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File1375)
Rated voltage Ur [kV] 10
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 42
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
(1)
Rated normal current Ir [A] 630 1250 630 1250 1250 1600 2000 2500 3150
Rated breaking capacity Isc [kA] – – – – – – – – –
20 20 20 20 – 20 – – –
25 25 25 25 – 25 25 25 25
31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 31.5
– – – – 40 40 40 40 40
– – – – 50 50 50 50 50
Rated short-time Ik [kA] – – – – – – – – –
withstand current (3 s) 20 20 20 20 – 20 – – –
25 25 25 25 – 25 25 25 25
31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 31.5
– – – – 40 40 40 40 40
– – – – 50 50 50 50 50
Making capacity Ip [kA] – – – – – – – – –
50 50 50 50 – 50 – – –
63 63 63 63 – 63 63 63 63
80 80 80 80 – 80 80 80 80
– – – – 100 100 100 100 100
– – – – 125 125 125 125 125
Operation sequence [O-0,3s-CO-15s-CO]
[O-0,3s-CO-20s-CO]
[O-0,3s-CO-180s-CO]
Opening time [ms] 45
Arcing time [ms] 10-15
Total breaking time [ms] 55-60
(1) Rated uninterrupted cur-
Closing time [ms] 80
rent defined in free air at
40 °C ambient tempera- Overall Dimension standardization table TN 7360 TN 7361 TN 7201 TN 7202
ture for HD4 17 and HD4 dimensions Pole distance [mm] 150 210 210 275
24; rated uninterrupted
currents in free air at 55 H [mm] 582 622 655 655
°C ambient temperature H L [mm] 493 618 618 730
for HD4/GT12.
L D D [mm] 459 456 493 493
(2) Rated service value.
(3) The minimum storage Weight [Kg] 114 114 145 165
and transportation tem- Absolute SF6 gas pressure (2)
[kPa] 380
perature is minus 35 °C.
Operating temperature (3) [°C] – 25 ... + 55
(4) Including insulating
shields (available on re- Tropicalization IEC: 60068-2-30, 60721-2-1
quest). Electromagnetic compatibility IEC 62271-1

6
HD4 17 HD4 24

17.5 24
17.5 24
38 50
95 125
50-60 50-60
630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600 630 1250 1600 630 1250 1600 1600 2000 2500 3150 3600
16 16 16 16 16 16 – – – – – 16 16 16 16 16 16 – – – – –
– – – – – – – – – – – 20 20 20 20 20 20 – – – – –
25 25 25 25 25 25 – 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 31.5 – – – – – – 31.5 31.5 31.5 31.5 31.5
– – – – – – 40 40 40 40 40 – – – – – – 40 40 40 40 40
– – – – – – 50 50 50 50 50 – – – – – – – – – – –
16 16 16 16 16 16 – – – – – 16 16 16 16 16 16 – – – – –
– – – – – – – – – – – 20 20 20 20 20 20 – – – – –
25 25 25 25 25 25 – 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
31.5 31.5 31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 31.5 – – – – – – 31.5 31.5 31.5 31.5 31.5
– – – – – – 40 40 40 40 40 – – – – – – 40 40 40 40 40
– – – – – – 50 50 50 50 50 – – – – – – – – – – –
40 40 40 40 40 40 – – – – – 40 40 40 40 40 40 – – – – –
50 50 50 50 50 50 – – – – – 50 50 50 50 50 50 – – – – –
– – – – – – – 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63
80 80 80 80 80 80 – 80 80 80 80 – – – – – – 80 80 80 80 80
– – – – – – 100 100 100 100 100 – – – – – – 100 100 100 100 100
– – – – – – 125 125 125 125 125 – – – – – – – – – – –

45 45
10-15 10-15
55-60 55-60
80 80
TN 7177 TN 7178 TN 7163 TN 7165 TN 7179 TN 7242 TN 7174 TN 7165
150 210 210 275 210 275 275 275
640 649 655 655 818 (4) 730 655 818 (4)
493 618 618 730 618 748 730 730
496 496 561 603 600 (4) 496 561 620 (4)
114 114 145 165 119 119 145 165
380 380
– 25 ... + 40 – 25 ... + 40

7
2 CIRCUIT-BREAKER SELECTION AND ORDERING

General characteristics of withdrawable circuit-breakers


(5)
for CBE enclosures and CBF fixed parts (12 - 17.5 - 24 kV)

Circuit-breaker HD4/C 12
Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File1375)
Rated voltage Ur [kV] 12
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
(1)
Rated normal current (40 °C) Ir [A] 630 1250 1250 1600 2000 2500 3150 (4)
Rated breaking capacity Isc [kA] 16 16 – – – – –
– – – – – – –
25 25 – 25 25 25 –
31.5 31.5 – 31.5 31.5 31.5 31.5
– – 40 40 40 40 40
– – 50 50 50 50 50
Rated short-time Ik [kA] 16 16 – – – – –
withstand current (3 s) – – – – – – –
25 25 – 25 25 25 –
31.5 31.5 – 31.5 31.5 31.5 31.5
– – 40 40 40 40 40
– – 50 50 50 50 50
Making capacity Ip [kA] 40 40 – – – – –
50 50 – – – – –
– – – 63 63 63 –
80 80 – 80 80 80 80
– – 100 100 100 100 100
– – 125 125 125 125 125
Operation sequence [O-0,3s-CO-15s-CO]
[O-0,3s-CO-20s-CO]
(1) Rated uninterrupted cur- [O-0,3s-CO-180s-CO]
rent guaranteed with Opening time [ms] 45
withdrawable circuit-
breaker installed in a Arcing time [ms] 10-15
switchboard at 40 °C Total breaking time [ms] 55-60
ambient temperature ex-
Closing time [ms] 80
ternally the panel.
(2) Rated service value. Overall Dimension standardization table TN 7184 TN 7151 TN 7153 TN 7155 1VCD000017
(3) The minimum storage dimensions Pole distance [mm] 150 210 275 275 275
and transportation tem-
perature is minus 35 °C. H [mm] 636 702 702 702 704
(4) Rated uninterrupted H L [mm] 532 682 882 882 882
current in switchboard D
L D [mm] 659 640 640 640 640
with forced ventilation
(forced ventilation at Weight [Kg] 120 177 210 220 230
customer care). Absolute SF6 gas pressure (2)
[kPa] 380
(5) For the replacement of
Operating temperature (3) [°C] – 25 ... + 40
already installed HD4/
C only, as CBE and Tropicalization IEC: 60068-2-30, 60721-2-1
CBF are phased-out Electromagnetic compatibility IEC 62271-1
product

8
HD4/C 17 HD4/C 24

17.5 24
17.5 24
38 50
95 125
50-60 50-60
630 1250 1250 1600 2000 2500 630 1250 1250 1600 2000 2500
16 16 – – – – 16 16 – – – –
– – – – – – 20 20 – – – –
25 25 – 25 25 25 25 25 – – 25 25
31.5 31.5 – 31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5
– – 40 40 40 40 – – 40 40 40 40
– – 50 50 50 50 – – – – – –
16 16 – – – – 16 16 – – – –
– – – – – – 20 20 – – – –
25 25 – 25 25 25 25 25 – – 25 25
31.5 31.5 – 31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5
– – 40 40 40 40 – – 40 40 40 40
– – 50 50 50 50 – – – – – –
40 40 – – – – 40 40 – – – –
50 50 – – – – 50 50 – – – –
– – – 63 63 63 63 63 – – 63 63
80 80 – 80 80 80 – – 80 80 80 80
– – 100 100 100 100 – – 100 100 100 100
– – 125 125 125 125 – – – – – –

45 45
10-15 10-15
55-60 55-60
80 80
TN 7184 TN 7151 TN 7153 TN 7155 TN 7186 TN 7156 TN7157 TN 7158 TN7159
150 210 275 275 210 210 275 275 275
636 702 702 702 792 792 838 838 838
532 682 882 882 682 682 882 882 882
659 640 640 640 799 799 788 788 771
120 177 210 220 125 177 177 177 220
380 380
– 25 ... + 40 – 25 ... + 40

9
2 CIRCUIT-BREAKER SELECTION AND ORDERING

General characteristics of withdrawable circuit-breakers


for UniGear type ZS1 switchboards (12 - 17.5 - 24 kV) (5)

Circuit-breaker HD4/GT/P 12
Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File1375)
Rated voltage Ur [kV] 10 10
Rated insulation voltage Us [kV] 12 12
(6)
Withstand voltage at 50 Hz Ud (1 min) [kV] 42 38 (6)
Impulse withstand voltage Up [kV] 75 75
Rated frequency fr [Hz] 50-60 50-60
Rated normal current (40 °C) (1)
Ir [A] 630 1250 1250 1600 2000 2500 3150 (4)
Rated breaking capacity Isc [kA] – – – – – – –
20 20 – 20 – – –
25 25 – 25 25 25 25
31,5 31,5 – 31,5 31,5 31,5 31,5
– – 40 40 40 40 40
– – – 50 50 50 50
Rated short-time Ik [kA] – – – – – – –
withstand current (3 s) 20 20 – 20 – – –
25 25 – 25 25 25 25
31,5 31,5 – 31,5 31,5 31,5 31,5
– – 40 40 40 40 40
(1) Rated uninterrupted cur-
– – – 50 50 50 50
rent guaranteed with
withdrawable circuit- Making capacity Ip [kA] – – – – – – –
breaker installed in 50 50 – 50 – – –
UniGear type ZS1
switchboard at 40 °C 63 63 – 63 63 63 63
ambient temperature ex- 80 80 – 80 80 80 80
ternally the panel.
– – 100 100 100 100 100
(2) Rated service value.
(3) The minimum storage – – – 125 125 125 125
and transportation tem- Operation sequence [O-0,3s-CO-15s-CO]
perature is minus 35 °C.
(4) Rated uninterrupted cur- [O-0,3s-CO-20s-CO]
rent in switchboard with [O-0,3s-CO-180s-CO]
forced ventilation. Opening time [ms] 45
(5) The locking electromag-
net (-RL2) in the truck to Arcing time [ms] 10-15
prevent the circuit- Total breaking time [ms] 55-60
breaker being racked-in
Closing time [ms] 80
with the auxiliary circuits
disconnected (plug not Overall Dimension standardization table TN 7286 TN 7350 TN 7351 TN 7352 TN 7371
inserted in the socket) is dimensions Pole distance [mm] 150 210 210 275 275
included in the standard
equipment. H [mm] 628 702 702 702 746
(6) UniGear type ZS1 H L [mm] 532 682 682 882 882
switchboard with rated 659 640 640 643 643
L D D [mm]
insulation voltage 17.5
kV. Weight [Kg] 120 177 177 220 230
(7) Rated uninterrupted cur- Absolute SF6 gas pressure (2)
[kPa] 380
rent in switchboard with
Operating temperature (3) [°C] – 25 ... + 40
forced ventilation. In a
switchboard with natu- Tropicalization IEC: 60068-2-30, 60721-2-1
ral ventilation, the rated Electromagnetic compatibility IEC 62271-1
current is 2300 A.

10
HD4/P 17 HD4/P 24

17.5 24
17.5 24
38 50
95 125
50-60 50-60
(4) (7)
630 1250 1250 1600 2000 2500 3150 630 1250 1250 1600 2000 2500
16 16 – – – – – 16 – – 16 16 –
– – – – – – – 20 20 – 20 20 20
25 25 – 25 25 25 25 25 25 – 25 25 25
31.5 31.5 – 31.5 31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5
– – 40 40 40 40 40 – – – – – –
– – – 50 50 50 50 – – – – – –
16 16 – – – – – 16 – – 16 16 –
– – – – – – – 20 20 – 20 20 20
25 25 – 25 25 25 25 25 25 – 25 25 25
31.5 31.5 – 31.5 31.5 31.5 31.5 – – 31.5 31.5 31.5 31.5
– – 40 40 40 40 40 – – – – – –
– – – 50 50 50 50 – – – – – –
40 40 – – – – – 40 – – 40 40 –
50 50 – – – – – 50 50 – 50 50 50
– – – 63 63 63 63 63 63 – 63 63 63
80 80 – 80 80 80 80 – – 80 80 80 80
– – 100 100 100 100 100 – – – – – –
– – – 125 125 125 125 – – – – – –

45 45
10-15 10-15
55-60 55-60
80 80
TN 7286 TN 7350 TN 7351 TN 7352 TN 7371 TN 7354 1VCD000099 TN 7355 TN7356
150 210 210 275 275 210 210 275 275
628 702 702 702 746 736 792 821 821
532 682 682 882 882 636 653 842 842
659 640 640 643 643 802 799 788 788
120 177 177 220 230 125 177 177 220
380 380
– 25 ... + 40 – 25 ... + 40

11
2 CIRCUIT-BREAKER SELECTION AND ORDERING

General characteristics of withdrawable circuit-breakers


for PowerCube modules (12 - 17.5 - 24 kV)

Circuit-breaker HD4/W 12
PowerCube enclosures PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3
Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File1375)
Rated voltage Ur [kV] 12
Rated insulation voltage Us [kV] 12
Withstand voltage at 50 Hz Ud (1 min) [kV] 28
Impulse withstand voltage Up [kV] 75
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C)(1) Ir [A] 630 1250 630 1250 1250 1600 2000 3150 (4)
Rated breaking capacity Isc [kA] 16 16 16 16 – 16 16 –
– – – – – – – –
25 25 25 25 – 25 25 –
31.5 31.5 31.5 31.5 – 31.5 31.5 31.5
– – – – 40 – – 40
– – – – 50 – – 50
Rated short-time Ik [kA] 16 16 16 16 – 16 16 –
withstand current (3 s) – – – – – – – –
25 25 25 25 – 25 25 –
31.5 31.5 31.5 31.5 – 31.5 31.5 31.5
– – – – 40 – – 40
– – – – 50 – – 50
Making capacity Ip [kA] 40 40 40 40 – 40 40 –
–- –- – – – – – –
63 63 63 63 –- 63 63 –
80 80 80 80 –- 80 80 80
(1) Rated uninterrupted cur- – – – – 100 – – 100
rent guaranteed with – – – – 125 – – 125
withdrawable circuit-
breaker installed in a Operation sequence [O-0,3s-CO-15s-CO]
switchboard at 40 °C [O-0,3s-CO-20s-CO]
ambient temperature
[O-0,3s-CO-180s-CO]
externally the panel.
(2) Rated service value. Opening time [ms] 45
(3) The minimum storage Arcing time [ms] 10-15
and transportation tem-
Total breaking time [ms] 55-60
perature is minus 35 °C.
(4) Rated uninterrupted cur- Closing time [ms] 80
rent in switchboard with Overall Dimension standardization table TN 7229 TN 7182 TN 7421 TN 7239 1VCD000053
natural ventilation; rated dimensions Pole distance [mm] 150 210 210 210 275
current 3600 A with one
fan pre-installed in PB3 H [mm] 636 702 702 702 742
cassette; rated current H
L [mm] 532 682 682 682 882
4000 A with one addi-
tional fan installed by L D D [mm] 659 640 640 640 643
customer in the back of Weight [Kg] 120 120 177 177 230
switchgear (see Absolute SF6 gas pressure (2) [kPa] 380
PowerCube Instruction
Manual). Operating temperature (3) [°C] - 25 ... + 40
(5) Rated uninterrupted cur- Tropicalization IEC: 60068-2-30, 60721-2-1
rent in switchboard with Electromagnetic compatibility IEC 62271-1
forced ventilation.

12
HD4/P 12 HD4/W 17 HD4/P 17 HD4/W 24 HD4/P 24
PB2 PB2 PB3 PB1 PB1 PB2 PB2 PB2 PB2 PB2 PB3 PB2 PB2 PB3 PB4 PB4 PB5 PB5

12 17.5 17.5 24 24
12 17.5 17.5 24 24
28 28 28 50 50
75 95 95 125 125
50-60 50-60 50-60 50-60 50-60
1600 2000 2500 630 1250 630 1250 1250 1600 2000 3150 (4) 1600 2000 2500 630 1250 1600 2000 2500(5)
– – – 16 16 16 16 – 16 16 – – – – 16 16 16 16 16
– – – – – – – – – – – – – – 20 20 20 20 20
– – 25 25 25 25 25 – 25 25 – – – 25 25 25 25 25 25
– – 31.5 31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 – – 31.5 – – – – –
40 40 40 – – – – 40 – – 40 40 40 40 – – – – –
50 50 50 – – – – 50 – – 50 50 50 50 – – – – –
– – – 16 16 16 16 – 16 16 – – – – 16 16 16 16 16
– – – – – – – – – – – – – – 20 20 20 20 20
– – 25 25 25 25 25 – 25 25 – – – 25 25 25 25 25 25
– – 31.5 31.5 31.5 31.5 31.5 – 31.5 31.5 31.5 – – 31.5 – – – – –
40 40 40 – – – – 40 – – 40 40 40 40 – – – – –
50 50 50 – – – – 50 – – 50 50 50 50 – – – – –
– – – 40 40 40 40 – 40 40 – – – – 40 40 40 40 40
– – – – – – – – – – – – – – 50 50 50 50 50
– – 63 63 63 63 63 – 63 63 – – – 63 63 63 63 63 63
– – 80 80 80 80 80 – 80 80 80 – – 80 – – – – –
100 100 100 – – – – 100 – – 100 100 100 100 – – – – –
125 125 125 – – – – 125 – – 125 125 125 125 – – – – –

45 45 45 45 45
10-15 10-15 10-15 10-15 10-15
55-60 55-60 55-60 55-60 55-60
80 80 80 80 80
TN 7350 TN 7351 TN 7352 TN 7229 TN 7182 TN 7421 TN 7239 1VCD000053 TN 7350 TN 7351 TN 7352 TN 7183 TN 7355 TN 7356
210 210 275 150 210 210 210 275 210 210 275 210 275 275
702 702 702 636 702 702 702 742 702 702 702 792 821 821
682 682 882 532 682 682 682 882 682 682 882 682 842 842
640 640 643 659 640 640 640 643 640 640 643 799 788 788
177 177 220 120 120 177 177 230 177 177 220 125 177 220
380 380 380 380 380
- 25 ... + 40 - 25 ... + 40 - 25 ... + 40 - 25 ... + 40 - 25 ... + 40

13
2 CIRCUIT-BREAKER SELECTION AND ORDERING

General characteristics of withdrawable circuit-breakers


for UniGear type ZS3.2 switchboards (40.5 kV)

Circuit-breaker HD4/Z 40.5


Standards GOST P 52565-2006
IEC 62271-100
CEI 17-1 (File 1375)
Rated voltage Ur [kV] 40.5
Rated insulation voltage Us [kV] 40.5
Withstand voltage at 50 Hz Ud (1 min) [kV] 95
Impulse withstand voltage Up [kV] 185
Rated frequency fr [Hz] 50-60
Rated normal current (40 °C) (1) Ir [A] 1250 1600 2000 2500
Rated breaking capacity Isc [kA] 25 25 25 25
31.5 (4) 31.5 (4) 31.5 (4) 31.5 (4)
Rated short-time Ik [kA] 25 25 25 25
withstand current (3 s) 31.5 31.5 31.5 31.5
Making capacity Ip [kA] 63 63 63 63
80 80 80 80
Operation sequence (4) [O-0,3s-CO-15s-CO]
Opening time [ms] 45
Arc time [ms] 10-15
Total breaking time [ms] 55-60
Closing time [ms] 80
Overall dimensions Dimension standardization table TN 7227
Pole distance [mm] 280
H [mm] 1575
H L [mm] 895
L D D [mm] 686
Weight [Kg] 280
(2)
Absolute SF6 gas pressure [kPa] 550
Operating temperature (3) [°C] – 25 ... + 40
Tropicalization IEC: 60068-2-30, 721-2-1
Electromagnetic compatibility IEC 62271-1

(1) Rated uninterrupted current guaranteed with withdrawable circuit-breaker installed in UniGear type ZS3.2. switchboard
at 40 °C ambient temperature externally the panel.
(2) Rated service value.
(3) The minimum storage and transportation temperature is minus 35 °C.
(5) The operating sequence is O-0.3sec-CO-3min-CO for the rated breaking capacity Isc = 31.5 kA.

14
Standard equipment Moreover:
The basic versions of the circuit-breakers are for fixed circuit-breaker
always three-pole and fitted with: – connection terminals (on request for
– manual operating mechanism HD4/GT 12)
– mechanical signalling device for closing springs – terminal board for auxiliary circuits;
charged/discharged
– mechanical signalling device for circuit-breaker for withdrawable circuit-breaker
open/closed – isolating contacts
– closing pushbutton – cord with connector (plug only) for auxiliary
– opening pushbutton circuits
– operation counter – earthing contact on truck (only for CBE, CBF)
– set of ten open/closed circuit-breaker auxiliary – lock to prevent racking-in of circuit-breaker with
contacts (four opening (NC) and three closing different rated current
(NO) available, according to the applications – racking-in/out lever (the quantity must be de-
requested) fined according to the number of pieces of ap-
– lever for manually charging the closing springs paratus ordered)
(the quantity must be defined according to the – locking electromagnet in the truck (/P and /W
number of pieces of apparatus ordered). versions).

Terminals for fixed circuit-breaker. Tulip isolating contacts for withdrawable Plier isolating contacts for withdrawable
circuit-breaker. circuit-breaker.

Circuit-breaker racking-out/racking-in lever. Manual charging lever of operating mechanism springs.

15
2 CIRCUIT-BREAKER SELECTION AND ORDERING

Table of availability of accessories

Mechanical override of undervoltage

-BB5 undervoltage release electric


electronic time delay device (power
-MO3 shunt opening release with

-MU undervoltage release with


(power supply on supply side).
-MO2 additional shunt opening
-MO1 shunt opening release.

signalling (energised or de-


-MC shunt closing release.

-MU undervoltage release

supply on supply side).


demagnetisation.

release trip.

energised).
release.
1 2A 2B 3 4A 4B 5 6

Fixed circuit-breakers
HD4/GT 12
HD4 17
HD4 24

Withdrawable circuit-breakers
for CBE enclosures and CBF fixed parts
HD4/C 12
HD4/C 17
HD4/C 24

Withdrawable circuit-breakers
for UniGear type ZS1 switchboards

(1) Standard fitting: no. 6 HD4/GT/P 12


auxiliary contacts. HD4/P 17
(2) Application of the pres-
sure switch is only possi- HD4/P 24
ble in the factory.
(3) For this version it is only Withdrawable circuit-breakers
available without LED. for UniGear 36 type ZS3.2 switchboards
(4) The locking electro-mag-
net in the truck (- HD4/Z 40.5
RL2) to prevent the cir-
cuit-breaker being Withdrawable c.-bs. for PowerCube modules
racked-in with the auxil-
HD4/W 12 - HD4/P 12
iar y circuits discon-
nected (plug not inserted HD4/W 17 - HD4/P 17
in the socket) is included
in the standard equip- HD4/W 24 - HD4/P 24
ment.

16
Group of 15 auxiliary circuit-breaker
contacts: 4 make and 5 break (alterna-
tive to the 10 provided as standard, of

7
which a maximum of 3 make and 4 bre-
ak are available depending on the
accessories requested).

8
-BB4 transient contact.

-BT3 position contact of the withdraw-


able circuit-breaker (installed on the





9
truck). It is compulsory if the RL1
locking magnet is present.

Withdrawable circuit-breaker transmit-



(1)
ted contacts (installed in the circuit-

10
breaker truck).

11
-MS spring charging geared motor.

-FB1 thermomagnetic protection of

12
spring charging geared motor.

Electric signalling of springs


charged.

Electric signalling of springs dis-


charged.


Opening pushbutton lock.


Closing pushbutton lock.

Open circuit-breaker key lock.


13A 13B 14 15 16

-RL1 operating mechanism locking


17

magnet.


-RL2 truck locking magnet.

(4)
(4)
(4)
(4)
(4)
(4)





Interlock for fixed circuit-breaker.
18 19

Mechanical isolation interlock with







the switchgear door.


20







Earthing contact on the truck.

(3)
Two-level pressure switch (2).

Two-level pressure switch plus SF6


21 22A 22

control device with three LEDs (2).


B/C/D













23

Insulating partitions.

17
2 CIRCUIT-BREAKER SELECTION AND ORDERING

Optional accessories
The accessories identified with the same number are alternative to each other.

Shunt opening release


1 -MO1 shunt opening release.

Additional shunt opening release


2A Additional -MO2 shunt opening release
2B -MO3 opening solenoid with demagnetisation.

Shunt closing release


Shunt opening release. 3 -MC shunt closing release.

Undervoltage release
4A -MU undervoltage release (power supply branched on the supply side).
4B -MU undervoltage release with electronic delay device (0.5 – 1 – 1.5 –
2 – 3 s) (power supply branched on the supply side). This device is
delivered set to 0.5 s see the Electric Diagram chapter - note I on
page 82).
5 Mechanical override of undervoltage release trip with electrical signalling.
6 -BB5 undervoltage release electric signalling (energised or de-ener-
gised).
Shunt closing release.

Auxiliary and signalling contacts


7 Group of 15 auxiliary circuit-breaker contacts: 4 make and 5 break (alter-
native to the 10 provided as standard, of which a maximum of 3 make
and 4 break are available depending on the accessories requested).
8 -BB4 transient contact with momentary closing during circuit-breaker
opening.
9 -BT3 position contact of the withdrawable circuit-breaker (installed on the
truck, only available for the /C, /P, /W version when the locking magnet is
not provided; mounted as standard when the -RL1 locking magnet is
provided on the operating mechanism).
10 Transmitted contacts of the withdrawable
Undervoltage release. circuit-breaker (installed in the circuit-breaker truck - only for
withdrawable circuit-breaker).

Motor operator
11 -MS spring-charging geared motor.
12 -FB1 thermomagnetic protection of the spring-charging geared motor
(mounted as standard for 24 V d.c. geared motors) complete with
electrical signalling of thermomagnetic protection trip.
13A Electrical signalling of operating mechanism springs charged.
13B Electrical signalling of operating mechanism springs discharged.

Auxiliary contacts.

18
Locks and interlocks

14 Opening pushbutton lock (with or without padlock).


15 Closing pushbutton lock (with or without padlock).
16 Key lock for circuit-breaker open (different keys or the same keys).
17 -RL1 operating mechanism locking magnet.
18 -RL2 truck locking magnet. Compulsory accessory for the withdrawable
versions for UniGear ZS1 type switchgear and PowerCube modules, to
prevent racking-in of the circuit-breaker into the switchboard with the
auxiliary circuit plug disconnected. The plug makes the anti-racking-in
Spring charging geared lock for different rated current (by means of a special pin).
motor.
19 Interlock for fixed circuit-breaker (for fixed apparatus converted into
withdrawable type by the customer).
20 Mechanical isolation interlock with the door of the switchboard (on request
for PoweCube version; not provided for HD4/Z 40.5 kV).

Withdrawable circuit-breaker earthing

21 Earthing contact on the truck (compulsory for circuit-breaker with CBE


enclosure and for CBF fixed part; not available for UniGear ZS1 type
switchgear and PowerCube modules).
Geared motor protection.

Gas control device


Notes:
– should application of the pressure switch be required, specify
the request at the time of order since subsequent application by
the customer is not possible.
– devices 22B and 22C are supplied without LEDs for the HD4/Z
40.5 kV series.
22A Two-level pressure switch.
22B Two-level SF6 pressure switch control device with three LEDs and -MO2
additional shunt opening release: circuit-breaker opening and lock on
SF6 control device with 3 closing
LEDs. 22C Two-level SF6 pressure switch control device with three LEDs: circuit-
breaker locking in the position it is found in.

Insulating partitions
23 Insulating partitions.

Opening and closing


pushbutton locks.

19
2 CIRCUIT-BREAKER SELECTION AND ORDERING

Characteristics of electrical accessories

Shunt opening release (-MO1; -MO2) Ps = 125 W/VA (Instantaneous service < 45 ms)
Un = 24, 30, 48, 60, 110, 125, 220, 250 V–
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz

Shunt closing release (-MC) Ps = 250 W/VA (150 ms)


Pc = 5 W/VA (antipumping function - continuous service)
Un = 24, 30, 48, 60, 110, 125, 220, 250 V–
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz

Undervoltage release (-MU) Ps = 250 W/VA (150 ms)


Pc = 5 W/VA (continuous service)
Un = 24, 30, 48, 60, 110, 125, 220, 250 V–
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz

Spring charging geared motor (-MS) Ps = 1500 W/VA (100 ms)


Pc = 400 W/VA (spring charging time: 6 s)
Un = 24, 30, 48, 60, 110, 125, 220, 250 V–
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz

Locking magnets (-RL1; -RL2) Ps = 250 W/VA (150 ms)


Pc = 5 W/VA (continuous service)
Un = 24, 30, 48, 60, 110, 125, 220, 250 V–
Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un = 110 (127), 230 (220/240) V~ 60 Hz
Un Rated voltage.
Cosϕϕ Power factor. Gas control device with 3 LEDs Un = 24, 30, 48, 60, 110, 125, 220, 250 V–
Icu Breaking capacity Un = 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Ps Inrush power con- Un = 110 (127), 230 (220/240) V~ 60 Hz
sumption (the inrush
time is indicated in Circuit-breaker auxiliary contacts Un = 500 V~ 220 V–
brackets). Icu = 15 A 1.5 A
Pc Continuous service cos ϕ = 0.4 –
power consumption. T = – 10 ms
T Time constant.

20
Identification of the circuit-breaker type
The identification code of a circuit-breaker is made up with the elements from
the table below.
For correct identification of a circuit-breaker, it is necessary to refer to the
characteristics tables on pages 12 to 16.
The selected circuit-breaker can then be completed with the optional accesso-
ries indicated on the following pages.

Examples of identification
• The code HD4/C 12.16.25 identifies a withdrawable circuit-breaker for CBE
enclosure or CBF fixed part with 12 kV rated voltage, 1600 A rated normal
current and 25 kA breaking capacity.
• The code HD4/W 24.20.25 identifies a withdrawable circuit-breaker for
PowerCube modules with 24 kV rated voltage, 2000 A rated normal current
and 25 kA breaking capacity.

HD4 ... ... ... ...

Version Fixed –
CBE / CBF C
UniGear ZS1 type P
PowerCube W-P
ZS3.2 Z

Rated voltage 12 kV 12
17.5 kV 17
24 kV 24
40.5 kV 40

Rated normal
current (1)
630 A 06
1250 A 12
1600 A 16
2000 A 20
2500 A 25
3150 A 32
3600 A 36

Rated
breaking
16 kA 16
capacity 20 kA 20
25 kA 25
31.5 kA 32
40 kA 40
50 kA 50

(1) Rated uninterrupted current defined in free air for fixed circuit-breaker.
For the withdrawable version, see the previous pages.

21
3 SPECIFIC PRODUCT CHARACTERISTICS

Resistance to vibrations 60721-2-1 and IEC 60068-2-2 (Test B: Dry Heat /


HD4 circuit-breakers are unaffected by mechani- IEC 60068-2-30 (Test Bd: Damp Heat, cyclic)
cally generated vibrations. Standards.
For the versions approved by the naval registers,
please contact us.
Altitude
The insulating property of air decreases as the alti-
Tropicalization tude increases, therefore this must always
HD4 circuit-breakers are manufactured in compli- be taken into account for external insulation of
ance with the strictest regulations for use in hot- the apparatus (the internal insulation does not
humid-saline climates. undergo any variations as it is guaranteed by
All the most important metal components are the SF6 gas).
treated against corrosive factors according to The phenomenon must always be taken into con-
UNI 3564-65 Standards environmental class C. sideration during the design stage of the insulating
Galvanisation is carried out in accordance with components of apparatus to be installed over 1000
UNI ISO 2081 Standards, classification code m above sea level In this case a correction coeffi-
Fe/Zn 12, with a thickness of 12x10-6 m, protected cient must be considered, which can be
by a conversion layer mainly consisting of taken from the graph to the side, built up on the
chromates in compliance with the UNI ISO 5420 basis of the indications in the IEC 60694 Stand-
Standards. ards.
These construction characteristics mean that the The following example is a clear interpretation of
whole HD4 series of circuit-breakers and its ac- the indications given above.
cessories comply with climate graph 8 of the IEC

Example
• Installation altitude 2000 m
• Operation at the rated voltage of 12 kV
• Withstand voltage at industrial frequency 28
Ka = e m (H – 1000)/8150
kV rms (IEC 60071-2)
• Impulse withstand voltage 75 kVp
• Factor Ka obtained from graph = 1.13.

Considering the above parameters, the


apparatus will have to withstand the following
values (under test and at zero altitude, i.e. at
sea level):
– withstand voltage at industrial frequency
equal to:

28 x 1.13 = 31.6 kVrms

– impulse withstand voltage equal to:

75 x 1.13 = 84.7 kVp.

From the above, it can be deduced that for


installations at an altitude of 2000 m above
sea level, with 12 kV service voltage, appara- Graph for determining the Ka correction factor accord-
tus must be provided with 17.5 kV rated volt- ing to the altitude
age, characterised by insulation levels at in- H = altitude in metres;
dustrial frequency of 38 kVrms with 95 kVp m = value referred to industrial frequency and the atmos-
impulse withstand voltage. pheric impulse withstand voltages and those between
phase and phase.

22
Switching special loads
The table indicates the breaking capacities which can be guaranteed for switching special loads.

Circuit-breaker HD4

Rated normal current In [A] 630 1250 1600 2000 2500 3150 3600
for fixed circuit-breaker

No-load MV/LV transformer Isc [A] 10 10 10 10 10 10 10


breaking

No-load cable Isc [A] 12 kV 25 25 25 25 25 25 25


breaking 17.5 - 24 kV 31.5 31.5 31.5 31.5 31.5 31.5 31.5
36 - 40.5 kV 50 50 50 50 50 – –

Capacitive current breaking Isc [A] 400 630 1000 1250 1250 1250 1250
(C2 class)

Reactance compensation Isc [A] 630 630 1250 1250 1250 1250 1250
current breaking

Breaking of rated motor Isc [A] 630 630 1250 1250 1250 1250 1250
currents

Environmental protection programme by a single opening operation and that there is no


HD4 circuit-breakers are manufactured in accord- closing operation after this. To obtain a further
ance with the ISO 14000 Standards (Guidelines closing operation, the closing command must be
for environmental management). released and then relaunched.
The production processes are carried out in com- Furthermore, the anti-pumping device only allows
pliance with the Standards for environmental pro- circuit-breaker closure if the following conditions
tection in terms of reduction in energy consump- are present at the same time:
tion as well as in raw materials and production of – operating mechanism springs fully charged
waste materials. All this is thanks to the medium – opening pushbutton and/or opening release
voltage apparatus manufacturing facility environ- (-MO1/-MO2) not enabled
mental management system. – main circuit-breaker contacts open.
Assessment of the environmental impact of the life
cycle of the product, obtained by minimising en- Spare parts
ergy consumption and overall raw materials of the Replacement can only be carried out by
product, became a concrete matter during the de- trained personnel and/or in our workshops:
sign stage by means of targeted selection of the – opening springs
materials, processes and packing. – closing springs
Production techniques which prepare the products – complete pole
for simple dismantling and separation of the com- – basic operating mechanism
ponents are used during manufacture of the cir- – bushings, terminals and insulating protections.
cuit-breakers. This is to allow maximum recycling
at the end of the useful life cycle of the apparatus. Replacement which can be carried out by the
customer:
Anti-pumping device – isolating contacts
The ESH operating mechanism on HD4 circuit- – geared motor limit switch contact
breakers (in all versions) is fitted with a mechanical – KA1 instantaneous relay
anti-pumping device which prevents re-closing due – KA2 instantaneous relay.
to either electrical or mechanical commands.
Should both the closing command and any one of Ordering
the opening commands be active at the same For availability and ordering of spare parts, please
time, there would be a continuous succession of contact our Service, specifying the circuit-breaker
opening and closing operations. serial number.
The anti-pumping device avoids this situation, en-
suring that each closing operation is only followed

23
4 OVERALL DIMENSIONS

Type HD4/GT Fixed circuit-breakers without terminals


TN 7201
Ur 12 kV
Ir 1250 A
Isc 40 kA
50 kA

Type HD4/GT
TN 7201
Ur 12 kV
Ir 1600 A
Isc 20 kA
25 kA
31.5 kA
40 kA
50 kA

Type HD4/GT Fixed circuit-breakers without terminals


TN 7202
Ur 12 kV
Ir 2000 A
2500 A
3150 A
Isc 25 kA
31.5 kA
40 kA
50 kA

24
Type HD4/GT Fixed circuit-breakers without terminals
TN 7360
Ur 12 kV
Ir 630 A
1250 A
Isc 20 kA
25 kA
31.5 kA

Type HD4/GT Fixed circuit-breakers without terminals


TN 7361
Ur 12 kV
Ir 630 A
1250 A
Isc 20 kA
25 kA
31.5 kA

25
4 OVERALL DIMENSIONS

Type HD4 Fixed circuit-breakers


TN 7177
Ur 17.5 kV
Ir 630 A
161
1250 A 493 176
44
1600 A 150 150 92 378.5 92
10 334.5 44

F 22
Isc 16 kA

F 22
50
25 kA
31.5 kA

317
317
28

10
F 22

10
640 F 22
YU
582

549.5

540
YU

8
297.5

297.5
257.5

Q60

21.5
43

347
F 10.5 F 13 120
473 1250A 270
37
493 1600A 335 630A

Type HD4 Fixed circuit-breakers


TN 7178
Ur 17.5 kV
Ir 630 A
1250 A
1600 A
600 161
Isc 16 kA 578 92 379
25 kA 210 210 176
44 335
92 44
31.5 kA 50 10
F 22
F 22

317
317

10

F 22
28 F 22
648.5

10

622
558.5

YU
468.5

YU
306.5
306.5
266.5

8
43

472 F 13 120
F 10.5
598 270
1250A 37
618
1600A 335 630A

26
Type HD4 Fixed circuit-breakers
TN 7163
Ur 17.5 kV 600
Ir 1600 A 578
210 210
Isc 40 kA
50 kA

Type HD4
TN 7163 2x F18

310
Ur 17.5 kV

310
Ir 2000 A 28

80
Isc 25 kA
15.5 32

655
31.5 kA

622
YU

40 kA

8
YU

50 kA

306.5
266.5
Q60
8

F 13
43

472
598 F 10.5 35
2.5

20
618 322
385
561

Type HD4 Fixed circuit-breakers


TN 7165
Ur 17.5 kV 137.5 137.5 420 min.
Ir 2500 A 730
708
3150 A
275 275
3600 A 465

349.5
Isc 25 kA
31.5 kA
40 kA
670 min.

50 kA
15
310

Type HD4 28
62

TN 7165 20 40
655

20

622

Ur 24 kV YU

Ir 2500 A
468.5
40

YU

3150 A
20
20

8
3600 A
266.5

Isc 25 kA 4 x F 18
F 13
31.5 kA
43

40 kA
602 F10.5 115
2
20

728 322
35
748 385
603

Insulating partitions (only for 24 kV) to be provided


by the customer (a special kit is available on
request).

27
4 OVERALL DIMENSIONS

Type HD4 Fixed circuit-breakers


TN 7179
Ur 24 kV 600
578
Ir 630 A 210 210 400 min. 200
1250 A 105 105 161
1600 A 92 44 399 176
10 92 44
50 355
Isc 16 kA
20 kA

F 22
25 kA

F 22
670 min.

362

362

F 22
F 22
10
729.5
28
712

639.5

622
YU

468.5
YU

342.5
342.5
302.5
10

Q60
8

F 13
43

472 120
598 F10.5 270
1250A 37
618 1600A 335 630A

Insulating partitions to be provided by


the customer (a special kit is available
on request).

Type HD4 Fixed circuit-breakers


TN 7242
Ur 24 kV
Ir 630 A 730
161
1250 A 708
44
275 275 92 399 176
1600 A 50 10 355
92
44
Isc 16 kA
20 kA
F 22

25 kA
F 22
362

362

F 22
F 22
729.5

10

28
639.5

620

YU
468.5

YU

10
342.5

342.5
302.5

8
Q60

F 13
43

602 120
728 F 10.5 270
1250A 37
748 335
1600A 630A

28
Type HD4 Fixed circuit-breakers
TN 7174
Ur 24 kV 730

Ir 1600-2000 A 708
275 275
Isc 25 kA
31.5 kA
40 kA

2x Ø 18

310
310

80
28
15.5 32

622
655
YU

8
YU

306.5
266.5
Q60

Ø 13
43

602 Ø 10.5 115 3

20
728 322
35
385
748
561

29
4 OVERALL DIMENSIONS

Type HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7184
For CBE11
493
CBF11
150 150
Ur 12 kV

10
30 202 56 72 5.5
17.5 kV
Ir 630 A
1250 A
Isc 16 kA
25 kA
31.5 kA

F 35
28

205

636
627

630
588

547
8

264

78
158
20

340 4
F 19.5
25.5
458 416
503 437
532 36 570 53
659

Type HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7151
For CBE21 636
Ur 12 kV 578
210 210
17.5 kV
272 56 63
Ir 1250 A 44 15
Isc 40 kA
10

50 kA

Type HD4/C
TN 7151
For CBE21
310

CBF21 (31.5 kA) 28


702
695

Ur 12 kV
673

640

17.5 kV
Ir 1600 A
Isc 25 kA
F 79

8
31.5 kA
284

89

40 kA
169
25.5

50 kA

4
F19.5

550 359
606 416
40
36 551 53
653
640
682

30
HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7153
For CBE31
Ur 12 kV
842
17.5 kV 730
56 63
Ir 2000 A 275 275 15
144 232 10
Isc 25 kA
31.5 kA
40 kA

F 109
50 kA

310
28

695
673

702
640
8

284

89
169
708 4

F 19.5
25.5
750 359 30
792 416 53
853
552
882 36

HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7155
For CBE31
Ur 12 kV
17.5 kV 842
Ir 2500 A 730

Isc 25 kA 275 275 15


34 x 80 56 63
144 232 10
31.5 kA
40 kA
50 kA
80

(*)
310

28
695
673

702
640

YU

YU

8
284

Q60
89
169

708 4
25.5

Φ 19.5

359 30
750
416
792 53
33 554
(*) Only for 17.5 kV. 853
640
882

31
4 OVERALL DIMENSIONS

Type HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 1VCD000017
For CBF31
Ur 12 kV
Ir 3150 A
Isc 25 kA
31.5 kA
40 kA
50 kA

Type HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7186
For CBE41
CBF41 636
578
Ur 24 kV 210 210
799

Ir 630 A
20

272 23
1250 A 44

Isc 16 kA
F 35

20 kA
25 kA
310

28
776

767

740

792
649

8
329

12.5
125
202

25.5

550 4 53
F 23
25.5

452
610
460
653
682 710
36

32
HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7156
For CBE41 641
578
Ur 24 kV 799
210 210
Ir 1250 A 272 23
Isc 31.5 kA 44

40 kA

20
F 35
310
28
776

718

682
792
8
329
25.5

125
10

202

550 25.5
452 4 53

F 23
610
460
653
710
682 36

HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures and CBF fixed parts
TN 7157
For CBE51
Ur 24 kV
Ir 1600 A
Isc 31.5 kA
40 kA

33
4 OVERALL DIMENSIONS

HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures


TN 7158
For CBE51
Ur 24 kV
Ir 2000 A
Isc 25 kA
31.5 kA
40 kA

HD4/C HD4/C withdrawable circuit-breakers for CBE enclosures


TN 7159
842
For CBE51 708
Ur 24 kV 275 275
34 x 80

144 232 20 23
Ir 2500 A
Isc 25 kA
31.5 kA
80

40 kA
380

28
821.5

838
704

8
349

125
202

750 4
452
F 23
25.5

805
457 30
853
882

34
HD4/GT/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 7286
Ur 12 kV
Ir 630 A
493
1250 A
150 150
Isc 20 kA 56 72 5.5
202

10
30
25 kA
31.5 kA

67.5
HD4/P (*)
TN 7286

F 35

622 MAX
51

205
Ur 12 kV

621.5
624.5

543
17.5 kV

586
Ir 630 A
63

1250 A
28
Isc 16 kA
247.5

25 kA 260
Q60

78
31.5 kA

154
20

4
4

21.5
F 19
4

458 416
503 437
532 570 53
36
(*) HD4/P kV for 659
PowerCube.

HD4/GT/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards


TN 7350
Ur 12 kV
Ir 1250 A
Isc 40 kA

HD4/GT/P
TN 7350
Ur 12 kV
Ir 1600 A
Isc 20 kA
25 kA
31.5 kA
40 kA
50 kA

HD4/GT/P
TN 7351
Ur 12 kV
Ir 2000 A
Isc 25 kA
31.5 kA
40 kA
50 kA

35
4 OVERALL DIMENSIONS

HD4/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards


TN 7350
Ur 12 kV (*)
17.5 kV
Ir 1250 A
Isc 40 kA
HD4/P
TN 7350
Ur 12 kV (*)
17.5 kV
Ir 1600 A
Isc 25 kA
31.5 kA
40 kA
50 kA
HD4/P
TN 7351
Ur 12 kV (*)
17.5 kV
Ir 2000 A
Isc 25 kA
31.5 kA
40 kA
50 kA
(*) HD4/P 12 kV for
PowerCube.

HD4/GT/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards


TN 7352
Ur 12 kV
Ir 2500 A
Isc 25 kA
31.5 kA
40 kA
50 kA

HD4/P
TN 7352
Ur 12 kV (*)
17.5 kV
Ir 2500 A
Isc 25 kA
31.5 kA
40 kA
50 kA

(*) HD4/P 12 kV for


PowerCube.

36
HD4/GT/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 7371
Ur 12 kV
Ir 3150 A (*)
Isc 25 kA
31.5 kA
40 kA
50 kA

HD4/P
TN 7371
Ur 17.5 kV
Ir 3150 A (*)
Isc 25 kA
31.5 kA
40 kA
50 kA

(*) 3600 - 4000 A with


forced switchboard
ventilation (consult the
UniGear type ZS1
switchboard technical
catalogue).

HD4/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards


TN 7354
Ur 24 kV
Ir 630 A
1250 A
Isc 16 kA
20 kA
25 kA

37
4 OVERALL DIMENSIONS

HD4/P (*) HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 7355
Ur 24 kV
Ir 1600 A
Isc 16 kA
20 kA
25 kA
31.5 kA (**)

(*) Also valid for


PowerCube.
(**) Not for PowerCube.

HD4/P (**) HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 7356
Ur 24 kV
Ir 2000 A
Isc 16 kA
20 kA
25 kA
31.5 kA (***)

HD4/P (**)
TN 7356
Ur 24 kV
Ir 2500 A (*)
Isc 20 kA
25 kA
31.5 kA (***)

(*) 2500 A with forced


ventilation; 2300 A
with natural ventila-
tion.
(**) Also valid for
PowerCube.
(***) Not for PowerCube.

38
HD4/P HD4/P withdrawable circuit-breakers for UniGear type ZS1 switchboards
TN 1VCD000099
Ur 24 kV
Ir 1250 A
Isc 31.5 kA

HD4/W HD4/W withdrawable circuit-breakers for PowerCube modules


TN 7229
Ur 12 kV
17.5 kV 493
Ir 630 A 150 150
72 5.5

10
1250 A 30 202 56

Isc 16 kA
25 kA
31.5 kA

48
F 35
205
625.5

628.5
590

547
636

28
264

Q60
78
158

340 416 4
21.5
F 19.5

458 437
20
503 570 53
36
532
659

39
4 OVERALL DIMENSIONS

HD4/W HD4/W withdrawable circuit-breakers for PowerCube modules


TN 7182
Ur 12 kV 636
17.5 kV 578

Ir 630 A 210 210

10
44 228 56 63 15
1250 A
Isc 16 kA

F 35
25 kA
31.5 kA

310
28

695
692

702
640
284 8

89
169
606 4
359
653 40
551 53
682 36
640

HD4/W HD4/W withdrawable circuit-breakers for PowerCube modules


TN 7421
Ur 12 kV
17.5 kV
Ir 1250 A
Isc 40 kA
50 kA

40
HD4/W HD4/W withdrawable circuit-breakers for PowerCube modules
TN 7239
636
Ur 12 kV 578
17.5 kV 210 210
Ir 1600 A 272
63
56 15

10
44
2000 A
Isc 16 kA
25 kA
31.5 kA

310
28

695
673

702
640
F 79
8

284

89
169
4
606 359 40
653 36 551 53
682 640

HD4/W HD4/W withdrawable circuit-breakers for PowerCube modules


TN 1VCD000053
Ur 12 kV
17.5 kV
Ir 3150 A
Isc 31.5 kA
40 kA
50 kA

41
4 OVERALL DIMENSIONS

HD4/W HD4/W withdrawable circuit-breakers for PowerCube modules


TN 7183
Ur 24 kV
636
Ir 630 A 578
210 210
1250 A 23

20
272
Isc 16 kA 44
20 kA
25 kA

F 35
310
776

28
767

740

792
649
8
329

125
12.5

202
25.5

610 4 53
460
653 710
682 36

HD4/Z 40.5 kV HD4/Z withdrawable circuit-breakers for UniGear type ZS3.2 - 40.5 kV switchboards
TN 7227
Ur 40.5 kV
Ir 1250 A
1600 A
2000 A
2500 A (*)
Isc 25 kA
31.5 kA

ØA
1250-1600 A 35 mm
2000-2500(*)A 79 mm

(*) With natural ventila-


tion in loose enclo-
sure type Powerbloc;
with forced ventila-
tion in switchboard
type ZS3.2.

42
5 ELECTRICAL CIRCUIT DIAGRAM

Application diagrams
The following diagram (No. 400007) shows the circuits of the withdrawable circuit-breakers up to 24 kV
type HD4/C, HD4/P, HD4/W, delivered to the customer by means of connector “X”.

Specific diagrams are avail-


able for other types of cir-
cuit-breakers:
– fixed circuit-breakers up to
24 kV - 1VCD 400005
– HD4/z 40.5 kV with draw-
able circuit- breakers -
1VCD 400013.
In any case, to take into ac-
count the evolution of the
product, it is always useful
to refer to the circuit diagram
provided with each circuit-
breaker.

43
5 ELECTRICAL CIRCUIT DIAGRAM

44
45
5 ELECTRICAL CIRCUIT DIAGRAM

Represented operational state -BT2 = Contacts signalling circuit-breaker in the isolated position (see
note G)
The diagram indicates the following conditions:
-SC = Pushbutton or contact for the circuit-breaker closing
– circuit-breaker open and connected
-BK = Contact operated by the key lock preventing electrical opening
– circuits de-energized
with earthing truck connected (It is mandatory for earthing truck
– closing springs discharged
with making capacity)
– key lock with key inserted and trapped
-SL1 = Contact locking for circuit-breaker closing
– SF6 gas pressure at rated service value (380 kPa absolute).
-SO = Pushbutton or contact for the circuit-breaker opening
-TR1, -TR2 = Rectifiers for shunt opening releases -MO1 and -MO2
Caption -XB = Connector for the circuit-breaker circuits
-XB2…-XB62 = Connectors of accessories
= Reference number of diagram figure -XB1 = Switchboard terminal board (mounted externelly to the circuit-
* = See note indicated by the letter breaker)
-BM = Device for the supervision of shunt opening release coil continuity -MC = Shunt closing release
(see note E) -RL1 = Locking magnet on the operating mechanism. If de-energized it
-BP = Pressure-switches with two operating levels: prevents the circuit-breaker closing mechanically
– operating for low gas pressure. Contacts 11-12-14 change -RL2 = Locking magnet on the truck. If de-energized it prevents the cir-
position, as regard the position indicated on the diagram, when cuit-breaker racking-in and racking-out mechanically (It is pos-
the pressure from 380 kPa absolute gets to a value lower than sible to limit its consumption by connecting in series a delaying
310 kPa absolute. In case of rated pressure reset the same pushbutton enabling the operation)
contacts change again position when the pressure, from a -MO1 = First shunt opening release (see note E)
value lower than 310 kPa absolute, gets up to 340 kPa -MO2 = Second shunt opening release (see note E)
absolute. -MO3 = Opening solenoid for the PR512 microprocessor based release
– operating for insufficient gas pressure. Contacts 21-22-24 external the circuit-breaker (see note D)
change position when the pressure from 380 kPa absolute -MU = Instantaneous undervoltage release or undervoltage release with
absolute gets to a value lower than 280 kPa absolute. In case electronic time-delaying device (see note B)
of rated pressure reset the same contacts change again -VF = Filter (provided with voltage supply 220V d.c. or greater)
position when the pressure, from a value lower than 280 kPa
absolute, gets up to 310 kPa absolute.
-KT = Solid-state time-delaying device for the undervoltage release
Diagram figures description
(see note I)
-KI = Integrated gas pressure control circuit, including: Fig. 1 = Spring charging-motor circuit (see note C).
-PG = Green led indicating normal gas pressure Fig. 2 = Shunt closing release (antipumping is achieved mechanically).
-PR = Red led indicating insufficient gas pressure Fig. 3 = Locking magnet on the operating mechanism. If de-energized
-PY = Yellow led indicating low gas pressure it prevents the circuit-breaker closing mechanically.
-KA1 = Auxiliary relay to double the -BP pressure-switch con- Fig. 4 = Locking magnet on the truck. If de-energized it prevents the
tacts operating for low gas pressure circuit-breaker racking-in and racking-out mechanically (It is
-KA2 = Auxiliary relay to double the -BP pressure-switch con- possible to limit its consumption by connecting in series a de-
tacts operating for insufficient gas pressure laying pushbutton enabling the operation) (see note H).
-XB5 = Connector Fig. 5 = Instantaneous undervoltage release (see note B)
-BR51 = Microprocessor based overcurrent release type PR512 external Fig. 6 = Undervoltage release with solid-state time-delaying device (see
to the circuit-breaker (see note D) notes B and I)
-MS = Motor for the closing springs charging (see note C) Fig. 7 = First shunt opening release circuit with possibility of perma-
-QB = Main circuit-breaker nent supervision of coil continuity (see note E).
-BB1…-BB3 = Circuit-breaker auxiliary contacts (no. 3 packs of 5 contacts) Fig. 9 = Second shunt opening release circuit with possibility of perma-
-BB4 = Auxiliary passing contact (closing momentarily when circuit- nent supervision of coil continuity (see note E).
breaker opens) Fig. 10 = Opening solenoid for PR512 microprocessor based release
-BB5 = Contacts signalling undervoltage release energized/de-energized external to the circuit-breaker (see note D).
-FB1 = Miniature breaker with thermomagnetic O/C release for protec- Fig. 11 = Gas pressure control circuit including:
tion of the spring-charging motor (see note F) – contacts for remote indication of normal, low and insufficient
-BS1...2 = Limit switches of the spring-charging motor gas pressure.
-BD1 = Position contact of the enclosure door. Foreseen for HD4/C only. For -BP pressure-switches tripping values see the caption.
-BT3 = Circuit-breaker position contact. It is open during the isolating Fig. 12 = Integrated gas pressure control circuit, including:
travel of the breaker – circuit-breaker opening through the -MO2 release and clos-
-BT5 = Contacts signalling circuit-breaker in the removed position (they ing lock through a -KA2 relay auxiliary contact in case of
are those signalling circuit-breaker in the isolated position located insufficient gas pressure (provide the locking magnet given
on the enclosure, in the fixed part: see contacts -BT2 given on in fig. 3)
circuit diagram 1VCD 400036 figures 5-6) – 3 leds for local indication of normal, low and insufficient gas
-BT1 = Contacts signalling circuit-breaker in the connected position (see pressure
note G)

46
– contacts for remote indication of normal, low and insufficient Notes
gas pressure. A) The circuit-breaker is only fitted with the accessories listed in the order
For -BP pressure switches tripping values see the caption. confirmation. To make out the order, please consult the catalogue of the
Fig. 14 = Integrated gas pressure control circuit, including: apparatus.
– lock of circuit-breaker closing and opening through -KA2 relay B) The undervoltage release can be provided for power supply with volt-
auxiliary contacts in case of insufficient gas pressure (provide age branched on the supply side of the circuit-breaker or from an inde-
the locking magnet given in fig. 3) pendent source.
– 3 leds for local indication of normal, low and insufficient gas Either the instantaneous undervoltage release or the one with elec-
pressure tronic delay device can be used (delay can be selected between 0.5 …
– contacts for remote indication of normal, low and insufficient 3 s; see note I). Circuit-breaker closing is only possible with the release
gas pressure. energised (the closing lock is made mechanically).
For -BP pressure switches tripping values see the caption. The contact in fig. 24 or the one in fig. 25 is available on request.
Fig. 20 = Contact operated by the key lock, preventing electrical opening, A delay of 50 ms between the moment of consent of the undervoltage
with earthing truck with making capacity connected. (It is obliga- release and energisation of the shunt closing release must be inserted
tory for earthing truck with making capacity when is requested the when there is the same power supply for the shunt closing and
first shunt opening release -MO1). undervoltage releases and automatic circuit-breaker closing on return
Fig. 21 = Miniature breaker with thermomagnetic O/C release for protec- of the auxiliary power supply is required. This can be carried out by
tion of the spring-charging motor (see note F). means of a circuit outside the circuit-breaker, including a permanent
Fig. 22 = Contact signalling closing springs charged. closing contact, the contact indicated in fig. 24 and a time-delay relay.
Fig. 23 = Contact signalling closing springs discharged. C) Check the power available on the auxiliary circuit to verify the possibil-
Fig. 24 = Contact signalling undervoltage release energized (see note B). ity of starting several motors for charging the closing springs at the
Fig. 25 = Contact signalling undervoltage release de-energized (see note B). same time. To avoid excessive consumption, it is necessary to charge
Fig. 26 = Contact signalling miniature breaker for protection of the spring- the springs manually before supplying the auxiliary circuit with voltage.
charging motor on. D) Please see diagram 401530 for the connections between the circuit-
Fig. 27 = Contact signalling miniature breaker for protection of the spring- breaker auxiliary circuits and the PR512 type of microprocessor-based
charging motor off. overcurrent release located in the switchboard.
Fig. 30 = Passing auxiliary make contact closing momentarily when cir- E) The circuit for controlling continuity of the shunt opening release winding
cuit-breaker opens (-MO1, -MO2, -MO3 and -MU). must only be used for this function.
Fig. 31 = Circuit-breaker available auxiliary contacts. At a power supply lower than 220V, connect the “Control Coil Continu-
Fig. 32 = Circuit-breaker available auxiliary contacts. ity” device, or a relay or a signalling lamp which consumes a current
Fig. 51 = Contacts signalling circuit-breaker in the connected and isolated not exceeding 20 mA.
positions located on the circuit-breaker, they are provided on At a power supply equal to or higher than 220V, connect a delay or
request (see note G). signalling lamp which consumes a current not exceeding 10 mA.
Other uses might jeopardise release functionality.
F) The -FB1 circuit-breaker in fig. 21 must always be provided when there
Incompatibility is a 24 kV d.c. spring charging motor.
The combination of circuits given in the figures below are not possible on In case of opening caused by a fault in the motor, before carrying out
the same circuit-breaker: manual resetting, recharge the springs by means of the special handle.
G) The contacts (-BT1 and -BT2) shown in fig. 51 for signalling the circuit-
breaker status are located on the circuit-breaker (moving part) and are
5 - 6 - 14 9 - 10 - 12 - 20 24 - 25
available on request. However, application of these contacts on the
5 - 6 - 20 11 - 12 - 14 26 - 27 enclosure is usually foreseen (fixed part): see diagram 401693 for CBE
9 - 10 - 12 - 14 22 - 23 31 - 32 11 - 21 - 31 and diagram 401526 for CBE 41 - 51.
H) When fig. 9 is requested, the contact of pack -BB3 to terminals 29-30 in
fig. 32 is not available.
When figs. 26-27 are requested, the -BB2 contact to terminals 29-30 of
figs. 31-32 is not available.
When fig. 30 is requested, the contact of pack -BB3 to terminals 23-24
in fig. 32 is not available.
I) Make one of the following bridges to select the delay required:
0.5 s: terminals 6-7
1 s: terminals 6-8
1.5 s: terminals 6-9
2 s: terminals 6-10
3 s: no bridge.
J) When fig. 4 is requested, the contact of pack -BB1 to terminals 7-8 in
figs. 31-32 is not available.

47
5 ELECTRICAL CIRCUIT DIAGRAM

Graphical symbols for electrical diagrams (IEC 60617 and CEI 3-14 ... 3-26 Standards)

Connections Break contact


Thermal effect
of conductors

Electromagnetic effect Terminal or clamp Change-over break


before make contact

Passing make contact


Socket and plug closing momentarily during
Timing (female and male) release

Resistor Closing position contact


Pushbutton control (general symbol) (limit switch)

Capacitor (general Opening position contact


Operated by key symbol) (limit switch)

Power circuit-breaker
Earth (general symbol) M Motor (general symbol) with automatic opening

Rectifier with two Control coil


Mass, frame half-waves (bridge) (general symbol)

Conductors in shielded
cable (two conductors Make contact Lamp (general symbol)
shown)

48
Contact us

ABB S.p.A. The data and illustrations are not binding. We reser-

1VCP000245 - Rev. B, en - Technical catalogue - 2009.09 (HD4 - IEC & GOST) gs


ve the right to make changes without notice in the
Power Products Division course of technical development of the product.
Unità Operativa Sace-MV
Via Friuli, 4 Copyright 2009 ABB.
I-24044 Dalmine All rights reserved.
Tel.: +39 035 6952 111
Fax: +39 035 6952 874
e-mail: sacetms.tipm@it.abb.com

ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33 Petzower Strasse 8
D-40472 Ratingen D-14542 Glindow
Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916
E-mail: calor.info@de.abb.comABB s.r.o.

www.abb.com

You might also like