50-EG1 (705)
TM
Packaged Rooftop
Air Conditioning Units
10050VIP
ASHRAE
90.1
50 THROUGH 130 TONS COMPLIANT
MEA
231-02-E
2
BASE MODEL NUMBER:
YPAL050-105
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
BASE PRODUCT TYPE NOMINAL CAPACITY APPLICATION REFRIGERANT VOLTAGE SUPPLY RETURN DESIGN/SPECIAL
C : Constant Volume
V : VAV, VFD
F : Flexsys
YPAL106-130
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
BASE PRODUCT TYPE NOMINAL CAPACITY APPLICATION REFRIGERANT VOLTAGE SUPPLY RETURN DESIGN/SPECIAL
C : Constant Volume
V : VAV, VFD
F : Flexsys
YORK INTERNATIONAL
FORM 100.50-EG1 (705)
FORM 100.50-EG1 (705)
Table of Contents
YORK INTERNATIONAL 3
FORM 100.50-EG1 (705)
Introduction
The eco2 packaged rooftop – De-
signed to meet the demands of
the market for today and
tomorrow.
Better Economy...
Lower total cost of ownership
• High efficiency eco2 rooftop units are optimized for
HCFC-22 refrigerant. YORK provides the FIRST
standard product offering that meets the latest
ASHRAE 90.1 energy efficiency requirements. LD07431
Better Ecology...
Indoor air quality features for the indoor environ-
ment
• A double-sloped stainless steel drain pan with a
single drain connection ensures that all conden-
sate is voided from the drain pan. It is also visible
and accessible for periodic inspection and clean-
ing required by the ASHRAE 62 IAQ standard.
• Double-wall construction of the roof, floor, doors,
and walls prevents insulation fibers from entering
the conditioned air. The inner liner also facilitates
periodic cleaning of the unit to prevent harmful build-
up of bacteria or contaminants.
• The rooftop unit control center uses microproces-
sor logic to analyze and optimize ventilation deci-
sions and perform demand ventilation, airflow com-
pensation, and airflow measurement to maintain
the air quality at a healthy level.
4 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 5
FORM 100.50-EG1 (705)
6 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
damper is positioned to the manually configured point pressure sensor must be supplied by others and in-
(set by mechanical stop). In the unoccupied mode, the stalled in a representative location in the building.
damper is fully closed.
Powered Return Fan with Exhaust – This option uses
Modulating Economizer – This option includes modu- SWSI plenum fan(s) to control building pressure. The
lating outdoor air and return air dampers that are inter- fan motors are driven by a VFD to maintain a constant
locked (YPAL050-065 mechanical interlock, YPAL070- return plenum pressure. An exhaust hood with a modu-
130 software interlock) and positioned by fully modulat- lating control damper is used to maintain building pres-
ing, solid state damper actuators. Control of the damper sure via the building static pressure. The static pres-
is via a standard ambient outdoor air dry bulb sensor, sure transducer is provided in the return plenum of the
or optional single or comparative enthalpy controls. rooftop unit, and 5/16" or 1/4" plastic tubing and static
pressure sensor must be supplied by others and in-
Airflow Measurement – Optional outside airflow mea-
stalled in a representative location in the building. The
surement is available on units equipped with a Modu-
powered return fan is also available without the exhaust
lating Economizer. Two options exist for airflow mea-
capabilities. For units with no exhaust capabilities, the
surement; minimum (0-25%) and full (0-100%) .
HVAC system must provide alternate means of control-
CO2 Sensors – Optional carbon dioxide sensors for ling building pressure.
occupied space that operate demand ventilation con-
trol opening outside air dampers to ventilate building. SUPPLY FAN OPTIONS
The CO2 sensors can operate in a single or compara-
tive control scheme. DWDI Forward-Curved Supply Fan – The standard
supply air blower in the YPAL050-105 models is a for-
Rain Hoods on Outside Air Intakes – For all options
ward-curved supply fan. This fan is good for medium
with outside air intake openings, rain hoods are pro-
static pressures and high airflows.
vided as standard to keep moisture from entering the
equipment. Rain hoods as an integral part of the unit DWDI Airfoil Supply Fan – An optional airfoil blade
and are rotated into place. supply fan is available on all models for higher static
conditions. This option offers higher efficiency and lower
RELIEF SYSTEM sound in certain applications.
Fan Skid Isolation – the entire supply fan assembly is
Barometric Relief – Optional building air exhaust shall
isolated from the unit base with two-inch deflection
be accomplished through barometric relief dampers in-
springs, or one (standard) or two-inch deflection springs
stalled in the return air plenum. The dampers will open
with seismic restraints.
relative to the building pressure. The opening pressure
shall be adjustable via a spring tension adjustment. Supply and Exhaust Fan Motors – high efficiency
ODP, and standard and high efficiency TEFC motors
On/Off Powered Exhaust – This option provides simple
are available all meeting the Energy Policy Act of 1992
building pressure control. It can be controlled via a
(EPACT).
building pressure signal, or via outside air damper con-
trol. This option is not available for VAV units. Supply Fan VFD and Manual Bypass – for VAV appli-
cations, VFD’s are provided to modulate air flow. Op-
Modulating Powered Exhaust with Damper Control
tional manual bypass can also be provided to allow full
– This option consists of a constant-speed exhaust fan
airflow in the event of a VFD failure.
with a discharge damper that is modulated to control
the flow of exhaust air. The damper control logic is
EVAPORATOR SECTION
based on the building static pressure setpoint within the
rooftop unit controller. The static pressure transducer
Double Sloped Stainless Steel Drain Pan – The Eco2’s
is provided in the return plenum of the rooftop unit, and
stainless steel drain pan is factory-mounted and installed
5/16" or 1/4" plastic tubing and static pressure sensor
on every unit. A condensate drain trap is needed, and
must be supplied by others and installed in a represen-
must be provided and installed in the field by others.
tative location in the building.
Drain Pan Detail*
Modulating Powered Exhaust with a VFD – This op-
tion consists of a VFD to modulate the speed of the
exhaust fan to control the flow of exhaust air. The VFD
control logic is based on the building static pressure
setpoint within the rooftop unit controller. The static pres-
sure transducer is provided in the return plenum of the
LD08022
rooftop unit, and 5/16" or 1/4" plastic tubing and static *NOTE:
This is a visual reference only. Actual drain pan pitch will vary.
YORK INTERNATIONAL 7
FORM 100.50-EG1 (705)
8 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 9
FORM 100.50-EG1 (705)
YORK INTERNATIONAL
Distributor Rainhoods to
Optional Optional tubes Angled or Optional prevent
Condenser
replaceable horizontal protected rigid flat airflow moisture
wire screen
core filter supply air in plastic filter measurement from entering
Optional louvers
driers openings sleeves section station the unit
available
Features and Benefits (continued)
10
11
FORM 100.50-EG1 (705)
Blower VFDs
Single supply fan
• Located in conditionedspace
• Eliminates stratification • Remote keypad in control section
• Fewer moving parts • In filtered air stream to prevent dust and
• Solid steel shaft dirt build-up
Evaporator • Isolated assembly
Exhaust & return fans • Angled coil to reduce • Laser aligned and balanced
• Horizontal return for all configurations risk of carryover
• DWDI centrifugal exhaust fans • Standard Stainless steel
• SWSI plenum return fans drain pan
• Variable-frequency drive options Side discharge with heat
Mixing box
• Does not require an elevated structure or curb
• OA from two sides
• Flexible solution for building application
• Facilitates mixing
YPAL106-130 MODEL
YORK INTERNATIONAL
• Collapsible for shipping to reduce freight • Induced draft furnace
• Single-piece shipment • Accepts gas pressures down to 3.5" • Control to discharge pressure
• Fast and easy setup • 6-stage base design • Quiet part load operation
Advanced Rooftop Controller
• Multimedia card for updates (no EPROM)
• Multimedia card used for data logging
• Integrated YORK ISNConneXsys control solution
• Standard BACnet MS/TP and Modbus communications
FORM 100.50-EG1 (705)
Application Data
GENERAL Finally, service clearances should be maintained in roof-
top design to insure safe access to the unit. Unit clear-
The eco2 air conditioning units are designed for out- ances are designed so that technicians have enough
door installation. When selecting a site for installation, space between units, building walls, and edges of build-
be guided by the following conditions: ing to gain access safely. In cases where space is lim-
ited, please call your local York representative for addi-
• Unit must be installed on a level surface.
tional information.
• For the outdoor location of the unit, select a place
having a minimum sun exposure and an adequate
supply of fresh air for the condenser.
• Also avoid locations beneath windows or between
structures.
• Optional condenser coil protection should be used
for seashore locations or other harsh environments.
• The unit should be installed on a roof that is struc-
turally strong enough to support the weight of the LD08044
unit with a minimum of deflection. It is recom-
RIGGING
mended that the unit(s) be installed not more than
15 feet from a main support beam to provide proper
Proper rigging and handling of the equipment is man-
structural support and to minimize the transmission
datory during unloading and setting it into position to
of sound and vibration. Ideally, the center of grav-
retain warranty status.
ity should be located over a structural support or
building column. Spreader bars must be used by cranes to prevent dam-
• Location of unit(s) should also be away from build- age to the unit casing. All lifting lugs must be used when
ing flue stacks or exhaust ventilators to prevent pos- lifting the rooftop unit. Fork lifts will damage the rooftop
sible reintroduction of contaminated air through the unit and are not recommended.
outside air intakes.
Care must be taken to keep the unit in the upright posi-
• Be sure the supporting structures will not obstruct tion during rigging and to prevent damage to the water-
the duct, gas or wiring connections. tight seams in the unit casing. Avoid unnecessary jar-
• Proper service clearance space of 6-feet around ring or rough handling.
the perimeter of the unit, 8-feet on one side for coil
servicing, and 12-feet to any adjacent units is re- UNIT PLACEMENT
quired to eliminate cross contamination of exhaust
and outdoor air, and for maintenance tasks such • Elevated – Elevated roof curbs or dunnage steel
as coil pull and cleaning. No obstructions should can be used to support the unit in order to raise it
be above the condensing unit section. to specific heights. When this type of placement is
required, be sure to keep unit access in mind. Cat
LOCATION walks or other forms of unit access may be required
to one or both sides of the unit, depending on your
Of the many factors that can effect the location of equip- area of the country and the local codes that are
ment, some of the most important to consider are Struc- enforced. Please check with local officials to en-
tural, Acoustical and Service clearances. Proper at- sure the application conforms to local codes and
tention should be made at the design stage to ensure regulations.
proper structural support. In cases where equipment • Ground Level Locations – It is important that the
is being replaced, be aware of building design to insure units be installed on a substantial base that will not
support is adequate for the application. settle, causing strain on the refrigerant lines and
The next most important consideration in applying roof sheet metal and resulting in possible leaks. A one-
top equipment is that of sound from the equipment. piece concrete slab with footers extended below
Special care should be made to keep the roof top unit the frost line is highly recommended. Additionally,
away from sound sensitive areas such as conference the slab should be isolated from the main building
rooms, auditoriums and executive offices and any other foundation to prevent noise and vibration transmis-
room that may have potential for tenant occupancy. sion to the building structure.
Possible locations could be above hallways, mechani- For ground level installations, precautions should
cal or utility rooms. be taken to protect the unit from tampering by, or
12 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
injury to, unauthorized persons. Erecting a fence TABLE 2: RETURN AIR DUCT CONNECTION CONFIGURATIONS
around the unit is common practice. Return Air
Unit Configuration
• Roof curb – YORK offers optional roof curbs de- Bottom Left Right Front
signed specifically for the eco2 footprint. These curbs No exhaust X X
come in full perimeter or open condenser models Barometric relief damper X Contact YORK
YPAL
and are shipped disassembled and require field as- 050-065 Powered exhaust fan
(all types) X
sembly and installation. For bottom supply and re-
Powered return fan X Not available
turn openings, the curbs have matching connections No exhaust X X X X
to ease installation. A pipe chase that matches the Barometric relief damper X X X
YPAL
rooftop unit pipe chase is also included in the curb Powered exhaust fan
070-105
footprint for through-the-curb utility connections. (all types) X X X
Powered return fan X
The curb should be located according to the loca-
No exhaust X X
tion recommendations above, and properly sealed
YPAL Barometric relief damper X X
to prevent moisture and air leakage into and out of Powered exhaust fan
the duct system. Flexible collars should be used 106-130
(all types) X X
when connecting the duct work to prevent unit noise Powered return fan X X
transmission and vibration into the building.
Duct work should be supported independently of
the unit. DUCT CONSIDERATIONS
Discharge Return
RIGHT
FRONT FRONT
LEFT BOTTOM
NOTE:
This diagram is provided as a visual reference of the eco2 discharge & return air openings & locations for all sizes. Please refer to the dimensional
data for exact size & location of panels and openings. LD08045
YORK INTERNATIONAL 13
FORM 100.50-EG1 (705)
their local environment. Air is returned from the room appropriate amount of air from the building.
at ceiling level (unducted plenum return is shown). The
Return fans – For high return static applications, such
resulting overall floor-to-ceiling air flow pattern takes
as buildings with ducted return systems, a powered
advantage of the natural buoyancy produced by heat
return fan may be necessary to maintain building pres-
sources in the space and more efficiently removes heat
sure control. York offers a powered return fan that is
loads and contaminants from the space, particularly for
located in the return plenum. This fan operates coinci-
cooling applications. In fact, some of the most impor-
dentally with the supply fan and draws return air back
tant advantages of underfloor systems over ceiling-
through the return ductwork and into a pressurized ple-
based systems occur during cooling conditions, which
num. A control damper modulates to exhaust air out of
are required year-round in the vast majority of interior
the building and maintain the building pressure. A sec-
office space in many parts of the United States.
ond control damper modulates to provide return air from
the ductwork to the unit to the rooftop air mixing section.
HARSH ENVIRONMENTS – CONDENSER AND
EVAPORATOR COIL PROTECTION The return fan configuration is available in two forms:
with and without an exhaust damper. The option with
For harsh environmental conditions such as seashore the exhaust damper provides a means of building ex-
applications, YORK offers three types of coil protec- haust at the unit. In some applications, the exhaust
tion: copper fin material, black fin and Technicoat coat- system is located elsewhere and the rooftop unit is not
ings. YORK recommends that for corrosive environ- required to provide building exhaust. In these situa-
ments that copper fins be used to protect the evapora- tions, the Eco2 can be offered without the exhaust
tor and/or condenser coils. In areas where chemicals damper to help reduce installed costs.
that can corrode copper are present, such as ammo-
Exhaust/relief fans – In this application, a powered
nia, YORK recommends that the black fin or Technicoat
exhaust fan may be suitable, however careful consid-
coating be used for maximum protection.
eration of the fan type is necessary. York offers a cen-
• Copper Fin Condenser Coil – Copper fins can be trifugal powered exhaust fan to perform this function.
used instead of aluminum for additional corrosion pro- Some manufacturers use a propeller exhaust fan, which
tection, however it is not suitable for areas that are cannot handle the static pressure requirements.
subject to acid rain or exposed to ammonia.
For systems with moderate to low return static pres-
• Pre-Coated Condenser Fins – Black fin coating sure, an exhaust fan is recommended. The benefit of
(yellow fin for evaporator fins) is pre-coated applica- the exhaust fan is that it does not run all of the time,
tion epoxy on aluminum fin stock to guard from cor- and may facilitate compliance with the ASHRAE 90.1
rosive agents and insulate against galvanic poten- fan motor horsepower requirement.
tial. It is used for mild seashore or industrial loca-
tions. This can provide corrosion resistance compa- The exhaust fan operates in parallel with the supply
rable to copper fin coils in typical seashore locations. fan. In this arrangement, the supply fan handles the
full static pressure requirements of the system. For
• Post-Coated Condenser Fins – Technicoat (a
normal building pressure control, the exhaust fan op-
post-coated application of epoxy) can be used for
erates to draw air from the return plenum and exhaust
seashore and other corrosive applications with the
it out of the building.
exception of strong alkaloides, oxidizers, wet bro-
mide, chlorine and fluorine in concentrations greater The exhaust fan configuration is available in two forms,
than 100 ppm. modulating and non-modulating. Modulating is the most
Any of the above suitable options should be se- common and recommended for the majority of appli-
lected based on the particular project design pa- cations, while non-modulating should be used with in
rameters and related environmental factors. The only certain circumstances.
application should be further reviewed and ap- In the modulating exhaust system, the volume of air-
proved by the consulting engineer or owner based flow exhausted from the building is proportional to the
on their knowledge of the job site conditions. entering volume of outside air. Control is accomplished
via either a discharge damper or a variable-frequency-
BUILDING PRESSURE CONTROL SYSTEMS drive (VFD). York recommends the use of a VFD to
reduce energy consumption, sound levels and improved
Building pressure control systems are often necessary reliability due to fewer moving parts.
when economizers are used to bring in outdoor air.
Without proper building exhaust, the building may be- In the non-modulating exhaust system, the exhaust air-
come over pressurized. The pressure control system flow is constant whenever the exhaust fan is operating.
maintains the proper building pressure by expelling the This type of control should only be used to either assist
YORK INTERNATIONAL 15
FORM 100.50-EG1 (705)
16 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 17
FORM 100.50-EG1 (705)
Physical Data
TABLE 3 – PHYSICAL DATA – MODELS 50-70
MODEL SIZE 50 55 60 65 70
GENERAL DATA
Standard cabinet length without hoods (inches) 344 344 344 344 454
Extended cabinet length without hoods (inches) 389 389 389 389 517
Width (Inches) 92 92 92 92 92
Height (Inches) 82 82 82 82 82
Weights (Lbs.) (base unit, no option)
Base cabinet, cooling only with economizer 8282 8394 8607 8703 11,951
Extended cabinet, cooling only with economizer 9126 9238 9451 9547 13,161
Option Weights (Lbs.)
Power Exhaust (Blower, mtr, mtr base, fan skid, mod damper & hood) 685 685 685 685 1045
Power Exhaust (Blower, mtr, mtr base, fan skid, VFD,
baro damper & hood) 692 692 692 692 1044
100% AMS (Measurement Station & Mounting) 110 110 110 110 125
25/75% AMS (Measurement Station & Mounting) 130 130 130 130 146
Min. AMS (Measurement Station & Mounting) 40 40 40 40 45
Barometric only 36 36 36 36 45
375 MBH Gas Heat 162 162 162 162 162
750 MBH Gas Heat 324 324 324 324 324
1050 MBH Gas Heat n/a n/a n/a n/a 486
40 kW/415/3/60 or 40 kW/480/3/60 2 Steps Electric Heat 410 410 410 410 430
80 kW/208/3/60 or 108 kW/240/3/60 5 Steps Electric Heat 490 490 490 490 510
108 kW/415/3/60 4 steps Electric Heat 450 450 450 450 470
150 kW/415/3/60 5 Steps Electric Heat 470 470 470 470 490
200 kW/415/3/60 or 200 kW/480/3/60 6 Steps Electric Heat 490 490 490 490 510
250 kW/480/3/60 7 Steps Electric Heat 510 510 510 510 530
Condenser Wire Guard 32 32 32 32 40
Copper Condenser Coils (additional) 617 617 793 793 617
Copper Evaporator Coils (additional) 262 320 400 500 280
Hot water coil 281 281 281 281 318
Steam heating coil 202 202 202 202 236
Diffuser3 44 44 44 44 53
Final filters3 344 344 344 344 535
Final filters, racks only3 224 224 224 224 297
Roof Curb Weights (Lbs.)
14" Full Perimeter Roof Curb 825 825 825 825 1,020
14" Open Condenser Roof Curb 555 555 555 555 577
Compressor Data
Quantity/Size (Nominal HP) 4x13 4x13 4x15 4x15 4x10, 2x13
Type Scroll Scroll Scroll Scroll Scroll
Capacity Steps (Qty x %) 4x25 4x25 4x25 4x25 4x15, 2x20
Supply Fan and Drive
Quantity 1 1 1 1 1
Type FC FC FC FC FC
Size 25-22 25-22 25-22 25-22 28-25
Motor Size Range (min. to max. HP) 7.5-40 7.5-40 7.5-40 7.5-40 7.5-60
Air Flow Range (min. to max. cfm) 10000-22500 10000-24000 14000-27000 14000-27000 14000-32000
Static Pressure Range (min. to max. ESP) 0-4" 0-4" 0-4" 0-4" 0-4"
Optional Airfoil Supply Fan
Quantity 1/1 1/1 1/1 1/1 1/1
Type AF AF AF AF AF
Size 25 25 25 25 32
Motor Size Range (min. to max. HP) 7.5-40 7.5-40 7.5-40 7.5-40 7.5-50
Air Flow Range (min. to max. cfm) 0-27000 0-27000 0-27000 0-27000 0-32000
Static Pressure Range (min. to max. ESP) 0-6" 0-6" 0-6" 0-6" 0-6"
18 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 19
FORM 100.50-EG1 (705)
Gas Pressure Range (min. to max. iwg) 3-14" w.c. 3-14" w.c. 3-14" w.c. 3-14" w.c. 3-14" w.c.
Airflow Range (min. to max. cfm) 6,950-27,000 6,950-27,000 11,150-27,000 11,150-27,000 6,950-36,000
Modulating Furnace Sizes 375 mbh / 300 mbh / 8:1 turndown
(input/output/turndown) 750 mbh / 600 mbh / 16:1 turndown
Gas Pressure Range (min. to max. iwg) 3.5-14" w.c.2 3.5-14" w.c.2 3.5-14" w.c.2 3.5-14" w.c.2 3.5-14" w.c.2
Airflow Range (min. to max. cfm) 8,250-27,000 8,250-27,000 11,150-27,000 11,150-27,000 8,250-36,000
Electric Heaters
Size Range (min. to max. kW) 40-150 40-150 40-150 40-150 80-200
Heating steps1 1-7 1-7 1-7 1-7 1-7
Minimum OA Temp. for Mech. Cig. 45 45 45 45 45
Low Ambient Option Min. OA Temp 0 0 0 0 0
NOTES
1. Electric heat steps and airflow range depends on voltage and size. Consult the air pressure drop tables for specific number of steps for a
given voltage.
2. 3.5" is minimum gas pressure for full firing rate. 3.0" is acceptable at reduced firing rate.
3. Weights are for components only and need to be added to the extended cabinet weights. The diffuser is required in the extended cabinet
for any unit with hot water or final filter option.
20 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 21
FORM 100.50-EG1 (705)
22 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
NOTES
1. Electric heat steps and airflow range depends on voltage and size. Consult the air pressure drop tables for specific number of steps for a
given voltage.
2. 3.5" is minimum gas pressure for full firing rate. 3.0" is acceptable at reduced firing rate.
3. Weights are for components only and need to be added to the extended cabinet weights. The diffuser is required in the extended cabinet
for any unit with hot water or final filter option.
YORK INTERNATIONAL 23
FORM 100.50-EG1 (705)
24 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 25
FORM 100.50-EG1 (705)
26 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 27
FORM 100.50-EG1 (705)
28 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 29
FORM 100.50-EG1 (705)
30 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 31
FORM 100.50-EG1 (705)
32 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 33
FORM 100.50-EG1 (705)
34 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL 35
FORM 100.50-EG1 (705)
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
36 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 37
FORM 100.50-EG1 (705)
38 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 39
FORM 100.50-EG1 (705)
40 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 41
FORM 100.50-EG1 (705)
42 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL 43
FORM 100.50-EG1 (705)
44 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 45
FORM 100.50-EG1 (705)
46 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 47
FORM 100.50-EG1 (705)
48 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 49
FORM 100.50-EG1 (705)
50 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 51
FORM 100.50-EG1 (705)
52 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL 53
FORM 100.50-EG1 (705)
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
54 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL 55
FORM 100.50-EG1 (705)
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
56 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL 57
FORM 100.50-EG1 (705)
58 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 59
FORM 100.50-EG1 (705)
60 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 61
FORM 100.50-EG1 (705)
62 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 63
FORM 100.50-EG1 (705)
64 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 65
FORM 100.50-EG1 (705)
66 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 67
FORM 100.50-EG1 (705)
68 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 69
FORM 100.50-EG1 (705)
70 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 71
FORM 100.50-EG1 (705)
72 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 73
FORM 100.50-EG1 (705)
74 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 75
FORM 100.50-EG1 (705)
76 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 77
FORM 100.50-EG1 (705)
78 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 79
FORM 100.50-EG1 (705)
80 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 81
FORM 100.50-EG1 (705)
82 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 83
FORM 100.50-EG1 (705)
84 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 85
FORM 100.50-EG1 (705)
ELECTRIC HEATING
86 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 87
FORM 100.50-EG1 (705)
88 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 89
FORM 100.50-EG1 (705)
NOTES: * Includes 2" pleated filters. ** Power exhaust pressure drops are for sizing supply fan.
1. Return air opening pressure drop does not include an exhaust fan. Use the value in the Powered Exhaust column to determine return air
pressure drop attributed to the exhaust fan assembly.
2. Front return is not available with barometric relief, exhaust fans or return fans.
3. Pressure drop for 12-inch rigid filter media includes a 2-inch prefilter.
90 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
Filters
Outside Powered
Rigid Filter Rack, 12" Rigid, 12" Rigid, 12" Rigid, 95%
Air Dampers Exhaust
No Media 65%* 95%* (Final Filter Position)*
0.09 0.21 0.30 0.24 0.17 0.01
0.12 0.28 0.38 0.30 0.21 0.01
0.15 0.34 0.46 0.37 0.25 0.02
0.18 0.42 0.55 0.43 0.31 0.03
0.20 0.47 0.62 0.48 0.36 0.03
0.21 0.49 0.65 0.50 0.38 0.03
0.25 0.58 0.74 0.57 0.46 0.04
0.27 0.62 0.79 0.60 0.51 0.04
0.28 0.66 0.84 0.64 0.57 0.05
0.32 0.75 0.95 0.71 0.69 0.06
0.12 0.28 0.38 0.30 0.21 0.01
0.15 0.34 0.46 0.37 0.25 0.02
0.18 0.42 0.55 0.43 0.31 0.03
0.21 0.49 0.65 0.50 0.38 0.03
0.23 0.54 0.71 0.54 0.43 0.04
0.25 0.58 0.74 0.57 0.46 0.04
0.28 0.66 0.84 0.64 0.57 0.05
0.32 0.75 0.95 0.71 0.69 0.06
0.15 0.34 0.46 0.37 0.25 0.02
0.18 0.42 0.55 0.43 0.31 0.03
0.21 0.49 0.65 0.50 0.38 0.03
0.25 0.58 0.74 0.57 0.46 0.04
0.27 0.62 0.79 0.60 0.51 0.04
0.28 0.66 0.84 0.64 0.57 0.05
0.32 0.75 0.95 0.71 0.69 0.06
0.36 0.84 1.06 0.79 0.84 0.07
0.38 0.89 1.11 0.82 0.93 0.07
0.15 0.34 0.46 0.37 0.25 0.02
0.18 0.42 0.55 0.43 0.31 0.03
0.21 0.49 0.65 0.50 0.38 0.03
0.25 0.58 0.74 0.57 0.46 0.04
0.27 0.62 0.79 0.60 0.51 0.04
0.28 0.66 0.84 0.64 0.57 0.05
0.32 0.75 0.95 0.71 0.69 0.06
0.36 0.84 1.06 0.79 0.84 0.07
0.38 0.89 1.11 0.82 0.93 0.07
0.10 0.24 0.33 0.26 0.13 0.01
0.12 0.29 0.39 0.31 0.15 0.01
0.14 0.34 0.46 0.36 0.18 0.02
0.17 0.40 0.53 0.41 0.21 0.02
0.19 0.45 0.60 0.46 0.25 0.02
0.22 0.51 0.67 0.51 0.29 0.03
0.25 0.58 0.75 0.56 0.34 0.03
0.28 0.64 0.82 0.61 0.40 0.04
0.31 0.71 0.90 0.67 0.47 0.04
0.10 0.24 0.33 0.26 0.13 0.01
0.12 0.29 0.39 0.31 0.15 0.01
0.14 0.34 0.46 0.36 0.18 0.02
0.17 0.40 0.53 0.41 0.21 0.02
0.19 0.45 0.60 0.46 0.25 0.02
0.22 0.51 0.67 0.51 0.29 0.03
0.25 0.58 0.75 0.56 0.34 0.03
0.28 0.64 0.82 0.61 0.40 0.04
0.31 0.71 0.90 0.67 0.47 0.04
YORK INTERNATIONAL 91
FORM 100.50-EG1 (705)
NOTES: * Includes 2" pleated filters. ** Power exhaust pressure drops are for sizing supply fan.
1. Return air opening pressure drop does not include an exhaust fan. Use the value in the Powered Exhaust column to determine return air
pressure drop attributed to the exhaust fan assembly.
2. Front return is not available with barometric relief, exhaust fans or return fans.
3. Pressure drop for 12-inch rigid filter media includes a 2-inch prefilter.
92 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
Filters
Outside Powered
Rigid Filter Rack, 12" Rigid, 12" Rigid, 12" Rigid, 95%
Air Dampers Exhaust
No Media 65%* 95%* (Final Filter Position)*
0.12 0.29 0.39 0.31 0.15 0.01
0.14 0.34 0.46 0.36 0.18 0.02
0.17 0.40 0.53 0.41 0.21 0.02
0.19 0.45 0.60 0.46 0.25 0.02
0.22 0.51 0.67 0.51 0.29 0.03
0.25 0.58 0.75 0.56 0.34 0.03
0.28 0.64 0.82 0.61 0.40 0.04
0.31 0.71 0.90 0.67 0.47 0.04
0.34 0.78 0.98 0.72 0.55 0.05
0.12 0.29 0.39 0.31 0.15 0.01
0.14 0.34 0.46 0.36 0.18 0.02
0.17 0.40 0.53 0.41 0.21 0.02
0.19 0.45 0.60 0.46 0.25 0.02
0.22 0.51 0.67 0.51 0.29 0.03
0.25 0.58 0.75 0.56 0.34 0.03
0.28 0.64 0.82 0.61 0.40 0.04
0.31 0.71 0.90 0.67 0.47 0.04
0.34 0.78 0.98 0.72 0.55 0.05
0.07 0.29 0.40 0.31 0.18 0.01
0.08 0.34 0.46 0.36 0.21 0.01
0.09 0.39 0.52 0.40 0.24 0.02
0.11 0.45 0.59 0.45 0.27 0.02
0.12 0.50 0.65 0.49 0.32 0.02
0.13 0.56 0.72 0.54 0.36 0.03
0.15 0.61 0.79 0.59 0.42 0.03
0.16 0.67 0.86 0.64 0.48 0.03
0.18 0.74 0.93 0.69 0.55 0.04
0.19 0.80 1.01 0.74 0.64 0.04
0.07 0.29 0.40 0.31 0.18 0.01
0.08 0.34 0.46 0.36 0.21 0.01
0.09 0.39 0.52 0.40 0.24 0.02
0.11 0.45 0.59 0.45 0.27 0.02
0.12 0.50 0.65 0.49 0.32 0.02
0.13 0.56 0.72 0.54 0.36 0.03
0.15 0.61 0.79 0.59 0.42 0.03
0.16 0.67 0.86 0.64 0.48 0.03
0.18 0.74 0.93 0.69 0.55 0.04
0.19 0.80 1.01 0.74 0.64 0.04
0.07 0.29 0.40 0.31 0.18 0.01
0.08 0.34 0.46 0.36 0.21 0.01
0.09 0.39 0.52 0.40 0.24 0.02
0.11 0.45 0.59 0.45 0.27 0.02
0.12 0.50 0.65 0.49 0.32 0.02
0.13 0.56 0.72 0.54 0.36 0.03
0.15 0.61 0.79 0.59 0.42 0.03
0.16 0.67 0.86 0.64 0.48 0.03
0.18 0.74 0.93 0.69 0.55 0.04
0.19 0.80 1.01 0.74 0.64 0.04
YORK INTERNATIONAL 93
FORM 100.50-EG1 (705)
94 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
Filters
Outside Powered Exhaust
Rigid Filter Rack, 12" Rigid, 12" Rigid,
Air Dampers (use with bottom return)
No Media 65%* 95%*
0.12 0.34 0.46 0.11 0.12
0.14 0.38 0.51 0.13 0.14
0.16 0.43 0.56 0.14 0.15
0.17 0.47 0.62 0.16 0.17
0.19 0.52 0.67 0.18 0.20
0.21 0.56 0.73 0.20 0.22
0.23 0.61 0.79 0.23 0.25
0.25 0.66 0.84 0.26 0.28
0.27 0.71 0.90 0.29 0.32
0.30 0.76 0.96 0.33 0.36
0.32 0.82 1.03 0.37 0.40
0.34 0.87 1.09 0.42 0.46
YORK INTERNATIONAL 95
FORM 100.50-EG1 (705)
96 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL 97
FORM 100.50-EG1 (705)
Air Flow
Model Electric Heater Air Pressure Drop (in w.c.)
CFM Std. Air
10000 0.01 0.01 0.02 0.03 0.03 0.04 0.05
12000 0.01 0.02 0.03 0.04 0.05 0.06 0.07
14000 0.02 0.03 0.04 0.05 0.07 0.08 0.09
16000 0.02 0.04 0.05 0.07 0.09 0.10 0.12
17500 0.02 0.04 0.06 0.08 0.10 0.12 0.14
18000 0.02 0.05 0.07 0.09 0.11 0.13 0.15
19250 0.03 0.05 0.08 0.10 0.12 0.15 0.17
YPAL050-065
20000 0.03 0.06 0.08 0.11 0.13 0.16 0.18
21000 0.03 0.06 0.09 0.12 0.15 0.17 0.20
22000 0.04 0.07 0.10 0.13 0.16 0.19 0.22
22500 0.04 0.07 0.10 0.14 0.17 0.20 0.23
24000 0.04 0.08 0.12 0.15 0.19 0.23 0.27
26000 0.05 0.10 0.14 0.18 0.22 0.27 0.31
27000 0.06 0.10 0.15 0.20 0.24 0.29 0.34
16000 0.02 0.03 0.04 0.06 0.07 0.09 0.10
18000 0.02 0.04 0.06 0.07 0.09 0.11 0.13
20000 0.03 0.05 0.07 0.09 0.11 0.13 0.15
22000 0.03 0.06 0.08 0.11 0.14 0.16 0.19
24000 0.04 0.07 0.10 0.13 0.16 0.19 0.22
YPAL070-085
26000 0.04 0.08 0.12 0.15 0.19 0.23 0.26
27000 0.05 0.09 0.13 0.16 0.20 0.24 0.28
28000 0.05 0.09 0.13 0.18 0.22 0.26 0.30
30000 0.06 0.11 0.15 0.20 0.25 0.30 0.35
32000 0.07 0.12 0.18 0.23 0.29 0.34 0.40
20000 0.02 0.04 0.05 0.07 0.09 0.10 0.12
22000 0.02 0.04 0.06 0.08 0.10 0.12 0.14
24000 0.03 0.05 0.08 0.10 0.12 0.15 0.17
26000 0.03 0.06 0.09 0.12 0.15 0.17 0.20
28000 0.04 0.07 0.10 0.14 0.17 0.20 0.23
YPAL090-105 30000 0.04 0.08 0.12 0.16 0.19 0.23 0.27
31500 0.05 0.09 0.13 0.17 0.21 0.25 0.30
32000 0.05 0.09 0.14 0.18 0.22 0.26 0.31
34000 0.06 0.11 0.15 0.20 0.25 0.30 0.34
36000 0.06 0.12 0.17 0.23 0.28 0.33 0.39
98 YORK INTERNATIONAL
FORM 100.50-EG1 (705)
Air Flow
Model Electric Heater Air Pressure Drop (in w.c.)
CFM Std. Air
24000 0.03 0.05 0.08 0.10 0.12 0.15 0.17
26000 0.03 0.06 0.09 0.12 0.15 0.17 0.20
28000 0.04 0.07 0.10 0.14 0.17 0.20 0.23
30000 0.04 0.08 0.12 0.16 0.19 0.23 0.27
32000 0.05 0.09 0.14 0.18 0.22 0.26 0.31
34000 0.06 0.11 0.15 0.20 0.25 0.30 0.34
YPAL106-130
36000 0.06 0.12 0.17 0.23 0.28 0.33 0.39
38000 0.07 0.13 0.19 0.25 0.31 0.37 0.43
40000 0.08 0.15 0.21 0.28 0.34 0.41 0.48
42000 0.09 0.16 0.23 0.31 0.38 0.45 0.53
44000 0.10 0.18 0.26 0.34 0.42 0.50 0.58
46000 0.11 0.19 0.28 0.37 0.46 0.54 0.63
YORK INTERNATIONAL 99
FORM 100.50-EG1 (705)
In order to determine the proper exhaust fan motor size, add the return duct static pressure to the appropriate
damper pressure drop value in Table 23 to get the total static pressure applied to the exhaust fan. Based on the
exhaust fan air flow and total static pressure, determine the brake horsepower and RPM of the exhaust fan.
NOTE: For performance at operating points not included in these tables, consult your
local YORK representative.
Electrical Data
ELECTRICAL SERVICE SIZING • LOAD3 is the current of the electric heaters – zero
for cooling only units.
In order to use the electrical service required for the cool-
ing only eco2 rooftop, use the appropriate calculations • LOAD4 is the sum of any remaining currents greater
listed below from U.L. 1995. Based on the configuration than or equal to 1.0 amp.
of the rooftop, the calculations will yield different MCA Use the following calculations to determine MCA
(minimum circuit ampacity), and MOP (maximum and MOP for units supplied with a single-point power
overcurrent protection). connection:
Using the following load definitions and calculations, MCA = (1.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4
determine the correct electrical sizing for your unit. All
concurrent load conditions must be considered in the MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4
calculations, and you must use the highest value for
any combination of loads. If the MOP does not equal a standard current rating of
an overcurrent protective device, then the marked maxi-
Load Definitions: mum rating is to be the next lower standard rating. How-
• LOAD1 is the current of the largest motor – com- ever, if the device selected for MOP is less than the
pressor or fan motor. MCA, then select the lowest standard maximum fuse
• LOAD2 is the sum of the remaining motor currents size greater than or equal to the MCA.
that may run concurrently with LOAD1.
Controls
CONTROL SEQUENCES COMMON TO ALL UNITS
GENERAL hard-wiring to an external indexing device such as a
central time clock, thermostat with built in scheduling,
The control system for the YORK eco² Packaged Roof- or a manual switch. The unit controller is also equipped
top Unit is fully self-contained and based around a Roof- with a built in 7-day time clock which can be used, in
top Unit controller. To aid in unit setup, maintenance, lieu of the contact closure input, to switch the unit be-
and operation, the rooftop unit controller is equipped tween Unoccupied and Occupied modes of operation.
with a user interface that is based around a 4 line x 20 The internal time clock is fully configurable via the user
character backlit LCD display. The LCD displays plain interface and includes Holiday scheduling. In addition
language text in a menu-driven format to facilitate use. to the hard-wired input or the internal time clock, the
In addition to the display, the Rooftop unit user inter- unit can also be indexed between unoccupied and oc-
face is also equipped with an LED indicator light, which cupied modes of operation via a BAS command.
will warn of any abnormal operation of the equipment
Note: a unit operated from a space sensor with over-
or communication failures.
ride buffer can be equipped to temporarily override an
For the maximum in system flexibility, the YORK eco² unoccupied mode of operation. This Unoccupied Over-
Packaged Rooftop Unit can be operated by either a typi- ride feature is fully configurable via the Rooftop Unit
cal 7-wire thermostat (2 cool/2 heat), a space tempera- user interface.
ture sensor, or stand-alone (VAV only). Note, a field wir-
ing terminal block is provided to facilitate unit setup and GAS HEATING OPERATION
installation.
Units supplied with gas heat can be equipped one, two,
In lieu of the hard-wired control options, the rooftop unit
or three independently operated burner modules. Each
controller can be connected to and operated by a Build-
module is fully self-contained furnace with all neces-
ing Automation System (BAS). If required, the Rooftop
sary ignition controls, safeties, and gas valves. The
Unit controller can be equipped with an optional BACNet
OptiLogic rooftop unit controller determines how the
IP communication card, which allows communication,
furnaces are started and stopped and prevents furnace
via Ethernet, to a BACNet IP based BAS.
operation if the Supply Fan airflow is not sufficient or if
the Supply Air Temperature is excessively high.
ROOFLINK™
If a furnace module receives a signal to start from the
The optional RoofLink™ control board will allow the build- OptiLogic controller, the ignition control engages the
ing owner increased flexibility through the use of ex- furnace inducer (draft) fan for a 30-second pre-purge
panded binary and analog inputs and outputs to the cycle. At the end of the 30-second pre-purge, the igni-
Optilogic controls system. When a building is using an tion control will stop the furnace and allows the inducer
automation system other than LON or BACnet, the fan to operate for a 30-second post-purge. Each fur-
RoofLink™ will allow for easy connections and commu- nace contains a direct spark ignition system and in-
nications to and from the OptiLogic controls through a cluded safeties for flame and inducer fan verification,
twisted pair connection. There are 5 analog inputs, 3 high temperature and flame roll-out.
analog outputs and 4 binary inputs/outputs. This allows
the user to send and retrieve information either through HYDRONIC HEAT
contact closures or voltage signals to and from the unit.
A technician or building manager now has access to If the unit is configured with either of the wet heat op-
specific information concerning the operating rooftop tions (steam or hot water) the Rooftop Unit controls will
functions. The Rooflink™ also includes expanded smoke modulate the hydronic valve to maintain a supply air set
purge capabilities through additional contacts on the point. In the event temperatures off the hydronic coil are
Rooflink™ board that are not found on the standard below 34 degrees the fans will be shut down and the
Optilogic controls. This provides even greater flexibility hydronic valve will open 100%. This function is an auto-
for building protection and occupant safety. matic reset so as the temperature rises above 36 de-
grees, the unit will automatically begin normal operation.
UNOCCUPIED / OCCUPIED SWITCHING
ELECTRIC HEATING OPERATION
Depending on application, the unit can be indexed be-
tween unoccupied and occupied modes of operation
For units equipped with electric heaters, the unit can
by one of three methods, hard-wired input, internal time
control up to six stages of electric heat which are staged
clock, or BAS. A contact-closure input is provided for
Controls (continued)
on based on heating demand calculates by the mizing when the Outside Air enthalpy is determined to
OptiLogic controller. be less than the reference enthalpy setting and the
Outside Air temperature is less than the reference tem-
MORNING WARM-UP perature setting. This method of economizing allows the
reference temperature setting to be set higher than the
Morning Warm-Up can be initialized by BAS or by the DB Economizer and is consequently a more efficient
OptiLogic controller if the Internal Scheduling is used. packaged rooftop economizer.
If the Internal Scheduling is used, the Morning Warm-
Up start time is calculated through an adaptive algo- Dual Enthalpy Economizer
rithm.
With the optional dual enthalpy economizer, the unit con-
When Morning Warm-Up is required, the OptiLogic con- troller monitors and compares the Outside Air and Re-
troller energizes the VAV heat relay, starts the Supply turn Air enthalpies in addition to comparing the Outside
Fan and qualifies the Return Air Temperature for 5 min- Air temperature to the reference temperature setting.
utes. The internal heat source (Gas, HW/Steam, or Outside Air is deemed suitable for economizing when
Electric) is controlled to maintain the Return Air Tem- the Outside Air enthalpy is determined to be less than
perature to the Morning Warm-Up Setpoint, Morning the Return Air enthalpy and the Outside Air tempera-
Warm-Up ends when occupancy occurs (BAS, Internal ture is less than the reference temperature setting. This
Scheduling, or contact closure), or when the Maximum method of economizing is the most accurate and pro-
Morning Warm-Up Time has expired. vides the highest degree of energy efficiency for a pack-
aged rooftop economizer.
ECONOMIZER OPERATION
VENTILATION CONTROL SEQUENCES
The unit can be equipped with one of three types of
optional economizers, dry bulb, single enthalpy, or com- Minimum OA Damper Position (CV Units)
parative enthalpy. When the unit controller determines
When the unit goes into the Occupied mode of opera-
that Outside Air is suitable for economizing, the unit
tion, the unit controller shall open the Outside Air Damper
controller will control the outside air damper(s) open to
to a fixed minimum position. The damper shall remain
provide economizer cooling. If economizer cooling alone
at this position as long as the unit is in the occupied
is insufficient for the cooling load, the unit controller
mode, and the economizer is not suitable for cooling.
shall stage up compressors, one at a time, to meet
demand.
Minimum OA Damper Position (VAV Units)
The control logic for the three types of economizers is
With Variable Air Volume units, there are two Minimum
as follows:
OA Damper Positions, one when the unit is at full speed
and the second when the unit is at approximately half
Dry Bulb Economizer
speed. These two points allow the control to linearly reset
The dry bulb economizer is the default economizer the position of the OA damper in response to fan speed.
control scheme. With the dry bulb economizer, the
When the unit goes into the Occupied mode of opera-
unit controller monitors the Outside Air temperature
tion, the unit controller shall monitor the speed of the
only and compares it to a reference temperature set-
supply fan and open the Outside Air damper to a calcu-
ting. Outside Air is deemed suitable for economizing
lated minimum position based on the fan speed. This
when the Outside Air temperature is determined to
minimum position shall vary as the speed of the fan
be less than the reference temperature setting. This
changes. The damper shall remain at this calculated
method of economizing is effective, but is prone to
position as long as the unit is in the occupied mode,
some change-over inefficiencies due to the fact that
and the economizer is not suitable for cooling.
this method is based on sensible temperatures only
and does not take Outside Air moisture content into
Air Measurement Stations
consideration.
When the unit is equipped with an air measurement sta-
Single Enthalpy Economizer tion, the unit controller shall control the Outside Air
damper to a measured flow rate through the Air Mea-
With the optional single enthalpy economizer, the unit
surement Station.
controller monitors the Outside Air enthalpy in addition
to the Outside Air temperature and compares it to a When the unit goes into the Occupied mode of opera-
reference enthalpy setting and a reference tempera- tion, the unit controller shall control the Outside Air
ture setting. Outside Air is deemed suitable for econo- damper to maintain the Minimum AirFlow Setpoint
through the Air Measurement Station. The unit control- quency Drive (VFD), which is controlled by the Rooftop
ler shall control the Outside Air damper to this flow rate Unit controller. The Rooftop Unit controller monitors the
as long as the unit is in the Occupied mode, and the pressure within the building. As the pressure rises, the
economizer is not suitable for cooling. VFD is controlled to increase Exhaust Fan speed. As
the pressure falls, the VFD is controlled to decrease
Demand Ventilation Exhaust Fan speed. The Building Pressure Setpoint is
user selectable from the Rooftop Unit User Interface.
If an optional CO2 sensor is connected to the unit, the
On/Off control is maintained the same as Exhaust-Dis-
unit controller can reset the minimum OA damper
charge Damper control stated above.
position(s) or minimum flow rate based on demand.
The unit controller shall monitor the CO2 level within Return Fan Controlled
the building. If the CO2 level rises above the CO2 setpoint,
This optional variable volume powered return fan sys-
the controller will temporarily increase the Minimum OA
tem consists of two return fans controlled by one VFD
Damper Position or Minimum OA flow rate to increase
that is controlled by the Rooftop Unit control center. The
ventilation. If the CO2 level drops below the CO2 setpoint,
VFD is controlled to maintain a slightly positive pres-
the controller will decrease the Minimum OA Damper
sure over the mixing box section to prevent reverse
Position or Minimum OA flow rate to decrease ventilation.
flow. As the return and/or exhaust air dampers open,
Demand Ventilation shall remain active as long as the the return plenum pressure drops, the fan will speed
unit is in the Occupied mode of operation. up to maintain pressure. When the return and/or ex-
haust air dampers close, the return plenum pressure
EXHAUST CONTROL SEQUENCES increases causing the VFD to slow the fan speed down.
Controls (continued)
dard with a Ventilation Override sequence to remove, Purge With Duct Pressure Control (VAV Only)
exhaust or ventilate smoke, fumes or other air born
When this purge sequence is selected and activated,
contaminates from the occupied space. This feature
the Supply Fan is cycled ON and controlled to maintain
offers 5 selectable operations, which include, Shutdown,
the duct static pressure setpoint. The Exhaust Fan is
Pressurization, Exhaust, Purge and Purge with duct
also controlled ON (Exhaust Damper driven full open)
pressure control. Once the selected operation is pro-
and the Outside Air Damper is driven full open. This
grammed through the Optilogic user interface, a con-
mode is maintained until the smoke purge input is de-
tact closure input will initiate the selected ventilation
activated and the unit returns to normal operation.
sequence. Some typical contact closures are smoke
detectors, fire alarms, manual switches etc . . . If de-
sired, the Rooflink™ option can be added to the con- VAV SPECIFIC SEQUENCES
trols system for more ventilation mode operations.
SUPPLY FAN OPERATION
Note: all cooling and heating modes are disabled dur-
ing any ventilation mode. For VAV units, the supply fan is controlled ON and OFF
based on the occupancy state or the G input from a
Shutdown Thermostat (Unit must be configured for Thermostat
When this purge sequence is selected and activated, operation to respond to the G input). When the unit
the supply and exhaust fans are controlled OFF and goes into the Occupied mode of operation (or “G” is
the Outside Air damper is overridden closed. This idle called) the Supply Fan will be controlled ON. The Roof-
state is maintained until the purge input is deactivated top Unit controller will monitor the static pressure within
and the unit returns to normal operation. the supply duct system and control the speed of the
supply fan to maintain a specified Duct Static Pressure
Pressurization setpoint. A Variable Frequency Drive (VFD) is used on
all VAV units to vary the speed of the supply fan. Note,
When this purge sequence is selected and activated, the use of a VFD in lieu of inlet guide vanes provides
the exhaust fan is controlled OFF and the Supply Fan for higher energy efficiency for the unit by eliminating
is controlled ON. The Outside Air damper is opened full the losses (air pressure drop) typical of inlet guide vane
and the Return Air Damper is closed full. If the unit is a systems.
VAV unit, the VAV boxes are also driven full open to
prevent duct over-pressurization. This mode is main- COOLING OPERATION
tained until the smoke purge input is deactivated and
the unit returns to normal operation. Thermostat Control
When a Cooling Stage 2 call (“Y2”) is received, and the Supply Air Tempering
unit is equipped with an economizer, the Rooftop Unit
Supply Air Tempering is a continuation of the a VAV
controller will check the Outside Air conditions to deter-
cooling operation when the outside air temperature is
mine if conditions are suitable for economizing and modu-
below the supply air temperature setpoint where heat-
late the outside air damper and/or stage up compres-
ing is used to maintain economizer operation. This func-
sors as required to maintain the VAV Low Supply Air Tem-
tion will use small increments of heat to maintain the
perature Setpoint (default set to 55°F). This setpoint is
Supply Air Temperature when the economizer dampering
user selectable at the Rooftop Unit User Interface. The
stages.
Rooftop Unit controller will control to this setpoint as long
as Cooling Stage 2 (“Y2”) remains active.
HEATING OPERATION
The VAV High SAT Setpoint is always greater than the
VAV Low SAT Setpoint and because of this essentially VAV Occupied Heating
makes this control sequence a Supply Air Temperature
When VAV Occupied Heating is enabled, full heating
Reset algorithm based on Zone Temperature or Out-
will energize when either the thermostat W1 or W2 sig-
side Air.
nal is received or the space temperature falls below
the VAV Setpoint for SAT Reset by more than 2°F. If
Zone Sensor Control
the return air temperature falls below the return air tem-
When a VAV unit is configured for Zone Sensor opera- perature setpoint for occupied heating, full heat capac-
tion, the Rooftop Unit controller will monitor a reference ity will be energized.
Zone Temperature and command the Supply Fan to
On VAV units the supply fan speed is controlled to main-
start when the unit goes into the Occupied mode.
tain static pressure allowing true VAV heating operation.
If the zone temperature is above the VAV Setpoint for
SAT Reset, the Rooftop Unit controller will modulate the CV SPECIFIC SEQUENCES
outside air damper (Economizer available and condi-
tions suitable) and/or stage compressors up and down, COOLING OPERATION
as required, to maintain the VAV High Supply Air Tem-
perature Setpoint. Thermostat Control
If the zone temperature is below or falls below the VAV If a 7-wire thermostat (2 Cool/2 Heat) controls the unit,
Setpoint for SAT Reset, the Rooftop Unit controller will all zone temperature setpoint control is maintained at
modulate the Outside Air Damper (Economizer avail- the thermostat. With this operation, the unit remains
able and conditions suitable) and/or stage compres- idle until it receives a stage call from the thermostat. If
sors up and down, as required, to maintain the VAV “G” is called from the thermostat, the Supply Fan
High Supply Air Temperature Setpoint. willstart. Ventilation functions (if equipped) will be per-
As with thermostat operation, this sequence is also a mitted to run with an occupied signal. Economizer func-
Supply Air Temperature Reset algorithm based on Zone tions will operate with a “G” call and a call for cooling.
Temperature. Stage 1 (“Y1”) Call
Stand-Alone Control If Y1 is called and the unit is equipped with an economizer,
the control will check to see if the Outside Air is suitable for
If the unit is not configured for Thermostat or Zone Sen- economizing. If conditions are suitable for economizing, the
sor operation, the unit will operate in Stand-Alone Mode. control will control the economizer and stage up compres-
In Stand-Alone Mode, the Rooftop Unit Controller will sors, as required, to maintain the economizer first-stage
monitor only the Occupied/Unoccupied state. When the setpoint. If conditions are not suitable for economizing or
unit is commanded into the Occupied Mode of opera- not equipped with an economizer, the control will stage up
tion, the Rooftop Unit Controller will start the Supply 50% of the compressors. This shall be maintained until
Fan. If the unit is equipped with an Economizer, the Stage 1 is deactivated or Stage 2 is called.
Controller will check to see if Outside Air conditions Stage 2 (“Y2”) Call
are suitable for Economizing. The controller will then
use Outside Air (when available and suitable) and/or If Y2 is called and the unit is equipped with an econo-
stage compressors up and down, as required, to main- mizer, the control will check to see if the Outside Air is
tain the VAV Low SAT Setpoint. suitable for economizing. If conditions are suitable for
economizing, the control will control the economizer and
stage up compressors, as required, to maintain the econo-
Controls (continued)
mizer second-stage setpoint. If conditions are not suit- Stage 1 (“W1”) Call
able for economizing or not equipped with an economizer,
If W1 is called and the unit is equipped with an econo-
the control will stage up 100% of the compressors. This
mizer, the economizer will go to minimum position with
shall be maintained until Stage 2 is deactivated.
an occupied signal or close with an unoccupied signal.
and the control will stage up 50% of the heating steps.
Zone Sensor Control
This shall remain active until Stage 1 call is deactivated
If a zone sensor controls the unit, the Rooftop Unit or a Stage 2 call is activated.
controller shall maintain the zone temperature setpoint.
Stage 2 (“W2”) Call
This setpoint is user selectable at the Rooftop Unit
User Interface. If W2 is called and the unit is equipped with an econo-
mizer, the economizer will go to minimum position with
When a zone sensor is used for control, the Rooftop
an occupied signal or close with an unoccupied signal,
Unit controller will monitor the temperature within the
and the control will stage up 100% of the heating steps.
space and control the unit accordingly. A closed-loop
This shall remain active until Stage 2 call is deactivated.
staging algorithm is used to stage compressors up and
down as required to maintain the desired zone tem-
Zone Sensor Control
perature setpoint. If the unit is equipped with an econo-
mizer, Outside Air conditions are continuously monitored If a zone sensor controls the unit, the Rooftop Unit con-
by the control to determine if conditions are suitable for troller shall maintain all zone temperature setpoints.
economizing. If conditions are suitable for economiz- These setpoints are user selectable at the Rooftop Unit
ing, the Rooftop Unit controller will modulate the Out- User Interface.
side Air damper in addition to staging compressors up
When a zone sensor is used for control, the Rooftop
and down to maintain the zone temperature setpoint.
Unit controller will monitor the temperature within the
space and control the unit accordingly. A closed-loop
HEATING OPERATION
staging algorithm is used to stage heating steps up and
down as required to maintain the desired zone tem-
Thermostat Control
perature setpoint. If the unit is equipped with an econo-
If a 7-wire thermostat (2 Cool/2 Heat) controls the unit, mizer, Outside Air conditions are continuously monitored
all zone temperature setpoint control is maintained at by the control to determine if conditions are suitable for
the thermostat. With this operation, the unit remains economizing. If conditions are suitable for economiz-
idle until it receives a stage call from the thermostat. If ing, the Rooftop Unit controller will modulate the Out-
“G” is called from the thermostat, the Supply Fan will side Air damper in addition to staging heating steps up
start. Ventilation functions (if equipped) will be permit- and down to maintain the zone temperature setpoint.
ted to run with an occupied signal.
Controls (continued)
TABLE 49 – THREE PHASE POWER SUPPLY CONDUCTOR SIZE RANGE (cont’d)
LD08171
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Consult the I.O.M manual or unit nameplate data to determine Minimum Circuit Ampacities (MCA) and recommended Dual Element fuse
sizes.
4. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
5. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
6. The “Incoming Wire Range” is the minimum and maximum wire sizes that can be accomodated by the unit wiring lugs. A (2) preceding the
wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires
per phase must be determined based on N.E.C.
7. Use copper conductors only.
8. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
LD08172
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Consult the I.O.M manual or unit nameplate data to determine Minimum Circuit Ampacities (MCA) and recommended Dual Element fuse
sizes.
4. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
5. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
6. The “Incoming Wire Range” is the minimum and maximum wire sizes that can be accomodated by the unit wiring lugs. A (2) preceding the
wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires
per phase must be determined based on N.E.C.
7. Use copper conductors only.
8. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
GND
1L1
1L2
1L3
TB1
Field Control
Wiring Terminal
Block
LD06414
Line 1
Field Power Line 2
Line 3
Supply
Earth
Ground
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
5. Use copper conductors only.
6. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
GND
Molded
1L1
1L2
1L3
Case
Disconnect
Switch
Field Control
Wiring Terminal
Block
LD06415
Line 1
Field Power Line 2
Line 3
Supply
Earth
Ground
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
5. Use copper conductors only.
6. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
TB2 TB1
GND
GND
2L1
2L2
2L3
1L1
1L2
1L3
Field Control
Wiring Terminal
Block
LD06416
Line 1
Field Power Line 2
Line 3
Supply #2
Earth
Ground
Line 1
Field Power Line 2
Line 3
Supply #1
Earth
Ground
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
5. Use copper conductors only.
6. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
LD08184
LD08186
122
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
12' - 5"
82 3/4"
70 5/8"
28 1/2"
4 5/8"
BOTTOM SUPPLY / BOTTOM RETURN
40"
4 5/8"
106 5/8"
4 5/8"
A I R F L OW
CP 10'
CO
_F
72" DP FS MB EE 72" 72" 72"
CC
REAR FRONT SIDE SIDE
23 5/16"
FE
6' - 10 5/8"
19 9/16" 9 11/16"
1-1/4" FPT COUPLING
2 3/8"
22 7/8" DRAIN CONN. (NEAR SIDE)
236 1/2"
*
95 1/8" 344"
11' - 5 13/16" 32' - 11/16" 92" 1 9/16"
YORK INTERNATIONAL
LD08126
FORM 100.50-EG1 (705)
NOTES: SECTION DESCRIPTIONS:
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
YORK INTERNATIONAL
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
12' - 5"
LEFT SUPPLY / FRONT RETURN
28 1/2"
A I R F L OW
CP 10'
CO
23 5/16"
72 1/4"
FE
6' - 10 5/8"
29 3/8"
6 1/4"
6 1/4"
LD08127
FORM 100.50-EG1 (705)
123
NOTES: SECTION DESCRIPTIONS:
124
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
13' - 5"
82 3/4"
70 5/8"
4 5/8"
34 1/2"
BOTTOM SUPPLY / BOTTOM RETURN
4 5/8"
161 1/2" 43" 4 5/8"
48"
A I R F L OW
10'
CP CO
_F 72" 72" 72"
72" DP FS CC MB EE FRONT SIDE SIDE
REAR
23 5/16"
FE
7' - 8 5/8"
19 9/16" 9 11/16" 1-1/4" FPT COUPLING
2 3/8"
DRAIN CONN. (NEAR SIDE)
22 7/8"
320 1/2"
*
95 1/8" 454"
11' - 5 13/16" 41' - 2" 92" 1 9/16"
REAR SIDE FRONT
VIEW VIEW VIEW
(LEFT SIDE)
* - DIM IS TO OUTSIDE OF 200 VOLT-3PH-60HZ
LIFTING LUGS 230 VOLT-3PH-60HZ
460 VOLT-3PH-60HZ
575 VOLT-3PH-60HZ
MODELS ONLY
General Arrangement Drawing – 70-85 Ton Models
LD08128
YORK INTERNATIONAL
FORM 100.50-EG1 (705)
NOTES: SECTION DESCRIPTIONS:
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
YORK INTERNATIONAL
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
LEFT SUPPLY / LEFT RETURN
13'-5"
34 1/2"
A I R F L OW
10'
CP CO
_F 72" 72" 72"
72" DP FS CC MB EE FRONT SIDE SIDE
REAR
23 5/16"
82 5/16"
7'-8 5/8"
FE
19 9/16" 58"
6 1/4"
2 3/8"
5 3/4"
LD08129
FORM 100.50-EG1 (705)
125
NOTES: SECTION DESCRIPTIONS:
126
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
LEFT SUPPLY / FRONT RETURN
13' - 5"
34 1/2"
A I R F L OW
10'
CP CO
_F 72" 72" 72"
72" DP FS CC MB EE FRONT SIDE SIDE
REAR
23 5/16"
82 5/16"
FE
7' - 8 5/8"
39 3/8"
6 1/4"
6 1/4"
LD08130
YORK INTERNATIONAL
FORM 100.50-EG1 (705)
NOTES: SECTION DESCRIPTIONS:
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
YORK INTERNATIONAL
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
12'-5"
82 3/4"
70 5/8"
4 5/8"
BOTTOM SUPPLY / BOTTOM RETURN
28 1/2"
A I R F L OW
10'
CP CO
_F 72" 72" 72"
72" DP FS CC MB EE FRONT SIDE SIDE
REAR
23 5/16"
FE
7' - 8 5/8"
19 9/16" 9 11/16" 1-1/4" FPT COUPLING
2 3/8"
325 1/2"
*
95 1/8" 488"
11' - 5 13/16" 44' - 1 3/4" 92" 1 9/16"
REAR SIDE FRONT
VIEW VIEW VIEW
(LEFT SIDE)
* - DIM IS TO OUTSIDE OF 200 VOLT-3PH-60HZ
LIFTING LUGS 230 VOLT-3PH-60HZ
460 VOLT-3PH-60HZ
575 VOLT-3PH-60HZ
MODELS ONLY
LD08131
FORM 100.50-EG1 (705)
127
General Arrangement Drawing – 90-105 Ton Models
NOTES: SECTION DESCRIPTIONS:
128
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
LEFT SUPPLY / LEFT RETURN
12'-5"
28 1/2"
A I R F L OW
10'
CP CO
_F 72" 72" 72"
72" DP FS CC MB EE FRONT SIDE SIDE
REAR
23 5/16"
82 5/16"
FE
7' - 8 5/8"
163 3/8" 41"
19 9/16" 1-1/4" FPT COUPLING
2 3/8"
6 1/4"
5 3/8"
22 7/8"
9 11/16"
325 1/2"
*
95 1/8" 488"
11' - 5 13/16" 43' - 4 3/4" 92" 1 9/16"
REAR SIDE FRONT
VIEW VIEW VIEW
(LEFT SIDE)
* - DIM IS TO OUTSIDE OF 200 VOLT-3PH-60HZ
LIFTING LUGS 230 VOLT-3PH-60HZ
460 VOLT-3PH-60HZ
575 VOLT-3PH-60HZ
MODELS ONLY
YORK INTERNATIONAL
LD08132
FORM 100.50-EG1 (705)
YORK INTERNATIONAL
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
LEFT SUPPLY / FRONT RETURN
12'-5"
28 1/2"
A I R F L OW
10'
CP CO
_F 72" 72" 72"
72" DP FS CC MB EE FRONT SIDE SIDE
REAR
23 5/16"
82 5/16"
FE
7' - 8 5/8"
39 3/8"
6 7/16"
6 1/4"
DRAIN CONN. (NEAR SIDE)
22 7/8"
9 11/16" 79 1/4"
325 1/2"
*
95 1/8" 488"
11' - 5 13/16" 43' - 4 3/4" 92" 1 9/16"
REAR SIDE FRONT
VIEW VIEW VIEW
(LEFT SIDE)
* - DIM IS TO OUTSIDE OF 200 VOLT-3PH-60HZ
LIFTING LUGS 230 VOLT-3PH-60HZ
460 VOLT-3PH-60HZ
575 VOLT-3PH-60HZ
MODELS ONLY
LD08133
FORM 100.50-EG1 (705)
129
NOTES: SECTION DESCRIPTIONS:
130
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. FF = Final Filter
DP = Discharge Plenum
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CO = Condenser Section
Shipment. CP = Control Panel
6. Clearance Downstream of the Diffuser.
If the Diffuser Factory Option is Not In-
stalled, Clearane, Downstream of the
Supply Fan Outlet is Required to Provide
Adquate Air Flow and Reduce Air Pres-
12'-5"
82 3/4"
sure Drop.
70 5/8"
4 5/8"
28 1/2"
4 5/8"
106 5/8" 40"
A I R F L OW
CP 10'
CO
DP FS CC MB EE
REAR FRONT SIDE SIDE
23 5/16"
6'-10 5/8"
FE
19 9/16"
2 3/8"
LD08134
YORK INTERNATIONAL
FORM 100.50-EG1 (705)
YORK INTERNATIONAL
DP = Discharge Plenum
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CO = Condenser Section
Shipment. CP = Control Panel
6. Clearance Downstream of the Diffuser.
If the Diffuser Factory Option is Not In-
stalled, Clearane, Downstream of the
Supply Fan Outlet is Required to Provide
Adquate Air Flow and Reduce Air Pres-
sure Drop.
12'-5"
28 1/2"
A I R F L OW
CP 3048
10'
CO
23 5/16"
72 1/4"
6'-10 5/8"
FE
6 1/4"
2 3/8"
6 1/4"
LD08135
FORM 100.50-EG1 (705)
131
NOTES: SECTION DESCRIPTIONS:
132
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
6. Clearance Downstream of the Diffuser.
If the Diffuser Factory Option is Not In-
stalled, Clearane, Downstream of the
Supply Fan Outlet is Required to Provide
Adquate Air Flow and Reduce Air Pres-
sure Drop.
13'-5"
82 3/4"
70 5/8"
4 5/8"
34 1/2"
4 5/8"
48"
TOP VIEW
EXTENDED CABINET / BOTTOM SUPPLY / BOTTOM RETURN
A I R F L OW
10'
CP CO
23 5/16"
7'-8 5/8"
FE
19 9/16"
2 3/8"
YORK INTERNATIONAL
LD08138
FORM 100.50-EG1 (705)
NOTES: SECTION DESCRIPTIONS:
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. FF = Final Filter
YORK INTERNATIONAL
DP = Discharge Plenum
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CO = Condenser Section
Shipment. CP = Control Panel
6. Clearance Downstream of the Diffuser.
If the Diffuser Factory Option is Not In-
stalled, Clearane, Downstream of the
Supply Fan Outlet is Required to Provide
Adquate Air Flow and Reduce Air Pres-
sure Drop.
13'-5"
34 1/2"
TOP VIEW
A I R F L OW
10'
CP CO
23 5/16"
82 5/16"
7'-8 5/8"
163 3/8" 38"
40"
19 9/16" 58"
6 1/4"
2 3/8"
5 3/4"
LD08137
FORM 100.50-EG1 (705)
133
NOTES: SECTION DESCRIPTIONS:
134
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. DP = Discharge Plenum
CO = Condenser Section
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CP = Control Panel
Shipment.
6. Clearance Downstream of the Diffuser.
If the Diffuser Factory Option is Not In-
stalled, Clearane, Downstream of the
Supply Fan Outlet is Required to Provide
Adquate Air Flow and Reduce Air Pres-
13'-5"
sure Drop.
34 1/2"
A I R F L OW
EXTENDED CABINET / LEFT SUPPLY / FRONT RETURN
10'
CP CO
REAR
23 5/16"
82 5/16"
7'-8 5/8"
FE
6 1/4"
2 3/8"
6 1/4"
YORK INTERNATIONAL
LD08138
General Arrangement Drawing – 70-85 Ton Models
FORM 100.50-EG1 (705)
NOTES: SECTION DESCRIPTIONS:
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. FF = Final Filter
YORK INTERNATIONAL
DP = Discharge Plenum
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CO = Condenser Section
Shipment. CP = Control Panel
6. Clearance Downstream of the Diffuser.
If the Diffuser Factory Option is Not In-
stalled, Clearane, Downstream of the
Supply Fan Outlet is Required to Provide
Adquate Air Flow and Reduce Air Pres-
sure Drop.
12'-5"
82 3/4"
70 5/8"
4 5/8"
28 1/2"
TOP VIEW
EXTENDED CABINET / BOTTOM SUPPLY / BOTTOM RETURN
A I R F L OW
10'
CP CO
23 5/16"
7'-8 5/8"
FE
19 9/16"
2 3/8"
LD08139
FORM 100.50-EG1 (705)
135
General Arrangement Drawing – 90-105 Ton Models
NOTES: SECTION DESCRIPTIONS:
136
1. 10' Clearance Minimal Over The Top of EE = Economizer
the Condensing Unit. FE = Fan Exhaust
2. Only One Adjacent Wall Can Exceed Unit MB = Mixing Box
Height. _F = Filter Segments
3. 12' Clearance Required to Adjacent Units CC = Cooling Coils
4. 8' Service AccessRecommended on One FS = Supply Fan
Side. FF = Final Filter
DP = Discharge Plenum
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CO = Condenser Section
Shipment. CP = Control Panel
6. Clearance Downstream of the Diffuser.
If the Diffuser Factory Option is Not In-
stalled, Clearane, Downstream of the
Supply Fan Outlet is Required to Provide
Adquate Air Flow and Reduce Air Pres-
12'-5"
sure Drop.
28 1/2"
A I R F L OW
10'
CP CO
23 5/16"
82 5/16"
7'-8 5/8"
FE
6 1/4"
2 3/8"
5 3/8"
YORK INTERNATIONAL
LD08137
FORM 100.50-EG1 (705)
YORK INTERNATIONAL
DP = Discharge Plenum
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for CO = Condenser Section
Shipment. CP = Control Panel
6. Clearance Downstream of the Diffuser.
If the Diffuser Factory Option is Not In-
stalled, Clearane, Downstream of the
Supply Fan Outlet is Required to Provide
Adquate Air Flow and Reduce Air Pres-
12'-5"
sure Drop.
28 1/2"
10'
EXTENDED CABINET / LEFT SUPPLY / BOTTOM RETURN
CP CO
REAR
23 5/16"
82 5/16"
7'-8 5/8"
FE
6 1/4"
2 3/8"
6 1/4"
LD08141
FORM 100.50-EG1 (705)
137
NOTES:
138
1. 10' Clearance Minimal Over The Top of
the Condensing Unit.
2. Only One Adjacent Wall Can Exceed Unit
Height.
3. 12' Clearance Required to Adjacent Units
4. 8' Service Access Recommended on
One Side.
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for
Shipment.
GAS HEAT / ANGLED FILTERS
YORK INTERNATIONAL
LD08173
FORM 100.50-EG1 (705)
YORK INTERNATIONAL
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for
Shipment.
ECONOMIZER / GAS HEAT / ANGLED FILTERS
LD08174
FORM 100.50-EG1 (705)
139
NOTES:
140
1. 10' Clearance Minimal Over The Top of
the Condensing Unit.
2. Only One Adjacent Wall Can Exceed Unit
Height.
378"
3. 12' Clearance Required to Adjacent Units
4. 8' Service Access Recommended on
One Side.
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for
178 15/16"
Shipment. POWER
CONNECTION
THRU FLOOR
OA
8"
4 5/8"
229 1/2"
276 1/2"
TOP
VIEW
72" CLEAR 84" CLEAR
ELETRIC
120" CLEAR
HEATER
BOTTOM SUPPLY / BOTTOM RETURN / POWERED RETURN FAN /
7'-6"
1 1/4" FPT DRAIN
140" BOTH SIDES OF UNIT
12'-0"
2 1/2"
120" CLEAR
FOR COIL PULL 16'-7 13/16"
A I R F L OW
YORK INTERNATIONAL
LD08175
FORM 100.50-EG1 (705)
YORK INTERNATIONAL
5. Economizer and Exhaust Hoods, Where
Applicable, are Folded Inside Unit for
Shipment.
LD08176
FORM 100.50-EG1 (705)
141
FORM 100.50-EG1 (705)
339"
237"
RETURN
SUPPLY
83"
87"
71.61"
40" 35.75"
2"
14"
LD08142
449"
292"
RETURN
SUPPLY
83"
87"
71.61"
43" 48"
2"
NOTES:
14"
483"
326"
RETURN
SUPPLY
83"
87"
71.61"
48" 54.25"
2"
14"
LD08144
384"
282.66"
SUPPLY
RETURN
83"
87"
2"
30" 35.75"
14"
NOTES:
1. Unit must be installed square and level.
2. Curb configuration for “bottom” return and “bottom” supply.
3, These drawings are not intended as construction documents for the field fabricated roof curbs. YORK will not be responsible for the
unit fit up, leak integrity, or sound level for installation using field fabricated roof curbs.
4. The YPAL unit does not have a base pan under the condensing section of the unit. Field fabricated roof curbs must have a cap on the
top of the condensing section of the curb to prevent moisture from entering the space. The cap design must be sloped away from the
supply duct opening to the end of the unit for the drainage of the moisture off of the top of the cap.
355"
RETURN
SUPPLY
83"
87"
2"
31" 48"
14"
LD08146
395"
SUPPLY
RETURN
83"
87"
2"
36" 54.25"
14"
NOTES:
1. Unit must be installed square and level.
2. Curb configuration for “bottom” return and “bottom” supply.
3, These drawings are not intended as construction documents for the field fabricated roof curbs. YORK will not be responsible for the
unit fit up, leak integrity, or sound level for installation using field fabricated roof curbs.
4. The YPAL unit does not have a base pan under the condensing section of the unit. Field fabricated roof curbs must have a cap on the
top of the condensing section of the curb to prevent moisture from entering the space. The cap design must be sloped away from the
supply duct opening to the end of the unit for the drainage of the moisture off of the top of the cap.
FIG. 10 – GENERAL ARRANGEMENT DRAWING LD08147
373"
Supply Return
Condenser
135"
81 7/8"
Air Air
109 3/4"
Opening Opening
23 1/4"
2" TYP
11"
14"
LD08177
NOTES:
1. Unit must be installed square and level.
2. Curb configuration for “bottom” return and “bottom” supply.
3, These drawings are not intended as construction documents for the field fabricated roof curbs. YORK will not be responsible for the
unit fit up, leak integrity, or sound level for installation using field fabricated roof curbs.
4. The YPAL unit does not have a base pan under the condensing section of the unit. Field fabricated roof curbs must have a cap on the
top of the condensing section of the curb to prevent moisture from entering the space. The cap design must be sloped away from the
supply duct opening to the end of the unit for the drainage of the moisture off of the top of the cap.
A
C
Piping Connections
D LD08118
From Baserail Bottom
Piping Connections
D Supply
D Return
. . .
19-3/8"
57" 54"
35-1/2"
33" 35-1/2"
30-1/2" 30-1/2"
12-1/4" 12-1/4"
9-1/4"
9-1/4"
6-1/4"
6-1/4" 6-1/4"
2-1/2"
PANEL A PANEL B
3/4" K.O. (CONTROL WIRING) 3/4" K.O. (CONTROL WIRING)
LD07315
BOTTOM VIEW
Guide Specifications
GENERAL 4. Electrical power requirements and wire/conduit and
overcurrent protection sizes.
Scope 5. All costs incurred to modify the building provisions
The requirements of the General Conditions, Supple- to accept the furnished units.
mentary Conditions, Division 1 and drawings apply to Warranty: Manufacturer shall warrant all equipment
all work herein. and material of its manufacture against defects in work-
Provide Microprocessor-controlled, air-cooled, double- manship and material for a period of eighteen (18)
wall construction outdoor packaged rooftop air condi- months from date of shipment.
tioning product of the scheduled capacities and perfor- 1. The warranty shall include parts only during this pe-
mance as shown and indicated on the Drawings, in- riod.
cluding but not limited to: 2. The warranty shall not include parts associated with
1. Single-piece rooftop package routine maintenance, such as belts, air filters, etc.
2. Charge of refrigerant and oil
Delivery and Handling
3. Electrical power and control connections
4. Supply and return duct connections Unit shall be delivered to the job site fully assembled,
wired, and charged with refrigerant and oil by the manu-
5. Factory start-up
facturer.
Quality Assurance Unit shall be stored and handled per Manufacturer’s
instructions.
All units are tested, rated or certified, as applicable, in
accordance with the following standards, guidelines and All handling and storage procedures shall be per
codes: manufacturer’s recommendations.
1. All units shall meet the latest ASHRAE 90.1 mini-
mum energy-efficiency requirements (EER) Submittals
2. All units shall meet the latest ASHRAE 62 require- Shop Drawings: Shop drawing submittals shall include,
ments for ventilation and indoor air quality. but not limited to, the following: drawings indicating com-
3. All units shall be rated in accordance with the ARI ponents, dimensions, weights, required clearances, and
Standard 340/360 location, type and size of field connections, and power
and control wiring connections.
4. All units shall be tested to ANSI/UL 1995 and CAN/
CSA C22.2 No. 236 standards Product Data: Product data shall include dimensions,
5. Gas heating units shall be designed in conform to weights, capacities, ratings, fan performance, motor
ANSI Z21.47-1998/CSA 2.3-M98 standards and be electrical characteristics, and gauges and finishes of
carry the UL listing materials.
6. Units shall be ETL and ETL Canada listed Documentation:
Manufacturers: The design shown on the drawing is 1. Fan curves with specified operating point clearly
based upon products of the manufacturer scheduled. plotted shall be provided.
Alternate equipment manufacturers shall be acceptable 2. Product data of filter media, filter performance data,
if equipment meets the scheduled performance and filter assembly, and filter frames shall be provided.
complies with these specifications. If equipment manu- 3. Electrical requirements for power supply wiring; in-
factured by manufacturer other than that scheduled is cluding wiring diagrams for interlock and control
utilized, then the Mechanical Contractor shall be respon- wiring shall be supplied. Factory and field-installed
sible for coordinating with the General Contractor and wiring shall be clearly indicated.
all affected Subcontractors to insure proper provisions
4. Operation and maintenance documentation shall be
for installation of the furnished unit. This coordination
supplied in accordance with Section 01830 – Op-
shall include, but not be limited to, the following:
eration and Maintenance, including but not limited
1. Structural supports for units. to instructions for lubrication, filter replacement,
2. Roof curb transition. compressor, motor and drive replacement, coil
3. Piping size and connection/header locations. cleaning, filter maintenance, spare parts lists, and
wiring diagrams.
[SELECT ONE OF THE FOLLOWING TYPES OF horsepower as specified. Motors shall be 1750
BUILDING PRESSURE CONTROL] RPM, open drip-proof type. The motor shall be lo-
2. No Building Exhaust/Relief: The unit has no provi- cated within the unit on an adjustable base.
sions to exhaust building return air. Mountings: Fan and fan motor shall be internally
2. Barometric Relief Damper: Building air exhaust mounted and isolated on a full width isolator sup-
shall be accomplished through barometric relief port channel using 1-inch springs [2-inch springs
dampers installed in the return air plenum. The and seismic restraints]. The fan discharge shall
dampers open relative to the building pressure. The be connected to the fan cabinet using a flexible
opening pressure shall be adjustable. connection to insure vibration-free operation.
2. On/Off Fan Powered Exhaust: A DWDI Class II Bearings and Drives: Fan bearings shall be self-
forward-curved centrifugal exhaust fan shall be pro- aligning, pillow block or flanged type regreaseable
vided to exhaust building return air to relieve build- ball bearings and shall be designed for an average
ing static pressure. The fans shall be constant vol- life (L50) of at least 200,000 hours. All bearings
ume and operate based on either a building static shall be factory lubricated and equipped with stan-
pressure, or outside air damper position. dard hydraulic grease fittings and lube lines ex-
tended to the motor side of the fan. Fan drives
2. Powered Exhaust with Modulating Discharge
shall be selected for a 1.5 service factor and anti-
Damper: A DWDI Class II forward-curved centrifu-
static belts shall be furnished. All drives shall be
gal exhaust fan shall be provided to exhaust build-
fixed pitch. Fan shafts shall be selected to operate
ing return air to relieve building static pressure. The
well below the first critical speed and each shaft
fans shall operate at a constant volume and oper-
shall be factory coated after assembly with an anti-
ate based on building static pressure. Exhaust air-
corrosion coating.
flow shall be modulated via a parallel-acting control
damper. The exhaust air dampers shall be sized Filter Section:
for 100% of the exhaust airflow.
[SELECT A FILTER RACK, FILTER MEDIA, AND
2. Powered Exhaust with Variable-Frequency-Drive: A SWITCH IF DESIRED]
twin DWDI Class II forward-curved centrifugal ex-
1. Angled Filter Rack: two-inch throwaway filters shall
haust fan shall be provided to exhaust building re-
be provided in an angled filter rack.
turn air to relieve building static pressure. Exhaust
airflow shall be modulated via a factory-installed and 1. Angled Filter Rack: two-inch carbon media filters
commissioned variable-frequency-drive with the shall be provided in an angled filter rack.
same nameplate horsepower as the supply fan 1. Angled Filter Rack: two-inch cleanable filters shall
motor. be provided in an angled filter rack.
2. Power Return Fan – A SWSI plenum fan shall be 1. Angled Filter Rack: two-inch high-efficiency (30%)
provided to draw return air from the building to the pleated filters shall be provided in an angled filter
rooftop unit. An access door shall be provided on rack.
at least one side of the unit for fan/motor access. 1. Flat Filter Rack: 60-65% Efficient Rigid Filters with
The return fan shall operate to maintain a constant a two-inch high-efficiency pleated pre-filters shall
pressure within the return plenum. be provided in a flat filter rack.
2. Power Return Fan – A SWSI plenum fan shall be 1. Flat Filter Rack: 90-95% Efficient Rigid Filters with
provided to draw return air from the building to the a two-inch high-efficiency pleated pre-filters shall
rooftop unit. An access door shall be provided on be provided in a flat filter rack.
at least one side of the unit for fan/motor access.
2. Dirty Filter Alarm: A dirty filter switch shall be pro-
The return fan shall operate to maintain a constant
vided and wired to the rooftop unit control panel.
pressure within the return plenum. A discharge
Upon closure of the switch, the controller shall dis-
damper shall be provided to modulate building ex-
play a dirty filter fault. The setting of the switch can
haust. The damper shall be controlled via building
be changed manually to close at a specified pres-
pressure. The return damper shall linked with the
sure drop across the filters.
outside air damper to modulate volumes of return
and outside airflows. Evaporator Section
[FOR POWERED EXHAUST OR RETURN FAN OP- 1. Cooling Coil: Evaporator coils shall be direct ex-
TIONS ABOVE, USE THE FOLLOWING] pansion type with intertwined circuiting to assure
complete coil face activity during part load opera-
3. Fan Motor: Fan motors shall be NEMA design ball-
tion. Coil tubes shall be 1/2" OD copper, with inter-
bearing types with electrical characteristics and
nally enhanced tubes. Fins shall be enhanced me-
Heat Exchanger(s): The heat exchanger(s) shall be tem. Power connection to the heater is through the
constructed of tubular aluminized steel [stainless power panel for the unit. Electric heat is ETL certi-
steel], with stainless steel flue baffles and flue as- fied to both US and Canadian safety standards.
sembly. 1. Hot Water Heating Coil
Burner(s) and Ignition Control: The burner(s) shall A hot water coil shall be installed in the rooftop unit
include a direct-driven induced-draft combustion fan discharge plenum.
with energy efficient intermittent pilot spark ignition,
Construction: The hot water coil shall have eight
redundant main gas valves with pressure regula-
[10, 12, 14] fins per inch, 2 tubes per circuit, and an
tor.
2" inlet and outlet connection. Primary surface shall
Combustion Air Fan(s): The inducer fan(s) shall be 1/2" OD copper tube, staggered in direction of
maintain a positive flow of air through each tube, to airflow. Connections have 1/4" FPT drain plug on
expel the flue gas and to maintain a negative pres- each connection. A structural galvanized steel cas-
sure within the heat exchanger relative to the con- ing shall protect the coil. An intermediate coil sup-
ditioned space. port shall be provided. The coil shall be circuited to
Safety Devices: A high limit controller with auto- provide free draining and venting, through one vent
matic reset to prevent the heat exchanger from and drain.
operating at an excessive temperature shall be in- Testing: Completed coil, including headers, con-
cluded. A centrifugal switch on the induced draft fan nections and return bends shall be tested with 325
motor shaft shall prevent ignition until sufficient air- pounds compressed air under water. Coils shall be
flow is established through the heat exchanger. A designed for operation at 250 psig design working
rollout switch shall provide secondary airflow safety pressure.
protection. The rollout switch shall discontinue fur-
1. Steam Heating Coil
nace operation if the flue becomes restricted.
A steam heating coil shall be installed in the rooftop
Flue: The furnace flue shall be shipped loose to
unit discharge plenum.
protect it from damage during transit. The flue shall
be field-mounted by the installing contractor. The Construction: The steam coil shall be constructed
flue outlet shall be located above the unit to help in the non-freeze style. The steam coil shall have
prevent recycling of combustion gases back through six fins per inch, an 2" inlet, and 1 1/2" outlet con-
the heat exchanger. nection. Tubes shall be 1" OD seamless copper
tubing with a minimum wall thickness of 0.035" and
Agency Certification: Gas heating sections are both
expanded into the fin collars for maximum fin-tube
UL and CGA approved to both US and Canadian
bond. Inner distributing tubes shall be 5/8" OD
safety standards.
seamless copper tubing with a minimum wall thick-
1. Electric Heat ness of 1/4". All header connections shall be of red
An electric slip-in heater is installed within the roof- brass or steel, with male pipe threads and silver
top unit discharge plenum to provide the heating braze to headers. Casing shall be galvanized steel.
requirements per the schedule shown on the plans. The core shall be pitched in the direction of the con-
The electric heater is wired in such a manner as to densate connection for proper drainage.
provide a minimum of two steps of capacity. Testing: The completed coil, including headers and
Heat Exchanger: The furnace is an industrial grade connections, shall be tested underwater with 325
design using an open coil made of the highest-grade lbs. compressed air to ensure a leak free coil.
resistance wire containing 80% nickel and 20% 2. Diffuser Section [available for YPAL050-105 only]:
chromium. The resistance coils are adequately sup- For applications with an extended discharge ple-
ported in the air stream using ceramic bushings in num for downstream filtration, a diffuser section is
the supporting framework. Terminals of the coil are provided. A diffuser shall be included to distribute
stainless steel with high temperature ceramic bush- the airflow from the fan evenly across the filter bank
ings. to optimize filter life and effectiveness. The diffuser
Safety Devices: The primary high temperature pro- shall be sized for 50% free area and provide ad-
tection is an automatic reset type thermal cut out. equate upstream and downstream clearance to
Secondary protection is an automatic reset type minimize airside pressure drop.
thermal cut out. Secondary protection is a replace-
[FOR EXTENDED DISCHARGE PLENUMS, SELECT
able thermal link.
ONE OF THE FOLLOWING]
Agency Certification: The operation of the electric
3. Downstream Final Filter Rack [available for
heater is an integral part of the roof top control sys-
YPAL050-105 only]: A 12-inch rigid filter rack and
tions, date and time shall be stored in the shutdown units shall be installed as specified.
history to facilitate service and troubleshooting. 1. Unit(s) specified shall include a protective covering
4. Controls and BAS Communications membrane for such equipment being shipped by
BACnet MSTP (RS-485) or Modbus: The unit shall truck, rail, or ship. The membrane is fully formed
include BACnet or Modbus communications directly around the equipment exterior. The membrane cov-
from the unit controller. Equipment that is not na- ers the entire top, side and end panel surface as to
tive BACnet at the unit control board shall include protect the product effectively during shipping & stor-
any necessary interface or translator device fac- age including “Long Term Storage”. Storing on job-
tory-mounted and wired within the unit. If a field- site shall no longer require the unit(s) to be cov-
installed gateway device is required by the manu- ered with a tarp as long as the covering membrane
facturer, the manufacturer shall include all neces- has not been removed.
sary materials, equipment, service and commission- 2. All size or shape equipment including electrical com-
ing of the gateway. A control points list, BIBBs and ponents, especially those not built with weather-
PICS statement shall be provided by the manufac- proof enclosures, variable-frequency drives and end
turer to facilitate communications programming with devices shall be effectively covered for protection
the building automation system. Programming, es- against rain, snow, wind, dirt, sun fading, road salt/
tablishing communications and commissioning shall chemicals, rust, and corrosion during shipping cycle.
be the responsibility of the installing controls con- Equipment shall remain clean and dry.
tractor. Start-up assistance and support may be 3. Manufacturers of units not having a protective mem-
purchased from the manufacturer. brane, fully formed around the equipment exterior,
Analog inputs: 0-5VDC inputs shall be provided for covering the entire top, side and end panel surface
remote reset of supply air temperature, and duct area shall be required to ship equipment covered
static pressure with a tarp, in crating or in a closed truck as is nec-
Binary inputs: Dry (or “wet”) contacts shall be pro- essary to ensure product protection from road salt/
vided for alarm outputs for supply fan fault, cooling/ chemicals damage, moisture and dirt infiltration.
heating fault, or general/sensor faults. Contacts Arrangements for long term storage at the job site
shall also be provided for occupied/unoccupied shall be required.
(start/stop) switching; shutdown, smoke purge, ex- Location: Locate the rooftop unit as indicated on draw-
haust or pressurization operations; call for cooling ings, including cleaning and service maintenance clear-
or heating; and for morning warm-up. ance per Manufacturer instructions. Adjust and level the
rooftop unit on support structure.
EXECUTION
INSPECTION AND START-UP SUPERVISION
Installation
General: Installing contractor shall install rooftop unit(s), A factory-trained service representative of the manu-
including components and controls required for opera- facturer shall supervise the unit startup and application
tion, in accordance with rooftop unit manufacturer’s specific calibration of control components.
written instructions and recommendations. Rooftop