AMAL POWER STATION

TYPICAL GTG TRIPPING MATRIX

A 9/1/2008 JSL Issued for Tender

0 6/1/2008 JSL Issued for Comments

DRAWN CHECKED APPROVED DESCRIPTION REF IND SIGN


REV DATE
BY BY BY
PDO APPROVAL

PROJECT DRAWING REVISION

AREA : Alam

PETROLEUMDEVELOPMENTOMAN
SUB AREA : Amal Power Station
DRAWING IDENTIFICATION
DRWG. TYPE : TYPICAL DRWG AREA ENG. SERIAL SHEET PROJ. DWG. REV.
TYPICAL GTG TRIPPING MATRIX CODE SECT. NUMBER No. CODE SIZE
No. Sketch 022
Page 01 of 04
Amal Power Station GAS TURBINE AND GAS TURBINE GENERATOR TRIP LOGIC DIAGRAM
CAUSE

1 • • • • • • 87G Generator Differential Operated 1

2 • • • • • • 59N1
Generator stator earth fault relay operated ( 0 to
95%)
2

3 • • • • • • 51N
Generator stator earth fault current relay
operated
3

Generator rotor earth fault relay first stage


4 64R 4
operated( <80kohm)

5 • • • • • • 64R
Generator rotor earth fault relay second stage
operated( <5kohm)
5

Generator Fire Detector temperature high Stage 1


6 26 6
( 80deg C)

7 • • • • • • 26
Generator Fire detector temperature high Stage 2
( 100deg C)
7

8 • • • • • • 59GN1
Generator stator earth fault protection operated
( 95 to 100%)
8

9 • • • • • 5 Emergency stop push button operated 9

10 • • • • 40G
Loss of excitation relay operated together with
27/40 rly oprtd and prot PT fuse healthy
10

11 • • • • 27/40
40G relay operated together with 27/40 rly not
oprtd, prot PT fuse healthy and with time delay
11

12 46G Negative sequence current relay stage-1 operated 12

13 • • • • 46G Negative sequence current relay stage-2 operated 13

14 14

15 • 49G
Over load relay ( thermal replica type) stage-1
operated
15

16 • • • • 49G
Over load relay ( thermal replica type) stage-2
operated
16

17 • • • • 78G Pole slipping relay operated 17

18 99G Over fluxing protection relay stage-1 operated 18

19 • • • • 99G Over fluxing protection relay stage-2 operated 19

20 • • • • 96G
Dead machine protection operated
20

21 21

22 • • • • 27G
Under voltage relay operated together with PT fuse
healthy - Stage 2
22

23 81.1G Under frequency relay stage-1 operated 23

24 • • • • 81.2G Under frequency relay stage-2 operated 24

25 59.1G Generator over voltage relay stage1 operated 25

26 • • • • 59.2G Generator over voltage relay stage2 operated 26

27 • • • • 32R1 Reverse power relay stage-1 operated 27

28 • • • • 32R2 Reverse power relay stage-2 operated 28

AVR Regulation Changeover from AUTO-2 to


AVR Regulation Changeover from AUTO-1 to
Release of CO2 into Generator enclosure

132kV Breaker A120/A720 86H tripped


Generator CB D570/D370 tripped ( Trip
Generator CB D570/D370 tripped ( Trip

132kV Breaker A120/A720 86E tripped


132kV Breaker A110/7310 86H tripped

132kV Breaker A110/A710 86E tripped


Gas Turbine Shurdown with Unload

prompt operator for load management


Trip GCB, Excitation, and Gas Turbine

Reduce Excitation command to AVR


Master Trip Relays 86G3 and 86G4
Master Trip Relays 86G2 and 86G3
Master Trip relays 86U1and 86U2

Release of CO2 into GT enclosure

6.6kV MVUAS-3 incomer tripped


Exciter field breaker tripped
Trip GCB and Excitation

Trip GCB and Excitation

Block Generator synch


Local and Romte Reset

132kV bus zone trip


Gas Turbine trip

Alarm/Indication
Local Reset Only

Local Reset Only

( E180/E280)
EFFECT

coil-2 opr.)
coil-1 opr.)

AUTO-2

AUTO-1
A

Class of Shutdown MASTER TRIP RELAYS MAJOR EQUIPMENT TRIPS ALARM/CONTROL EFFECTS

LEGEND FOR Class of Shutdown

A Shut down : Trip GCB, Trip Excitation, GT Running C Shut down : Trip GCB, Trip Excitation, Trip GT via MARK-VI ( GT Shuts down)

Shut down : Unload GT, Trip GCB, Trip Excitation, Trip GT via MARK-
B D Shut down : Trip GCB, Trip Excitation, Trip GT via MARK-VI ( GT Shuts down), Trip 132kV Circuit Breaker(s), Trip 6.6kV incomer
VI ( GT Shuts down)
Page 01 of 04
Amal Power Station GAS TURBINE AND GAS TURBINE GENERATOR TRIP LOGIC DIAGRAM
CAUSE

29 29

30 30

31 31

32 32

33 33

34 • • • • • • Gas Turbine trip 34

35 • • • • • 50LBB
Generator Circuit Breaker fail protection
operated
35

Generator Backup impedance relay


36 • • • • 21GT operated togather with PT fuse healthy
( 132kv side)
36

37 51.1G Over current protection relay operated 37

38 • • • • • • • • • • • 59N2 11kV bus earth fault relay operated 38

39 60.2G AVR PT1 fuse failure 39

40 60.4G AVR PT2 fuse failure 40

41 60.5G Metering PT fuse failure 41

41A 58 Excitor Diode Failure (Open ckt) 41A

41B 58 Excitor Diode Failure (Short ckt) 41B

42 60.1G Protection PT1 fuse failure 42

43 60.3G Protection PT2 fuse failure 43

Synchronisation PT fuse failure (Both


44 FFR generator side and step-up transformer 44
side of generator circuit breaker)

45 • • • • • • • 87GT
Generator transformer differential relay
operated
45

46 • • • • • • • 64R(gt)
Generator transformer REF protection
operated
46

47 • • • • • • • 51SBEF
Generator transformer backup earth fault
protection operated
47

48 • • • • • • 67N
GTX directional earth fault relay operated
( 132kv side)
48

49 • • • • • • • 21 G
Generator backup impedance prot.
Operated ( 11kV Side)
49

50 • • • • • 59/81
Generator transformer overfluxing
protection operated ( 132kV side)
50

51A • • • • • • • 50BF1
132kV Bus Circuit Breaker Fail
(A510/A310)
51A

51B • • • • • • • 50BF2
132kV Tie Circuit Breaker Fail
(A520/A320)
51B

Generator transformerGTX 49(OT)A,


52 49(WT)A, 63(B)A, 63(TCB)A, 71(LO)A - 52
Stage 1
Generator transformer GTX 49(OT)T,
53A 53A
49(WT)T - Stage 2

53B • • • • • Generator transformer 63(B)T,


63(TCB)T, 63(PR)T - Stage 2
53B

54 • • • • • 87T MVUAT diff. Protection operated 54

55 • • • • • 64R(LV) MVUAT LV REF Protection operated 55

56 • • • • • 50, 51,
51N
MVUAT Non direct. O/C, E/F protection
operated
56

57A MVUAT 49(OT)T, 49(WT)T 57A

57B • • • • • MVUAT 63(B)T, 63(TCB)T, 63PRV(T) 57B

MVUAT 49(OT)A, 49(WT)A, 63(B)A,


58 58
63(TCB)A, 71(LO)A
6.6kV MVUAS switchboard incomer
59 86T 59
master trip relay operated

59A • • • • • • IPS trip 59A


Generator CB D570/D370 tripped ( Trip coil-2
Generator CB D570/D370 tripped ( Trip coil-1

6.6kV MVUAS-3 incomer tripped (E180/E280)

AVR Regulation Changeover from AUTO-2 to


AVR Regulation Changeover from AUTO-1 to
132kV Breaker A120/A720 86H tripped

132kV Breaker A120/A720 86E tripped


132kV Breaker A110/7310 86H tripped

132kV Breaker A110/A710 86E tripped


Gas Turbine Shurdown with Unload
Trip GCB, Excitation, and Gas Turbine

Promt operator for load management


Master Trip Relays 86G3 and 86G4

Reduce Excitation command to AVR


Master Trip Relays 86G2 and 86G3
Master Trip relays 86U1and 86U2

Release of CO2 into Gt Enclosure


Release of CO2 into Generator
Excitor field breaker tripped
Trip GCB and Excitation

Trip GCB and Excitation


Local and Romte Reset

Block Gnerator synch


132kV bus zone trip
Gas Turbine trip
Local Reset Only

Local Reset Only

Alarm/Inication
EFFECT

AUTO-2

AUTO-1
opr.)

opr.)
A

Class of Shutdown MASTER TRIP RELAYS MAJOR EQUIPMENT TRIPS

LEGEND FOR Class of Shutdown

A Shut down : Trip GCB, Trip Excitation, GT Running C Shut down : Trip GCB, Trip Excitation, Trip GT via MARK-VI ( GT Shuts down)

Shut down : Unload GT, Trip GCB, Trip Excitation,


B D Shut down : Trip GCB, Trip Excitation, Trip GT via MARK-VI ( GT Shuts down), Trip 132kV Circuit Breaker(s), Trip 6.6kV incomer
Trip GT via MARK-VI ( GT Shuts down)
Page 01 of 04
Amal Power Station GAS TURBINE AND GAS TURBINE GENERATOR TRIP LOGIC DIAGRAM
CAUSE

60 • • • • • R5E
Emergency remote manual
trip-MKVI panel
60

61 • • • • • L94FX4
Failure to leave premix
transfer-trip
61

62 • • • • • L94FX3
Fail to reignite prim in sec-
L.R.trip
62

63 • • • • • L94FX2
Failure to reignite primary
zone-trip
63

64 • • • • • L94FX1
Failure to leave secondary
XFER-trip
64

65 • • • • • L86TXT
Exhaust over temperature
trip
65

66 • • • • • L86TFB
Exhaust thermocouples open
trip
66

67 • • • • • L86FPG2LT Post-ignition P2 low trip 67

68 • • • • • L86FPG2HT Post-ignition P2 high trip 68

69 • • • • • L63QTX
Turbine lube oil header press
low trip
69

70 • • • • • L63ETH
Exhaust duct pressure high
trip
70

71 • • • • • L63CSHH
Inlet filter very high
pressure drop -trip
71

72 • • • • • L5E
Emergency manual trip-MKVI
panel
72

73 • • • • • L4IGVT
Inlet guide vane control fault
trip
73

74 • • • • • L4GFIVPT
P2 supply pressure too low
trip
74

75 • • • • • L4DLNT
Dry low nox system trouble-
trip
75

76 • • • • • L4CT Common BOP IPS trip 76

77 • • • • • L12H
prot module speed sgnl loss
(Decel Det)
77

78 • • • • • L3SFLT Control system fault trip 78

79 • • • • • L39VT High vibration trip 79

80 • • • • • L30SPT
High exhaust temperature
spread trip
80

81 • • • • • L2SFT
Start up fuel flow excessive
trip
81

82 • • • • • L28FDT Loss of flame trip 82

83 • • • • • L26QT
Lube oil header temperature
high high trip
83

84 • • • • • L12H Electrical overspeed trip-HP 84


Generator CB D570/D370 tripped ( Trip coil-2
Generator CB D570/D370 tripped ( Trip coil-1

AVR Regulation Changeover from AUTO-2 to


AVR Regulation Changeover from AUTO-1 to
132kV Breaker A120/A720 86H tripped

132kV Breaker A120/A720 86E tripped


Gas Turbine Shurdown with Unload

132kV Breaker A110/7310 86H tripped

132kV Breaker A110/A710 86E tripped


Trip GCB, Excitation, and Gas Turbine

Promt operator for load management


Reduce Excitation command to AVR
Master Trip Relays 86G3 and 86G4
Master Trip Relays 86G2 and 86G3
Master Trip relays 86U1and 86U2

Release of CO2 into Gt Enclosure

6.6kV MVUAS-3 incomer tripped


Release of CO2 into Generator
Excitor field breaker tripped
Trip GCB and Excitation
Trip GCB and Excitation

Local and Romte Reset

Block Gnerator synch


132kV bus zone trip
Gas Turbine trip
Local Reset Only

Local Reset Only

Alarm/Inication
EFFECT

AUTO-2

AUTO-1
opr.)

opr.)
A

Class of Shutdown MASTER TRIP RELAYS MAJOR EQUIPMENT TRIPS ALARM/CONTROL EFFECTS

LEGEND FOR Class of Shutdown

A Shut down : Trip GCB, Trip Excitation, GT Running C Shut down : Trip GCB, Trip Excitation, Trip GT via MARK-VI ( GT Shuts down)

Shut down : Unload GT, Trip GCB, Trip Excitation, Trip


B D Shut down : Trip GCB, Trip Excitation, Trip GT via MARK-VI ( GT Shuts down), Trip 132kV Circuit Breaker(s), Trip 6.6kV incomer
GT via MARK-VI ( GT Shuts down)
Page 01 of 04
Amal Power Station GAS TURBINE AND GAS TURBINE GENERATOR TRIP LOGIC DIAGRAM
CAUSE

85 • • • • • • L45HT1
Haz.Gas detected in
turb.compartment
85

86 • • • • • • L30LTA
Load tunnel temp high-auto
unloading
86

87 • • • • • L12HF Control speed signal loss-HP 87

88 • • • • • LCPRERR
comp op limit protection max
control error
88

89 • • • • • L86GCVT G1 GCV not following ref.trip 89

90 • • • • • L86GCVST G2 GCV not following ref.trip 90

91 • • • • • L86GCV3T G3 GCV not following ref. trip 91

92 • • • • • L86CBT
Cool & seal air compt.bleed valve
open pos trbl
92

93 • • • • • • L86BTX
Heat vent loss of turb.compt.vent -
fast shut down
93

94 • • • • • L60BOG Turbine startup bogged down-trip 94

95 • • • • • • • L45FT1 Unit fire protection operated 95

96 • • • • • • • L45FPX Unit fire protection operated 96

97 • • • • • L3GRVT
Stop/speed ratio valve not tracking
trip
97

98 • • • • • L3FTGLT Gas fuel temperature too low-trip 98

99 • • • • • • L39VSD High vibration shutdown 99

100 • • • • • L26QT2
Lube oil header temperature high
high-LTTH
100

101 • • • • • L12HFD Protective speed signal trouble 101

102 • • • • • • L12HFD Control speed signal trouble 102

102 • • • • • • • Software "Stop" Button 102

AVR Regulation Changeover from AUTO-1 to AUTO-2

AVR Regulation Changeover from AUTO-2 to AUTO-1


Generator CB D570/D370 tripped ( Trip coil-2 opr.)
Generator CB D570/D370 tripped ( Trip coil-1 opr.)

132kV Breaker A120/A720 86H tripped

132kV Breaker A120/A720 86E tripped


Gas Turbine Shurdown with Unload

132kV Breaker A110/7310 86H tripped

132kV Breaker A110/A710 86E tripped


Trip GCB, Excitation, and Gas Turbine

Promt operator for load management


Reduce Excitation command to AVR
Master Trip Relays 86G3 and 86G4
Master Trip Relays 86G2 and 86G3
Master Trip relays 86U1and 86U2

Release of CO2 into Gt Enclosure

6.6kV MVUAS-3 incomer tripped


Release of CO2 into Generator
Excitor field breaker tripped
Trip GCB and Excitation
Trip GCB and Excitation

Local and Romte Reset

Block Gnerator synch


132kV bus zone trip
Gas Turbine trip
Local Reset Only

Local Reset Only

Alarm/Inication
EFFECT

Class of Shutdown MASTER TRIP RELAYS MAJOR EQUIPMENT TRIPS ALARM/CONTROL EFFECTS

LEGEND FOR Class of Shutdown

A Shut down : Trip GCB, Trip Excitation, GT Running C Shut down : Trip GCB, Trip Excitation, Trip GT via MARK-VI ( GT Shuts down)

Shut down : Unload GT, Trip GCB, Trip Excitation, Trip


B D Shut down : Trip GCB, Trip Excitation, Trip GT via MARK-VI ( GT Shuts down), Trip 132kV Circuit Breaker(s), Trip 6.6kV incomer
GT via MARK-VI ( GT Shuts down)