Professional Documents
Culture Documents
overvoltages
and insulation
coordination in
MV and HV
D. Fulchiron
Their varied and random nature makes More precisely, when an insulation fault Xo = ∞: Sd = 31/2 = 3 ;
them hard to characterise, allowing only occurs on phase A, an earth fault ■ if the neutral is completely earthed,
a statistical approach to their duration, factor, Sd, is defined by the ratio of the Xo = Xd: Sd = 1;
amplitudes and effects. The table in voltage of phases B and C with respect ■ if, as in the general case,
figure 1 presents the main to earth, to network phase to neutral Xo ≤ 3 Xd: Sd ≤ 1.25.
characteristics of these disturbances. voltage.
In point of fact, the main risks are The following equation is used to Overvoltage on a long off-load line
calculate Sd: (Ferranti effect)
malfunctions, destruction of the
equipment and, consequently, lack of An overvoltage may occur when a long
3 (k 2 + k + 1) line is energised at one of its ends and
continuity of service. These effects may Sd =
occur on the installations of both k + 2 not connected at the other. This is due
energy distributors and users.
Disturbances may result in:
■ short disconnections (automatic overvoltage MV-HV over term steepness damping
type voltage of frequency
reclosing on MV public distribution
(cause) coefficient front
networks by overhead lines);
■ long disconnections (intervention for at power frequency ≤ 3 long power low
changing damaged insulators or even (insulation fault) >1s frequency
replacement of equipment). switching 2 to 4 short medium medium
Protective devices limit these risks. (short-circuit 1 ms 1 to 200 kHz
Their use calls for careful drawing up of disconnection)
consistent insulation and protection atmospheric >4 very short very high high
levels. For this, prior understanding of (direct lightning stroke) 1 to 10 µs 1,000 kV/µs
the various types of overvoltages is
vital: such is the purpose of this fig. 1: characteristics of the various overvoltage types.
chapter.
C
power frequency B
A
overvoltages VCT
earth fault VBT
This term includes all overvoltages with
frequencies under 500 Hz. VAT
T
Reminder: the most common network
frequencies are: 50, 60 and 400 Hz.
VB VC
Overvoltage caused by an insulation
N the phase-earth voltage of fault-free
fault (see fig. 2)
phase is raised to the value of the
An overvoltage due to an insulation VA phase-to-phase voltage:
fault occurs on a three-phase network
when the neutral is unearthed or VBT = 3 VBN
impedance-earthed. VCT = 3 VCN
T
In actual fact, when an insulation fault
fig. 2: temporary overvoltage on an unearthed neutral network in presence of an insulation
occurs between a phase and the frame
fault.
or earth (a damaged underground
These e.m.f. variations may generate fig. 4: equivalent circuit for the study of overvoltages caused by inductive current breaking
oscillating currents (see fig. 4) of high where:
frequency in the adjacent capacitances, Cp1: circuit-breaker capacitance,
both stray and voluntary. The amplitude Lp1: circuit-breaker inductance.
of these currents can become non-
negligible with a 50 Hz current and
reach 10 % of its value. current in
circuit-breaker
Superimposition of the 50 Hz current
and of this high frequency current in the
circuit-breaker will result in the current
moving to zero several times around "pinched-off"
the zero of the fundamental wave current
(see fig. 5).
The circuit-breaker, little affected by possible
these low currents, is often capable of extinguishing
breaking at the first current zero
occurring. At this moment, the currents
in the generator and load circuits are
not zero. The instantaneous value, i, of 50 Hz wave
the 50 Hz wave on arc extinguishing is
fig. 5: superimposition of a high frequency oscillating current on a power frequency current.
known as the «pinched-off current».
5 10 15 20 25 30 days
i L di
fig. 8: isokeraunic levels in continental France (graduated in annual mean number of stormy U = R +
days). 2 2 dt
Source: Météorologie Nationale. i
U i/2
U = Zc i/2 likelihood (%)
99.5
225 kV
98
95
U i L
90 400 kV
i/2
i/2 70
750 kV
50 1,100 kV
30
1,500 kV
R
10
3 5 10 20 30 50
lightning stroke strenght (kA)
fig. 10: statistical distribution of the strength fig. 11: when lightning falls on the earth
fig. 9: when lightning strikes directly, the of direct lightning stokes and minimum cable, current evacuation causes an
current wave propagates on either side of arcing strengths as a function of network increase in the potential of the pylon metal
the point of impact. voltage level. frame with respect to earth.
The first electrical networks (Grenoble- reminder will be given of the definitions clearance and voltage
Jarrie 1883) were technologically of clearance and withstand voltage.
extremely rudimentary and at the mercy withstand
of atmospheric conditions such as wind Clearance
and rain: This term covers two notions: «gas
■ wind, by causing inter-conductor
overvoltage overvoltage clearance (air, SF6, etc...) and
clearance gaps to vary, was factor types «creepage distance» of solid insulators
responsible for arcing;
lightning
(see fig. 15):
■ rain encouraged current leaks to
■ gas clearance is the shortest path
earth.
These problems resulted in: between two conductive parts;
■ creepage distance is also the
■ use of insulators;
■ determination of clearances;
shortest path between two conductors,
■ earthing of metal frames of devices. >4 electrostatic but following the outer surface of a solid
insulator (this is known as creepage).
These two clearances are directly
definition 4 related to the concern with overvoltage
The purpose of insulation coordination protection, but do not have identical
is to determine the necessary and withstand.
sufficient insulation characteristics of 2 to 4 switching
the various network components in Voltage withstand
order to obtain uniform withstand to This varies in particular according to
normal voltages and to overvoltages of the type of overvoltage applied
≤ 3 power frequency
(voltage level, rising front, frequency,
various origins (see fig. 14). Its final
objective is to ensure safe, optimised time....).
distribution of electrical power. 1
Moreover, creepage distances may be
By «optimised» is meant finding the subjected to ageing phenomena,
best possible economic balance specific to the insulating material in
between the various parameters fig. 14: various voltage levels present on question, causing deterioration of their
depending on this coordination: MV-HV networks. characteristics.
■ cost of insulation;
■ cost of protective devices;
■ cost of failures (operating loss and
repairs) in view of their probability.
air
The first step towards removing the clearance
detrimental effects of overvoltages is to
confront the phenomena generating
them: a task which is not always
simple. Indeed, although equipment creepage
switching overvoltages can be limited distance
by means of suitable techniques, it is air clearance
impossible to have any effect on
lightning.
It is thus necessary to locate the point
of least withstand through which the
current generated by the overvoltage
will flow, and to equip all the other
network elements with a higher level of
dielectric withstand.
Before presenting the various technical
fig. 15: air clearance and creepage distance.
solutions (methods and equipment), a
.001 .01 .1 1 10 100 1,000 10,000 I fig. 25: example of characteristics of a ZnO
arrester meeting specification EDF
fig. 24: characteristics of two arresters with the same level of protection 550 kV/10 kA peak kV. HN 65S20.
For many years now the International shapes producible in laboratories and acceptable as regards operating safety.
Electrotechnical Commission (IEC) has having shown satisfactory equivalence. Moreover, the gradual replacement of
been concerned with the problem of Moreover, two new concepts are dealt dischargers by arresters enables
HV insulation coordination. with in this standard: reduction of the safety margin which
■ longitudinal insulation (between the had become superfluous between
Insulation coordination is dealt with in
terminals of the same phase of an open arrester protection level and equipment
two main documents:
device); specified insulating voltage.
■ IEC 664 for LV;
■ consideration of altitude and of Determining insulation levels
■ IEC 71 for HV.
IEC 71 is divided into two parts, the installation ageing. The standard does not stipulate
second part forming an exhaustive This draft-standard distinguishes invariable withstand voltages valid in all
application guide. internal insulation, external insulation cases, but enables insulation
«Product» standards, including: and two voltage ranges: coordination studies to be carried out in
■ IEC 694 «common clauses for ■ internal insulation covers everything a number of stages:
equipment»; not in ambient air (for example, liquid ■ definition of relationships between
■ IEC 76 «transformers»; insulation for transformers, SF6 or network type and choice of its
■ IEC 99 «surge arresters»; vacuum for circuit-breakers); insulations.
comply with IEC 71 as regards specific ■ external insulation refers to air The purpose is to establish the
withstand voltages. clearances. characteristics of the maximum
■ range l: from 1 kV to 245 kV inclusive possible permanent voltages and the
■ range ll: above 245 kV. foreseeable temporary overvoltages as
HV insulation coordination a function of:
For each of these, implementation of
as in IEC 71 insulation coordination varies slightly.
■ network structure and its rated
fig. 26: representative overvoltage shapes and tests considered by draft-standard IEC 71.
fig. 28: standardised insulation levels for root mean square voltage networks between 1 and
245 kV (there is a similar table for voltages greater than 245 kV).
fig. 29: example of an insulation coordination study for a 24 kV network, with external insulation equipment (taken and adapted from the draft-
revision of IEC 71).
The high operating voltage involved for energy distributors (invoice losses), ferromagnetic resonance. To prevent
increases the economic importance of industrial consumers (production this, the capacitances must be reduced
this study. losses) and people (safety). by approaching, for example, the
Three criteria justify this statement: In LV transformer energising equipment.
■ increase of number of customers or
In practice, the lower the operating Connection of a load prior to energising
of distributed power; voltage, the more limited the is useful since this load acts as a
■ increase of failure cost (cost of consequences of breakdown in power reducing resistance which can prevent
equipment to be replaced); distribution terms. However resonance.
■ the smaller relative part of the development of electronic equipment Earthing the neutral is also a solution
coordination study in total installation and systems is responsible for a large for phase/earth resonances.
cost. number of incidents further to Overvoltage caused by capacitive
overvoltages. In point of fact, current breaking
breakdown consequences disturbance withstand level is not The solution is to prevent successive
always specified or is not coordinated reignitions by increasing contact
Dielectric failure (breakdown or arcing)
with the level corresponding to its separation speed and using a good
can cause:
installation. dielectric (vacuum or SF6).
■ tripping of the protective devices in
the best possible case; However, these systems play an Overvoltage caused by closing off-
■ destruction of equipment in the worst increasingly large role in the integrity of load lines
possible case; installations, production and This is prevented on transmission
■ interruption of operation each time a management, and the economic networks by progressive energising,
failure occurs. consequences for the company obtained by adding insertion
concerned can be serious. resistances to the circuit-breaker.
In HV, the resulting power failure can
affect an entire town, a region or an Coordination of «withstands» is thus Overvoltage caused by lightning
iron and steel plant, and causes: vital, even in LV... stroke
■ a risk of network destabilisation; .... and the use of arresters should be There are three possibilities:
■ a loss of energy billed for the energy generalised. Today they are highly ■ installation of earth cables to prevent
distributor; recommended for LV consumers direct impulses (see chapter 1);
■ production loss for industrial supplied by overhead lines. ■ installation of protective devices at
consumers; vulnerable points (dischargers or,
■ a risk for people (e.g. in hospitals) reduction of overvoltage preferably, arresters), (see appendix 2);
and for computer data. ■ creation of good quality earth
risks and level connections (see chapter 1).
To avoid such incidents, studies must
Simple solutions to the various
be conducted for each new installation
overvoltages looked at in chapter 1 can
to provide consistent and optimised risk
be considered as from the initial project
protection. of installation.
One solution is to increase installation
Overvoltage due to ferromagnetic
insulation level by increasing resonance
clearances. However, this results in
The only means of removing this
considerable increase in cost: doubling completely is for 1/C ω to be greater
these clearances means multiplying than the slope at the origin of L ω i.
eight times volumes and costs. However, other solutions can be
Oversizing is therefore unacceptable considered, in particular in MV where
in HV, which accounts for the
■ an unbalance between the 3 phases
importance of optimising HV equipment.
can occur in the case of protection by
In MV phase by phase controlled switch. The
The consequences of insulation faults greatest simultaneity possible must be
on MV networks are the same, on a sought on closing the 3 network phases
lesser scale, as those in HV. (omnipole equipment);
The consequences of the resulting ■ closing an off-load transformer may
electricity failures can also be serious be the transient phenomenon causing
Insulation coordination aims at finding rules out the possibility of absolute alongside optimisation of economy and
the right balance between equipment solutions. electrical operating stresses.
reliability from a dielectric standpoint, Although the modellings chosen may Increasing use of arresters, partly due
on the one hand, and their sizing and appear somewhat arbitrary at first sight, to improvement of their characteristics
thus cost, on the other. they have been confirmed by and reliability, contributes to greater
experience. control of protection levels.
The presentation made in this
document shows the complexity of the More detailed information can be found Consideration of this aspect by
in the publications quoted for readers international standard committees, both
parameters involved in such an
wishing to examine the subject in generally and as regards product
analysis.
greater depth. The progress made in recommendations, is proof of the
Moreover, the statistical aspect of knowledge of phenomena now ensures importance of the subject and of its
behaviour to transient overvoltages increased installation reliability associated advantages.
,,,,
,,,,,
earthing circuit.
Example:
■ current wave: 1 kA/ µs;
■ earth down-cable inductance:
1µH/m;
■ hence UL = 1 kV/m.
L
arrester
transformer
fig. 34: arrester cabling principle: load-arrester connections must be as short as possible
transformer.
Standards
■ IEC 60: Hight voltage test techniques.
■ IEC 71-1: Insulation co-ordination:
definition, principles and rules.
■ IEC 71-2: Insulation co-ordination:
application guide.
■ IEC 99: Surge arresters.
Merlin Gerin "Cahier technique"
publications
■ HV industrial network design,
Cahier Technique n° 169
G. THOMASSET
■ Behaviour of the SF6 MV circuit-
breakers Fluarc for switching motor
starting currents,
Cahier Technique n° 143
J. HENNEBERT
Other publications
■ Techniques de l’ingénieur : chapter
on «Gaz Isolants».
■ Les propriétés diélectriques de l’air et
les très hautes tensions.
(EDF Publication).
■ Principles and procedures of the
insulation co-ordination.
KH. WECK.
■ Dimensionnement des parafoudres
MT pour le réseau EDF (1988).
A. ROUSSEAU (EDF).