You are on page 1of 24

n° 151

overvoltages
and insulation
coordination in
MV and HV
D. Fulchiron

Having graduated from the Ecole


Supérieure d’Electricité in 1980, he
joined Merlin Gerin in 1981 working
in the High Power Testing Station
(VOLTA) until 1987.
He then joined the technical
department of the Medium Voltage
Division in which he is currently
project manager. His involvement in
secondary distribution equipment
studies has led him to examine
insulation coordination more
thoroughly.

The author would like to thank:


Florence Bouchet
A student at the Supelec Institute
who, as trainee, helped to produce
this document.
Jean Pasteau
Member of the Technical
Management who provided his
competence as expert contributing
to the revision of standard IEC 71.

E/CT 151, first issued February 1995


Cahier Technique Merlin Gerin n° 151 / p.2
overvoltages and insulation coordination Insulation coordination is a discipline
aiming at achieving the best possible
in MV and HV technico-economic compromise for
protection of persons and equipment
against overvoltages, whether caused
by the network or lightning, occurring
on electrical installations.
It helps ensure a high degree of
availability of electrical power.
contents Its value is doubled by the fact that it
concerns high voltage networks. To
control insulation coordination:
1. Overvoltages Power frequency overvoltages p. 4 ■ the level of the possible overvoltages
Switching overvoltages p. 5 occurring on the network must be
known;
Lightning overvoltages p. 8
■ the right protective devices must be
2. Insulation coordination Definition p. 11
used when necessary;
Clearance and voltage withstand p. 11
■ the correct overvoltage withstand
Withstand voltage p. 12 level must be chosen for the various
Insulation coordination principle p. 13 network components from among the
3. Overvoltage protective devices Dischargers p. 14 insulating voltages satisfying the
Surge arresters p. 14 particular constraints.
4. Standards and insulation HV insulation coordination p. 17 The purpose of this "Cahier Technique"
coordination as in IEC 71 is to further knowledge of voltage
5. Coordination applied to Breakdown consequences p. 20 disturbances, how they can be limited
electrical installation design and the standards to ensure safe,
Reduction of overvoltage p. 20
optimised distribution of electrical
risks and level
power by means of insulation
6. Conclusion p. 21 coordination. It deals mainly with MV
Appendix 1: propagation of overvoltage p. 21 and HV.
Appendix 2: installing a surge arrester Maximum safety clearance p. 22
Cabling the surge arresters p. 22
Appendix 3: electricity standards p. 23
Appendix 4: bibliography p. 24

Cahier Technique Merlin Gerin n° 151 / p.3


1. overvoltages

These are disturbances superimposed cable, earthing of an overhead Xo


on circuit rated voltage. They may conductor by branches, equipment where k =
fault, ...), the phase in question is Xd
occur:
■ between different phases or circuits. placed at earth potential and the Xd is the direct reactance of the
They are said to be differential mode; remaining two phases are then network seen from the fault point, and
■ between live conductors and the subjected, with respect to earth, to the Xo the zero sequence reactance.
frame or earth. They are said to be phase-to-phase voltage Note that:
common mode. U = V 3. ■ if the neutral is completely unearthed,

Their varied and random nature makes More precisely, when an insulation fault Xo = ∞: Sd = 31/2 = 3 ;
them hard to characterise, allowing only occurs on phase A, an earth fault ■ if the neutral is completely earthed,
a statistical approach to their duration, factor, Sd, is defined by the ratio of the Xo = Xd: Sd = 1;
amplitudes and effects. The table in voltage of phases B and C with respect ■ if, as in the general case,
figure 1 presents the main to earth, to network phase to neutral Xo ≤ 3 Xd: Sd ≤ 1.25.
characteristics of these disturbances. voltage.
In point of fact, the main risks are The following equation is used to Overvoltage on a long off-load line
calculate Sd: (Ferranti effect)
malfunctions, destruction of the
equipment and, consequently, lack of An overvoltage may occur when a long
3 (k 2 + k + 1) line is energised at one of its ends and
continuity of service. These effects may Sd =
occur on the installations of both k + 2 not connected at the other. This is due
energy distributors and users.
Disturbances may result in:
■ short disconnections (automatic overvoltage MV-HV over term steepness damping
type voltage of frequency
reclosing on MV public distribution
(cause) coefficient front
networks by overhead lines);
■ long disconnections (intervention for at power frequency ≤ 3 long power low
changing damaged insulators or even (insulation fault) >1s frequency
replacement of equipment). switching 2 to 4 short medium medium
Protective devices limit these risks. (short-circuit 1 ms 1 to 200 kHz
Their use calls for careful drawing up of disconnection)
consistent insulation and protection atmospheric >4 very short very high high
levels. For this, prior understanding of (direct lightning stroke) 1 to 10 µs 1,000 kV/µs
the various types of overvoltages is
vital: such is the purpose of this fig. 1: characteristics of the various overvoltage types.
chapter.
C
power frequency B
A
overvoltages VCT
earth fault VBT
This term includes all overvoltages with
frequencies under 500 Hz. VAT
T
Reminder: the most common network
frequencies are: 50, 60 and 400 Hz.
VB VC
Overvoltage caused by an insulation
N the phase-earth voltage of fault-free
fault (see fig. 2)
phase is raised to the value of the
An overvoltage due to an insulation VA phase-to-phase voltage:
fault occurs on a three-phase network
when the neutral is unearthed or VBT = 3 VBN
impedance-earthed. VCT = 3 VCN
T
In actual fact, when an insulation fault
fig. 2: temporary overvoltage on an unearthed neutral network in presence of an insulation
occurs between a phase and the frame
fault.
or earth (a damaged underground

Cahier Technique Merlin Gerin n° 151 / p.4


to resonance which takes the form of a parallel-connected on C. However, switching overvoltages
voltage wave increasing in linear more generally, the powers involved Sudden changes in electrical network
fashion along the line. are fairly low (1/2 C V2 with low C) and structure give rise to transient
In point of fact, where: only likely to damage fragile equipment. phenomena frequently resulting in the
■ L and C refer to line inductance and It is up to the equipment designer to creation of an overvoltage or of a high
total capacity respectively; evaluate and limit this risk. frequency wave train of aperiodic or
■ Us and Ue are the voltages at the oscillating type with rapid damping.
Notes:
open end and at line entrance, the
Ferromagnetic resonance, depending Normal load switching overvoltage
overvoltage factor equals:
on variable L, may occur for a wide A «normal» load is mainly resistive, i.e. its
Us 1 frequency band. power factor is greater than 0.7. In this
=
LCω
2 A similar demonstration can be made
Ue case, breaking or making of load currents
1 − for parallel resonance. does not present a major problem. The
2 A load connected to the circuit acts as overvoltage factor (transient voltage
This overvoltage factor is around 1.05 a reducing resistance and prevents amplitude/operating voltage ratio) varies
for a 300 km line and 1.16 for a 500 km maintenance of resonance conditions. between 1.2 and 1.5.
line. These values are more or less the
same for HV and EHV lines.
This phenomenon is particularly
common when a long line is suddenly
discharged.
Lωi
Overvoltage by ferromagnetic
L
resonance i
In this case the overvoltage is the result e Cω
of a special resonance which occurs
when a circuit contains both a capacitor
C i
(voluntary or stray) and an inductance
with saturable magnetic circuit (e.g. a
transformer). This resonance occurs e
particularly when an operation (circuit
opening or closing) is performed on the
network with a device having poles
either separate or with non-
simultaneous operation. diagram vectorial representation
The circuit shown in the diagram in
figure 3, with connected in series a
saturable core inductance, L, and the
network capacitance, C, makes it
u
easier to understand the phenomenon.
The following three curves can then be i
Uc =
drawn: Uc = f(i), UL = f(i) and Cω
(UL - 1 / C ω i) = f(i);
■ the first one is a straight sloping line
1 / C ω; U L= L ω i
■ the second one presents a saturation
bend;
■ and the third one displays two
operating points (O and B) for which
i
voltage at the terminals of the -Lωi
LC assembly is zero, and two other Cω
stable operating points, M and P; N is
an unstable point of balance.
The voltages at the terminals E
of L and C (point P) are high. Move e
from M to P may be due only to a M N P
transient temporarily raising voltage e
to a value greater than E.
O B i
These overvoltages (see the diagram in
figure 3) present a risk of dielectric fig. 3: ferromagnetic resonance principle..
breakdown and a danger for any loads

Cahier Technique Merlin Gerin n° 151 / p.5


Overvoltages caused by making and The energy trapped in the circuit varies If C2 is only made up of stray
breaking of small inductive currents according to the type of impedances capacitances with respect to frames,
This type of overvoltage is caused by involved, mainly resistive and inductive. the value of V may present a risk for
three phenomena: Small inductive currents (see fig. 4) equipment insulation (circuit-breaker or
current pinch-off, rearcing and present a load with a high inductance load).
prearcing. which, when the arc is extinguished, The generator circuit has an equivalent
will have an energy given by: behaviour, but its inductance is
The diagram in figure 4 shows a
1 generally much smaller and the
network supplying a load through a L2 I2 . voltages occurring at the terminals of
circuit-breaker. It contains: 2 C1 are thus far lower.
■ a sinusoidal voltage source with an The L2 C2 circuit is now in the slightly
■ rearcing
inductance, L1 and a capacitance, C1, damped, free oscillation state, and the This occurs when the pinching-off
■ a circuit-breaker, D, which cannot be peak value V of the voltage occurring phenomenon described above causes
dissociated from its stray elements, at the terminals of C2 is approximated an input-output overvoltage to occur at
Lp1 and Cp1, by the energy conservation the terminals of the circuit-breaker
■ an inductive load, L2, the distributed hypothesis: unable to be withstood by the latter: an
capacitance of which cannot be 1 1 arc then occurs. This simplified
overlooked, symbolised by a L2 I2 = C2 V 2 .
2 2 explanation is complicated by the
capacitor, C2,
■ finally, a line inductance, L0,
generally negligible.
first parallel oscillation loop
■ current pinch-off L1
The arc occurring on breaking of low D
currents, in particular less than circuit-
breaker rated current, takes up little
space. It undergoes considerable
cooling due to the circuit-breaker’s
C1 C2 L2
capacity to break far higher currents.
Lp1
It thus becomes unstable and its Cp1
voltage may present high relative
variations, whereas its absolute value L0
remains far below network voltage second oscillation
(case of breaking in SF6 or vacuum). loop

These e.m.f. variations may generate fig. 4: equivalent circuit for the study of overvoltages caused by inductive current breaking
oscillating currents (see fig. 4) of high where:
frequency in the adjacent capacitances, Cp1: circuit-breaker capacitance,
both stray and voluntary. The amplitude Lp1: circuit-breaker inductance.
of these currents can become non-
negligible with a 50 Hz current and
reach 10 % of its value. current in
circuit-breaker
Superimposition of the 50 Hz current
and of this high frequency current in the
circuit-breaker will result in the current
moving to zero several times around "pinched-off"
the zero of the fundamental wave current
(see fig. 5).
The circuit-breaker, little affected by possible
these low currents, is often capable of extinguishing
breaking at the first current zero
occurring. At this moment, the currents
in the generator and load circuits are
not zero. The instantaneous value, i, of 50 Hz wave
the 50 Hz wave on arc extinguishing is
fig. 5: superimposition of a high frequency oscillating current on a power frequency current.
known as the «pinched-off current».

Cahier Technique Merlin Gerin n° 151 / p.6


presence of the stray elements oscillation of existing parallel circuits oscillation is mainly centered around
presented above. (surging discharge of stray the 50 Hz wave peak value. The
In actual fact, following current breaking capacitances) and reflections on maximum voltage value observed is
and rearcing, three oscillating impedance failures, and hence in the then around twice the 50 Hz wave peak
phenomena occur simultaneously at appearance of high frequency currents, value.
with respect to 50 Hz, through the arc.
the respective frequencies Fp1, Fp2 and In the case of faster operating devices,
Fm: If device operation is slow compared arcing does not systematically occur
■ in the loop with this phenomenon, the arcing
around the peak value: the overvoltage,
D - Lp1 - Cp1: current may be made to move through
if any, is thus lower.
zero by superimposition of the high
1 frequency current and the incipient If a capacitor bank is put back into
Fp1 = 50 Hz current. operation very soon after it has been
2 π Lp1 Cp1 disconnected from the network, its
Extinguishing of the arc, according to
of around a few MHz. equipment characteristics, will then residual load voltage is between zero
■ in the loop result in a behaviour similar to that and the 50 Hz wave peak voltage.
D - C1 - Lo - C2: described for the phenomena above. Arcing between contacts occurs around
However, since dielectric withstand a peak of opposite polarity (breakdown
1 C1 + C2 between contacts decreases with under a stress twice peak voltage).
Fp2 = closing, the successive overvoltages The oscillation described above occurs
2π Lo C1 C2
decrease right up to complete closing. with a double initial pulse. The
of around 100 to 500 kHz. This phenomenon is extremely maximum voltage value observed may
■ throughout the circuit, complex. The resulting overvoltages then be close to three times the 50 Hz
depend, among other factors, on: peak voltage.
1 L1 + L 2
Fm = ■ circuit-breaker characteristics For safety reasons, capacitor banks are
2π L1 L 2 5 (C1 + C2 ) (dielectric properties, capacity to break always fitted with discharging resistors
high frequency currents, ...), able to eliminate residual voltages with
of around 5 to 20 kHz. ■ characteristic cable impedance, time constants of around one minute.
Multiple rearcing then occurs ■ load circuit natural frequencies. Consequently, an overvoltage factor
(chopping) until it is stopped by Overvoltages, extremely hard to of 3 corresponds to very specific cases.
increasing contact clearance. This calculate, cannot generally be
rearcing is characterised by high ■ energising of off-load lines or cables
predetermined since they involve Slow closing of a device on this type of
frequency wave trains of increasing uncalculable elements which vary from
amplitude. These overvoltage trains load causes, in this case also, arcing
site to site. They also require a
upstream and downstream from the around the 50 Hz peak: the voltage
sophisticated mathematical model of
circuit-breaker can thus present a the arc chute. step applied to one end of the line or
considerable risk for equipment cable will spread and be reflected on
containing windings. Prearcing overvoltages particularly
the open end (see appendix 1).
affect, in HV and MV, off-load
This phenomenon must not be transformers on energising and motors Superimposition of the incident step
confused with «reignition» which is the on starting (see Merlin Gerin "Cahier and the reflected step results in a
reappearance of a power frequency Technique" n° 143). voltage stress twice the applied step,
current wave and thus a breaking give or take the dampings, and
failure on the current wave zero. Overvoltage caused by switching on
capacitive circuits assuming that the 50 Hz can be likened
■ prearcing to DC for these phenomena.
Capacitive circuits are defined as
When a device closes (switch,
circuits made up of capacitor banks,
contactor or circuit-breaker), there is a
and off-load lines.
moment when dielectric withstand L
between contacts is less than applied ■ energising of capacitor banks
voltage. In the case of rapidly closing When capacitor banks are energised,
devices, with respect to 50 Hz, normally without initial load, and in the
behaviour depends on the phase angle case of slow operating devices, arcing e C
during operation. occurs between the contacts around
the 50 Hz wave peak.
An arc is then created between the
contacts, and the circuit witnesses a Damped oscillation of the LC system in
voltage pulse due to the sudden figure 6 then occurs. The frequency of fig. 6: schematic diagram showing a
cancellation of voltage at the device this oscillation is generally far higher capacitor operating circuit.
terminals. This pulse may result in than power frequency, and voltage

Cahier Technique Merlin Gerin n° 151 / p.7


As this type of behaviour is related to Note that the rising front of lightning U then reaches values of several
the distributed inductances and strokes chosen by standards is 1.2 µs million volts, which no line can
capacitances of the conductors for voltage and 8 µs for current. withstand. At a point in the line, for
considered, overhead lines present, in A distinction is often made between: example at the first pylon the wave
addition, a phase-to-phase coupling ■ «direct» lightning strokes striking a meets, voltage increases until
making modelling relatively complex. line; clearance breakdown occurs (insulator
This reflection phenomenon must be ■ «indirect» lightning strokes, falling string). According to whether or not
taken into consideration particularly in next to a line, on a pylon or, which arcing has occurred (depending on the
(EHV) transmission lines, as a result of comes to the same, on the earth cable value of the current injected into the
the small relative difference between (this cable, earthed, connects the tops line), the wave which continues to
operating voltage and insulating of pylons and protects live conductors propagate after the pylon is said to be
voltage. from direct lightning strokes). broken or full.
■ capacitive circuit breaking Direct lightning strokes For various network voltages, arcing
Breaking of capacitive circuits normally This results in the injection of a current does not occur below the critical current
presents few difficulties. In point of fact, wave of several dozens of kA in the line. indicated by the straight line in figure 10.
as capacitances remain charged at the This current wave, which may cause For networks with a voltage less than
50 Hz wave peak value, after the arc is conductors to melt by propa-gating on 400 kV, virtually all direct lightning
extinguished at current zero, voltage is either side of the point of impact (see strokes result in arcing and an earth
resumed at the equipment terminals at fig. 9) results in an increase in voltage U fault.
50 Hz with no transients. However, one given by the formula:
In actual fact, it is estimated that only
alternation after breaking, the device is i 3 % of overvoltages, observed on the
subjected to an input output voltage U = Zc
2 French 20 kV MV public network,
twice peak voltage. where i is the injected current and exceed 70 kV and are thus ascribable
If it is unable to withstand this stress Zc the characteristic line zero sequence to direct lightning strokes. Moreover, as
(e.g. opening not yet sufficient), impedance (300 to 1,000 ohms). a result of attenuation of the voltage
reignition may occur. This is followed,
provided the circuit so allows (single-
phase or connected neutral circuit) by
voltage inversion at capacitor terminals, +5 Vc
raising them to a maximum load of
three times peak voltage (see fig. 7).
The current breaks yet again and a
new reignition may take place with a
value five times peak voltage at the
next alternation.
Such behaviour may result in
considerable escalation and must be
avoided by choosing equipment which
prevents reignition.
20 ms 1/2 T
V U, I
lightning overvoltages Vc
A storm is a natural phenomenon well
known to all, and which is both
spectacular and dangerous.
On average 1,000 storms break out
t
each day throughout the world.
In France, (see fig. 8), they cause each I
year 10 % of fires, the death of
40 people and 20,000 animals and
50,000 electricity or phone cuts.
Overhead networks are those most
affected by lightning overvoltages and breaking
overcurrents.
Lightning strokes are characterised by -3 Vc
their polarisation: they are generally
negative (negative cloud and positive fig. 7: voltage escalation on separation of a capacitor bank from the network by a slow
ground). Roughly 10 % have reversed operating device.
polarity, but these are the most violent.

Cahier Technique Merlin Gerin n° 151 / p.8


wave throughout its propagation along
the line, maximum overvoltages (very
10 rare) at the entrance of a substation or
building are estimated at 150 kV
in MV.
5 20
10 It should be remembered that the
15 highest impulse withstand of 24 kV
5 10
25 equipment is 125 kV.
Indirect lightning strokes
10 When indirect strokes fall on a support
5
or even simply next to a line, high
15 overvoltages are generated in the
10 network.
5 30
Indirect strokes, more frequent than
direct ones, may prove almost as
dangerous.
25 ■ if lightning falls on the pylon or the
10 30 earth cable, the current flowing off
15
causes an increase in metal frame
30 potential with respect to earth
(see fig. 11). The corresponding
overvoltage U may reach several
30 hundreds of kV.
25
i L di
U = R +
20 15 25 25 2 2 dt
25
where R is the earth connection steep
wave resistance and L is the
25 inductance of the pylon and/or the
earthing conductor.

5 10 15 20 25 30 days
i L di
fig. 8: isokeraunic levels in continental France (graduated in annual mean number of stormy U = R +
days). 2 2 dt
Source: Météorologie Nationale. i

U i/2
U = Zc i/2 likelihood (%)
99.5
225 kV
98
95
U i L
90 400 kV
i/2

i/2 70
750 kV
50 1,100 kV

30
1,500 kV
R
10
3 5 10 20 30 50
lightning stroke strenght (kA)

fig. 10: statistical distribution of the strength fig. 11: when lightning falls on the earth
fig. 9: when lightning strikes directly, the of direct lightning stokes and minimum cable, current evacuation causes an
current wave propagates on either side of arcing strengths as a function of network increase in the potential of the pylon metal
the point of impact. voltage level. frame with respect to earth.

Cahier Technique Merlin Gerin n° 151 / p.9


When this voltage reaches the arcing on LV lines, induced overvoltages are For example, in the minutes preceding
voltage of an insulator, an «arcing generally less than 7 kV. a lightning stroke, when a cloud
return» occurs between the metal A statistical observation, retained by charged at a certain potential is placed
structure and one or more of the live the French electrotechnical committee, above a line, this line takes on a
conductors. revealed that 91 % of overvoltages charge of opposite direction (see
In the case of network voltages greater occurring at LV consumers did not diagram in figure 13).
than 150 kV, this arcing return is exceed 4 kV and 98 % did not exceed Before the lightning strikes, thus
unlikely. The quality of pylon earth 6 kV (see fig. 12). This accounts, for discharging the cloud, an electric field,
connections plays an important role. example, for the connection circuit- E, thus exists between the line and the
From 750 kV onwards, there is virtually breaker manufacturing standard which ground which can reach 30 kV/m.
no more risk of arcing return, thus stipulates an impulse withstand of 8 kV. Under the effect of this field, the line/
earth capacitor is charged to a potential
justifying the installation of earth cables Electrostatic overvoltages
of around 150 to 500 kV according to
on EHV lines. Below 90 kV, these Other types of atmospheric discharges
how high the line is from the ground.
cables only provide efficient protection exist. Indeed, although the majority of
if the pylon earth connection is induced overvoltages are Unenergetic breakdown may then
excellent. electromagnetic in origin, some are occur in the least well insulated
electrostatic and concern in particular components of the network.
■ if lightning falls next to the line, the
energy flowing off to the ground causes unearthed networks. When arcing occurs between the cloud
a very fast variation of the and the earth, since the electric field
electromagnetic field. The waves has disappeared, the capacitances
induced on the line are similar in shape number of discharge.
and amplitude to those obtained by overvoltages
direct lightning. They are mainly 30
characterised by their very steep front 25
(around one micro-second) and their 20
very fast damping (whether or not 15 + + +
aperiodic) (typical characteristics of - - -
10
these waves as in standard IEC 60:
5
front time: 1.2 µs and tail time: ≈ 50 µs).
■ when the voltage wave resulting from
a lightning stroke passes through a
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 kV
atmospheric overvoltage
+ + +
MV / LV transformer, transmission levels
mainly occurs by capacitive coupling.
The amplitude of the overvoltage thus fig. 12: statistical distribution of atmospheric
overvoltage amplitude drawn up from two E
transmitted, observed on the secondary
observation campaigns (183 between 1973
winding on the LV side, is less than
and 1974, and 150 in 1975), hence
10 % of its value on the MV side
duplication of curves. fig. 13: origin of an electrostatic overvoltage.
(generally less than 70 kV). Therefore,

Cahier Technique Merlin Gerin n° 151 / p.10


2. insulation coordination

The first electrical networks (Grenoble- reminder will be given of the definitions clearance and voltage
Jarrie 1883) were technologically of clearance and withstand voltage.
extremely rudimentary and at the mercy withstand
of atmospheric conditions such as wind Clearance
and rain: This term covers two notions: «gas
■ wind, by causing inter-conductor
overvoltage overvoltage clearance (air, SF6, etc...) and
clearance gaps to vary, was factor types «creepage distance» of solid insulators
responsible for arcing;
lightning
(see fig. 15):
■ rain encouraged current leaks to
■ gas clearance is the shortest path
earth.
These problems resulted in: between two conductive parts;
■ creepage distance is also the
■ use of insulators;
■ determination of clearances;
shortest path between two conductors,
■ earthing of metal frames of devices. >4 electrostatic but following the outer surface of a solid
insulator (this is known as creepage).
These two clearances are directly
definition 4 related to the concern with overvoltage
The purpose of insulation coordination protection, but do not have identical
is to determine the necessary and withstand.
sufficient insulation characteristics of 2 to 4 switching
the various network components in Voltage withstand
order to obtain uniform withstand to This varies in particular according to
normal voltages and to overvoltages of the type of overvoltage applied
≤ 3 power frequency
(voltage level, rising front, frequency,
various origins (see fig. 14). Its final
objective is to ensure safe, optimised time....).
distribution of electrical power. 1
Moreover, creepage distances may be
By «optimised» is meant finding the subjected to ageing phenomena,
best possible economic balance specific to the insulating material in
between the various parameters fig. 14: various voltage levels present on question, causing deterioration of their
depending on this coordination: MV-HV networks. characteristics.
■ cost of insulation;
■ cost of protective devices;
■ cost of failures (operating loss and
repairs) in view of their probability.
air
The first step towards removing the clearance
detrimental effects of overvoltages is to
confront the phenomena generating
them: a task which is not always
simple. Indeed, although equipment creepage
switching overvoltages can be limited distance
by means of suitable techniques, it is air clearance
impossible to have any effect on
lightning.
It is thus necessary to locate the point
of least withstand through which the
current generated by the overvoltage
will flow, and to equip all the other
network elements with a higher level of
dielectric withstand.
Before presenting the various technical
fig. 15: air clearance and creepage distance.
solutions (methods and equipment), a

Cahier Technique Merlin Gerin n° 151 / p.11


The main influencing factors are: ■ nonlinearity, mentioned above, in the
■ environmental conditions (humidity, clearance/voltage relationship; 50Hz
pollution, UV radiation); ■ dispersion, which means withstand breakdown
■ permanent electrical stresses (local must be expressed in statistical terms; voltage
■ unbalance (withstand varies (peak kV) 2 mm
value of electric field).
Gas clearance withstand also depends according to whether wave polarity is
on pressure: positive or negative); 100
■ variation of air pressure with altitude; ■ passage through a minimum curve SF6
■ variation of device filling pressure. value of the withstand voltage as a 80
function of front time. When the gap
between electrodes increases, this 60
withstand voltage minimum value moves to increasingly air
In gases, insulation withstand voltage is higher front times (see fig. 17). On 40
a highly nonlinear function of clearance. average it is around 250 µs which
For example, in air, a root mean square accounts for the choice of standard test 20
voltage stress of 300 kV/m is voltage rising front (standard tests as in
acceptable under 1 m, but can be IEC 60: application of a wave of front 0
reduced to 200 kV/m between 1 and 1 2 3 4 5 6 7
time 250 µs and half-amplitude time
4 m and to 150 kV/m between 4 and 2,500 µs). absolute pressure (bar)
8 m. It should also be pointed out that fig. 16: SF6 and air breakdown voltage as a
Lightning overvoltage withstand
this clearance is practically unaffected function of absolute pressure.
by rain. In the case of lightning, withstand is
characterised by far greater linearity
This macroscopic behaviour is due to than for the other stress types. withstand voltage U50 (MV)
the lack of uniformity of the electric field
between electrodes of all shapes and Dispersion is present in this case also
not to intrinsic gas characteristics. It with a positive polarity withstand (the 4
would not be observed between flat «+» applied to the most pointed
electrodes of «infinite» size (uniform electrode) inferior to that of negative 3
field). polarity. 13 m
2 7m
Creepage distances of busbar The two following simple formulas 4m
supports, transformer bushings and enable withstand to a 1.2 µs/50 µs
1 2m
insulator strings are determined to positive polarity impulse of an air gap to
1m
obtain a withstand similar to direct air be evaluated for EHV and MV networks:
0
clearance between two end electrodes d 1 10 100 1,000 front
■ U50 =
when they are dry and clean. On the 1.9 time (µs)
other hand, rain and especially wet U50 = voltage for which breakdown locus of minimums
pollution considerably reduce their likelihood is 50 %; fig. 17: line showing minimum withstand
withstand voltage. d values as a function of front time of impulse
■ Uo = applied in positive polarity.
Power frequency withstand 2.1
In normal operating conditions, network Uo = withstand voltage
voltage may present short duration where d is clearance in metres U50
power frequency overvoltages (a U50 and Uo are in MV. kV
fraction of a second to a few hours:
A large number of experimental studies d=8m
depending on network protection and
have made it possible to draw up 4,000
operating mode). Voltage withstand
precise correspondence tables between
checked by the standard one-minute
clearance and withstand voltage, 6m
dielectric tests is normally sufficient. 3,000
taking into account a variety of factors
Determination of this category of
characteristics is simple, and the such as front and tail times,
environmental pollution and insulator 4m
various insulators are easy to compare. 2,000
For example, figure 16 provides a type.
comparison of voltage withstands To give an example, figure 18 shows
the variations in voltage U50 as a 1,000
between air and SF6 as a function of 10 100 1,000 T2 µs.
pressure. function of clearance and tail time T2 for
Switching impulse voltage withstand a positive peak-plane interval. fig. 18: U50 as a function of time T2
Clearances subjected to switching Moreover, table T in figure 19 shows decreasing at half-amplitude.
that withstand voltage does not depend Intervale between the positive peak and the
impulses have the four following main
plane: d = 4 - 6 - 8 m.
properties: on rising front time.

Cahier Technique Merlin Gerin n° 151 / p.12


Tcr 7 22 overvoltage overvoltage types protection level withstand level
(µs) factor
atmospheric
T2 1,400 1,500 overvoltages
(µs) cleared MV equipment
U50 2,304 2,227 electrostatic insulation
>4
(kv)
4
σ 370 217
dischargers
2 to 4 switching surge arresters
fig. 19: influences of time up to the peak on
dielectric withstand of a positive peak-plane power frequency
interval = d = 8 m. ≤ 3
voltage
withstood
1
insulation coordination
principle fig. 20: insulation coordination: correctly protection level and equipment withstand as a function
of probable overvoltages.
Study of insulation coordination of an
electrical installation is thus the environment;
■ As regards lightning, a compromise
definition, based on the possible ■ equipment use. must generally be found between
voltage and overvoltage levels on this insulation level, protection level of
installation, of one or more overvoltage Study of these «conditions» determines
the overvoltage level to which the arresters, if any, and acceptable failure
protection levels. Installation equipment risk.
equipment could be subjected during
and protective devices are thus chosen
use. Choice of the right insulation level Proper control of the protection levels
accordingly (see fig. 20).
will ensure that, at least as far as power provided by surge limiters requires
Protection level is determined by the frequency and switching impulses are thorough knowledge of their
following conditions: concerned, this level will never be characteristics and behaviour: this is
■ installation; overshot. the purpose of the following chapter.

Cahier Technique Merlin Gerin n° 151 / p.13


3. overvoltage protective devices

Dischargers and surge arresters are Moreover, after arcing, ionisation


the devices used to clip and limit high between the electrodes maintains the
amplitude transient overvoltages. They birdproof rod
arc which is then supplied by network
are normally designed so that they can earth electrode phase electrode voltage and may give rise (according
deal with lightning overvoltages. to neutral earthing) to a power
frequency retaining current. This
dischargers 45° 45° current is a full earth fault and requires
intervention of the protective devices
Used in MV and HV, they are placed in
placed at the front of the line (e.g.
particularly exposed network points and
rapid reclosing circuit-breaker or shunt
at the entrance to MV/LV substations.
circuit-breaker).
Their function is to create a weak point
controlled in network insulation so that electrode B Finally, arcing causes the appearance
any arcing will systematically occur just holder of a steep front broken wave which
there. could damage the windings (transfor-
The first and oldest protective device is Ø mers and motors) placed nearby.
the point discharger. It consisted of two Although still used in networks,
points facing each other, known as rigid anchoring dischargers are today increasingly
electrodes, one connected to the chain replaced by surge arresters.
conductor to be protected and the other device for adjusting B and
to the earth. locking the electrode surge arresters
The most common current models use
fig. 21: a MV discharger with birdproof rod Arresters have the advantage of having
the same principle but contain two
e.g.on EDF 24 kV networks, B ≈ 25 mm. no retaining current and of preventing
«horns» to elongate the arc, simplify
restoration of dielectric qualities by
deionising the arcing gap and, in
certain cases, to extinguish the arc. kv point discharger e = 350 mm
In addition, some models are fitted with 900 tests performed in 1.2 / 50 wave
a rod, between these two electrodes, arcing points
designed to prevent untimely «short- 800
circuiting» by birds (see fig. 21) and theoretical voltage curve line:
their electrocution.
700
The gap between the two electrodes
enables adjustment of protection level. before after
600 arcing arcing
Although this device is simple, fairly
efficient and economical, it has many
drawbacks: 500
■ arcing voltage is considerably voltage/time characteristic
dispersed and depends to a large 400
extent on atmospheric conditions:
variations of more than 40 % have 300
been observed;
■ arcing level also depends on
overvoltage amplitude (see fig. 22); 200
■ arcing delay increases as overvoltage
decreases. 100
In these conditions, an impulse voltage
may cause arcing of a device with a
withstand voltage greater than that of 0 0.5 1 1.5 2 2.5 3 3.5 4 µs
the discharger, for the simple reason
fig. 22: behaviour of a point discharger in standard lightning impulse, as a function of peak
that this device has a smaller arcing
value.
delay (e.g. cables).

Cahier Technique Merlin Gerin n° 151 / p.14


the network from being short-circuited ■ its impulse current evacuation Absence of air gap means that ZnO
and then de-energised after arcing. capacity, i.e. its energy dissipation arresters are permanently conductive,
A variety of models have been capacity. Absorption capacity is but under protected network rated
designed: water stream arrester, gas generally given by withstand to voltage, have a very small earth
arrester… Only the most common types rectangular current waves. leakage current (less than 10 mA).
are presented in the paragraphs below. Zinc oxide (ZnO) arresters Their operating principle is very simple,
These arresters are used on HV and Made up only of varistors, they are based on the highly nonlinear
MV networks. increasingly replacing nonlinear characteristic of ZnO varistors.
Nonlinear resistance arresters and resistance arresters and air gap This nonlinearity is such that resistance
air gap protectors protectors (see fig. 23). decreases from 1.5 M Ω to 15 Ω
This arrester type connects in series air
gap protectors and nonlinear
resistances (varistors) able to limit connecting spindle
current on occurrence of a surge.
Once the discharging current wave has
flown off, the arrester is only subjected flange
to network voltage. This voltage (aluminium alloy)
maintains an arc on the air gap
protector, but the corresponding
current, known as the «retaining elastic stirrup
current» flows through the resistance
whose value is now high. It is thus rivet
sufficiently low not to damage the air exhaust pipe and
gap protector and to be cleared when overpressure device
in the upper and ZnO blocks
the current moves to zero for the first
lower flanges
time (the arc is naturally extinguished).
Nonlinearity of resistances maintains a washer
residual voltage which appears at the
terminals of the device, close to arcing
level, since resistance decreases as fault indication
current increases. plate
A variety of techniques have been
used to produce varistor arresters and spacer
air gap protectors. The most classical
kind uses a silicon carbide (SiC)
resistance. thermal shield
exhaust pipe
Some arresters also contain voltage
distribution systems (resistive or porcelain enclosure
capacitive dividers) and arc blowing
systems (magnets or coils for magnetic compression spring
blowing).
This type of arrester is characterised flange
rubber seal
by:
■ its extinction voltage or rated
voltage, which is the highest power
frequency voltage under which the prestressed tightness
device
arrester can be spontaneously de-
energised. It must be greater than the
highest short duration power frequency
overvoltage which could occur on the overpressure device
network; ring clamping
■ its arcing voltages according to wave device
shape (power frequency, switching
fig. 23: example of the structure of a ZnO arrester in a porcelain enclosure for the EDF 20 kV
impulse, lightning impulse....); they are
network.
statistically defined;

Cahier Technique Merlin Gerin n° 151 / p.15


between operating voltage and voltage ■ the protection level, defined arbitrarily fact, humidity is the main cause of
at rated discharging current as the residual voltage of the arrester failure identified on the ZnO arresters.
(see fig. 24). subjected to a given current impulse The outside of these arresters is
The advantage of these arresters is (5, 10 or 20 kA according to class), generally made up of silicon polymer
their increased limitation and reliability 8/20 µs wave; providing environmental resistance and
compared with silicon carbide arresters. ■ rated discharging current; reconstitution of sufficient creepage
■ impulse current withstand. distances. Their internal composition
Improvements have been made in
(this refers to the need for withstand to and silicon enclosures mean that these
recent years, in particular in the thermal
long waves causing considerable arresters can be placed in far more
and electrical stability field of ZnO
energy dissipation and not to the need positions with optimisation of imple-
pellets on ageing.
to flow off such currents in operation). mentation (e.g.: horizontal mounting).
Thus in 1989 only two failures were
observed on 15,000 surge arresters of Enclosure In addition to EDF specifications such
this type installed by EDF after eighteen Zinc oxide arresters are available: as HN 65S20 / IEC 99-1, a variety of
months’ experimentation. No changes ■ in porcelain enclosures for nearly all French standards apply to arresters,
were noted in the characteristics, operating voltages; e.g. the NF C 65-100 for HV installation
checked by tests. ■ in synthetic enclosures (glass fibre devices.
plus resin) for distribution networks.
ZnO arrresters are characterised by In conclusion, these various arrester
(see fig. 25): The second technique, more recent, types are used for protection of
■ their maximum permanent operating has produced arresters which are far equipment, transformers and cables. In
voltage; lighter, less vulnerable to vandalism this case, practically all the arresters
■ their rated voltage which may be linked, and with better live part protection used are zinc oxide ones which are
by analogy with silicon carbide arresters, against humidity since they are gradually replacing horn gaps and
to withstand to temporary overvoltages; completely compound-filled. In point of silicon carbide arresters.
The purpose of this evolution is
increased accuracy of protection levels
peak kV to guarantee insulation coordination to
U a even higher degree.
Readers interested in implementation
600 of arresters can refer to appendix 2.
500
400 ZnO
■ maximum permanent 12.7 kV
300
voltage
200 ■ rated voltage 24 kV
linear ■ residual voltage at rated
discharging current < 75 kV
SiC
100 ■ rated discharging current
(8/20 µs wave) 5 kA
■ impulse current withstand
(4/10 µs wave) 65 kA

.001 .01 .1 1 10 100 1,000 10,000 I fig. 25: example of characteristics of a ZnO
arrester meeting specification EDF
fig. 24: characteristics of two arresters with the same level of protection 550 kV/10 kA peak kV. HN 65S20.

Cahier Technique Merlin Gerin n° 151 / p.16


4. standards and insulation coordination

For many years now the International shapes producible in laboratories and acceptable as regards operating safety.
Electrotechnical Commission (IEC) has having shown satisfactory equivalence. Moreover, the gradual replacement of
been concerned with the problem of Moreover, two new concepts are dealt dischargers by arresters enables
HV insulation coordination. with in this standard: reduction of the safety margin which
■ longitudinal insulation (between the had become superfluous between
Insulation coordination is dealt with in
terminals of the same phase of an open arrester protection level and equipment
two main documents:
device); specified insulating voltage.
■ IEC 664 for LV;
■ consideration of altitude and of Determining insulation levels
■ IEC 71 for HV.
IEC 71 is divided into two parts, the installation ageing. The standard does not stipulate
second part forming an exhaustive This draft-standard distinguishes invariable withstand voltages valid in all
application guide. internal insulation, external insulation cases, but enables insulation
«Product» standards, including: and two voltage ranges: coordination studies to be carried out in
■ IEC 694 «common clauses for ■ internal insulation covers everything a number of stages:
equipment»; not in ambient air (for example, liquid ■ definition of relationships between

■ IEC 76 «transformers»; insulation for transformers, SF6 or network type and choice of its
■ IEC 99 «surge arresters»; vacuum for circuit-breakers); insulations.
comply with IEC 71 as regards specific ■ external insulation refers to air The purpose is to establish the
withstand voltages. clearances. characteristics of the maximum
■ range l: from 1 kV to 245 kV inclusive possible permanent voltages and the
■ range ll: above 245 kV. foreseeable temporary overvoltages as
HV insulation coordination a function of:
For each of these, implementation of
as in IEC 71 insulation coordination varies slightly.
■ network structure and its rated

One of the objectives of this standard voltage,


A table of standardised rated withstand ■ the neutral earthing connection
which should come into force in 93 is to
voltages exists for each range. These diagram,
explain and break down the various tables have been drawn up according ■ the substations and rotating
factors for achievement of withstand to various criteria, and, although mostly machines present on the line,
voltages. This approach encourages empirical up to now, have been ■ the type and position of surge
search for optimisation and even confirmed, with a few reservations, by limitation devices, if any,
reduction in voltage withstand levels. experience. Indeed, it cannot be denied and according to considerations
Standard IEC 71 proposes conventional that the levels laid down, which have common to all overvoltage classes
modelling of actual stresses by wave not been changed for years, are fully defined by the standard (see fig. 26).

overvoltage low frequency transient


class permanent temporary slow front fast front very fast front
shape
Tp T1 Tf
Tt Tt T2 T2 Tt

100 > Tf > 3 ns


shape range f = 50 or 60 Hz 10 < f < 500 Hz 5,000 > Tp > 20 µs 20 > T1 > 0.1 µs 0.3 > f1 > 100 MHz
(frequency, rising front, 30 > f2 > 300 kHz
term) Tt ≥ 3,600 s 3,600 ≥ Tt ≥ 0.03 s 20 ms ≥ T2 300 µs ≥ T2 3 ms ≥ Tt
standardised shape f = 50 or 60 Hz 48 ≤ f ≤ 62 Hz Tp = 250 µs T1 = 1.2 µs (*)
Tt (*) Tt = 60 s T2 = 2,500 µs T2 = 50 µs
standardised (*) short duration switching lightning (*)
withstand test power frequency impulse test impulse test
test
(*) to be specified by the relevant product Committee

fig. 26: representative overvoltage shapes and tests considered by draft-standard IEC 71.

Cahier Technique Merlin Gerin n° 151 / p.17


■ coordination of network insulation For operating voltages under 245 kV, designers is the sizing of external
Once these data have been collected, the power frequency test and the insulations. Whereas use of SF6 for
the corresponding coordination lightning impulse test are the ones insulation and of the vacuum or SF6
withstand voltage must be determined normally chosen. for the breaking gap means that
for each overvoltage class taking into ■ the final choice is made from
internal dielectric withstand is clearly
consideration the required performance standardised levels (see fig. 28) from determined and not dependent on
and, generally, the acceptable all the rated voltages. environmental conditions (climate,
insulation failure rate. The value altitude, degree of moisture,
An example: pollution,....).
obtained is specific to the network
Figure 29 presents a calculation of this
studied and to its situation and is the Rated insulation levels to be retained:
kind taken from the application guide of
lowest withstand voltage to the ■ 50 kV at power frequency meets
the draft-revision of publication IEC 71. rated withstand voltage at low
overvoltage in question that the It shows the insulation coordination
network has to have in its operating frequency permanent overvoltages
study for a substation characterised by (32 kV) and at more than 81 % rated
conditions. the highest voltage for the equipment withstand voltage at slow front
To choose the components of a Um = 24 kV. transients (61 kV by equivalence);
network, their specified withstand This example mainly deals with ■ 125 kV chosen as a technico-
voltages must be defined. external insulation, as the chief problem economic compromise for fast front
Determination of coordination withstand facing installation and network transients, results in:
voltages consists in setting the
minimum values of the insulation
withstand voltages satisfying
■ origin and classification of constraining network analysis (§ 4.02)
performance criterion when insulation is
voltages (§ 3.16)
subjected to the representative ■ protection level of voltage limiting
overvoltages in operating conditions. devices (§ 3.20)
Determination of specified insulation ■ insulation characteristics representative voltages
withstand voltages consists in and overvoltages Urp (§ 3.18)
converting the coordination withstand
voltages into appropriate standardised ■ insulation characteristics
test conditions. This is achieved by ■ performance criterion (§ 3.21) choice of insulation satisfying
■ statistical distribution (+) the performance criterion (§ 4.03)
multiplying the coordination withstand
■ inaccuracy of initial data (+)
voltages by factors compensating the (+) effects combined in a
differences between actual insulation coordination factor Kc (§ 3.24)
operation conditions and standardised coordination withstand
withstand test conditions. voltage Ucw (§ 3.23)

Rated insulation level is chosen by ■ atmospheric correction

selecting the most economical series of factor ka (§ 3.26)


■ all equipment tested (*) application of factors taking into
standardised insulation withstand ■ production dispersion (*) consideration the differences
voltages, sufficient to prove that all the ■ installation quality (*) between standard test conditions
specified withstand voltages are ■ ageing in operation (*) and operating conditions (§ 4.04)
satisfied. ■ other unknown factors (*)
(*) effects combined in a safety
The study chart for final determination factor Ks (§ 3.27)
of rated insulation is shown in figure 27. specified withstand voltage Urw (§ 3.26)
This chart covers the two factors,
altitude and manufacturing dispersion, ■ test conditions (Chapter 5)
defined in the draft-standard, by the ■ test conversion factor Kt (§ 3.29) choice of standardised
term of corrective factor. ■ standardised withstand withstand voltage (§ 4.05 & 4.09)
voltages (§ 4.06 & 4.07)
■ rated withstand voltage or insulation ■ Um ranges (§ 4.08)
level is the same as specified withstand
voltage for overvoltages which can be
tested, i.e.: standardised or rated insulation level: all of Uw (§ 3.32 & 3.33)
■ power frequency test,
■ switching impulse test, fig. 27: organisation chart for determining rated and standardised insulation levels.
■ lightning impulse test. Notes: between brackets, paragraphs of IEC 71 where the term is defined or the action
■ the equivalence factors proposed by
described.
data to be condidered.
standard IEC 71 mean generally that
actions to be performed.
only two withstand voltages need be
results obtained.
specified out of the 3 considered.

Cahier Technique Merlin Gerin n° 151 / p.18


■ either acceptance of a failure rate
greater than that already taken as an highest voltage standardised short standardised withstand
hypothesis, for equipment duration withstand voltage voltages to lightning
■ or addition of arresters to the Um at power frequency impulses
installation to ensure the latter is not kV rms kV rms kV rms
stressed beyond this level. 3.6 10 20/40
For high and extra high voltages, the 7.2 20 40/60
insulation coordination procedure is the 12 28 60/75/95
same, but equipment insulation is
17.5 38 75/95
generally qualified by its switching
impulse and lightning impulse 24 50 95/125/145
withstands. 36 70 145/170
52 95 250
72.5 140 325
123 (185)/230 450/550
145 (185)/230/275 (450)/550/650
170 (230)/275/325 (550)/650/750
245 (275)/(325)/360/395/460 (650)/(750)/850/950/1050

fig. 28: standardised insulation levels for root mean square voltage networks between 1 and
245 kV (there is a similar table for voltages greater than 245 kV).

rated withstand voltage at short duration to lightning


kV power frequency impulses
rated withstand voltage 74 108 141
to lightning impulses
equivalence factor 1.06 1.06
slow front ➔ fast
rated withstand voltage 28 32 42 61
to an overvoltage at short
duration power frequency
equivalence factor 0.6 0.6
slow front ➔ 50 Hz
specified withstand voltage
withstand voltage 28 32 70 102 141
altitude correction 1.13 1.13 1.13
dispersion factor 1.15 1.15 1.05 1.05 1.05
coordination withstand voltage 24 28 59 86 119*
(case of equipment subjected
to atmospheric pressures)
overvoltages in operation
conventional representative short duration 250-2,500 µs impulse 1.2-50 µs impulse
impulse shape 50 Hz power frequency (1 mn) 2 % arcing
conventional representative 24 28 59 86
amplitude (kV) (2.6 p.U.) (3.86 p.U)
overvoltage categories phase / phase to phase / phase to phase / frame and
frame phase frame phase phase to phase
temporary slow front fast front
at power frequency (switching) (lightning)
*: this value comes from the following Calculation example:
criteria: for a slow front coordination withstand voltage of 59 kV
- arrester protection level: 80 kW ■ slow front specified withstand voltage = 59 kV x 1.05 x 1.13 = 70 kV
- arrester/equipment clearance: 8 m ■ equivalent rated withstand voltage at standard short term frequency = 70 kV x 0.6 = 42 kV
- safety factor: 1.05 ■ equivalent rated withstand voltage to lightning impulses = 70 kV x 1.06 = 74 kV.

fig. 29: example of an insulation coordination study for a 24 kV network, with external insulation equipment (taken and adapted from the draft-
revision of IEC 71).

Cahier Technique Merlin Gerin n° 151 / p.19


5. coordination applied to electrical
installation design

The high operating voltage involved for energy distributors (invoice losses), ferromagnetic resonance. To prevent
increases the economic importance of industrial consumers (production this, the capacitances must be reduced
this study. losses) and people (safety). by approaching, for example, the
Three criteria justify this statement: In LV transformer energising equipment.
■ increase of number of customers or
In practice, the lower the operating Connection of a load prior to energising
of distributed power; voltage, the more limited the is useful since this load acts as a
■ increase of failure cost (cost of consequences of breakdown in power reducing resistance which can prevent
equipment to be replaced); distribution terms. However resonance.
■ the smaller relative part of the development of electronic equipment Earthing the neutral is also a solution
coordination study in total installation and systems is responsible for a large for phase/earth resonances.
cost. number of incidents further to Overvoltage caused by capacitive
overvoltages. In point of fact, current breaking
breakdown consequences disturbance withstand level is not The solution is to prevent successive
always specified or is not coordinated reignitions by increasing contact
Dielectric failure (breakdown or arcing)
with the level corresponding to its separation speed and using a good
can cause:
installation. dielectric (vacuum or SF6).
■ tripping of the protective devices in
the best possible case; However, these systems play an Overvoltage caused by closing off-
■ destruction of equipment in the worst increasingly large role in the integrity of load lines
possible case; installations, production and This is prevented on transmission
■ interruption of operation each time a management, and the economic networks by progressive energising,
failure occurs. consequences for the company obtained by adding insertion
concerned can be serious. resistances to the circuit-breaker.
In HV, the resulting power failure can
affect an entire town, a region or an Coordination of «withstands» is thus Overvoltage caused by lightning
iron and steel plant, and causes: vital, even in LV... stroke
■ a risk of network destabilisation; .... and the use of arresters should be There are three possibilities:
■ a loss of energy billed for the energy generalised. Today they are highly ■ installation of earth cables to prevent
distributor; recommended for LV consumers direct impulses (see chapter 1);
■ production loss for industrial supplied by overhead lines. ■ installation of protective devices at
consumers; vulnerable points (dischargers or,
■ a risk for people (e.g. in hospitals) reduction of overvoltage preferably, arresters), (see appendix 2);
and for computer data. ■ creation of good quality earth
risks and level connections (see chapter 1).
To avoid such incidents, studies must
Simple solutions to the various
be conducted for each new installation
overvoltages looked at in chapter 1 can
to provide consistent and optimised risk
be considered as from the initial project
protection. of installation.
One solution is to increase installation
Overvoltage due to ferromagnetic
insulation level by increasing resonance
clearances. However, this results in
The only means of removing this
considerable increase in cost: doubling completely is for 1/C ω to be greater
these clearances means multiplying than the slope at the origin of L ω i.
eight times volumes and costs. However, other solutions can be
Oversizing is therefore unacceptable considered, in particular in MV where
in HV, which accounts for the
■ an unbalance between the 3 phases
importance of optimising HV equipment.
can occur in the case of protection by
In MV phase by phase controlled switch. The
The consequences of insulation faults greatest simultaneity possible must be
on MV networks are the same, on a sought on closing the 3 network phases
lesser scale, as those in HV. (omnipole equipment);
The consequences of the resulting ■ closing an off-load transformer may
electricity failures can also be serious be the transient phenomenon causing

Cahier Technique Merlin Gerin n° 151 / p.20


6. conclusion

Insulation coordination aims at finding rules out the possibility of absolute alongside optimisation of economy and
the right balance between equipment solutions. electrical operating stresses.
reliability from a dielectric standpoint, Although the modellings chosen may Increasing use of arresters, partly due
on the one hand, and their sizing and appear somewhat arbitrary at first sight, to improvement of their characteristics
thus cost, on the other. they have been confirmed by and reliability, contributes to greater
experience. control of protection levels.
The presentation made in this
document shows the complexity of the More detailed information can be found Consideration of this aspect by
in the publications quoted for readers international standard committees, both
parameters involved in such an
wishing to examine the subject in generally and as regards product
analysis.
greater depth. The progress made in recommendations, is proof of the
Moreover, the statistical aspect of knowledge of phenomena now ensures importance of the subject and of its
behaviour to transient overvoltages increased installation reliability associated advantages.

appendix 1: propagation of overvoltage

Whatever the origin of the overvoltage, Propagation speed approaches that of


it will propagate along the line or cable the velocity of light, i.e. approximately
L R
making up the network. 3 x 108 m/s. This speed can also be
This propagation support can be said to be equal to 300 metres per
modelled by using values per length microsecond, thus providing an
unit of inductance and resistance in estimation of the distribution along the
C 1/G
longitudinal and of capacitance and conductor of a very short term wave
conductance in transverse (see fig. 30). front (see fig. 31).
The impedance, in sinusoidal state, is The theory of guided propagation
then given by: makes it possible to establish that,
fig. 30: modelling of a propagation support. when a wave propagating along a
L ω + R
Z =
C ω + G
At the high frequencies generally
associated with overvoltages, the evolution V
in time front: 300 kv/µs
inductive and capacitive terms become
600 kv
preponderant. The impedance known
as "characteristic impedance" then 2 µs
equals:
L
Zc = distribution
t (at constant x)
C V
in space front: 1 kv/m
The resistive and conductive terms
correspond to losses causing wave 600 m
attenuation during its propagation.
The magnitudes of the characteristic
impedances are: x (at constant t)
■ EHV lines: 300 to 500 ohms;
■ HVA lines (overhead); approximately
fig. 31: representation in time and space of a lightning wave.
1,000 ohms,

Cahier Technique Merlin Gerin n° 151 / p.21


conductor arrives at a point of zero transmitted wave and a reflected This case results in a high stress at the
impedance change, partial reflection wave with a factor -1; reflection point and in its vicinity
and transmission are observed. ■ Za = Zc (homogeneous conductor): (vicinity in the space distribution sense
transmission equals 1 and reflection mentioned above).
If Zc is the characteristic impedance of
zero; The expression «doubling of the
the first conductor and Za that of the
■ Za = infinite (line open): voltage at the voltage wave», frequently used, may
second, the transmission and reflection
reflection point is given by the lead to confusion by letting people think
coefficients are given by:
superimposition of the incident wave that the reflected wave is twice as large
T = 2 Za/(Za + Zc) et R = (Za-Zc)/(Za +
and the reflected wave with a as the initial wave. It is only at the
Zc) factor + 1. Its maximum value will then reflection point that the maximum value
The limit values of these coefficients be equal to twice the peak of the observed is twice the value of the
correspond to simple physical cases: incident wave. Although there is no incident wave, since this is the only
■ Za = 0 (line closed at the frame): propagation in the medium Za, the point where the incident wave and the
voltage at the point in question is thus border value is still given by T which reflected wave join their peaks.
zero at all times: this corresponds to a also equals 2.

appendix 2: installing a surge arrester

maximum safety clearance As its conduction level (if approximated Note:


to the protection level) is 75 kV, The coefficient 2 does not mean that
Wave reflection and propagation (see
appendix 1) mean that surge arresters intervention is only possible by the peak voltage is doubled but refers to
only limit overvoltages at their superimposition of the reflected wave superimposition of the incident wave
terminals. on the incident wave. and the reflected wave (see fig. 32).
The reflected wave must have reached
The clipped wave retains the dv/dt of
a value of 75 - 62.5 = 12.5 kV.
its rising front and could develop, by cabling the surge arresters
reflection, at the opening point, a The difference between the incident
A current wave flows off to the earth
voltage twice that of limitation voltage. value (62.5 kV) and the reflected value
when an arrester is used for limitation.
As equipment withstand voltage is (12.5 kV), i.e. 50 kV, corresponds to the
This results from application of the
generally lower than twice the residual wave front distributed on the return
voltage wave to the characteristic line
voltage of the arrester, there is a journey between the arrester and the
impedance:
maximum clearance not to be open point. The return distance is thus
exceeded between the arrester and the no more than 50 m, i.e. a maximum u
line: I = .
substation equipment. protection clearance of 25 m. Zc
Example:
■ lightning wave: 300 kV/ µs;
■ hence a voltage gradient on the line
on passage of the rising front direction of displacement
of 1 kV/m; of the lightning wave
voltage
■ MV substation: impulse withstand of instants... T0 T1
wa wa
125 kV; ve ve
at at
■ surge arrester: residual voltage: T0 T1
2 x U0 = maximum stress reached
75 kV. at T1 ⇒ T1 the most severe instant
The maximum stress at the open point
will be generated by reflection of the Up = arrester protection level
wave peak limited by the arrester. This
stress will have twice the value of this U0 = value of the incident wave
peak. reached on the arrester at T0
In order to keep to the limit of 125 kV of
u = value of the reflected wave
the equipment, the arrester must reached on the arrester at T0
therefore act at the latest when the (U0 + U = Up ⇒ start of conduction)
incident wave in its position d
125 locations: arrester equipment
equals: = 62.5 kV
2
fig. 32: propagation and reflection in the presence of an arrester.
(instant T0 in figure 32).

Cahier Technique Merlin Gerin n° 151 / p.22


A voltage drop, mainly inductive and
which may be high, then occurs in the

,,,,
,,,,,
earthing circuit.
Example:
■ current wave: 1 kA/ µs;
■ earth down-cable inductance:
1µH/m;
■ hence UL = 1 kV/m.


  L

if L < 25 m: a surge limiter placed on the pole is sufficient


if L 25 m: a second limiter must be placed at the transformer terminals
If this voltage is not to be added to
residual voltage, the proposed
equipment must be bypassed at the
arrester terminals as regards the
«lightning phenomenon».
In practice this consists in connecting
as shown in figure 33. If the HV/
equipment link is not made on the
fig. 33: position of surge limiters on a substation supplied by an overhead-underground
network. arrester, conductor length must be as
short as possible (see fig. 34).

arrester

transformer

wrong cabling right cabling

fig. 34: arrester cabling principle: load-arrester connections must be as short as possible
transformer.

appendix 3: electricity standards

There are three levels of standards: ■ the CENELEC (European


The following three organisations act at Electrotechnical Standardisation
international, European and French Committee) produces the «EN»
level respectively: standards and groups 18 countries,
■ the IEC (International mostly European. Application of the
Electrotechnical Commission) produces standards it votes is mandatory.
the «IEC» standards with the ■ the UTE (Union Technique de
participation of 60 countries. Standards l’Electricité) produces the French «NF»
are accepted only if opposition is less standards.
than 20 %. Its application may give rise
to waivers in certain countries.

Cahier Technique Merlin Gerin n° 151 / p.23


appendix 4: bibliography

Standards
■ IEC 60: Hight voltage test techniques.
■ IEC 71-1: Insulation co-ordination:
definition, principles and rules.
■ IEC 71-2: Insulation co-ordination:
application guide.
■ IEC 99: Surge arresters.
Merlin Gerin "Cahier technique"
publications
■ HV industrial network design,
Cahier Technique n° 169
G. THOMASSET
■ Behaviour of the SF6 MV circuit-
breakers Fluarc for switching motor
starting currents,
Cahier Technique n° 143
J. HENNEBERT
Other publications
■ Techniques de l’ingénieur : chapter
on «Gaz Isolants».
■ Les propriétés diélectriques de l’air et
les très hautes tensions.
(EDF Publication).
■ Principles and procedures of the
insulation co-ordination.
KH. WECK.
■ Dimensionnement des parafoudres
MT pour le réseau EDF (1988).
A. ROUSSEAU (EDF).

Réal.: Illustration Technique - Lyon


Cahier Technique Merlin Gerin n° 151 / p.24 DTE - 02-95 - 2500 - Impr.: Clerc

You might also like