You are on page 1of 28

OISD – STD – 173

First Revision Sept 2003

FOR RESTRICTED
CIRCULATION ONLY

FIRE PREVENTION AND PROTECTION SYSTEM


FOR ELECTRICAL INSTALLATIONS

Prepared by:

COMMITTEE ON ELECTRICAL FIRE PROTECTION

OIL INDUSTRY SAFETY DIRECTORATE


7th Floor, ‘New Delhi House’
27-Barakhamba Road
New Delhi 110001

NOTE

1
Oil Industry Safety Directorate(OISD) publications are prepared for use in the oil and
gas industry under Ministry of Petroleum & Natural Gas. These are the property of
Ministry of Petroleum & Natural Gas and shall not be reproduced or copied and loaned
or exhibited to others without written consent from OISD.

Though every effort has been made to assure the accuracy and reliability of the data
contained in these documents, OISD hereby expressly disclaims any liability or
responsibility for loss or damage resulting from their use.

These documents are intended to supplement rather than replace the prevailing
statutory requirements.

2
FOREWORD

The oil industry in India is nearly a 100 years old. Due to various collaboration
agreements with foreign companies, a variety of practices have been in vogue and
various international codes, standards are being followed. Standardisation in design
philosophies and operating and maintenance practices at a national level was hardly in
existence. This lack of uniformity coupled with feedback from some serious accidents
that occurred in the recent past in India and abroad, emphasised the need for the
industry to review the existing state of the art in designing, operating and maintaining oil
and gas installations.

With this in view, the Ministry of Petroleum and Natural Gas in 1986 constituted
a Safety Council assisted by the Oil Industry Safety Directorate (OISD) staffed from
within the industry in formulating and implementing a series of self regulatory measures
aimed at removing obsolescence, standardising and upgrading the existing standards to
ensure safer operations. Accordingly OISD constituted a number of functional
committees comprising of experts nominated from the industry to draw up standards
and guidelines on various subjects.

The first edition of the document on ‘Fire Prevention and Fire Protection System
for Electrical Installations’ was prepared by the Committee on ‘Electrical Fire Protection’
and published in July 1996. The present revised edition has been prepared by
Committee constituted with help of member industries. This document is based on the
accumulated knowledge and experience of industry members, and various national and
international codes and practices.

It is hoped that the provision of this document, if implemented objectively, may


go a long way in improving the safety in the oil and gas industry.

This document will be reviewed periodically for improvements based on the new
experiences and better understanding. Suggestions from industry members may be
addressed to:

The Coordinator
Committee on Electrical Fire Protection
OIL INDUSTRY SAFETY DIRECTORATE
7th Floor, ‘New Delhi House’
27-Barakhamba Road
New Delhi – 110 001

3
COMMITTEE ON ELECTRICAL FIRE PROTECTION

LIST OF MEMBERS

____________________________________________________________________

NAME ORGANISATION
____________________________________________________________________

LEADER

Shri V P Sharma Engineers India Ltd.

MEMBERS

Shri K K Gupta Indian Oil Corporation Ltd.

Shri N V Mani Cochin Refineries Ltd.

Shri G C Dwivedi Gas Authority of India Ltd.

Shri P Kamalasekharan Indian Oil Corporation Ltd.

Shri Niraj Sethi Engineers India Ltd.

MEMBER CO-ORDINATOR

Shri J K Jha Oil Industry Safety Directorate

-----------------------------------------------------------------------------------------------------------------

4
COMMITTEE ON REVISION OF OISD-STD-173

LIST OF MEMBERS

____________________________________________________________________

NAME ORGANISATION
____________________________________________________________________

MEMBERS

Shri R P Singh Bharat Petroleum Corporation Ltd.

Shri K S Mishra Indian Oil Corporation Ltd.

Shri S M Ghotavadekar Hindustan Petroleum Corporation Ltd.

Shri K V Bhaskara Rao Hindustan Petroleum Corporation Ltd.

Shri Niraj Sethi Engineers India Ltd.

Shri H K Sarsar Bongaigaon Refinery & Petrochemicals Ltd.

Shri A K Das Kochi Refineries Ltd.

Shri A P Chakravarty Numaligarh Refinery Ltd.

MEMBER CO-ORDINATOR

Shri C M Sharma Oil Industry Safety Directorate

GUIDANCE

Shri V P Sharma (Leader of 1st Committee) Engineers India Ltd.

Shri Anant Narayan Engineers India Ltd.

-----------------------------------------------------------------------------------------------------------------

5
FIRE PREVENTION AND PROTECTION SYSTEM FOR
ELECTRICAL INSTALLATIONS

CONTENTS

SECTION DESCRIPTION PAGE

1.0 INTRODUCTION 1

2.0 SCOPE 1

3.0 DEFINITIONS 1

4.0 GENERAL REQUIREMENTS 3

5.0 FIRE PROTECTION FOR SUBSTATION 9

6.0 ELECTRICAL GENERATOR INSTALLATIONS 13

7.0 TRANSFORMER INSTALLATION 14

8.0 CABLE INSTALLATION 16

9.0 TEMPORARY INSTALLATIONS 18

10.0 REFERENCES 20

6
FIRE PREVENTION AND PROTECTION SYSTEM
FOR ELECTRICAL INSTALLATIONS

i) CABLE RUN
1.0 INTRODUCTION
A stretch of cable(s) for carrying
Fire protection assumes greater electrical current from one point to the
importance in context of the electrical other.
installations located in hydrocarbon
industry where classified hazardous ii) CABLE TRAY
atmosphere may be encountered and
electricity may constitute one of the A horizontal or vertical metal / FRP
sources of ignition for fire incidents and support for a cable run. A cable tray
explosions. may support one or more cables.

It is therefore imperative that the iii) CABLE RACK


concept of fire prevention / protection is
built into the electrical system right Two or more cable trays arranged one
from the design and engineering stage above the other.
and continued to the operation /
maintenance stage. iv) CABLE TUNNEL/ GALLERY

2.0 SCOPE Any closed section of the structure or


building which primarily serves as a
This document provides the minimum distribution route for cables for
requirements for preventing fire hazard, electrical power and / or the control &
containing and suppression of fire in monitoring of equipment and having
the electrical installations in the walk-through corridors. The Tunnel /
petroleum, oil and gas sector. Gallery could be above ground or
However, this standard does not cover below ground.
off-shore oil installations. It also
excludes drilling rigs and well head v) CABLE TRENCH
installations. Consideration has been
given to the prevalent national and An Underground or below ground
international standards on fire section with RCC / Brick lining which
protection of Electrical Installations. primarily serves as a distribution route
This standard in no way supercedes for cables for electrical power and / or
the statutory rules such as Indian the control and monitoring of
Electricity Rules and Regulations of the equipment. RCC lined trenches are
Chief Electrical Inspectorate, Factory usually provided with removable
Inspectorate, Chief Controller of covers.
Explosives, Directorate General of
Mines Safety, Central Electricity vi) CABLE CELLAR
Authority or other Government bodies.
Fire protection system shall be The space below the substation floor,
designed in accordance with applicable which is utilised for installation of cable
OISD standards as amended time to trays in sub stations with the floor
time. raised above grade level.

vii) CABLE SHAFT AND RISERS


3.0 DEFINITIONS
Vertical ways for carrying cables
For the purpose of this standard, the constructed either of concrete /
following definitions will apply. masonary or fabricated from steel.

7
“Petroleum Class B”: means petroleum
viii) CABLE VAULTS having a flash-point of twenty-three
degrees centigrade and above but
Cable vaults are generally built below a below sixty-five degrees centigrade.
control room wherein cables from
various facilities terminate before
entering the control panels. “Petroleum Class C“: means
petroleum having a flash-point of
ix) ELECTRICAL INSTALLATIONS sixty–five degrees centigrade and
above but below ninety-three degrees
Electrical installations include centigrade.
generating stations, sub-stations, xiv) HAZARDOUS AREA
switch gear rooms, transformers,
cabling systems and outdoor switch In accordance with the Petroleum
yards. Rules applicable to Hydrocarbon
liquids, an area shall be deemed to be
x) FIRE STOP a hazardous area, where:

A through penetration fire stop is a a) Petroleum having flash point


specific construction consisting of below 65 0 C or any flammable gas or
materials that fill the opening around vapour in a concentration capable of
penetrating items, such as cables, ignition is likely to be present
cable trays, Bus Ducts, conduits, ducts
and pipes, and their means of support b) Petroleum or any flammable
through the wall or opening to prevent liquid having flash point above 650C is
the spread of fire. likely to be refined, blended, handled
or stored at or above its flash point.
xi) FIRE BARRIERS
The Petroleum Act, 1934 is applicable
Fire barriers are passive fire protection for Hydrocarbon liquids with Flash
systems which prevent propagation of Point upto 93 Degrees Celsius.
fire through floor penetration or wall
penetrations. xv) VOLTAGE

xii) FIRE BREAKS The difference of electric potential


measured in volts between any two
Fire breaks are passive fire protection conductors or between any part of
systems like chemical coating which either conductor and the earth as
prevent the propagation of fire in measured by a suitable voltmeter and
horizontal or vertical run of cables and is said to be;
prevent spread of fire to nearby
combustibles, e.g. for preventing “Low” where the voltage does not
propagation of fire in long cable runs in exceed 250 volts under normal
the cable galleries, cable trenches and conditions subject, however, to the
cable cellars etc. percentage variation allowed in Indian
Electricity Rules;
xiii) CLASSIFICATION OF
FLAMMABLE LIQUIDS “Medium” where the voltage does
not exceed 650 volts under normal
conditions subject, however, to the
Flammable liquids vary in volatility and percentage variation allowed by Indian
have a flash point below 93 degree C. Electricity Rules;
These are divided into following three
classes as per the Petroleum “High“ where the voltage does not
Act,1934: exceed 33,000 volts under normal
“Petroleum Class A”: means petroleum conditions subject, however, to the
having a flash-point below twenty- percentage variation allowed by Indian
three degrees centigrade. Electricity Rules;

8
“Extra High” where the voltage installed and operated along with
exceeds 33,000 volts under normal switchgear, switch boards and other
conditions subject, however, to the equipment required to generate /
percentage variation allowed by Indian control power.
Electricity Rules.
xxi) SHALL
xvi) INDOOR TRANSFORMER
“Shall’’ indicates a mandatory
The transformer installations which requirement.
have limitations in approach for the
Fire Tender (in other words, which are xxii) SHOULD
not easily accessible by a fire tender)
shall be considered indoors for the ``Should’’ indicates a requirement
purpose of fire protection. which is recommendatory in nature.

xvii) SWITCH GEAR 4.0 GENERAL REQUIREMENTS


Switch gear shall denote circuit i) Electrical installations including
breakers, cut outs and other generating stations, distribution station
apparatus used for the operation, etc. are exposed to considerable fire
regulation and control of circuits. risk since these facilities handle
hydrocarbons as fuels, as well as,
xviii) SWITCH BOARDS mineral oils for transformers which are
highly flammable. Oil and gas
Switch Boards shall mean a Panel handling or bearing equipment,
assembly including the switch gear for storage of fuel oil, piping related to
the control of electrical circuits, fuel oil and gas are risk prone areas.
electrical connections and supporting
frame. ii) All the above fire risks need to be
minimized by taking suitable
xix) SUB – STATION measures for the prevention of fire
and also for protection against fire.
Sub – station means any premises or
enclosures / building or part thereof, iii) Electrical equipment shall be
being large enough to admit the regularly inspected and tested to
entrance of a person after the prevent the chances of fire.
apparatus therein is in position, Precautions to be adopted for fire
containing apparatus for transforming safety of electrical installations should
or converting energy to or from a conform to relevant Indian Standards
voltage, apparatus for distribution or i.e IS : 1646, OISD-STD-137 etc.
any other apparatus for switching,
controlling or otherwise regulating the iv) Periodic tests of electrical
energy, and includes the apparatus equipment shall be carried out as per
therein. IS : 1646 and preventive maintenance
schedule shall be prepared based
a) Large Sub-Station upon the recommendations of
equipment manufacturers.
Sub Station housing High and Medium
Voltage cabling and switchgear. v) Flammable cleaning fluids such as
gasoline, benzene, ether, alcohol etc.
b) Small Sub-Station shall not be used on energized
equipment. These fluids may,
Sub Station having Medium and Low however, be used on de-energized
Voltage cabling and switchgear. equipment. The equipment should be
left in de-energised condition at least
xx) GENERATING STATION half an hour after such cleaning.

Any building or part thereof where


power generating sources are
9
vi) All electrical equipment shall be
kept free of carbon dust, oil deposits, i) Electrical apparatus in general
grease etc. and switching and controlling
apparatus in particular should be
vii) All electrical equipment shall be installed in safe area i.e. non-
effectively earthed in accordance with hazardous area.
requirements of IS : 3043, OISD-RP-
149. ii) While deciding the route of
overhead power lines, necessary
viii) Generating stations shall be consideration shall be given to avoid
kept clean and free from any overhead lines passing through
obstacles at all times. Waste material hazardous areas.
shall not be dumped near storage
areas for oil, gas and other Electrical equipment intended for
combustible material. service in hazardous area shall be
selected in accordance with IS:5571
ix) Naked flame, welding etc. shall and these shall be tested by
not be permitted in storage area or in agencies such as CMRI, ERTL, CPRI
the vicinity of fuel oil tanks. In case it or independent test laboratory of
is unavoidable, prior permission in country of origin for such equipment.
writing, from appropriate authority, Indigenous Flameproof equipment
shall be obtained and due care and shall comply with relevant BIS
protection shall be exercised in line standard as per requirements of
with provisions under OISD-STD- statutory authorities. All hazardous
105 in respect of Work Permit . area equipment shall be approved by
the applicable statutory authority.
4.1 ELECTRICAL EQUIPMENT FOR
HAZARDOUS AREAS For details on hazardous area
classification, enclosure protection
4.1.1 In order to ensure that electrical etc., OISD-STD–113, OISD-RP-149,
equipment does not become a NEC – 1985, IS:5571, 5572, IS:
source of ignition in an oil / gas 13408, Petroleum Rules and Oil
handling installation, it is necessary Mines Regulations shall be referred.
that the equipment is suitably
selected for installation in hazardous 4.2 PLANT EARTHING
areas.
4.2.1 It is recommended that all electrical
4.1.2 Following factors shall be considered equipment be suitably earthed.
for proper selection of electrical Earthing system shall, in general
apparatus and equipment for areas cover the following:
where risks due to flammable gases
or vapours may arise: • Equipment earthing for personnel
safety.
a) Area classification i.e. Zone-0,
Zone-1 or Zone-2 (Refer OISD-STD- • System neutral earthing, and
113 for definitions)
• Protection against Static and
b) Gas group classification i.e. the Lightning discharges.
gas group IIA, IIB or IIC (Refer OISD-
STD-113 for gases covered in the The earthing system shall have an
gas groups) earthing network with required
number of earth electrodes
c) Temperature classification i.e. connected to it. The following shall
T1,T2, T3, T4,T5 or T6 (Refer OISD- be earthed:
RP-147 for temperature ranges)
• System neutral
d) Environmental conditions in
which the apparatus is to be • Current and potential transformer
installed: secondary neutral
10
not require lightning protection with
• Metallic non-current carrying aerial rod and down conductors.
parts of all electrical apparatus such They shall, however, be connected
as transformers, switchgears, to the earthing system, at least, at
motors, lighting / power panels, two points at the base.
terminal boxes, control stations,
lighting fixtures, receptacles etc. OISD-GDN-180 may be referred for
details on lightning protection
• Steel structures, loading
platform etc. 4.3 The resistance values of an earthing
system to the general mass of earth
• Cable trays and racks, lighting should be as below:
mast and poles.
• For the electrical system and
• Storage tanks, spheres, equipment a value that ensures the
vessels, columns and all other operation of the protective device in
process equipment. the electrical circuit but not in excess
of 4 Ohms. However, the generating
• Electrical equipment fencing stations and large sub stations, this
(e.g. transformer, yard etc.) value shall not be more than 1 Ohm.

• Cable shields and armour. • 10 Ohms in the case of all non-


current carrying metallic parts of
• Flexible earth provision for major electric apparatus or any
wagon, truck. metallic object.

• Pump handling Hydrocarbon if • Earthing of Tanks


its base Plate is separate from
motor‘s base plate. a) Every tank or other
receptacle for the storage of
• Turbo driven pump handling petroleum in bulk, other than a well
hydrocarbon head tank or tanks of less than
50,000 litres capacity containing
4.2.2 Plant earthing design shall generally petroleum Class C shall be
be carried out in accordance with electrically connected with the earth
the requirements of Indian Electricity in an efficient manner by not less
Rules and IS : 3043. Following than two separate and distinct
requirements should be met: connections placed at the opposite
extremities of such tank or
• All earth connections should be receptacle. The roof and all metal
visible for inspection to the extent connections of such tank or
possible. receptacle shall be in efficient
electrical contact with the body of
such tank or receptacle.
• Unless adequately connected to
earth elsewhere, all utility and
b) The connections and the
process pipelines should be bonded
contacts required under (a) shall
to a common conductor by means
have as few joints as possible. All
of earth bars or pipe clamps and
joints shall be rivetted, welded or
connected to the earthing system at
bolted and also soldered to ensure
a point where the pipelines enter or
both mechanical and electrical
leave the hazardous area except
soundness.
where conflicting with the
requirements of cathodic protection .
c) The resistance to earth shall not
exceed 7 Ohms and the resistance to
4.2.3 Where installed, lightning protection
any part of the fitting to the earth
shall be provided as per the
plate or to any other part of fitting
requirements of IS:2309. Self
shall not exceed 2 Ohms.
conducting structures having metal
thickness of more than 4.8 mm may
11
• All joints in pipelines, valves, in detail in OISD-STD-110 and same
plants , storage tanks and associated should be referred.
facilities and equipment for petroleum
shall be made electrically continuous 4.4 MINIMISING EQUIPMENT FAILURE
by bonding or otherwise; the
resistance value between each joint 4.4.1 Maintenance
shall not exceed 1 Ohm.
a) Proper functioning of electrical
Pipeline runs / installations having equipment can only be ensured by
cathodic protection shall be means of periodic preventive and
governed by Rule-109 of Indian predictive maintenance of the
Petroleum Rules-2002. equipment. This enhances
equipment life and also ensures
4.3.1 Earth rods and conductors shall be safety of the equipment, installation
designed to cope with the conditions and operating personnel.
imposed. The earth conductor shall
be adequately sized to carry the b) Maintenance may be daily,
applicable maximum earth fault weekly, quarterly or annual
current without undue temperature depending upon the type of
rise. All joints shall be protected equipment. Adequate logs shall be
against corrosion. maintained to ensure that
maintenance is carried out as per
4.3.2 All the electrical equipment operating approved checklists. Preventive
above 250 volts shall have two maintenance should be carried out
separate and distinct connections to as per schedules laid down in OISD-
earth grid. STD-137.

4.3.3 In all cases, connection to earth c) Live parts of switch gear shall
should be made in accordance with be made inaccessible from any
IS : 3043. inadvertent physical contact, lizard
entry etc. These shall be suitably
4.3.4 For further details on earthing covered by barriers and shrouds.
installation practices, refer OISD-RP-
147 and OISD-RP-149. d) It shall be ensured that the
electrical installation shall be rust /
4.3.5 The main earthing network shall be corrosion protected. This should be
used for earthing of equipment to achieved by painting all equipment at
protect it against static electricity. regular intervals by use of zinc
passivated, nickel plated hardware,
An independent earthing network stainless steel hardware, through
shall be provided for lightning provision of canopies for outdoor
protection and this shall be bonded equipment and covering of terminal
with the main earthing network below boxes to prevent ingress of water etc.
ground, minimum at two points. Battery rooms shall be kept dry and
well ventilated and all terminals shall
4.3.6 An approach for removing fire or be kept covered with petroleum jelly
explosion danger is to provide means to avoid corrosion.
for adequate dissipation and
prevention of accumulation of static e) During maintenance if any
electricity, thereby ensuring that equipment is removed from panel
static discharges do not occur. One doors, etc. which leaves an open cut-
of the methods to eliminate risk of out on the equipment, the same shall
static electricity build up is be promptly sealed using blanking
grounding and bonding. plates or other means, to ensure that
there is no loss of the degree of
The subject of Static accumulation ingress protection and also that this
caused by flow of petroleum products does not provide a means of access
and the mitigation methods are dealt for entry of dust / vermin etc. It shall

12
be ensured that all unused cable o) Transformer and switchyards
entries are blanked off. shall be maintained free of vegetation
/ dry grass.
f) All battery banks shall be
routinely checked for healthy cell p) Earth grid resistance shall be
voltage, specific gravity of cells, measured and recorded regularly to
electrolyte level etc. ensure operation of related protective
devices in case of fault. The
g) Insulation resistance of all periodicity and documentation shall
electrical equipment, such as, all be governed by IE-Rule 61 (5&6).
switchboards, motors, transformers,
cables etc. shall be routinely For bulk storage tanks, Rule-128 of
measured and logged to ensure Petroleum Rules 2002 shall be
healthiness of equipment. followed in respect of testing of earth
connections.
h) Dielectric strength of
transformer insulating oil, Oil Circuit Water should be poured in the earth
Breakers etc. shall be measured at pits at regular intervals to maintain
regular intervals and recorded and oil the required earth resistance.
filtration shall be carried out
wherever necessary. Dissolved Gas q) Special emphasis shall be laid
analysis for transformers rated on the maintenance of equipment
5MVA and above may be carried installed in hazardous areas to meet
out as a predictive method to assess requirements of Rules-112 & 113 of
health of transformer. Indian Petroleum Rules-2002. The
rules are quoted for ready reference:
i) All cable terminations, bus-bar
joints, etc. shall be tightened, more Rule-112:
so for equipment subjected to
vibrations, to ensure that there are no “Maintenance of approved electric
hot spots which could lead to fire / apparatus and wiring:
equipment failure.
All electric apparatus and wiring in a
j) Settings of protective relays shall hazardous area shall at all times be so
be checked to ensure that they are maintained as to retain the
set as per the recommended characteristic on which their approval
settings. Protective Relays shall be has been granted”
tested / calibrated once an year to
ensure proper operation as per Rule-113:
manufacturer’s recommendations.
“Repair and test work:
k) Unused cable entries in any
switchboard / Electrical installation 1) No Flame proof or intrinsically
shall not be kept open. safe apparatus shall be opened and
no work likely to impair the safety
l) Conduits used for cable entry characteristics of such apparatus or
shall be sealed and earthed. electric wiring connected thereto
shall be carried out until all voltage
m) All wall openings of an electrical has been cut off from said apparatus
sub station including cable entries or wiring. The voltage shall not be
shall be properly sealed to arrest restored thereto until the work has
water entry inside sub station. been completed and the safety
characteristics provided in connection
n) All switchboards shall be with the apparatus and wiring have
provided with safety interlocks as been fully restored.
covered under OISD-RP-149 and
inspected as per OISD-STD-137. 2) Notwithstanding anything
contained in this rule, use of soldering
apparatus or other means involving
13
flame, fire or heat or use of industrial
type of apparatus in a zone “1” area A system shall be established to
shall be permitted for the purposes of record the results of all inspections
effecting repairs and testing and and the action taken to correct
alterations, provided that the area in defects.
which such apparatus or wiring has
been installed, has first been made 4.5 FIRE ALARM AND GAS
safe and certified by a competent DETECTION SYSTEM
person after testing with an approved
gas – testing apparatus to be safe and 4.5.1 Each installation should be equipped
free from inflammable vapours, gases with a fire detection and alarm system
or liquids and is maintained in such which shall be able to detect fire at
conditions, so long as the work is in the earliest and to give an alarm so
progress” that appropriate action can be taken
(e.g. evacuation of personnel,
No alteration that might invalidate the summoning of fire fighting
certificate or other document relating organisation, triggering of the
to the safety of the apparatus, shall be extinguishing process etc.)
made to any apparatus.
4.5.2 The alarm system may be activated
If replacement components such as by automatic detection devices viz.
cable glands, conduit or conduit smoke detectors, heat detectors etc.
accessories, are available only with or by manual operation of manual call
thread forms which differ from those points i.e. brake glass units.
provided on the apparatus, suitable
adaptors having necessary 4.5.3 Installations involving hazardous
certification and approval shall be gases shall additionally be equipped
employed. with gas detection system which shall
be able to detect the leakage of
Equipment enclosures and fittings hazardous gases and give alarm
shall be examined to see that all when the gas concentration has
stopping plugs and bolts are in reached 20% of lower explosive limit
position and properly tightened. (LEL) and should activate the shut-
Locking and sealing devices shall be down system, as well as give signal
checked to ensure that they are to shut-off valves to prevent further
secured in prescribed manner. release of the hazardous gases in the
concerned areas when 40% LEL has
Replacement fasteners, nuts, studs reached. The tripping should be based
and bolts shall be of the type specified on a logic to prevent any nuisance
by the manufacturer for the particular operation.
apparatus. No attempt shall be made
to replace or repair a glass in a Gas detectors shall be employed in
flameproof enclosure e.g. in a outdoor / indoor process areas
luminaire or other enclosures, except handling hydrocarbons.
by replacement with the complete
assembly or part obtainable from the 4.6 COMMUNICATION SYSTEM
manufacturer, complying with the
approval certificate. The plant shall have adequate
communication system in line with the
If at any time, there is a change in the requirements of OISD-RP-149.
area classification or in the
characteristics of the flammable 4.7 EMERGENCY LIGHTING
material handled in the area or if the
equipment is relocated in the area, the 4.7.1 In addition to the normal lighting, each
area classification drawing should be installation shall be equipped with
correspondingly revised and a check emergency (AC) and critical (DC)
shall be made to ensure that the lighting.
equipment selection corresponds to
the revised area classification.
14
4.7.2 Emergency lighting shall enable the conditions, switching, lightning surges
operators to carry out safe shut-down etc.
of the plant, to gain access and permit
ready identification of fire fighting b) The continuity of operation of
facilities such as fire water pumps, fire those parts of the system not affected
alarm stations etc. by the fault, is maintained.

4.7.3 Critical lighting, sourced from 220V or c) Personnel and plant safety.
110V DC system shall enable safe
evacuation of operating personnel Accordingly, relays and protective
and shall be employed along escape devices shall be suitably selected and
route, assembly point and critical coordinated. Refer OISD-RP-149 for
installations such as first aid centre, further details.
control rooms, manned sub-stations,
fire water pump house etc. 5.0 FIRE PROTECTION FOR SUB-
STATION
4.7.4 As a good engineering practice, the
AC emergency load should be 5.1 Sub-station is a vital Electrical
considered as 20-25% of normal installation which has a number of
lighting load. In small plants, with sources of fire hazards like Cables,
small AC emergency load and where Transformers and Circuit Breakers.
there is no separate standby DG set, Cables are normally PVC/XLPE
critical DC lighting system may take insulated and pose fire hazard in
care of the entire emergency lighting. case of overheating or short circuit.
An Oil filled Transformer contains
4.7.5 For hazardous areas, emergency large quantity of oil and is liable to
lighting fixtures shall be explosion explosion and fire in case electrical
proof Ex(d) type, irrespective of the faults do not clear fast or get
area being classified as zone-1 or sustained. Circuit Breaker and other
zone-2. switchgear items may cause low
intensity fire along with explosion in
4.7.6 For details on lighting philosophy and case of severe earth fault.
installation practices, refer OISD-RP-
147, OISD-RP-149. 5.2 LOCATION OF SUB-STATION
4.8 REQUIREMENTS FOR CONTROL 5.2.1 The sub-station shall be located in a
ROOM / BUILDING safe area as close to the load centre
as possible. Consideration should be
Manned areas such as control rooms, given to cooling tower sprays, vapours
operator rooms etc. and areas contributing to insulation breakdown
housing critical equipment including etc. and other factors affecting the
power supplies required for safe shut safe operation of the sub-station.
down of plants located close to
process units / hydrocarbon storage Refer also OISD standard 118 ‘Layout
areas shall be governed by for Oil and Gas installations’)
provisions in OISD-STD-163.
5.3 LAYOUT OF SUB STATION
4.9 REQUIREMENTS AND EQUIPMENT
PROTECTION Following requirements should be
borne in mind while engineering the
The electrical system shall be layout of a sub-station:
designed and selected to ensure the
following: i) Access for initial installation of the
switchgear, possible removal,
a) Protection of equipment against overhaul or replacement, as well as
damage which can occur due to fire fighting etc.
internal or external short circuits,
overloading, abnormal operating ii) Ease of operation.

15
iii) The location must be considered
in conjunction with possible cable 5.3.6 The design of the floor must take
routes. account of any fixing arrangements
and base channels for switch boards.
iv) It is imperative that any water It is essential to ensure that the holes
tanks or pipes are not positioned or slots for cables are clear of floor
directly above the switchgear. steelwork or reinforcement.

5.3.1 In large plants, the main sub-station 5.3.7 Switch boards should be provided with
floor shall be raised above grade level space heaters of sufficient rating to
and the space below the sub-station prevent condensation. Switchgear
floor (cellar) shall be utilised for located in a high ambient temperature
installation of cable trays. (for example, in a boiler house of the
building) should be adequately
5.3.2 Every sub-station shall have a ventilated in order to avoid excessive
minimum of two exits. These exits cubicle temperature.
shall be located at opposite ends of
the building, to prevent the possibility 5.3.8 Cable trenches inside sub-stations
of operating personnel being trapped shall be filled with sand, pebbles or
in case of fire. Large sub-stations similar non-flammable materials or
shall have three exits. Maximum covered with incombustible slabs. All
distance for a man trapped in fire shall cable entries to the sub-station
not exceed 30 meters to the nearest building should be properly sealed to
fire escape. Panel and equipment prevent entry of any fluids/chemicals
layout shall be so designed that etc. IE-Rule-64-2 (g) shall be referred
personnel can go out from any exit. in the context.
The doors shall open outward and be
equipped with exit signs. 5.3.9 Fire extinguishers, suitable for
electrical fires (CO2 type) and round
5.3.3 The cable cellar level of the sub- bottom fire buckets with clean dry
station floor shall be suitably raised sand, conspicuously marked, should
from adjacent grade level to avoid be kept in easily accessible position
water ingress. The roof shall be given near the switchgear enclosure.
adequate water proofing treatment to
ensure that rain water does not seep 5.3.10 The switchgear rooms should be kept
into the sub-station. clean and tidy and should not be
used as a storage room, especially
5.3.4 In line with provisions under Rule-64- for combustible materials such as
2(e-iv) of Indian Electricity Rules, Dry discarded printer outputs,
Type transformers should be preferred newspapers, cans, rags for cleaning
over Oil filled transformers for indoor etc.
duty. If unavoidable, location and
provisions for indoor transformers 5.3.11 a) Transformers and equipment
shall be governed by relevant clauses installed outdoors, having an
of Rule-64 of Indian Electricity Rules. individual or aggregate oil content of
2000 Litres or more shall be located
Further guidelines on sub-station in a suitably fenced and locked
layout may be referred to OISD-RP- enclosure separated on all sides by
149. at least 6 Metres from any building
including substation. There should be
5.3.5The switchgear layout shall allow no door or window opening in the
sufficient space at front of the surrounding building if transformers
switchgear to withdraw and maneuver are within 6 Metres thereof.
the circuit breaker trolley and at the
rear to allow access for cable b) If the transformers are within 6
terminations, maintenance and Metres of doors and window
inspection of equipment. Indian openings of surrounding buildings
Electricity Rule No.51(c) shall be then they shall be protected by single
referred in the context.
16
fireproof doors and 6 mm thick wired All openings from out door transformer
glass in steel frames respectively. bays into the building shall be sealed
to prevent smoke from entering other
c) Separating walls shall be provided portions of the sub-station.
between transformers having an
individual or aggregate oil content of The requirements under this clause,
2000 Litres if the distance between however, do not apply to dry type
transformers cannot be maintained as transformers or transformers having
6 metres minimum. sulphur hexa fluoride, non-flammable
coolants and having primary voltage
d) Separating walls shall not be not more than 33 kV.
necessary in case of transformers
having an aggregate oil capacity 5.4 TRANSFORMER
exceeding 2000 Litres but individual
oil capacity of less than 5000 litres if It is essential to pay major attention to
the distance between transformers early detection of any abnormality /
and other apparatus is more than 6 fault and to protect the transformer
Metres or if the transformers are from faults/fires so that fault is cleared
protected by an approved type of high before transformer catches fire.
velocity water spray system. Regular monitoring of checks as
specified by manufacturer (such as Oil
e) Where, however, oil capacity of Temperature, Winding Temperature
individual transformer is larger than and calibration / testing of IDMT and
5000 litres, separating walls shall be instantaneous Over current / Earth
provided unless all equipment / Fault protections, Stand by earth fault
buildings / plants are located at a clear protection, Restricted earth fault
distance of not less than the following: protection, Differential protection etc.)
should be followed.
Oil Capacity
of Individual Clear Separating a) OUTDOOR TRANSFORMER
Transformer Distance(Mtrs)
For outdoor transformer, fire fighting
5000-20000 Lit. 8 equipment and fire prevention
arrangement shall be as per Clause
20000-30000 Lit. 15 7.0.

f) The provisions as above shall not It shall be ensured that the discharge
be applicable if the transformer is filled from any pressure relief devices on
with non-combustible insulant liquid. the transformer shall be directed away
from any nearby equipment in order to
5.3.12 Separating walls between sub-station prevent any damage to that
and outdoor transformer bays, if equipment by discharged flaming oil.
required, shall have a four hour fire
rating. In general, a 230 mm thick b) INDOOR TRANSFORMER
reinforced concrete wall or a 355 mm
thick brick wall is considered to Selection of indoor transformer shall
provide adequate fire protection. be guided vide clause 5.3.4.
Separating walls shall be carried right Separating wall for indoor oil
upto the roof level, unless the roof is transformers shall be as per Clause
more than 3 mtrs. above the highest 5.3.12.
point of the equipment, in which case,
the wall shall be carried upto a height 5.5 SWITCHGEAR ROOM
of at least 600 mm above the top of
the equipment (e.g: Transformer a) Smoke detectors of ionization and
conservator) level. The separating optical types in sufficient quantity on
wall shall extend at least 600 mm cross-zoning principle with suitable
beyond the width of the transformer time delay devices incorporated as
and cooling radiators. per guidelines given in IS:2189,

17
should be installed in large and corresponding deluge valve will
substations . open and spray water.

b) Capacitor units containing a 5.7 CABLE CELLAR


flammable dielectric fluid, if located
indoor, should be separated from An effective fire/smoke Detection
adjacent electrical equipment by a one system shall be installed. Alarm /
hour fire barrier. annunciation system shall be
provided in Control Room / Manned
c) Fixed exhaust and ventilation Sub station to facilitate appropriate
systems should be switched off action. Performance / efficacy of
during a hydrocarbon leak. such system shall be checked
periodically. Selection of fire fighting
d) The Battery rooms should be given equipment should be governed by
special attention and the amount of provisions under item 5.8.
hydrogen evolved from the batteries
during charging should be well Additionally, Hydrants at strategic
ventilated to preclude a build-up of locations for fighting fire in major
flammable atmosphere. The entrance emergencies may be installed.
door to a battery room shall have a
NO SMOKING warning sign. Light 5.8 FIRE FIGHTING EQUIPMENT FOR
switches should be located outside MINOR FIRES
the battery room. Lighting fixtures
shall be corrosion resistant and gas 5.8.1 Electrical de-energisation / isolation
tight. of the equipment from the energized
system should be the first step to
5.6 CABLE TUNNEL/ GALLERY fight an electrical fire. Following
should be given attention:
An effective fire / smoke Detection
system shall be installed. Alarm / i) Where energized electrical
annunciation system shall be equipment is involved in a fire, the
provided in Control Room / Manned non-conductivity of the extinguishing
Sub station to facilitate appropriate media is if utmost importance, and
action. Performance / efficacy of only extinguishers expelling dry
such system shall be checked powder, Carbon Di-oxide (without
periodically and documented. metal horn) or vaporizing liquids
Selection of fire fighting equipment should be used. Once the electrical
should be governed by provisions equipment is de-energised,
under item 5.8. extinguishers suitable for the class of
fire risk involved can be used safely.
As an abundant safety measure,
fixed fire extinguishing system with ii) All foams are electrically
deluge facility using water spray may conductive and should not be used
be applied for cable galleries and on fires involving exposed energized
cable tunnels. electrical equipment. After de-
energization, fire extinguishers
The water spray system consists of a should be used depending on class
number of spray nozzles mounted on of fire.
piping network covering the complete
span of cable trays laid horizontally 5.8.2 Annexure B of IS:2190 shall be
and vertically. To avoid total referred for assessment of class of
flooding, cable galleries and tunnels fire / nature of occupancy criteria etc.
may be divided into a number of
zones. Each zone is controlled by Following fire fighting equipment
one deluge valve assembly shall be provided in electrical sub-
connected to detection network. station to fight minor fires:
When fire occurs in a particular zone,
detection unit in that zone will actuate i) Dry Chemical Powder fire
extinguisher (10 Kg. Capacity)
18
iii) The fire fighter does not stand in
To be located inside sub-station. a pool of water.
The number should be determined
based on a maximum travelling ANSI/IEEE Standard 979 may be
distance of 15 meters. At least 1 fire referred for further guidelines on the
extinguisher shall be provided for types of water-spray nozzles.
every 100 m2 area.
5.8.4 Carbon dioxide is ineffective for
ii) CO2 Extinguisher (4.5 Kg. outdoor applications because it is
Capacity) rapidly dispersed by wind.

To be located in sub-stations. The 6.0 ELECTRICAL GENERATOR


number should be determined based INSTALLATIONS
on a maximum travelling distance of
10 meters. At least 1 fire 6.1 A fire in a generating installation
extinguisher shall be provided for would affect the continuity of power
every 100 m2 area. supply along with consequent loss of
production and probable replacement
iii) Sand Buckets of highly valuable equipment. It is
necessary that every effort be made
One in each Transformer Bay. The to reduce the chances of fire.
use of fire buckets shall not be
considered as a substitute for fire One of the prime causes of fire is the
extinguishers. failure of insulation. Other causes
relate to fuel burning equipment, lube
The inspection & maintenance of the oil systems and fuel oil handling /
above fire extinguishers shall be storage systems.
based on the guidelines of OISD-
STD-115. 6.2 Gas Turbo generator (GTG) room
shall be adequately ventilated and
5.8.3 Water should be used with discretion shall be provided with fixed automatic
in areas of electrical equipment. hydrocarbon detector (LEL detectors)
Provision should be made to prevent and alarm system. All cable
inadvertent operation of a water trenches, tunnels and other
suppression system. When water is basement areas on the turbo
used, an adequate drainage system generator building shall also be
should be provided. Before selecting similarly protected.
water for use indoors, it should be
determined if the equipment is water 6.3 a) The fire protection system of
tight. generators should consist of
standard practice of generator
If conditions are such that the manufacturers. This can be realised
equipment cannot be de-energized in most case by CO2 flooding within
and the fire cannot be extinguished the generator enclosure on
by non-conducting agents, water occurrence of a fire. Monitoring of
spray may be used with proper such a fire and CO2 flooding shall be
nozzle selection. Water-spray automatic. If it is not automatic, CO2
nozzles can be used safely and cylinders shall be readily accessible.
effectively on voltages upto 138 KV,
phase to phase with the following Simulation of operation of system
precautions : shall be carried out at regular
intervals.
i) Only spray type nozzles are
used. b) Generators halls should be
provided with automatic fire detection
ii) The minimum distance from the system such as smoke detectors. In
equipment is at least 2 meters. case of generator halls with high
roofs, liner beam type smoke
detectors may be employed.
19
Additionally, manual call points 150-200 lux for control rooms and
(break glass boxes) shall be sub-stations.
employed for fire alarm.
6.8 a) Emergency diesel generator (DG)
c) Fixed fire water spray type sets are normally required to be
protection system shall be used for operated only on failure of the
controlling a fire involving large normal supply. These emergency
quantities of lubricating Oil on DG sets shall be located in well
Turbine generators. This shall consist ventilated rooms and provided with
of two systems of water protection, air exhaust equipment in order to
one for areas below the operating dissipate the heat generated during
floor of the turbo generator and power generation. The day tank for
designed to extinguish pool fires and diesel shall not be located inside the
also providing protection against heat emergency DG room as it is a
generated by three dimensional or potential source of fire and may also
spray fires. The other is a water release flammable vapours. The day
spray system for oil fires at or around tank shall be located outside the DG
the bearing housings. Fixed C02 or room within a fenced area, preferably
dry chemical extinguishing systems with a corrugated sheet roof to
have been found to be inadequate for provide protection from direct sun
basic protection of turbo generator and rain.
because of the likelyhood of re-
ignition and, further, these Emergency Diesel Generator should
extinguishing media may not be be provided with auto cut in system.
sufficient to cope with a long duration
fire. However, in some cases, fixed b) The exhaust from the emergency
dry chemical or C02 systems backed DG shall be conveyed outside the
by water spray systems should be DG room through an exhaust pipe.
provided. The direction of exhaust pipe shall be
so chosen as to help disperse the
6.4 Gas intake to gas turbines shall be exhaust away from the DG room.
through separate pipe-lines with
remote controlled solenoid / motor c) Batteries for starting the DG set
operated valves located in the open shall have containers of non-
area. Additionally, manually corrosive, non-flammable material.
controlled stop valves shall be Batteries shall be located in a well
located near the gas turbines. ventilated location, to prevent the
accumulation of an explosive
6.5 All fuel oil tanks located above mixture.
ground, with a capacity exceeding 45
KL shall be bonded to the ground 7.0 TRANSFORMER
with at least two separate and distinct INSTALLATION
connections on the opposite
extremities of such tank. The roof 7.1 A transformer is the main equipment
and all metal connections of such in the switchyard / sub-station which
tanks shall be bonded to the body of is prone to fire hazards due to the
such tanks. large quantity of oil it contains.
Special attention shall be devoted to
6.6 To prevent the hazard of static safeguard the transformer and other
electricity, the fill and recirculation nearby equipment against fire.
lines to storage tanks shall
discharge below the liquid level. 7.2 SEPARATING WALL
6.7 Adequate illumination shall be Separating walls shall have fire rating
provided at all locations, for effective and specifications as per clause
fire fighting purposes. The minimum 5.3.12. Separating wall shall also be
illumination level shall be 150 lux for designed to withstand the explosion
boiler house, turbine hall etc. and of transformer bushing or lightning
arrestor. Clause no. 5.3.11 shall be
20
referred for provision of separation The whole pit around the transformer
walls / safe inter distance etc. shall be filled with stones of about
40/60 mm granulation except that the
7.3 OIL CONTAINING PIT top 150 mm of the pit shall be devoid
of stones. A layer of stones of this
In order to prevent oil, whether from size extinguishes the burning oil
a small leakage or outflow from penetrating it. A Porosity factor of
transformer tank, from reaching and 40% may be considered for 40/60
polluting the water bearing stratum, mm size gravel.
transformers shall have the following
provisions, depending on the oil CASE – 2
capacity of the transformer.
The oil containing pit shall be similar
7.3.1 Oil Capacity upto 2,000 litres in construction to CASE – 1,
however, it shall be able to contain a
Transformers installed adjacent to quantity of oil corresponding to
sub-station/buildings shall, where oil approximately a third or even less
capacity does not exceed 2,000 than the volume of oil contained in
litres, be provided with a layer of 100 the transformer. In such a case, the
mm deep stones of about 40 mm oil containing pit shall be connected
granulation, all around the to a waste oil tank as per Clause
transformer, for a width of 20% of the 7.3.3.
transformer height or with a minimum
width of about 800 mm. In case oil capacity exceeds 9,000
litres, in any chamber, provision shall
7.3.2 Oil Capacity exceeding 2,000 be made for draining away of any oil,
litres which may escape or leak from the
tanks, to a waste oil tank as per
Transformers installed adjacent to Clause 7.3.3.
sub-station / building shall, where oil
capacity exceeds 2,000 litres of oil in In both the cases, it shall be possible
a chamber, be provided with oil to empty the pit by means of a pump.
containing pits.
If the emptying is automatic, the
The oil containing pit may be shaped emptying system shall be laid out
as illustrated in Figure – 1, where two and controlled in such a way as to
alternative solutions are considered. prevent oil flowing into the general
In both schemes, it is recommended drains of the sub-station. The bottom
that the pit shall extend all around the of the pit shall be constructed of
transformer for a width of 20% of the impermeable concrete.
transformer height, with a minimum
width of about 800 mm. 7.3.3 Waste Oil Tank

CASE – 1 The oil containing pit, when of a


smaller volume than required, say
The oil containing pit shall be able to able to contain a quantity of oil
contain an quantity of oil equal to that corresponding to only a third of the
of the oil contained in the volume of oil contained in a
transformer, plus the volume of water transformer, shall be connected by a
in the fixed fire fighting installation (if draining pipe of earthenware or steel,
any) plus a certain margin for rain not less than 150 mm diameter, to a
water. This margin should be waste oil tank situated in suitable
proportionate to the quantity of rain place. If only one waste oil tank
falling in the region where the sub- collects the drainage of several
station lies and to the frequency of containing pits, the tank should be
the maintenance and emptying situated either in a place central to
operations. the transformers or in the lowest part
of the sub-station to assist drainage.
The tank shall be of sufficient
21
capacity to receive, without Piping for spraying should not be
overflowing, the contents of the carried across the top of the
largest transformer of the sub-station transformer unless no other
plus the water of any fixed fire alternative space is available.
fighting system, and a certain Water spray shall not impinge on
quantity of rain water collected from energized bushing and lightning
all pits. No other drain shall lead to arrestor.
the tank. This tank shall be provided
with an air vent large enough to avoid The system operation shall be
over pressure during operation. The automatic unless :
vent shall be provided with a flame
arrestor. The whole internal surface • Automatic operation presents a
shall be impermeable. (Refer hazard.
Figure:2).
• System is attended by trained
7.4 FIRE PROTECTION personnel round the clock.

The first para of Clause 5.4 on fire Foregoing clauses 5.8.1 and 5.8.3
prevention rather than fire fighting should be kept in mind while
should be recapitulated . adopting water as a medium of
fighting electrical fire.
7.4.1 Fixed fire extinguishing systems for
oil filled transformers shall be ii) Nitrogen Purging
provided if any one of the following
conditions exists: Nitrogen injection system offers a
fast fire prevention and
a) Neither separating walls having extinguishing system for oil filled
fire rating and specs as per 5.3.12 transformers. Pressure relief valve
are erected in line with criteria under operation due to internal faults
clause 5.3.11 nor the inter distance activates the system and nitrogen is
criteria under same clause is met. injected from the bottom area of the
tank, which brings down the oil
b) The transformers of the sub- temperature, as well as, provides an
station/ switch station are located in inert nitrogen layer on top of the hot
the basement of the building. oil to prevent any contact of oil with
oxygen. Such system may be
7.4.2 In case, fixed fire extinguishing considered in areas where
systems are to be installed, they availability of water is limited or
may consist of the following: there is probability of water freezing.
Alternately, use of dry type
i) Water Spray (Mulsifyre) transformers may also be
System considered for such areas.

Such a system shall be provided Use of Nitrogen Purging is optional.


with automatic high velocity water Necessary techno- economic study
spray system (Mulsifyre System) or is to be done by the user before
foam water spray. going for the system.

Complete impingement on all 8.0 CABLE INSTALLATION


exterior surface (except bottom
surface) shall be done with a rate 8.1 Electrical cables are usually
not less than 12.5 ltr./min/sq. meter. sheathed with polyvinyl chloride
Any space of width greater than 300 (PVC) which contributes to the rapid
mm shall have separate spread of fire. PVC also gives off
arrangement for spray of water. highly toxic products out of
Separate arrangement of water combustion including corrosive
spraying shall be considered for gases, when it is exposed to intense
conservator. heat or is involved in fire. Dense
smoke from the cable fires hinders
22
fire fighting efforts and the approach as paper, plastic, rags, wood
to the source of fire. shavings etc. accumulate within the
trench prior to backfilling. H.V. and
The concept of fire protection of M.V cables should be segregated
cables, cable trenches, tunnels and by a 300 mm gap and a layer of
galleries is based on the following bricks laid between the two.
considerations:
8.3.2 Cables Laid In Trenches
a) Preventing / delaying fire
damage to the cables to preserve a) Where cables are laid in lined
their functioning and increasing trenches, the trenches shall be with
their resistance to fire/heat. covers of fire retardant material.

b) Preventing / retarding flame b) Lined Cable trenches located in


propagation through cable runs. hazardous areas, shall be filled with
sand.
c) Segregating cable runs into
compartments with a view to c) Cables laid in lined trenches in
localising a possible cable fire and safe (non-hazardous) areas should
its spread. be run on cable rack/trays
supported from the walls of the
d) Providing effective fire detection cable trench. The cable trays/racks
and alarm system shall be suitably spaced to ensure
that a fire in one tier will not
e) Providing effective fire propagate to another tier. Minimum
extinguishing system. distance between tiers shall not be
less than 225 mm. Cables may also
f) Avoiding cable joints in Over be laid in lined trenches using the
Head cable Racks and Trenches in methodology as applicable for direct
hazardous areas and, burial.

g) Avoiding cable runs in close 8.3.3 Cables laid in Tunnels / Galleries /


proximity to drains carrying Steam / Cellars
Hydro carbons at high temperature.
a) Measures shall be taken to keep
8.2 To minimize spreading of fire due to the tunnels well ventilated. Cable
cables, the outer PVC sheath of tunnel floors shall be provided with a
cables used in Oil industry shall slope leading to a sump with a sump
have a minimum Oxygen Index of pump. The tunnels shall be kept
29. dewatered at all times. Fire fighting
equipment and hydrants shall be
For plants having sub station with located at the entrances of tunnels.
trenches (without cellar) and major
under ground cable runs, minimum b) Compartmentalisation of cable
Oxygen index requirement, as tunnel should be done by provision
above, is not essential. of separating walls at an interval not
more than 30 meters and by sealing
8.3 For various types of cable laying the opening with the use of fire stop
methods employed, the following / fire barriers.
precautions are recommended from
fire safety point of view: c) All cable tunnels, cellars etc.
shall be provided with adequate
8.3.1 Directly Buried Cables number of fire escapes, evenly
distributed, so that maximum
Where cables are directly buried in distance for a man trapped in fire
the ground after excavation of soil does not exceed 30 meters to the
and then backfilled with sand and nearest fire escape.
soil, care shall be taken to ensure
that no combustible materials such
23
d) Inter-compartment movement sheet of adequate thickness shall be
should be through fire check doors. provided for protection of cables.

e) Fire detection and alarm system d) Special attention, such as the


shall be provided in the cable installation of fire stops or fire
tunnels, cellars. breaks, shall be given to vertical
cable runs, since they propagate fire
f) Emergency lighting shall be more rapidly as compared to
provided inside the cable cellars and horizontal runs.
cable tunnels.
8.3.5 Fire Prevention in above ground
g) The fire rating of fire stop when installation
tested according to IS : 12458 and
of barrier wall when tested a) Above ground cable installations
according to IS : 3809 shall not be where proper separation can not
less than the rating of the building be achieved, a fire resistant barrier
components. or shield shall be deployed between
the trays or a passive fire-retardant
h) No welding or naked flame coating may be applied to the
should be allowed inside cable cables. Fire hazards can also be
tunnels and cellars. Same, if minimized by installing fire breaks.
unavoidable, shall be carried out Fire resistance criteria shall be in
with proper work permit and line with IS-12459.
precautions meeting norms under
OISD-STD-105 and OISD-STD-137. b) Consideration should be given to
the application of passive fire
i) Fire stops should be deployed at coating for the following areas:
the locations where the trenches
enter the sub-station. Entry of i) Immediately after end
cables to the blast resistant control termination or joints upto a length
room buildings shall be through fire not less than one meter in either
resistant multi cable transits direction.
(MCTs).
ii) Crossing or T-crossings upto a
8.3.4 Cables Laid On Overhead Cable length not less than one meter in
Trays either direction.

a) Cables laid on cable trays iii) Cable passing through high


supported on pipe sleepers etc. temperature area, entire length.
shall be at least 300 mm above
grade level. The space below the iv) Exposed vertical length, entire
cable trays shall be kept free of dry length.
grass/vegetation.
9.0 TEMPORARY
b) Cable trays installed on elevated INSTALLATIONS
pipe racks, especially if carrying
hydrocarbons, shall be provided 9.1 Temporary electrical supply is
with GI sheet, of adequate generally required for installations
thickness, to protect the cables in erected for short periods of time
case of a fire in the pipe ranging from a few hours to a few
rack/equipment located below the months. Temporary supply
cable trays. installations need extreme care to
avoid any hazard from electrical
c) Cable trays should not be shock by exposure to live wires or
installed at an elevation where fire due to short circuiting. Such
acid/hydro-carbon piping is located installations are exposed to
above the cable tray. For cables environmental hazards also. It is,
running directly below the Air fin therefore, necessary to take extra
coolers/ Acid/ alkali Pipelines, GI precautions for such installations to
24
ensure safety of personnel and avoided. The height of the main
equipment. switch shall not exceed 1.5 m

9.2 Temporary installations are 9.5 The outgoing shall be double or


considered as electrical installations triple pole switches with
open to sky or partially covered and fuses/MCBs. Rewirable type fuse
intended to be used for periods not should not be used. Copper wire
exceeding 6 months or during Plant shall not be used as a replacement
Turn Around. of fuse in fuse carriers . HRC fuses
of proper rating shall be used.
9.3 Such installations may be exposed Loads in a 3 phase circuit should
to the following environmental be balanced and load on neutral
conditions: should not exceed 20% of load in
the phases at the point of supply.
• Water splashes/jets of water from
any direction 9.6 An independent earthing facility
• Partial or total covering by water should preferably be established
• Dust/ Dirt within the temporary installation
• Vibrations premises. All appliances and
• Impact equipment shall be adequately
• Ingress of insects,rodents, birds, earthed. In case of armoured
vermin etc. cables, armour shall be bonded to
• Exposure of solar radiation the earthing arrangement of power
supply source.
• Exposure of lightning strokes
In case of local earthing, earth
Apart from the above, fire risk may
electrodes shall be buried near the
be enhanced in such temporary
supply point and earth continuity
installations due to the nature of
wire shall be connected to local
construction material and, in some
earth electrode/ plate and further
cases, due to storage of
distributed to various appliances.
combustible material.
9.7 Earth should not be used as Neutral
9.4 Each installation shall have a main
of an Electrical installation.
switch with a protective device,
installed in an enclosure adjacent to
9.8 Unless unavoidable, Taped joints
the metering point. The enclosure
shall be avoided and proper
housing the main switch and other
Industrial Type extension cord shall
distribution equipment shall not be
be used for joining of cables in
affected by conditions specified in
Construction power installation and
Clause 9.3.
temporary electrical installations. If
unavoidable, taped joints shall not
The room housing the main
be employed at heights less than
switches shall be well ventilated with
3 Mtrs. Such joints shall be
an adequate clearances and
clamped at either side to avoid any
operational space around.
strain.
9.4.1 The main switch shall be connected
9.9 The installation shall be adequately
to the point of supply by means of
protected against overload, short
an armoured cable adequately
circuit and earth leakage by the use
protected from rain water. Cables
of suitable protective devices. In
shall be laid underground covered
construction sites, protection of
with sand, brick and earth for
personnel against indirect contact
ensuring mechanical protection.
shall be assured by automatic
disconnection of supply by means of
When laid above ground, cables
residual current devices having
shall be properly cleated or
sensitivity not exceeding 30 mA
supported on rigid poles at least 2m
with instantaneous tripping.
high. Crossing of roads shall be
Healthiness of the RCCB/ELCB
25
shall be checked before b) OISD-110: Recommended
commencement of work everytime. Practices on Static Electricity.

9.10 All temporary installations shall be c) OISD-113: Classification of Area


tested before connection of supply for Electrical Installations at
to ensure suitability of protection Hydrocarbon handling Facilities.
system, adequacy of feeders,
cables etc., to check the loads in d) OISD-115: Guidelines on Fire
various circuits and sub-circuits, Fighting Equipment and Appliances
ensure proper earthing and bonding in Petroleum Industry.
etc.
e) OISD-116: Fire Protection
9.11 Temporary installation shall not be Facilities for Petroleum Refineries
employed in hazardous areas. and Oil/Gas Processing Plants.
However, adequate provisions shall
be made in the permanent electrical f) OISD-118: Layouts for Oil and
installation to cater to the Gas installations
requirements of temporary loads,
such as those requiring electrical g) OISD-137 : Inspection of
power during plant shut-down etc. Electrical Equipment

Adequate number of flameproof 240 h) OISD-147 : Inspection and Safe


V AC plug-sockets, flameproof Practices during electrical
portable hand lamps for illumination installation.
of interior of vessels / equipment,
during maintenance shall be i) OISD-149 : Design Aspects for
provided as a part of the permanent Safety in Electrical System.
electrical installation. As a good
engineering practice, these facilities j) OISD-163: Process Control
shall be accessible with a flexible Room Safety.
cable of 50 Mtrs. length. Flexible
cables used for construction power k) OISD-180: Lightning Protection.
installations shall be doubly
sheathed and fine wire armoured. (II) Latest BIS (Bureau of
Indian Standards) Publications :
415 V, TPN, 63A, flameproof
welding receptacles, outlets for IS-1646 : Code of Practice for fire
hydro-jetting/ Stress Relieving safety of buildings (General)
machines etc. shall be provided in Electrical Installations.
the plant area at regular intervals to
take care of maintenance IS-2148: Flameproof enclosure for
requirements during plant shut electrical apparatus.
down.
IS-2189: BIS guidelines for Smoke
10.0 REFERENCES Detection.

The following codes, standards and IS- 2190 : Code of Practice for
publications have either been Selection, Installation &
referred to or used in the preparation Maintenance of Portable First Aid
of this document and the latest Fire appliances.
editions of the same shall be read in
conjunction with this document: IS-2309: Protection of buildings
and allied structures against
(I) OISD Standards / Recommended lightning.
Practices (as per latest
amendments) such as: IS-3034: Code of Practice for Fire
Safety of Industrial Buildings:
a) OISD-105: Work Petmit System Electrical Generating and
Distributing Station
26
(III) NEC-1985
IS-3043: Code of Practice for
Earthing. (IV) INDIAN ELECTRICITY ACT &
RULES, 1956 as per latest
IS:3809: BIS Standard for testing of amendments.
Fire Rating for Barrier Wall.
(V) THE PETROLEUM RULES-
IS-5571: Guide for selection of 2002 with latest amendments.
electrical equipment for hazardous
areas. (VI) IEC 331: Fire resisting
characteristics of electrical cables.
IS-5572:Classification of Hazardous
areas (other than Mines) for (VII) ANSI/IEEE STD-979: GUIDE
electrical installations. FOR SUB-STATION FIRE
PROTECTION.
IS-10028: (Part 1,2,3) Code of
practice for selection, installation (VIII) NFPA-850
and maintenance of Transformer.
“Recommended Practice for Fire
IS-10810: Methods of tests for Protection for Electric Generating
Cables. Plants and High Voltage Direct
Current Converter Station.
IS-12458: BIS Standard for testing
of Fire Rating. (IX) Oil Mines Regulation

IS-12459: Code of practice for fire


safety in cable runs.

IS-13408: Code of Practice for the


selection, installation and
maintenance of electrical apparatus
for use in potentially explosive
atmosphere (other than mining
applications or explosives
processing and manufacture).

27
28

You might also like