Professional Documents
Culture Documents
Basic principles
The transformer is based on two principles: firstly, that an electric current
can produce a magnetic field (electromagnetism), and, secondly that a changing
magnetic field within a coil of wire induces a voltage across the ends of the coil
(electromagnetic induction). Changing the current in the primary coil changes the
magnetic flux that is developed. The changing magnetic flux induces a voltage in
the secondary coil.
1. Instrument transformer
3. Leakage transformer
4. Auto transformer
5. Audio transformer
6. Resonant transformer
Types of transformer
1. Instrument transformer:
Instrument transformers are used for measuring voltage and current in
electrical power systems, and for power system protection and control. Where a
voltage or current is too large to be conveniently used by an instrument, it can be
scaled down to a standardized, low value. Instrument transformers isolate
measurement, protection and control circuitry from the high currents or voltages
present on the circuits being measured or controlled.
3. Auto transformer:
An autotransformer has a single winding with two end terminals, and one
or more terminals at intermediate tap points. The primary voltage is applied across
two of the terminals, and the secondary voltage taken from two terminals, almost
always having one terminal in common with the primary voltage. The primary and
secondary circuits therefore have a number of windings turns in common.[43]
Since the volts-per-turn is the same in both windings, each develops a voltage in
proportion to its number of turns.
5. Resonant transformer:
A resonant transformer is a kind of leakage transformer. It uses the
leakage inductance of its secondary windings in combination with external
capacitors, to create one or more resonant circuits. Resonant transformers such as
the Tesla coil can generate very high voltages, and are able to provide much
higher current than electrostatic high-voltage generation machines such as the
Van de Graaff generator.[49] One of the applications of the resonant transformer is
for the CCFL inverter. Another application of the resonant transformer is to couple
between stages of a superheterodyne receiver, where the selectivity of the
receiver is provided by tuned transformers in the intermediate-frequency
amplifiers.[50]
7. Audio transformer:
Audio transformers are those specifically designed for use in audio
circuits. They can be used to block radio frequency interference or the DC
component of an audio signal, to split or combine audio signals, or to provide
impedance matching between high and low impedance circuits, such as between
a high impedance tube (valve) amplifier output and a low impedance loudspeaker,
or between a high impedance instrument output and the low impedance input of a
mixing console.Such transformers were originally designed to connect different
telephone systems to one another while keeping their respective power supplies
isolated, and are still commonly used to interconnect professional audio systems
or system components.
2. Polarity test
3. Load test
2. Polarity Test:
This is needed for identifying the primary and secondary phasor
polarities. It is a must for poly phase connections. Both a.c. and d.c methods can
be used for detecting the polarities of the induced emfs. The dot method discussed
earlier is used to indicate the polarities. The transformer is connected to a low
voltage a.c. source with the connections made as shown in the fig. 18(a). A supply
voltage Vs is applied to the primary and the readings of the voltmeters V1, V2 and
V3 are noted. V1: V2 gives the turns ratio. If V3 reads V1−V2 then assumed dot
locations are correct (for the connection shown). The beginning and end of the
primary and secondary may then be marked by A1 −A2 and a1 −a2 respectively. If
the voltage rises from A1 to A2 in the primary, at any instant it does so from a1 to
a2 in the secondary. If more secondary terminals are present due to taps taken
from the windings they can be labeled as a3, a4, a5, a6. It is the voltage rising
from smaller number towards larger ones in each winding. The same thing holds
well if more secondaries are present.
The D.C. method of testing the polarity. When the switch S is closed if the
secondary voltage shows a positive reading, with a moving coil meter, the
assumed polarity is correct. If the meter kicks back the assumed polarity is wrong.
3. Load Test:
Load Test helps to determine the total loss that takes place, when the
transformer is loaded. Unlike the tests described previously, in the present case
nominal voltage is applied across the primary and rated current is drown from the
secondary. Load test is used mainly
1. to determine the rated load of the machine and the temperature rise
Pc= I2s R1 = Ws
R'1 = Ws/I2s
Z'1 = Vs/Is
Function of substation:
The main functions of sub-station are to receive energy transmitted at high voltage
from the generating station, reduce to a value appropriate for local distribution and
provide facilities for switching.
Grid
A heavy, rigid electrical conductor (usually uninsulated copper or aluminum) which
serves as an interconnection between power-handling devices (such as switches
and circuit breakers) or as a common connection between several circuits.
Transmission line
A transmission line is the material medium or structure that forms all or part of a
path from one place to another for directing the transmission of energy, such as
electromagnetic waves or acoustic waves, as well as electric power transmission.
Types of transmission line include wires, coaxial cables, dielectric slabs, strip lines,
optical fibers, electric power lines, and waveguides.
Long transmission line:- its length is more than 150km.and line voltage is very
high >20kv<100kv.capacitance effect are taken into account.
Underground transmission
Electric power can also be transmitted by underground power cables instead of
overhead power line
1. Less subject to damage from severe weather conditions (mainly lightning, wind
and freezing).
3. Underground cables pose no hazard to low flying aircraft or to wildlife, and are
significantly safer as they pose no shock hazard (except to the unwary
digger).Much less subject to conductor theft, illegal connections, sabotage, and
damage from armed conflict.
• circuit breakers
• switchgear
• fuses
• relays
1. Switch gear
The apparatus used for switching, controlling and protecting the electrical
circuit and equipment is known as switch.
2. Fuses
A fuse is a short piece of wire or thin strip which melts when excessive
current flows through it for sufficient time. It is inserted in series with the circuit to
be protected.
3. Circuit breaker
A circuit breaker is equipment which can open or close a circuit under all
conditions, no load, full load and fault condition. It is also designed that it can be
operated manually or by remote control under normal and abnormal condition. A
circuit breaker is an automatically-operated electrical switch designed to protect an
electrical circuit from damage caused by overload or short circuit.
TYPES OF CIRCUIT BREAKERS:-
Vacuum
circuit
Breaker
Types Oil
Sf6
of circuit
Circuit
Circuit
breaker
Breaker Breaker
Air
blast
Circuit
breaker
Air vaccum
4. Relay:
A relay is a device which detects fault and supplies information to the circuit
breaker for circuit interruption.
DIFFERENT TYPES OF RELAY:-
1. Solenoid type
3. Electrodynamics Type.
5. Induction type
6. Thermal relay
Current transformer
Current transformer (CT) is used for measurement of electric currents.
Current transformers, together with voltage transformers (VT) (potential
transformers (PT)), are known as instrument transformers. When current in a
circuit is too high to directly apply to measuring instruments, a current transformer
produces a reduced current accurately proportional to the current in the circuit,
which can be conveniently connected to measuring and recording instruments. A
current transformer also isolates the measuring instruments from what may be
very high voltage in the monitored circuit. Current transformers are commonly
used in metering and protective relays in the electrical power industry.
Potential transformers
It is a transformer which is used to measure voltage and also it limit the
voltage of the device.
Lightning arrester
A lightning arrester is a device used on electrical power systems to protect
the insulation on the system from the damaging effect of lightning. Metal oxide
varistors (MOVs) have been used for power system protection since the mid 1970s.
The typical lightning arrester also known as surge arrester has a high voltage
terminal and a ground terminal. When a lightning surge or switching surge travels
down the power system to the arrester, the current from the surge is diverted
around the protected insulation in most cases to earth.
Buchholz relay
Buchholz relays have been applied to large power transformers at least since
the 1940's. The relay was first developed by Max Buchholz (1875-1956) in 1921. In
the field of electric power distribution and transmission, a Buchholz relay, is a
safety device mounted on some oil-filled power transformers and reactors,
equipped with an external overhead oil reservoir called a conservator. The
Buchholz Relay is used as a protective device sensitive to the effects of dielectric
failure inside the equipment. Depending on the model, the relay has multiple
methods to detect a failing transformer. On a slow accumulation of gas, due
perhaps to slight overload, gas produced by decomposition of insulating oil
accumulates in the top of the relay and forces the oil level down. A float switch in
the relay is used to initiate an alarm signal. Depending on design, a second float
may also serves to detect slow oil leaks. If an arc forms, gas accumulation is rapid,
and oil flows rapidly into the conservator. This flow of oil operates a switch
attached to a vane located in the path of the moving oil. This switch normally will
operate a circuit breaker to isolate the apparatus before the fault causes additional
damage. Buchholz relays have a test port to allow the accumulated gas to be
withdrawn for testing. Flammable gas found in the relay indicates some internal
fault such as overheating or arcing, whereas air found in the relay may only
indicate low oil level or a leak.
Buchholz relay
Lt Meter
We are offering our clients, quality and well calibrated HT/LT Meter. These
meters have digital control system and a temperature indicator in order to make
tracking of value indicated by the meter easier. Ruggedly constructed, the meters
also have in-built overload protection along with safety fuses to save the entire
system in overload situations. We offer our HT/LT Meter in cabinets that are
manufactured using various graded material.