You are on page 1of 2

Design Flexibility : Mini Feeder Pillar

Designed & Manufactured based on Customer’s Requirements


(1) Phase and Neutral Busbar
(2) Earth Busbar
(3) Incoming Termination Link
(4) Support Insulator

Low Voltage
(5) Steel Cable Clamp
(6) Disconnecting Link

Feeder Pillar
(7) 100 Amps Din Type Fuse Base
(8) Outgoing Termination Link

Mini Feeder Pillar Features


Rated Current : 400A - 2 Nos. (Incoming)
: 160A - 6 Nos. (Outgoing)

Rated Operational Voltage : 440 Volts

Rated Insulation Voltage : 1000 Volts

Rated Short Circuit withstand : 6kA/1 sec Outdoor & Indoor Design
strength with fuse link
| Compact & Robust |
Cable Termination : 300 sq. mm (Incoming) | Safe & Reliable Operation |
: 70 sq. mm (Outgoing)
| Vandalism Protection |
Fuse Base : 160A (suitable for DIN Fuses) | Customised Solutions |

Enclosure : Suitable for outdoor

Degree of Protection : IP54


for Enclosure
Type-Test Certification
Overall Size (L × H × W) : 650mm × 1245mm × 340mm

Application Standards :
Fuse Base - VDE 0636 Pt 1 & 21
Fuse - NH Fuse 100A
LV Switchgear & - IEC 60439-1
Control Gear assembly
Degree if protection - IEC 60529
Current Transformers
One set of 3 nos busbar mounted rectangular/ring type current Current
Responding To Your Needs transformers are mounted on phase busbar beside incoming Transformer
link for metering indication. Technical Data
The low voltage feeder pillar comprises of the following components :
• Feeder Pillar Enclosure
Instrument Panel
• Busbars
Instrument panel complete with
• Current Transformer
• Fully insulated thermal type ammeter for maximum demand indication
• Instrument Panel
• Cartridge type fuses to facilitate the connection of auxiliary loads
• Incoming Units
(e.g. lighting, portable tools)
• Outgoing Units
• 13 amps 3 pin switched socket outlet
• Energy meter (option)
Cartridge type fuses Ammeter with maximum
demand indication

Enclosure Major Compartments/Components


The metal enclosure is made of sheet steel of minimum 2mm thickness, mounted on a steel base
frame of minimum 3mm thickness. Enclosure is suitable for outdoor application. The enclosure is
fitted with 2 hinges lockable doors, with padlocking facilities and arranged to open through >120
degrees for maximum access. Watershed roof is provided to prevent the accumulation of water.
Ample ventilation is provided to permit natural circulation of air. The ventilation apertures are
(1) Phase and Neutral Busbar
screened to prevent the entry to vermin and foreign objects. The enclosure is fitted with lifting lugs.
(2) Earth Busbar and Cable Clamp
(3) Incoming Units
(4) Outgoing Units
(5) Current Transformer
(6) Instrument Panel

Busbars * *
Busbars
The busbars consists of the following : Outgoing Units
Fuse unit consists of 3 nos. true grip type insulated fuse carriers to provide a hinge action at the * Higher rating is available upon request.
• One set of 3 phase copper busbars bottom contacts for circuit closing and to accommodate various ratings of ‘J’ slotted pattern HRC
• One number copper neutral bar having current rating equivalent to phase bar fuses (BS88-5). The neutral phase is provided with detachable hinge bolted type solid link.
• One number copper earth bar for system earthing
Standards
• EA Tech Specs 37-2 (LV Distribution Fuse board)
On request the phase and neutral busbars are insulated with heat shrinkable tubings. Detachable
fuse holder housings are directly assembled on to the phase busbars. Incoming Units • IEC 60439-1 (LV Switchgear and controlgear assemblies)
Link unit consists of 3 nos. through-grip type insulated link carriers to provide a hinge action at the • IEC 60269-1 (LV Fuses)
bottom contacts for circuit closing and to accommodate tinned solid copper links for the phases and
a detachable hinged bolted type solid link in the neutral. Alternatively, the ‘J’ slotted pattern HRC
fuses can be accommodated upon request.