You are on page 1of 2

712 Flue Gas Analyzer

New! Five Tools in One!


Five
Tools in 1. Combustion Efficiency Analyzer
One!! • Measure 02 and CO
• Calculate CO2, efficiency, excess air and ratio.
The TPI 712 is • Will work with high efficiency furnaces, hot water
an all in one heaters, and other combustible gas appliances.
instrument
designed 2. Combustible Gas Detector
to maximize • Set at 100 ppm sensitivity for natural gas
diagnostic
efficiency and 3. CO Analyzer
accuracy. • Measure 0-10,000 ppm CO

Ask about 4. Differential Thermometer


• Dual input K-Type thermocouple temperature tester
the optional
5. Differential Digital Manometer
A740 • Dual input differential manomoter with 3 selectable
Infrared units of measure: kPa, mBar, inH2O

Printer. 3-YEAR
LIMITED
4.0”w x 8.12”h x 2.25”d WARRANTY

Turn over for


technical
712 FEATURES A740 Infrared
• Easy to use
information
and accessory • Large, easy-to-read display Printer
part numbers. • Data log up to ten sets; timed • Easy to use
logging 400 sets • Battery operated
• PC interface • Self test facility
• Adjustable contrast
NOTE: When • IR printer port
• Manual paper feed
selecting oil as • Protective rubber boot included • Maximum
fuel be sure to 712 ACCESSORIES transmitting
use the optional distance 16”(45cm)
oil filter or CO Sensor, Oxygen Sensor, Protective Boot, • Compatible with
reading could Stack Probe, PVC Tubing, Water/filter trap on most other
combustion
become erratic. Stack Probe, Shoulder Strap Carrying Case,
analyzers
Order item A773. Spare Particle Filters, AC/DC Adapter,
Rechargeable Batteries 3-YEAR
LIMITED
712 OPTIONAL ACCESSORIES WARRANTY

The A740 IR Printer


A767 IRDA Adapter for Data Logging
Value A773 Sulfer Filter
3.0”w
x 6.0 h

Leader™ x 1.75”d

www.industrialindia.com
712 Flue Gas Analyzer
TECHNICAL
SPECIFICATIONS Temperature Measurement Instrument Specifications
AND Range
Resolution
-40° to 1472°, or -40° to 800°C
1°F or C
Operating Temperature Range
Battery
14° to 122°F (-10° to 50°C)
Rechargeable Ni-MH, >6 Hour Life
ACCESSORIES Accuracy (K-type) ±0.3%, ±2°F or ±1°C Charger Input Voltage 115V or 230V : 50/60 Hz AC
Fuels Natural Gas, LPG, Light Oil, Heavy Oil
Display Backlit LCD
Draft/Pressure Measurement Data Storage 10 sets of readings
Selectable Ranges mBar,kPa, and inH2O Data Logging 400 sets of readings on
Ranges -150 mBar to +150 mBar ‘Timed Interval Logging’
-15 kPa to +15 kPa Time & Date 24 Hour Real Time Clock
-60 inH2O to +60 in H20 Dimensions 200mm x 90mm x 60mm
Weight 500g
Resolution 0.01mBar Exhaust Safety Spigot
Accuracy ±0/5% fsd Conforms To: BS7927 (and the draft BS7967

Gross/Net Efficiency
Range 0 to 100% ACCESSORIES
Resolution 0.1% Standard
Flue Probe w/K-type A770
K-Type Temperature Probe GK11M
Oxygen (02) Measurement In-Line Filter Complete A762
Range 0 to 25% Mini Pump Protection Filter Assembly A763
Resolution 0.1% Battery Charger A766
Accuracy ±0.3% Protective Boot A765
Soft Carrying Case A768
Exhaust Spigot A764
Carbon Monoxide (CO) Measurement (2) Static Tips A776
Range 0 to 10,000 ppm
Resolution 1 ppm
Accuracy ±5 ppm or 5%, whichever is greater
Optional
Infrared Printer A740
PC Software A772
Carbon Dioxide (CO2)
IRDA-RS232C Adapter A767
Range 0 to 25% 20 Foot Flue Gas Analyzer Probe A770-20
Resolution 0.1% Replacement Printer Paper (10 rolls) A746
Accuracy Calculated Oil Filter A773

CO/CO2 Ratio NOTE: When selecting oil as fuel be sure to


Range 0 to 0.999
Resolution 0.001
use the optional oil filter or reading could
Accuracy Calculated become erratic.
Order item A773.

Industrial Supply Syndicate


54, Ezra Street, Kolkata - 700 001
Phone: (033) 3291 6080, 22356676 Fax: (033) 3022 2923
Email: info@industrialindia.com
.
Website: www.industrialindia.com
TPI 712 Gas analyser Flue gas analyzer cumbustion analyser instrument meter kolkata calcutta west bengal eastern india

You might also like