Professional Documents
Culture Documents
Abstract—A control algorithm is proposed for a three- in series with the load. The first one is especially
T
phase hybrid power filter constituted by a series active appropriate for the mitigation of harmonics of the loads
filter and a shunt passive filter. The control strategy is called harmonic current source. In contrast, the series
based on the dual formulation of the compensation system configuration is suitable for the compensation of loads
principles. It is applied by considering a balanced and called harmonic voltage source. The shunt connection
resistive load as ideal load, so that the voltage waveform APF is the most studied topology [6]–[10]. However,
injected by the active filter is able to compensate the the costs of shunt active filters are relatively high for
reactive power, to eliminate harmonics of the load current
large-scale system and are difficult to use in high-
ES
and to balance asymmetrical loads. This strategy improves
the passive filter compensation characteristics without
depending on the system impedance, and avoiding the
series/shunt resonance problems, since the set load-filter
voltage grids. In addition, their compensating
performance is better in the harmonic current source
load type than in the harmonic voltage source load type
[10].
would present resistive behaviour. An experimental
prototype was developed and experimental results are
presented. Another solution for the harmonic problem is to
adopt a hybrid APF [11]–[18]. The hybrid topologies
Index Terms—Active power filters (APFs), harmonics, aim is to enhance the passive filter performance and
hybridfilters, instantaneous reactive power, power quality. power-rating reduction of the active filter. Two
configurations have been mainly proposed: active filter
I. INTRODUCTION connected in series with a shunt passive filter and series
A
Many Social and economic activities depend on active filter combined with shunt passive filter. Both
electrical energy quality and efficiency. Both industrial topologies are useful to compensate harmonic current
and commercial users are interested in guaranteeing the source load type. However, when the load also
electrical waveform quality, which supplies their generates voltage harmonics, the second topology is the
different systems. The nonlinear load can generate most appropriate. In this paper, the topology used is
current harmonics and/or voltage harmonics, which series active filter combined with shunt passive filter.
makes worse the power quality. Therefore, these For this configuration, different techniques have been
IJ
harmonics must be mitigating. In order to achieve this, applied to obtain the control signal for the APF [12]–
series or parallel configurations or combinations of [18]. The control target most used is that provides high
active and passive filters have been proposed depending impedance for the harmonics while providing zero
on the application type [1], [2]. impedance for the fundamental harmonic. This strategy
is achieved when the APF generates a voltage
Traditionally, a passive LC power filter is used to proportional to the source current harmonics [12], [13].
eliminate current harmonics when it is connected in With this control algorithm, the elimination of series
parallel with the load [3], [4]. This compensation and/or parallel resonances with the rest of the system is
equipment has some drawbacks [5] mainly related to the possible. The active filter can avoid that the passive
appearance of series or parallel resonances because of filter becomes a harmonics drain of the close loads.
which the passive filter cannot provide a complete Besides, it can prevent the compensation features from
solution. its dependence on the system impedance. From the
theoretical point of view, the ideal situation would be
Since the beginning of the 1980s, active power that the proportionality constant k between the active
filters (APFs) have become one of the most habitual filter output voltage and source current harmonics had a
compensation methods. A usual APF consists of a three- high value, at the limit it would be an infinite value.
phase pulse width modulation (PWM) voltage source However, this would mean that the control objective
inverter. The APF can be connected either in parallel or was impossible to achieve. The chosen k value is
usually small. It avoids high power active filters. Electrical companies try to generate electrical power
However, the choice of the appropriate k value is an with sinusoidal and balanced voltages and it has been
unsolved question, since it is related to the passive filter obtained as areference condition in the supply. Due to
and the source impedance values. Besides, this strategy this fact, the compensation target is based on an ideal
is not suitable to be used in systems with variable loads reference load, which must beresistive, balanced, and
because the passive filter reactive power is constant, and linear. It means that the source currentsare collinear to
therefore, the set compensation equipment and load has the supply voltages and the system will haveunity power
a variable power factor. factor. Therefore, at the point of common coupling
(PCC), the following expression will be satisfied:
In another proposed control technique the APF
generates a voltage waveform similar to the voltage (1)
harmonics at the load side, but in opposition [15]. This
strategy only prevents the parallel passive filter Here, Re is the equivalent resistance, v is the voltage
depending on the source impedance; the other vectoron the connection point, and i is the supply
limitations of the passive filter nevertheless remain. current vector.
Other control strategies combining both the
aforementioned have been proposed to improve the Fig. 1 shows the configuration active filter connected
parallel passive filter compensation characteristics [11], in serieswith passive filter connected in shunt with the
T
but they go on suffering the difficulty of finding an load.
appropriate value for the APF gain k.
In low voltage distribution systems, there is usually
Finally, another approach has recently been the presence of single-phase loads. That produces severe
proposed [16]. It suggests that the active filter generates unbalance voltages and currents in the system. For this
a voltage, which compensates the passive filter and load reason, even if thevoltage source is balanced, the PCC
ES
reactive power, so it allows the current harmonics to be
eliminated. The calculation algorithm is based on the
instantaneous reactive power theory [19], [22]. There,
the control target is to achieve constant power in the
voltage cannot be balanceddue to the presence of
unbalanced three-phase loads and/orsingle-phase loads.
A compensating system will have to avoidthe
propagation of the voltage imbalance from the PCC to
source side. otherconsumers.
All presented strategies are applied to a three-phase
three-wire system with balanced load.
T
where a = ej120 and zero-, positive-, and negative-
sequence components are denoted by superscripts 0, +, Therefore, the equivalent resistance can be calculated by
and –, respectively.
With the inverse transformation, the ideal source equipment will behave as a resistor with a Re value.
current vector is obtained, which will be balanced and
free of harmonics B. Comparison between Resistive Load and
Synchronous Reference Frame Methods
T
Fig. 4.Direct-sequence component calculation.
ES
Fig. 3.Reference voltage calculation.
T
component of the source current vector is multiplied by voltages, therefore, the control scheme must include a
sinωt and cosωt, where ω is the fundamental frequency loop with proportional-integral (PI) controller to ensure
in radian/second. The average values of the results are the capacitor voltages to remain constant [16] at the
obtained using two LPFs. inverter dc side. Fig. 7 shows this control loop and the
PWM generator. Here, VRef is the reference voltage to
remain in the capacitors; Vdc+ and Vdc− are the
ES measured voltage. The difference between the reference
value of the dc-link voltage and the monitored dc-link
voltages serves as an input signal to the PI controller.
voltage calculated by means of (14). The modulation With respect to the performance of the compensation,
technique must be chosen according to the designed the system behaves like a closed-loop control system.
application. For APF use, the most important criterion Therefore, the analysis in the s domain could be
could be a fast response, because the shape of the developed with the help of the blocks diagram shown in
reference to be followed is very sharp in certain regions Fig. 10. The transfer function G(s) contains the
and very flat in other regions. On the other hand, it is impedances ZF and ZS , and the feedback block H(s),
very important to reduce high harmonics generated by includes the impedance ZF and the equivalent resistance
the APF when it is designed to reduce the load Re , defined according to (12). For the sake of
distortion. For it, a hysteresis band control was simplicity, the overall delay time of the control circuit τ
developed. The insulated gate bipolar transistor (IGBT) is considered, thus the block with ejsτ lets model the
gating signals are generated, comparing the reference delay mainly due to the ALPFs. The Nyquist criterion to
signal with the inverter output voltage by considering a analyze the stability of systemis considered. Phase
hysteresis band. This method switches the transistor margin (Pm) is an effective index in addressing relative
when the error exceeds a fixed magnitude: the hysteresis stability and dynamic performance. If the open-loop
band. Therefore, the switching frequency is variable, frequency response is relatively smooth in the gain/Pm
although in our design, this frequency is limited to 20 region, the larger the Pm, the less the overshoot in the
kHz, not to reach the IGBTs maximum switching closed-loop step response. However, if Pm < 0, the
frequency. closed-loop system is unstable. The open-loop transfer
T
in Fig. 10 is given by
In Fig. 8(a) four-wire system is considered. In four-
wire inverter, if the neutral conductor is connected to (22)
the dc bus midpoint, each leg can be controlled
separately. This avoids that the current error can reach
This criterion is applied to experimental prototype
the double of the hysteresis band.
presented in Section IV. It is considered a τ = 50 µs,
B. Stability Analysis
ES
Fig. 9 shows an equivalent single-phase circuit of the
which is the sample time in the control cards. It is
possible to represent the equivalent resistance versus
Pm, which let obtain the Re values that do the stable
system considering current and voltage harmonics. system. Fig. 11 shows that the system is stable when Re
Here, VS is the supply voltage, ZS is the source < 62.1 Ω. Therefore, from the stability point of view,
impedance, ZF is the passive filter impedance, and the the experimental prototype is valid for these systems
nonlinear load is modeled by a current source. that fulfill this condition. In Section IV, the practical
case corresponds to Re values between 11 and 12 Ω. In
the same Section IV appears the resulting waveform of
a step change in the load.
A
Fig. 9.Equivalent single-phase circuit.
IJ
In the equivalent circuit, the controlled voltage source PASSIVE ELEMENT VALUES
represents the APF.
Source Ls=2.8 mH; Rs= 1.8Ω
From the equivalent circuit, it is obtained Passive filter L5=13.5mH C5=30µF
IV. EXPERIMENTAL RESULTS power distribution systems generate large currents that
flow through the power lines, until the circuit breaker
The experimental prototype has been developed. The operates for clearing the fault. The power system
power circuit is a three-phase system supplied by a equipment, such as power transformers, cables, buses,
sinusoidal balanced three-phase 100 V source and 50 Hz etc., are designed to withstand short circuit current
frequency with a source inductance of 2.8 mH and a during at least ten cycles, the series active filter may
source resistance of 1.8 Ω.The inverter consists of an suffer severe damage during this short time. The
IGBT three-legs bridge. It is a Semikron withstand capability of the series APF depends mainly
SKM50GB123-type IGBT bridge. Two 2200 µF on the inverter power semiconductor characteristics.
capacitors are connected at the dc side. The reference Therefore, a protection circuit must be included in the
voltage at the capacitors is 100 V. A small-rated passive system. An interesting protection scheme is proposed in
filter LC has been included to eliminate the switching [24].
ripples at the inverter output. The selection criteria for
ripple filter have been the following [13]: for low-
frequency components, the inverter output voltage must
be almost equal to voltage across Crf . However, for
high-frequency components, the dropped voltage in Lrf
must be higher than in capacitor Crf . Furthermore, Lrf
T
and Crf values must be selected to not exceed the
transformer burden. Therefore, the following design
criteria must be satisfied.
frequency.
ES
XCrf<< ZS + ZF , to ensure that voltage divider
is between Lrf and Crf , where ZS is the source
Fig. 12.Source currents,
compensating 4 A/div. 5 ms/div.
system
impedance and ZF is the shunt passive filter, three single-phase uncontrolled rectifiers with an
reflected by the secondary winding. inductor and a resistor connected in parallel at the dc
side. The inductor is the same for the three phases 55
At 20-kHz switching frequency, ZS = 728 Ω, ZF = 565 mH. However, the resistor was different for each phase;
Ω, XCrf = 0.16 Ω, and XLrf=1696Ω. Table II includes it was 8.3 Ω for phase a, 12.5 Ω for phase b, and 16.6Ω
their values. for phase c. Fig. 12 shows the three source currents
without compensation equipment. The currents are
The set inverter and ripple filter is matched to the distorted and unbalanced. A three-phase power quality
A
power system by means of three single-phase meters Fluke 434, was used to measure the THD,
transformers with a turn ratio of 1:1 to ensure galvanic harmonics, and powers. The measured rms values for
isolation. phase a, b, and c are 8.7, 6.1, and 5.0 A, and the current
THD 28.5%, 27.6%, and 25.6%. The power factors are
The passive filter is constituted by two LC branches 0.91, 0.91, and 0.92 for each phase. Table III
tuned to the fifth and seventh harmonics; element values summarizes some measures.
are included in Table II.
IJ
TABLE III
Phase V 12.4 96 95.8 6.7 5.8 4.8 3.8 0.76 0.23(ind) 0.79 0.91 -
a
Without Compensation
T
Phase V 11.3 97.8 97.1 9.4 3.3 1.2 2.3 0.79 0.05(ind) 0.79 0.93 -
a
I 34.9 8.6 8.2 2.8 0.6 0.2 0.2
With Passive Filter
Phase V 7.6 98.9 98.6 6.1 2.0 0.6 1.6 0.57 0.02(cap) 0.57 0.94 -
b
I 32.4 6.1 5.8 1.8 0.4 0.1 0.2
Phase V 5.6 100 99.8 4.2 1.3 0.5 1.3 0.47 0.07(cap) 0.78 0.94 -
c
Neutral
Phase
a
I
V
28.9
1.0
5.0
6.7
98.5
ES
4.8
3.3
98.4
1.3
5.8
0.5
0.2
0.3
0.2
0.1
0.1
0.1
0.1
0.5
0.1
-
0.56
-
0.01
-
0.56
-
0.99
-
0.10
With active and passive
Phase V 1.2 98.8 98.8 0.5 0.1 0.1 0.2 0.56 0.01 0.56 0.99 0.10
c
I 2.9 5.7 5.7 0.1 0.0 0.0 0.0
Neutral 0.5 0.3 0.4 0.0 0.0 0.0 - - - -
A
IJ
T
A, the same value that without passive filter and the
third harmonic of 5.8 A. Fig. 15 shows the neutral Table III summarizes the most important results.
current waveform. Fig. 16 shows the source currents Harmonics, THD, powers, and power factors are
when the active filter is connected, then the source included. The last columns show the active, reactive,
currents waveforms are sinusoidal and balanced, apparent powers, and power factor per phase. The last
which is the aimof the control strategy. The power column of Table III indicates the capacity of the APF
factor measured is practically the unit for the three
ES
phases. The rms values are 5.7, 5.6, and 5.7A. There
is a slight unbalance due to outliers in the measured
sensors and modulation technique. The current THD
are reduced to 2.6%, 2.6%, and 2.9%.
series to obtain the harmonic filtering and the load
balancing. An important part of the APF capacity is
to correct load imbalance.
current. The resonance of the line impedance and the [7] B. S. Chen and G. Joos, “Direct power control of
passive filters may be easily excited. As Table III active filters with averaged switching frequency
shows, it is avoided with the active filter. When the regulation,” IEEE Trans. Power Electron.,vol. 23, no.
active filter is offline due to malfunction or 6, pp. 2729–2737, Nov. 2008.
maintenance could appear this problem if the passive
LC filter keeps online. The compensation equipment [8] F. Zhang and Y. Yan, “Selective harmonic
includes the active and passive filters; therefore, its elimination PWM control scheme on a three-phase
disconnection is referred to the compensation system four-leg voltage source inverter,” IEEE Trans. Power
as a whole. Electron., vol. 24, no. 7, pp. 1682–1689, Jul. 2009.
T
filter compensation characteristics without depending Mar. 2009.
on the system impedance, since the set load filter
would present resistive behavior. It also avoids the [11] Z. Wang, Q. Wang, W. Yao, and J. Liu, “A
danger that the passive filter behaves as a harmonic series active power filter adopting hybrid control
drain of close loads, and likewise, the risk of possible approach,” IEEE Trans. Power Electron., vol. 16, no.
series and/or parallel resonances with the rest of the 3, pp. 301–310, May 2001.
ES
system. In addition, the compensation is also possible
with variable loads, not affecting the possible passive
filter detuning. The control strategy was applied to a
three-phase four-wire system. An experimental
[12] F. Z. Peng, H. Akagi, and A. Nabae, “A novel
harmonic power filter,” in Proc. IEEE/PESC, Apr.
1988, pp. 1151–1159.
prototype was manufactured and its behavior
[13] F. Z. Peng, H. Akagi, and A. Nabae, “A new
checked. Experimental results are also presented. It
approach to harmonic compensation in power
allows the verification of the developed theoretical
systems-a combined system of shunt passive and
analysis.
series active filters,” IEEE Trans. Ind. Appl., vol. 26,
REFERENCES no. 6, pp. 983–990, Nov./Dec. 1990.
[1] F. Z. PengandD. J.Adams, “Harmonics sources [14] A. Luo, Z. Shuai, W. Zhu, R. Fan, and C. Tu,
A
and filtering approaches,” in Proc. Ind. Appl. Conf., “Development of hybrid active power filter based on
vol. 1, Oct. 1999, pp. 448–455. the adaptive fuzzy dividing frequency-control
method,” IEEE Trans. Power Del., vol. 24, no. 1, pp.
[2] H.Akagi, “Active harmonic filters,” Proc. IEEE, 424–432, Jan. 2009.
vol. 93, no. 12, pp.2128-2141, Dec. 2005.
[15] G.-M. Lee, D.-C.Lee, and J.-K. Seok, “Control
[3] H. L. Ginn III and L. S. Czarnecki, “An of series active power filters compensating for source
IJ
optimization-based method for selection of resonant voltage unbalance and current harmonics,” IEEE
harmonic filter branch parameters,” IEEE Trans. Trans. Ind. Electron., vol. 51, no. 1, pp. 132–139,
Power Del., vol. 21, no. 3, pp. 1445–1451, Jul. 2006. Feb. 2004.
[4] J. A. Pomilio and S. M. Deckmann, [16] Y. S. Kim, J. S. Kim, and S. H. Ko, “Three-
“Characterization and compensation of harmonics phase three-wire series active power filter, which
and reactive power of residential and commercial compensates for harmonics and reactive power,”
loads,” IEEE Trans. Power Del., vol. 22, no. 2, pp. IEEE Proc. Electr. Power Appl., vol. 151, no. 3, pp.
1049–1055, Apr. 2007. 276–282, May 2004.
[5] J. C. Das, “Passive filters-potentialities and [17] H. Yang and S. Ren, “A practical series-shunt
limitations,” IEEE Trans. Ind. Appl., vol. 40, no. 1, hybrid active power filter based on fundamental
pp. 232–241, Jan. 2004. magnetic potential self-balance,” IEEE Trans. Power
Del., vol. 23, no. 4, pp. 2089–2096, Oct. 2008.
[6] P. Lohia,M. K.Mishra, K. Karthikeyan, and K.
Vasudevan, “A minimally switched control algorithm [18] V. F. Corasaniti, M. B. Barbieri, P. L. Arnera,
for three-phase four-leg VSI topology to compensate and M. I. Valla, “Hybrid active filter for reactive and
unbalanced and nonlinear load,” IEEE Trans. Power harmonics compensation in a distribution network,”
Electron.,vol. 23, no. 4, pp. 1935–1944, Jul. 2008. IEEE Trans. Ind. Electron., vol. 56, no. 3, pp. 670–
677, Mar. 2009.
T
Electron., vol. 23, no. 4, pp. 1945–1955, Jul. 2008.
AUTHORS
Mr.S.Suresh Associate
Professor, EEE Dept.,
Kalaignar Karunanidhi Institute
A
of Technology, Coimbatore. He
received his B.E., degree in
Electrical and Electronics
Engineering from Bharathiar
University and M.E (Power
Systems) from Government
College of Technology, Coimbatore. He is currently
IJ
Mrs.M.Geetha Assistant
Professor, ECE Dept.,
Kalaignar Karunanidhi Institute
of Technology, Coimbatore.
She received her B.E. (ECE)
and M.E (PED) from Anna
University, Chennai. Her
research interests accumulate in
the area of power electronics,
digital system and control systems.