You are on page 1of 36

Technical

Information Differential Pressure Transmitter


TI 256P/24/ae
deltabar S PMD 230 / 235
deltabar S FMD 230 / 630 / 633
Deltabar S with ceramic and silicon sensors
Overload resistant with function monitoring
HART®, Profibus or Foundation Fieldbus
protocols

PMD 230

PMD 235 Features and Benefits


FMD 230 Flush Mount • High accuracy
– accuracy better than 0.1% of set
span
– optional “platinum” version,
accuracy better than 0.05% of set
span
– stability better than 0.1% of URL
per year or 0.25% of URL per
5 years
• Process temperatures up to 250°F
(120°C) as standard
• Universal modularity for differential
pressure and gauge/absolute
pressure (Deltabar S and Cerabar S),
i.e.
– replaceable display
– sensor modules
– universal electronics for
FMD 633 Remote Seals
gauge/absolute pressure and
differential pressure
• Simple and easy operation via
4 to 20 mA, HART® protocol or
Applications connection to Profibus-PA or
• Measurement of flow, level or Foundation Fieldbus
differential pressure of gases, vapors • Zero and span freely adjustable with
and liquids or without reference pressure
• Measuring spans from 0.4 inH2O to • Self-monitoring with diagnostics from
580 psi (1 mbar to 40 bar) sensor to electronics
• Nominal pressure up to 6000 psi • Wide variety of software functions
(420 bar) such as linearization curves,
• Suitable for use in hazardous areas diagnostic codes, totalizer, etc.

The Power of Know How


Instrument Selection The Deltabar S is designed with replace- The table below gives a complete
able modules and is based on the same summary of the Deltabar S and
construction principle as the Cerabar S Cerabar S product family. Further
pressure transmitter. This has the information on instruments:
following advantages: • Grey background fields are found
• One electronics unit for all process in this Technical Information document
pressure and differential pressure • White background fields are found in
transmitters Technical Information TI 216P/24/ae
• Sensor modules and electronics can and TI 217P/24/ae, both available from
be replaced on site (automatic Endress+Hauser, USA.
up-load)
Applications Sensors
Gauge and Flow Level Differential Ceramic sensor Metallic sensor
absolute pressure pressure Differential pressure: Differential pressure:
0.4 to 1200 inH2O 0.4 inH2O to 580 psi
PMD 230, PMD 235 PMD 230, PMD 235 PMD 230, PMD 235 PMD 230 PMD 235

Deltabar S
Standard 2-1/8”
connection

S
Z
S
S

metal-free Hastelloy C 276

Z
Z

connection also diaphragm standard


available

FMD 230, FMD 630 FMD 230 FMD 630

Flanged liquid
level transmitter
flush-mounted ceramic
Z S

metallic
sensor, also metal-free diaphragm
connection available with optional
extension

FMD 633 FMD 633 FMD 633

Remote chemical
and sanitary
S

diaphragm seal
S
Z

PMC 731, PMP 731 PMC 731, PMP 731 PMC 731 PMP 731

0 - 10 bar

Cerabar S
Threaded and
Gauge pressure:
flush-mounted Gauge and
2 inH2O to 600 psi
process connections Absolute pressure: Absolute pressure:
(Ti 216P/24/ae) 16 mmHga to 600 psia 0.75 psi to 6000 psi

PMC 631, PMP 635 PMC 631, PMP 635 PMC 631 PMP 635

0 - 10 bar

Diaphragm seal
(Ti 217P/24/ae)

2
Mechanical Modularity Interchangeable electronics
All transmitters in the Deltabar S • One electronic board is used for all
Construction (differential pressure) and Cerabar S transmitters. Plug-in connectors make
(gauge/absolute pressure) family share exchange easy, sensor specific data
parts that are fully interchangeable, thus is automatically up-loaded.
optimizing resources for spare part • The electronics board is lacquered for
inventory and ease of repair. additional protection.
• Local rotary switch is used to set
Interchangeable sensor modules output damping (0 to 16 seconds).
The sensor modules are fully calibrated • Smart operation via 4 to 20 mA,
and temperature compensated in the HART®, Profibus-PA or Foundation
factory. These data parameters are Fieldbus.
permanently stored in an ASIC (applica-
tion specific integrated circuit) located at 4-digit display with 0 to 100%
the sensor. After replacing a module, the bargraph
electronics automatically reads the The Deltabar S transmitter with display
sensor data. The transmitter is then can be calibrated on-site without any
ready for operation. (Zero and span may special electrical or mechanical tools.
need adjustment for specific applica- The display can be mounted in hazard-
tions) ous areas and is easy to retrofit (the
signal circuit load remains constant).
Simple
replacement Local adjustment
of the electronics 4 external push-buttons for zero and
T4 housing
(display on side) span are standard on all versions.
Adjustment can be made with or without
T5 housing reference pressure with a turndown of
0 mA
4...2
3
Test 2
1

(display on top)
BCD
789 A

EF

ule
01

23456

od 20 : 1. Adjustment is also permitted in


orm hazardous areas, and lock function
ns
0 mA
4...2

le
3
2

se
Test

odu
1

so rm tal prevents unauthorized changes.


sen me
a mic
cer
Housings
• NEMA 4X (IP 65) dual compartment
housing protected from corrosion by a
thick polyester powder coating.
~~ • Housing can be rotated 330° and
display can be rotated in 90° steps.
For PMD 230 • Standard 1/2” NPT cable entry
For FMD 630
For FMD 633
For PMD 230 ~~ Process connections
For PMD 235 A wide variety of process connections
are available for chemical, sanitary and
Simple
replacement general-purpose applications. Verify
of the sensor material compatibility to process
module medium.

Modular transmitter concept


Certificates
The versatility of the Deltabar S is
underlined by world-wide approvals and
certificates; including Factory Mutual,
ATEX, CSA, CE, 3-A, and others (refer to
Example: PMD 230 construction Technical Data).
Oval flange *
Sensor seal *
Ceramic sensor *

T5 housing
(display on top)

Mounting
Terminal set with
0 mA

hardware
20
4...2
4...
3
Test

1
2
connection area
0123456789ABCDEF

0 - 10
BAR
ABS

Electronics area Deltabar S PMD 230


* wetted parts

3
Measuring System System components
Deltabar S
The complete measuring system
consists of:
• Deltabar S differential pressure

S
transmitter with 4 to 20 mA signal

Z
output and power supply.

The Deltabar S can be connected to


various systems as listed below.
Computer for configuration
and / or data acquisition
HART®
Complete system consists of:
HART handheld
• Deltabar S differential pressure DXR 275 2
PMD
Onl 230
1 >Grine
PV oup
:LIC

Sele
ct
000
1

transmitter with 4 to 20 mA output


HEL
P

8.7
m

I
O

and HART® digital communication Personal Computer HART


protocol. or input
HART PLC card card
Connect to a controller via HART® input
card, a handheld configurator (DXR275),
or a PC for data monitoring or configura- 4 to 20 mA
250Ω
tion via software configurator (such as R
Communwin II).
HART

Profibus-PA Controller with Profibus input card


for configuration
Complete system consists of: and / or data acquisition
• Deltabar S differential pressure
Personal Computer
transmitter with Profibus-PA digital with Profibus input card
communication protocol
• Profibus-PA/DP segment coupler
(connects up to 10 intrinsically safe Profibus-DP
devices or 32 non-hazardous devices) PLC
Connects to a controller via a Profibus- +
_ +
DP scanner module or a PC with Profibus-PA ENDRESS + HAUSER
_ 24 VDC
Profibus Input card. The PC can be used
for data monitoring or configuration via Profibus-PA/DP
Segment coupler
software configurator (such as
Commuwin II software).

Computer with Foundation Fieldbus HI


Foundation Fieldbus input card for configuration
Complete system consists of: and / or data acquisition

• Deltabar S differential pressure


transmitter with Foundation Fieldbus
digital communication protocol
• Foundation Fieldbus H1 connection
offers data acquisition and
configuration of devices via H1 PC
card. H1 DCS
• Input to control system via H1 input FF H1
module Controller with FF H1
input module

Computer with ControlNET or HSE


ControlNet with HSE (High Speed input card for configuration
Ethernet) connection and / or data acquisition
Offers data acquisition and configuration
of devices via PC input card.
(ControlNet Input Card or Ethernet PC
card).

Input to control system via ControlNet CNET or HSE


DCS
input card or HSE input card.
Controller with
Linking CNET or HSE
device input module

Either ControlNet or HSE


linking device
4
Operating Principle Rugged Single-Chamber Ceramic
Sensor for up to 1200 inH2O
(3000 mbar)
1
The ceramic sensor consists of a
substrate Œand two diaphragms  . The
2 diaphragms and substrate constitute two
measuring surfaces and are connected
by a capillary. Silicon oil, mineral oil or
inert fill serve as a filling fluid. A differen-
3 tial pressure proportional to the change
in the capacitance is measured by the
Ceramic sensor electrodes Žon the ceramic substrate
x basic body
y diaphragm and diaphragms.
4
z electrodes
{ fritted glass 5 Advantages of the Ceramic Sensor
| integrated temperature sensor
for self-monitoring • Ceramic is resistant to aggressive
Ceramic sensor
chemicals. Ceramic materials do not
Deltabar S PMD 230, FMD 230 age, and therefore provide high
measurement quality over many
years.
• The Deltabar S is the first differential
pressure transmitter which also
monitors the diaphragms of the
sensor.
• PVDF flange connections provide
metal free option
• Draft ranges down to 0.4 inH2O

Silicon Sensors (metal diaphragm) Advantages


The separating diaphragm is deflected • Standard system pressures 2320 psi
on both sides by the acting pressure with (160 bar) and 6090 psi (420 bar)
a fill fluid transmitting the pressure to a • Excellent long-term stability
Polysilicon resistance bridge. The bridge • Guaranteed resistance to single-
output voltage, which is proportional to sided overload
differential pressure, is then measured. • Hastelloy C 276 diaphragm as
standard
• Welded stainless steel versions
available

Metal sensor 4 inH2O and 16 in H2O Metal sensor from 40 inH2O


Deltabar S PMD 235 Deltabar S PMD 235, FMD 630, FMD 633

Metal sensor 7
4 to 16 inH2O
x measuring element
y silicon diaphragm
8
z separating diaphragm 3
{ filling fluid
| integrated overload 4 6
protection 9
Metal sensor
from 40 inH2O 5
} measuring element
~ overload diaphragm
 filling fluid
€ separating diaphragm

5
Operation The Deltabar S can be operated in the • Using segment couplers to connect
following ways: to the intrinsically safe Profibus-PA
• Using the four keys on the instrument fieldbus and operating the instrument
directly at the mounting point for via PC and Commuwin II operating
calibrating zero point and span software
• Operating remotely using HART® • Using interface card H1 or via link
data protocol: and interface card H1 for connecting
– e.g. via Commubox FXA 191 and the intrinsically safe Foundation
a PC with Endress+Hauser Fieldbus and for operating via PC
Commuwin II software and operating program
– using the universal HART®
communicator DXR 275 handheld
terminal

Calibration Adjustment range


Zero and span values are freely adjust- • Non-linearity better than 0.1%
able within the measuring limits: • Accurate measurement with 20 : 1
lower limit: -100% of upper range limit turndown
upper limit: +100% of upper range • 4 to 20 mA signal can be inverted
limit • Adjustable output damping; 0 to 16 s
• Shifting the zero point leaves the span via switch, 0 to 40 s via handheld
unchanged terminal

Rapid on-site measurement check Display in calibration mode


Display • Large four-digit pressure display with Example (see figure below): Measuring
bargraph (28 segment bargraph, limits -40 to 40 inH2O with a rating of
0 to 100%) 40 inH2O. The display shows the
• Information on the instrument status digitally accurate pressure value for the
and diagnosis available without zero point (4 mA) which has been set:
special tools Z = -5.000 inH2O. The bargraph shows
• Calibration mode: display of zero and that the measuring range lies within the
span, both showing measuring limits set limits.
of sensor (and bias pressure).
Advantage: zero and span can be
NOTE: Zero and span can also be set
calibrated with digital accuracy
without display module. Actual refer-
• The display can be rotated in
ence pressure has to be applied. Push
90° steps
the ±Z and ±S buttons simultaneously to
* Display units freely programmable
set 4 mA and 20 mA respectively.
via HART®, Profibus-PA, or
Foundation Fieldbus protocol

Before operating the keys,


unscrew cover screws and slide
cover to one side. ++
Z S
– –
Z S

-5 to 20 inH2O

Display module with 4


character differential
pressure display and
bar graph indicating
current in %.

Z S

6
Remote Operation Handheld terminal Operation using the Commubox
A handheld terminal can be connected FXA 191 and personal computer
at any point in the 4 to 20 mA line to The Commubox FXA 191 connects
check, configure and read additional 4 to 20 mA Smart transmitters with
information from the Deltabar S. The HART® protocol to the RS 232 C serial
handheld universal HART® Communica- interface of a personal computer. This
tor DXR 275 for HART® protocol is used enables the transmitter to be remotely
for this purpose. operated with the Endress+Hauser
A large display gives detailed and self- Commuwin II operating program.
explanatory information. The transmitter The Commubox FXA 191 is approved for
continues to measure normally while the use with intrinsically-safe signal circuits.
data is entered.

DXR 275 HART® handheld terminal Function


A digital communication signal is
superimposed on the 4 to 20 mA signal
line and provides all information
required for remote calibration. Other
devices connected to the current output
are not affected by this digital signal.

Instrument Connection Electrical connection HART® A separate, shielded two-wire cable is


The intrinsically safe handheld terminal recommended for transmitters with
HART® or FXA 191 is connected either: HART® communication interface.
• directly to the transmitter Ground the shield in accordance to any
• in the control room hazardous location regulations. For
• to any point in the signal cable non-hazardous applications, the shield
To ensure reliable communication, the should be grounded at one end only.
4 to 20 mA signal line must exhibit a
minimum resistance between the NOTE: If shielded cable is not used,
connection points and the power supply. interference may affect the digital
HART®: Minimum line resistance greater communication signal.
than 250Ω, max. 180 nF.
R ≤ 0.0076 Ω/ft (25 Ω/km), max. length
3280 ft (1 km).

Field Control Room


minimum total resistance = 250Ω

other
Text
4...20 mA 0000 R instruments
1 2 3
HART® +
4 to 20 mA
protocol

PMD 230:LIC0001
Online PMD 230:LIC0001
1 >Group Select Online
2 PV 8.7 m 1 >Group Select
2 PV 8.7 m

HELP

Commubox
HELP

I
OR FXA 191
O I
O

Personal Computer
with Commuwin II
software

EX EX

Connecting the handheld terminal for HART® protocol.


Commubox FXA 191 is connected indentical to the hand-
held terminal.

7
Instrument Connection Profibus-PA The number of instruments at one bus
The Profibus-PA is an open fieldbus segment:
Profibus-PA standard for connecting sensors and • up to 10 intrinsically safe Deltabar S
actuators, which may also be in hazard- locations
ous areas using one bus cable. The two- • up to 32 standard Deltabar S
wire sensors are supplied with power applications for non-hazardous areas
over the Profibus-PA line and the The Deltabar S consumes a maximum of
process information of the sensor is 11 mA per unit.
digitally transmitted.
Profibus-PA is an open bus which allows
The Deltabar S with PA electronics is any Profibus-PA device to be connected
connected to a segement coupler which to the segment; such as valves, actua-
supplies the signal to a PLC or personal tors, or other measuring devices.
computer with Communwin II software.

Personal computer
with operating
program e.g.
Commuwin II PLC

Profibus-DP

S
Deltabar S

Z
Segment
coupler

S
Z
ENDRESS + HAUSER
S
Z
S
Z

Fieldbus with Profibus-PA

Deltabar S with
Profibus-PA

8
Instrument Connection Foundation Fieldbus
Foundation Fieldbus is an open fieldbus The following instruments can be
Foundation Fieldbus standard to enable several sensors and operated via an interface card or via Link
actuators, including those in hazardous and an interface card:
areas, to be connected to a bus line. • up to 10 instruments for hazardous
With Foundation Fieldbus, two-wire locations
looped instruments can be supplied by • up to 32 instruments for non-
the sensor with power and digital hazardous locations
process information. NOTE: amount of instruments con-
nected is dependent on electrical wiring
concept and accessories used.

CO H1 AI AO DI

Fieldbus H1
S

S
Z

Connection via Link and Fieldbus interface card H1

CO H1 AI AO DI

ControlNET or HSE

I/O FC LD
Deltabar S with Fieldbus H1
Foundation Fieldbus
function blocks
CO: Controller
H1: H1 interface
CN: ControlNet
S

AI: Analog input


Z

AO: Analog output


DI: Digital input
I/O: Input / Output
FC: Frequency converter
LD: Link

9
Installation Mounting instructions Zero point correction
• For measurement in media with a The Deltabar S is calibrated based on
solids content (e.g. contaminated the limit point method according to
liquids). Separators and drain valves DIN 16 086.
should be used in order to trap and Due to the hydrostatic column of fluid in
remove any build-up that may occur. the sensor, the zero point of the instru-
• By simply loosening the locking screw, ment may vary up to 0.8 inH2O (2 mbar).
the housing can be rotated through Diaphragm seals also shift the zero point
330°. depending on the orientation of the
• A mounting bracket for wall or pipe instrument. This shift due to position can
mounting is available for the be fully corrected by zero point adjust-
Deltabar S. ment directly on the instrument using the
push buttons.
A 3-valve or 5-valve manifold can be
mounted directly to the PMD 230 or PMD Instructions for flanged level
235 which facilitates easy shut-off, transmitters or remote seal versions
removal and equalization for the • The diaphragm seal and the pressure
measuring point (refer to page 11 and sensor together form a closed and
12). calibrated system which is filled with
Mounting tip: filling fluid. All filling holes are sealed
Use the manifold mounting bracket, it and are not to be opened!
simplifies removal of the transmitter and • The protective caps should only be
secures piping. removed just before mounting in order
to protect the diaphragm seal.
• When using a bracket for mounting
remote seals, it should not be put
under strain and cause kinks in the
capillary tubing (minimum bending
radius 4.0” / 100 mm).

Wall mounted Pipe mounted


11.6"
3.41 (294)
2.62" (86.5)
(66.5)

5.63" Z S
4.84"
Z S

(143) (123)

1.77"
(45)
~ 7.68"
(195)
~ 10.8"
(274) 0.39"
(10)
max. 330°
2.
9 3.94"
(7 1" (100)
4)

4.25" 2.91"
(108) (74)
0 - 25 mbar

0 - 25 mbar

ø 2.37"
ø 0.47" (60.3)
(ø 12)
304 SS Mounting bracket

Rotating the housing Wall and pipe mounting with bracket


It is recommended that the cable entry face SS mounting set for pipe or wall PN: 943153-1001
downwards. This provides extra protection against (includes hardware, order both part numbers) PN: 943153-0031
water / condensation entering the terminal chamber.
Carbon steel mounting set for pipe or wall PN: 943153-1000
(includes hardware, order both part numbers) PN: 943153-0030

FMD 230 accessories

Weldspud for “WH” process connection option PN: 61001673


4” clamp for weldspud PN: 61001674

10
Accessories
3-valve manifold, PMD 235 / PMD 230 3-Valve manifold mounting bracket

9.29" Flow 3.00"


Max. open Schematic
0.09"
0.69"
DP
Body
1.75"

3.70"
Horizontal Mounting Face
4.00"
1.81"
3.38" Manifold
2.12" ∅ 0.28"
Inlet 2.00" (4-pl)
(2-Pl)
Bracket
3.68"

2.00"

3.52"
Max 2.38"
Open 1.62"
5.82" Bolts, nuts
and lock
washers U-bolt kit
2.00" 2.38" (2 of each) (2)
Typ.

3.37" ∅ 0.44"
(8-pl)
2.38"
3-valve manifold, 316 SS, 6980 psig @ 100°F, U-bolt mounting holes
allows 90° rotation
4800 psig @ 450°F, 1/2” process connections, Teflon packing PN: 84600538
3-valve manifold, carbon steel, 6580 psig @ 100°F, Vertical Mounting Face
4800 psig @ 450°F, 1/2” process connections, Teflon packing PN: 84600539
3-valve manifold, 316 SS, 6980 psig @ 100°F, Mounting bracket, carbon steel, for 3-valve manifold. PN: 84600541
4300 psig @ 650°F, 1/2” process connections, Grafoil packing PN: 84601058 Mounting bracket, stainless steel, for 3-valve manifold. PN: 84601068
3-valve manifold, carbon steel, 6580 psig @ 100°F,
4300 psig @ 650°F, 1/2” process connections, Grafoil packing PN: 84601057

3-valve manifold, PMD 235 / PMD 230, flanged

9.29" Flow
Max. open Schematic
0.09" Outlet
0.69" (2 pl)
DP
Body
1.75"

3.28"

2.12"

3-valve manifold, 1/2” process connections

Cap screw
3.52"
2.38" Handle
Max.
open 1.62"

2.00"
Typ.

Inlet
(2 pl) 0.721" X 0.165" DP.

3.37"

3-valve manifold, 316 SS, 6980 psig @ 100°F,


4800 psig @ 450°F, flanged process connections, Teflon packing PN: 84601062

3-valve manifold, flanged process connections

11
5-valve manifold, PMD 230 / PMD 235, gas metering

11.61" Max. open


4.64"
3.88" Max. open

3.30"

4.00"
1.30"
(Typ.)

2.125" 1.58"

Flow
Schematic

DP

5-valve manifold, 1/2” process connections,


gas metering

5-valve manifold, 316 SS, 1500 psig @ 100°F, 500 psig @ 200°F,
1/2” process connections, gas metering, Teflon packing PN: 84600848

5-valve manifold, PMD 230 / PMD 235

0.09" Flow
0.69" Schematic
(2-Pl) 0.25"
(2-PL)

DP
1.25"

4.27"
5-valve manifold, 1/2” process connections
2.12"

Outlet (backside)
(2-PL)

1/4" TEST (2-PL)

1/2” FNPT offset flange adapter


2.50"
1.63" 2.55"
(65.0)
1.62"
(41.3)
1.25" 1/2" NPT Inlet
0.81"
6.75" (2-pl) (20.6)
5/16" Mtg. holes (2)

5-valve manifold, 316 SS, 6000 psig @ 100°F, 3980 psig @ 500°F, 0.47"
1/2” process connections, standard metering, Grafoil packing PN: 84601195 1/2" (12.0)
NPT dia.
5-valve manifold, 316 SS, 6000 psig @ 100°F, 3980 psig @ 500°F,
1/2” process connections, power (ANSI B31.1), Grafoil packing PN: 84601196 0.98"
(25)

0.43"
(11.0)
dia.

1.18"
(30.0)

0.71"
(18.0) dia.
0.94"
(24.0) dia.

1/2” FNPT offset flange adapters


PN: 84600362

12
Application for Flow Flow measurement Primary elements
The Deltabar S was designed to be The Deltabar S can be used with any
Measurement easily applied together with various standardized primary device allowing for
styles of primary devices for new or a wide, cost effective application range.
existing differential pressure applica- Primary devices are available for small
tions. The transmitter is easily config- pipes up to ducts several feet in size.
ured onsite or delivered from the factory • Orifice plates
set to required values. The choice of • Pitot tubes
conventional or ceramic sensors allow • Nozzles
for optimal cost and performance in • Venturi pipes
given applications. • Others

Deltabar S features
• Standard mounting dimensions allows • Local selection of linear or square
for easy retrofit and connection to root mode.
3 or 5-valve manifolds. • 4-digit display: display flow rate, % of
• Excellent performance for draft ranges flow, or totalized flow.
down to a span of 0 to 0.4 inH2O. • Optional 7-digit internal totalizer
• Standard accuracy of 0.1% of span function (no pulse output).
(optional 0.05% for PMD 235). • Adjustable low flow cut-off is essential
to eliminate erroneous measurement
at low flow. Typically set at 0% to 8%
of maximum flow rate.
I ~q
measured
q max

Dynamic
at least
12:1
Note!

8 % q max Perfect accuracy


for 8 % ... 100 % of q max
dPspan dP Dynamic 12:1 possible
(typical: 6:1 to 3:1)
8%
For lowest flow
(< 8% of q max. ):
linear linear curve
High reproduceability,
stable signal

Low flow cut-off


Measuring systems with flow
computer
For applications where optimal accuracy By compensating for temperature and
is required. Applications include, for pressure changes in a flow computer
example, steam or gas flow measure- (see Compart DXF 351 Ti 032D/24/ae)
ment with changing pressure or tem- the accuracy is optimized and allows for
perature. output in compensated volumetric flow
rate, mass flow rate, heat quantity or
calorific value.

Application for Level Level, volumetric and mass


measurement
Measurement Hydrostatic pressure is the most widely For pressurized vessels, the negative
used principle for continuous level side of the sensor is connected to the top
measurement in liquids. A hydrostatic of the tank (the static pressure is
pressure is created due to the weight of cancelled out).
a column of liquid. At constant density ρ, The measurement principle can be used
the hydrostatic pressure is determined for measuring liquids with foam, in
only by the height h of the liquid column. vessels with agitators or filters, and in
any shape vessel. Using the program-
∆p = ρ x g x h mable linearization curve, the level can
Where: be converted into a volumetric value.
ρ = density of the medium The Deltabar S also features a “Density
g = gravity constant, 32.2 ft/s2 (9.81 m/s2) factor” calibration option which simplifies
h = level set up in applications where the density
of the final media does not match that
used during start-up / calibration.
13
Examples of Measuring Systems
Flow Measurement

Deltabar S PMD 230/235 Deltabar S PMD 230/235 Deltabar S PMD 230/235

orifice plate or
0 - 25 mbar

condensate pitot tube


shut-off shut-off
pot
valve valve
3-valve
manifold + +
3-valve 3-valve
manifold manifold
+ shut-off valve optional optional:
separator
separator
and drain and drain
valve valve 0 - 25 mbar
0 - 25 mbar

Orifice plate or pitot tube

Gas: Steam: Liquids:


• Mount the Deltabar S above the measuring • Mount the Deltabar S below the measuring • Mount the Deltabar S below the measuring
point so that any condensate in the point. point so that the pressure piping is always
process line runs back. • Mount and fill the condensate pot. filled with liquid.

Level Measurement

Deltabar S with remote seal Deltabar S PMD 230/235 Deltabar S FMD 230/630
shut-off condensation pot
max. valve (for condensing media
only)
Max. horizontal
shut-off
Max.
valve

min.
+ +
Min. Min.
S

Z S
Z

3-valve optional:
optional: manifold separator
separator
and drain
+ and drain
valve
valve 0 - 25 mbar

Capillary diaphragm seal: Closed vessels: Closed vessels with flanged


• Mount the Deltabar S below the lower • Mount the Deltabar S below the lower Deltabar S:
connection. Exceptions, see page 14 connection so that the pressure piping is • Mount the Deltabar S directly onto the
• Mount the diaphragm seal with capillary always filled with liquid. vessel.
tube on the vessel. • The negative side must be connected • The negative side must be connected
above the maximum level. above the maximum level.
• The condensate pots ensure a constant
column of fluid with a layer of vapor.

Differential Pressure Measurement

Deltabar S PMD 230/235 Deltabar S PMD 230/235 Deltabar S with remote seal

0 - 25 mbar
shut-off
valve +
3-valve
manifold
+ e.g.
filter
3-valve
+ manifold
shut-off optional
valve separator
and drain Z S

valve
e.g. filter 0 - 25 mbar

Gas and vapor: Liquids: Gas and liquids:


• Mount the Deltabar S above the measuring • Mount the Deltabar S below the measuring • Mount the diaphragm seal above the
point so that any condensate in the point so that the pressure piping is always piping.
process line runs back. filled and gas bubbles can rise and return • Mount the transmitter below the measuring
to the process piping. point.

14
Design Planning for the 1 2 5
Diaphragm Seal Diaphragm seal fluid Temperature effects
The temperature and pressure of the The temperature coefficients of the
Version FMD 633 process are of critical importance when diaphragm seals as stated in the
selecting the fluid for the diaphragm technical data and dimensions apply to
seal. silicon oil (calibrating temperature of
6 68°F / 20°C) and are specified by the
process temperature and ambient
The suitability of the fluid to meet the
temperature. For other fluids used, the
requirements of the process material
TK value is to be multiplied by the TK
must also be considered. For foodstuff
applications only food grade fluids such correction factor.
as vegetable oil or silicone oil (AK 100) The total temperature coefficient TK is
may be used in the diaphragm seal. derived from adding the TK of the
The smallest recommended Deltabar S to that of the diaphragm seal
measuring span and diaphragm together with the capillary tubing.
diameter. NOTE: Due to small variations in seal
The effects of temperature cause the fill design, the calculated error may have an
fluid to expand and contract. This in turn error of up to±10%, and should be used
has a direct effect on the zero point and as a selection guideline only. Please
accuracy of the measured value. To contact Endress+Hauser for detailed
minimize the temperature effects, the calculation performance.
following guidelines should be ob- • The temperature effects of the
served: capillary tubing are determined by the
• Use as large a diaphragm diameter as ambient temperature at the measuring
possible. A large diaphragm is more point.
flexible and absorbs more of the TK for every meter of silicon oil
volume changes of the fill fluid. – one-sided, 0.5 mbar/10 K
• The largest possible diaphragm – two-sided, 0.12 mbar/10K
should be chosen for small Both capillary tubes are always the
measuring spans. same length in order to minimize
• Keep capillaries as short as possible temperature effects. Both capillary
to minimize the temperature effects. tubes should be at the same
temperature.
3
Guide lines for mounting remote
seals with capillary tubes
For applications in vacuum, the transmit-
ter should always be mounted below the
measuring point. The maximum height
difference between measuring point and
transmitter should not exceed the height
listed in the table below. Failure to do so
may result in a break of the liquid
column in the capillary.
The minimum bending radius of the
capillary tube is 3.9” (100 mm).
1 2 3 4 5 6
Fill fluid of Permissible temp. Permissible temp. Maximum height Minimum Density TK Notes
diaphragm of medium at of medium at difference ** permissible (g/cm3) correction
seal 0.73 psia ≤pabs≤14.7psia pabs≥14.7psia pabs≥14.7psia pressure at factor
(0.05 bar ≤pabs≤1bar) (pabs ≥1bar) (pabs ≥1bar) 88°F (20°C)
Silicone oil -40° to +356°F -40° to +482°F 23 ft. max. 0.15 psi Standard, foodstuffs
(-40° to +250°C) (7 m max.) (10 mbar abs ) 0.96 1
SWS 101 (AK 100) (-40° to +180°C) applications
High temperature +14° to +392°F +14° to +662°F 23 ft. max. 0.15 psi
(-10° to +350°C) (7 m max.) (10 mbar abs ) 0.81 0.72
oil, paraffin (-10° to +200°C)
-40° to +176°F -40° to +374°F 23 ft. max. 0.15 psi Inert oil for O2 gas
Fluorolube (-40° to +175°C) (7 m max.) 1.87 0.91
(-40° to +80°C) (10 mbar abs ) or chlorine
+59° to +392°F 13.1 ft. max. 0.15 psi
Glycerine - 1.26 0.64 Food grade
(+15° to +200°) (4 m max.) (10 mbar abs )
Vegetable oil * +14° to +392°F +14° to +392°F 23 ft. max. 0.15 psi Food grade FDA
(Neobee M20) (-10° to +200°C) (7 m max.) (10 mbar abs ) 0.94 1.05
(-10° to +200°C) No: 21CFR172 856
Silicone oil * -40° to +400°F 23 ft. max. 0.15 psi Standard, foodstuffs
(7 m max.) 0.93 applications
DC200-10CS (-40° to +205°C) (10 mbar abs )
High temperature 32° to +600°F 23 ft. max. 0.15 psi High temperature
1.07
oil, Silicone DC 704 * (0° to +315°C) (7 m max.) (10 mbar abs ) application ***

* Standard fill fluid used for FMD 633


** Maximum height difference between the transmitter and the lower measuring point connection. For applications in vacuum, the
transmitter should be mounted below the measurement point connection.
*** Not for use in nitric or sulfuric acid.
15
4
Mounting position importance for
measuring range
The columns of fluid in the capillary
tubes for the PMD 235 with seals and
piping to the PMD 230 and PMD 235
produce a differential pressure which
depends on the difference in height
between the two process connections.
When selecting the measuring range,
the zero point shift must lie within the
nominal range of the sensor.

_
10 ft. glycerine Maximum
approximately
156 inH2O
8 ft.
ρ = 1.3 sg (1.3 g/cm ) approx.
3

96 inH2O

ρ = 1.3 sg (1.3 g/cm3)

+ p=ρxgxh

Minimum

Example: Sensor selection

The measuring cell selected must be greater than 156 inH2O

Electrical Connection 4 to 20 mA wiring


The two-wire cable is connected to 4 to 20 mA
screw terminals suitable for 13 to 20 Standard: 11.5 to 45 VDC
AWG (0.5 to 2.5 mm) wire in the connec- IS: 11.5 to 30 VDC
tion compartment.
• Use shielded transposed 2-wire 4 to 20 mA 0003

cable. 1 2
Test

3
• Input supply voltage: +
- standard, 11.5 to 45 VDC
- Intrinsically safe, 11.5 to 30 VDC
• Reverse polarity, HF interference and
over-voltage peaks are internally
protected.
• Test signal: the output current can be
measured between terminals 1 and 3
without breaking the 4 to 20 mA loop.

Profibus-PA wiring
The digital communication signal is
Profibus-PA
transmitted to the bus using a 2-wire
connecting cable. The bus cable also
carries the power supply. PROFIBUS-PA 0002

• Input supply voltage: PA PA


- standard, 9 to 32 VDC + 1 2 3

- intrinsically safe, 9 to 24 VDC


• Bus cable: use shielded twisted pair
cable. The following specifications PA-
must be observed when using the PA+
FISCO model (explosion protection):
- Loop resistance, DC, 15 to 150 Ω/km
- Inductance, 0.4 to 1 mH/km
Ground terminal on
- Capacitance, 80 to 20 nF/km housing: must be
Instructions on connecting and ground- grounded!
ing the network are given in BA 198F
“Project Instructions for Profibus-PA” as
well as Profibus-PA specifications.

16
Foundation Fieldbus wiring Foundation Fieldbus
The digital communication signal is
transmitted to the bus using a 2-wire
0002
connecting cable. The bus cable also Foundation Fieldbus

carries the power supply. FF FF


+ 1 2 3
• Supply voltage:
- Standard, 9 to 32 VDC
- Intrinsically safe, 9 to 24 VDC
• Bus cable: use shielded twisted pairs. FF-
Further information on the type of FF+
cabling to use can be found in the
FF specification or in IEC 61158-2.
Further information on connecting and Ground terminal on
grounding the network is given at the housing: must be
grounded!
Internet address “http://www.fieldbus.org”.

“Platinum” transmitters
Special Applications Besides the standard versions (linearity Three versions are available (refer to
0.1% of set span), instruments with PMD 235 ordering codes)
higher accuracy are also available. • PMD 235 - C (psi)
These are known as “Platinum” versions • PMD 235 - A (bar/mbar)
and are available for the PMD 235. • PMD 235 - B (Pa/MPa)
Platinum instruments can be ordered
as standard with HART® electronics and
with various diaphragm and flange
materials.

Oxygen and very pure gas


applications
Oxygen and other gases react very These state the application limits for
explosively with oils. Plants that are pressure and temperature.
totally oil and grease-free must use Exceptions:
instruments which are oil and grease- PMD 235 with tantalum diaphragm
free. The Deltabar S can be specially Tmax = 140°F, pmax = 145 psi
treated according to DIN 19247 and (Tmax = 60°C, pmax = 10 bar)
BAM standards to meet thoses require-
PMD 235 with Hastelloy or Monel
ments. Instruments for oxygen applica-
diaphragm
tions can be selected in the product
Tmax = 140°F, pmax = 580 psi
structure as follows:
(Tmax = 60°C, pmax = 40 bar)
• PMD 230 - 6
• PMD 235 - 6
Oil and grease-free instruments are also
• FMD 230 - 6
available but without the oxygen service.
• FMD 630 - 6
• PMD 230 - 8
Tmax = 140°F, pmax = 1000 psi
• PMD 235 - 8
(Tmax = 60°C, pmax = 70 bar) • FMD 630 - 8
Total performance
Total Performance A detailed summary of the accuracy of The following graph shows the TPE of
measurement data under process the PMD 235 as well as “Platinum”
conditions is know as the Total Probable instruments. The example given here is
Error (TPE) and is given as a % of the for a typical 30 K temperature variation
set span. This value is calculated as and 150 psi (10 bar) static pressure.
follows:

TPE = (L2 + S2 + T2) Typical High End differential


pressure transmitter
TPE
Where: Deltabar S PMD 235

L = linearity including Deltabar S PMD 235


"Platinum"
hysteresis and repeatability
0.2 %
S = static pressure effects on
the span 0.15 %

T = temperature effects 0.1 %

Total Probable Error (TPE)


0.0145 0.362 1.8 6 14.5
as a function of the set span
Set span psi

17
Technical Data
General Information Manufacturer Endress+Hauser
Product name Deltabar S; PMD 230, PMD 235, FMD 230, FMD 633

Application Deltabar S The instrument is used for the measurement of flow in gases,
vapors, and liquids; for the measurement of level in liquids as
well as for the measurement of differential pressure in gases,
vapors, and liquids

Operation and System Design Measuring principle For PMD 230, FMD 230: capacitive with ceramic single-
chamber sensor
For PMD 235, FMD 630, FMD 633: silicon sensor with
metallic diaphragm
With 4 to 20 mA current Operation via
output and HART - four keys on the instrument and a plug-in display module
communication protocol - universal HART Communicator DXR 275 handheld terminal
- PC with Communwin II operating software via Commubox
FXA 191
With Profibus-PA Via segment coupler connection to the PLC or PC e.g. with the
Commuwin II operating software
With Foundation Fieldbus Via interface card H1 direct connection to PC with operating
program or via Link and interface card H1 connection to PC with
operating program

Input Measured variables Differential pressure for deriving flowrate (volumetric or mass
flow), level, mass, or volume

Ceramic sensor measuring range


Nominal Limits Span System Pressure Sensor fill
Value fluid

PMD 230 lower-range upper-range minimum maximum overload overload


FMD 230 value value one side both sides
10 inH2O -10 inH2O 10 inH2O 0.4 inH2O 10 inH2O 145 psi 145 psi Silicone oil **
25 mbar -25 mbar 25 mbar 1 mbar 25 mbar 10 bar 10 bar
40 inH2O -40 inH2O 40 inH2O 2 inH2O 40 inH2O 230 psi * 230 psi * Silicone oil **
100 mbar -100 mbar 100 mbar 5 mbar 100 mbar 16 bar * 16 bar *
200 inH2O -200 inH2O 200 inH2O 10 inH2O 200 inH2O 1450 psi * 2000 psi * Mineral oil **
500 mbar -500 mbar 500 mbar 25 mbar 500 mbar 100 bar * 140 bar *
1200 inH2O -1200 inH2O 1200 inH2O 60 inH2O 1200 inH2O 1450 psi * 2000 psi * Mineral oil **
3000 mbar -3000 mbar 3000 mbar 150 mbar 3000 mbar 100 bar * 140 bar *
* 145 psi (10 bar) for process connection PVDF with PMD 230. 580 psi (40 bar) with process flange for
FMD 230. 200 psi (14 bar) at 70°F with “WH” process connection for FMD 230 if using Tri-clover type clamp.
** Voltalef 1A for oxygen service, grease-free.

Silicon sensor measuring range


Nominal Limits Span System Overload 3) Pressure
3)
Value Pressure transmission
sensor fluid 2)
PMD 235 lower-range upper-range minimum maximum Overload Overload
FMD 630 value value one side two sides 4)
FMD 633
4 inH2O 1) -4 inH2O 4 inH2O 0.4 inH2O 4 inH2O 2320 psi 5) 2320 psi 3480 psi Silicone oil
10 mbar -10 mbar 10 mbar 0.5 mbar 10 mbar 160 bar 160 bar 240 bar
16 inH2O 1) -16 inH2O 16 inH2O 0.8 inH2O 16 inH2O 2320 psi 5) 2320 psi 3480 psi Silicone oil
40 mbar -40 mbar 40 mbar 2 mbar 40 mbar 160 bar 160 bar 240 bar
40 inH2O -40 inH2O 40 inH2O 2 inH2O 40 inH2O 2320 psi 5) 2320 psi 3480 psi Silicone oil
100 mbar -100 mbar 100 mbar 5 mbar 100 mbar 160 bar 160 bar 240 bar
200 inH2O -200 inH2O 200 inH2O 10 inH2O 200 inH2O 2320 psi 6090 psi 2320 psi 6090 psi 3480 psi 9135 psi Silicone oil
500 mbar -500 mbar 500 mbar 25 mbar 500 mbar 160 bar 420 bar 160 bar 420 bar 240 bar 630 bar
1200 inH2O -1200 inH2O 1200 inH2O 60 inH2O 1200 inH2O 2320 psi 6090 psi 2320 psi 6090 psi 3480 psi 9135 psi Silicone oil
3000 mbar -3000 mbar 3000 mbar 150 mbar 3000 mbar 160 bar 420 bar 160 bar 420 bar 240 bar 630 bar
230 psi -230 psi 230 psi 320 inH2O 230 psi 2320 psi 6090 psi 2320 psi 6090 psi 3480 psi 9135 psi Silicone oil
16000 mbar -16000 mbar 16000 mbar 800 mbar 16000 mbar 160 bar 420 bar 160 bar 420 bar 240 bar 630 bar
580 psi 1) -580 psi 580 psi 800 inH2O 580 psi 2320 psi 6090 psi 1450 psi 6090 psi 2175 psi 9135 psi Silicone oil
40000 mbar -40000 mbar 40000 mbar 2000 mbar 40000 mbar 160 bar 420 bar 100 bar 420 bar 150 bar 630 bar
1) PMD 235 only
2) Voltalef 1A for applications in very pure gases, other fill fluids on request.
3) 2320 psi (160 bar) version with stainless steel bolts, 6090 pse (420 bar) with chromized steel bolts.
4) Type tested for burst pressure (FM) up to 16,000 psi (1120 bar) on both sides with 6090 psi (420 bar) version.
5) High pressure 6090 psi (420 bar) version available on request, consult factory.

Minimum system pressure PMD 230, PMD 235, FMD 230: pabs larger than 0.7 mmHga
(1 mbar) for all sensors and measuring ranges
FMD 630, FMD 633: pabs larger than 7 mmHga (10 mbar) for
all sensors and measuring ranges

18
Output Profibus-PA
Output signal Digital communication signal, Profibus-PA
PA function Slave
Transmission rate 31.25 kBits/s
Response time Slave: approximately 20 ms; PLC: approx. 600 ms (depending on
system coupler) for approx. 30 transmitters
Signal on alarm Signal: status bit set, last valid measured value will be held
Display module: error code
Communication resistance Profibus-PA termination resistor

Foundation Fieldbus
Output signal Digital communication signal, Foundation Fieldbus protocol
FF function Publisher-Scriber
Transmission rate 31.25 kBits/s
Signal on alarm Signal: status bit set, last valid measured value will be held
Display module: error code
Communication resistance Foundation Fieldbus termination resistor
4 to 20 mA with HART®
Output signal 4 to 20 mA, under-run 3.8 mA (4 mA adjustable), over-run
20.5 mA (adjustable)
Load Field of operation for Deltabar S Field of operation for Deltabar S
PMD 230 / FMD 230 PMD 235 / FMD 630 / FMD 633
R/Ω for Ι max 21.5 mA R/Ω for Ι max 21.5 mA
1560 1560

1000 1000
860 860

Permitted Permitted
500 500

0 0
11.5 20 30 45 U/V 11.5 20 30 45 U/V
Standard FM IS CL. I, Div 2 Standard FM IS Cl 1 Div 1

Signal on alarm Selectable 21.5 mA or 3.8 mA


Resolution Better than 1 µA
Integration time 0 to 40 seconds adjustable via communication, 0 to 16 seconds
via rotary switch
Communication resistance Minimum 250Ω
Adjusting range Freely adjustable within the limits of the lower range value and
full scale value

Accuracy Reference conditions DIN IEC 770 TU = 77°F (20°C)


Accuracy data adopted after entering “low sensor calibration”
and “high sensor calibration” for lower range value and full
scale value
Linearity including Based on the Terminal Based method to IEC 770
Explanation of terms: hysteresis and repeatability To TD 10:1, ± 0.1% (± 0.05% for “platinum” versions) of set span
Above TD 10 : 1, ± 0.1% (± 0.05% for “platinum” versions)
Set Span x [upper range limit value / (set span x 10)] of the set span
LRL URL
Long term drift As a function of nominal value; 0.1% of upper range limit per
-1200 inH2O 400 inH2O 1200 inH2O year, 0.25% of upper range limit per 5 years
Turn Down (TD)
TD = URL / Set Span Upper Range Limit Effects of system pressure Metal sensor Ceramic sensor
LRL = Lower Range Limit
URL = Upper Range Limit
on the zero point URL Deviation URL Deviation
Example:
(on the span) 4 inH2O 1.5 (0.5)%/1450 psi 10 inH2O 0.5 (0.2)%/145 psi
URL = 1200 inH2O 16 inH2O 0.5 (0.2)%/1450 psi 40 inH2O 0.2 (0.2)%/232 psi
Set span = 400 inH2O
TD = 3 : 1 Values in percent of 40 inH2O 0.3 (0.2)%/1450 psi 200 inH2O 0.2 (0.2)%/1450 psi
nominal value 200 inH2O 0.2 (0.2)%/1450 psi 1200 inH2O 0.2 (0.2)%/1450 psi
(values in parenthesis 1200 inH2O 0.2 (0.2)%/1450 psi
are “Platinum” versions) 232 psi 0.2 (0.2)%/1450 psi
580 psi 0.2 (0.2)%/1450 psi
Temperature coefficient 0.04% (0.03% for “Platinum” version) of upper range limit/30 K
(14° to 140°F) and 0.1% (0.08% for “Platinum” version) of
upper range limit/30 K (-40° to 14°F or 140° to 185°F)
Thermal effects (0.2% x TD + 0.2%) of set span
Temperature coeffiecient See table of diaphragm seals for TK of the zero point on
of diaphragm seal pages 29 and 31
Response time PMD 230/FMD 230: 300 ms
PMD 235: 250 ms
FMD 630/633: depends on diaphragm seal

19
Accuracy (con’t.) Update rate Minimum 20 times per second
Rise time (T 90) 1/3 of response time
Warm-up period 2 seconds
Adjustable damping 0 to 16 s with switch, 0 to 40 s with PC or handheld terminal
Vaccum resistance PMD 230/235, FMD 230: up to 0.0145 psia
FMD 630/633: up to 0.145 psia

Application Conditions Installation conditions


Position for factory 1 2 3 4
calibration

Orientation As required, orientation-dependent zero shift can be fully


corrected, with no effect on span

Process conditions
Product temperature range PMD 230 / FMD 230: -40° to +185°F (-40° to +85°C)
in process PMD 235: -40° to +248°F (-40° to +120°C)
FMD630 / 633: to +660°F (+350°C)
Process pressure Corresponds to permissible overload, see Page 17

Ambient conditions
Ambient temperature -40° to +185°F (-40° to +85°C)
Storage temperature -40° to +212°F (-30° to +100°C)
Climatic class G P C to DIN 40 040
Vibration resistance Ceramic sensor, ± 0.1% of span (DIN IEC 68 Part 2-6)
Metal sensor, ± 0.1% of span (DIN IEC 68 Part 2-6)
Protection NEMA 4X (IP 65)
Electromagnetic compatibility Interference emission to EN 61 326 electrical equipment B,
interference immunity to EN 61 326 Annex A (industrial) and
NAMUR directive NE 21.
Interference immunity to EN 61 000-4-3, 30 V/m.
Use twisted shielded 2-wire cable.

Mechanical Construction Design


Housing T4 housing (display on side) or T5 housing (display on top).
Housing can be rotated 330°.
Separated electronics and connection compartments, optional
electrical connection via 1/2” NPT (Pg 13.5 with cable gland,
M 20 x 1.5 or G 1/2) or via Profibus-PA M12 or 7/8”
Foundation Fieldbus connector.
Process connections Optional flange or diaphragm seal with capillary extension
available, refer to Ordering Information

Materials
Housing Cast aluminum housing with protective polyester based powder
coating RAL 5012 (blue), cover RAL 7035 (grey, seawater
resistant, seawater spray test DIN 50021 (504 h) passed).
Optional 316L SS
Nameplate 304 SS
Process connections 316L SS, Steel C 22.8, or Hastelloy C 276
Process diaphragm Ceramic sensor, AI2O3 Aluminum oxide ceramic.
Metal sensor: Hastelloy C, Monel, Tantalum, or 316L SS
Fill fluid in diaphragm Silicone oil AK 100, high temperature oil, Fluorolube,
seals glycerine, vegetable oil, silicon DC 200 high temp DC 704
Seals Ceramic sensor
FPM Viton, FPM Viton oil and grease-free, Kalrez, FPM Viton
oil and grease-free for oxygen, EPDM, PTFE-bound
Hastelloy C-4 seal for pabs > 370 psi (900 mbar).
Metal sensor
FPM Viton, NBR, FPM Viton oil and grease-free for oxygen,
FPM Viton oil and grease-free, PTFE
Cover seal o-ring NBR
Mounting accessories Mounting bracket with screws, 304 SS

20
Display and Operating Interface Display and operating module
Display (optional) Plug-in display module with four-character pressure display and
analog display (bargraph) of current with 28 segments
Local operation Four keys; Z-, Z+, S-, and S+
Communication interface
Handheld terminal HART® protocol: universal HART® Communicator DXR 275 for
connecting to anywhere along the 4 to 20 mA line, minimum
resistance of 250 Ω
PC Commubox FXA 191 for connecting to a serial interface of a
PC and operating with the Communwin II operating program
for connection anywhere along the 4 to 20 mA line, minimum
resistance of 250 Ω
Profibus-PA Segment coupler for connecting to PLC or PC, e.g. with the
Commuwin II operating program
Foundation Fieldbus Via interface H1 card direct connection to PC with operating
program or via Link and interface H1 card connection to PC
with operating program

Power Supply Power supply 11.5 to 45 VDC


Residual ripple No effect for 4 to 20 mA signal up to ± 5% residual ripple within
permissible range. With communication; HART® protocol:
Upp smaller than 0.2 V (0.47 Hz to 125 Hz) and Ueff smaller
than 2.2 mV (500 Hz to 10 kHz)
Profibus-PA
Power supply 9 to 32 VDC; for IS, refer to Certificate of Conformity
Current consumption 10 mA ± 1 mA, for IS, refer to Certificate of Conformity
Power up current Corresponds to Table 4, IEC 1158-2
Foundation Fieldbus
Power supply 9 to 32 VDC, for IS, refer to Certivicate of Conformity
Current consumption 10 mA, ± 1mA
Power up current Corresponds to Table 4, IEC 1158-2

Certificates and Approvals CE Mark By attaching the CE Mark, Endress+Hauser confirms that the
instrument fulfills all the requirements of the relevant CE
directives.
Protection Refer to Ordering Information

Supplementary Documentation Deltabar S Operating instructions: BA 174P/00/en


Deltabar S Profibus-PA Operating Instructions: BA 167P/00/en
Profibus-DP/PA, Buidelins for planning and commissioning: BA 198/00/en
EMC test procedures Technical Information: TI 241F/900/en

21
Dimensions and Deltabar S housings

Mounting Details X View X


3.35"
(85) 4.09" 1.54"
4.09"
(104) (39)
(104)

3.15"
5.90" * (80)
(150)

10" 5.35" Y 0 - 25 mbar

(255) (136)

View Y
* With display

S
4.41" *

Z
(112) 4.09"
Deltabar S housing versions 3.86"
Above: T5 housing, with display on top (98) (104)
Below: T4 housing, with display on side
2.16"
• Can be rotated (55)
• Separate electornics and connection 0 - 25 mbar

compartments
10"
• Optional electrical connection via Pg 13.5
(255)
with cable gland or M 20 x 1.5, G 1/2, or
1/2” NPT
• Cast aluminum hosuing with protective
polyester-based powder coating
• Optional 316L SS
* With display

Deltabar S PMD 230

7/16 -20 UNF


M 10
8.97" * 4.25"
PMD 230 process connection and mounting (228) (108) 1.63"
Oval flange with 7/16 - 20 UNF mounting pin with T4 (41.3)
and 1/4 - 18 NPT connection housing
• Version B: C 22.8 steel 1/4-18 NPT
• Version D: 316L SS
• Version F: Hastelloy C
Oval flange with M10 mounting pin to DIN 19213 and * 10.1" with T 5 housing 2.12"
1/4 - 18 NPT connection (54) 3.78"
• Version A: C 22.8 steel (96)
• Version C: 316L SS
3.23" Mounting bracket
(82) with hardware
• Version L: 316L SS

7/16-20 UNF
PVDF
8.97" *
(228) 4.25"
with T4 (108) 1.63"
housing (41.3)

1/4-18 NPT

PMD 230 (PVDF wetted parts) process connection


and mounting 2.12" 3.78"
* 10.1" with T 5 housing
Oval flange with 7/16 - 20 UNF mounting and (54) (96)
1/4 - 18 NPT connection (in center of flange) 3.23"
• Version G: PVDF wetted part (82)

22
Ordering Information 1 2 3 4 5 6 7
PMD 230 Differential pressure PMD 230 -
transmitter with ceramic sensor
1 Certificate / Cable Entry
K Standard / M 20 x 15
5 Standard / G 1/2
S Standard / 1/2” NPT
3 M 12 Profibus-PA connector
4 7/8” Foundation Fieldbus connector
Calibration position:
L EEx ia IIC T4/T6 and ATEX II / 1/2 G, M 20 x 1.5
as shown, vertical on the oval flange 6 EEx ia IIC T4/T6 and ATEX II / 1/2 G, 1/2” NPT
I EEx ia IIC T4/T6 and ATEX II / 1/2 G, M12 Profibus-PA connector
T5 Housing J EEx ia IIC T4/T6 and ATEX II / 1/2 G, 7/8” Foundation Fieldbus connector
with display on top U FM explosion proof, Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
W FM intrinsically safe, Cl. I, II, III; Div. 1 / 1/2” NPT
V FM intrinsically safe, Cl. I, II, III; Div. 1 / 7/8” Foundation Fieldbus connector
2 CSA intrinsically safe (non-incendive), Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
2 Housing / Electronics / Communication Protocol / Display
B T5 housing / 4 to 20 mA / HART / with top display
H T5 housing / 4 to 20 mA / HART / with top cover, no display
M T4 housing / 4 to 20 mA / HART / with side cover, no display
U T4 housing / 4 to 20 mA / HART / with side display
T4 Housing D T5 housing / Profibus-PA / with top display
with display on side P T4 housing / Profibus-PA / with side display
X T4 housing / Profibus-PA / with side cover, no display
F T5 housing / Foundation Fieldbus / with top display
K T4 housing / Foundation Fieldbus / with side display
R T4 housing / Foundaiton Fieldbus / with side cover, no display
0 - 25 mbar
2 316L SS / 4 to 20 mA / HART / with display
3 316L SS / Profibus-PA / with display
4 316L SS / Foundation Fieldbus / with display
3 Ceramic sensor (wetted ceramic diaphragm)
–+ Nominal range Static pressure
1B 10 inH2O (25 mbar) 145 psi (10 bar)
2D 40 inH2O (100 mbar) 232 psi (16 bar)
–+ 3F 200 inH2O (500 mbar)
3H 1200 inH2O (3 bar)
1450 psi (100 bar)
1450 psi (100 bar)
4 Nominal range calibration technical units
1 mbar / bar
2 kPa / MPa
3 mmH2O
4 inchH2O
5 kgf / cm2
6 psi
9 Calibrated from _____ to _____, technical units, linear or square root
E Calibrated from _____ to _____, technical units, linear or square root, calibration report
5 Equipment
EA No accessories (2 blind plugs included)
ED 2 drain valves
EH 2 drain valves, 1 mounting bracket
EM 1 bracket for wall and pipe mounting
6 Sensor seal (wetted part) / lower temperature limit
1 FPM Viton / -4°F (-20°C)
3 PTFE-bound Hastelloy C-4 sealing ring, from pabs 360 inH2O (900 mbar) / -40°F (-40°C)
4 EPDM / -40°F (-40°C)
6 FPM Viton oil and grease-free for oxygen applications / -14°F (-10°C)
Tmax = 140°F (60°C), pmax = 1015 psi (70 bar)
7 Kalrez / +41°F (+5°C)
8 FPM Viton, oil and grease-free / -4°F (-20°C)
C Chemraz / +23°F (-5°C)
7 Process connection 1/4 - 18 NPT (wetted part) mounting / material
A Oval flange with M10 / C 22.8 steel
B Oval flange with 7/16 - 20 UNF / C 22.8 steel
C Oval flange with M10 / 316L SS
D Oval flange with 7/16 - 20 UNF / 316L SS
I Oval flange with M10 / Hastelloy C
F Oval flange with 7/16 - 20 UNF / Hastelloy C
G Oval flange with 7/16 - 20 UNF / PVDF

NOTE: Special versions for sensor, seal, etc. on request, consult factory

23
Ordering Information 1 2 3 4 5 6 7

PMD 235 Differential pressure PMD 235 -


transmitter with silicon sensor
1 Certificate / Cable Entry
K Standard / M 20 x 15
5 Standard / G 1/2
S Standard / 1/2” NPT
3 M 12 Profibus-PA connector
4 7/8” Foundation Fieldbus connector
Calibration position: L EEx ia IIC T4/T6 and ATEX II / 1/2 G, M 20 x 1.5
as shown, vertical on the process flange 6 EEx ia IIC T4/T6 and ATEX II / 1/2 G, 1/2” NPT
I EEx ia IIC T4/T6 and ATEX II / 1/2 G, M12 Profibus-PA connector
T5 Housing J EEx ia IIC T4/T6 and ATEX II / 1/2 G, 7/8” Foundation Fieldbus connector
with display on top E EEx ia IIC T4/T6 Zone 0, overspill protection: VbF, WHG / Pg 13.5
M EEx d IIC T5/T6 and ATEX II 2 G / M 20 x 1.5
T EEx d IIC T5/T6 and ATEX II 2 G / 1/2” NPT
U FM explosion proof, Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
W FM intrinsically safe, Cl. I, II, III; Div. 1 / 1/2” NPT
V FM intrinsically safe, Cl. I, II, III; Div. 1 / 7/8” Foundation Fieldbus connector
1 CSA explosion proof CL. I, II, III; Div. 1, Groups A - G / 1/2” NPT
2 CSA intrinsically safe (non-incendive), Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
T4 Housing 2 Housing / Electronics / Communication Protocol / Display
with display on side B T5 housing / 4 to 20 mA / HART / with top display
H T5 housing / 4 to 20 mA / HART / with top cover, no display
M T4 housing / 4 to 20 mA / HART / with side cover, no display
U T4 housing / 4 to 20 mA / HART / with side display
D T5 housing / Profibus-PA / with top display
0 - 25 mbar
P T4 housing / Profibus-PA / with side display
X T4 housing / Profibus-PA / with side cover, no display
F T5 housing / Foundation Fieldbus / with top display
+– K T4 housing / Foundation Fieldbus / with side display
R T4 housing / Foundaiton Fieldbus / with side cover, no display
2 316L SS / 4 to 20 mA / HART / with display
3 316L SS / Profibus-PA / with display
4 316L SS / Foundation Fieldbus / with display
+ – 3 Metallic sensor (Wetted metallic diaphragm) - Hastelloy C-276 is standard)
Select wetted part material, select nominal range - code requires 2 characters
Example: B D B = Hastelloy C-276 diaphragm, D = 40 inH2O range (100 mbar)
Material of wetted parts Static pressure Nominal range
B Hastelloy C-276 diaphragm 2320 psi (160 bar) A 4 inH2O (10 mbar)
H Hastelloy C-276 diaphragm 6090 psi (420 bar) C 16 inH2O (40 mbar)
4 316 SS diaphragm 2320 psi (160 bar) D 40 inH2O (100 mbar)
5 316 SS diaphragm 6090 psi (420 bar) F 200 inH2O (500 mbar)
D Monel diaphragm 2320 psi (160 bar) H 1200 inH2O (3 bar)
L Monel diaphragm 6090 psi (420 bar) L 232 psid (16 bar)
F Tantalum diaphragm 2320 psi (160 bar) M 580 psid (40 bar)
N Tantalum diaphragm 6090 psi (420 bar
4 Nominal range calibration technical units
A Nominal calibration 0.05%, mbar/bar, platinum version
C Nominal calibration 0.05%, psi, platinum version
1 mbar / bar
2 kPa / MPa
3 mmH2O
4 inchH2O
5 kgf / cm2
6 psi
9 Adjusted from _____ to _____, technical units, linear or square root
E Calibrated from _____ to _____, technical units, linear or square root, calibration report
5 Equipment
EA No accessories (2 blind plugs included)
ED 2 drain valves
EH 2 drain valves, 1 mounting bracket
EM 1 bracket for wall and pipe mounting
6 Sensor seal (wetted part) / lower temperature limit
1 FPM Viton / -4°F (-20°C)
2 NBR / -4°F (-20°C)
3 PTFE-bound Hastelloy C-4 sealing ring, from pabs 360 inH2O (900 mbar) / -40°F (-40°C)
6 FPM Viton oil and grease-free for oxygen applications / -14°F (-10°C)
Tmax = 140°F (60°C), pmax = 1015 psi (70 bar)
8 FPM Viton, oil and grease-free / -4°F (-20°C)
7 Process connection 1/4 - 18 NPT (wetted part) mounting / material
A Oval flange with M10 / C 22.8 steel
B Oval flange with 7/16 - 20 UNF / C 22.8 steel
C Oval flange with M10 / 316L SS
D Oval flange with 7/16 - 20 UNF / 316L SS
I Oval flange with M10 / Hastelloy C
F Oval flange with 7/16 - 20 UNF / Hastelloy C

NOTE: Special versions for sensor, seal, etc. on request, consult factory

24
Dimensions and Deltabar S PMD 235

Mounting Details

9.25" 7/16-20 UNF


(235) M 10 (M 12)

1.62"
3.35" (41.3) – + 1/4-18 NPT
(85)

PMD 235 process connection and mounting


2.12" 4.17"
for 4 inH2O, 16 inH2O and 580 psi
(10 mbar, 40 mbar and 40 bar) (54) (106)
• Flange with 7/16 - 20 UNF mounting 3.35"
and 1/4 - 18 NPT connection (85)
• Oval flange with M10 mounting to DIN 19213
and 1/4 - 18 NPT connection
3.94"
(100)

7/16 -20 UNF


8.66"
(220) M 10 (M 12)

2.77" 1.62"
(70.4) (41.3) +– 1/4 -18 NPT

2.13" 3.94"
PMD 235 process connection and mounting (54) (100)
for standard measuring ranges
40 inH2O, 200 inH2O, 1200 inH2O, and 232 psi 3.35"
(100 mbar, 500 mbar, 3 bar, and 16 bar) (85)
• Flange with 7/16 - 20 UNF mounting
and 1/4 - 18 NPT connection 3.78"
• Oval flange with M10 mounting to DIN 19213 (96)
and 1/4 - 18 NPT connection

25
1 2 3 4 5 6 7 8
Ordering Information FMD 230 -
FMD 230 Differential pressure
transmitter, flush mounted ceramic 1 Certificate / Cable Entry
sensor K Standard / M 20 x 15
5 Standard / G 1/2
S Standard / 1/2” NPT
3 M 12 Profibus-PA connector
4 7/8” Foundation Fieldbus connector
L EEx ia IIC T4/T6 and ATEX II / 1/2 G, M 20 x 1.5
Calibration position: 6 EEx ia IIC T4/T6 and ATEX II / 1/2 G, 1/2” NPT
I EEx ia IIC T4/T6 and ATEX II / 1/2 G, M12 Profibus-PA connector
as shown, vertical on the process flange J EEx ia IIC T4/T6 and ATEX II / 1/2 G, 7/8” Foundation Fieldbus connector
M EEx d IIC T5/T6 and ATEX II 2 G, M 20 x 1.5
T5 Housing T EEx d IIC T5/T6 and ATEX II 2 G, 1/2” NPT
with display on top W FM intrinsically safe, Cl. I, II, III; Div. 1 / 1/2” NPT
V FM intrinsically safe, Cl. I, II, III; Div. 1 / 7/8” Foundation Fieldbus connector
2 CSA intrinsically safe (non-incendive), Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
2 Housing / Electronics / Communication Protocol / Display
B T5 housing / 4 to 20 mA / HART / with top display
H T5 housing / 4 to 20 mA / HART / with top cover, no display
M T4 housing / 4 to 20 mA / HART / with side cover, no display
U T4 housing / 4 to 20 mA / HART / with side display
D T5 housing / Profibus-PA / with top display
P T4 housing / Profibus-PA / with side display
X T4 housing / Profibus-PA / with side cover, no display
F T5 housing / Foundation Fieldbus / with top display
T4 Housing
K T4 housing / Foundation Fieldbus / with side display
with display on side
R T4 housing / Foundaiton Fieldbus / with side cover, no display
2 316L SS / 4 to 20 mA / HART / with display
3 316L SS / Profibus-PA / with display
4 316L SS / Foundation Fieldbus / with display
0 - 25 mbar
3 Ceramic sensor (wetted ceramic diaphragm)
Nominal range Static pressure
2D 40 inH2O (100 mbar) 232 psi (16 bar)
3F 200 inH2O (500 mbar) 1450 psi (100 bar)
3H 1200 inH2O (3 bar) 1450 psi (100 bar)
4 Nominal range calibration technical units
1 mbar / bar
2 kPa / MPa
3 mmH2O
4 inchH2O
5 kgf / cm2
6 psi
9 Calibrated from _____ to _____, technical units, linear or square root
E Calibrated from _____ to _____, technical units, linear or square root, calibration report
5 Equipment
EA No accessories (1 blind plug included)
EC 1 bleed valve, 316 SS
6 Sensor seal (wetted part) / lower temperature limit
1 FPM Viton / -4°F (-20°C)
3 PTFE-bound Hastelloy C-4 sealing ring, from pabs 360 inH2O (900 mbar) / -40°F (-40°C)
4 EPDM / -40°F (-40°C)
6 FPM Viton oil and grease-free for oxygen applications / -14°F (-10°C)
Tmax = 140°F (60°C), pmax = 1015 psi (70 bar)
7 Kalrez / +41°F (+5°C)
8 FPM Viton, oil and grease-free / -4°F (-20°C)
C Chemraz / +23°F (-5°C)
7 Process connection 1/4 - 18 NPT (wetted part) mounting / material
A Oval flange with M10 / C 22.8 steel
B Oval flange with 7/16 - 20 UNF / C 22.8 steel
C Oval flange with M10 / 316L SS
D Oval flange with 7/16 - 20 UNF / 316L SS
I Oval flange with M10 / Hastelloy C
F Oval flange with 7/16 - 20 UNF / Hastelloy C
8 Process connection, positive side / material
BK DIN 2501 flange, DN 80 PN 10-40 / 316L SS
BM DIN 2501 flange, DN 80 PN 10-40 / ECTFE-coated
BN DIN 2501 flange, DN 80 PN 10-40 / Hastelloy C
BU DIN 2501 flange, DN 100 PN 10-16 / 316L SS
BR DIN 2501 flange, DN 100 PN 25-40 / 316L SS
BS DIN 2501 flange, DN 100 PN 25-40 / ECTFE-coated
BW DIN 2501 flange, DN 100 PN 10-16 / Hastelloy C
BT DIN 2501 flange, DN 100 PN 25-40 / Hastelloy C
DK 3” Class 150 ANSI flange / 316L SS
DM 3” Class 150 ANSI flange / ECTFE-coated
DN 3” Class 150 ANSI flange / Hastelloy C
DR 4” Class 150 ANSI flange / 316L SS
DS 4” Class 150 ANSI flange / ECTFE-coated
DT 4” Class 150 ANSI flange / Hastelloy C
NOTE: Special versions for sensor, seal,
WH 1/4-18 NPT sanitary connection with 2” extension, negative side / 316L SS
etc. on re quest, consult factory

26
Dimensions and Deltabar S FMD 230

Mounting Details 1.61"


(41)
1-5/8"
(41.3)
7/16-20 UNF
M 10 8.27"
(210)
0.06"
1/4-18 NPT
(1.6)

ø1.81"
(ø46) 0.94"
ø5.0" (24)
FMD 230 process connection and mounting (ø127)
for 3” / 4” ANSI flange, Class 150 ø6 / 4 x ø0.75"
• Version DK / DR: 316L SS (ø152.4 / 4 x ø20)
• Version DM / DS: ECTFE-coated
• Version DN / DT: Hastelloy C ø7.52"
(ø191)

41

M 10
7/16-20 UNF 41.3
210
1/4-18 NPT

ø 46
24
FMD 230 process connection and mounting
ø160 / 8 x ø22 (26)
for DN 80 PN 40 / DN 100 PN 40 Din flange (ø190 / 8 x ø26)
• Version BK / BR: 316L SS ø200
• Version BM / BS: ECTFE-coated (ø235)
• Version BN / BT: Hastelloy C

5.90"
(150)
Vent
valve
1/4-18 NPT

4.39"
(111.5)

316 SS
1.93" Ceramic
(48.9) sensor
3.94"
(100) 5.22"
5.24" (133)
(133)
Weldspud
Part No.
61001673 2.11"
(54)

3.69"
FMD 230 process connection and mounting (94)
for sanitary connection with 2” extension, 0.50"
5.98" (13)
negative side 1/4 - 18 NPT
• Version WH: 316L SS (152)

27
1 2 3 4 5 6 7 8 9
Ordering Information FMD 630 -
FMD 630 Differential pressure
transmitter with direct mount 1 Certificate / Cable Entry
diaphragm seal for level K Standard / M 20 x 15
measurement 5 Standard / G 1/2
S Standard / 1/2” NPT
3 M 12 Profibus-PA connector
4 7/8” Foundation Fieldbus connector
L EEx ia IIC T4/T6 and ATEX II / 1/2 G, M 20 x 1.5
Calibration position: 6 EEx ia IIC T4/T6 and ATEX II / 1/2 G, 1/2” NPT
as shown, vertical on the process flange I EEx ia IIC T4/T6 and ATEX II / 1/2 G, M12 Profibus-PA connector
J EEx ia IIC T4/T6 and ATEX II / 1/2 G, 7/8” Foundation Fieldbus connector
M EEx d IIC T5/T6 and ATEX II 2 G, M 20 x 1.5
T5 Housing
T EEx d IIC T5/T6 and ATEX II 2 G, 1/2” NPT
with display on top
U FM explosion proof, Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
W FM intrinsically safe, Cl. I, II, III; Div. 1 / 1/2” NPT
V FM intrinsically safe, Cl. I, II, III; Div. 1 / 7/8” Foundation Fieldbus connector
1 CSA explosion proof Cl. I, II, III; Div. 1, Groups B-G / 1/2” NPT
2 CSA intrinsically safe (non-incendive), Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
2 Housing / Electronics / Communication Protocol / Display
B T5 housing / 4 to 20 mA / HART / with top display
H T5 housing / 4 to 20 mA / HART / with top cover, no display
M T4 housing / 4 to 20 mA / HART / with side cover, no display
T4 Housing U T4 housing / 4 to 20 mA / HART / with side display
with display on side D T5 housing / Profibus-PA / with top display
P T4 housing / Profibus-PA / with side display
X T4 housing / Profibus-PA / with side cover, no display
F T5 housing / Foundation Fieldbus / with top display
K T4 housing / Foundation Fieldbus / with side display
0 - 25 mbar
R T4 housing / Foundaiton Fieldbus / with side cover, no display
2 316L SS / 4 to 20 mA / HART / with display
3 316L SS / Profibus-PA / with display
4 316L SS / Foundation Fieldbus / with display
3 Ceramic sensor (wetted ceramic diaphragm)
Nominal range Static pressure
4D 40 inH2O (100 mbar) 2320 psi (160 bar)
+– 4F 200 inH2O (500 mbar) 2320 psi (160 bar)
4H 1200 inH2O (3 bar) 2320 psi (160 bar)
4L 232 psi (16 bar) 2320 psi (160 bar)
4 Nominal range calibration technical units
1 mbar / bar
2 kPa / MPa
3 mmH2O
4 inchH2O
5 kgf / cm2
6 psi
9 Calibrated from _____ to _____, technical units, linear or square root
E Calibrated from _____ to _____, technical units, linear or square root, calibration report
5 Equipment
EA No accessories (1 blind plug included)
EC 1 bleed valve, 316 SS
6 Sensor seal (wetted part low side) / lower temperature limit
1 FPM Viton / -4°F (-20°C)
2 NBR / -4°F (-20°C)
3 PTFE-bound Hastelloy C-4 sealing ring, from pabs 360 inH2O (900 mbar) / -40°F (-40°C)
4 EPDM / -40°F (-40°C)
6 FPM Viton oil and grease-free for oxygen applications / -14°F (-10°C)
Tmax = 140°F (60°C), pmax = 1015 psi (70 bar)
8 FPM Viton, oil and grease-free / -4°F (-20°C)
7 Process connection 1/4 - 18 NPT (wetted part) mounting / material
B Flange with 7/16 - 20 UNF / C 22.8 steel
D Flange with 7/16 - 20 UNF / 316L SS
8 Process connection positive side, wetted parts 316L SS or 316 Ti SS
Refer to charts on page 30, “Order Code” column for appropriate character
9 Diaphragm seal / filling fluid (extended versions are always 316 Ti SS)
A Hastelloy / Silicone oil
D Hastelloy / high-temperature oil
F Tantalum / Silicone oil
G Tantalum / high-temperature oil
1 316L SS / Silicone oil
2 316L SS / vegetable oil
3 316L SS / glycerine
4 316L SS / high-temperature oil
5 316L SS / oil for oxygen applications

NOTE: Special versions for sensor, seal, etc. on request, consult factory

28
Dimensions and Deltabar S FMD 630

Mounting Details

0 - 25 mbar 3.94"
(100)

7/16-20 UNF
M 10

1.62"
(41.3)

5.90" 1/4-18 NPT


(150)

3.23"
(82)
FMD 630 with direct diaphragm seal

29
Dimensions FMD 630
Diaphragm seal flange and 14.2"
(360)
connection to top of
transmitter g
2

b
dM L

k
D d3

FMD 630 Diaphragm seal - mounting dimensions per ANSI B 16.5, 316L SS

Pipe
Order Nominal Mounting Diaphragm
Code Diameter Flange Holes Seal

Coefficient (for
silicone oil, for
other oils, see
Temperature
Diaphragm

Diaphragm

Diaphragm
Thickness

Weight of
Extended

Extended

Bolt Hole

Bolt Hole

page 12)
Pressure

Diameter

Diameter

Diameter

FMD 630
Nominal

Number
Length

Width
Circle
Outer

in. psi D (in.) b (in.) L (in.) d3 (in.) g2 (in.) k (in.) dM (in) Tk (mbar/10°K) lbs
P 2 150 6 0.75 NA NA 4 0.75 4.75 1.75 +2.5 19.8
R 3 150 8.25 0.937 NA NA 4 0.75 6 2.75 +1.5 24.3
S 3 150 8.25 0.937 2 3 4 0.75 6 2.75 +1.5 28.7
T 3 150 8.25 0.937 4 3 4 0.75 6 2.75 +2 33.1
Order code for U 3 150 8.25 0.937 8 3 4 0.75 6 2.75 +2 39.7
position 8 4 300 10 1.5 NA NA 8 0.937 6 2.75 +1 28.7
W

FMD 630 Diaphragm seal - mounting dimensions per DIN 2501, 316L SS

Pipe
Order Nominal Mounting Diaphragm
Code Diameter Flange Holes Seal

Coefficient (for
silicone oil, for
other oils, see
Temperature
Diaphragm

Diaphragm

Diaphragm
Thickness

Weight of
Extended

Extended

Bolt Hole

Bolt Hole
Pressure

Diameter

Diameter

Diameter

FMD 630
page 12)
Nominal

Number
Length

Width
Circle
Outer

mm bar D (mm) b (mm) L (mm) d3 (mm) g2 (mm) k (mm) dM (mm) Tk (mbar/10K) kg


A 50 10-40 165 17.8 NA NA 4 18 125 50 +2.5 9
C 80 10-40 200 23.8 NA NA 8 18 160 89 +1.5 11
D 80 10-40 200 24 50 77 8 18 160 71.5 +1.5 13
E 80 10-40 200 24 100 76 8 18 160 75 +2 15
Order code for 80 10-40 200 24 200 77 8 18 160 71.5 +2 18
F
position 8
H 100 10-25 220 20 NA NA 8 18 180 80 +1 13
G 100 25-40 235 24 NA NA 8 22 190 80 +1 13

30
1 2 3 4 5 6 7
Ordering Information FMD 633 -
FMD 633 Differential pressure
transmitter with remote seal 1 Certificate / Cable Entry
K Standard / M 20 x 15
5 Standard / G 1/2
S Standard / 1/2” NPT
3 M 12 Profibus-PA connector
4 7/8” Foundation Fieldbus connector
L EEx ia IIC T4/T6 and ATEX II / 1/2 G, M 20 x 1.5
Calibration position: 6 EEx ia IIC T4/T6 and ATEX II / 1/2 G, 1/2” NPT
as shown, vertical with diaphragm seals at the I EEx ia IIC T4/T6 and ATEX II / 1/2 G, M12 Profibus-PA connector
same height J EEx ia IIC T4/T6 and ATEX II / 1/2 G, 7/8” Foundation Fieldbus connector
M EEx d IIC T5/T6 and ATEX II 2 G, M 20 x 1.5
T EEx d IIC T5/T6 and ATEX II 2 G, 1/2” NPT
U FM explosion proof, Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
T5 Housing
W FM intrinsically safe, Cl. I, II, III; Div. 1 / 1/2” NPT
with display on top
V FM intrinsically safe, Cl. I, II, III; Div. 1 / 7/8” Foundation Fieldbus connector
1 CSA explosion proof Cl. I, II, III; Div. 1, Groups B-G / 1/2” NPT
2 CSA intrinsically safe (non-incendive), Cl. I, II, III; Div. 1, Groups A-G / 1/2” NPT
2 Housing / Electronics / Communication Protocol / Display
B T5 housing / 4 to 20 mA / HART / with top display
H T5 housing / 4 to 20 mA / HART / with top cover, no display
M T4 housing / 4 to 20 mA / HART / with side cover, no display
U T4 housing / 4 to 20 mA / HART / with side display
D T5 housing / Profibus-PA / with top display
P T4 housing / Profibus-PA / with side display
X T4 housing / Profibus-PA / with side cover, no display
F T5 housing / Foundation Fieldbus / with top display
K T4 housing / Foundation Fieldbus / with side display
R T4 housing / Foundaiton Fieldbus / with side cover, no display
2 316L SS / 4 to 20 mA / HART / with display
3 316L SS / Profibus-PA / with display
T4 Housing 4 316L SS / Foundation Fieldbus / with display
with display 3 Ceramic sensor (wetted metallic diaphragm)
on side Nominal range Static pressure *
4D 40 inH2O (100 mbar) 2320 psi (160 bar)
4F 200 inH2O (500 mbar) 2320 psi (160 bar)
4H 1200 inH2O (3 bar) 2320 psi (160 bar)
0 - 25 mbar
4L 232 psi (16 bar) 2320 psi (160 bar)
* Note pressure rating of diaphragm seal
4 Nominal range calibration technical units
1 mbar / bar
2 kPa / MPa
3 mmH2O
4 inchH2O
5 kgf / cm2
+– 6 psi
9 Calibrated from _____ to _____, technical units, linear or square root
E Calibrated from _____ to _____, technical units, linear or square root, calibration report
5 Equipment
EA No accessories (1 blind plug included)
EM 1 mounting set with screws for wall or pipe mounting
EP 4 mounting screws, 7/16 UNF, 1-1/2” length
6 Process connection, wetted parts 316L SS and diaphragm material
Refer to charts on page 32, 33, 34, and 35 “Order Code” column for appropriate order code
7 Capillary length / filling fluid
11 3 ft (1 m) capillary / silicone oil
12 6 ft (2 m) capillary / silicone oil
14 13 ft (4 m) capillary / silicone oil
18 26 ft (8 m) capillary / silicone oil
21 3 ft (1 m) capillary / vegetable oil
22 6 ft (2 m) capillary / vegetable oil
24 13 ft (4 m) capillary / vegetable oil
28 26 ft (8 m) capillary / vegetable oil
31 3 ft (1 m) capillary / high-temperature oil
32 6 ft (2 m) capillary / high-temperature oil
34 13 ft (4 m) capillary / high-temperature oil
41 3 ft (1 m) capillary / oil for oxygen applications
42 6 ft (2 m) capillary / oil for oxygen applications
44 13 ft (4 m) capillary / oil for oxygen applications
48 26 ft (8 m) capillary / oil for oxygen applications
99 Other capillary tube and filling fluid

NOTE: Special versions for sensor, seal, etc. on request, consult factory

31
Dimensions and Deltabar S FMD 633

Mounting Details

0 - 25 mbar

7/16-20 UNF

1.62" 3.35"
(41.3) (85)

2.12"
(54) 3.94"
3.35" (100)
(85)
3.78"
(96)

FMD 633 with capillary tubing

Deltabar S FMD 633 diaphragm seal, pancake style

dM

FMD 633 Diaphragm seal cell - mounting dimensions per ANSI B 16.5, 316L SS

Order Nominal Diaphragm


Code Diameter Flange Seal
diaphragm seals
One-sided

Two-sided

Weight for two


Temperature
Diaphragm

Coefficient
Thickness

Minimum
Pressure

Diameter
Nominal

Interval
Width
Outer

in. psi D (in.) b (in.) dM (in) Tk (mbar/10°K) A (in) lbs


CA 2 150/2500 3.9 0.79 2.05 +3.0 +0.5 5.0 5.7
CK 3 150/2500 5.35 0.79 3.15 +0.7 +0.1 5.0 10.1
CR 4 150/2500 6.22 0.79 3.15 +0.7 +0.1 5.0 13.6

32
Deltabar S FMD 633 diaphragm seal, flush flanged / extended flange seal

A = DA, IA 2" version


Retainer ring
g2 (DA, IA version)

dM L
g

k d3
D g
FMD 633 Diaphragm seal flange - mounting dimensions per ANSI B 16.5, 316L SS

Order Nominal Mounting Diaphragm


Flange Seal
Code Diameter Holes

Diaphragm seals
One-sided

Two-sided

Weight for two


Contact Face

Temperature
Diaphragm

Diaphragm

Coefficient
Diaphragm
Thickness

Minimum
Extended

Extended

Bolt Hole

Bolt Hole
Diameter

Diameter
Pressure

Diameter

Diameter
Nominal

Number

Interval
Length

Circle
Outer

in. psi D (in.) b (in.) g (in.) L (in.) d3 (in.) g2 (in.) k (in.) dM (in) Tk (mbar/10°K) A (in) lbs
DA 2 150 6 0.78 3.6 NA NA 4 0.79 4.75 2.05 +2.5 +0.5 5.12 11.4
DK 3 150 7.5 0.95 5 NA NA 4 0.79 6 3.15 +1.5 +0.1 5.12 15.9
1K 3 150 7.5 0.95 5 2 3 4 0.79 6 2.83 +1.5 +0.1 5.12 26.4
2K 3 150 7.5 0.95 5 4 3 4 0.79 6 2.83 +1.5 +0.1 5.12 29.5
3K 3 150 7.5 0.95 5 6 3 4 0.79 6 2.83 +1.5 +0.1 5.12 31.3
DH 4 150 9 0.95 6.2 NA NA 8 0.79 7.5 3.15 +0.7 +0.1 5.12 31.7
1H 4 150 9 0.95 6.2 2 3.7 8 0.79 7.5 3.15 +0.7 +0.1 5.12 37.9
2H 4 150 9 0.95 6.2 4 3.7 8 0.79 7.5 3.15 +0.7 +0.1 5.12 43.6
3H 4 150 9 0.95 6.2 6 3.7 8 0.79 7.5 3.15 +0.7 +0.1 5.12 49.1
IA 2 300 6.5 0.86 3.6 NA NA 8 0.79 5 2.05 +2.5 +0.1 5.12 14.9
IK 3 300 8.3 1.12 5.0 NA NA 8 0.9 6.62 3.15 +1.5 +0.1 5.12 30.9
IH 4 300 10 1.26 6.2 NA NA 8 0.9 7.88 3.15 +0.7 +0.1 5.12 51.6

Deltabar S FMD 633 diaphragm seal Tri-clamp®

dM

FMD 633 Diaphragm seal Tri-clamp - mounting dimensions, 316L SS


Pipe
Order Nominal Diaphragm
Code Diameter Tri-clamp adapter Seal
diaphragm seals
One-sided

Two-sided

Weight for two


Temperature
Diaphragm

Coefficient

Minimum
Pressure

Diameter
Nominal

Interval
Height

Width
Outer

in. psi D (in.) L (in.) dM (in) Tk (mbar/10°K) A (in) lbs


H1 1-1/2 580 2.0 1.3 1.42 +4.0 +1.0 4.0 4.4
HA 2 580 2.5 1.4 1.77 +3.0 +0.5 4.0 4.9
HK 3 580 3.58 1.1 2.81 +0.7 +0.1 4.0 5.3

33
Dimensions and Deltabar S FMD 633 diaphragm seal, Tri-clamp® flow-thru seal

Mounting Details

D d1 d2

L
FMD 633 Pipe Diaphragm seal - mounting dimensions, 316L SS
Pipe
Order Nominal Diaphragm
Code Diameter Pipe Clamp Seal

External diameter
Internal diameter

diaphragm seals
One-sided

Two-sided

Weight for two


Temperature
Coefficient

Minimum
Diameter
Pressure
Nominal

Interval
Length
in. psi D (in.) d1 (in.) d2 (in) L (in.) Tk (mbar/10°K) A (in) lbs
PR 1 580 0.89 1.71 2.0 3.54 +5.0 +0.5 5.12 7.5
P1 1-1/2 580 1.36 1.71 2.5 3.54 +3.0 +0.3 5.63 4.4
PA 2 580 1.86 2.22 2.5 3.54 +2.0 +0.2 6.06 7.3

Deltabar S FMD 633 diaphragm seal tank spud

ø5.22" FMD 633 Diaphragm seal tank spud - mounting dimensions, 316L SS
(132.7)
Order Nominal Tank spud Diaphragm
Code Diameter Extended Seal

diaphragm seals
One-sided

Two-sided

Weight for two


Temperature
Diaphragm

Coefficient
Pressure
Nominal

Height

Width

L2
in. psi L1 (in) L2 (in) dM (in) Tk (mbar/10°K) lbs
L1
WH 2 145 2.10 3.07 2.85 +0.7 +0.1 11

5.22"
(133)
dM
ø3.60" Weldspud
(91.45) Part No. 2.11"
(54)
ø3.94" 61001673
(100)

3.69"
(94)
5.98" 0.50"
(152) (13)

34
Deltabar S FMD 633 diaphragm seal varivent

Ø 3.30"
(84)

FMD 633 Diaphragm seal Varivent - mounting dimensions, 316L SS


Ø 2.95"
A (75)
Order Nominal Tuchenhagen Diaphragm
Code Diameter Verivent Seal

diaphragm seals
One-sided

Two-sided

Weight for two


1.40"

Temperature
(35.5)

Diaphragm

Coefficient

Minimum
Pressure
Nominal
0.48"

Interval
Height

Width
(12)
Ø 2.20"
mm psi in in Tk (mbar/10°K) A (in) lbs
(56)
LE 68 (2") 580 1.40 2.20 +1.5 +0.25 4.0 5.7
Ø 2.51"
(64)
Ø 2.67"
(68)

Deltabar S FMD 633 diaphragm seal 1/2” threaded

FMD 633 Diaphragm seal Off-line threaded - mounting dimensions, 316L SS

Order Nominal 1/2" NPT Diaphragm


A Code Diameter Threaded Seal

diaphragm seals
1.83"

One-sided

Two-sided

Weight for two


Temperature
(46)

Diaphragm

Coefficient

Minimum
Pressure
Nominal

Interval
Height

Width

in. psi in in Tk (mbar/10°K) A (in) lbs


1/2" NPT ∅4.00"
VR 1/2" 580 1.83 2.20 +1.5 +0.1 4.0 6.4
(100)

35
Deltabar S HART®
Program Matrix
Group Select
1 (H0) 2 (H1) 3 (H2) 4 (H3) 5 (H4) 6 (H5) 7 (H6) 8 (H7) 9 (H8) 10 (H9)

Set bias
Basic Measured Set Set Set 4mA Set 20 mA Set bias Output Pressure
1 (V0) calibration value 4 mA 20 mA automatically automatically pressure
pressure Damping
on alarm unit
automatically

Current Last
Transmitter Minimum Maximum Overload Current Minimum Maximum
2 (V2) information
diagnostic diagnostic Software no.
pressure pressure counter temperature temperature temperature Reset
code code

Lineari- Operating 4 mA after 20 mA after Unit after Density Low flow Level Table Entry Entry
3 (V3) zation mode linearization linearization linearization factor cut-off manual number level volume

Current Lower Upper


Extended Output Simulation 4 mA Upper Lower Sensor Temperature
4 (V7) parameter current
simulation
current threshold
calibration calibration
range limit range limit pressure unit
on/off pressure pressure

Pressure Pressure Lock


5 (V9) Service without bias with bias

Process Process
User Tag no. User text Device Sensor Process
6 (VA) information serial no. serial no.
connection connection Seal
diaphragm
Oil fill
P+ P–

Display field Entry field modified H position

Pressure Unit
Conversion Table
To Pa (N/m2) kPA MPa bar mbar mm H2O kg/cm2 atm inch Hg mm Hg inch H2O psi
From
Pa (N/m2) 1 10-3 10
-6
10-5 1.020 x 10-5 9.869 x 10-6
10-2 0.1020 2.953 x 10-4 7.501 x 10-3 4.016 x 10-3 1.451 x 10-4
kPA 10
3
1 10
-3
10 -2
10 102.0 0.0102 9.869 x 10 -3
0.2953 7.501 4.016 0.14505
MPa 106 10
3
1 10 104 1.020 x 105 10.20 9.869 295.3 7501 4016 145.05
bar 105 100 0.1 1 103 1.020 x 104 1.020 0.9869 29.530 750.1 401.6 14.505
mbar 100 0.1 10
-4
10
-3
1 10.20 1.020 x 10
-3
9.869 x 10-4 0.0295 0.7501 0.4016 0.0145
mm H2O 9.807 9.807 x 10
-3
9.807 x 10
-6
9.807 x 10
-5
9.807 x 10
-2
1 10-4 9.678 x 10-5 2.891 x 10-3 0.0734 0.0394 1.4224 x 10-3
kg/cm2 9.807 x 104 98.07 0.0981 0.98077 980.7 10
4
1 0.9678 28.910 734.2 393.7 14.224
5
atm 1.013 x 10 101.3 0.1013 1.013 1013 1.033 x 10
4
1.033 1 29.922 760.1 406.7 14.68
-3
inch Hg 3.386 x 103 3.386 3.386 x 10 0.0339 33.864 345.9 0.0346 0.0334 1 25.40 13.62 0.4912
-4 -3 -3 -3
mm Hg 133.3 0.1333 1.333 x 10 1.333 x 10 1.333 13.62 1.362 x 10 1.316 x 10 0.0394 1 0.5362 0.0193
-4
inch H2O 249.1 0.2491 2.491 x 10 2.491 x 10
-3
2.491 25.40 2.54 x 10
-3
2.458 x 10
-3
0.0734 1.8650 1 0.0361

psi 6.895 x 103 6.895 6.895 x 10-3 0.0689 68.948 704.3 0.0704 0.0680 2.036 51.71 27.73 1

For application and selection assistance,


in the U.S. call 888-ENDRESS

For total support of your installed base, 24 hours


a day, in the U.S. call 800-642-8737

Visit us on our web site, www.us.endress.com

United States Canada Mexico

Endress+Hauser, Inc. Endress+Hauser Endress+Hauser


2350 Endress Place Canada Ltd. Paseo del Pedregal No. 610
Greenwood, IN 46143 1440 Graham’s Lane Col. Jardines del Pedregal
Phone: (317) 535-7138 Unit 1, Burlington 01900, Mexico D.F.
888-ENDRESS ON, L7S 1W3 Mexico
FAX: (317) 535-8498 Phone: (905) 681-9292 Phone: (525) 568-2405
800-668-3199 FAX: (525) 568-7459
FAX: (905) 681-9444
Endress+Hauser
The Power of Know How

TI 256P/24/ae/01.03
© 2002 Endress+Hauser, Inc.

You might also like