in overhead systems. For the hanging on poles, m 3 HV mobile plug-in connectors 250 A / 24 kV,
in an inclined position, they are equipped with a straight or elbow (the cable characteristics
hook in accordance with EDF technical specifi- should always be specified);
cation HN 52 S 20 (1986); m polyester box equipped with Gardy circuit-
m step-down type (1); breakers:
m rated frequency: 50 Hz (6); M D 165 for 50 and 100 kVA;
m maximum ambient temperature : 40°C (5); M D 265 T for 160 kVA,
m mineral oil immersed (1); protection through thermal image tripping device:
m hermetically sealed with integral filling (1); M 3T/6T bicalibre up to 100 kVA inclusive;
m bolted cover on corrugated tank; M 7T for 160 kVA;
m ONAN type natural cooling; Note: Gardy circuit-breakers are in accordance
m anti-corrosive treatment : tank and cover fully with EDF specifications HN 63 S 11 (1984) and
hot dip galvanized; approved by EDF technical departments.
m anti-corrosive coating; m manual mechanical control, lockable in both
m final colour grey RAL 7033. positions (connected or disconnected).
The circuit-breaker box and its mechanical 50 kVA - 20 kV/400 V
standards control can not be mounted on poles of differ-
These transformers comply with (1): ent section or nature.
– IEC standards;
– French standards NF C 52-100 (1990) and Note : the above options concern usual cases
NF C 52-112-1 (1994); and are not restrictive. For other information,
– “Electricité de France” technical specification please consult us.
HN 52 S 20 (1986);
– CENELEC harmonization document
PR-HD 428-5.
basic fittings
s
Each tranformer includes: vec de
alisé a t
m 1 off-circuit tappings switch with padlocking
st g aranti ré tout élémen
located on the cover ; this switch operates on s form ateur e exempts de été pollué
n t ir
Ce tra nts neufs e ptible d’avo
the highest rated voltage to bring the transform- a
constitu pération susc
e
er to the supply voltage-actual value; u
de réc CB. as be
en
m 3 HV porcelain bushings on the cover; par des
P rmer h lly
this transfo and is tota
m 4 LV porcelain bushings - 250 A on the small at rial ’s.
w arrant th h new mate ted with PCB
side of the tank; We
c ture d wit d pa rts pollu
manu fa nd ha n
m 1 LV bushing protection (only for storage and
m seco nsform
ers.
handling); free fro o n all tra
tu ck
m 1 earthing terminal on the hanging device; Label s
m 2 lifting and untanking lugs;
m 1 rating plate fixed on the small side of the
France Transfo guarantees that its transformers are
tank; assembled using components that are both new and
m 1 filling plug; PCB-free (< 2 ppm level), in strict compliance with the
m protection index IP 00. current standards.
electrical characteristics
rated power (kVA) (1) 50 100 160
rated voltage primary (1) 15 or 20 kV
secondary at no-load (1) 400 V between phases,
231 V phase to neutral
rated insulation primary 24 kV for 20 kV
level (3) 17.5 kV for 15 kV
HV tapping range (off voltage) ± 2.5 % or ± 5 % (1)
vector group star - zigzag neutral brought-out,
Yzn 11 for 50 kVA.
delta - star neutral brought-out,
Dyn 11 for 100 and 160 kVA.
no-load 145 210 460(4) (1) others possibilities upon request, consult us.
losses (W)
load (2) 1350 2150 2350 (2) load losses and rated impedance voltage at 75°C.
(3) reminder of insulation levels :
rated impedance voltage (%) (2) 4 4 4
no-load current (%) 2.9 2.5 2.3 insulation level (kV) 7.2 12 17.5 24
voltage drop P.F. = 1 2.68 2.16 1.54 kV r.m.s. 50 Hz - 1 mn 20 28 38 50
at full load (%) P.F. = 0.8 3.92 3.73 3.43 kV B.I.L. 1.2/50 µs 60 75 95 125
efficiencies P.F. = 1 97.10 97.69 98.27
(4) Noise measure in compliance with the IEC 551 standard.
at full load (%) P.F. = 0.8 96.40 97.13 97.85 (5) other ambient temperature (45°C, 50°C, 55°C, etc.)
noise level (4) acoustic power LWA 50 49 62 upon request, consult us.
(6) other rated frequency (60 Hz) upon request, consult us.
dB(A) acoustic pressure LPA at 0,3 metre 40 39 52
GEa 01 e 22/07/98 10:34 Page 2
off-circuit 350
tappings switch filling plug N. B.
The terminal marking is in accordance with
A B C NFC 52 100 (1990), see attached diagram.
transformers with
• Edition France Transfo - BP140 F57211 Maizières-les-Metz Cedex - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 06/98
Upon request, it can be done in accordance
standards HV with IEC standards 616 (1978).
porcelain bushings
dimensions (mm)
kVA 50 100 160
A 880 960 1170
B 610 680 700
C 770 820 830
F 260 265 265
J 730 750 800
weights (kg)
total 340 490 615
mineral oil 90 110 150
M12
lifting lug
35
480
30
b
c a
n
M12 C
J
A B
off-circuit 350
tappings switch filling plug
A B C
transformers with
special “seaside” 355
355
HV porcelain bushings
dimensions (mm)
kVA 50 100 160
A 930 960 1170
B 610 680 700
C 770 820 830
J 730 750 800
weights (kg)
total 350 500 625
mineral oil 90 110 150
Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings.
Due to the evolution of standards and materials, the present France Transfo
document will bind us only after confirmation from our techni-
cal department. BP 10140
F 57281 Maizières-lès-Metz Cedex
tel. (+33) 87 70 57 57 - fax (+33) 87 51 10 16
Ref : GEa 01 e
GEa.02 e 22/07/98 14:40 Page 1
m
description m
1 draining device;
protection index IP 00.
This range consists of transformers complying
with the following specification: options
m three-phase transformers, for indoor or out-
kV r.m.s. 50 Hz - 1 mn 20 28 38 50
kV B.I.L. 1.2/50 µs 60 75 95 125
earthing terminal
off-circuit tappings switch dimensions and weights
lifting lug
Typical dimensions and weights are indicated in
the table below for mineral oil immersed
transformers.
They are provided for 20 kV / 400 V transformers
with electrical characteristics, as described in
Groupe Merlin Gerin · Usine de Maizières-lès-Metz (Moselle) France nº 216540
J 40 (2)
Ø = 125(1) K J 38 (3) N. B.
A B
(1)
The terminal marking is in accordance with IEC
for 3150, Ø = 200
(2) for 3150, 80 standards 616 (1978), see attached diagram.
F F (3) for 3150, 60
off-circuit tappings switch
earthing
terminal
earthing
terminal 1W 1V 1U C B A
2W 2V 2U 2N n c b a
D* : height over LV protection cover ; assembly
filling
possible only if the HV is fitted with plug-in
plug connectors.
Edition France Transfo - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 09/96
H H H
dimensions (mm)
kVA 100 160 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150
A 1000 1100 1160 1295 1315 1495 1510 1695 1810 1850 1930 2160 2550 2700
B 700 710 860 895 915 925 940 975 975 1000 1220 1250 1830 1840
C 900 965 1010 1060 1150 1215 1225 1395 1495 1555 1575 1685 1690 1795
D* 1250 1315 1360 1410 1500 1565 1575 1745 1905 1965 1985 2195 2200 2305
F 265 265 265 265 265 265 265 265 265 265 265 265 265 265
H 75 75 150 150 150 150 150 150 150 170 170 170 170 170
J 520 520 520 670 670 670 670 670 670 670 820 820 820 820
K 105 105 105 105 105 105 105 105 85 85 85 85 85 85
flat-bars — — 1250A 1250A 1250A 1250A 1250A 1250A 1600A 2500A 2500A 3150A 5000A 5000A
porcelain LV 250A 250A 630A 630A 630A 1000A 1000A 1600A 1600A 2500A 2500A 3150A 4000A 5300A
weights (kg)
total 550 700 1000 1165 1350 1545 1740 2100 2390 2850 3500 3880 4640 5730
mineral oil 110 150 215 275 310 350 380 450 580 670 790 870 1130 1230
31,5 12 31,5
97,5
250
50 87
221
52
52
45
45
1600A
with elbow mobile with straight mobile
1250A 2500A 3150A 5000A
connector connector
LV porcelain bushings (compulsory for 100 and 160 kVA) HV porcelain bushings
Ø 63 h10 Ø 65 h10
Ø 56 M 12
Ø 40 Ø 50 h10
Ø 30 h10 h10 h10
Ø 16 160 100 Note : never use HV
h10 120 120 140
M 12 80
35 porcelain bushings
60 300
300
295
315 350
330
with LV protected
215 250
35 165 by a terminal cover.
Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings.
Due to the evolution of standards and materials, the present France Transfo
document will bind us only after confirmation from our technical BP 10140
department.
F 57281 Maizières-lès-Metz Cedex
tel. (+33) 03 87 70 57 57 - fax (+33) 03 87 51 10 16
Ref : GEa.02 e
GEa.04d 22/07/98 14:45 Page 1
description options
This range consists of transformers complying The following fittings may be provided as an
with the following specification : option :
m three-phase transformers, for indoor or out- m 1 conservator (for breathing type transformer)
sides ; des
é avec
m 2 earthing terminals on the cover ; g aran ti réalis ut élément
st to
ateur e exempts de été po
llué
m 4 bi-directional flat rollers ; nsform
m 2 lifting and untanking lugs ;
Ce tra nts neufs et ptible d’avoir
a e
constitu pération susc mineral oil immersed transformer
m 1 rating plate to be fixed on 1 of the 4 sides ; u
de réc CB. been 5000 kVA, 20/6 kV.
par des
P r has
m 1 filling plug ;
tra n sforme d is totally
is n
m 1 draining device ; that th w material a with PCB’s.
arrant e
m protection index IP 00. We w tured with n parts polluted
c
manufa second hand .
free fro
m formers
all trans
ab el stuck on
L
electrical characteristics
rated power (kVA) (1) 2500 3150 4000 5000 2500 3150 4000 5000
rated insulation primary 7.2 - 12 - 17.5 - 24 36
level (4) secondary 7.2 -12 7.2 - 17.5
HV tapping range (off-voltage) ± 5 (1) ± 5 (1)
(1) others upon request, consult us.
vector group Dyn 11 or YynO (1) Dyn 11 or YynO (1) (2) load losses and rated impedance voltage at 75°C.
no-load 3.35 4.5 5 6 4 4.5 5.5 6.5 (3) classification of dielectrics according to NF C 27-300 :
losses (kW) m O1 for mineral oil ;
load (2) 32 29 33 40 25 30 34 41
m K3 for silicone oil.
rated impedance voltage (%) (2) 6 7 7 7.5 6.5 7 7 7.5 (4) reminder of insulation levels :
no-load current (%) 1.8 1.6 1.4 1.3 2.1 1.9 1.8 1.6
rated insulation 7.2 12 17.5 24 36
voltage drop at P.F. = 1 1.45 1.16 1.07 1.08 1.21 1.19 1.09 1.10 level (kV)
full load (%) P.F. = 0.8 4.62 5.02 4.96 5.26 4.76 5.05 4.98 5.28 kV r.m.s. 50 Hz - 1 mn 20 28 38 50 70
load P.F. = 1 98.61 98.95 99.06 99.09 98.85 98.92 99.02 99.06 kV B.I.L. 1,2/50 µs 60 75 95 125 170
100 % P.F. = 0.8 98.26 98.69 98.83 98.86 98.57 98.65 98.78 98.83 (5) other ambient temperature (45°C, 50°C, 55°C, etc…) upon
efficiencies (%) request, consult us.
load P.F. = 1 99.87 99.13 99.22 99.25 99.05 99.10 99.19 99.22
(6) other rated frequency (60 Hz) upon request, consult us.
75 % P.F. = 0.8 98.60 98.91 99.03 99.06 98.81 98.88 98.98 99.02 (7) breathing type with conservator, upon request, consult us.
GEa.04d 22/07/98 14:45 Page 2
D
N. B.
draining
Edition France Transfo - BP140 F57211 Maizières-les-Metz Cedex - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 02/96
The terminal marking is in accordance with IEC
device
standards 616 (1978), see attached diagram.
E
earthing
terminal
A
filling
plug
earthing 2N 2U 2V 2W
terminal
1U 1V 1W B
HV porcelain bushings
Ø 30
M 12 Ø 16
80
330 (23/24kV)
250 (7,2/23kV)
35
490 (36kV)
62 407
312
290
255 locking
locking 87 lug
lug
(1) Breathing type transformer with conservator.
(2) For dimensions of other plug-in connectors, please,
consult us.
with elbow mobile connector with straight mobile connector
Casual arrangements such as bars and cables supports, flexible connectors, etc… are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings.
Due to the evolution of standards and materials, the present France Transfo
document will bind us only after confirmation from our technical BP 140
department.
F 57211 Maizières-lès-Metz Cedex
tel. (+33) 87 70 57 57 - fax (+33) 87 51 10 16
Ref : GEa.4 d
GEa.05 c 22/07/98 14:51 Page 1
M
description M
1 protective relay and eventually, on request:
1 parallel operation device;
This range consists of transformers complying M 1 voltage regulator with voltage drop equalizer;
with the following specification: M 1 remote indicator of tap changer position.
m three-phase transformers, 50 or 60 Hz,
m magnetic level indicator (with or without
for indoor or outdoor use (installation to be contact, please specify);
specified); m HV fixed plug-in connectors HN 52 S 61:
m maximum ambient temperature: 40°C (5);
M 250, 400, 630 or 1250 A - 24 kV;
m mineral oil immersed (other dielectric upon
M 400, 630 or 1250 A - 36 kV.
request); m HV mobile plug-in connectors HN 52 S 61,
m breathing type with conservator ;
straight or elbow (the cable characteristics
m cover bolted on tank or welded bell type as
should be specified);
per specification; m condenser bushings;
m ONAN, ONAF, ODAF or ODWF cooling type;
m increased creepage distance bushings;
m standard anti-corrosion surface treatment
m 1 bonnet on HV bushings:
and coating (1); M in the air for connection by dry cables or bus-
m final colour grey RAL 7033 (1).
ducts (except rated insulation level 72.5 kV) ;
M oil immersed, hermetically sealed for cable Transformer 20/25 MVA, 65/20 kV with on-load tap
standards connection; changer, ONAN/ONAF type cooling.
These transformers comply with the following M SF6 immersed, hermetically sealed for
tripping);
m 1 dial type thermometer (without contact);
ec des
m 4 directional flat rollers; lisé av
t g aranti réa ut élément
s to
m lifting and/or untanking lugs;
ateur e exempts de été po
llué
nsform
m 1 rating plate; Ce tra nts neufs et ptible d’avoir
a e
m 1 filling plug; constitu pération susc
u
m 1 draining device and treatment valve with de réc CB. been
par des
P er has
sampler. is transform and is totally
that th w material with PC
B’s.
arrant e
We w tured with n parts polluted
options manu fac
m seco
nd han
d
.
free fro formers
The following fittings may be provided as an all trans
abel stuck on
option: L
m 1 on-load tap changer in the main tank
(generally ± 12% - 19 positions maximum) with: France Transfo guarantees that its transformers are
M 1 motor drive unit fitted on tank;
assembled using components that are both new and
M 1 tap changer compartment in the conservator
PCB-free (< 2 ppm level), in strict compliance with the
with a level indicator; current standards.
(1) other possibilities upon request, please consult us.
(2) load losses and rated impedance voltage at 75°C.
(3) each type of cooling device comes with its particular type
of equipment (circulators, ventilators, etc.).
cooling type
electrical characteristics él of natural through
ONAN
m
ODAF ONAF
m
ODWF
Typical characteristics are indicated in the table It is possible to develop equipment with totally oil thermosiphon
below up to 30 MVA / 72.5 kV. Above, please different values of voltage and rated impedance directional through m m
circulators
consult us. They correspond to transformers of voltage. In this case, dimensions and weights of natural through m
ONAN type cooling (3), with or without tap are also different. tank air convection
changer. forced m m
through fans
forced through m
rated power (3) 5 10 20 25 5 10 20 25 30 water circulation
(MVA)
rated primary 24-36 72.5 (4) reminder of insulation levels:
insulation secondary 7.2 - 12 - 17.5 - 24 7.2 - 12 - 17.5 - 24 rated insulation 7.2 12 17.5 24 36 52 72.5 90 123
level (kV) (4) level (kV)
rated 8 9 10 11 8 9 10 11 11
impedance voltage (%) (2) (5) other ambient temperature (45°C, 50°C, 55°C, etc.) upon
request, consult us.
GEa.05 c 22/07/98 14:51 Page 2
Edition France Transfo - SA au capital de 10 280 000 FRF - RCS Metz B 357 801 109 • Imprimé en France • Composition et illustrations : COREDIT • 09/96
montage possible uniquement lorsque la MT
C
est équipée de prises embrochables.
E B
Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings.
Due to the evolution of standards and materials, the present France Transfo
document will bind us only after confirmation from our BP 10140
technical department.
F 57281 Maizières-lès-Metz Cedex
tel. (+33) 03 87 70 57 57 - fax (+33) 03 87 51 10 16
Ref : GEa.05 c