Permissive:
Disch v/v closed
Suction Pressure > 0.5 kg/cm2
Atleast minimum time elapsed after starting of last SWBP
ACW P/P
Permissive:
L/O relay reset
Disch v/v closed
Level in O/H tank > 1.7 M
Atleast minimum time elapsed after starting of last P/P
Trip:
L/O relay operated
Emergency switch operated
Auto start
ACW P/P on auto &
Runninig ACW P/P trip &
Dischrge header pressure Lo &
Atleast minimum time elapsed after starting of last P/P
Air Compressor
Trip:
LO pressure Low
LP stage 1 or 2 dischrge air temp. Hi
HP stage dischrge air temp. Hi
Motor O/L
Breaker protection operated ( Inst. O/C, O/C with time delay
Remark:
Stn air to Inst. Air CV air fail- Opn
Inst. Air Hdr pr.CV maintains 0.3bar dp.& Air fail- Close
Air Drier
Trip:
Lack of oil
Refrigerent high pressure
Refrigerent low pressure
High current
HMP
Auto start:
Any HMP running for > 5 sec & hdr pr. ≤ 3 bar
Runninig HMP trip
CEP
Permissive:
Suction V/V open
HW Lvl OK ( -50 mm)
Seal water pr. OK ( 3 bar)
Dischrge V/V closed or Hdr pr. > 8 bar
L/O relay reset
Trip:
L/O relay operated
Emergency stop switch operated
dp strainer Hi ( > 0.6 bar) - Not i/s
Locked rotor current trip = 6 * FLC
Instan. O/C trip = 10*FLC
Time O/C trip = 1.2*FLC
Minimum R/C flow = 100 Kg/s, Max flow through R/C = 166.7 kg/s
Auto start:
CEP auto ON
CEP trip or dischrge Hdr pr. < 18 bar
CEP disch. v/v opening permissive:
Dischrge hdr pr. > 8 bar
CEP suction. v/v closing permissive:
5 sec elapsed after CEP stopping
Heater drip pump
Permissive:
Seal water pr OK
Drain receiver lvl not lo
Lockout relay reset
Trip:
Emergency stop switch operated
Drain receiver lvl lo
Lockout relay operated.
Winding temp high 120 deg
Locked rotor current trip = 6 * FLC
Inst O/C trip = 10 * FLC
Time O/C trip = 120%FLC
MBFP
Permissive:
Lub oil pressure > 0.8 bar
Lub oil tank level > 50%
Minimum flow 100% open
Warm up valve closed
No reverse rotation
Lockout relay reset
Dea lvl Ok
Up stream isolating valve of 25% & 100% CV closed or disc hdr pr OK
cooling water flow OK
Suction V/V open
(Any one STBFP trip & MBFP on auto S/B ) or barrel top & bottom differential temp < 30 deg with control ckt 3 off
Trip:
MBFP running & LO Pr < 0.5 bar for 1 sec
MBFP running & flow lo lo Pr < 0.5 bar for 10 sec
MBFP running & W/U valve not closed
Reverse rotation
lockout operated
dea lvl lo lo
shaft disp > 1.5mm
BP or MP S/S DP > 0.6 bar for 15 sec
Suction V/V not open
2/3 FW hdr pr hi-hi
both temp of radial brg left or right HH
both temp of Axial brg left or right HH
Emergency trip switch operated.
MBFP Auto S/B ON results in opening of isolating valves of 100% & 25% CV & AC oil pump auto start
MBFP Auto S/B ON results in opening of isolating valves of 100% & 25% CV & AC oil pump auto start
MBFP auto S/B put off under following conditions 1) Discharge hdr pressure low or MBFP trip criteria present
MBFP LO system
Permissive for AC LOP:
Lvl in oil tank OK
Criteria for auto starting of LOPs
MBFP auto S/B On & LO Pr < 1 bar or MBFP stopped or MBFP startup programme step 1 for starting or AC oil pu
auto & LO Pr < 1 bar for 2 Sec
Criteria for auto starting of LOPs on protection
MBFP reverse rotation starts AOP & EOP both & LOPs on auto & lub oil pressure < 0.7 bar starts EOP
Permissive for stopping AC LOP
MBFP stopped or oil pump on auto + MBFP running for more than 46 sec + lub oil Pr > 3 bar
Permissive for stopping DC LOP
MBFP stopped or AC oil P/P running & LO Pressure > 0.8 bar
Criteria for auto stopping of AC LOP
MBFP LOP on auto & LO Pr > 3 bar & MBFP running for 40 Sec
Criteria for auto stopping of AC LOP
MBFP LOPs on auto & LO Pr ≥ 3 bar
STBFP
Permissive:
1 Disch v/v & its B/P v/v closed
2 Suction v/v open
3 deaerator lvlv ok
4 No reverse rotation
5 W/U cv closed
6 temp differential of barrel top & bottom < 30 deg
7 W/U control off
8 R/C V/V full open
9 Lub oil pr > 0.8 bar
Trip:
1 Pump Trip Criteria
2 Shaft displacement > max (1.5mm)
3 Suction v/v not 100% open
4 Dearator lvl lo lo (-585 mm)
5 reverse rotation
6 Turbine reset & W/U v/v not closed
7 MP or BP S/S Dp > 0.6 bar for 10 sec
8 Emergency trip switch operated.
9 R/C V/V not 100% open & flow < min for 10 sec
10 Turbine reset & lub oil pressure < 0.5 bar for 1 sec
11 Radia brg or axial brg temp hi-hi (90 deg)
12 FW hdr pr hi hi ( not in service)
13 Turbine trip Criteria
14 Control oil pr low (2.5 bar)
15 Gov oil pressure low for 10 sec (4 bar)
16 LO pr very low (1 bar)
17 exhaust temp very hi (140 degC)
18 O/S mech & elect (6174 rpm)
19 Emergency trip switch operated.
20 remote trip
21 BFP fault & BFP fault not bypassed
22 Axial shift hi (0.7mm)
23 Vacuum lo lo (0.5)
* STBFP suction v/v opening permissive, its B/P v/v open & STBFP speed is 0 rpm.
STBFP reverse rotation results in closing of following v/vs 25% CV isolating v/vs ( up & down stream), 100% di
* its B/P v/v & booster stage isolating v/v
Auto starting of S/B AOP
BFP turbine running & running AOP trips or BFP reverse rotation & LO pressure low Or Lub oil pressure low.
AOP stopping criteria
Other AOP running & turbine speed > zero & stop command from UCP or field OR turbine speed is zero & stop co
given
DC JOP interlock
JOP switch on auto & turb speed < 500 rpm
TG Interlock for auto open
TG on auto & Turb speed < 100 rpm & LO pr OK & JO Pr > 55 bar
TG Interlock for manual open
TG V/V on manual & LO Pr OK & JO Pr OK & open command given from local panel.
Engage / disengage coupling interlock
JO pr OK & Engage / disengage switch in engage position & Lub oil pr OK & turbine speed = zero & coupling not
Criteria for disengaging
Turbine trip & engage/disengage switch in disengage condition & coupling not disengage & speed < 100 rpm
Exhaust valve
closing interlock: Closes if local switch is on auto & turbine is in tripped condition or closes when close command
from local/UCB panel provided turbine is in tripped condition
Vacuum Pump
Permissive:
1 solenoid v/v closed &
2 inlet v/v closed &
3 other vacuum p/p startup sequence not in progress &
4 air water seperatoe tank lvl normal &
For pump start command from UCP 1) respective p/p switch on remote (at local cabinet) 2) Holding selection off (
5A
Vacuum p/p ON command from UCB
5B For local starting. 1) bypass, inlet v/v opening & circulation p/p starting is done from respective switchgear module
pump switch in local cabinet tobe put on 'Local' selection & local start/stop to be given
Vacuum bkr
Opens when 1) Fire protection operated 2) When vacuum bkr partial open command is given from CR , vacuum b
first & then closes when condenser pr ≥ 0.88 bar
HPLP BP
High speed TCV protection close criteria
1) MFT or 2) Water injection pr low or 3) Down stream temp hi
Normal speed TCV protection close criteria
Above 1 or 2 or 3 or 4) Manual close commad from HS valve & HS v/v ≤ 15% open
High speed TCV protection open criteria
1) Generator trip or 2) Turbine trip or 3) Load shedding relay operated
Normal speed TCV protection open criteria
Above 1 or 2 or 3 or 4) Manual open commad for TCV (HS) valve & HS TCV <15% open
Block the open criteria(TCV):
1) TCV (HS) > 15% & 2) Protection or manual open command for TCV (HS)
High speed PCV protection close criteria
1) MFT or 2) Water injection pr low or 3)Downstream temp hi
Normal speed PCV protection close criteria
Any condition for PCV(HS) closing & PCV (HS) almost close.
High speed PCV protection open criteria
1) gen trip or 2) turb trip or 3)load shedding relay operation, 4) Actual steam Pr > set point & any of PCV block op
condition not present.
Normal speed PCV protection open criteria
Any condition for PCV(HS) opening & PCV (HS) open> 95%
Block the open criteria PCV (HS)
1) TCV ≤ 15% open & PCV (HS) close
Block the open criteria PCV ( Normal Speed)
Any condition for PCV (HS) opening or closing present & it is not opened or closed respectively.
7 kg/s
hdr pr OK
ing of LOPs
BFP startup programme step 1 for starting or AC oil pump on
LOPs on protection
s on auto & lub oil pressure < 0.7 bar starts EOP
ing AC LOP
S/B AOP
lock
O Pr > 55 bar
nual open
& Lub oil pr OK & turbine speed = zero & coupling not engaged
ngaging
ion & coupling not disengage & speed < 100 rpm
ve
on close criteria
hi
ion close criteria
mmad from HS valve & HS v/v ≤ 15% open
on open criteria
operated
tion open criteria
ia PCV (HS)
V ( Normal Speed)
Vacuum
> 0.9 0.885bar 0.7(T)
HPBP
Down stream temp 320 400
spray water pressure
LPBP
Vacuum 0.9 0.4
steam temp after LP 50 90
spray water pressure 23 8.5
steam pressure after 0.14
Remark
TRIP
Alarm
Alarm
Alarm/ 18 bar S/b p/p cuts in
Alarm
Alarm./ Trip
C
Alarm
alarm
W/U valve opens at Dt > 30 degC
at load < 400 MW
Start permit at 50%
trip
trip
trip
alarm
trip
trip
trip
trip
trip
alarm
trip
trip
trip
yes
alarm
alarm
alarm
trip
trip
trip
trip
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
ineffective
alarm
trip
trip S/B Vac P/P cuts in at -0.83 bar
Protection close
open permissive at 12 bar
protection close
Capability= 252 MW
NPSH 2.2
Upper limit for extraction pressure of heater 6 ( without time bar) is 44.8 bar
In special cases at no load Htr 6 steam temperature may go upto 500 deg
422
280
49
295
275
0.1
5.9
280
49.08
STBFP
STBFP minimum speed 1180 rpm
coasting down after tripping from full load with vacuum 25 min
critical speed: 7550 rpm
Normal O/P with steam flow 11.43 kg/s 6038KW
Max O/P 8500 KW
Normal speed 5556 rpm
Max speed 5940 rpm
speed range 1180 - 5940 rpm
EHC operating range 1120 - 6160 rpm
MHC operationg range 2800 - 6160 rpm
Pressure
specified initial steam pr: 7.067 kg/cm2
Permissible deviation at no load operation: 7.42 kg/cm2
Permissible deviation instaneously for a total duration of 12 hrs p.
a.: 8.4 kg/cm2
Turb exhaust pr.: 0.122 kg/cm2