Professional Documents
Culture Documents
Paper 0134
Paper 0134
this paper. Both devices use a fixed voltage source and a insulation oil on copper contacts is according to [6]:
−6 3.862 0.3559
test current of 1ADC to measure the resistance. A short
circuit at the secondary side of the transformer also allows a
s = 1.883 *10 θ 0 t (1)
fast response of the test current. Dynamic resistance Where s is the thickness of the oil film layer in Å, θ0 is the
measurements use this fast response to detect increased contact surface temperature in ˚C and t the duration of the
contact resistances. When applied to a power transformer, aging test in hours.
DRM is able to detect deviant contact resistances when the To form a representative artificial oil film layer, simulation
on-load tap changer switches. These deviant resistances can parameters are selected based on the transformer population
be caused by the long term aging effect on the change-over of a Dutch utility. The average age of power transformers is
selector contacts or by other defects inside the OLTC. 30 years. The long-term effect is measured (using DRM) at
transformers of at least 25-35 years old. The population of
transformers with disruptions in the DRM current pattern
EXPERIMENTS WITH OLTC CONTACTS has an average age of 40 years.
Measurement setup
Laboratory experiments on several aged tap changer
contacts are performed to get more insight in the way aged
contacts influence the dynamic resistance. Different stages
of aging are considered. A test model is used for testing
artificial tap changer aging. The test model is connected in
series with the power transformer that is tested. The design
of the test model is based on a common selector switch type
tap changer in the Netherlands. The model consists of one
phase of this tap changer and uses resistors to simulate the Fig. 3. An undisrupted current pattern as measured with dynamic
transformer windings. Fig. 2 shows a schematic resistance measurement on the test model. The slope of the current
representation of the test model. profile is caused by resistors that simulate the winding resistance
of the transformer's regulating windings. Each time the tap
changer selects another tap; its transition resistors shortly change
the test current.
Paper 0134
Fig. 7. The time that the transition resistor is used for each tap
change operation. The arcing contact of contact 3 is worn. This
results in longer use of the transition resistor.
Paper 0134
CONCLUSION
This paper focused on the contact diagnosis of on-load tap
changers for high voltage power transformers using DRM.
In particular the following can be concluded:
1. The contact deterioration of OLTC’s can be
described by different aging mechanisms.
2. Modelling and laboratory investigation of the
deterioration processes is helpful to gain more
systematic knowledge about the applicability of
DRM.
3. Dynamic resistance measurements provide more
information about the contact status compared to
static resistance measurements.
4. Laboratory investigation has shown that light aging
(the thin oil film layer as presented above) is not
measured with DRM while advanced aging (coking)
Fig. 8. Left: a stator contact of the tested change-over selector is measurable. Thick artificial coking is measured at
suffered from the long term effect. Deep pitting and coking is every measurement while a thin layer of artificial
visible at the top, the oil film layer is visible in the middle. Right: coking tends to break due to contact pressure and is
silver plated stator contacts are measured after the overhaul. therefore not always measured.
5. Transitions resistors are used longer when the arcing
The measured tap changer is a common selector switch type contacts are worn and this can be measured by DRM.
tap changer in the Netherlands and is almost equal to the 6. Laboratory experiments and a test case showed that
laboratory model used for the experiments described above. DRM is indeed effective for assessing the long term
However, this tap changer has a change-over selector which effect on the tap changer contacts.
doubles the number of tap positions. DRM data from this
tap changer showed deteriorated contacts due to the long
term effect. Based on these diagnostic measurements, it was REFERENCES
decided to overhaul the transformer and to plate the contacts [1] R. Jongen, et. al., 2007, “A statistical approach to
of the change-over selector with silver. processing power transformer failure data”, Cired
All aging and damage from the long term effect was 19th International Conference on Electricity
removed during this overhaul. The tap changer has been Distribution, Paper 546.
tested extensively before and after this process. Fig. 8 [2] H.F.A.Verhaart, 1994, “Tussenrapport over
shows two representative stator contacts of this tap changer. faaloorzaken van distributie- en
Typical DRM data before (collapsed current pattern) and koppeltransformatoren op basis van de onvoorziene
after cleaning (undisrupted current pattern) are shown in fig. niet-beschikbaarheid.”, KEMA rapport 43613-T&D
9. It can be clearly seen that the dynamic resistance 94-102278.
measurement is very sensitive for the long term effect on [3] EPRI, December 2006, “Evaluation of load tap
the aged change-over selector contacts. changer oil for susceptibility to coking.”, from
www.epriweb.com.
[4] H. F. A. Verhaart, 1995, “A diagnostic to determine
the condition of the contacts of the tap changer in a
power transformer,” in Proc. CIRED, Brussels,
Belgium, paper 1.13.
[5] P. Seitz, et al., 2008, “Advanced on-site diagnosis of
power transformers”, International conference on
condition monitoring and diagnosis, paper 148.
[6] K. Lemelson, 1973, “About the failure of closed
heavy current contact pieces in insulating oil at high
temperature.”, IEEE transactions on parts, hybrids,
and packaging, vol. Php-9, no.1.
[7] Z. Wang, Y. Liu, P.J. Griffin, 2000, “Artificial
Intelligence in OLTC Fault Diagnosis Using
Fig. 9. A typical dynamic resistance current pattern as recorded Dissolved Gas-In-Oil Information.”, IEEE Power
before (top) and after (bottom) the tap changer was cleaned. The Engineering Society Summer Meeting, Volume 4,
tap changer suffered from the long term effect. 2422-2427.