Motor Starters

Type MN
Direct-On-Line Starters
l

Star-Delta Starters
l
Larsen & Toubro Limited, India’s largest
manufacturer of low voltage switchgear
products introduces the new MN range of
starters. These starters are available in
Direct-On-Line (DOL) and Star-Delta versions.
This range represents the culmination of
intensive R&D and extensive field trials.
MN starters, comprising MNX contactors and
MN relays, provide Overload and Single
phasing protection to your motors.

MN starter family conforms to IS13947-4, IEC 60947-4

Starter
Range
Operational Details
Salient Features Relay Setting
Conform to IS 13947 (Part 4) & IEC 60947-4
l A screwdriver is used to set the relay
Built-in single phasing protection
l indicator (which is on the dial) to the
In Star Delta Starters, Star contactor has
l full load current setting. This ensures
same rating as Hold-on & Delta optimum protection under Overload and
Suitable for Industrial & Rural applications
l Single Phasing of the motor. In case of
Terminal block for ease of termination
l
Star-Delta Starters, the relay must be set
Starter enclosure with IP 540 of protection
l
at the values In / 3 (0.58 In) as given in
the selection table, since the connected
relay carries only the phase current in
Applications Motors having Delta connected winding.

MN starters are available in following versions:


MN DOL starters
Direct-On-Line starter
l

Semi automatic Star-Delta, starter (SASD)


l lMN 16, 25, 32, 45, 65 DOL starters
Fully automatic Star-Delta, starter (FASD)
l incorporate type MNX contactors.
lMN 16, 25, 32 DOL starters
All MN DOL & Star-Delta starters are suitable incorporate MN 2 relays.
for 3-Phase Squirrel Cage motors. MN DOL lMN 45, 65 DOL starters incorporate
starters are available in following ratings: MN 5 relays.
MN 16 DOL-upto 10 HP (7.5kW)
l

MN 25 DOL-upto 15 HP (11kW)
l

MN 32 DOL-upto 20 HP (15kW)
l MN Star-Delta Starters
MN 45 DOL-upto 30 HP (22.5kW)
l
MN Star-Delta starters are available in
MN 65 DOL-upto 45 HP (33.5kW)
l
semi automatic and fully automatic
versions.
MN Star-Delta starters are available in
following ratings:
MN 16, 25, 32, 45, 65, 80, 110, 140
MN 16 Star-Delta-upto 15 HP (11kW)
l Star-Delta starters incorporate type
MN 25 Star-Delta-upto 25 HP (18.5kW)
l MNX contactors.
MN 32 Star-Delta-upto 35 HP (26kW)
l

MN 45 Star-Delta-upto 50 HP (37.5kW)
l lMN 16, 25, 32, Star-Delta starters
MN 65 Star-Delta-upto 75 HP (55kW)
l incorporate MN 2 relays.
MN 80 Star-Delta-upto 90 HP (67.5kW)
l l MN 45, 65, 80, 110, Star-Delta starters
MN 110 Star-Delta-upto 125 HP (90kW)
l
incorporate MN 5 relays.
MN 140 Star-Delta-upto 175 HP (130kW)
l
lMN 140 Star-Delta starters
incorporate MN 12L relays.
MN 45, MN 65, MN 80, MN 110 & MN 140
Star-Delta starters are available only in FASD
version. In case of SASD Starters, the motor
gets connected in Star connection when
the green button is pressed, after
releasing the green button motor gets
Construction connected in Delta connection. The
MN starters consist of MNX contactors & MN button must be released only when the
relays. The relay is directly mounted on the motor reaches its normal speed.
contactor. The colour of the sheet steel enclosure
is two-toned. The box is powder coated and gray In case of FASD Starter, motor gets
in colour. The cover is powder coated with ivory connected in Star connection, when
colour. The push button is flush mounted in an the green button is pressed. An electronic
enclosure cover, which has been given an timer automatically performs the change-
altogether ‘new look’. over function from Star to Delta.

1
Different sized holes with grommets
at top & bottom for various cable sizes IP54 Protection class of enclosure
makes it suitable for
industrial and rural applications.

Earthing screw with Two-tone colour Better corrosion resistance Flush-mounted


proper marking combinations with box in through powder coated push buttons.
steel gray & cover in ivory enclosure

Features & Benefits


Single Phasing Protection Base Plate Mounting Simultaneously ‘Alarm Contact’ (97-
98) will close. The motor cannot be
MN relays having phase failure MN Star-Delta starters are mounted restarted until the relay has been
sensitive tripping mechanism on base plate that can absorb reset. To reset the relay, allow the
provides reliable protection against vibrations and it makes MN starters bimetals to cool down sufficiently &
Single Phasing & Overload maintenance friendly. push this button to reset the trip
conditions. MN relays are contact (95-96).
compensated for variation in ambient Electronic Timer
temperature from -5OC to 55OC. MN Fully Automatic Star-Delta If the relay is in reset condition,
starters are provided with Electronic pressing this push-button will open
IP 54 degree of protection Timer for high repeat accuracy. ‘Trip Contact’. But now the alarm
Corrosion resistant powder coated contact will not close. This indicates
enclosure with IP/54 protection class Trip Test Facility healthy operation of the relay
makes MN starters most suitable for This facility enables the user to mechanism. The trip contact will
chemical factories, polluted industrial manually check the operation of the again close when this button is
and dusty agricultural environment. trip mechanism. Move the trip slide in released.
the direction shown on the relay. The
Terminal Block relay trips with an audible ‘Click’ Auto-Manual Reset Switch
MN Star-Delta starters are provided sound, indicating that the trip There are two modes of reset
with terminal block with proper mechanism is in good working order. available : Manual and Auto. By
terminal marking for ease of wiring. default the relay is in the Manual reset
Terminal block can accommodate Off / Reset Push-Button mode and can be converted to Auto
both aluminium & copper cables. The relay will trip in case of overloads reset mode by moving the switch to
or single phasing conditions. Auto position marked on the label.

2
Chart for MN DOL starters
Maximum Motor Rating Approx. Full Recommended
Load Relay Switch
Type at 415V, 3 O, 50Hz Range Relay Back-up HRC Fuse Disconnector
Current In Contactor
(A) (A) Fuse Unit
HP KW Type Rating (A)

2 1.5 3.5 3-5 HF 16 FN 32


2.5 1.8 4.8 3-5 HF 16 FN 32
3 2.2 5 4.5 - 7.5 HF 16 FN 32

MN 16 4 3 6.2 4.5 - 7.5 HF 20 FN 32


MN 2 MNX 18
DOL 5 6 - 10 HF FN 32
3.7 7.5 20
6 4.5 9 6 - 10 HF 25 FN 32
7.5 5.5 11 9 - 15 HF 32 FN 32
10 7.5 14 9 - 15 HF 32 FN 32
7.5 5.5 11 9 - 15 HF 32 FN 32

MN 25 10 7.5 14 9 - 15 HF 32 FN 32
MN 2 MNX 25
DOL 12.5 14 - 23 HF FN 63
9.3 18 50
15 11 21 14 - 23 HF 63 FN 63
15 11 21 20 - 33 HF 63 FN 63
MN 32 HF FN 63
17.5 13 24 20 - 33 MN 2 MNX 32 63
DOL
20 15 28 20 - 33 HN/100 63 FN 100

MN 45 25 18.5 35 30 - 50 HN/100 80 FN 100


MN 5 MNX 45
DOL 30 22.5 40 30 - 50 HN/100 80 FN 100
30 22.5 40 30 - 50 HN/100 80 FN 100
35 26 47 30 - 50 HN/100 100 FN 100
MN 65
MN 5 MNX 70
DOL 40 30 55 45 - 75 HN/100 100 FN 100
45 33.5 60 45 - 75 HN/100 100 FN 100

Selection Chart for MN DOL Starters

Chart for Star-Delta starters


Maximum Motor Rating Approx. Full Phase Relay Recommended Switch
at 415V, 3 O, 50Hz Load Back-up HRC Fuse
Type Current Range Relay Contactor Disconnector
Current In in / 3 (A) Fuse Unit
HP KW (A) Type Rating (A)

10 7.5 14 8.08 6 - 10 HF 20 FN 32
MN 16
SASD/ 12.5 9.3 18 10.4 9 - 15 MN 2 MNX 18 HF 32 FN 32
FASD
15 11 21 12.1 9 - 15 HF 32 FN 32

MN 25 20 15 28 16.2 14 - 23 HF 40 FN 63
MN 2 MNX 25
SASD/ 25 18.5 35 20.2 14 - 23 HF 50 FN 63
MN 32 30 22.5 40 23 20 - 33 HF 63 FN 63
SASD/ MN 2 MNX 32
FASD 35 26 47 27 20 - 33 HN/00 63 FN 100
40 30 55 31.8 30 - 50 HN/00 63 FN 100
MN 45
45 33.5 60 34.6 30 - 50 MN 5 MNX 45 HN/00 80 FN 100
FASD
50 37.5 66 38.2 30 - 50 HN/00 80 FN 100
60 45 80 46.2 45 - 75 HN/00 100 FN 100

MN 65 65 48.5 87 50 45 - 75 HN/00 100 FN 100


MN 5 MNX 70
FASD 70 52 94 54.5 45 - 75 HN/00 125 FN 125
75 55 100 57.5 45 - 75 HN/00 125 FN 125
MN 80 MN 5 MNX 80
FASD 90 67.5 120 69.2 45 - 75 HN/0 160 Fn 200

MN 110 100 75 135 77.9 66 - 110 HN/0 160 FN 200


MN 5 MNX 110
FASD 125 90 165 95 66 - 110 HN/0 200 FN 200

MN 140 150 110 200 115 90 - 150 HN/1 250 FN 250


MN 12L MNX 140
FASD 175 130 230 132.8 90 - 150 HN/1 250 FN 250

Selection Chart for MN Star-Delta Starters

3
Ordering Information - MN DOL Starter*
Example: MN 16 DOL - 240V with relay range 9-15 A
Ordering Information - SS94015BOBO

Srarter Type Version MN 16 MN 25 MN 32 MN 45 MN 65


Cat. No. SS94351 SS94352 SS94353 SS94017 SS94018
Rated control
Relay Range
voltage (Us) VAC
3.0 - 5.0 — — — — —
4.5 - 7.5 — — — — —
6.0 - 10 — — — — —
9.0 - 15 — BOBO — — —
240
14 - 23 — BODO — — —
20 - 33 — — BOEO — —
30 - 50 — — — — —
45 - 75 — — — — —
3.0 - 5.0 COSO — — — —
4.5 - 7.5 COUO — — — —
6.0 - 10 COVO — — — —
9.0 - 15 COBO COBO — — —
360
14 - 23 — CODO — — —
20 - 33 — — COEO — —
30 - 50 — — — — —
45 - 75 — — — — —
3.0 - 5.0 DOSO — — — —
4.5 - 7.5 DOUO — — — —
6.0 - 10 DOVO — — — —
9.0 - 15 DOBO DOBO — — —
415
14 - 23 — DODO — — —
20 - 33 — — DOEO — —
30 - 50 — — — DOGO —
45 - 75 — — — — DOJO

Ordering Information - MN Star- Delta Starter*


Example: MN 16 SASD - 360V with relay range 9-15 A
Ordering Information - SS94019COBO

Srarter Type Version MN 16 MN 25 MN 32 MN 45 MN 65 MN 80 MN 110 MN 140


SASD SS94361 SS94363 SS94365 — — — — —
Cat. No. SS94021 SS94022 SS94705 SS94706 SS94707
FASD SS94362 SS94364 SS94366
Rated control Relay
voltage (Us) VAC Range
6.0 - 10 COVO — — — — — — —
9.0 - 15 COBO — — — — — — —
14 - 23 — CODO — — — — — —
20 - 33 — — COEO — — — — —
360
30 - 50 — — — — — — — —
45 - 75 — — — — — — — —
66 - 110 — — — — — — — —
90 - 150 — — — — — — — —
6.0 - 10 DOVO — — — — — — —
9.0 - 15 DOBO — — — — — — —
14 - 23 — DODO — — — — — —
20 - 33 — — DOEO — — — — —
415
30 - 50 — — — DOGO — — — —
45 - 75 — — — — DOJO DOJO — —
66 - 110 — — — — — — DOKO —
90 - 150 — — — — — — — DOMO

* Note: These are the stnadard combinations of relay and contactor. Any other combinations can be supplied on request.
4
Overall Dimensions
4 MOUNTING HOLES O 6

375
430
219

185

235 136

188 4 MOUNTING HOLES O 8.5


O 34

105 128 2.3

139
DOL Starters O 26 SASD & FASD Starters
MN 16, MN 25, MN 32 MN 16, MN 25, MN 32
252
324

649

577
200 142
352 153

146 4 MOUNTING HOLES O 8.5 O 38 297 4 MOUNTING HOLES O 8.5


O 38

O 26 DOL Starters O 26 FASD Starters


MN 45, MN 65 MN 45, MN 65

453
212.6
430

725
147.5

483
519
2 HOLES O 39 2 HOLES O 34 4 MOUNTING HOLES O 11
218.9

FASD Starters
MN 80F, MN 110F, MN 140F

5
For selection and product demonstration, please contact any of our branch offices listed below:

REGISTERED OFFICE AND L&T House A28,Indira Nagar


HEAD OFFICE Group MIG - 5 Faizabad Road
L&T House, Ballard Estate Padmanabhpur Lucknow 226 016
P. O. Box 278 Durg 491 001 Uttar Pradesh
Mumbai 400 001 Tel: 0788-2200105, 2322809 Tel: 0522-4040905 / 902 / 903
Tel: 022-67525656 Fax: 0788-2210161 Fax: 0522-2311671
Fax: 022-67525858 e-mail: esp-Lko@Lntebg.com
Website: www.Larsentoubro.com A1/11, Astronauts Avenue
Bidhan Nagar Plot No. 518
ELECTRICAL STANDARD PRODUCTS (ESP) Durgapur 713 212 4th Main Road
501, Sakar Complex Tel: 0343-2536891 / 952 K.K. Nagar
Opp. Gandhigram Rly. Station Fax: 0343-2536493 Madurai 625 020
Ashram Road e-mail: esp-dgp@Lntebg.com Tel: 0452-2537404/303
Ahmedabad 380 009 Fax: 0452-2537552
Tel: 079-55304007-11, 55304000/1 (Faridabad Switchgear Works) e-mail: esp-mdu@Lntebg.com
Fax: 079-26580491 12/4, Delhi-Mathura Road
e-mail: esp-ahm@Lntebg.com Faridabad 121 003 North Wing, Level II,
Tel: 0129-2277543, 2275314 Gate 7, Powai
38, Cubbon Road, Post Box 5098 Fax: 0129-2275405 Mumbai 400 072
Bangalore 560 001 e-mail: esp-fbd@Lntebg.com Tel: 022-67052287 / 2661 / 2737
Tel: 080-25020100 / 325 Fax: 022-67051112
Fax: 080-25580525 Milanpur Road, Bamuni Maidan e-mail: esp-bom@Lntebg.com
e-mail: esp-blr@Lntebg.com Guwahati 781 021
Tel: 0361-2550565 8B, Farmland, Ramdaspeth
131/1, Zone II Fax: 0361-2551308 Behind Hotel Radhika
Maharana Pratap Nagar e-mail: esp-gau@Lntebg.com Nagpur 440 010
Bhopal 462 011 Tel: 0712-2420641 / 24
Tel: 0755-4233907 / 8 / 9 5-10-173, Fateh Maidan Road Fax: 0712-2420619
Fax: 0755-2769264 P. O. Box 12 e-mail: esp-ngp@Lntebg.com
e-mail: esp-bho@Lntebg.com Hyderabad 500 004
Tel: 040-23296468 32, Shivaji Marg, P.O. Box 6223
Plot No. 559, Annapurna Complex Fax: 040-23242356 New Delhi 110 015
Lewis Road e-mail: esp-hyd@Lntebg.com Tel: 011-41419500 / 1, 41419515
Bhubaneswar 751 014 Fax: 011-41419600
Tel: 0674-2537301, 2436696 D-24, Prithvi Raj Road e-mail: esp-del@Lntebg.com
Fax: 0674-2537309 C-Scheme
e-mail: esp-bbi@Lntebg.com Jaipur 302 001 L&T House, P.O. Box 119
Tel: 0141-2341385/386 191/1, Dhole Patil Road
SCO 32, Sector 26-D Fax: 0141-2373280 Pune 411 001
Madhya Marg, P. O. Box 14 e-mail: esp-jai@Lntebg.com Tel: 020-26135048, 26135611
Chandigarh 160 026 Fax: 020-26129586, 26124910
Tel: 0172-2790750 / 151 Akashdeep Plaza, 2nd Floor e-mail: esp-pnq@Lntebg.com
Fax: 0172-2792764 P. O. Golmuri
e-mail: esp-chd@Lntebg.com Jamshedpur 831 003 3rd Floor, Vishwakarma Chambers
Jharkhand Majura Gate, Ring Road
10, Club House Road Tel: 0657-2433673 Surat 395 002
Chennai 600 002 Fax: 0657-2341250 Tel: 0261-2473726
Tel: 044-28462072 / 4 e-mail: esp-jam@Lntebg.com Fax: 0261-2477078
Fax: 044-28462102 e-mail: esp-sur@Lntebg.com
e-mail: esp-maa@Lntebg.com Skybright Bldg.
M.G. Road Radhadaya Complex
67, Appuswamy Road Ravipuram Junction Old Padra Road
Post Bag 7156 Ernakulam Near Charotar Society
Opp. Nirmala College Kochi 682 016 Vadodara 390 015
Coimbatore 641 045 Tel: 0484-4409422-27 Tel: 0265-6613610/11/12
Tel: 0422-2588120, 2588123 Fax: 0484-4409430 Fax: 0265-2336184
Fax: 0422-2588148 e-mail: esp-cok@Lntebg.com e-mail: esp-bar@Lntebg.com
e-mail: esp-cbe@Lntebg.com
3-B, Shakespeare Sarani 48-8-16, Dwarakanagar
Kolkata 700 071 Visakhapatnam 530 016
Tel: 033-44002301/2/3/4/5, 44002572 Tel: 0891-2755493, 2704928
Fax: 033-22822589 Fax: 0891-2746075
e-mail: esp-ccu@Lntebg.com e-mail: esp-viz@Lntebg.com

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Electrical Standard Products


Larsen & Toubro Limited
Powai Campus, Mumbai 400 072
Tel: 022-6705 0505
Fax: 022-67051324 / 1746
E-mail: esp@LNTEBG.com
Website: www.LNTEBG.com

SP 01936 R 10407