You are on page 1of 44

‡ Fuseal

‡ Fuseal
Easy and Reliable Solution for Corrosive
Waste Piping Systems

Electrofusion and Mechanical Joining of Pipe


and Fittings
• Fuseal II
• Fuseal 25/50 PVDF
• Fuseal Squared Double Containment

www.us.piping.georgefischer.com 7.1

*07_001-023 1 6/7/02, 11:38 AM


Not for Use with Compressed Air or Gases
George Fischer, Inc. DOES NOT RECOMMEND the use of thermoplastic piping products for systems to transport
or store compressed air or gases, or the testing of thermoplastic piping systems with compressed air or gases in
above or below ground locations. The use of George Fischer, Inc. products in compressed air or gas systems
automatically voids George Fischer, Inc. warranty for such products, and their use against our recommendation is
entirely the responsibility and liability of the installer. George Fischer, Inc. will not accept responsibility for damage
or impairment from its products, or other consequential or incidental damages caused by misapplication, incorrect
assembly, and/or exposure to harmful substances or conditions.

Threaded fittings are not recommended for pressure applications.

For more information about any of our product lines, please call (800) 854-4090.
7.2 ¬ ‡

*07_001-023 2 6/7/02, 11:38 AM


‡ Fuseal
Table of Contents
Fuseal II .................................................................................. 7.5
Introduction ................................................................................................................. 7.6
System Overview .................................................................................................................7.8
Fusion Control Unit ..............................................................................................................7.9
Specifications and Material Properties
Fuseal II and Fuseal LD Suggested Specification Guide ...................................... 7.10
Fuseal MJ Suggested Specification Guide ............................................................... 7.12
Material Physical Properties ........................................................................................... 7.13
Fuseal II Installation and Engineering Data ..........................................................7.14
Thermal Expansion Compensation .............................................................................. 7.14
Instructions for Above Ground ...................................................................................... 7.18
Instructions for Underground ......................................................................................... 7.18
Specifications for MSA 250SE/EX Fusion Units ...................................................... 7.20
Plastic Piping and Fire ..................................................................................................... 7.21
Protection Methods .......................................................................................................... 7.22
Fuseal II Dimensions
Fuseal Pipe .......................................................................................................................... 7.24
7
Fuseal Small Diameter Fittings ...................................................................................... 7.25
Fuseal LD (Large Diameter Fittings) ............................................................................. 7.39
Fuseal MJ (Mechanical Joint Fittings) ......................................................................... 7.43

Fuseal 25/50 PVDF ............................................................ 7.47


Introduction ...................................................................................................................................... 7.48
Fuseal 25/50 PVDF Dimensions ............................................................................................. 7.50
Specifications and Material Properties
Fuseal 25/50 PVDF System Suggested Specification Guide ............................. 7.55
PVDF Material Physical Properties .............................................................................. 7.57
Fuseal 25/50 PVDF System Installation & Engineering Data
Thermal Expansion Compensation ............................................................................. 7.57
Expansion Loops, Offsets, Change of Direction ..................................................... 7.58
Restraints ............................................................................................................................. 7.59
Support During Installation ........................................................................................... 7.60
Support Spacing .............................................................................................................. 7.61
General Properties of PVDF .......................................................................................... 7.61

Fuseal Squared .................................................................... 7.65


Introduction ...................................................................................................................................... 7.66
Fuseal Squared Fitting Dimensions ....................................................................................... 7.68
Specifications and Material Properties
Fuseal Squared Suggested Specification Guide ................................................... 7.72
Material Physical Properties ..........................................................................................7.74
Fuseal Squared Installation & Engineering Data
Thermal Expansion Compensation ............................................................................. 7.75
Instructions for Buried Installation ............................................................................... 7.75

www.us.piping.georgefischer.com 7.3

*07_001-023 3 6/7/02, 11:38 AM


7.4 ¬ ‡

*07_001-023 4 6/7/02, 11:38 AM


‡ Fuseal II
‡ Fuseal
Easy and Reliable Solution for Corrosive
Waste Piping Systems

Electrofusion and Mechanical Joining of Pipe


and Fittings

www.us.piping.georgefischer.com 7.5

*07_001-023 5 6/7/02, 11:38 AM


‡ Fuseal Offers: Applications Flame Retardant
+ GF + Fuseal’s excellent chemical and Polypropylene
• Electrofusion and physical properties make the system
Mechanical Joint The +GF + Fuseal flame retardant
ideal for handling corrosive chemical
System polypropylene compound yields a
waste solutions present in laboratory
combination of high chemical resis-
and industrial DWV applications.
+ GF + Fuseal is suitable for use in tance, toughness and high strength at
• Handles corrosive
elevated temperatures.
drainage fluids up to chemical and industrial plants as well
212°F (100°C) inter- as in hospital and university laborato-
mittently ries where mixtures of acids, bases The Perfect Union
and solvents are drained. An engineer or contractor can
• High chemical and combine the benefits of the +GF +
corrosion resistance Fuseal electro-fusion joint and the
Excellent Corrosion, Chemical mechanical joint in a single system.
• Flame retardant +GF + Fuseal can be used in
Polypropylene and Environment Resistance inaccessible areas and the +GF +
+GF + Fuseal is resistant to the corro- Fuseal mechanical joint works well
• Highly reliable, under bench where speed of
multiple fusion tech- sive action of alkalis, alcohols, acids,
solvents and salt solutions. Dilute min- installation or future disassembly is
nologies that offer the needed.
most innovative and eral acids and aqueous solutions of
advanced in the acid salts, which are so destructive to The same MSA 250SE or MSA
industry most metals, have no affect on the 250EX machine can be used to fuse
+GF + Fuseal system. In general, +GF + the +GF + PPro-Seal Natural Polypro-
Fuseal is attacked only by strong oxi- pylene Piping System and the Fuseal
dizing acids and weakened by cer- 25/50 PVDF System. +GF + PPro-Seal
tain organic solvents and chlorinated is a pressure system (up to 150 psi,
hydrocarbons. +GF + Fuseal will not 10 bar) which can handle basically
rust, pit, scale, corrode or be affected the same fluids as +GF + Fuseal.
by electrolysis.
In above ground installations, the pig- The +GF + Fuseal 25/50 PVDF
mentation protects the system from System offers pipe and fittings that
sunlight. The pigmentation is highly can not only handle high temperatures
resistant to ultraviolet radiation and is (up to 280° F) and a wide range of
heat-stabilized to provide long life chemicals, but is also flame retardant
while handling hot reagents. and does not generate smoke.

Improved ‡ Fuseal
Fusion Collar
The +GF + Fuseal Process has been
improved through the development of
the +GF + Fuseal fusion collar. The
new fusion collar provides the same
joint as the original +GF + Fuseal coil,
however, it can be made in less time.
The many improved benefits include:
• Fast positive electrical connection
with a duplex clear plug
• Simple insertion of pipe without coil
removal
• Elimination of socket sanding
• Elimination of the temporary band
clamp — clamps are provided with
fusion collars for sizes 1 1/2"–3"
• Rotation of fusion collar allows
exact positioning of the duplex plug
• Ability to dry fit an entire system
prior to fusion
7.6 ¬ ‡

*07_001-023 6 6/7/02, 11:38 AM


‡ Fuseal II
Mechanical Joint MSA 250SE / MSA 250EX
Make fast, leakproof joints in two The MSA 250SE and the MSA
easy steps. Slide the nut, grab ring 250EX represent the most ad-
and seal ring on the pipe. Insert the vanced fusion technology in the
pipe into the socket and tighten 1/2 industry, featuring advanced trans-
turn past hand tight. That’s it! former technology. This unit can be
As the nut is tightened, the grab ring used to join all George Fischer
grips and cuts a retaining groove in Sloane polypropylene products,
the pipe. Further tightening seals the including Fuseal II, Fuseal Squared,
polypropylene ring to ensure a leak- PPro-Seal, and Fuseal 25/50 PVDF.
proof joint. The MSA 250 can run on both
network (110v/60Hz) and genera-
This simple method of joining cuts tor power sources.
installation time in half and requires
no hot water, electricity, or pipe All required fusion parameters are MSA 250 Fusion
grooving. programmed into the MSA 250 by Control Unit
simply scanning a barcode specific • Developed using
to each fitting. Barcodes also pro- proven technology
vide the capability to perform pro- with a global part-
gram updates for new products in ner, Breutsch Elec-
the field. tronics, Inc.
• Advanced trans- 7
The MSA 250 has multiple joint former technology
capability as well as a built-in fail- allows lightweight
safe mode. design
• Fuses on both net-
work and generator
power sources
• Easy operation
based on scanning
barcodes
• Program updates
Product Range for new products
Fittings Connection Dimensions Material
performed in the
field
• Fuseal II New Electrofusion 1 1/2" - 6" Flame Retardant • Operates on 110v/
Process Polypropylene
60Hz power source
• Fuseal LD Original Electrofusion 8"/10"/12" Non Flame Retardant
(Large Diameter) Process Polypropylene
• Built-in fail-safe
• Fuseal MJ Mechanical 1 1/2" - 4" Flame Retardant
mode
(Mechanical Joint) Polypropylene • Multiple joint capa-
bility
Pipes Dimensions Material • Digital read-out for
• Schedule 40 1 1/2" - 8" Flame Retardant all pertinent operat-
(Bluish Color) Polypropylene ing parameters
• Schedule 40 1 1/2" - 12" Non Flame Retardant
(Black Color) Polypropylene
• Schedule 80 1 1/2" - 12" Non Flame Retardant
(Black Color) Polypropylene

Double Containment System


for Optimum Protection
For optimum protection of the environ-
ment the +GF + Fuseal System can be
combined with the unique +GF +
Contain-It Double Containment Sys-
tem. Due to its split fittings and pipe,
the clear PVC system can be installed
even after the +GF + Fuseal System is
tested.
www.us.piping.georgefischer.com 7.7

*07_001-023 7 6/7/02, 11:38 AM


System Overview
Fuseal II products are all manufactured provide long life while handling hot
of polypropylene, a material that is reagents.
known to have wide acceptance as a
superior thermoplastic material for The Fuseal II flame retardant polypropy-
handling harsh, corrosive fluids. lene compound yields a combination of
high chemical resistance, toughness and
Because of the chemical resistance, high strength at elevated temperatures.
solvent cementing is not an option for
this heavy duty material. Thus, George Fuseal II's excellent chemical and
Fischer engineers developed a coil physical properties make the system
fusion process to easily and effectively ideal for use in chemical and industrial
join these systems. plants as well as hospital and university
laboratories. In fact, all major pharma-
Following are brief descriptions of the ceutical and universities have Fuseal
features of these systems. installations currently installed.

Fuseal II The following features make Fuseal II


faster and easier to install than our
Fuseal II is available in sizes 11/2" - 12". original Fuseal piping system.
It handles temperatures up to 180°F.
• Fast electrical connection with the
Fuseal II is resistant to the corrosive duplex plug.
action of alkalies, alcohols, acids,
solvents and salt solutions. Dilute mineral • Fusion collar stays on fitting—pipe
acids and aqueous solutions of acid inserts easily without the extra step of
salts, which are so destructive to most removing the coil and placing it on
metals, have no effect on the Fuseal II the pipe.
system.
• Plastic clamps are provided with 11/2"
In general, Fuseal II is attacked only by through 3" fusion collars. Metal band
strong oxidizing acids and weakened by clamps are available for 4"–12"
certain organic solvents and chlorinated fittings. Both styles of clamps allow
hydrocarbons. Fuseal II will not rust, pit, for dry-fitting of the entire system
scale, corrode or be affected by elec- prior to fusing.
trolysis.
• Fusion collar is rotatable to allow
exact positioning of the duplex plug.
In above ground installations the pig-
mentation is highly resistant to ultra- • Band clamps on each socket allow
violet radiation and is heat-stabilized to dry fit of entire system before fusion.

Fuseal LD
Fuseal LD is our large diameter Fuseal
Band Clamp piping system. This is available in 8", 10"
and 12" sizes and it utilizes our original
fusion process. Also made of flame
resistant polypropylene, Fuseal LD offers
all the basic system benefits of Fuseal II.
Fusion Collar
Fuseal MJ
Fuseal MJ is our mechanical joint system.
It is available in sizes 11/2" - 4". This
system is also made of the same flame
retardant material as our Fuseal II
system, however, there is no fusion
process. The joints are mechanically
joined for a nonpermanent joint in easily
accessible locations, such as under sinks.

7.8 ¬ ‡

*07_001-023 8 6/7/02, 11:38 AM


‡ Fuseal II
MSA 250 Electrofusion Unit

Cord to power supply

Power cable
to fitting

Scroll button

Start button

Display screen

Barcode pen

www.us.piping.georgefischer.com 7.9

*07_001-023 9 6/7/02, 11:38 AM


Sample Short Form Specifications and Materials Properties
Fuseal II Piping
Specification Fuseal II and Fuseal LD Submittals
Catalog Data: Contractor shall sub-
Suggested Specification mit___ copies of manufacturer's litera-
All Fuseal II fittings shall Guide
be as manufactured by ture on the Fuseal II and Fuseal LD
George Fischer Sloane, systems. The literature shall contain
Inc. so that they are The following guide specifications can complete and current installation
compatible with Fuseal be used when preparing project orders instructions.
pipe. All Fuseal pipe or inquiries for George Fischer, Fuseal II
shall conform to the and Fuseal LD, Corrosive Waste Piping Part 2 — Product
dimensional require- System. Two forms are included:
ments of ASTM D-1785 a general and a short form specifica-
for schedule 40/80 Manufacturer
tion. The laboratory corrosive drainage
pipe as produced by
George Fischer Sloane, waste and vent system shall be Fuseal II
Inc. The Fuseal II system (11/2"-6") and Fuseal LD (8", 10" & 12")
shall be joined by use
General Specification as manufactured by George Fischer
of electrical resistance Part 1 — General Sloane, Inc.
coils energized by a
variable low voltage Materials
power supply. The Special Waste Pipe and Fittings
Special Waste and Vent Pipe and Fitting The products described in this specifica-
Fuseal II fusion collar tion consist of:
will have an integral System shall be +GF+ Fuseal polypropy-
electrical resistance lene as manufactured by George
coil which is joined to Fischer Sloane, Inc. in Little Rock, Arkan- A. Pipe and fittings made of flame
the power supply via a sas as described below. Piping installed retardant polypropylene joined by
duplex connector. Each below grade shall be non-flame retar- electrical fusion coils made of
fusion collar will be dant polypropylene. Pipe and fittings conductive metal wire coated with
furnished with a band installed above grade shall be flame polypropylene and molded into a
clamp. retardant polypropylene. flame retardant polypropylene fusion
collar.
Quality Assurance B. Joining Method — The pipe and
The Fuseal system shall be manufac- fittings are joined by use of the
tured to the following ASTM Standards: electrical fusion collars energized by
a low-voltage power supply.
D 4101 - Standard Specification for
Propylene Plastic Injection and Extrusion C. Basic Materials — This specification
Materials. covers flame retardant polypropy-
D 3311 - Standard Specification for lene (PPFR) pipe and fittings made
Drain, Waste and Vent (DWV) Plastic from PPFR plastic, as defined in
Fittings Pattern. ASTM D 4101 Propylene Plastic
D 1785 - Standard Specification for Injection and Extrusion Materials.
(PVC) Plastic Pipe, Schedule 40, 80 and Flammability requirements are based
120 (Dimensional requirements only). on ASTM
D 1599 - Test Method for Short-Time
Hydraulic Failure Pressure of Plastic Pipe, D 635, Standard Test Method for
Tubing and Fittings. Rate of Burning and/or Extent and
D 2122 Test Method of Determining Time of Burning of self supporting
Dimensions of Thermoplastic plastics in a horizontal position.
Pipe and Fittings. D. Compound — The PPFR compound
F 1290 - Standard Practice for used in the pipe and fittings covered
Electrofusion Joining Polyolefin Pipe and by this specification shall meet the
Fittings. requirements of Class PP110B63153
F 1412 - Standard Specification for material as described in ASTM
Polyolefin Pipe and Fittings for
Corrosive Waste Drainage Systems. D 4101 . As other compounds are
shown to be suitable for these
products, such compounds will be
added to this specification.

7.10 ¬ ‡

*07_001-023 10 6/7/02, 11:38 AM


‡ Fuseal II
Source Quality Control F. Fittings — Shall be legibly marked
with molded-on letters showing
A. Pipe Dimensions — Requirement, pipe manufacturer’s trademark, pipe size
shall be produced to Schedule 40 of each socket, manufacturer’s part
and Schedule 80 Iron Pipe Sizes number, NSF-CW-SE and symbol
dimensional standards and shall PPFR indicating the material.
meet the dimension and tolerances
for outside diameter.
Part 3 — Execution
B. Fittings, Design and Dimensions —
Requirements, fittings design shall be Installation
based upon the laying length dimen- A. Fuseal II, Fuseal MJ and Fuseal LD
sions in ASTM D 3311 DWV Plastic pipe and fittings shall be installed
Fitting Patterns. according to the current installation
instructions as published by the
C. Electrical Fusion Collars (11/2"- 6") — manufacturer.
Each coil shall consist of polypropy-
lene jacketed wire, mandrel wound B. A manufacturer’s representative, who
and heat fused on the outer surface has been certified as a training
and molded into a self-supporting instructor, shall be at the site prior to
fusion collar with an integral duplex the day the piping system installation
receptacle. Each collar shall be is to commence. A manufacturer’s
provided with a ratchet style plastic rep. will perform a complete training 7
clamp for sizes up to 3". 4" and 6" session on the proper method of
fittings will require the use of the steel installation for the piping system.
band clamps that must be ordered Upon completion of the training, the
separately. installers will be given a test on the
items covered in the session. Persons
D. Electrical Fusion Coils (8"-12") — successfully completing the test shall
Each coil shall consist of polypropy- be given a laminated card which
lene jacketed wire, mandrel wound certifies them for one year as install-
and heat fused on the outer surface. ers of the Fuseal piping system.
These coils shall be inserted and
taped in place within the fusion
sockets of all LD fitings at the factory. Testing
Properly sized steel band clamps Joints may be pressure tested 10 minutes
(ordered separately) will be required after fusing, (30 minutes for 10" and
for proper fusion of fittings to pipe 12"). Test in accordance with local
during installation. plumbing codes. All sections of the
system shall be tested with a maximum
E. Pipe Markings — Schedule 40 PPFR, of 30-foot head of water.
Flame Retardant, shall be bluish in
color, Group 1-63153, manufactured
in 10-foot lengths. Schedule 40 PPRO,
Non-Flame Retardant, shall be black
in color, Group 1-53653 manufac-
tured in 20-foot lengths. Schedule 80
PPRO, Non-Flame Retardant shall be
black in color, Group 2-53653
manufactured in 20-foot lengths.
All previously listed lengths of pipe
shall be marked with +GF+, Fuseal,
NSF-CW-SE, Pipe Size, Schedule,
Type, Quality Control Mark and be
compatible with the coil fusion
method.

www.us.piping.georgefischer.com 7.11

*07_001-023 11 6/7/02, 11:38 AM


Fuseal MJ Suggested Submittals
Sample Short Form Catalog Data: Contractor shall sub-
Fuseal, Mechanical
Specification Guide mit___ copies of manufacturer's litera-
Joint in Accessible ture on the Fuseal MJ system. The
Locations The following guide specifications can
be used when preparing project orders literature shall contain complete and
Specification current installation instructions.
or inquiries for George Fischer, Fuseal
The system shall be made Mechanical Joint (MJ) Piping System.
of flame retardant Two forms are included: Part 2 — Product
polypropylene pipe and a general and a short form specification.
fittings and in concealed Manufacturer
locations shall be joined Pipe and Fittings in exposed or easily
by the George Fischer
General Specification accessible locations may be joined with
Fuseal method. In the George Fischer Sloane Mechanical
exposed or easily Part 1 — General Joint System.
accessible location,
George Fischer Fuseal Special Waste Pipe and Fittings Materials
Mechanical joint fittings Special Waste and Vent Pipe and Fitting The products described in this specifica-
may be used. All flame System shall be +GF+ Fuseal polypropy-
retardant polypropylene
tion consist of:
pipe and fittings shall
lene as manufactured by George Fischer
conform to George Sloane, Inc. in Little Rock, Arkansas as A. Pipe and fittings made of flame
Fischer, Inc. specifications. described below. Pipe and fittings retardant polypropylene. The fittings
Installation and test shall installed above grade shall be flame include a seal ring made of polypro-
be in accordance with retardant polypropylene. pylene based material and a grab
the manufacturer's ring made of Ryton® (trademark of
recommendations and Quality Assurance Phillips Petroleum).
the governing local code. The Fuseal systems shall be manufac-
tured to the following ASTM Standards: B. Joining Method — The pipe and
fittings shall be installed according to
D 4101 - Standard Specification for the current MJ installation instructions.
Propylene Plastic Injection
and Extrusion Materials. C. Basic Materials — This specification
covers flame retardant polypropylene
D 3311 - Standard Specification for (PPFR) pipe and fittings made from
Drain, Waste and Vent (DWV) PPFR plastic, as defined in ASTM
Plastic Fittings Pattern. D 4101 Propylene Plastic Injection
and Extrusion Materials. Flammability
D 1785 - Standard Specification for requirements are based on ASTM
(PVC) Plastic Pipe, Schedule D 635, Standard Test Method for
40, 80 and 120 (Dimensional Rate of Burning and/or Extent and
requirements only). Time of Burning of self supporting
plastics in a horizontal position.
D 1599 - Test Method for Short-Time
Hydraulic Failure Pressure of D. Compound — The PPFR compound
Plastic Pipe, Tubing and used in the pipe and fittings covered
Fittings. by this specification shall meet the
requirements of Class PP110B63153
D 2122 Test Method of Determining material as described in ASTM
Dimensions of Thermoplastic D 4101 . As other compounds are
Pipe and Fittings. shown to be suitable for these
products, such compounds will be
F 1290 - Standard Practice for added to this specification.
Electrofusion Joining Polyolefin
Pipe and Fittings. Part 3 — Execution
F 1412 - Standard Specification for Installation
Polyolefin Pipe and Fittings for A. Fuseal Mechanical Joint fittings shall
Corrosive Waste Drainage be installed according to current
Systems. Fuseal Mechanical Joint installation
Instructions.

7.12 ¬ ‡

*07_001-023 12 6/7/02, 11:38 AM


‡ Fuseal II
B. A manufacturer’s representative, D 635 Flammability:
who has been certified as a Average time of burning - less
training instructor, shall be at the than 5mm, actual 2.7 seconds
site prior to the day the piping
system installation is to commence. Average extent of burning - less
A manufacturer’s rep. will perform than 5mm, actual 1 .8mm
a complete training session on the D 2843 Smoke Density:
proper method of installation for Maximum Smoke Density 88.7
the piping system. Upon comple- Rating, % 67.8
tion of the training, the installers D 694 Coefficient of Linear
will be given a test on the items Expansion @ 0-150°F, 6.1
covered in the session. Persons (in. /in.°F x 10-5)
successfully completing the test (-17°C - 62°C)
shall be given a laminated card
which certifies them for one year C 177 Thermal Conductivity
as installers of the Fuseal piping BTU/hr. sq. ft./°F/in. 1 .3
system. D 570 Water Absorption, % 0.03
D 1238 Melt Flow Rate, g/10min.
Testing @ 230°C 0.05
Joints may be pressure tested after
assembly. Test in accordance with local D 638 Elongation at Break, % 200
plumbing codes. All sections of the
system shall be tested with a minimum
D 4101 Polypropylene Molding
& Extrusion Material B63153
7
ten foot head of water up to a maximum
thirty foot head of water. Schedule 40 (Black)
Non-Flame Retardant — Group 1
Homopolymer ASTM Test No.
Material Physical Properties D 792 Specific Gravity @ 23°C 0.91
(73°C) (g/cm3)
Material — Group 1 63153 D 638 Tensile Yield Strength @
Homopolymer Pipe Grade 2 in./min.,psi 5,000
George Fischer Sloane flame retardant
polypropylene, when tested per ASTM D 256 Izod Impact @ 23°C, (73°F)
D 635 shows an average time of burning ft.lb./in. 2.2
of under 5 seconds (actual 2.72 sec- D 747 Stiffness-Flexural, 108 psi 1 .7
onds) and an average extent of burning D 676 Hardness, Rockwell R 95
of under 5 millimeters (actual 1 .8 mm). It
is recognized that small scale laboratory D 648 Heat Distortion Temp.
combustibility tests do not necessarily @ 66 psi 176°F, 80°C
indicate the burning characteristics of C 177 Thermal Conductivity,
the material in an actual building fire. BTU/hr. sq.ft./°F/in. 1 .3
This material ceases to burn when the D 694 Coefficient of Linear
igniting flame source is removed. It is not Expansion @150°F, (62°C) 5.0
non-combustible. (in./in.°F x 10-5)
Schedule 40 (Blue) D 149 Dielectric Strength,
Flame Retardant — Group 1 volts/mil;ST 610
Homopolymer ASTM Test No. Power Factor @ 60 cps 0.007
D 792 Specific Gravity @ 23°C 0.94 D 570 Water Absorption
D 638 Tensile Yield Strength @ in 24 hrs., % 1 .9
2 in./min., psi 4500 D 1693 Environmental Stress
D 256 Izod Impact 23°C, (73°F) Cracking None
ft.lb./in. 1 .0 D 4101 Propylene Molding
D 790 Flexural Modulus Proc. & Extrusion Materials B63153
B - 1 % Secant, psi 200,000
D 785 Hardness, Rockwell R 80
D 648 Heat Distortion Temp.
@ 264 psi 167°F, 75°C

www.us.piping.georgefischer.com 7.13

*07_001-023 13 6/7/02, 11:38 AM


temperature and to the piping being
Schedule 80 (Black) enclosed within wall and ceiling spaces.
Non-Flame Retardant — Group 2
Copolymer ASTM Test No. Buried piping or piping in the crawl
D 792 Specific Gravity @ 23°C 0.91 spaces under a building is subject to less
than ambient temperatures and to the
D 638 Tensile Yield Strength
piping being enclosed within wall and
@ 2 in./min.,psi 3900
ceiling spaces.
D 256 Izod Impact @ 23°C 8
D 676 Hardness, Rockwell R 87 There are three methods of controlling or
compensating for thermal expansion of
D 648 Heat Distortion Temp.
Fuseal corrosive waste systems:
@ 66 psi 212°F, 100°C
1 .) taking advantage of offsets and
C 177 Thermal Conductivity, changes of direction in the piping;
BTU/hr. sq. ft./°F/in. 1 .15 2.) vertical expansion joint assemblies;
D 694 Coefficient of Linear 3.) restraint of the system.
Expansion @ 68°F 6.1
(in. / in. °F x 10-5) Offsets
Most waste systems have many short
D 570 Water Absorption
runs of pipe with frequent changes in
in 24 hrs., % 0.03
direction. Advantage may be taken of
D 1694 Environmental Stress the changes in direction by allowing
Cracking None thermally induced length changes to be
D 4101 Propylene molding taken up in movement of the pipe
& Extrusion Materials B53653 beyond the bends.

Expansion loop and offset lengths, which


Fuseal Installation and are dependent on pipe diameter, may
Engineering Data be obtained from the charts in two
pages.
Thermal Expansion
Compensation In areas of the system where this method
Temperature changes in waste systems is used, support but do not rigidly
depend on the quantity and temperature restrain the piping at branches or
of the liquid waste discharged into the changes of direction. Do not anchor the
system. In general, the quantities of pipe rigidly in walls. Holes through the
wastes discharged through waste structure must allow for free movement.
systems in laboratories in educational Figure A indicates the recommended
institutions will be relatively small (a few expansion loop and offset configuration
gallons at a time), while industrial to be used with the charts on page 7.15
laboratories and processing systems dimensions.
may discharge large quantities of very
hot or very cold water. Linear expansion may be determined
from the chart on page 7.14, which is
Because polypropylene piping is not the independent of pipe diameter.
best conductor of heat, low volume
discharges will not raise the piping to
the temperature of the wastes, hence,
the thermal induced length changes in
general will be less than expected. High
volumes of wastes which take longer to
flow through the piping will bring the
system up to or close to the temperature
of the wastes.

Waste pipe also is subject to ambient


temperature changes. These changes
will be more pronounced during the
construction period and generally will
be negligible after the laboratory is
occupied due to control of building
7.14 ¬ ‡
‡ Fuseal II
Vertical Expansion Joint Assemblies
Fuseal vertical expansion joint assem- pre-lubricated EPDM O-Ring gasket
blies are designed to absorb expansion joint; 2) piston spigot. They are avail-
and contraction in vertical piping runs in able in 11/2”, 2”, 3” and 4” sizes. Vertical
multi-story buildings. The expansion expansion joint assemblies are quickly
joints are factory assembled and consist and easily installed by means of our
of two components: 1) O-ring fitting with standard Fuseal joining process.

Thermal Expansion — Fuseal


Length Temperature Change — ∆ T in °F
(Feet) 40°F 50°F 60°F 70°F 80°F 90°F 100°F
1
Schedule 40 (black) Non-Flame Retardant Homopolymer 1 /2 – 10"
20 .48 .60 .72 .84 .96 1.08 1.20
40 .96 1.20 1.44 1.68 1.92 2.16 2.60
60 1.44 1.80 2.16 2.52 2.88 3.24 3.60
80 1.92 2.40 2.88 3.36 3.84 4.32 4.80
100 2.40 3.00 3.60 4.20 4.80 5.40 6.00
Schedule 80 (black) Non-Flame Retardant Copolymer 11/2 – 12" and
Schedule 40 (blue) Flame Retardant Homopolymer 11/2 – 8" 7
20 .59 .73 .88 1.02 1.17 1.32 1.96
40 1.17 1.46 1.76 2.05 2.34 2.69 2.93
60 1.76 2.20 2.64 3.07 3.51 3.95 4.39
80 2.34 2.93 3.51 4.10 4.68 5.27 5.86
100 2.93 3.66 4.39 5.12 5.86 6.59 7.32

Note: Table based on: ∆L = 12 eL ∆T


Example:
Highest Temperature Expected 120°F
Lowest Temperature Expected 50°F
Total Change ∆T 70°F
Length of Run — 40 ft.
From 70°F column, read 1.68 inches length change, ∆L
Where:
*e = Coefficient of Thermal Expansion = 5 x 10-5 in./in.°F
**e= Coefficient of Thermal Expansion = 6.1 x 10-5 in./in.°F
L = Length of Run, ft.
∆T = Temperature Change, °F

www.us.piping.georgefischer.com 7.15

*07_001-023 15 6/7/02, 11:39 AM


Fuseal Polypropylene Expansion Loops

Polypropylene Length of Run (feet)


Fuseal
10 20 30 40 50 60 70 80 90 100
Pipe O.D. of
Size Pipe Minimum Deflected Pipe Length (inches)
(in.) (in.)
1
/2 0.840 17 25 30 35 39 43 46 49 52 55
3
/4 1.050 19 27 34 39 43 48 51 55 58 61
1 1.315 22 31 38 43 49 53 57 61 65 69
11/4 1.660 24 35 42 49 55 60 65 69 73 77
11/2 1.900 26 37 45 52 58 64 69 74 78 83
2 2.375 29 41 51 58 65 72 77 83 88 92
3 3.500 35 50 61 71 79 87 94 100 106 112
4 4.500 40 57 70 80 90 98 106 114 121 127
6 6.625 49 69 84 98 109 119 129 138 146 154
8 8.625 56 79 96 111 124 136 147 157 167 176
10 10.750 62 88 108 124 139 152 164 176 186 196
12 12.750 68 96 117 135 151 166 179 191 203 214

Fuseal Polypropylene Offsets and Change of Directions

Polypropylene Length of Run (feet)


Fuseal
10 20 30 40 50 60 70 80 90 100
Pipe O.D. of
Size Pip Minimum Deflected Pipe Length (inches)
(in.) (in.)
1
/2 0.840 25 35 43 49 55 60 65 69 74 78
3
/4 1.050 27 39 48 55 61 67 73 78 82 87
1 1.315 31 43 53 61 69 75 81 87 92 97
11/4 1.660 35 49 60 69 77 85 91 98 104 109
11/2 1.900 37 52 64 74 83 90 98 104 111 117
2 2.375 41 58 72 83 92 101 109 117 124 131
3 3.500 50 71 87 100 112 123 133 142 150 159
4 4.500 57 80 98 114 127 139 150 161 171 180
6 6.625 69 98 119 138 154 169 183 195 207 218
8 8.625 79 111 136 157 176 193 208 223 236 249
10 10.750 88 124 152 176 196 215 232 249 264 278
12 12.750 96 135 166 191 214 234 253 271 287 303

7.16 ¬ ‡

*07_001-023 16 6/7/02, 11:39 AM


‡ Fuseal II
Restraint to be a restrained system and not
subject to thermally induced dimensional
Restraint is rigidly anchoring the pipe
changes.
runs to the building structure at appro-
priate places so that thermally induced
It should be noted that two unusual
dimension changes will be replaced by
properties of polypropylene make for
thermally induced stresses. This can be
the success of these methods of handling
accomplished by use of adequately
thermal expansion. Polypropylene is not
strong clamps or supports to hold the
subject to stress cracking. It can be
pipe in place. The appended Table 4
stressed for long periods of time in what
shows the forces to be resisted. For
might be considered unfriendly environ-
horizontal runs, braced clamp type
ments without harm. In addition,
hangers may be used. For floor penetra-
nolypropylene has an extremely high
tions, extension riser clamps may be
fatigue life. Its “self-hinge” characteristics
used.
are well known and the piping materials
will stand repeated drastic flexures
Underground installation in properly
without harm.
backfilled trenches may be considered

Expansion Loop and Offset Configuration for Polypropylene


7

Expansion Loop Expansion Offset Change of Direction

Restraint Force, (lbs.)


Nominal Schedule 40 *Schedule 80
Size A(in.2) ∆T= 50°F ∆T=100°F A(in.2) ∆T= 50°F ∆T=100°F
(in.) S=500 psi S=1000 psi S=500 psi S=1000 psi
11/2 .799 400 800 1.068 534 1070
2 1.075 538 1080 1.477 739 1478
3 2.228 1110 2220 3.016 1510 3020
4 3.173 1590 3180 4.407 2200 4400
6 5.584 2790 5580 8.405 4200 8400
8* 8.399 4610 4220 12.763 7020 14040
10* 11.908 6536 13070 18.922 10405 20810
12* 15.745 8645 17290 16.035 14320 28640

NOTE: Table based on: S=e∆TE, F=A x S


*Indicates copolymer polypropylene.
Where:
S = Thermal Stress, psi
F = Restraint Force Necessary, lbs.
A = Cross Sectional Area of Pipe Wall, in.2
∆T = Temperature Difference, °F
e = Coefficient Thermal Expansion = 5 x 10-5 in./in.°F
E = Modulus of Elasticity = 2.0 x 105 psi
*e = Coefficient Thermal Expansion = 6.1 x 10-5 in./in.°F
*E = Modulus of Elasticity = 1.8 x 105 psi
www.us.piping.georgefischer.com 7.17

*07_001-023 17 6/7/02, 11:39 AM


Instructions for Above Ground
The physical properties of polypropy- Horizontal Piping
lene are such that it is excellent piping
material and may be handled and 1 . Piping should be installed in hangers
installed in much the same manner as so that the system will be free moving,
other materials. or clamped where necessary to
control thermal expansion.
Vertical Risers
2. Conventional split ring or clevis type
1 . Piping may penetrate floors or slabs band hangers may be used. No
through sheet metal or steel pipe special padding or isolation is re-
sleeves with normal clearances. quired.

2. Risers should be supported with 3. Horizontal piping hangers must be


standard riser clamp or wall bracket spaced in accordance with the
at each floor or ten feet. following chart.

Fuseal Support Spacing (feet)


Pipe Temperature (°F)
Size
(in.) 73°F 120°F 140°F 160°F 180°F  200°F 210°F
11/2 43/4 41/2 41/2 41/2 41/4 4 33/4
1
2 5 /4 5 5 43/4 41/2 41/4 4
3 61/4 6 53/4 53/4 51/2 51/4 5
4 63/4 61/2 61/2 61/4 6 53/4 51/2
6 8 71/2 71/2 71/4 7 61/2 6
1
8 8 /2 8 71/2 63/4 61/2 61/4 6
10 91/2 83/4 8 71/2 7 63/4 61/2
12 10 91/2 81/2 8 71/2 71/4 7

Instructions for Underground


Trenching 3. Trench depth—trenches under build-
ing slabs should allow for 12” cover
1 . The bottom of the trench shall be of over the pipe. Trenches in exposed
stable material. Where ground water locations should permit burial of pipe
is encountered, the bottom shall be at least 12” below maximum ex-
stabalized with granular material of pected frost penetration. A minimum
1
/2” maximum particle size. A 4” of 24” cover should be provided
cushion shall be placed over rock or where pipe may be exposed to
hardpan. heavy overhead traffic. Applicable
plumbing codes may require greater
2. Trench width—should be sufficient to trench depth and cover than techni-
provide working room if pipe is to be cally required.
jointed in the trench. Minimum width
may be used if pipe is to be joined
before placing in ditch.

Trench Widths for Polypropylene


;;;
;;;
;;;;;
;;; ;;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;
;;; ;;;;;;;;;;;;;
W
;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;
H
;;;
;;;
;;;;;
;;;
H ;;;;;;;;;;;;;
;;;;;;;;;;;;; H ;;;;;;;;;;;;
;;;;;;;;;;;; H ;;;;;;;;;;;
;;;;;;;;;;;
;;;
W W W

;;;;; ;;;;;;;;;;;;; ;;;;;;;;;;;;


;;;
;;;;;
;;;;;
;;;;;;;;;;;;;
;;;;;;;;;;;;;
;;;;;;;;;;;;;
;;;;;;;;;;;;
;;;;;;;;;;;;
;;;;;;;;;;;;
;;;;;;;;;;;
;;;;;;;;;;;
;;;;;;;;;;;
;;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;
Note: W = Trench width at top of pipe.
;;;;;;;;;;;
7.18 ¬ ‡

*07_001-023 18 6/7/02, 11:39 AM


‡ Fuseal II
Bedding and Backfill Material Bedding and Backfilling - ASTM D2321 Note 1: Figures are
1 . Bedding — Install in 6” maximum calculated from minimum
The backfill material surrounding the layers. Level final grade by hand. soil resistance values (E’ =
pipe shall be readily compactable and Minimum depth 4” (6” in rock cuts). 200 psi for uncompacted
2. Haunching — Install in 6” maximum sandy clay loam) and
shall consist of coarse sand, sand with
compacted soil (E’ = 700
gravel or clay, sand that is free from layers. Work around pipe by hand for side-fill soil that is
frozen lumps, stone larger than 1/2” and to provide uniform support. compacted to 90% or more
excessive fines, silt or clay. The material 3. Initial Backfill — Install to a minimum of Proctor Density for a
shall fall within the Highway Research of 6” above pipe crown. distance of two pipe
Board Classification Group A-1, A-2 4. Embedment Compaction — Minimum diameters on each side of
(Plasticity Index less than 10) or A-3. density 95% Standard Proctor per the pipe). If Wc’ is less than
ASTM D 698. Use hand tampers or Wc at a given trench
vibratory compactors. depth and width, then soil
5. Final Backfill — Compact as required compaction will be
by the engineer. necessary.

Fuseal Soil Load and Pipe Resistance Note 2: These are soil
loads only and do not
Wc’ = Load Resistance of Pipe (lb./ft.) H=Height Wc = Soil Loads at Various include live loads.
Nom. of fill Trench Widths at Top of Pipe
Size Schedule 40 Pipe Schedule 80 Pipe Above (lb./ft.)
Pipe
7
E’ = 200 E’ = 700 E’ = 200 E’ = 700 (ft.) 2 ft 3 ft. 4 ft.
10 106 125 136
11/2 556 764 1375 1561 20 138 182 212
30 144 207 254
10 132 156 170
2 466 718 1161 1400 20 172 227 265
30 180 259 317
10 160 191 210
21/2 701 1005 1593 1879 20 204 273 321
30 216 306 377
10 196 231 252
3 614 988 1416 1772 20 256 336 392
30 266 384 469
10 223 266 293
31/2 578 1011 1318 1731 20 284 380 466
30 300 426 524
10 252 297 324
4 564 1055 1266 1735 20 328 432 504
30 342 493 603
10 310 370 407
5 555 1170 1206 1796 20 395 529 621
30 417 592 730
10 371 437 477
6 573 1313 1323 2028 20 484 636 742
30 503 725 888
10 483 569 621
8 638 1612 1319 2250 20 630 828 966
30 656 945 1156
10 602 710 774
10 721 1944 1481 2649 20 785 1032 1204
30 817 1177 1405
10 714 842 918
12 809 2266 1676 3067 20 931 1225 1429
30 969 1397 1709

Wc´ = ∆x(EI + 0.061 E´r3)80


r3
Wc´= Load Resistance of the Pipe, lb./ft. E´ = Modulus of Passive Soil Resistance,
∆x = Deflection in Inches @ 5% (.05 x I.D.) psi
E = Modulus of Elasticity = 2.0 x 105 psi H = Height of Fill Above Top of Pipe, ft.
t = Pipe Wall Thickness, in. I = Moment of Inertia t3/12
r = Mean Radius of Pipe (O.D. - t)/2
www.us.piping.georgefischer.com 7.19

*07_001-023 19 6/7/02, 11:39 AM


Specification for the MSA 250SE
Part number MSA 250SE
Input Voltage 90-130 VAC Nominal Voltage: 110 V /
Generator: 110-120 VAC Nominal
Voltage
Input Current 15 Amps
Output Voltage 0 to 45 VAC
Output Current 0 to 30 Amps
Power Consumption max. 1200 W nominal output
Generator Output Performance 2 KVA Sinusoidal (unipolar operation)
depending on the fitting diameter
Back-up Fuse 10–16 AT depending on the fitting size
Fusion Voltage 3,7 -32 VAC galvanically separated

Protection Type Protection class 1/IP 65


Operating Temperature –10°C (14°F) to + 45°C (113°F)
Duty Cycle 100%
Dimensions Width: 280 mm (.91 ft.)
Depth: 200 mm (.66 ft.)
Height: 350 mm (1 .15 ft.)
(measured inc. carrying handle)
Weight 11 .5 kg (24 lbs.) (with cables)
Power Cable Length 3 m (10 ft.)
Extension Cord Requirement 150’ (10 gauge/3 strand)

Specification for the MSA 250EX


Part number MSA 250EX
Input Voltage 200-250 VAC Nominal Voltage: 230 V /
Generator: 210-230 VAC Nominal
Voltage
Input Current 15 Amps
Output Voltage 0 to 45 VAC
Output Current 0 to 30 Amps
Power Consumption max. 1200 W nominal output
Generator Output Performance 2 KVA Sinusoidal (unipolar operation)
depending on the fitting diameter
Back-up Fuse 10–16 AT depending on the fitting size
Fusion Voltage 3,7 -32 VAC galvanically separated

Protection Type Protection class 1/IP 65


Operating Temperature –10°C (14°F) to + 45°C (113°F)
Duty Cycle 100%
Dimensions Width: 280 mm (.91 ft.)
Depth: 200 mm (.66 ft.)
Height: 350 mm (1 .15 ft.)
(measured inc. carrying handle)
Weight 11 .5 kg (24 lbs.) (with cables)
Power Cable Length 3 m (10 ft.)
Extension Cord Requirement 150’ (10 gauge/3 strand)

7.20 ¬ ‡

*07_001-023 20 6/7/02, 11:39 AM


‡ Fuseal II
Plastic Piping and Fire one inch sample is exposed propane
burner flame and light transmission
Increasingly, fire protection officials and through the smo} generated by the
code officials are becoming sensitive to burning plastic is measured with a
the fire characteristics of plastic materi- standard lamp and photocell for four
als used in building construction and minutes. Results are reported as light
plastic piping is naturally included in absorption and smoke density.
these concerns. To satisfy the fire safety
requirements set out by the authorities, D. ASTM D 2863 - Minimum Oxygen
the engineer and the architect must have Concentration to Support Candle-
a better understanding of the plastics Like Combustion of Plastics (Oxygen
used in piping, appropriate test methods Index).
and means of protection against fire
danger attributable to plastic piping. A one eighth inch by one quarter inch
by three to six inch long specimen is
To put this into the proper perspective, burned in a variable oxygen-nitrogen
the architect, engineer and administra- mixture to determine the percentage
tive authority must realize that, in the oxygen required to maintain combus-
vast majority of cases, fires start in tion.
occupied areas of a building, not within
the walls. 2. Large Scale Tests - These tests are run
Testing Methods
on full sized wall or floor (floor- 7
ceiling) assemblies or on large
The following are common laboratory material specimens. They are in-
tests conducted on small samples of tended to determine the response of
plastic material and are useful in varying construction methods and
characterizing and comparing different materials to actual fire conditions.
plastics. However, these tests are of only
limited use in predicting the behavior of A. ASTM E 119 - Fire Tests of Building
the materials in real fire situations. Construction and Materials.
NFPA 251
A. ASTM D 635 - Rate of Burning and/ UL 263
or Extent and Time of Burning of Self UBC 43-1
Supporting Plastics in a Horizontal
Position. Wall sections of at least 100 square
feet in size are attached as the front
One half inch wide by five inch long wall of a furnace and exposed to a
horizontal specimens are exposed to flaming environment, the temperature
a bunsen burner flame. The time of of which rises according to a stan-
burning and distance burned are dard time temperature curve. The test
recorded. The results are reported as specimen may or may not be expos
measured, except that the minimum to vertical or horizontal loads. The
time of burning is reported as "less specimen, after exposure ma be
than five seconds" and the minimum subjected to a high pressure hose
extent of burning is reported as "less stream to determine its integrity after
than five millimeters." exposure.

B. UL 94 - One half inch wide by five This test is universally accepted as the
inch long vertical specimens are method of rating wall assemblies for
exposed repeatedly to a bunsen fire resistance as related to time of
burner flame. Time of burning, pos- exposure. Ratings may be 1, 2, 3 or 4
sible dripping of burning particles hours, depending on the time for the
and after glow are observed. Results temperature to rise to not more than
are reported as V-0, V-1 or V-2, 250°F above its initial temperature on
depending on test results. the non-exposed face. Floor and
floor-ceiling assemblies of at least
C. ASTM D 2843 - Density of Smoke 180 square feet in size are also
from the Burning or Decomposition of tested per E 119 as the roofs of a
Plastics. floor-ceiling furnace, and rated on
the basis of the time for the tempera-
A one quarter inch by one inch by ture to rise 250°F above the initial
www.us.piping.georgefischer.com 7.21

*07_001-023 21 6/7/02, 11:39 AM


temperature on the unexposed face, Protection Methods
as for walls.
Fuseal Waste and Vent Piping
B. ASTM E 814 - Fire Tests of Through- 1 . For through the wall penetration,
Penetration Fire Stops. three methods have been used.
This test method (published Spring A. A thin, close fitting sheet metal
1982) is essentially identica] the E sleeve covering the pipe continuously
119 test except that it is intended to for a 10 inch to 18 inch projection of
determine the ability fire stopping each side of the wall.
methods and devices to maintain the B. A 36 inch length of glass or high
fire rating (integrity) of rated fire silicon iron pipe through the wall.
resistive walls, floors or floor-ceiling
assemblies which are penetrated by C. A one inch thick high temperature
pipe, conduits or cables. 0, the years, magnesia pipe insulation for five feet
plastic piping has shown to be both of developed length on each side of
a durable material and capable of the wall or floor penetration.
playing its part in fire containment.
Method "A" has been tested in both
C. ASTM E 84 - Surface Burning Charac- Canada and Sweden, but not by
teristics of Building Materials. ASTM E 119. This method has been
NFPA 255 approved by some states. Methods
UL 723 "B" and "C" have not been tested but
UBC 42-1 have been assumed to work and
have been approved by some states.
As stated, this test is intended for
testing of surface finish materials 2. For piping contained in one hour
which are capable of supporting wood stud, gypsum wall boarr
themselves or of being supported covered walls and with trap arms
other than by support on the under- penetrating the wall facing, tests at
side of the test specimen. Samples the University of California and the
are 20 inches (min.) wide by 24 feet Ohio State University have shown
long and are attached to the roof of three ways of maintaining the fire
an 18 inch by 30 foot furnace. integrity of the walls.
Burning characteristics of the samples A. The stud space is packed with mineral
are stated as percentage of the rate wool insulation from floor level to four
of burning of red oak. feet above the floor. This method
furnishes protection for walls contain-
This test, being specifically aimed at ing PVC-DWV and flame retardant
testing surface finish materials, is polypropylene (FRPP) corrosive waste
recognized as not applying to plastic piping.
pipe by those who understand the
test method. The National Fire B. A galvanized iron plate measuring 16
Protection Association has stated that inches by 26 inches with a tight fitting
the test is not to be applied to plastic hole 4 inches from the bottom edge is
pipe and that the pipe should be placed around the trap arm on the
tested as a component of a wall or studs on both sides of the wall. This
floor assembly in the E 119 test. method furnishes protection for ABS,
PVC and Fuseal DWV.

C. Completely backpacking the space


around the penetrating pipe through
the gypsum wall board. This method
was shown to work in ABS and PVC-
DWV installations where the penetra-
tions were in the stud spacing next to
the one containing the vertical piping.

7.22 ¬ ‡

*07_001-023 22 6/7/02, 11:39 AM


‡ Fuseal II
In addition to these test-proven methods, non-combustible insulation material
penetrations by well supported non- encapsulated with aluminum foil. It is
combustible pipe connected to the classified by Omega Point Laborato-
plastic pipe in the wall has been ac- ries for use on PVC, CPVC, PB, PE, PP,
cepted by some jurisdictions without test. PVDF and ABS pipe in return air
plenums. Tested to the UL 910
3. In a fire hazard area, exposed piping flammability test. The 3M FireMaster
should be enclosed with 5/8" class X PlenumWrap provides protection
gypsum wall board. from external flame-propagation and
smoke. It protects plastic pipes that
4. In plenum spaces between a floor are to be installed in ducts, plenums
and a suspended ceiling, protection and other spaces used for environ-
can be provided by 3M FireMaster mental air.
PlenumWrap. This PlenumWrap is a

www.us.piping.georgefischer.com 7.23

*07_001-023 23 6/7/02, 11:39 AM


‡ Fuseal 25/50 PVDF
‡ Fuseal 25/50 PVDF
Corrosive Waste Piping System

New Picture

Pipe, Fittings, Accessories


Electrofusion
Mechanical Joints

www.us.piping.georgefischer.com 7.47
‡ Fuseal 25/50 ‡ Fuseal 25/50 PVDF Piping Superior Flame and
PVDF Piping System System – User friendly and Reliable
offers: System that meets your Corrosive Smoke Resistance
Waste Requirements while Providing The + GF+ Fuseal 25/50 PVDF Piping
O Electrofusion and Superior Flame and Smoke System is composed of Polyvinylidene
mechanical joint Retardance Fluoride resin which provides a broad
systems range of chemical resistance, high
tensile strength, and excellent impact
O Handles resistance. An important added benefit
temperatures of PVDF resin is its natural characteristics
up to 280°F intermit- Code Requirements of flame retardance and limited smoke
tently generation. PVDF is the only plastic
In recent years, federal, state, and local piping material that meets the strict
O Excellent chemical regulations have been enacted that requirements of recent building and
and corrosion mandate the reduction of sources of fire plumbing fire codes.
resistance and smoke hazards in most types of
facilities. These regulations cover virtually
O UL 94VO & UL723 all aspects of building materials, as well Flame Retardant PVDF
(ASTM E84)certifi- as, the infrastructure within the building. + GF+ PVDF is UL 94-VO listed and is
cations Piping systems and their respective
materials, are no exception. Return air considered a non-combustible material.
plenums are of particular concern in this PVDF also complies with UL723 (ASTM
O High impact
market. Fire and smoke prevention in E84.) In addition, PVDF also provides a
resistance
plenums, a primary route for pipe runs, is combination of superior chemical
especially critical, as these two elements resistance, and high strength at elevated
O Lightweight and easy
can rapidly sweep through a building via temperatures.
to install
the plenum system.
O Easy transition to High Temperature Rating
other ‡ piping Applications The + GF + Fuseal 25/50 PVDF Piping
systems
+ GF+ Fuseal 25/50 PVDF Piping System’s System handles corrosive drainage
superior chemical and physical fluids up to 280°F intermittently.
properties make the system ideal for
handling corrosive chemical waste
solutions where non-combustible material
is required. Applications include
hospitals, schools, laboratories and
industrial processes.

So how is it possible to safely and


economically transport corrosive fluids
and still provide the required flame and
smoke ratings?

‡ Fuseal 25/50 PVDF Piping


System is the answer.

7.48 GEORGE FISCHER ‡


‡ Fuseal 25/50 PVDF

Pipe and Fittings Specification for ‡


Pipe comes in 10 foot lengths and is Fuseal 25/50 PVDF Piping
available in 1-1/2” through 4” sizes. System
Associated fittings include couplings, 1/8
+ GF+ Fuseal 25/50 PVDF Pipe and
and 1/4 bends, wyes, combination
wyes, pipe increasers, caps, p-traps Fittings shall conform to ASTM F1673,
clean-outs, and reducing wyes and standard specification for Polyvinylidene
combinations. In addition, a mechanical Fluoride (PVDF) corrosive waste drainage
joint transition fitting allows for a smooth, systems. All + GF+ Fuseal 25/50 PVDF
and quick transition to the + GF+ Fuseal fittings shall be manufactured so they
Acid Waste Piping System. are compatible with + GF+ Fuseal 25/50
PVDF pipe. The + GF+ Fuseal 25/50 PVDF
Piping System shall be joined by either
Joining Methods electrofusion with the MSA 250SE or
with a Fuseal 25/50 PVDF mechanical
The + GF+ Fuseal 25/50 PVDF Piping joint as manufactured by + GF+ George
System offers (2) joining methods:
1) electrofusion – using our state of the
Fischer. 7
art fusion technology (MSA 250SE), joints Product range is 1-1/2” to 4” diameter
are quickly fused with a seamless bond, pipe and associated drainage pattern
forming a permanent joint or fittings.
2) mechanical joint – available for use in
easily accessible areas, such as under
sink (p-traps) or clean-outs.

MSA 250SE
The MSA 250SE represents the most
advanced fusion unit in the industry. This
unit features advanced transformer
technology and can be used with either
network or generator power sources. All
required fusion parameters are
programmed into the MSA 250SE by
simply scanning a barcode specific to
each pipe size. The MSA also has
multiple joint capability, and a built in
fail-safe mode.

Certification by an authorized George


Fischer representative is required
before using the MSA 250SE.

Product Range
Fittings Connection Dimensions Material
Fabricated and Electrofusion and 1-1/2" through 4" PVDF (Kynar)
Molded Mechanical Joint

Pipe Connection Dimensions Material


Sch. 40/SDR 21 Electrofusion and 1-1/2" through 4" PVDF (Kynar)
Mechanical Joint
www.us.piping.georgefischer.com 7.49
‡ Fuseal 25/50 PVDF
Specifications and Material Properties
Fuseal 25/50 PVDF drain, waste and vent system as specified
and as shown on the contract drawings.
Suggested Specification System shall be made up of Fuseal 25/50
Guide PVDF flame retardant polyvinylidene
The following specification guide can be fluoride pipe (1-1/2", 2", 3" and 4") and
used when preparing project orders or fittings in return air plenums and shall be
inquiries for +GF + Fuseal 25/50 PVDF joined to the George Fischer Sloane , Inc.
Corrosive Waste Piping System. Fuseal II polypropylene acid waste
Two forms are included: a general and system supplied in either electrofusion or
an abbreviated specification. mechanical joint systems*. (Please see
Fuseal II product specifications).
* The mechanical joint system is to be utilized
General Specification only in easily accessible locations.
General Materials
Quality Assurance The products described in this specifica-
The PVDF Plenum Rated System shall be tion consist of:
manufactured to the following ASTM A. Pipe and fittings made of flame
standards: retardant polyvinylidene fluoride 7
D 1599 –Test Method for Short-Time (PVDF) joined by an electrofusion
Hydraulic Failure Pressure of system.
Plastic Pipe, Tubing and Fittings B. Joining Method: The pipe and fittings
D 2122 –Test Method of Determining are joined by use of the electrofusion
Dimensions of Thermoplastic couplings energized by a low-voltage
Pipe and Fittings power supply.
D 3222 –Standard Specification for C. Basic Materials: This specification
unmodified Polyvinylidene covers flame retardant polyvinylidene
Fluoride (PVDF) Molding fluoride (PVDF) pipe and fittings made
Materials from polyvinylidene fluoride resin
D 3311 –Standard Specification for (conforming to ASTM D3222) and
Drain, Waste and Vent (DWV) defined in ASTM F1673 - Standard
Plastic Fittings Pattern Specification for Polyvinylidene
F 1673 – Standard Specification for Fluoride (PVDF) Corrosive Waste
Polyvinylidene Fluoride (PVDF) Drainage Systems. Flammability
Corrosive Waste Drainage requirements are based on ASTM
Systems 635, Standard Test Method for Rate
F 1290 – Practice for Electrofusion Join- of Burning and/or Extent and Time of
ing Polyolefin Pipe and Fittings Burning of Self-Suporting Plastics in a
E 84 – Standard Test Method for Horizontal Position. The George
Surface Burning Characteristics Fischer Inc. PVDF system meets and
of Building Materials exceeds ASTM E84 25/50 (UL 723)
Certifications – and UL 94-VO.
BOCA, IAPMO, UPC, UL, D. Compound: The PVDF compound
ASTM used in the pipe and fittings covered
by this specification shall meet the
Submittals requirements of ASTM D3222. As
Catalog Data: Contractor shall submit other compounds are shown to be
two (2) copies of manufacturer’s literature suitable for these products, such
on the PVDF Plenum Rated system. The compounds will be added to this
literature shall contain complete and specification.
current installation instructions. Source Quality Control
A. Pipe Dimensions (Requirement): Pipe
shall be produced to Schedule 40 or
Product SDR 21, Iron Pipe Size dimensional
Manufacturer standards and shall meet the dimen-
Contractor shall furnish and install a sions and tolerances for outside
complete corrosion resistant non-pressure diameter.
www.us.piping.georgefischer.com 7.55
B. Fittings, Design and Dimensions Under no circumstances should the
(Requirements): Fittings design shall system be tested with air or any other
be based on ASTM D3311 DWV gas.
Plastic Fittings Patterns. Joints may be pressure tested 10 minutes
C. Electrical Fusion Couplings: Each after fusing.
coupling shall consist of a Certifications
polyvinylidene fluoride jacketed wire, George Fischer, Inc. Fuseal 25/50 PVDF
mandrel wound, and heat fused on system (pipe and fittings) is UL 723 and
the outer surface. The wire is inserted IAPMO, UPC certified. The PVDF system
into the socket at the factory and is meets all ASTM F1673 standards for
designed to have a snug fit. The wire Polyvinylidene Fluoride Corrosive Waste
is terminated with a duplex recep- Drainage Systems.
tacle for connection to the fusion unit.
D. Pipe Markings: All pipe shall be Short Form Specification
marked as per the requirements of Product Specification for George
ASTM F1673 with the following: Part Fischer Fuseal 25/50 PVDF Plenum-
No. +GF + PVDF SCH 40 size ASTM Rated Corrosive Waste Drainage
F1673 E84 UPC® UL Classified date-
System
stamp Made in USA.
PVDF acid waste drain lines shall be
E. Fittings Marking: All fittings shall be George Fischer Fuseal 25/50 PVDF
marked as per the requirements of Plenum-Rated, as manufactured or
ASTM F1673 with the following: produced by George Fischer, Inc. All
Molded Fittings: PVDF Plenum-Rated fittings shall be as
Part No. +GF + PVDF size ASTM F1673 manufactured by George Fischer, Inc. so
UPC® USA. that they are compatible with PVDF
Fabricated Fittings: Plenum-Rated pipe. All Fuseal 25/50
Part No. +GF + PVDF size ASTM F1673 PVDF Plenum-Rated pipe shall conform to
IAPMO c USA. the dimensional and quality requirements
of ASTM F1673 as produced by George
Fischer, Inc. Pipe shall be specified as
Execution Schedule 40 or SDR 21, blue
Installation polyvinylidene fluoride. The pipe and
Pipe and fittings shall be intalled accord- fittings shall meet the requirements of the
ing to current Fuseal 25/50 PVDF installa- ASTM E84 burn test. The PVDF Plenum-
tion instructions. Rated system shall be joined by the use
of couplings with electrically resistant
Testing coils energized by a variable low
Test in accordance with local plumbing voltage power supply. Pipe and fittings
codes. All sections of the system shall be shall be manufactured from PVDF mate-
tested with a maximum of 30-foot head rial conforming to ASTM D3222 and UL-
723.
of water (approx. 15 psi of water).

Table 1 ASTM F1673 Dimensional Standard


SCH 40 & SDR 21 SCH 40 SDR 21
Size Avg. O.D. Min. W Min. W
1 1/2" 1 .900 0.145 ----
2" 2.375 0.154 0.077
3" 3.500 0.216 0.114
4" 4.500 0.237 0.147

7.56 GEORGE FISCHER ‡


‡ Fuseal 25/50 PVDF
PVDF Material Physical Properties
Material: The PVDF material used is
Kynar 740-02.
Testing in accordance to ASTM D2863 resin exhibit zero flame spread and a 10
indicates that PVDF has a Limited smoke generation when tested in
Oxygen Index (i.e., LOI) of greater than accordance to the ASTM E84 tunnel test.
60. This value indicates that a 60% or Underwriters Laboratory (UL) has given
greater oxygen environment is required PVDF a vertical burn rating of 94 V-0.
for the polymer to continue to burn. A PVDF also meets the UL 1887 Stenier
material with an LOI value above 21 Tunnel Test with a zero flame
should not support combustion in air at propagation, 0.02 peak optical density,
room temperature. Generally, a value and a zero average optical density. The
above 27 means that the material will material is also listed with BOCA
only burn under extreme conditions (National Building Code) for drainage
where very high heat is applied. pipe and fittings installation in
Sheets of metal coated with the PVDF noncombustible plenums.

Specifications and Material Physical Properties


7
ASTM Property Unit Range
Test No.
D792 Specific Gravity - 1.77 – 1.79
D3418 Melt Temperature °C 165 – 172
D570 Water Absorption % .03
D696 Coefficient of Linear °C -1
14.4 x 10-5
Thermal Expansion
D2868 LOI - >60
UL-94 Burning Rate - V–O
E84 Flame Spread/ - 0/10
Smoke Generation
D638 Tensile Yield Strength MPa 40 – 55
D790 Flexural Strength MPa 48 – 62
D256 Izod Impact Strength notched J/m 107 – 214
D2240 Hardness Shore D - 76 – 80
D3222 Polyvinylidene Fluoride Kynar 740-02

Fuseal Squared Installation & Engineering Data


Thermal Expansion Compensation may discharge larger quantities of hot or
Temperature changes in waste systems cold water and other waste products. If
depend on the quantity and temperature the application requires a range of
of the liquid waste discharged into the elevated temperatures, it may be
system. In general, the quantity of waste necessary to factor in change of length
discharged through waste systems in due to axial thermal expansion. All
laboratories and in educational plastic piping systems experience some
institutions is relatively small (e.g., a few axial expansion when exposed to
gallons at a time), while industrial elevated temperatures. The equation
laboratories and processing systems
www.us.piping.georgefischer.com 7.57
that follows is used to determine the Note: Particular care should be given to
change in length of the +GF + Fuseal 25/ anchor points to allow expansion to
50 PVDF piping system as a result of occur without restriction.
temperature changes that your system
will experience. Waste pipe is also subject to ambient
temperature changes. These changes
iL = L x iT x d
will be more pronounced during the
iL = Change of length in inches construction period and generally will
L = Original length of pipe in inches be negligible after the laboratory is
iT = Change in temperature between occupied due to control of building
installation temperature and temperature and to the piping being
operating temperature in °C or enclosed within wall and ceiling spaces.
°F (see Table 2 and Table 3)
There are two methods of controlling or
d= Coefficient of axial linear expan- compensating for thermal expansion:
sion material for + GF + Fuseal 1) offsets and changes of direction in the
25/50 PVDF piping and 2) restraint of the system.
d= 0.000144 [in / in °C] These will be discussed in the next
d= 0.00008 [in / in °F] section.

Note: Tables 2 and 3 are valid for both Expansion Loops, Offsets
SDR 21 and SCH 40 Pipe
and Change of Direction
Most waste systems have many short
Table 2
runs of pipe with frequent changes in
Celsius THERMAL EXPANSION for ‡ Fuseal 25/50 PVDF direction. Advantage may be taken of
Pipe Length Temperature Change = iT [°C] the changes in direction by allowing
thermally induced length changes to be
10°C 20°C 30°C 40°C 50°C
taken up in movement of the pipe
Feet Inches Inches Inches Inches Inches beyond the bends.
20 0.35 0.69 1 .04 1 .38 1 .73
40 0.69 1 .38 2.07 2.76 3.46
60 1 .04 2.07 3.11 4.15 5.18
Expansion loops, offset lengths and
80 1 .38 2.76 4.15 5.53 6.91 change of direction lengths, which are
100 1 .73 3.46 5.18 6.91 8.64 dependent on pipe diameter, may be
obtained from Tables 4 and 5.
Table 3
In areas of the system where this method
Fahrenheit THERMAL EXPANSION for ‡ Fuseal 25/50 PVDF is used, support but do not rigidly
Pipe Length Temperature Change = iT [°F] restrain, the piping at branches or
20°C 40°C 60°C 80°C 100°C changes of direction. Do not anchor the
pipe rigidly.
Feet Inches Inches Inches Inches Inches
20 0.19 0.77 1 .15 1 .54 1 .92
40 0.77 1 .54 2.30 3.07 3.84 Holes through the structure must allow
60 1 .15 2.30 3.46 4.61 5.76 for free movement. Figures A, B and C
80 1 .54 3.07 4.61 6.14 7.68 indicate the recommended expansion
100 1 .92 3.84 5.76 7.68 9.60
loop, offset and change of direction
configurations to be used with Table 4
and Table 5.

7.58 GEORGE FISCHER ‡


‡ Fuseal 25/50 PVDF
Table 4
Fuseal 25/50 Expansion Loops
Pipe size Length of Run (feet)
10 20 30 40 50 60 70 80 90 100
Minimum Deflected Pipe Length (DPL) inches
1-1/2” 16 23 28 33 36 40 43 46 49 51
2” 18 26 32 36 41 45 48 51 55 58
3” 22 31 38 44 49 54 58 62 66 70
4” 25 35 43 50 56 61 66 71 75 79

Table 5
Fuseal 25/50 Offsets and Change of Direction
Pipe size Length of Run (feet)
10 20 30 40 50 60 70 80 90 100
Minimum Deflected Pipe Length (DPL) inches
1-1/2” 23 33 40 46 51 56 61 65 69 73
2” 26 36 45 51 58 63 68 73 77 81
3” 31 44 54 62 70 77 83 88 94 99
4” 35 50 61 71 79 87 94 100 106 112

7
Restraints
Restraint is rigidly anchoring the pipe This can be accomplished by use of
runs to the building structure at adequately strong clamps or supports to
appropriate places so that thermally hold the pipe in place. For horizontal
induced dimension changes will be runs, braced clamp type hangers may
replaced by thermally induced stresses. be used. For floor penetrations, extension
riser clamps may be used.

Table 6a:
Restraint Force: SCH 40 Pipe
iT=50 [°F] iT=50 [°F]
Nominal Size Area (in2) S = 1392 psi S = 2785 psi
SCH 40 Pipe OD Force [lbs] Force [lbs]
1-1/2" 0.799 1113 2226
2" 1 .075 1496 2992
3" 2.228 3101 6202
4" 3.174 4418 8836

Table 6b:
Restraint Force: SDR 21 Pipe
iT=50 [°F] iT=50 [°F]
Nominal Size Area (in2) S = 1392 psi S = 2785 psi
SDR 21 Pipe OD Force [lbs] Force [lbs]
-- -- -- --
2" 0.555 773 1545
3" 1 .213 1689 3378
4" 2.010 2798 5596

The above table is based on


S = e x iT x E, F=A x S, where

S = Thermal Stress, psi iT = Temperature difference, °F


F = Restraint force necessary, lbs e = Coefficient of thermal expansion =
A = Cross sectional area of pipe wall, 8 x 10-5 in/in °F
in2 E = Modulus of Elasticity =
348090.6, psi

www.us.piping.georgefischer.com 7.59
Support During Installation
In addition to the standard support Examples of supports recommended
spacing described in the next section, during installation and fusion are shown
fittings and pipe must be properly below. Note that the support for the
supported during the fusion process. This pipe and coupling joint can be accom-
will ensure a quality and maintenance- modated by using a single support for
free joint. both.

All fittings and pipe require adequate


support to prevent movement during the
fusion process. The fitting supports
may be removed after the cool-down
period, while pipe supports shall remain
in place. The pipe support requirements
Horizontal pipe runs should be
are listed in Table 8.
supported with spacing indicated in
Table 8. In addition, pipe should be
The order in which the fittings and pipe
supported on either side of the coupling
are assembled and fused will greatly
during the fusion process.
facilitate the installation process. The
following describes the recommended
practice for order of installation and for
Support
support of fittings and pipe.

Recommended order of installation:


1. Coupling joints between horizontal
pipe runs
2. Fittings branching off horizontal runs
3. Vertical pipe runs installed upwards
(recommended)
4. Fittings running off vertical runs
5. Vertical pipe runs installed
downward (not recommended)
6. Fusing close-proximity assemblies on
the ground may, in some cases, save Vertical pipe runs shall be additionally
time supported to prevent motion during
fusion.
Support during installation and fusion:
1. Pipe runs shall be supported with a
maximum spacing found in Table 8
2. Pipe shall be supported on either
side of coupling during fusion
3. Fittings shall be supported to prevent
movement of joint during fusion
4. Vertical pipe runs shall be
additionally supported to prevent
motion during fusion
5. In particular P-traps and other heavy
fittings (3”, 4”) should be supported
to prevent motion during the fusion Fittings shall be supported to prevent
process movement of joint during fusion.

7.60 GEORGE FISCHER ‡


‡ Fuseal 25/50 PVDF
Support Spacing
Apart from the support during installation
and fusion (previous section), support of
the piping system is required to provide
proper operation. The table below
outlines the suggested support spacing
of the PVDF Plenum-Rated piping system.
(Tables 8 and 9 are valid for both SDR
21 and SCH 40 Pipe)

Table 8
Support Spacing for ‡ Fuseal 25/50
Pipe size Temperature (ambient) for water**
68° F 104° F 140° F 176° F 212° F 248° F 284° F
20° C 40° C 60° C 80° C 100° C 120° C 140° C
Inches Inches Inches Inches Inches Inches Inches Inches
1-1/2” 60 60 50 50 40 40 40
2” 60 60 50 50 40 40 40
3” 60 60 50 50 40 40 40
4” 60 60 50 50 40 40 40
7
The actual support spacing is based on
the density of the liquid being
transported. The above values are
based on the density of water (1000 kg/
m3).

For applications** where the density of


the fluid being transported is greater
than 1000 kg/m3, the support spacing
will decrease. Please use Table 9 to
determine the correction factor. Multiply
the correction factor by the support
spacing length listed in Table 8 to
determine the support spacing for your
application.

Table 9
Spacing Correction Factors for ‡ Fuseal 25/50
Density [kg / m3] 1250 1500 2000 2500 2750
Correction Factor 0.94 0.83 0.77 0.70 0.57

General Properties of PVDF


Physical and Mechanical Properties

Polyvinylidene fluoride (PVDF) - is a


polymer which consists of long chains of
molecules of CH2CF2. PVDF is a strong
and tough material as reflected in its
tensile properties and impact strength,
even at low temperatures. Compared
with many thermoplastics, PVDF has
excellent resistance to creep and fatigue.
PVDF also exhibits excellent resistance to
abrasion.
www.us.piping.georgefischer.com 7.61
The chemical bonding of the fluorine Strength and Toughness
atoms in the molecule lends PVDF The strength characteristics of PVDF are
• High chemical resistance to aggres- retained over a wide range of
sive acids, aliphatics, aromatic temperature as shown in Figure D.
hydrocarbons, inorganic/organic
compounds. Stability to UV
• Outstanding thermostability PVDF maintains its mechanical properties
• Excellent combustion resistance throughout many years of outdoor
• Excellent resistance to aging exposure.

Thermal Stability Fungus Resistance


PVDF resins will not support growth of
PVDF resins have excellent thermal fungi when tested as per Method 508 of
stability. Prolonged exposure to 280°F Military Standard 810B (June 15, 1967).
does not lead to loss of weight. No
oxidative or thermal degradation has Solubility
been detected during the continuous PVDF has limited solubility. Generally,
exposure of PVDF resin at 150°C (302°F) PVDF resin is not soluble in aliphatics,
for a period of 5 years. Based on TGA hydrocarbons, aromatic hydrocarbons,
(Thermo-graviometeric Analysis),the PVDF chlorinated solvents, alcohols, acids,
resin is thermally stable to 375°C (707°F). halogens, and/or basic solutions.
Therefore, operating conditions of 280°F
or below are well within the functional Flame Spread & Smoke Developed
range of PVDF. The + GF + Fuseal 25/50 PVDF Plenum
rated system has flame and smoke
ratings that meet ASTM E-84 (UL723).

Figure D: Tensile Strength vs.


Temperature
Ultimate Tensile Strength vs. Temperature
9000
8000
Tensile Strength (psi)

7000
6000
5000
4000
3000
2000
1000
0
70 90 110 130 150 170 190 210 230 250 270 290
Temperature (F)

7.62 GEORGE FISCHER ‡


‡ Fuseal 25/50 PVDF
Table 10 Joint Strength
Surface Burning Characteristics The PVDF joints formed by electrofusion
with the +GF+ MSA 250SE/MSA 250EX
Classification Value Assigned
are permanent and have been designed
Flame Spread 0
with ample safety margins to meet the
Smoke Developed 10
needs of any Plenum application.

Operating Pressure Furthermore, the system is designed to


The standard operating pressure of the meet all the strict test requirements of
+ GF + Fuseal 25/50 PVDF Plenum System ASTM F1673.
is atmospheric, e.g., drain, waste and
vent conditions, with a maximum
pressure of 15 psi. The + GF + Fuseal
25/50 PVDF is not a pressure rated
system.

www.us.piping.georgefischer.com 7.63
7.64 GEORGE FISCHER ‡
‡ Fuseal Squared
‡ Fuseal Squared
Double Containment Polypropylene
Corrosive Waste Piping System

Pipe, Fittings, Accessories


Superior Electrofusion Technology
Fuseal Squared Reliability

www.us.piping.georgefischer.com 7.65
‡ Fuseal Squared

Fuseal Squared EPA Requirements


With standard, non-flame Fuseal utilized Federal, state, and local regulations
for both the primary and containment have been created to protect our
pipe and fittings, the Fuseal Squared environment from industrial pollution.
system offers the performance and Protection of the soil and water table are
reliability of the Fuseal II drainage of primary concern. The Fuseal Squared
system. Five advantages are realized: system, with a modular design, is a
reliable and cost-effective solution by
O The pipe and fittings are easily joined which to safely convey industrial and
with our state of the art fusion laboratory waste products. The George
technologies Fischer Corrosive Waste Piping System,
O Fuseal Squared joins to the standard including pipe, fittings, and instrumenta-
Fuseal II system without the need for tion, provides many features which
special fittings or tools benefit the owner, engineer, and installer,
O Added protection with polypropylene as well as our environment.
material for both the primary and
containment pipe Pipe and Fittings
O Custom fittings and sizes can be
quickly designed and manufactured Fuseal Squared pipe is manufactured to
to meet customer needs through our ASTM Schedule 40 requirements and all
Custom Fabrication Department and Fuseal Squared standard fittings are
O All standard primary fitting joints are fabricated to DWV patterns utilizing butt-
butt-welded and factory tested. welding technology.
The primary pipe is tested hydrostati- Fabrication allows for precise production
cally, while the containment pipe is tolerances which provide for an optimal
tested with air. fit between the primary and containment
fitting, as well as assuring standard
The standard wall thickness of Fuseal II connections to single wall Fuseal II.
makes Fuseal Squared ideal for buried
applications. Truly a complete acid The size range for pipe and fittings
waste drainage system! includes 1 1/2" x 4" through 8" x 12".
Fuseal Squared meets all requirements of
the UPC 164-2001* double containment
specification.
*pending

7.66 GEORGE FISCHER ‡


‡ Fuseal Squared

Termination Fittings Polypropylene Resin


Termination fittings also utilize the
electrofusion process to join to the single The George Fischer resin offers superior
wall pipe. No maintenance is required. chemical resistance for a broad spec-
trum of chemicals and waste products.

Centralizers +GF+ Fuseal Squared handles corrosive


drainage fluids up to 212°F (100°C)
intermittently.
Centralizers support and center the
primary pipe and fittings within the
containment pipe and fittings. Fuseal ‡ Fuseal Squared
Squared centralizers are factory welded
to the primary components, which offers Offers:
the benefit of permanent and proper
positioning in accordance with UPC 164- • Free-floating primary pipe for easy
2001*. joint per UPC, fit-up and field flexibilty.
* pending • Standard fittings are factory con- 7
structed using butt-welded joining
techniques for primary joints.
Offerings
• Reliable electrofusion system.
Leak Detection – Fuseal Squared is
capable of being electronically leak • Handles temperatures up to 212°F
detected. (100°C) intermittently.

Custom Fabrication – fabrication • Excellent chemical and corrosion


services are available per project resistance.
specifications through our Custom
Fabrications Department. • Standard connection to Fuseal II.
• George Fischer quality, field support,
and factory engineering.

Applications
+GF+ Fuseal Squared’s chemical and
physical properties make this system
ideal to handle corrosive, chemical
waste solutions for buried laboratory
and industrial DWV applications.
+GF+ Fuseal Squared is suitable for
use in virtually every application where
acids, bases, and solvents are drained
and where environmental protection is
key.
Product Range
Fittings Connection Dimensions Material
DWV pattern Electrofusion 1-1/2" x 4" through Non-flame Retardant
8" x 12" Polypropylene

Pipe Connection Dimensions Material


Schedule 40 Electrofusion 1 1/2" x 4" through Non-flame Retardant
8" x 12" Polypropylene

www.us.piping.georgefischer.com 7.67
Specifications and Material Properties
Fuseal Squared Suggested Part 2 Product
Specification Guide Manufacturer
The following specification guide can be The corrosive drainage waste and vent
used when preparing project orders or system shall be Fuseal Squared
inquiries for George Fischer, Inc. Fuseal (1 1/2" x 4" – 8" x 12") as manufactured
Squared Double Containment Corrosive by George Fischer , Inc.
Waste Piping System. Two forms are
included: Materials
1) a general specification form and The products described in this specifica-
2) a specification short form. This system tion consist of:
shall be considered for specification A. Pipe and fittings made of non-flame
in underground applications. retardant polypropylene, joined
together by electric fusion coils made
General Specification of conductive-metal wire coated in
polypropylene and either molded or
Part 1 General independently fit between the fitting
and pipe components. Pipe and
Quality Assurance fittings shall consist of both primary
The Fuseal Squared system shall be and containment components fabri-
manufactured to the following ASTM cated by the factory.
standards: B. Joining Method – The pipe and
D 4101 – Standard Specification for fittings are joined by use of the
Propylene Plastic Injection and electric fusion coils energized by a
Extrusion Materials low voltage power supply. Couplings
D 3311 – Standard Specification for shall be used as the standard joining
Drain, Waste, and Vent connection.
(DWV) Plastic Fittings Pattern C. Basic Materials / Compounds -
D 1599 – Test Method for Short-Term Fittings, pipe, centralizers, and/or
Hydraulic Failure Pressure of other components of the corrosive
Plastic Pipe, Tube, and Fittings waste drainage system shall be
D 2122 – Test Method of Determining manufactured in accordance to ASTM
Dimensions of Thermoplastic D-4101 “Standard Specification for
Pipe and Fittings Propylene Plastic Injection and
F 1290 – Standard Practice for Extrusion Materials” from either Type
Electrofusion Joining Polyolefin I, homopolymer polypropylene or
Pipe and Fitttings Type II, copolymer polypropylene.
F 1412 – Standard Specification for Source Quality Control
Polyolefin Pipe and Fittings for
Corrosive Waste Drainage A. Pipe Dimensions – Pipe shall be
Systems produced to Schedule 40 Iron Pipe
UPC 164-2001 – Standard Specification Size dimensional standards and meet
for Dual Containment ASTM F-1412 quality requirements for
Piping Systems intended “Polyolefin Pipe and Fittings for
to Convey Acid Waste Corrosive waste Drainage Systems.”
or other Special Wastes B. Fittings Design – Fittings design shall
(pending) be based upon ASTM D-3311 “DWV
Plastic Fitting Patterns.”
Submittals C. Electric Fusion Coils – Each coil shall
Catalog Data: Contractor shall submit consist of a polypropylene jacketed
_____ copies of manufacturer’s literature wire, mandrel wound, and heat fused
on the Fuseal Squared system. The on the outer surface. The coils shall
literature shall contain complete and be either molded into a polypropy-
current installation instructions. lene collar or shall be independent
and loose fitting pending the size
used. Both styles shall have a duplex
receptacle for connection to the
fusion unit.
7.72 GEORGE FISCHER ‡
‡ Fuseal Squared
D. Pipe Markings – All pipe shall be Testing and testing times shall be in
marked with +GF+ Fuseal, pipe size, accordance to local plumbing codes. If
Schedule 40, PP110, ASTM F1412, local plumbing codes are not estab-
UPC, date stamp, “Made in USA”; lished in your area, George Fischer
and be compatible with the coil recommends that the primary piping
fusion method. shall be visually inspected during a
E. Fittings – Primary components shall be hydrostatic test of the primary system
molded or fabicated via standard prior to being permanently covered by
plastic injection molding, butt-fusion the containment piping. Primary piping
or electrofusion. systems shall be tested to a maximum
Secondary components shall be of 30 feet of head. The containment
molded or fabricated via standard pipe can be tested pneumatically with
plastic injection molding, butt-fusion, a maximum 5- psi air so not to wet
manual hot air welding or the interstitial space of the system, if
electrofusion. used for leak detection purposes. All
Centralizers shall be welded to the joints are to be inspected with soapy
primary component of the fitting and/ water to detect for the presence of
or pipe. bubbles, indicating leaks.
Custom fittings shall be allowed per
engineering specification as required;
however, they shall conform to the Short Form Specification
requirements of this specification. Product Specification for George 7
F. Chemical Resistance – Fuseal Fischer Fuseal Squared
Squared meets the same chemical Double Containment Corrosive Waste
resistance values as standard Fuseal Drainage System
polypropylene material. Please
consult the chemical resistance chart Double containment acid waste drain
located in the Fuseal Squared Techni- lines shall be George Fischer Fuseal
cal Specification, Section 6. Squared, as manufactured or produced
by George Fischer, Inc. All Fuseal
Squared fittings shall be as manufac-
Part 3 Execution tured by George Fischer, Inc. so that they
Installation are compatible with Fuseal pipe. All
Fuseal Squared pipe shall conform to the
Fuseal Squared primary pipe (1 1/2" – 8") dimensional and quality requirements of
and fittings shall be installed according to ASTMF1412 as produced by George
current Fuseal Squared installation Fischer, Inc. Pipe shall be specified as
instructions. Refer to Chapter 4, Installa- Schedule 40 non-flame retardant “black”
tion Instructions, of the Fuseal Squared polypropylene. The Fuseal Squared
Technical Manual. The primary piping system shall be joined by the use of
shall be completely installed, fused, couplings with electrically resistant coils
and tested prior to fusing joints on the energized by a variable low voltage
containment piping. power supply. Pipe and fittings shall be
manufactured from either Schedule 40
Testing ASTM D-4101 Type I homopolymer
polypropylene material or Type II
Joints, 8" and smaller, may be pressure copolymer polypropylene material.Inc.
tested 10 minutes after fusing (or 30 All Fuseal Squared fittings shall be as
minutes for sizes 10" and larger.)

Table 1 Schedule 40 Dimensional Standards


Size Avg. O.D. Avg. O.D. Calc. Max. OOR
1 1/2" 1 .900 ± 0.006 0.060
2" 2.375 ± 0.006 0.070
3" 3.500 ± 0.008 0.080
4" 4.500 ± 0.009 0.100
6" 6.625 ± 0.011 0.100
8" 8.625 ± 0.015 0.150
10" 10.750 ± 0.015 0.150
12" 12.750 ± 0.015 0.150
www.us.piping.georgefischer.com 7.73
manufactured by George Fischer, Inc. so by the use of couplings with electrically
that they are compatible with Fuseal resistant coils energized by a variable
pipe. All Fuseal Squared pipe shall low voltage power supply. Pipe and
conform to the dimensional and quality fittings shall be manufactured from either
requirements of ASTMF1412 as pro- Schedule 40 ASTM D-4101 Type I
duced by George Fischer, Inc. Pipe shall homopolymer polypropylene material or
be specified as Schedule 40 non-flame Type II copolymer polypropylene mate-
retardant “black” polypropylene. The rial.
Fuseal Squared system shall be joined

Specification and Material Properties


Material Physical Properties
Material – Group 1 63153 Homopolymer Pipe Grade
Non-flame Retardant – Group 1 Homopolymer
ASTM Test No.
D792 Specific Gravity @ 23°C 0.91
D638 Tensile Yield Strength @ 2 in./min., psi 5,000
D256 Izod Impact @ 23°C, ft.lb./in. 2.2
D747 Stiffness-Flexural, 108 psi 1 .7
D676 Hardness, Rockwell R 95
D648 Heat Distortion Temp. @ 66 psi, °C 176°F, 80°C
C177 Thermal Conductivity, BTU/hr.sq.ft./°F/in. 1 .3
D694 Coefficient of Linear Expansion @ -150°F
(in./in. °F x 10-5) 5.0
D149 Dielectric Strength, volts/mil; ST 610
Power Factor @ 60 cps 0.007
D570 Water Absorption in 24 hrs., % 1 .9
D1693 Environmental Stress Cracking None
D4101 Propylene Molding & Extrusion Materials 63153

Non-Flame Retardant – Group 3 Copolymer


ASTM Test No.
D792 Specific Gravity @ 23°C 0.905
D638 Tensile Yield Strength @ 2 in./min., psi 3900
D256 Izod Impact @ 23°C, ft.lb./in. 8
D676 Hardness, Rockwell R 87
D648 Heat Distortion Temp. @ 66 psi, °C 212°F,100°C
C177 Thermal Conductivity, BTU/hr.sq.ft./°F/in. 1 .15
D694 Coefficient of Linear Expansion @ -150°F
(in./in. °F x 10-5) 6.1
D570 Water Absorption in 24 hrs., % 0.03
D1693 Environmental Stress Cracking None
D4101 Propylene Molding & Extrusion Materials 53653
7.74 GEORGE FISCHER ‡
‡ Fuseal Squared

Fuseal Squared Installation & Engineering Data


Thermal Expansion documented and the piping material will
withstand repeated flexures without
Compensation harm.
Temperature changes in waste systems Instructions for Buried
depend on the quantity and temperature
of the liquid waste discharged into the Installation
system. In general, the quantity of waste Trenching
discharged through waste systems in 1 . The bottom of the trench shall be of
laboratories and in educational institu- stable material. Where ground water
tions is relatively small (a few gallons at a is encountered, the bottom shall be
time), while industrial laboratories and stabilized with granular material of
processing systems may discharge larger 1
/2" maximum particle size. A 4"
quantities of hot or cold water and other cushion shall be placed over rock or
waste products. hardpan.
Because polypropylene piping is a poor 2. The trench width should be sufficient
conductor of heat, low volume dis- to provide working room if the pipe is
charges will not raise the system to the to be joined in the trench. Minimum
temperature of the waste and therefore,
the thermal induced length changes will
width may be used if the pipe is to be 7
joined before placing in the ditch.
be limited. High volume of wastes, 3. Trench depth – trenches under
which take longer to flow through the building slabs should allow for 12"
piping, will bring the system up to, or cover over the pipe. Trenches in
close, to the waste temperature. exposed locations should permit
Fuseal Squared, being used for buried burial of the pipe at least 12" below
applications, is not dramatically af- the maximum expected frost penetra-
fected by thermal expansion for three tion. A minimum of 24" cover should
reasons: be provided where the pipe may be
1) If the trench is properly backfilled, the exposed to heavy overhead traffic.
system is considered to be totally Applicable plumbing codes may
restrained and not subject to ther- require greater trench depth and
mally induced changes cover than technically required.
2) buried pipe is not subject to signifi-
cant changes in ambient tempera- Figure A, Trench Widths For Polypro-
tures and pylene.
3) the primary pipe is free-floating and
allows for unhindered thermal expan-
sion.
Polypropylene is not subject to stress W
cracking. It can be stressed for long H
H
periods of time in an unfriendly environ- W

ment without damage. Polypropylene


also exhibits an extremely high fatigue
life. Its “self-hinge” characteristic is well

H W
H W
Table 2 Centralizer
(Support) Spacing
Primary Pipe Size Sch. 40
1 1/2" 4'
Note: W = Trench width at top of pipe.
2" 4'
3" 5'
4" 5'
6" 5'
8" 5'
10" 5'
12" 5'
www.us.piping.georgefischer.com 7.75
Bedding and Backfill Material 2. Haunching – Install in 6" maximum
layers. Work around pipe by
The backfill material surrounding the hand to provide uniform support.
pipe shall be readily compactable and 3. Initial backfill – Install to a minimum of
shall consist of coarse sand, sand with 6" above pipe crown.
gravel or clay, sand that is free from 4. Embedment Compaction – Minimum
frozen lumps, stone larger than 1/2" and density 95% Standard Proctor per
excessive fines, silt, or clay. The material ASTM D 698. Use hand tampers or
shall fall within the Highway Research vibratory compactors.
Board Classification Group A-1, A-2 5. Final Backfill – Compact as required
(plasticity index less than 10) or A-3. by the engineer.
Bedding and Backfilling – ASTM D
2321
1 . Bedding – Install in 6" maximum
layers. Level final grade by hand.
Minimum depth 4" (6” in rock cuts)

7.76 GEORGE FISCHER ‡

You might also like