INTRODUCTION
1.1 GENERAL
1
three obvious limitations which are; the source impedance strongly influences the filtering
characteristics, parallel resonance may occur with the source impedance, and bulky in size
with fixed compensation characteristics. To solve the limitations of passive filter, active
power filter is introduced. Basically, active power filter is a power electronic converter
incorporating energy-storage element. There are two types of active power filter which are
shunt active power filter and series active power filter. These two typical active filters are
distinguished by connection with the power lines. By means of shunt connected active
power filters, which can be regarded as a kind of source current compensating for the
current harmonics drawn by non-linear loads. However, the cost of shunt active filters is
relatively high and they are not preferable for a large-scale system since the power
capacity of the filter is directly proportional to the load current to be compensated. In
addition, their compensating performance is better in the current-type harmonic source
than in the voltage-type harmonic source (3). Thus, to overcome harmonics distortion
generated by voltage fed type harmonics-producing loads, the series active filter was
introduced at the end of the 1980s. Such filter acts as a kind of harmonic isolator, since it
provides high impedance for the harmonics while providing zero impedance for the
fundamental. Besides, it reduces the need for protection of the loads because it injects
series harmonic voltage source into the supply line through injecting transformer.
In addition, the series active power filter can regulate the point of common
coupling voltage at a desired value by controlling the inverter output in order to
compensate distorted utility voltage. Combination system of series active filter and passive
filter is introduced to complement each others. Since series active filter behaves like an
active impedance, which not causing any voltage drop for the fundamental component,
instead it forces the load current harmonics into the passive filter. Therefore, series active
filter improves the filtering characteristics of passive filter and load power factor in such
way of compensating the the reactive power required by the load. On the other hand, such
combination system makes possible to significantly reduce the rating of the series active
filter. Hence, this configuration is also well known as hybrid active power filter since it
inherits the efficiency of passive filters and the improved performance of active filter.(4)
proposed adaptive fuzzy dividing frequency-control method for hybrid active power filter
is an example for a new control technique in compensating current harmonics. Considering
all advantages and limitations of the combined system, the objective of this simulation
studies is to mitigate source current harmonics drawn by typical harmonics-producing
2
loads specifically three phase diode rectifier with smoothing dc capacitor to comply with
international standards such as IEEE519-1992 and IEC61000, and evaluates the
performance of the combined filter system. In this thesis, a control scheme based on SRF
is introduced. It works well by compensating source current harmonics and source voltage
unbalance using a series hybrid active power filter. For unbalance voltage compensation,
the desired fundamental component is derived from positive sequence component of the
unbalance voltage. Then, an all-pass filter is implemented, giving a desired phase shift
without magnitude reduction.
3
suppression. The reference current can be calculated by dq transformation. An improved
generalized integrator control was proposed to improve the performance of APF. The
above all the concepts have been developed in his thesis.
The main objective of the thesis is to suppress the harmonics by using series hybrid
power filter in electrical power system with non linear loads in order to develop the power
quality of the system.
The thesis is organized into five chapters. The description about each chapter is as
follows:
Chapter 1 presents the introductory part and the objective of the thesis. It also
explains about the various suggestions given by various authors.
Chapter 3 deals with the modeling of the system and the control scheme used to
suppress the harmonics.
Chapter 4 describes the system performance without and with filter and the
simulation result for both the cases.
1.5 SUMMARY
In this chapter, how the power system is affected by harmonics and what are the
precautions and preventive measures taken by usage of filters and it has been explained
by different literature survey.
4
CHAPTER 2
- Excessive neutral current, resulting in overheated neutrals. The odd triplen harmonics in
three phase wye circuits are actually additive in the neutral. This is because the harmonic
number multiplied by the 120 degree phase shift between phases is a integer multiple of
360 degrees.
5
Figure 2.1. Additive Third Harmonics.
• Incorrect reading meters, including induction discW-hr meters and averaging type
current meters.
6
• Zero, negative sequence voltages on motors and generators. In a balanced system,
voltage harmonics can either be positive (fundamental, 4th, 7th,...), negative (2nd,
5th, 8th...) or zero (3rd, 6th, 9th,...) sequencing values. This means that the voltage
at that particular frequency tries to rotate the motor forward, backward, or neither
(just heats up the motor), respectively. There is also heating from increased losses
as in a transformer.
• Bearing failure from shaft currents through uninsulated bearings of electric motors.
• If there are voltage subharmonics in the range of 1-30Hz, the effect on lighting is
called flicker. This is especially true at 8.8Hz, where the human eye is most
sensitive, and just 0.5% variation in the voltage is noticeable with some types of
lighting.
There are many different reasons for the enormous increase in the interest in power
quality. Some of the main reasons are:
• Electronic and power electronic equipment has especially become much more
sensitive. Equipment has become less tolerant of voltage quality disturbances,
production processes have become less tolerant of incorrect of incorrect operation
of equipment, and companies have become less tolerant of production stoppages.
The main perpetrators are interruptions and voltage dips, with the emphasis in
discussions and in the literature being on voltage dips and short interruptions. High
frequency transients do occasionally receive attention as causes of equipment
malfunction.
7
• Equipment produces more current disturbances than it used to do. Both low and
high power equipment is more and more powered by simple power electronic
converters which produce a broad spectrum of distortion. There are indications that
the harmonic distortion in the power system is rising, but no conclusive results are
obtained due to the lack of large scale surveys.
• The deregulation of the electricity industry has led to an increased need for quality
indicators. Customers are demanding, and getting, more information on the voltage
quality they can expect.
2. Equipment produces more current disturbances than it used to do. Both low and
high power equipment is more and more powered by simple power electronic converters
which produce a broad spectrum of distortion. There are indications that the harmonic
distortion in the power system is rising, but no conclusive results are obtained due to the
lack of large scale surveys.
8
3. The deregulation of the electricity industry has led to an increased need for
quality indicators. Customers are demanding, and getting, more information on the voltage
quality they can expect. Some issues of the interaction between deregulation and power
quality are discussed.
Standards that define the quality of the supply have been present for decades
already. Almost any country has standards defining the margins in which frequency and
voltage are allowed to vary. Other standards limit harmonic current and voltage distortion,
voltage fluctuations, and duration of an interruption. There are three reasons for
developing power quality standards.
Voltage variation: Standard EN 50160 gives limits for some variations. For each of these
variations the value is given which shall not be exceeded for 95% of the time. The
measurement should be performed with a certain averaging window. The length of this
9
window is 10 minutes for most variations; thus very short time scales are not considered
in.
Voltage magnitude: 95% of the 10-minute averages during one week shall be within
±10% of the nominal voltage of 230 V.
Voltage unbalance Up to 2%
Sag is a decrease in rms voltage or currents to between 0.1 to 0.9 p.u at the power
frequency for duration of from 0.5 cycles to 1 minute.
Balanced Sag is an equal drop in the rms value of voltage in the three-phases of a
three-phase system or at the terminals of three-phase equipment for duration up to a few
minutes.
Voltage dip is sudden reduction in the supply voltage by a value of more than 10%
of the reference value, fallowed by a voltage recovery after a short period of time.
10
Unbalanced Fault is a short circuit or open circuit fault in which not all three
phases are equally involved.
Duration (of Voltage Sag) it is the time during which the voltage deviates
significantly from the ideal voltage.
Critical Distance is the distance at which a short-circuit fault will lead to a voltage
sag of a given magnitude for a given load position.
Interruption is the voltage event in which the voltage is zero during a certain time.
The time during which the voltage is zero is referred to as the “duration” of the
interruption. (OR) A voltage magnitude event with a magnitude less than 10% of the
nominal voltage.
Over Voltage is an abnormal voltage higher than the normal service voltage, such
as might be caused from switching and lightning surges. (OR) Abnormal voltage between
two points of a system that is greater than the highest value appearing between the same
two points under normal service conditions.
Under Voltage is a voltage event in which the rms voltage is outside its normal
operating margin for a certain period of time. (OR) A voltage magnitude event with a
magnitude less than the nominal rms voltage, and a duration exceeding 1 minute.
Swell it is a momentary increase in the rms voltage or current to between 1.1 and
1.8pu delivered by the mains, outside of the normal tolerance, with a duration of more than
one cycle and less than few seconds.
11
Recovery Time is the time interval needed for the voltage or current to return to its
normal operating value, after a voltage or current event.
Fault is an event occurs on the power system and it effects the normal operation of
the power system.
12
2.7.3 Harmonics
From the discussion already presented, it is evident that for improving power
quality, the steps given in fig (4) have to be taken. As also pointed out, the appropriate
decomposition of power for purposes of both identification and control of the distortion
elimination by filters has to be achieved. Since it is essential to use clear and consistent
terminology, the term non-active power filter will be used for equipment that eliminates
non-active power. The actual types of these filters are to be discussed in a further chapter
of this paper.
13
Identify distortion by using
Appropriate power theory
Decide on method of
Distortion elimination
Equipment with
Dynamic filters for
appropriate power
distortion
electronic input
elimination
converters.
(Dynamic input filters)
The non-active power filters to be used can be divided into the classes of input
converters, dynamic filters and tuned impedance filters. Theses principles and the control
requirements will now be discussed shortly.
Figure 2.3 Principle of input converter to eliminate distortion loads on the power network.
14
2.9 IMPROVEMENT TECHNIQUES
2.9.1 Harmonics
Harmonic Filters may be used to mitigate, and in some cases, eliminate problems
created by power system harmonics. Non-linear loads such as rectifiers, converters, home
electronic appliances, and electric arc furnaces cause harmonics giving rise to extra losses
in power equipment such as transformers, motors and capacitors. They can also cause
other, probably more serious problems, when interfering with control systems and
electronic devices. Installing filters near the harmonic sources can effectively reduce
harmonics. For large, easily identifiable sources of harmonics, conventional filters
designed to meet the demands of the actual application are the most cost efficient means of
eliminating harmonics. These filters consist of capacitor banks with suitable tuning
reactors and damping resistors. For small and medium size loads, active filters, based on
power electronic converters with high switching frequency, may be a more attractive
solution.
Benefits
• Eliminates harmonics
• Improved Power Factor
• Reduced Transmission Losses
• Increased Transmission Capability
• Improved Voltage Control
• Improved Power Quality
Other applications
• Shunt Capacitors
15
2.9.2 Voltage Flickers
Voltage flicker can become a significant problem for power distributors when large
motor loads are introduced in remote locations. Installation of a series capacitor in the
feeder strengthens the network and allows such load to be connected to existing lines,
avoiding more significant investment in new substations or new distribution lines.
Benefits
2.9.3 Bottlenecks
Bottlenecks may be relieved by the use of Series Compensation. Longer lines tend
to have stability-constrained capacity limitations as opposed to the higher thermal
constraints of shorter lines. Series Compensation has the net effect of reducing
transmission line series reactance, thus effectively reducing the line length. Series
Compensation also offers additional power transfer capability for some thermal-
constrained bottlenecks by balancing the loads among the parallel lines. The power
transfer between two-area interconnected systems is limited to 1500MW due to stability
constraints. Additional electricity can be delivered between them if Series Compensation is
applied to increase the maximum stability limits.
Benefits
16
Other applications
Regulation of the power factor to increase the transmission capability and reduce
transmission losses. Shunt capacitors are primarily used to improve the power factor in
transmission and distribution networks, resulting in improved voltage regulation, reduced
network losses, and efficient capacity utilization. Figure shows a plot of terminal voltage
versus line loading for a system that has a shunt capacitor installed at the load bus.
Improved transmission voltage regulation can be obtained during heave power transfer
conditions when the system consumes a large amount of reactive power that must be
replaced by compensation. At the line surge impedance loading level, the shunt capacitor
would decrease the line losses by more than 35%. In distribution and industrial systems, it
is common to use shunt capacitors to compensate for the highly inductive loads, thus
achieving reduced delivery system losses and network voltage drop.
Benefits
Other applications
• Harmonic Filters
The primary purpose of the shunt reactor is to compensate for capacitive charging
voltage, a phenomenon getting more prominent for increasing line voltage. Long high-
voltage transmission lines and relatively short cable lines (since a power cable has high
capacitance to earth) generate a large amount of reactive power during light power transfer
17
conditions which must be absorbed by compensation. Otherwise, the receiving terminals
of the transmission lines will exhibit a “voltage rise” characteristic and many types of
power equipment cannot withstand such over voltages. A better fine tuning of the reactive
power can be made by the use of a tap changer in the shunt reactor. It can be possible to
vary the reactive power between 50 to 100 % of the needed power.
Benefits
• Simple and robust customer solution with low installation costs and minimum
maintenance
• No losses from an intermediate transformer when feeding reactive
compensation from a lower voltage level.
• No harmonics created which may require filter banks.
2.9.6 SVC
18
Static Var Compensators are mainly used to perform voltage and reactive power
regulation. However, when properly placed and controlled, SVCs can also effectively
counteract system oscillations. A SVC, in effect, has the ability to increase the damping
factor (typically by 1-2 MW per Mvar installed) on a bulk power system which is
experiencing power oscillations. It does so by effectively modulating its reactive power
output such that the regulated SVC bus voltage would increase the system damping
capability.
Benefits
2.9.7 STATCOM
STATCOM, when connected to the grid, can provide dynamic voltage support in
response to system disturbances and balance the reactive power demand of large and
fluctuating industrial loads. A STATCOM is capable of both generating and absorbing
variable reactive power continuously as opposed to discrete values of fixed and switched
19
shunt capacitors or reactors. With continuously variable reactive power supply, the voltage
at the STATCOM bus may be maintained smoothly over a wide range of system operation
conditions. This entails the reduction of network losses and provision of sufficient power
quality to the electric energy end-users.
Benefits
20
2.9.8 Shunt Active Filters
The various nonlinear loads like Adjustable Speed Drives (ASD’s), bulk rectifiers,
furnaces, computer supplies, etc. draw non sinusoidal currents containing harmonics from
the supply which in turn causes voltage harmonics. Harmonic currents result in increased
power system losses, excessive heating in rotating machinery, interference with nearby
communication circuits and control circuits, etc.
It has become imperative to maintain the sinusoidal nature of voltage and currents
in the power system. Various international agencies like IEEE and IEC have issued
standards, which put limits on various current and voltage harmonics. The limits for
various current and voltage harmonics specified by IEEE-519 for various frequencies are
given in Table 3.1 and Table 3.2.
Table 2.2
69 kV and below 3 5
The objectives and functions of active power filters have expanded from reactive
power compensation, voltage regulation, etc. to harmonic isolation between utilities and
consumers, and harmonic damping throughout the distribution as harmonics propagate
through the system. Active power filters are either installed at the individual consumer
premises or at substation and/or on distribution feeders. Depending on the compensation
objectives, various types of active power filter topologies have evolved, a proper briefing
provided in further.
21
Table 2.3
22
2.10.2 Topology based Classification
AF’s can be classified based on the topology used as series or shunt filters, and
unified power quality conditioners use a combination of both. Combinations of active
series and passive shunt filtering are known as hybrid filters. Fig 3.3 is an example of an
active shunt filter, which is most widely used to eliminate current harmonics, reactive
power compensation (also known as STATCOM, and balancing unbalanced currents. It is
mainly used at the load end, because current harmonics are injected by nonlinear loads. It
injects equal compensating currents, opposite in phase, to cancel harmonics and/or reactive
components of the nonlinear load current at the point of connection. It can also be used as
a static VAR generator (STATCOM) in the power system network for stabilizing and
improving the voltage profile.
Fig 2.4 Current fed type AF Fig 2.5 Voltage fed type AF
Fig 2.4 shows the basic block of a stand-alone active series filter. It is connected
before the load in series with the mains, using a matching transformer, to eliminate voltage
harmonics, and to balance and regulate the terminal voltage of the load or line. It has been
used to reduce negative-sequence voltage and regulate the voltage on three-phase systems.
It can be installed by electric utilities to compensate voltage harmonics and to damp out
harmonic propagation caused by resonance with line impedances and passive shunt
compensators.
Fig 2.4 shows the basic block of a stand-alone active series filter. It is connected
before the load in series with the mains, using a matching transformer, to eliminate voltage
harmonics, and to balance and regulate the terminal voltage of the load or line. It has been
23
used to reduce negative-sequence voltage and regulate the voltage on three-phase systems.
It can be installed by electric utilities to compensate voltage harmonics and to damp out
harmonic propagation caused by resonance with line impedances and passive shunt
compensators.
Fig 2.5 shows the hybrid filter, which is a combination of an active series filter and
passive shunt filter. It is quite popular because the solid-state devices used in the active
series part can be of reduced size and cost (about 5% of the load size) and a major part of
the hybrid filter is made of the passive shunt L–C filter used to eliminate lower order
harmonics. It has the capability of reducing voltage and current harmonics at a reasonable
cost.
Fig 2.8 Hybrid filter Fig 2.9 Unified Power Quality Conditioner
24
Fig 2.9 shows a unified power quality conditioner (also known as a universal AF),
which is a combination of active shunt and active series filters. The dc-link storage
element (either inductor or dc-bus capacitor) is shared between two current-source or
voltage-source bridges operating as active series and active shunt compensators. It is used
in single-phase as well as three-phase configurations. It is considered an ideal AF, which
eliminates voltage and current harmonics and is capable of giving clean power to critical
and harmonic-prone loads, such as computers, medical equipment, etc. It can balance and
regulate terminal voltage and eliminate negative-sequence currents. Its main drawbacks are
its large cost and control complexity because of the large number of solid-state devices
involved.
This classification of AF’s is based on the supply and/or the load system having
single-phase (two wire) and three-phase (three wire or four wire) systems. There are many
nonlinear loads, such as domestic appliances, connected to single-phase supply systems.
Some three-phase nonlinear loads are without neutral, such as ASD’s, fed from three-wire
supply systems. There are many nonlinear single-phase loads distributed on four-wire
three-phase supply systems, such as computers, commercial lighting, etc. Hence, AF’s
may also be classified accordingly as two-wire, three-wire, and four-wire types.
1) Two-Wire AF’s
Two-wire (single phase) AF’s are used in all three modes as active series, active
shunt, and a combination of both as unified line conditioners. Both converter
configurations, current-source PWM bridge with inductive energy storage element and
voltage-source PWM bridge with capacitive dc-bus energy storage elements, are used to
form two-wire AF circuits. In some cases, active filtering is included in the power
conversion stage to improve input characteristics at the supply end.
2) Three-Wire AF’s
Three-phase three-wire nonlinear loads, such as ASD’s, are major applications of
solid-state power converters and, lately, many ASD’s, etc., incorporate AF’s intheir front-
end design. A large number of publications have appeared on three-wire AF’s with
different configurations. All the configurations shown in Figs 3.1–3.6 are developed, in
three-wire AF’s, with three wires on the ac side and two wires on the dc side. Active shunt
25
AF’s are developed in the current-fed type (Fig 3.1) or voltage-fed type with single-stage
(Fig 3.2) or multi-step/multilevel and multi-series configurations. Active shunt AF’s are
also designed with three single-phase AF’s with isolation transformers [18] for proper
voltage matching, independent phase control, and reliable compensation with unbalanced
systems. Active series filters are developed for stand-alone mode (Fig 3.4) or hybrid mode
with passive shunt filters (Fig 3.5). The latter (hybrid) has become quite popular to reduce
the size of power devices and cost of the overall system. A combination of active series
and active shunt is used for unified power quality conditioners (Fig 3.6) and universal
filters.
3) Four-Wire AF’s
A large number of single-phase loads may be supplied from three-phase mains with
neutral conductor. They cause excessive neutral current, harmonic and reactive power
burden, and unbalance. To reduce these problems, four-wire AF’s have been attempted.
They have been developed as: 1) active shunt mode with current feed and voltage feed; 2)
active series mode; and 3) hybrid form with active series and passive shunt mode.
26
2.10.5 Voltage Type Vs Current Type APF’s
A clear trend for preferred type of APF’s does not exist. A choice depends on
source of distortion at the specified bus, equipment cost, and amount of correction desired.
Since they are easily expandable, voltage type APF’s are likely to be used for
network wide compensation. Current type APF’s will continue to popular for single-node
distortion problems. In other words, electric utility interest will likely to be focused on
voltage type converters, while industrial users likely to use both type of converters.
In recent years, the power quality of the AC main system has become a great
concern due to the rapidly increased number of electronic equipment. In order to reduce
the harmonic contamination in power lines and improve the transmission efficiency Active
power filters become essential. A current source is connected in parallel with nonlinear
load and controlled to generate the harmonic currents needed for the load.
27
The basic configuration of a three-phase three-wire active power filter is shown in
Fig 2.9 The diode bridge rectifier is used as an ideal harmonic generator to study the
performance of the Active filter. The current-controlled voltage-source inverter (VSI) is
shown connected at the load end. This PWM inverter consists of six switches with
antiparallels diode across each switch. The capacitor is designed in order to provide DC
voltage with acceptable ripples. In order to assure the filter current at any instant, the DC
voltage Vdc must be at least equal to 3/2 of the peak value of the line AC mains voltage.
The main sources of harmonic current are at present the phase angle controlled
rectifiers and inverters. These are often called static power converters. These devices take
AC power and convert it to another form, sometimes back to AC power at the same or
different frequency, based on the firing scheme. The firing scheme refers to the controlling
mechanism that determines how and when current is conducted. One major variation is the
phase angle at which conduction begins and ends. A typical such converter is the
switching-type power supplies found in most personal computers and peripheral
equipment, such as printers. While they offer many benefits in size, weight and cost, the
large increase of this type of equipment over the past fifteen years is largely responsible
for the increased attention to harmonics. Figure shows how a switching-type power supply
works. The AC voltage is converted into a DC voltage, which is further converted into
other voltages that the equipment needs to run. The rectifier consists of semi-conductor
devices (such as diodes) that only conduct current in one direction. In order to do so, the
voltage on the one end must be greater than the other end. These devices feed current into
a capacitor, where the voltage value on the cap at any time depends on how much energy
is being taken out by the rest of the power supply. When the input voltage value is
higher than voltage on the capacitor, the diode will conduct current through it. This results
in a current waveform and harmonic spectrum . Obviously, this is not a pure sinoidal
waveform with only a 60 Hz frequency component.
28
Fig.2.10 Output current waveform
Fluorescent lights can be the source of harmonics, as the ballasts are non-linear
inductors. The third harmonic is the predominate harmonic in this case. As previously
mentioned, the third harmonic current from each phase in a four-wire wye or star system
will be additive in the neutral, instead of cancelling out Some of the newer electronic
29
ballasts have very significant harmonic problems, as they operate somewhat like a
switching power supply, but can result in current harmonic distortion levels over 30%.
Low power, AC voltage regulators for light dimmers and small induction motors
adjust the phase angle or point on the wave where conduction occurs. Medium power
converters are used for motor control in manufacturing and railroad applications, and
include such equipment as ASDs (adjustable speed drives) and VFDs (variable frequency
drives). Metal reduction operations, like electric arc furnaces, and high voltage DC
transmission employ large power converters, in the 2-20MVA rating. This type of 3-phase
equipment may also cause other types of power quality problems. When the semiconductor
device is supposed to turn-off, it does not do so abruptly. This happens under “naturally”
commutated conditions, where the voltage that was larger on the anode side compared to
the cathode is now the opposite. This occurs each cycle as the voltage waveform goes
through the sine waveform. It also happens under “forced” commutation conditions, where
the semi-conductor device has a “gate”-type control mechanism built in to it. This
commutation period is a time when two semiconductor devices are both conducting
current at the same time, effectively shorting one phase to the other and resulting in large
current transients. When transformers are first energized, the current drawn is different
from the steady state condition. This is caused by the inrush of the magnetizing current.
The harmonics during this period varies over time. Some harmonics have zero value for
part of the time, and then increase for a while before returning to zero. An unbalanced
transformer (where either the output current, winding impedance, or input voltage on each
leg are not equal) will cause harmonics, as will overvoltage saturation of a transformer.
Wherever the aforementioned equipment is used, one can suspect that harmonics are
present. The amount of voltage harmonics will often depend on the amount of harmonic
currents being drawn by the load, and the source impedance, which includes all of the
wiring and transformers back to the source of the electricity. Ohm’s Law says that Voltage
equals Current multipled by Impedance. This is true for harmonic values as well. If the
source harmonic impedance is very low (often referred to as a “stiff” system) then the
harmonic currents will result in lower harmonic voltages than if the source impedance
were high (such as found with some types of isolation transformers). Like any power
30
quality investigation, the search can begin at the equipment effected by the problem or at
the point-of-common-coupling (PCC), where the utility service meets the building
distribution system. If only one piece of equipment is effected (or suspected), it is often
easier to start the monitoring process there. If the source is suspected to be from the utility
service side (such is the case when there is a neighboring factory that is known to generate
high harmonics), then monitoring usually begins at the PCC.
The phase voltages and currents, as well as the neutral-to-ground voltage and
neutral current should be monitored, where possible. This will aid in pinpointing problems,
or detecting marginal systems. Monitoring the neutral will often show a high 3rd harmonic
value, indicating the presence of non-linear loads in the facility.
Hand-held harmonic meters can be useful tools for making spot checks for known
harmonic problems. However, harmonic values will often change during the day, as
different loads are turned on and off within the facility or in other facilities on the same
electric utility distribution system. This requires the use of a harmonic monitor or power
quality monitor with harmonic capabilities which can record the harmonic values over a
period of time. Power Quality Monitor with Harmonic Analysis Typically, monitoring will
last for one business cycle. A business cycle is how long it takes for the normal operation
of the plant to repeat itself. For example, if a plant runs three identical shifts, seven days a
week, then a business cycle would be eight hours.
More typically, a business cycle is one week, as different operations take place on a
Monday, when the plant equipment is restarted after being off over the weekend, then on a
Wednesday, or a Saturday, when only a skelton crew may be working. Certain types of
loads also generate typical harmonic spectrum signatures, that can point the investigator
towards the source. This is related to the number of pulses, or paths of conduction. The
general equation is h = ( n * p ) +/- 1, where h is the harmonic number, n is any integer
(1,2,3,..) and p is the number of pulses in the circuit, and the magnitude decreases as the
ration of 1/h (1/3, 1/5, 1/7, 1/9,...). Table 4 shows examples of such.
31
Most electrical loads (except half-wave rectifiers) produce symmetrical current
waveforms, which means that the positive half of the waveform looks like a mirror image
of the negative half. This results in only odd harmonic values being present. Even
harmonics will disrupt this half-wave symmetry. The presence of these even harmonics
should cause the investigator to suspect there is a half-wave rectifier on the ciruit. This
also result from a full wave rectifier when one side of the rectifier has blown or damaged
components. Early detection of this condition in a UPS system can prevent a complete
failure when the load is switched onto back-up power. To determine what is normal or
acceptable levels, a number of standards have been developed by various organizations.
ANSI/IEEE C57.110 Recommended Practice for Establishing Transformer Compatibility
when supplying non sinusoidal load currents is a useful document for determining how
much a transformer should be derated from its nameplate rating when operating in the
presence of harmonics. There are two parameters typically used, called K-factor and TDF .
Some power quality harmonic monitors will automatically calculate these values. IEEE
519-1992 Recommended Practices and Requirements for Harmonic Control in Electrical
Power Systems provides guidelines from determining what are acceptable limits.
For voltage harmonics, the voltage level of the system is used to determine the
limits. At the higher voltages, more customers will be effective, hence, the lower limits.
The European Community has also developed susceptibility and emission limits for
harmonics. Formerly known as the 555-2 standard for appliances of less than 16 A, a more
encompassing set of standards under IEC 1000-4-7 are now in effect.
Care should be undertaken to make sure that the corrective action taken to
minimize the harmonic problems don’t actually make the system worse. This can be the
result of resonance between harmonic filters, PF correcting capacitors and the system
impedance. Isolating harmonic pollution devices on separate circuits with or without the
use of harmonic filters are typical ways of mitigating the effects of such. Loads can be
relocated to try to balance the system better. Neutral conductors should be properly sized.
Phase conductors are particularly important with some modular office partition-type walls,
which can exhibit high impedance values. The operating limits of transformers and motors
should be derated, in accordance with industry standards from IEEE, ANSI and NEMA on
32
such. Use of higher pulse converters, such as 24-pulse rectifiers, can eliminate lower
harmonic values, but at the expense of creating higher harmonic values.
Electronic filters are electronic circuits which perform signal processing functions,
specifically to remove unwanted frequency components from the signal, to enhance
wanted ones, or both. Electronic filters can be:
• passive or active
• analog or digital
• high-pass, low-pass, band pass, band-reject (band reject; notch), or all-pass.
• discrete-time (sampled) or continuous-time
• linear or non-linear
• infinite impulse response (IIR type) or finite impulse response (FIR type)
The passive filters have been used as a conventional solution to solve harmonic
currents problems, but they present some disadvantages: they only filter the frequencies
they were previously tuned for; its operation cannot be limited to a certain load or group of
loads; resonance can occur due to the interaction between the passive filters and others
loads, with unexpected results.
33
and capacitors to determine the time-constants of the circuit, and therefore the frequencies
to which it responds.
The inductors and capacitors are the reactive elements of the filter. The number of
elements determines the order of the filter. In this context, an LC tuned circuit being used
in a band-pass or band-stop filter is considered a single element even though it consists of
two components.
At high frequencies (above about 100 megahertz), sometimes the inductors consist
of single loops or strips of sheet metal, and the capacitors consist of adjacent strips of
metal. These inductive or capacitive pieces of metal are called stubs.
The simplest passive filters, RC and RL filters, include only one reactive element, except
hybrid LC filter which is characterized by inductance and capacitance integrated in one
element.
An L filter consists of two reactive elements, one in series and one in parallel.
34
Fig.2.14 High-pass T filter
Three-element filters can have a 'T' or 'π' topology and in either geometries, a low-
pass, high-pass, band-pass, or band-stop characteristic is possible. The components can be
chosen symmetric or not, depending on the required frequency characteristics. The high-
pass T filter in the illustration has a very low impedance at high frequencies, and a very
high impedance at low frequencies. That means that it can be inserted in a transmission
line, resulting in the high frequencies being passed and low frequencies being reflected.
Likewise, for the illustrated low-pass π filter, the circuit can be connected to a transmission
line, transmitting low frequencies and reflecting high frequencies. Using m-derived filter
sections with correct termination impedances, the input impedance can be reasonably
constant in the pass band.
Multiple element filters are usually constructed as a ladder network. These can be
seen as a continuation of the L,T and π designs of filters. More elements are needed when
it is desired to improve some parameter of the filter such as stop-band rejection or slope of
transition from pass-band to stop-band.
With this filter it is possible to effectively compensate the harmonic currents and
the reactive power (correcting power factor to the unity), and also to balance the power
supply currents (distributing the loads for the three-phases in equal form, and
compensating zero sequence current).
An active filter is a type of analog electronic filter, distinguished by the use of one
or more active components i.e. voltage amplifiers or buffer amplifiers. Typically this will
be a vacuum tube, or solid-state (transistor or operational amplifier).
35
Active filters have three main advantages over passive filters:
• Inductors can be avoided. Passive filters without inductors cannot obtain a high
Q (low damping), but with them are often large and expensive (at low
frequencies), may have significant internal resistance, and may pick up
surrounding electromagnetic signals.
• The shape of the response, the Q (Quality factor), and the tuned frequency can
often be set easily by varying resistors, in some filters one parameter can be
adjusted without affecting the others. Variable inductances for low frequency
filters are not practical.
• The amplifier powering the filter can be used to buffer the filter from the
electronic components it drives or is fed from, variations in which could
otherwise significantly affect the shape of the frequency response
2.13 SUMMARY
In this chapter, the functions of active filter and passive filter are explained. It
also deals with the harmonic present in the system.
36
CHAPTER 3
MODELLING
3.1 INTRODUCTION
Filters are used to restrict the flow of harmonic currents in the Power Systems. It is
a LC circuit, which passes all frequencies in its pass bands and stops all frequencies in its
stop bands. There are two basic types of filters. They are active filter and passive filter.
The simplest method of harmonic filtering is with passive filters. It uses the reactive
storage components, namely capacitors and inductors.
Shunt passive filter is the Combination of L and C elements, which are connected
in parallel with the line. It will restrict the flow of harmonics through the line. Fig-3.1
shows the configuration of Shunt passive Filter.
37
Fig.3.1The configuration of Shunt passive filter
The active filter concept uses power electronics to produce harmonic current
components that cancel the harmonic current components from the non-linear loads. The
active filter uses power electronic switching to generate harmonic currents that cancel the
harmonic currents from a non-linear load. The active filter configuration investigated in
this lecture is based on a Pulse-Width Modulated (PWM) voltage source inverter that
interfaces to the system through a system interface filter as shown in Figure 3.1 . In this
configuration, the filter is connected in parallel with the load being compensated.
Therefore, the configuration is often referred to as an active parallel or shunt filter. Figure
1 illustrates the concept of the harmonic current cancellation so that the current being
supplied from the source is sinusoidal. The voltage source inverter used in the active filter
makes the harmonic control possible. This inverter uses dc capacitors as the supply and
can switch at a high frequency to generate a signal that will cancel the harmonics from the
non-linear load.
The active filter does not need to provide any real power to cancel harmonic
currents from the load. The harmonic currents to be cancelled show up as reactive power.
Reduction in the harmonic voltage distortion occurs because the harmonic currents flowing
through the source impedance are reduced. Therefore, the dc capacitors and the filter
components must be rated based on the reactive power associated with the harmonics to be
38
cancelled and on the actual current waveform (rms and peak current magnitude) that must
be generated to achieve the cancellation.
The current waveform for cancelling harmonics is achieved with the voltage source
inverter in the current controlled mode and an interfacing filter. The filter provides
smoothing and isolation for high frequency components. The desired current waveform is
obtained by accurately controlling the switching of the Insulated Gate Bipolar Transistors
(IGBTs) in the inverter. Control of the current wave shape is limited by the switching
frequency of the inverter and by the available driving voltage across the interfacing
inductance.
The driving voltage across the interfacing inductance determines the maximum
di/dt that can be achieved by the filter. This is important because relatively high values of
di/dt may be needed to cancel higher order harmonic components. Therefore, there is a
trade-off involved in sizing the interface inductor. A larger inductor is better for isolation
from the power system and protection from transient disturbances. However, the larger
inductor limits the ability of the active filter to cancel higher order harmonics.
The power circuit topology of a combination series active filter with shunt passive
filters on three phase system, feeding non-linear loads which is a three phase bridge diode
rectifier with smoothing dc capacitor. The designed LC passive filters is single-tuned at
5th and 7th harmonic frequency, both are parallel connected to the power line before the
load. Installation of such passive filter in the vicinity of the non-linear load due to its
responsibility as a harmonic sink path for the tuned harmonic frequency, and also helps in
lowering the power rating of active power filter. A three-phase Voltage Source Inverter
(VSI) is connected in series with the power line via three single phase series coupling
transformer in order to inject the compensation voltage. This VSI is three phase bridge
configuration consist of six Insulated Gate Bipolar Transistor (IGBT) switch connected
with anti-parallel diodes and snubber circuit, is fed by SVPWM control signal from the
controller. Harmonic mitigation by active filters is entirely depends on modulation method
where SVPWM technique has distinct advantages and displays very good characteristics
over this matters. SVPWM has the following advantages over other control schemes in
terms of the use factor of the DC side voltage is high; switching losses are low; in
39
applications such as motor drives it can be conveniently used as flux tracking control or
current control; and also it is easy to digitally implement the modulation scheme. Fig 3.3
indicates the basic switching and sectors applied in SVPWM technique. In order to
implement SVPWM following steps needs to be determined. Firstly, determination of
stationary d-q reference frame vectors Vd, Vq, and reference voltage vector vref and angle;
next step is to determine the time duration T1, T2 and T0; and lastly,
To determine the switching time of each switch applied in VSI. For the
simulation study using Matlab/Simulink, only the configuration of Shunt passive Filter Vd,
Vq, Vref and is required for SVPWM generator block. The turn ratio of the series coupling
transformer connecting the active power filter to the power line is chosen to be 1:1 ratio.
This type of transformer is not only isolate SVPWM-VSI from the power line, but also
matching the voltage and current rating of SVPWM inverter with that of the power line.
The harmonic-producing load is a three-phase diode rectifier with capacitive dc load
having characteristics of voltage-type harmonics. Smoothing dc capacitor capacitance
value is 1000 (μF), while load resistance is 50Ω. System parameters used in the simulation
is depicted on Table 1. Hence, with implementation of Mat lab/Simulink, the simulation
and performance of the system is executed well.
40
41
Fig 3.2 Series Hybrid Power Filter Circuit Configuration
42
Fig 3.3 Basic switching vectors and sectors
43
Table 3.1: System Parameters
For accurate estimation of the fundamental component, two methods are dominant
and widely used in reference generation control; SRF control theory is utilized for the
proposed system. It has been confirmed that SRF controller achieves significant
performance improvement for active filter implementation without any assumptions
regarding supply power quality. Practically the series active filter is controlled in a manner
where there is no impedance at fundamental frequency and insertion of gain K (Ω)
between source and load at harmonic frequency.
Based on series active filter control used in, derivation of balanced positive-
sequence components from unbalanced voltages but without predicted reference voltages,
control of the system begins to be designed. The balanced positive components is derived
from unbalanced sets can be expressed in equation below,
..……. (3.1)
44
The j meaning phase shift angle of 90, is obtained using all-pass filter which is given using
the following equation,
….….. (3.2)
Here, b=377 (rad/s) and c=π/2. The variables ea(+), eb(+), and ec(+), the balanced positive
sequence components is used to derive source phase angle, θ by employing d-q
transformation, as depicted in (3.3),
…….(3.3)
……… (3.4)
3.3.2 Compensation of Source Voltage Unbalance
The equations (3.3) and (3.4) employs that the d-q quantities which are
transformed into SRF based on equation proposed by
………....(3.5)
Where, the superscript “e” means a quantity in SRF.
Thus, required fundamental component of balanced source voltage is obtained from,
45
……..(3.6)
……..(3.7)
Using (3.6), reference voltage for unbalance compensation is determined by,
………(3.8)
………(3.9)
If esh, vc and vLh are harmonic of source voltage, injected voltage, and load voltage
harmonic, respectively. Whereby, zsh represents source side harmonic impedance. Given
the reference voltage for current harmonic compensation, vc expressed as,
………..(3.10)
46
The harmonic source current is suppressed to be zero provided that the source
voltage is assumed to be sinusoidal. Since zsh is so small that can be neglected, and vc has
no fundamental component. Hence, vLh is can be assumed using following equation,
………..(3.11)
Avoiding additional voltage sensor, the estimated load voltage is obtained from,
……...….(3.12)
Here, es and is are source voltage and current respectively, while vL is load
voltage. Source impedance zs is assumed to be negligible because it is usually 2%-5% p.u.
Secondly, reference voltage compensating for the current-type harmonic source is
calculated from the harmonic current comes from the source side, which is equal to
….......….(3.13)
…….(3.14)
47
…......…..(3.15)
Thus by combining eqns. (3.4) & (3.6), new reference voltage for the current
harmonics compensation is formed, which is expressed by,
………..(3.16)
Here ,Kvh is a controller gain which is far bigger than Zf, an equivalent impedance
of the shunt passive filter . To achieve optimized and good performance in controlling the
reference voltage and balance voltage magnitude, Kvh and Kh, both is set to 1.
Therefore, from (8) and (16) the reference voltages are current harmonics
compensation and unbalance compensation are add together to become,
…….......(3.17)
The resultant reference voltage or control voltage signal then is transformed into d-
q axis, after being transformed into 2 phase quantities from three phase quantities using
Clarke transformation to obtain vd,c and vq,c. These two values is then used to calculate for
the magnitude and angle for reference voltage vector , vref,c. Hence,
………..(3.18)
48
………….(3.19)
As a result, these values are used in generating the gating signal fired by
SVPWM.
In order to tuned LC shunt passive filter, resonant frequency for specific harmonic
frequency need to be calculated first, hence, using well-known fact that the passive filter
presents good filtering characteristics around vicinity of the resonant frequency. Given Lf
and Cf are respective filter inductance and capacitance , therefore the equation for resonant
frequency ,fr is as follows,
………..(3.20)
………..(3.21)
.……. (3.22)
49
from the primary of the series transformer, Zpwm is the amplitude of the sum of the source
impedance, Zs and load impedance, ZL. If “a” is the transformer ratio, thus, corresponding
equation as given above.
……….(3.23)
Where XCr and XLr are the capacitive and inductive reactance of the ripple filter
respectively. The harmonics current caused by switching voltage ripple, Vr are completely
shunted by Cr, the ripple filter capacitor.
50
Fig.3.5 (Lower trace) after filtering
…………(3.24)
51
Fig 3.7 (Lower trace) THD spectrum after filtering
Upper trace shows severely distorted source current harmonics before filtering, but
after filtered by hybrid power filter, the source current looks smooth and clean as shown at
lower trace. This is due to harmonics produced by diode rectifier with RC load flowing
back to the source that in turn affected the source current. Obviously, the current effective
value has been dropped to more than half, while it is measured a total up to 68% content of
total harmonic distortion (THD), where, 2/3 of it is 3rd harmonic alone. The 3rd harmonic
is more dominant than expected 5th or 7th harmonic because of source voltage unbalance
influence. However, after combination filter system is installed on the power circuit,
source current harmonics is significantly decreased due to the harmonics has been
mitigated. Measured THD for filtered source current shows only 0.5% harmonics left in
the current. Hence, source current looks almost fundamental waveform in shape.Two
different condition of bar plots for in total 25 orders of spectrum harmonics which is
calculated using Fast Fourier Transform (FFT) algorithm. Upper trace plot which is the
uncompensated source current owns substantial distorted harmonics spectrum that can be
observed. From the upper plot, it can be seen that dominant harmonics such as 3rd, 5th and
7th are high in magnitude, whereas the much higher order harmonics can be considered
much lower in magnitude. The plot also shows typical harmonic producing load
characteristics that as the order of harmonic increased, the magnitudes are decreasing.
52
Provided that for lower trace plot, harmonic order other than fundamental is
hardly to be seen. There is significant reduction of harmonics content in the source current
after filtering. Clearly, the outcome has surpassed well below the standard level of 5% for
IEEE519-1992. Although the passive filters only tuned the 5th and 7th harmonics, the 3 rd
harmonic is mainly compensated through series active filter that provides high resistance
for the harmonics but allowing only fundamental component flows into the source current.
3.4 SUMMARY
The system configuration of shunt active filter and the control scheme for
suppressing harmonics is verified in this chapter.
53
CHAPTER-4
DESIGN OF FILTERS
4.1 INTRODUCTION
A simple power system with non linear load is considered and its output waveform
is found out and given below. The simple power system has the source input voltage of
230V and frequency of 50Hz. The non-linear load has the following parameters of
capacitance 1µF, inductance 0.5mH and resistance of 0.5Ω.From the simulation result the
output waveform has total harmonic distortion of 5%.
54
Fig 4.1 A system with nonlinear load
4.4 SUMMARY
From the system performance and simulation results, the output waveform with
harmonics is found out without using filters.
55
4.5 INTRODUCTION FOR A SYSTEM WITH FILTERS
Various filters are designed in various systems in order to reduce harmonics
present in the system and the value of total harmonic distortions for that system.
56
4.7 SIMULATION RESULTS
Fig 4.3 – Three – Phase Thyristor Converter’s current and voltage waveforms
57
Fig 4.4 – Three – Phase Harmonic Filter with total harmonic distortion value
58
Fig 4.5 – Three Phase Harmonic Filters with sampling time period
59
4.8 SUMMARY
The output of the system with filters describes the system without harmonics or
any other voltage unbalance or current unbalance in the output.
60
CHAPTER-5
CONCLUSIONS
Finally, it has been concluded that the simulation of the system presented in this
thesis shows harmonic supression of source current to the level that comply the standard of
IEEE519-1992 and IEC61000 by using filters.
Initially a simple system is considered with non linear load and the harmonics
present in the system is analyzed without using filters and the output harmonics as well as
the order of the harmonics present in the system are found out from the output results.
Finally, filters are added to the system and the harmonics are deleted and the THD value
is calculated using
2. Output waveform and the order of the harmonics of the system with tunable
band pass filter are evaluated.
61
REFERENCES
1. Adil M-Zamil and Torrey. D.A. , “A Passive Series Active Shunt Filter for High
Power Application”, IEEE Transactions on Power Electronics, 16(1), January
2001, pp. 1010-109.
2. Akagi.H, “Modern active filters and traditional passive filters”, Bulletin of the
Polish Academy of Sciences, Vol 54, No.3. 2006, pp.255-269.
4. An Luo, Zhikang Shuai, Wenji Zhu, Ruixiang Fan, and Chunming Tu,
‘‘Development of Hybrid Active Power Filter Based on the Adaptive Fuzzy
Dividing Frequency-Control Method’’, IEEE Trans. on Power Delivery, Vol. 24,
No. 1, Jan. 2009, pp. 424-432.
6. Myoung Lee.G, Dong-Choon Lee and Jul-Ki Seok, “Control of Series Active
Power Filters Compensating for Source Voltage Unbalance and Current
Harmonics”, IEEE Trans. on Ind. Electron., Vol. 51, No. 1, Feb. 2004, pp. 132-
139.
62
8. Rahim. N.A , Mekhilef. S and Zahrul. I , “Design and Implementation of Single
Phase Hybrid Active Power Filter Controller”, IEEE PEDS 2005, Kuala Lumpur,
Malaysia, pp. 944-948.
63