UniGear
The Refinement
in MV Switchgear
UniGear: an innovative solution for all installation requirements
2
Double level UniGear switchgear. Each panel
consists of two independent stacked units which
can be equipped with circuit-breaker or contactor.
UniGear switchgear with simple busbar system coupled to UniGear type ZVC
contactor units. Each type ZVC unit is equipped with a withdrawable vacuum
contactor with fuses.
3
UniGear switchgear with simple busbar system
Height
Branch connection rated current A 630 630 630 630
1250 1250 1250 1250
1600 1600 1600 1600
2000 2000 2000 2000
2500 2500 2500 2300
3150 3150 3150 –
Branch connection rated current A 3600 3600 3600 2500
with forced ventilation 4000 4000 4000 – Width Depth
Unit width mm 550-650 550-650 550-650 –
800-1000 800-1000 800-1000 800-1000 A Apparatus D Instruments
1000 1000 1000 1000 B Main busbar E Gas exhaust duct
Unit height mm 2200 2200 2200 2325 C Feeder
Unit height with gas duct mm 2595 2595 2595 2720
Unit depth (1) mm 1340/1390 1340/1390 1340/1390 1700
(1) 1390 mm from 3150 to 4000 A
IF BT R RM M IFD IFDM
Incoming/Outgoing Bus-tie Bus-riser Bus-riser Measurements Direct incoming/ Direct incoming/
feeder with measurements Outgoing feeder Outgoing feeder
with measurements
Standard components Accessories Alternative solutions
4
Double level UniGear switchgear
Height
Peak current kA …125 …125 …100
Internal arc withstand current kA 1s …40 …40 …40
kA 0.5s …50 …50 – D e B1 D
Standard components
IF IF IF IF IF IF Accessories
Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Incoming/Outgoing Alternative solutions
5
UniGear switchgear with double busbar system
The double busbar system switchgear is based on two – flexibility during the inspection and maintenance
different schemes: procedures without interruption of the load
– two busbar systems, two line-side isolators and a – possibility of extension without turning the switchgear
circuit-breaker (up to 2500 A) off.
– two busbar systems, two circuit-breaker units with one
The switchgear requires access from the rear for the
or two circuit-breakers.
installation and maintenance procedures. The service
The schemes offer redundancy of the busbar system
operations are carried out from the front.
with physical isolation between the systems. The use of
this switchgear may be necessary in the case of:
– switching incoming units with unsynchronised circuit- Studied to offer
breakers Line with double isolation up to 2500 A
– disconnection of loads with different levels of impor- 3150 A and 4000 A duplex line
tance under emergency conditions Segregated busbar and isolation compartments
– isolation of particular outgoing units from the normal
Earthing switch with making capacity
network
Operations can be carried out from the front
– balance of the outgoing units under normal service
Reliable and uninterrupted service conditions
conditions
Height
Internal arc withstand current kA 1s …31.5 …31.5 …25
Main busbar rated current A 1250...4000 1250...4000 1250...2500
Branch connection rated current A 630...3150 630...3150 630...2000
Branch connection rated current A 3600...4000 3600...4000 –
with forced ventilation
Unit width mm 650-800 650-800 800
1000 1000 1000 Depth
Unit height mm 2200 2200 2200 Width
Unit height with gas duct mm 2595 2595 2720 A Apparatus C Feeder
Unit depth (1) mm 2070/2120 2070/2120 2570 B1 Busbar 1 D Instruments
(1) 2120 mm from 3150 to 4000 A B2 Busbar 2 E Gas exhaust duct
6
UniGear type ZVC switchgear for motor switching and control
Height
Unit height mm 2200/2595 2200/2595 A A
Unit height with gas duct mm 2675 2675
Unit depth mm 1125 1125
1 2 Depth
Width
A Apparatus D Instruments
B Main busbar E Gas exhaust duct
C Feeder
3 Off
Standard components
Accessories
Alternative solutions
7
We reserve the right to make changes in the course of technical development of the product.
1VCP000070 – Rev. D, en – Brochure – 2006.07
The data and illustrations are not binding.