You are on page 1of 41

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery

Application of Distance Protection

Jay Gosalia
Vice President of Marketing
Doble Engineering Company
Distance Protection

¾ 3 Zones of protection
¾ Zone 1 operates with no intentional time
delay
¾ Zone 2 provides back up protection to Zone
1 and operates with some time delay
¾ Zone 3 typically has offset characteristic
and has a time delay longer then Zone 2
¾ Zone 2 and Zone 3 are used in pilot
scheme if employed

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
General Application Rules
A B C D

Zone 3
Zone 2
Time

Zone 1

Zone11protects
¾¾ Zone protects80-85%
80-85%of ofline
linelength
lengthABAB
Zone22protects
¾¾ Zone protectsline
lineAB
AB++50%
50%of ofline
lineBC
BC
Zone33Protects
¾¾ Zone ProtectsABAB++Line
LineBCBC++20-30%
20-30%ofofline
lineCD
CD++20-30%
20-30%
ofline
of linebehind
behindterminal
terminalAA

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reach Setting Criteria : Zone 1
A B C D

Zone 1

¾ Zone 1 should never over reach for the faults on or


beyond remote terminal
ƒ Considering 5% accuracy of CTs and PTs maximum
reach of Zone 1 can be 90% of line length AB
ƒ Considering accuracy of Zone 1 protection 5% and safety
margin of 5% Zone 1 reach can be 80% of the line length.
ƒ In some instances based on the previous practices Zone
1 is set to 90% of line length
ƒ It is safe to set Zone 1 reach 80% of line length in general

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Zone 1: Requirements
A B C D

Zone 1

¾ Should cover the protected circuit and should


provide good fault resistance coverage
¾ Fast operation for limiting the system disturbance
¾ Directional discrimination for security and reliability

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reach Setting Criteria : Zone 2
A B C D

Zone 2

¾ Zone 2 should always over reach for the faults on or


beyond remote terminal
ƒ Zone 2 should always reach beyond the remote terminal and
cover at least 50% of next line section
ƒ Zone 2 time delay should be larger then the operating time
of Protection + CB (at terminal C of line CD) + safety margin
• Breaker fail timer co ordination is required
ƒ Zone 2 is used in the pilot aided trip scheme to provide
instantaneous protection for faults anywhere on line BC

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Zone 2 Time Delay : Criteria
A B C D

1 2 3 4 5 6

Zone 2

¾ Determine Zone 2 time if Breaker fail protection is employed


ƒ Breaker fail protection clears the fault by tripping back up breaker if
the primary breaker fails to clear the fault after the protection trip
¾ For fault on line CD, protection at breaker 5 will see the fault and
issues a trip command to breaker 5 and at the same time initiates
breaker fail protection
ƒ If breaker 5 trip it resets the breaker fail protection
ƒ The fault is seen by the protection at breaker 3, in Zone 2.
ƒ If breaker 5 fails then Breaker fail protection trip all breakers at bus C
¾ What should be the Zone 2 time delay for protection at breaker 3?

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Breaker Fail Scheme
¾ Breaker fail scheme principle
ƒ Consists of a timer, high speed pick up/drop out over
current protection and lock out protection
ƒ Some time re-trip protection is employed
ƒ Needs 52a breaker input to sense breaker status
¾ When protection operates it initiates breaker fail
scheme
ƒ Timer is starts and seals in with the high speed over
current protection
ƒ Issues re trip command to second trip coil of the breaker
ƒ If breaker trips then 52a resets the timer and at the same
time over current protection.
ƒ If breaker fails to trip then timer times out and picks up lock
out protection to trip the back up breakers connected to the
bus
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Breaker Fail Protection Logic

62X
62Y
OR

AND Timer 86
50

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Timing Diagram : Normal Operation

Drop out time


Protection
Of current prot : 1 Cy.
Trip: 1Cy.
Operating Margin: 5 Cy.
Time of CB: 2Cy.

Breaker fail timer time delay : 7 Cy.

Breaker fail protection start

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Timing Diagram : Failed CB

Drop out time


Protection
Of current prot : 1 Cy.
Trip: 1Cy.
Operating Margin: 5 Cy.
Time of CB: 2Cy.

Breaker fail timer time delay : 7 Cy. Operating Margin


Breaker fail Time of CB: 2 Cy. 7 Cy.
Breaker fail protection start Protection trip : 0.5 Cy

Remote Zone 2 Back up protection operation time :say 20 Cy.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reach Criteria Zone 3
¾ Zone 3 is a back up protection and last resort for the
isolation of the fault if everything fails
¾ Time Delayed protection. Time delay is longer then
Zone 2 delay
¾ When a very long line is following the short line Zone
3 reach may be very long
ƒ Can interfere with load on the line
ƒ Lens characteristic is a potential solution
¾ It is used in the pilot aided protection when blocking
scheme is employed to detect the fault direction
¾ Typically set in the offset mode to cover the reverse
fault
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Zone 3 : Load Encroachment

Load

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Zone 1 Reach : 3 Terminal Line
X Ix Ix + Iy Z

d
Iy

Faultvoltage
Fault voltageatatXX==VVF==Ix*Z
Ix*ZF++Iy* Iy*(1-d)Z
(1-d)ZF
F F F
Fault current at X =
Fault current at X = IxIx
ApparentImpedance
Apparent Impedanceat atXX=V=VF/I/IF==VVF/Ix
/Ix=Z
=ZF++Iy/Ix
Iy/Ix(1-d)Z
(1-d)ZF
F F F F F
Additional impedance due to in feed = Iy/Ix
Additional impedance due to in feed = Iy/Ix (1-d)ZFF (1-d)Z
Faultwill
Fault willbe
beseen
seenfarther:
farther:Protection
Protectionwill willnot
nottrip
trip

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Zone 1 Reach : 3 Terminal Line
X Ix Z
F

Let’sSet
Let’s Setthe
thereach
reachconsidering
consideringmaximum
maximumininfeedfeedso
soprotection
protectiontrips
trips
Nowsay
Now saybreaker
breakerat atYYisisout
outfor
formaintenance
maintenance
Nowthe
Now thefault
faultininthe
thenext
nextline
linesection
sectionwill
willbe
beseen
seenas
asinternal
internal
Protectionwill
Protection willtrip
tripfor
forthe
theexternal
externalfault
fault

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rules for Zone 1 and Zone 2 Reach

¾ Zone 1 should never overreach and Zone 2 should


always over reach the remote terminal
¾ For 3 terminal line set the
ƒ Zone 1 Reach
• As if there is no in feed
• Set the Zone 1 only up to tap point
ƒ Zone 2 Reach
• Set the Zone 2 reach considering maximum in feed
¾ General rule and good practice for Zone 1
ƒ Its better not to trip for an internal fault then to trip for the
external fault

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Phase to Phase Fault
A

Zs B
G
C

¾ Phase to phase fault MHO is an ideal characteristic


ƒ Fault resistance is arc resistance
ƒ Fault current = V/(Zs+ZL+ Rarc)
ƒ Arc resistance inversely proportional to current and directly
proportional to line spacing
• Rarc = (8750 * L)/ I1.4
ƒ For strong source: lower Zs, creates high fault current,
produces lower arc resistance
ƒ For weak source : higher Zs, creates lower fault current,
produces higher arc resistance
ƒ For phase to phase fault MHO characteristic adjusts based
on the source impedance
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Arc Resistance

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Phase to Phase Fault: Fault Resistance

¾ Phase-Phase faults
consist only of arc
resistance
¾ Earth faults consist of
arc and tower footing
resistance

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Arc resistance Coverage
ZR ZR

Rarc Rarc

Zs Zs

Strongsource,
Strong source,Lower
LowerZs,
Zs,smaller
smallerRarc,
Rarc,lower
lowerexpansion
expansion==Good
GoodRarc
Rarccoverage
coverage
Weaksource,
Weak source,Higher
HigherZs,
Zs,larger
largerRarc,
Rarc,higher
higherexpansion
expansion==Good
GoodRarc
Rarccoverage
coverage

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Power Swing
¾ Variation in power flow
ƒ Sudden removal of fault
ƒ Loss of synchronism between ends of power system
ƒ Change in the direction of power flow
¾ Protection on the system may see the impendence
moving from load condition to its operating zone.
¾ During transient condition Protection should not trip
¾ Only protection that requires system disconnection
at suitable point should trip
¾ To prevent tripping some type of sensing need to
be employed to distinguish between power swing
and actual fault
¾ Requires Power Swing Blocking Protection

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Power Swing
A I B
EA ZsA ZL ZsB EB

E 21

Power Flow
¾Power
¾ Flow from
from AA to
to BB
EAleads
ƒƒ EA leadsEB
EBby
byangle
angle δδ
Total impedance
¾Total
¾ impedance :: Z=ZSA
Z=ZSA +ZL+ZSB
+ZL+ZSB
Current II == (EA-EB)/Z
¾Current
¾ (EA-EB)/Z
Voltage EE at
¾Voltage
¾ at the
the Relay
Relay == EA-I*ZSA
EA-I*ZSA

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Power Swing : Normal Condition
I B
EA ZsA ZL ZsB EB

ZR=E / I
E 21

EA
EA - EB
I I*ZSA
E
δ
EA - EB

EB

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Power Swing : Abnormal Condition
I B
EA ZsA ZL ZsB EB

ZR’=E’ / I

E I
21

ZR’isismuch
¾¾ ZR’ muchsmaller
smallerthen
thenZR
ZR
ƒƒ E’isissmall
E’ small
EA
I*ZSA ƒƒ EA-EBisislarge
EA-EB largedue
duelarge
largeδδ

E’ EA - EB
δ
EB

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Power Swing

EA
I*ZSA

E’ EA - EB
EA δ
EA - EB EB
I I*ZSA
E
δ
EA - EB

EB

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Power Swing : Locus

X ZSB

PSB

Z
P.S. LOCUS
ZL LOAD
O
R

ZSA

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
MHO Characteristic : Power Swing

X ZSB

P.S. LOCUS
ZL LOAD

ZSA

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
QUAD Characteristic : Power Swing

X ZSB

P.S. LOCUS
ZL LOAD

ZSA

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Switch ON to Fault

¾ Ensures inst. Trip under switch on to fault condition when


line is energized with earthing clamps connected to
breaker terminals
¾ Need for SOTF
ƒ Protection against close up 3 Phase Faults when line
VTs are used
ƒ When used with Bus PT pre fault memory polarization
can provide tripping through distance protection

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Switch ON to
Fault

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: VT Supervision

¾Condition shall be Detected when;


¾3Vo > 20% of VN (L-N) & 3Io < 20% of IN

¾FUSE FAILURE WILL CAUSE VOLTAGE UNBALANCEAND HENCE VO(V2) BUT


NO CURRENT UNBALANCE IO(I2)

¾UNBALANCED FAULTS CAUSE BOTH VOLTAGE/CURRENT


UNBALANCE,PREVENTING VTS OPERATION

¾FUSE FAIL SUPERVISION IS BLOCKED FOR 150 TO 300ms FOLLOWING LINE


ENERGIZATION IN ORDER NOT TO OPERATE FOR UNEQUAL POLE CLOSING &
ALSO DURING AUTO-RECLOSING
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria
PERMISSIVE OVERREACHING SCHEMES ARE
ADOPTED FOR SHORT LINES ( ALSO CALLED
DIRECTIONAL COMPARISON SCHEMES) ADVANTAGES
ARE;

¾ BETTER PERFORMANCE FOR HIGH RESISTANCE


FAULTS.

¾ SUPERIOR TO PILOT WIRE AS DIGITAL DECISIONS


ARE EXCHANGED AND NOT ANALOGUE

¾ SUPERIOR TO PHASE COMPARISON WHICH


REQUIRES FAITHFUL TRANSMISSION OF PHASE
INFORMATION.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria

¾Communication signal is sent to remote


end when the fault is detected in the reverse
direction. Tripping is achieved when this
blocking signal is not received within a time
T0 (20-40 ms) and the local relay has
detected a fault in the forward direction.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Distance Protection: Setting Criteria

¾ BLOCKING SCHEMES ARE USED WHEN


COMMUNICATION SIGNALS SHALL NOT
BE TRANSMITTED OVER FAULTY LINE
FOR RELIABILITY REASONS

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery

You might also like