You are on page 1of 86

Emax power breakers

Index

P
br ow
ea er
ke
rs

17 - Emax power breakers


Emax power breakers.............................................17.1 - 17.84

Selection
Air circuit breakers, installed optional features, UL & IEC...........17.29, 17.30, 17.31, 17.32
Air circuit breakers, optional features, UL & IEC...........................................................17.33
Catalog number explanation, Emax breaker..................................................................17.4
Catalog number explanation, Emax, cradle....................................................................17.5
Circuit breakers in accordance with IEC 6097-2...............................................17.19, 17.20
Description......................................................................................................................17.1
Electronic trip units for UL circuit breakers...................................................................17.10
Fixed breakers, 3 pole, IEC...........................................................................................17.21
Fixed breakers, 3 pole, UL............................................................................................17.11
Fixed breakers, 4 pole, IEC...........................................................................................17.22
Fixed breakers, 4 pole, UL............................................................................................17.12
General ratings & specifications.....................................................................................17.2
Non-automatic switches, UL.................................................................................17.8, 17.9
Non-automatic switches, fixed switches, 3 pole, IEC..................................................17.25
Non-automatic switches, fixed switches, 3 pole, UL....................................................17.15
Non-automatic switches, fixed switches, 4 pole, IEC..................................................17.26
Non-automatic switches, fixed switches, 4 pole, UL....................................................17.16
Non-automatic switches, withdrawable switches, 3 pole, IEC.....................................17.27
Non-automatic switches, withdrawable switches, 3 pole, UL......................................17.17
Non-automatic switches, withdrawable switches, 4 pole, IEC.....................................17.28
Non-automatic switches, withdrawable switches, 4 pole, UL......................................17.18
Request for quote form......................................................................................17.83, 17.84
Selection guide, UL circuit breakers......................................................................17.6, 17.7
Submittal sheet..................................................................................................17.83, 17.84
Withdrawable breakers, 3 pole, IEC.............................................................................17.23
Withdrawable breakers, 3 pole, UL...............................................................................17.13
Withdrawable breakers, 4 pole, IEC.............................................................................17.24
Accessories
Conversion kit for rear horizontal terminals to vertical.................................................17.36
Current transformers, UL & IEC....................................................................................17.34
Electronic time delay for undervoltage release.............................................................17.36
Kirk key lock adaptor plate...........................................................................................17.36
Mechanical interlocks...................................................................................................17.35
Spare parts...................................................................................................................17.36
Test kits.........................................................................................................................17.36
Transparent front cover (IP54).......................................................................................17.36
Dimensions
E1, fixed with horizontal rear terminals, 3 pole.............................................................17.37
E1, fixed with horizontal rear terminals, 4 pole.............................................................17.38
E1, withdrawable with horizontal rear terminals, 4 pole...............................................17.40
E1,withdrawable with horizontal rear terminals, 3 pole................................................17.39
E1-E2, withdrawable with vertical rear terminals, 3 pole..............................................17.41
E1-E2, withdrawable with vertical rear terminals, 4 pole..............................................17.42
E1-E6, fixed with vertical rear terminals, 3 pole............................................................17.81

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

E1-E6, fixed with vertical rear terminals, 4 pole............................................................17.82


E2, fixed with horizontal rear terminals, 3 pole.............................................................17.43
E2, fixed with horizontal rear terminals, 4 pole.............................................................17.44
E2, withdrawable with horizontal rear terminals, 3 pole...............................................17.45
E2, withdrawable with horizontal rear terminals, 4 pole...............................................17.46
E3 (1200,1600,2000A), withdrawable w/vert. rear terminals, 3P..................................17.53
E3 (1200,1600,2000A), withdrawable w/vert. rear terminals, 4P..................................17.54
E3 (2500A), withdrawable with vertical rear terminals, 3 pole......................................17.51
E3 (2500A), withdrawable with vertical rear terminals, 4 pole......................................17.52
E3 (3200A), fixed w/vertical rear terminals, 3 pole........................................................17.55
E3 (3200A), fixed w/vertical rear terminals, 4 pole........................................................17.56
E3 (3200A), withdrawable w/vertical rear terminals, 3 pole..........................................17.57
E3 (3200A), withdrawable w/vertical rear terminals, 4 pole..........................................17.58
E3, fixed with horizontal rear terminals, 3 pole.............................................................17.47
E3, fixed with horizontal rear terminals, 4 pole.............................................................17.48
E3, withdrawable with horizontal rear terminals, 3 pole...............................................17.49
E3, withdrawable with horizontal rear terminals, 4 pole...............................................17.50
E3X Draw-out with vertical rear terminals, 3 pole, 800-2000A.....................................17.59
E3X Draw-out with vertical rear terminals, 4 pole, 1600-2000A...................................17.61
E3X Fixed with vertical rear terminals, 3 pole, 800-2000A...........................................17.60
E3X fixed with vertical rear terminals, 4 pole, 800-2000A............................................17.62
E4 fixed with horizontal rear terminals, 3 pole..............................................................17.63
E4 fixed with horizontal rear terminals, 4 pole, 100% neutral......................................17.65
E4 fixed with horizontal rear terminals, 4 pole, 50% neutral........................................17.64
E4 withdrawable w/horiz. rear terminals, 4 pole, 100% neutral...................................17.68
E4 withdrawable w/horiz. rear terminals, 4 pole, 50% neutral.....................................17.67
E4 withdrawable w/vert. rear terminals, 4 pole, 100% neutral.....................................17.71
E4 withdrawable w/vert. rear terminals, 4 pole, 50% neutral.......................................17.70
E4 withdrawable w/vertical rear terminals, 3 pole........................................................17.69
E4 withdrawable with horizontal rear terminals, 3 pole................................................17.66
E6 fixed w/horizontal rear terminals, 3 pole..................................................................17.72
E6 fixed w/horizontal rear terminals, 4 pole, 100% neutral..........................................17.74
E6 fixed w/horizontal rear terminals, 4 pole, 50% neutral............................................17.73
E6 withdrawable w/horiz. rear terminals, 4 pole, 100% neutral...................................17.77
E6 withdrawable w/horiz. rear terminals, 4 pole, 50% neutral.....................................17.76
E6 withdrawable w/vert. rear terminals, 4 pole, 100% neutral.....................................17.80
E6 withdrawable with horizontal rear terminals, 3 pole................................................17.75
E6 withdrawable with vertical rear terminals, 3 pole.....................................................17.78
E6 withdrawable with vertical rear terminals, 4 pole.....................................................17.79

17.A
1SXU000023C0202

17

r
we ers
o
P ak
e
br

Notes

17

17.B
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Emax power breakers

Po

we Em
r b ax
re
ak
e

ABBs Emax series of low voltage power


circuit breakers embodies over half a
centurys experience and technological
development in power circuit breakers.
The Emax offers a series of breakers that is
totally innovative in its technological design,
ease of installation and use, making it the
ideal solution for the growing requirements
of designers, switchboard and switchgear
manufacturers, installers, OEMs and users.
The Emax power circuit breakers are UL
Listed and meet the ANSI and IEC Standards
for low voltage power circuit breakers.

ABB Emax power circuit breakers are


available in five different models with rated
continuous current from 800A to 6300A and
rated short-circuit current range from 42kA
to 200kA (480V).
Technical catalog 1SDC200005 D0201 is
available upon request.

17

Emax

Power breakers

rs

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.1
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

General ratings and specifications

E1

UL 1066
Levels of performance
Frame Size

Capacity of neutral pole for four-pole circuit breakers


Rated short circuit current

240V

480V

600V
Rated short time current

E2

E1

E3

E2

E3

B-A
800
1200

100

N-A
800
1200

100

B-A
1600

100

N-A
800
1200
1600

100

S-A
800
1200
1600

100

H-A
800
1200
1600

100

N-A
2000
2500

100

S-A
800
1200
1600
2000
2500
3200
100

H-A
800
1200
1600
2000
2500
3200
100

V-A
800
1200
1600
2000
2500
3200
100

X-A
800
1200
1600
2000

42
42
42
42

50
50
50
50

42
42
42
42

65
50
50
50

65
65
65
65

85
85
65
65

65
50
50
50

85
65
65
65

85
85
85
65

125
125
100
85

200
200
14
14

B
800
1000
1250
1600

100

N
800
1000
1250
1600

100

B
1600
2000

100

N
1000
1250
1600
2000

100

S
800
1000
1250
1600
2000

100

L
1250
1600

100

N
2500
3200

100

S
1000
1250
1600
2000
2500
3200

100

H
800
1000
1250
1600
2000
2500
3200
100

V
800
1250
1600
2000
2500
3200

100

L
2000
2500

100

[kA]
[kA]
[kA]
[kA]

42
42
42
42

50
50
50
50

42
42
42
42

65
65
55
55

85
85
65
65

130
110
85
85

65
65
65
65

75
75
75
75

100
100
100
85

130
130
100
100

130
110
85
85

[kA]
[kA]
[kA]
[kA]
[kA]

42
42
42
42
42

50
50
50
50
50

42
42
42
42
42

65
65
55
55
55

85
85
65
65
65

130
110
65
65
10

65
65
65
65
65

75
75
75
75
75

85
85
85
85
75

100
100
85
85
85

130
110
65
65
15

[A]
[A]
[A]
[A]
[A]
[A]
[%Iu]
[kA]
[kA]
[kA]
[kA]

IEC 60947-2
Levels of performance
Currents: rated uninterrupted current (at 40C) Iu

17

Capacity of neutral pole for four-pole circuit breakers


Rated ultimate breaking capacity under short circuit Icu

220/230/380/400/415V

440V

500/525V

660/690V
Rated service breaking capacity under short circuit Ics

220/230/380/400/415V

440V

500/525V

660/690V
Rated short time withstand current Icw (1s)

[A]
[A]
[A]
[A]
[A]
[A]
[A]
[%Iu]

UL 1066 and IEC 60947-2 3

Overall dimensions
Fixed: H = 418mm/16.46 in; D = 302 mm/11.89 in

W (3 poles/4 poles)

W (3 poles/4 poles)

[mm]
[in]

296/386
11.65/15.2

Draw out: H = 461mm/18.15 in; D = 396.5 mm/15.61 in



W (3 poles/4 poles)
[mm]
324/414

W (3 poles/4 poles)
[in]
12.76/16.3
Weights (circuit breaker complete with trip unit, RH terminals, CS, excluding accessories)
Fixed

3 poles/4 poles
[Kg]
45/54

3 poles/4 poles
[lbs]
99/119
Draw out

3 poles/4 poles
[Kg]
70/82

3 poles/4 poles
[lbs]
154/181
1 four poles only
2 100% neutral protection
3 For X Versions, see page 16.7.

17.2
1SXU000023C0202

296/386
11.65/15.2

404/530
15.91/20.82

324/414
12.76/16.3

432/558
17.01/21.97

50/61
110/134

66/80
145/176

78/93
172/205

104/125
229/275

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

General ratings and specifications

rs

E4

UL 1066

E4

Capacity of neutral pole for four-pole circuit breakers


Rated short circuit current

240V

480V

600V
Rated short time current

E6
H-A/f

S-A

H-A

V-A

L-A

H-A

V-A

L-A

X-A

3200
3600

50

3200
3600

50

3200
3600

50

3200
3600

50

3200
3600

100

4000
5000

50

4000
5000

50

4000
5000

50

4000
5000

50

4000
5000

100

4000
5000

100

85
65
65
65

100
85
85
85

100
100
100
100

125
125
100
100

100
85
85
85

125
85
85
100

125
125
100
100

150
150
100
100

200
200
100
100

125
85
85
100

200
200
100
100

S
4000

50

H
3200
4000

50

V
3200
4000

50

S/f 1
4000

100

H/f 1
3200
4000

100

H
4000
5000
6300

50

V
3200
4000
5000
6300

50

H/f 1
4000
5000
6300

100

[kA]
[kA]
[kA]
[kA]

75
75
75
75

100
100
100
85

150
150
130
100

80
80
75
75

100
100
100
100

100
100
100
100

150
150
130
100

100
100
100
100

[kA]
[kA]
[kA]
[kA]
[kA]

75
75
75
75
75

100
100
100
85
100

150
150
130
100
100

80
80
75
75
80

100
100
100
100
85

100
100
100
100
85

125
125
100
100
85

100
100
100
100
100

Levels of performance
Frame Size

E6

[A]
[A]
[A]
[A]
[A]
[A]
[%Iu]
[kA]
[kA]
[kA]
[kA]

H-A/f 1 X-A/f 1

IEC 60947-2
Levels of performance
Currents: rated uninterrupted current (at 40C) Iu

Capacity of neutral pole for four-pole circuit breakers


Rated ultimate breaking capacity under short circuit Icu

220/230/380/400/415V

440V

500/525V

660/690V
Rated service breaking capacity under short circuit Ics

220/230/380/400/415V

440V

500/525V

660/690V
Rated short time withstand current Icw (1s)

[A]
[A]
[A]
[A]
[A]
[A]
[A]
[%Iu]

17

UL 1066 and IEC 60947-2 3

Overall dimensions
Fixed: H = 418mm/16.46 in; D = 302 mm/11.89 in

W (3 poles/4 poles)

W (3 poles/4 poles)

[mm]
[in]

566/656
22.28/25.83

Draw out: H = 461mm/18.15 in; D = 396.5 mm/15.61 in



W (3 poles/4 poles)
[mm]
594/684

W (3 poles/4 poles)
[in]
23.39/26.93
Weights (circuit breaker complete with trip unit, RH terminals, CS, excluding accessories)
Fixed

3 poles/4 poles
[Kg]
97/117

3 poles/4 poles
[lbs]
214/258
Draw out

3 poles/4 poles
[Kg]
147/165

3 poles/4 poles
[lbs]
324/363
1 four poles only
2 100% neutral protection
3 For X Versions, see page 16.7.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

7462
29.37

782/908
30.79/35.78

10342
40.71

7742
30.47

810/936
31.89/36.85

10622
41.81

1252
276

140/160
308/353

1852
408

2002
441

210/240
463/529

2752
607

17.3
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

General information
Catalog number explanation
Emax breaker

D 3 V

H B A H 0 A 0 0 0 X X
Locking provisions: X = none;
A = keylock (open)
B = button guard
C = padlock provision (open)
D = withdrawable position lock (connected, test, and
disconnected positions
E = withdrawable position lock (test, and disconnected
positions)
F= A+B; G=A+C; H=A+D; J=A+E; K=B+D; L=B+E;
M=C+D; N=C+E; P=A+B+D; Q=A+B+E; R=A+C+D;
S=A+C+E; T=heavy duty padlock provision (open);
U=A+T; V=T+D; W=T+E; Y=A+T+D; Z=A+T+E
Accessories: X=none;
A=mechanical counter; B = bell alarm
C=bell alarm w/remote reset 24-30VAC/DC
D=bell alarm w/remote reset 110-130VAC/DC
E=bell alarm w/remote reset 220-240VAC/DC
F= A+B; G=A+C; H=A+D; J=A+E
Undervoltage trip: 0= none
50/60Hz & VDC:
A=24VDC

C=48V

E=110-120V

G=220-240V

J= 380-400VAC
Second shunt trip: L= 24VDC

N=48V

Q=110-120V

S=220-240V

U=380-400VAC

B=30V
D=60V
F=125-127V
H=250V
K=440-480VAC
M=30V
P=60V
R=125-127V
T= 250V
V=440-480VAC

Shunt trip: 0 = none


50/60Hz & VDC: A=24VDC; B=30; C=48; D=60; E=110-120; F=125-127;
G=220-240, H=250; J=380-400VAC; K=440-480VAC;
L=special low Z=120-127VAC/DC
Spring charging motor: (includes spring charged signal, P/N does not show)
0=none, A=24-30VAC/VDC, B=48-60VAC/VDC, C=110-130VAC/VDC,
D=220-250VAC/VDC, E=spring charged signal only
Contacts: A=4 aux
B=10 aux
D=UV energ. N.O.

F=A & D
G=A & E
H=B & D

(15 auxiliary contacts available as separate accessory)

E=UV energ. NC
J = B & E

Closing coil: 0=none



50/60Hz & VDC: A=24VDC; B=30; C=48; D=60; E=110-120; F=125-127;

G=220-240; H=250; J=380-400VAC; K=440-480VAC
Trip unit accessories: (not compatible with PR121/P)

A=PR120/K4C; B=PR120/V (bottom; supplied as std on PR123/P); C=PR120/D-M;

D=PR120/D-BT; E=A+B; F=A+C; G=A+D; H=A+B+C; I=A+B+D; J=B+C+D;

K=A+C+D; L=A+B+C+D; M=B+C; N=PR120/V (top); P=A+N; Q=A+N+C; R=A+N+D;

S=N+C+D; T=A+N+C+D; U=N+C; V=B+D; W=N+D; 0=none

17

Trip unit: A=PR121/P, LI; B=PR121/P, LSI; C=PR121/P, LSIG; D=non-automatic; E=PR122/P, LI; F=PR122P, LSI

G=PR122/P, LSIG; H=PR122/P, LSIRc1 J=PR123/P, LSI + PR120/V; K=PR123/P, LSIG + PR120/V
Version: B=UL fixed3; D=UL drawout, less cradle; F=IEC fixed3; W=IEC drawout, less cradle
Rating plug: A=400; B=600/630; C=800; D=1000; E=1200/1250; F=1600; G=2000; H=2500; J=30002; K=3200, L=36002;

M=4000; N=5000; P=63001; 0=None (Non-automatic only)
Frame ampere rating: : A=800; B=1200/1250; C=1600; D=2000; E=2500; F=3200; G=3600; H=4000; J=5000, N=63001;

P=10001
Breaking capacity: B=basic; N=normal; S=standard; H=high; V=very high; L=limiting; Q=1000VAC, R=750VDC (3P) 1000VDC (4P)5;

X=200kA4
Frame size: 1=E1, 3P; 2=E2, 3P; 3=E3, 3P; 4=E4, 3P; 6=E6, 3P;

A=E1, 4P; B=E2, 4P, C=E3, 4P; D=E4, 4P; (50% neutral); F=E6, 4P (50% neutral); G=E4, 4P (100% neutral); H=E6, 4P (100% neutral)

1 IEC only
2 UL only
3 Horizontal terminals are standard except for the E3 3200A; for vertical terminals, see page 16.36 for conversion kit.
4 Available as E3 up to 2000A and E6 up to 5000A.
5 Consult factory.

17.4
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

General information
Catalog number information
Emax, cradle (fixed part)
D 3 S

2 5

Po

we Em
r b ax
re
ak
e

rs

V A X

Options5:

X=none
R=DC rated (750V 3P, 1000V 4P)1

Contacts: 0=none

A=5 position auxiliaries, TOC

B=10 position auxiliaries, TOC

Terminal types: (1st letter is upper terminal, 2nd letter is lower terminal)

UL/IEC: H=rear horz. (H=HH); V=rear vert. (V=VV); A=HV; B=VH

IEC ONLY: F=front; L=rear flat; F=FF; L=LL; C=HF; D=FH; E=HL; G=LH; J=VF; K=FV; M=VL;

N=LV; P=FL; Q=LF

Max. ampere rating: UL: 12=1200 (E1); 16=1600 (E2); 20=2000 (E3)3; 25=2500 (E3); 32=3200 (E3)4, 36=3600 (E4);

50=5000 (E6)

IEC: 16=1600 (E1); 20=2000 (E2); 32=3200 (E3); 40=4000 (E4); 63=6300 ( E6)

Version: UL: N=E1B-A; E1N-A; E2B-A; E2N-A;



H=E2S-A; E2H-A; E4S-A; E4H-A; E4H-A/f; E6H-A; E6H-A/f;

S=E3N-A; E3S-A;

V=E3H-A; E3V-A;

L=E4V-A; E4L-A;

X=E3X-A2; E6V-A; E6L-A; E6X-A

IEC: C=IEC Cradle

Frame size: 1=1, 3P; 2=2, 3P; 3=3, 3P; 4=4, 3P; 6=6, 3P;

A=1, 4P; B=2, 4P; C=3, 4P; D=4, 4P (50% neutral); F=6, 4P (50% neutral);

G=4, 4P (100% neutral); H=6, 4P (100% neutral)

17

1 IEC only
2 Available as E3 up to 2000A
3 Vertical only up to 2000A
4 Vertical only
5 Consult factory for pricing

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.5
1SXU000023C0202

rs

ax ke UL circuitSelection
Emax
breakersguide
Em rea
er

w
Po

UL Circuit breakers

Rated maximum voltage


Rated voltage

Test voltage (1 min. 50/60 Hz)

[V]

[V]

[kV]

635

600

2.2

Frequency

[Hz]

Version

Fixed (F) - Draw out (W)

Number of poles

1SDC200008F0201

Voltages

1SDC200007F0201

Common data

50 - 60

3-4

E1
Level of performance
Currents
Frame size

[A]
[A]
[A]
[A]
[A]
[A]
[%Iu]

E2

B-A

N-A

B-A

N-A

S-A

H-A

800
1200

800
1200

1600

800
1200
1600

800
1200
1600

800
1200
1600

100

100

100

100

42
42
42
42

65
50
50
50

65
65
65
65

85
85
65
65

80
70
30

80
70
30

80
70
30

80
70
12

Capacity of neutral pole for four-pole circuit breakers


100
100
Rated short circuit current
240 V
[kA]
42
50
480 V
[kA]
42
50
600 V
[kA]
42
50
Rated short time current
[kA]
42
50
Trip units
PR121/P
PR122/P
PR123/P
Trip times
Make time (max)
[ms]
80
80
Break time (I<ST current) (max)
[ms]
70
70
Break time (I>ST current) (max)
[ms]
30
30
Overall dimensions
Fixed: H = 418 mm/16.46 in - D = 302 mm/11.89 in *
W (3 poles/4 poles)
[mm]
296/386
W (3 poles/4 poles)
[in]
11.65/15.2
Draw out: H = 461 mm/18.15 in - D = 396.5 mm/15.61 in **
W (3 poles/4 poles)
[mm]
324/414
W (3 poles/4 poles)
[in]
12.76/16.3
Weights (Circuit breaker complete with trip unit, RH terminals, CS, excluding accessories)
Fixed
3 poles/4 poles
[kg]
45/54
3 poles/4 poles
[lbs]
99/119
Draw out
3 poles/4 poles
[kg]
70/82
3 poles/4 poles
[lbs]
154/181

17

296/386
11.65/15.2
324/414
12.76/16.3

50/61
110/134
78/93
172/205

(1) four poles only.


* for E3X-A: H = 438 mm/ 17.24 in - D = 302 mm/ 11.89 in
** for E3X-A: H = 481 mm/ 18.94 in - D = 396.5 mm/ 15.61 in

E1 B-A / N-A
Continuous current rating Iu

Mechanical life with regular ordinary maintenance


Operation frequency
Electrical life

Operation frequency

E2 B-A / N-A / S-A / H-A

[A]

800

1200

800

1200

1600

[No. Operations x 1000]

20

20

20

20

20

[Operations/hour]

30

30

30

30

30

[No. Operations x 1000]

10

10

10

10

10

[Operations/hour]

30

30

30

30

30

(2) 10 for E3X-A.


(3) 1.5 for E3X-A.

17.6
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

1SDC200011F0201

rs

1SDC200010F0201

1SDC200009F0201

Selection guide
UL Circuit breakers

E3

E4

E6

N-A

S-A

H-A

V-A

X-A

S-A

H-A

V-A

L-A

2000
2500

800
1200
1600
2000
2500
3200
100

800
1200
1600
2000
2500
3200
100

800
1200
1600
2000

3200
3600

3200
3600

3200
3600

3200
3600

100

800
1200
1600
2000
2500
3200
100

100

50

50

50

65
50
50
50

85
65
65
65

85
85
85
65

125
125
100
85

200
200
14
14

85
65
65
65

100
85
85
85

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

H-A/f

H-A/f (1) X-A/f(1)

H-A

V-A

L-A

X-A

3200
3600

4000
5000

4000
5000

4000
5000

4000
5000

4000
5000

4000
5000

50

100

50

50

50

50

100

100

100
100
100
100

125
125
100
100

100
85
85
85

125
85
85
100

125
125
100
100

150
150
100
100

200
200
100
100

125
85
85
100

200
200
100
100

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

(1)

404/530
15.91/20.82

566/656
22.28/25.83

746
29.37

782/908
30.79/35.78

1034
40.71

432/558
17.01/21.97

594/684
23.39/26.93

774
30.47

810/936
31.89/36.85

1062
41.81

66/80
145/176

70/84
154/185

97/117
214/258

125
276

140/160
308/353

185
408

104/125
229/275

106/128
233/282

147/165
324/363

200
441

210/240
463/529

275
607

E4 S-A / H-A / V-A / L-A / H-A/f

E3 N-A / S-A / H-A / V-A

E6 H-A / V-A / L-A / X-A / H-A/f / X-A/f

800

1200

1600

2000

2500

3200

3200

3600

4000

15(2)

15(2)

15(2)

15(2)

15

15

30

30

30

30

30

30

30

30

30

30

10(3)

10(3)

10(3)

8(3)

30

30

30

30

30

30

30

30

30

30

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17

5000

17.7
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Non-automatic switches
UL

The switches share the same frames and accessories as the circuit breakers, with
the only difference the absence of the trip unit.
The switch is available in both three-pole and four-pole fixed and draw out version
and is identified by the code "/MS" (on the label). The electrical characteristics of the
switches are given in the following table.

Frame size

Number of Poles
Capacity of neutral pole for four-pole circuit breakers
Rated voltage
Rated maximum voltage
Test voltage (1 min. 50/60 Hz)
Frequency
Rated short time current
Version

[A]
[A]
[A]
[A]
[A]
[A]
[%Iu]
[V]
[V]
[kV]
[Hz]
[kA]

E1B-A/MS
800
1200

3/4
100
600
635
2.2
50-60
42
F -W

E1N-A/MS
800
1200

3/4
100
600
635
2.2
50-60
50
F -W

E2B-A/MS
1600

3/4
100
600
635
2.2
50-60
42
F -W

E2 N-A/MS
800
1200
1600

3/4
100
600
635
2.2
50-60
50
F -W

E2S-A/MS
800
1200
1600

3/4
100
600
635
2.2
50-60
65
F -W

E3N-A/MS
2000
2500

3/4
100
600
635
2.2
50-60
650
F -W

E3S-A/MS
800
1200
1600
2000
2500
3200
3/4
100
600
635
2.2
50-60
650
F -W

17

17.8
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

Non-automatic switches
UL

Frame size

Number of Poles
Capacity of neutral pole for four-pole circuit breakers
Rated voltage
Rated maximum voltage
Test voltage (1 min. 50/60 Hz)
Frequency
Rated short time current
Version

[A]
[A]
[A]
[A]
[A]
[A]
[%Iu]
[V]
[V]
[kV]
[Hz]
[kA]

E4S-A/MS
3200
3600

3/4
50
600
635
2.2
50-60
65
F -W

E4H-A/MS
3200
3600

3/4
50
600
635
2.2
50-60
85
F -W

rs

E4V-A/MS
3200
3600

3/4
50
600
635
2.2
50-60
100
F -W

E4H-Af/MS
3200
3600

4
50
600
635
2.2
50-60
85
F -W

E6H-A/MS
4000
5000

3/4
50
600
635
2.2
50-60
100
F -W

E6H-Af/MS
4000
5000

4
100
600
635
2.2
50-60
100
F -W

17

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.9
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Electronic trip units


Rating plugs for UL circuit breakers

Rating plugs
Type of circuit
breaker

E1B-A
E2B-A
E2N-A

E2S-A

E2H-A

E3N-A
E3S-A

E3H-A

E3V-A

E4S-A
E4H-A
E4V-A
E4L-A
E6H-A

17

E6V-A
E6L-A

Rated
current Iu

In [A]
400

600

800

800
1200
1600
800
1200
1600
800
1200
1600
800
1200
1600
2000
2500
800
1200
1600
2000
2500
3200
800
1200
1600
2000
2500
3200
800
1200
1600
2000
2500
3200
3200
3600
3200
3600
3200
3600
3200

1000

1200

1600

2000

2500

3000

3200

3600

4000

5000

3600

4000

5000

4000

5000

4000

5000

1 See page 16.29 for rating plugs sold separately.

17.10
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

Fixed breakers, 3 pole


UL

rs

Fixed breakers
Manually Operated

Electrically Operated

Set of Three
Vertical Terminals

UL

Frame Amps

Interrupting Ratings kA, 480V

E1B-A08
E1N-A08
E2N-A08
E2S-A08
E2H-A08
E3S-A08
E3H-A08
E3V-A08
E3X-A08
E1B-A12
E1N-A12
E2N-A12
E2S-A12
E2H-A12
E3S-A12
E3H-A12
E3V-A12
E3X-A12

800
800
800
800
800
800
800
800
800
1200
1200
1200
1200
1200
1200
1200
1200
1200

42
50
50
65
85
65
85
125
200
42
50
50
65
85
65
85
125
200

$ 6,815
6,933
7,729
8,458
8,664
8,755
8,931
9,926
11,678
7,321
7,429
7,819
8,712
8,835
8,780
9,048
9,953
11,709

$ 9,176
9,294
10,090
11,819
11,025
11,116
11,292
12,287
14,039
9,682
9,790
10,180
11,073
11,196
11,141
11,409
12,314
14,070

$ 644
644
690
690
690
790
790
790
790
644
644
690
690
690
790
790
790
790

E2B-A16
E2N-A16
E2S-A16
E2H-A16
E3S-A16
E3H-A16
E3V-A16
E3X-A16

1600
1600
1600
1600
1600
1600
1600
1600

42
50
65
85
65
85
125
200

7,871
9,082
9,764
10,019
9,797
10,352
11,387
13,396

10,232
11,443
12,125
12,380
12,158
12,713
13,748
15,757

690
690
690
690
790
790
790
790

E3N-A20
E3S-A20
E3H-A20
E3V-A20
E3X-A20

2000
2000
2000
2000
2000

50
65
85
125
200

10,032
11,053
13,602
14,962
17,603

12,393
13,414
15,963
17,323
19,964

790
790
790
790
790

E3N-A25
E3S-A25
E3H-A25
E3V-A25

2500
2500
2500
2500

50
65
85
125

14,778
16,451
17,708
19,479

17,139
18,812
20,069
21,840

790
790
790
790

E3S-A32
E3H-A32
E3V-A32
E4S-A32
E4H-A32
E4V-A32
E4L-A32

3200
3200
3200
3200
3200
3200
3200

65
85
125
65
85
100
150

23,242
23,929
26,488
21,102
21,566
24,047
27,812

25,603
26,290
28,849
23,463
23,927
26,408
30,173

E4S-A36
E4H-A36
E4V-A36
E4L-A36

3600
3600
3600
3600

65
85
100
150

23,939
27,302
28,666
29,203

26,300
29,663
31,027
31,564

1,664
1,664
1,664
1,664

E6H-A40
E6V-A40
E6L-A40
E6X-A40

4000
4000
4000
4000

85
125
150
200

31,528
43,932
50,399
53,052

33,889
46,293
52,760
55,413

2,783
2,783
2,783
2,783

E6H-A50
E6V-A50
E6L-A50
E6X-A50

5000
5000
5000
5000

85
125
150
200

43,221
51,684
55,439
58,356

45,582
54,045
57,800
60,717

2,783
2,783
2,783
2,783

6 Vertical
Terminals are
Standard
1,664
1,664
1,664
1,664

Standard features manually operated UL breaker










Rear horizontal terminals except where noted


PR121 trip unit with LI protection functions
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open/closed position indication
Lifting plates
Current transformers
Terminal box

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule ED1 [P1] - ED6 [P6]

17.11
1SXU000023C0202

17

rs
ax ake
m
E bre
er
ow

Fixed breakers, 4 pole


UL

Fixed breakers
UL

17

Interrupting Ratings kA, 480V

Manually Operated

E1B-A08
E1N-A08
E2N-A08
E2S-A08
E2H-A08
E3S-A08
E3H-A08
E3V-A08
E3X-A08

800
800
800
800
800
800
800
800
800

42
50
50
65
85
65
85
125
200

$ 9,200
9,323
9,662
10,587
10,851
10,970
11,197
12,495
15,765

$ 11,561
11,684
12,023
12,948
13,212
13,331
13,558
14,856
18,126

$ 870
870
935
935
935
1,067
1,067
1,067
1,067

E1B-A12
E1N-A12
E2N-A12
E2S-A12
E2H-A12
E3S-A12
E3H-A12
E3V-A12
E3X-A12

1200
1200
1200
1200
1200
1200
1200
1200
1200

42
50
50
65
85
65
85
125
200

9,883
10,038
10,556
11,826
11,903
11,853
12,215
13,436
15,807

12,244
12,399
12,917
14,187
14,264
14,214
14,576
15,797
18,168

870
870
935
935
935
1,067
1,067
1,067
1,067

E2B-A16
E2N-A16
E2S-A16
E2H-A16
E3S-A16
E3H-A16
E3V-A16
E3X-A16

1600
1600
1600
1600
1600
1600
1600
1600

42
50
65
85
65
85
125
200

10,626
12,261
12,978
13,121
13,226
13,975
15,373
18,085

12,987
14,622
15,339
15,482
15,587
16,336
17,734
20,446

935
935
935
935
1,067
1,067
1,067
1,067

E3N-A20
E3S-A20
E3H-A20
E3V-A20
E3X-A20
E3N-A25
E3S-A25
E3H-A25
E3V-A25

2000
2000
2000
2000
2000
2500
2500
2500
2500

50
65
85
125
200
50
65
85
125

13,543
14,922
18,363
20,199
23,763
19,950
22,209
23,906
26,296

15,904
17,283
20,724
22,560
26,124
22,311
24,570
26,267
28,657

1,067
1,067
1,067
1,067
1,067
1,067
1,067
1,067
1,067

E3S-A32
E3H-A32
E3V-A32
E4S-A32
E4H-A32
E4H-A/f32 1
E4V-A32
E4L-A32

3200
3200
3200
3200
3200
3200
3200
3200

65
85
125
65
85
85
100
150

29,772
30,081
33,340
28,488
29,114
31,916
32,463
35,712

32,133
32,442
35,701
30,849
31,475
34,277
34,824
38,073

8 Vertical
Terminals
are standard
2,250
2,250
2,572
2,250
2,250

E4S-A36
E4H-A36
E4H-A/f36 1
E4V-A36
E4L-A36

3600
3600
3600
3600
3600

65
85
85
100
150

32,318
36,858
39,866
38,669
40,931

34,679
39,219
42,227
41,060
43,292

2,250
2,250
2,572
2,250
2,250

E6H-A40
E6H-A/f40 1
E6V-A40
E6L-A40
E6X-A40
E6X-A/f40

4000
4000
4000
4000
4000
4000

85
85
125
150
200
200

42,563
46,110
59,308
65,076
71,620
81,851

44,924
48,471
61,669
67,437
73,981
84,212

3,757
4,294
3,757
3,757
3,757
4,294

E6H-A50
E6H-A/f50 1
E6V-A50
E6L-A50
E6X-A50
E6X-A/f50

5000
5000
5000
5000
5000
5000

85
85
125
150
200
200

58,348
65,097
69,773
71,628
78,781
90,035

60,709
67,458
72,134
73,989
81,142
92,396

3,757
4,294
3,757
3,757
3,757
4,294

Standard features manually operated UL breaker

Neutral pole rating

E1 E3 = 100% rating
E4 E6 = 50% rating

Rear horizontal terminals except where noted


PR121 trip unit with LI protection functions
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open/closed position indication
Lifting plates
Current transformers
Terminal box

Electrically Operated

Set of Four
Vertical Terminals

Frame Amps

1 Special 100% neutral pole rating.

17.12
1SXU000023C0202

Discount schedule ED1 [P1] - ED6 [P6]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

Withdrawable breakers, 3 pole


UL

rs

Withdrawable breakers
UL

Frame Amps

Interrupting Ratings kA,


480V

Manually Operated

Electrically Operated

Cradle w/Rear
Horizontal Terminals

E1B-A08
E1N-A08
E2N-A08
E2S-A08
E2H-A08
E3S-A08
E3H-A08
E3V-A08
E3X-A08

800
800
800
800
800
800
800
800
800

42
50
50
65
85
65
85
125
200

$ 7,383
7,754
8,529
9,038
9,564
9,408
9,792
10,404
12,240

$ 9,744
10,115
10,890
11,399
11,925
11,769
12,153
12,765
14,601

$ 2,281
2,281
2,400
2,400
2,400
2,925
2,925
2,925
4,109

$ 644
644
690
690
690
790
790
790
790

E1B-A12
E1N-A12
E2N-A12
E2S-A12
E2H-A12
E3S-A12
E3H-A12
E3V-A12
E3X-A12

1200
1200
1200
1200
1200
1200
1200
1200
1200

42
50
50
65
85
65
85
125
200

8,375
8,690
8,814
9,242
9,687
9,520
9,633
10,596
12,467

10,736
11,051
11,175
11,603
12,048
11,581
11,994
12,957
14,828

2,281
2,281
2,400
2,400
2,400
2,925
2,925
2,925
4,109

644
644
690
690
690
790
790
790
790

E2B-A16
E2N-A16
E2S-A16
E2H-A16
E3S-A16
E3H-A16
E3V-A16
E3X-A16

1600
1600
1600
1600
1600
1600
1600
1600

42
50
65
85
65
85
125
200

9,320
10,483
11,506
11,726
10,931
11,445
12,590
14,812

11,681
12,844
13,867
14,087
13,292
13,806
14,951
17,173

2,400
2,400
2,400
2,400
2,925
2,925
2,925
4,109

690
690
690
690
790
790
790
790

E3N-A20
E3S-A20
E3H-A20
E3V-A20
E3X-A20

2000
2000
2000
2000
2000

50
65
85
125
200

11,386
12,700
14,262
15,688
18,456

13,747
15,061
16,623
18,049
20,817

2,925
2,925
2,925
2,925
4,109

790
790
790
790
790

E3N-A25
E3S-A25
E3H-A25
E3V-A25

2500
2500
2500
2500

50
65
85
125

17,767
20,315
22,622
24,884

20,128
22,676
24,983
27,245

2,925
2,925
2,925
2,925

790
790
790
790

E3S-A32
E3H-A32
E3V-A32
E4S-A32
E4H-A32
E4V-A32
E4L-A32

3200
3200
3200
3200
3200
3200
3200

65
85
125
65
85
100
150

25,310
26,009
27,177
23,800
24,447
25,863
31,205

27,671
28,370
29,538
26,161
26,808
28,224
33,566

7,259
7,259
7,259
6,259
6,259
6,259
6,259

6 Vertical
Terminals are
standard
1,664
1,664
1,664
1,664

E4S-A36
E4H-A36
E4V-A36
E4L-A36

3600
3600
3600
3600

65
85
100
150

26,863
30,865
31,948
42,215

29,224
33,226
34,309
44,576

6,259
6,259
6,259
6,259

1,664
1,664
1,664
1,664

E6H-A40
E6V-A40
E6L-A40
E6X-A40

4000
4000
4000
4000

85
125
150
200

34,676
46,570
51,407
54,113

37,037
48,931
53,768
56,474

7,398
7,398
7,398
7,398

2,783
2,783
2,783
2,783

E6H-A50
E6V-A50
E6L-A50
E6X-A50

5000
5000
5000
5000

85
125
150
200

46,402
57,078
59,375
62,500

48,763
59,439
61,736
64,861

7,398
7,398
7,398
7,398

2,783
2,783
2,783
2,783

Standard features electrically operated breaker


Moving part

Standard features electrically operated breaker


Fixed part

PR121 trip unit with LI protection feature


Spring charging motor
Shunt trip
Closing coil
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts
Fail safe device (not available with YU)

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Set of Three
Vertical Terminals

17

Safety shutters
Rear horizontal terminals except where noted
Sliding contacts
Anti-insertion lock
Ground connection

Discount schedule ED1 [P1] - ED6 [P6]

17.13
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Withdrawable breakers, 4 pole


UL

Withdrawable breakers
E1B-A08
E1N-A08
E2N-A08
E2S-A08
E2H-A08
E3S-A08
E3H-A08
E3V-A08
E3X-A08

800
800
800
800
800
800
800
800
800

Interrupting Ratings kA,


480V
42
50
50
65
85
65
85
125
200

E1B-A12
E1N-A12
E2N-A12
E2S-A12
E2H-A12
E3S-A12
E3H-A12
E3V-A12
E3X-A12

1200
1200
1200
1200
1200
1200
1200
1200
1200

E2B-A16
E2N-A16
E2S-A16
E2H-A16
E3S-A16
E3H-A16
E3V-A16
E3X-A16

UL

17

Frame Amps

Manually Operated

Electrically Operated

Cradle w/Rear
Horizontal Terminals
$ 3,079
3,079
3,240
3,240
3,240
3,949
3,949
3,949
4,109

Set of Four
Vertical Terminals
$ 870
870
935
935
935
1,067
1,067
1,067
1,067

$ 9,967
10,513
11,107
11,306
12,508
11,107
12,287
13,645
16,524

$ 12,328
12,874
13,468
13,667
14,869
13,468
14,648
16,006
18,885

42
50
50
65
85
65
85
125
200

11,306
11,262
11,899
12,596
12,846
12,447
13,005
14,305
16,830

13,667
13,623
14,260
14,957
15,207
14,808
15,366
16,666
19,191

3,079
3,079
3,240
3,240
3,240
3,949
3,949
3,949
4,109

870
870
935
935
935
1,067
1,067
1,067
1,067

1600
1600
1600
1600
1600
1600
1600
1600

42
50
65
85
65
85
125
200

12,582
14,152
14,515
14,800
14,757
15,451
16,996
19,996

14,943
16,513
16,876
17,161
17,118
17,812
19,357
22,357

3,240
3,240
3,240
3,240
3,949
3,949
3,949
4,109

935
935
935
935
1,067
1,067
1,067

1,067

E3N-A20
E3S-A20
E3H-A20
E3V-A20
E3X-A20

2000
2000
2000
2000
2000

50
65
85
125
200

15,371
17,145
19,254
21,179
24,916

17,732
19,506
21,615
23,540
27,277

3,949
3,949
3,949
3,949
4,109

1,067
1,067
1,067
1,067
1,067

E3N-A25
E3S-A25
E3H-A25
E3V-A25

2500
2500
2500
2500

50
65
85
125

23,985
27,425
30,540
33,594

26,346
29,786
32,901
35,955

3,949
3,949
3,949
3,949

1,067
1,067
1,067
1,067

E3S-A32
E3H-A32
E3V-A32
E4S-A32
E4H-A32
E4H-A/f32 1
E4V-A32
E4L-A32

3200
3200
3200
3200
3200
3200
3200
3200

65
85
125
65
85
85
100
150

24,789
33,369
33,884
32,130
33,003
34,067
34,915
40,123

27,150
35,730
36,245
34,491
35,364
36,428
37,276
42,484

9,679
9,679
9,679
8,450
8,450
9,657
8,450
8,450

E4S-A36
E4H-A36
E4H-A/f36 1
E4V-A36
E4L-A36

3600
3600
3600
3600
3600

65
85
85
100
150

36,265
41,668
43,659
43,130
48,173

38,626
44,029
46,020
45,491
50,534

8,450
8,450
9,657
8,450
8,450

2,250
2,250
2,572
2,250
2,250

E6H-A40
E6H-A/f40 1
E6V-A40
E6L-A40
E6X-A40
E6X-A/f40

4000
4000
4000
4000
4000
4000

85
85
125
150
200
200

46,813
53,123
62,870
66,386
73,053
83,489

49,174
55,484
65,231
68,747
75,414
85,850

9,987
11,414
9,987
9,987
9,987
11,414

3,757
4,294
3,757
3,757
3,757
4,294

E6H-A50
E6H-A/f50 1
E6V-A50
E6L-A50
E6X-A50
E6X-A/f50

5000
5000
5000
5000
5000
5000

85
85
125
150
200
200

63,643
68,799
77,055
80,156
84,375
96,429

65,004
71,160
79,416
82,517
86,736
98,790

9,987
11,414
9,987
9,987
9,987
11,414

3,757
4,294
3,757
3,757
3,757
4,294

Standard features electrically operated breaker


Moving part

Standard features electrically operated breaker


Fixed part

PR121 trip unit with LI protection feature


Spring charging motor
Shunt trip
Closing coil
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts
Fail safe device (not available with YU)

17.14
1SXU000023C0202

8 Vertical
Terminals are
standard
2,250
2,250
2,572
2,250
2,250

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating

1 Special 100% neutral pole rating.

Discount schedule ED1 [P1] - ED6 [P6]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Non-automatic switches
Fixed switches (without trip unit & c.t.s.), 3 pole
UL

Po

we Em
r b ax
re
ak
e

rs

Fixed switches
Manually Operated

Electrically Operated

Set of Three
Vertical Terminals

UL

Frame Amps

Rated Short Time Current, kA

E1B-A/MS-08
E1N-A/MS-08
E2N-A/MS-08
E2S-A/MS-08
E3S-A/MS-08
E3V-A/MS-08

800
800
800
800
800
800

42
50
50
65
65
85

$ 5,086
5,334
7,230
7,498
7,053
9,050

$ 7,447
7,695
9,591
9,859
9,414
11,411

$ 644
644
690
690
790
790

E1B-A/MS-12
E1N-A/MS-12
E2N-A/MS-12
E2S-A/MS-12
E3S-A/MS-12
E3V-A/MS-12

1200
1200
1200
1200
1200
1200

42
50
50
65
65
85

5,592
5,627
6,090
7,348
6,944
9,407

7,953
7,988
8,451
9,709
9,305
11,768

644
644
690
690
790
790

E2B-A/MS-16
E2N-A/MS-16
E2S-A/MS-16
E3S-A/MS-16
E3V-A/MS-16

1600
1600
1600
1600
1600

42
50
65
65
85

6,142
7,353
8,550
7,961
10,731

8,503
9,714
10,911
10,322
13,092

690
690
690
790
790

E3N-A/MS-20
E3S-A/MS-20
E3V-A/MS-20

2000
2000
2000

50
65
85

8,196
9,217
14,564

10,557
11,578
16,925

790
790
790

E3N-A/MS-25
E3S-A/MS-25
E3V-A/MS-25

2500
2500
2500

50
65
85

12,942
14,615
17,658

15,303
16,976
20,019

790
790
790

E3S-A/MS-32
E3V-A/MS-32
E4S-A/MS-32
E4H-A/MS-32
E4V-A/MS-32
E4S-A/MS-36
E4H-A/MS-36
E4V-A/MS-36

3200
3200
3200
3200
3200
3600
3600
3600

65
85
65
85
100
65
85
100

20,091
21,148
18,733
19,197
24,305
21,570
24,933
29,258

22,452
23,509
21,094
21,558
26,666
23,931
27,294
31,619

6 Vertical Terminals
are standard

E6H-A/MS-40

4000

100

28,946

31,307

2,783

E6H-A/MS-50

5000

100

40,639

43,000

2,783

1,664
1,664
1,664
1,664
1,664
1,664

Standard features manually operated UL switch







Rear horizontal terminals except where noted


Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Terminal box

17

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule ED1 [P1] - ED6 [P6]

17.15
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Non-automatic switches
Fixed switches (without trip unit & c.t.s.), 4 pole
UL

Fixed switches

17

Electrically Operated

Set of Four
Vertical Terminals

$ 6,866
7,108
9,634
9,991
9,169
12,059

$ 9,227
9,469
11,995
12,352
11,530
14,420

$ 870
870
935
935
1,067
1,067

42
50
50
65
65
85

7,549
7,648
8,222
10,349
9,374
12,229

9,910
10,009
10,583
12,710
11,735
14,590

870
870
935
935
1,067
1,067

1600
1600
1600
1600
1600

42
50
65
65
85

8,282
9,927
12,042
10,747
13,950

10,653
12,288
14,403
13,108
16,311

935
935
935
1,067
1,067

E3N-A/MS-20
E3S-A/MS-20
E3V-A/MS-20

2000
2000
2000

50
65
85

11,065
12,443
18,933

13,426
14,804
21,294

1,067
1,067
1,067

E3N-A/MS-25
E3S-A/MS-25
E3V-A/MS-25

2500
2500
2500

50
65
85

17,472
19,730
23,452

19,833
22,091
25,813

1,067
1,067
1,067

E3S-A/MS-32
E3V-A/MS-32
E4S-A/MS-32
E4H-A/MS-32
E4H-A/f/MS-32 1
E4V-A/MS-32

3200
3200
3200
3200
3200
3200

65
85
65
85
85
100

26,118
27,492
25,290
25,916
27,899
31,597

28,479
29,853
27,651
28,277
30,260
33,958

8 Vertical Termianls
are standard
2,250
2,250
2,572
2,250

E4S-A/MS-36
E4H-A/MS-36
E4H-A/f/MS-36 1
E4V-A/MS-36

3600
3600
3600
3600

65
85
85
100

29,120
33,660
36,372
38,035

31,481
36,021
38,733
40,396

2,250
2,250
2,572
2,250

E6H-A/MS-40
E6H-A/f/MS-40 1

4000
4000

100
100

39,077
42,260

41,438
44,621

3,757
4,294

E6H-A/MS-50
E6H-A/f/MS-50 1

5000
5000

100
100

54,863
59,535

57,224
61,896

3,757
4,294

UL

Frame Amps

Rated Short Time Current, kA

E1B-A/MS-08
E1N-A/MS-08
E2N-A/MS-08
E2S-A/MS-08
E3S-A/MS-08
E3V-A/MS-08

800
800
800
800
800
800

42
50
50
65
65
85

E1B-A/MS-12
E1N-A/MS-12
E2N-A/MS-12
E2S-A/MS-12
E3S-A/MS-12
E3V-A/MS-12

1200
1200
1200
1200
1200
1200

E2B-A/MS-16
E2N-A/MS-16
E2S-A/MS-16
E3S-A/MS-16
E3V-A/MS-16

Manually Operated

Standard features manually operated UL switch

Neutral pole rating

E1 E3 = 100% rating
E4 E6 = 50% rating

Rear horizontal terminals except where noted


Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Terminal box

1 Special 100% neutral pole rating.

17.16
1SXU000023C0202

Discount schedule ED1 [P1] - ED6 [P6]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po
Non-automatic switches
we Em
r a
Withdrawable switches (without trip unit & c.t.s.), 3 pole breax
ke
rs
UL
Withdrawable switches
UL

Frame Amps

Rated Short Time


Current, kA

Manually Operated

Electrically Operated

Cradle w/Rear
Horizontal Terminals

Set of Three
Vertical Terminals

E1B-A/MS-08
E1N-A/MS-08
E2N-A/MS-08
E2S-A/MS-08
E3S-A/MS-08
E3V-A/MS-08

800
800
800
800
800
800

42
50
50
65
65
85

$ 5,654
6,355
7,407
7,560
7,931
9,360

$ 8,015
8,716
9,768
9,921
10,292
11,721

$ 2,281
2,281
2,281
2,281
2,925
2,925

$ 644
644
690
690
790
790

E1B-A/MS-12
E1N-A/MS-12
E2N-A/MS-12
E2S-A/MS-12
E3S-A/MS-12
E3V-A/MS-12

1200
1200
1200
1200
1200
1200

42
50
50
65
65
85

6,646
6,920
7,085
8,149
7,384
10,064

9,007
9,281
9,446
10,510
9,745
12,425

2,281
2,281
2,400
2,400
2,925
2,925

644
644
690
690
790
790

E2B-A/MS-16
E2N-A/MS-16
E2S-A/MS-16
E3S-A/MS-16
E3V-A/MS-16

1600
1600
1600
1600
1600

42
50
65
65
85

7,591
8,754
10,029
9,095
11,585

9,952
11,115
12,390
11,456
13,946

2,400
2,400
2,400
2,925
2,925

690
690
690
790
790

E3N-A/MS-20
E3S-A/MS-20
E3V-A/MS-20

2000
2000
2000

50
65
85

9,550
10,864
14,800

11,911
13,225
17,161

2,925
2,925
2,925

790
790
790

E3N-A/MS-25
E3S-A/MS-25
E3V-A/MS-25

2500
2500
2500

50
65
85

15,931
18,479
22,505

18,292
20,840
24,866

2,925
2,925
2,925

790
790
790

E3S-A/MS-32
E3V-A/MS-32
E4S-A/MS-32
E4H-A/MS-32
E4V-A/MS-32

3200
3200
3200
3200
3200

65
85
65
85
100

23,833
25,327
21,431
22,078
24,831

26,194
27,688
23,792
24,439
27,192

4,515
4,515
6,259
6,259
6,259

E4S-A/MS-36
E4H-A/MS-36
E4V-A/MS-36

3600
3600
3600

65
85
100

24,494
28,496
32,148

26,855
30,857
34,509

6,259
6,259
6,259

1,664
1,664
1,664

E6H-A/MS-40

4000

100

32,094

34,455

7,398

2,783

E6H-A/MS-50

5000

100

43,820

46,181

7,398

2,783

6 Vertical Terminals
are standard
1,664
1,664
1,664

Standard features manually operated switch


Moving part

Standard features manually operated switch


Fixed part

Manual mechanical close and open pushbuttons


Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts
Fail-safe device (not available with YU)

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Safety shutters
Rear horizontal terminals except where noted
Sliding contacts
Anti-insertion lock
Ground connection

17

Discount schedule ED1 [P1] - ED6 [P6]

17.17
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Non-automatic switches
Withdrawable switches (without trip unit & c.t.s.), 4 pole
UL

Withdrawable switches

17

UL

Frame Amps

Rated Short Time


Current, kA

Manually Operated

Electrically Operated

Cradle w/Rear
Horizontal Terminals

Set of Four
Vertical Terminals

E1B-A/MS-08
E1N-A/MS-08
E2N-A/MS-08
E2S-A/MS-08
E3S-A/MS-08
E3V-A/MS-08

800
800
800
800
800
800

42
50
50
65
65
85

$ 7,633
7,886
9,244
9,828
9,898
11,681

$ 9,994
10,247
11,605
12,189
12,259
14,042

$ 3,079
3,079
3,240
3,240
3,949
3,949

$ 870
870
935
935
1,066
1,066

E1B-A/MS-12
E1N-A/MS-12
E2N-A/MS-12
E2S-A/MS-12
E3S-A/MS-12
E3V-A/MS-12

1200
1200
1200
1200
1200
1200

42
50
50
65
65
85

8,972
8,996
9,565
10,594
9,968
13,084

11,333
11,357
11,926
12,955
12,329
15,445

3,079
3,079
3,240
3,240
3,949
3,949

870
870
935
935
1,066
1,066

E2B-A/MS-16
E2N-A/MS-16
E2S-A/MS-16
E3S-A/MS-16
E3V-A/MS-16

1600
1600
1600
1600
1600

42
50
65
65
85

10,248
11,818
12,516
12,278
15,060

12,609
14,179
14,877
14,639
17,421

3,240
3,240
3,240
3,949
3,949

935
935
897
1,066
1,066

E3N-A/MS-20
E3S-A/MS-20
E3V-A/MS-20

2000
2000
2000

50
65
85

12,893
14,666
19,240

15,254
17,027
21,601

3,949
3,949
3,949

1,066
1,066
1,066

E3N-A/MS-25
E3S-A/MS-25
E3V-A/MS-25

2500
2500
2500

50
65
85

21,507
24,947
29,257

23,868
27,308
31,618

3,949
3,949
3,949

1,066
1,066
1,066

E3S-A/MS-32
E3V-A/MS-32
E4S-A/MS-32
E4H-A/MS-32
E4H-A/f/MS-32 1
E4V-A/MS-32

3200
3200
3200
3200
3200
3200

65
85
65
85
85
100

28,599
30,181
28,932
29,805
31,237
32,280

30,960
32,542
31,293
32,166
33,598
34,641

6,083
6,083
8,450
8,450
9,657
8,450

E4S-A/MS-36
E4H-A/MS-36
E4H-A/f/MS-36 1
E4V-A/MS-36

3600
3600
3600
3600

65
85
85
100

33,067
38,470
43,786
45,592

35,428
40,831
46,147
47,953

8,450
8,450
9,657
8,450

2,250
2,250
2,572
2,250

E6H-A/MS-40
E6H-A/f/MS-40 1

4000
4000

100
100

43,327
46,217

45,688
48,578

9,987
11,414

3,757
4,294

E6H-A/MS-50
E6H-A/f/MS-50 1

5000
5000

100
100

59,157
63,669

61,518
66,030

9,987
11,414

3,757
4,294

8 Vertical Terminals
are standard
2,250
2,250
2,572
2,250

Standard features manually operated switch


Moving part

Standard features manually operated switches


Fixed part

Manual mechanical close and open pushbuttons


Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts
Fail-safe device (not available with YU)

Safety shutters
Rear horizontal terminals except where noted
Sliding contacts
Anti-insertion lock
Ground connection

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating

1 Special 100% neutral pole rating.

17.18
1SXU000023C0202

Discount schedule ED1 [P1] - ED6 [P6]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

Circuit breakers in accordance with


IEC 6097-2

we Em
r b ax
re
ak
e

rs

E1

E1B

Automatic circuit-breakers

Poles
4p c.-b neutral current-carring capacity

Iu

(40 C)

Ue
Icu
Ics
Icw

(220...415V)
(220...415V)
(1s)
(3s)

[No.]
[%Iu]
[A]

E2

E1N

3-4
100
800
800 10011000
25001250
1600
1600

[V~]
[kA]
[kA]
[kA]
[kA]

690
42
42
42
36

690
50
50
50
36

E2B
16002000

690
42
42
42
42

E3

E2N
E2S
3-4
100
100080012501000160012502000
1600

690
65
65
55
42

690
85
85
65
42

E2L

E3N

E3S

12501600

25003200

100012501600200025003200

690
130
130
10

690
65
65
65
65

690
75
75
75
75

E3H
3-4
100
8001000
1250
1600
2000
2500
3200
690
100
85
75
65

E3V

E3L

80012501600200025003200

20002500

690
130
100
85
65

690
130
130
15

Automatic circuit-breakers with full-size neutral conductor

Poles
4p c.-b neutral current-carring capacity
Iu
(40 C)
Ue
Icu
(220...415V)
Ics
(220...415V)
Icw
(1s)

(3s)

[No.]
[%Iu]
[A]
[V~]
[kA]
[kA]
[kA]
[kA]

Switch-disconnectors

Standard version

Standard version

Standard version

E1B/MS

E1N/MS

E2B/MS

E2N/MS

E2S/MS

E3N/MS

E3S/MS

E3V/MS

[No.]
[A]

3-4
800100012501600

3-4
800100025001600

3-4
16002000

3-4
1000125016002000

3-4
1000125016002000

3-4
25003200

[V~]
[kA]
[kA]
[kA]

690
42
36
88.2

690
50
36
105

690
42
42
88.2

690
42
42
88.2

690
65
42
143

690
65
65
143

3-4
100012501600200025003200
690
75
65
165

3-4
80012501600200025003200
690
85
65
286

Automatic circuit-breakers for applications up to 1150VAC

E2B/E

E2N/E

E3H/E

Poles
Iu

(40 C)

[No.]
[A]

3-4
16002000

3-4
125016002000

Ue
Icu
Ics
Icw

(1150V)
(1150V)
(1s)

[V~]
[kA]
[kA]
[kA]

1150
20
20
20

1150
30
30
30

3-4
12501600200025003200
1150
30 1
30 1
30 1

Poles
Iu

(40 C)

Ue
Icw

Icm

(1s)
(3s)
(220...440V)

E2B/E MS E2N/E MS

Switch-disconnectors for applications up to 1150VAC

Poles
Iu

Ue
Icu
Ics

(40 C)

3-4
16002000

3-4
125016002000

(1s)
(1000V)

[V~]
[kA]
[kA]

1150
20
40

1150
30
63

3-4
12501600200025003200
1150
50
105

Switch-disconnectors for applications up to 1000VDC

Poles
Iu

E2N/E MS

E3H/E MS

(40 C)

[No.]
3-4
[A] 800-1250

3-4
125016002000

(1s)
(750V)
(1000V)

[V~] 750 (3p)1000(4p)


[kA]
20
[kA]
42
[kA]
42

750 (3p)1000(4p)
25
52.5
52.5

3-4
12501600200025003200
750 (3p)1000(4p)
40
105
105

E1 CS

E2 CS

E3 CS

1250

2000

3200

E1 MTP

E2 MTP

E3 MTP

UE
Icw
Icm

Sectionalizing truck

Iu

(40 C)

[A]

Earthing switch with makeing capacity

Iu

(40 C)

[A]

Earthing truck

Iu

E3H/E MS

[No.]
[A]

(40 C)

[A]

E1B/E MS

1250

2000

3200

E1 MT

E2 MT

E3 MT

1250

2000

3200

17

1 The performance at 1000V is 50kA.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.19
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Circuit breakers in accordance with


IEC 6097-2

E4

E4S

Automatic circuit-breakers

Poles

[No.]

4p c.-b neutral current-carring capacity

Iu
Ue

E6H

E6V
3 -4

50

50

[A]

4000

3200-4000

3200-4000

4000-5000-6300

3200-4000-50006300

[V~]

690

690

690

690

690

Icu

(220...415V)

[kA]

75

100

150

100

150

Ics

(220...415V)

[kA]

75

100

150

100

125

Icw

(1s)

[kA]

75

100

100

100

100

(3s)

[kA]

75

75

75

85

85

E4S/f

E4H/f

Automatic circuit-breakers with full-size neutral conductor

E6H/f

Poles

[No.]

4p c.-b neutral current-carring capacity

[%Iu]

100

100

100

Iu

(40 C)

Ue

[A]

4000

3200-4000

4000-5000-6300

[V~]

690

690

690

Icu

(220...415V)

[kA]

80

100

100

Ics

(220...415V)

[kA]

80

100

100

Icw

(1s)

[kA]

80

85

100

(3s)

[kA]

75

75

E4S/MS

E4H/MS

E4H/fMS

E6H/MS

[No.]

3 -4

3 -4

3 -4

3 -4

3 -4

[A]

4000

3200-4000

3200-4000

4000-5000-6300

4000-5000-6300

Switch-disconnectors

Poles
Iu

(40 C)

Ue

100
E6H/fMS

[V~]

690

690

690

690

690

Icw

(1s)

[kA]

75

100

85

100

100

(3s)

[kA]

75

75

75

85

85

Icm

(220...440V)

[kA]

165

220

220

220

220

Automatic circuit-breakers for applications up to 1150VAC

Poles
Iu

E4H/E

[No.]
(40 C)

Ue

E6H/E

3 -4

3-4

[A]

3200-4000

4000-5000-6300

[V~]

1150

1150

Icu

(1150V)

[kA]

65

65

Ics

(1150V)

[kA]

65

65

Icw

(1s)

[kA]

65

65

E4H/E MS

E6H/E MS

3 -4

3-4

Switch-disconnectors for applications up to 1150VAC

Poles
Iu

[No.]
(40 C)

Ue

17

E6

E4V

3 -4

[%Iu]

(40 C)

E4H

[A]

3200-4000

4000-5000

[V~]

1150

1150

Icu

(1s)

[kA]

65

65

Ics

(1000V)

[kA]

143

143

E4H/E MS

E6H/E MS

Switch-disconnectors for applications up to 1000VDC

Poles
Iu

[No.]
(40 C)

UE

3 -4

3-4

[A]

3200-4000

4000-5000-6300
750(3p) - 1000(4p)

[V~]

750(3p) - 1000(4p)

Icw

(1s)

[kA]

65

65

Icm

(750V)

[kA]

143

143

(1000V)

[kA]

143

143

Sectionalizing truck

Iu

(40 C)

E4 CS

[A]

Earthing switch with makeing capacity

Iu

(40 C)

[A]

Earthing truck

Iu

(40 C)

17.20
1SXU000023C0202

[A]

E3H/E MS

E6 CS

4000

6300

E4 MTP

E6 MTP

4000

6300

E4 MT

E6 MT

4000

6300

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

Fixed breakers, 3 pole


IEC

rs

Fixed breakers
IEC

Frame Amps

Interrupting Ratings
kA, 415V

Manually Operated

Electrically
Operated

Set of Three Vertical


Terminals

Set of Three
Front Terminals

E1B08
E1N08
E2S08
E3H08
E3V08

800
800
800
800
800

42
50
85
100
130

$ 6,027
6,199
6,968
7,709
7,825

$ 8,388
8,560
9,329
10,070
10,186

$ 644
644
690
790
790

$ 367
367
888
1,232
1,232

E1B10
E1N10
E2N10
E2S10
E3S10
E3H10

1000
1000
1000
1000
1000
1000

42
50
65
85
75
100

6,289
6,352
7,078
7,184
7,947
8,190

8,650
8,713
9,439
9,545
10,308
10,551

644
644
690
690
790
790

367
367
888
888
1,232
1,232

E1B12
E1N12
E2N12
E2S12
E2L12
E3S12
E3H12
E3V12

1250
1250
1250
1250
1250
1250
1250
1250

42
50
65
85
130
75
100
130

6,656
6,839
7,314
7,854
9,368
7,808
8,036
9,453

9,017
9,200
9,675
10,215
11,729
10,169
10,397
11,814

644
644
690
690
690
790
790
790

367
367
888
888
888
1,232
1,232
1,232

E1B16
E1N16
E2B16
E2N16
E2S16
E2L16
E3S16
E3H16
E3V16

1600
1600
1600
1600
1600
1600
1600
1600
1600

42
50
42
65
85
130
75
100
130

6,940
7,010
7,293
8,014
8,689
11,189
8,700
9,232
11,265

9,301
9,371
9,654
10,375
11,050
13,550
11,061
11,593
13,626

644
644
690
690
690
690
790
790
790

367
367
888
888
888
888
1,232
1,232
1,232

E2B20
E2N20
E2S20
E3S20
E3H20
E3V20
E3L20

2000
2000
2000
2000
2000
2000
2000

42
65
85
75
100
130
130

8,509
9,024
9,784
9,817
11,762
13,157
13,425

10,870
11,385
12,145
12,178
14,123
15,518
15,786

690
690
690
790
790
790
790

888
888
888
1,232
1,232
1,232
1,232

E3N25
E3S25
E3H25
E3V25
E3L25

2500
2500
2500
2500
2500

65
75
100
130
130

13,870
15,242
16,948
18,010
19,454

16,231
17,603
19,309
20,371
21,815

790
790
790
790
790

1,232
1,232
1,232
1,232
1,232

E3N32
E3S32
E3H32
E3V32
E4H32
E4V32
E6V32

3200
3200
3200
3200
3200
3200
3200

65
75
100
130
100
150
150

17,963
18,662
20,217
21,711
22,085
28,163
36,328

20,324
21,023
22,578
24,072
24,446
30,524
38,689

790
790
790
790
1,664
2,783
2,783

1,232
1,232
1,232
1,232
1,696
2,464
2,464

E4S40
E4H40
E4V40
E6H40
E6V40

4000
4000
4000
4000
4000

75
85
100
100
150

26,873
30,645
34,445
38,497
42,739

29,234
33,006
36,806
40,858
45,100

1,664
1,664
1,664
2,783
2,783

1,696
1,696
1,696
2,464
2,464

E6H50
E6V50

5000
5000

100
150

42,047
50,281

44,408
52,642

2,783
2,783

2,464
2,464

E6H63
E6V63

6300
6300

100
150

50,456
60,337

52,817
63,698

2,783
2,783

2,464
2,464

17

Standard features manually operated breaker


Fixed breaker








Rear horizontal terminals


PR121 trip unit with LI protection functions
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Terminal box

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule ED1 [P1] - ED6 [P6]

17.21
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Fixed breakers, 4 pole


IEC

Fixed breakers

17

IEC

Frame Amps

Interrupting Ratings kA,


415V

Manually Operated

Electrically Operated

E1B08
E1N08
E2S08
E3H08
E3V08

800
800
800
800
800

42
50
85
100
130

$ 7,475
7,688
8,960
9,213
10,353

$ 9,836
10,049
11,321
11,574
12,714

$ 837
837
897
1,027
1,027

$ 489
489
1,183
1,643
1,643

E1B10
E1N10
E2N10
E2S10
E3S10
E3H10

1000
1000
1000
1000
1000
1000

42
50
65
85
75
100

7,800
8,053
8,512
8,959
9,069
9,452

10,161
10,414
10,873
11,320
11,430
11,813

837
837
897
897
1,027
1,027

489
489
1,183
1,183
1,643
1,643

E1B12
E1N12
E2N12
E2S12
E2L12
E3S12
E3H12
E3V12

1250
1250
1250
1250
1250
1250
1250
1250

42
50
65
85
130
75
100
130

8,293
8,520
9,148
9,446
12,725
9,306
9,591
11,389

10,654
10,881
11,509
11,807
15,086
11,667
11,952
13,750

837
837
897
897
897
1,027
1,027
1,027

489
489
1,183
1,183
1,183
1,643
1,643
1,643

E1B16
E1N16
E2B16
E2N16
E2S16
E2L16
E3S16
E3H16
E3V16

1600
1600
1600
1600
1600
1600
1600
1600
1600

42
50
42
65
85
130
75
100
130

8,647
8,733
9,121
10,059
10,906
13,666
10,413
10,550
14,162

11,008
11,094
11,482
12,420
13,267
16,849
12,774
12,911
16,523

837
837
897
897
897
897
1,027
1,027
1,027

489
489
1,183
1,183
1,183
1,183
1,643
1,643
1,643

E2B20
E2N20
E2S20
E3S20
E3H20
E3V20
E3L20

2000
2000
2000
2000
2000
2000
2000

42
65
85
75
100
130
130

10,701
11,371
12,329
11,795
13,621
16,872
17,093

13,062
13,732
14,690
14,156
15,982
19,233
19,454

897
897
897
1,027
1,027
1,027
1,027

1,183
1,183
1,183
1,643
1,643
1,643
1,643

E3N25
E3S25
E3H25
E3V25
E3L25

2500
2500
2500
2500
2500

65
75
100
130
130

17,671
19,454
21,672
23,301
24,930

20,032
21,815
24,033
25,662
27,291

1,027
1,027
1,027
1,027
1,027

1,643
1,643
1,643
1,643
1,643

E3N32
E3S32
E3H32
E3V32
E4H32
E4H/f32
E4V32
E6V32

3200
3200
3200
3200
3200
3200
3200
3200

65
75
100
130
100
100
150
150

22,992
23,900
27,307
30,714
28,351
29,920
36,153
45,410

25,353
26,261
29,668
33,075
30,712
32,281
38,514
47,771

1,027
1,027
1,027
1,027
2,163
2,472
2,163
3,618

1,643
1,643
1,643
1,643
2,260
2,583
2,260
3,286

E4S40
E4H40
E4H/f40
E4V40
E6H40
E6H/f40
E6V40

4000
4000
4000
4000
4000
4000
4000

75
85
85
100
100
100
150

34,610
39,516
41,652
42,923
48,122
50,528
53,424

36,971
41,877
44,013
45,284
50,483
52,889
55,785

2,163
2,163
2,472
2,163
3,618
4,135
3,618

2,260
2,260
2,583
2,260
3,286
3,756
3,286

E6H50
E6H/f50
E6V50

5000
5000
5000

100
100
150

52,558
56,142
62,852

54,919
58,503
65,213

3,618
4,135
3,618

3,286
3,756
3,286

E6H63
E6H/f63
E6V63

6300
6300
6300

100
100
150

63,070
67,370
75,422

65,431
69,731
77,783

3,818
4,135
3,618

3,286
3,756
3,286

Standard features manually operated breaker


Fixed breaker





Rear horizontal terminals


PR121 trip unit with LI protection functions
Manual mechanical close and open pushbuttons
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator

1 Consult factory for special 100% neutral pole rating.

17.22
1SXU000023C0202

Set of Four Vertical


Terminals

Set of Four
Front Terminals

2NO & 2NC auxiliary contacts for open-closed position indication


Lifting plates
Current transformers
Terminal box

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating

Discount schedule ED1 [P1] - ED6 [P6]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

Withdrawable breakers, 3 pole


IEC

rs

Withdrawable breakers
IEC

Frame Amps

Interrupting
Ratings kA, 415V

Manually Operated

Electrically Operated

Cradle w/Rear
Horizontal Terminals

Set of Three Vertical


Terminals

E1B08
E1N08
E2S08
E3H08
E3V08

800
800
800
800
800

42
50
85
100
130

$ 6,501
6,877
7,883
8,125
8,246

$ 8,862
9,238
10,244
10,486
10,607

$ 2,281
2,281
2,400
2,925
2,925

$ 644
644
690
790
790

$ 367
367
888
1,232
1,232

E1B10
E1N10
E2N10
E2S10
E3S10
E3H10

1000
1000
1000
1000
1000
1000

42
50
65
85
75
100

7,337
7,684
8,007
8,127
8,585
8,749

9,698
10,045
10,368
10,488
10,946
11,110

2,281
2,281
2,400
2,400
2,925
2,925

644
644
690
690
790
790

367
367
888
888
1,232
1,232

E1B12
E1N12
E2N12
E2S12
E2L12
E3S12
E3H12
E3V12

1250
1250
1250
1250
1250
1250
1250
1250

42
50
65
85
130
75
100
130

7,757
8,101
8,626
9,151
12,180
8,760
8,897
9,363

10,118
10,462
10,987
11,512
14,541
11,121
11,258
11,724

2,281
2,281
2,400
2,400
2,400
2,925
2,925
2,925

644
644
690
690
690
790
790
790

367
367
888
888
888
1,232
1,232
1,232

E1B16
E1N16
E2B16
E2N16
E2S16
E2L16
E3S16
E3H16
E3V16

1600
1600
1600
1600
1600
1600
1600
1600
1600

42
50
42
65
85
130
75
100
130

8,222
8,304
9,097
10,234
11,371
14,704
10,674
11,100
15,126

10,583
10,665
11,458
12,595
13,732
18,281
13,035
13,461
17,487

2,281
2,281
2,400
2,400
2,400
2,400
2,925
2,925
2,925

644
644
690
690
690
690
790
790
790

367
367
888
888
888
888
1,232
1,232
1,232

E2B20
E2N20
E2S20
E3S20
E3H20
E3V20
E3L20

2000
2000
2000
2000
2000
2000
2000

42
65
85
75
100
130
130

10,987
11,182
11,377
11,361
13,256
13,864
17,817

13,348
13,543
13,738
13,722
15,617
16,225
20,178

2,400
2,400
2,400
2,925
2,925
2,925
2,925

690
690
690
790
790
790
790

888
888
888
1,232
1,232
1,232
1,232

E3N25
E3S25
E3H25
E3V25
E3L25

2500
2500
2500
2500
2500

65
75
100
130
130

15,220
17,896
19,528
21,210
22,892

17,581
20,257
21,889
23,571
25,253

2,925
2,925
2,925
2,925
2,925

790
790
790
790
790

1,232
1,232
1,232
1,232
1,232

E3N32
E3S32
E3H32
E3V32
E4H32
E4V32
E6V32

3200
3200
3200
3200
3200
3200
3200

65
75
100
130
100
150
150

22,337
23,340
23,724
25,367
23,842
25,731
38,539

24,698
25,701
26,085
27,728
26,203
28,092
40,900

2,925
2,925
2,925
2,925
6,259
6,259
7,398

790
790
790
790
1,664
1,664
2,783

1,232
1,232
1,232
1,232
1,696
1,696
2,464

E4S40
E4H40
E4V40
E6H40
E6V40

4000
4000
4000
4000
4000

75
85
100
100
150

30,399
34,540
38,681
44,177
50,140

32,760
36,901
41,042
47,701
52,501

6,259
6,259
6,259
7,398
7,398

1,664
1,664
1,664
2,783
2,783

1,696
1,696
1,696
2,464
2,464

E6H50
E6V50

5000
5000

100
150

45,541
53,341

47,902
55,702

7,398
7,398

2,783
2,783

2,464
2,464

E6H63
E6V63

6300
6300

100
150

64,163
78,427

66,524
80,788

7,398
7,398

2,783
2,783

2,464
2,464

Standard features electrically operated breaker


Moving part

Standard features electrically operated breaker


Fixed part

PR121 trip unit with LI protection functions


Spring charging motor
Shunt trip
Closing coil
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Set of Three
Front Terminals

17

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Discount schedule ED1 [P1] - ED6 [P6]

17.23
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Withdrawable breakers, 4 pole


IEC

Withdrawable breakers

17

IEC

Frame Amps

Interrupting
Ratings kA, 415V

Manually Operated

Electrically Operated

Cradle w/Rear
Horizontal Terminals

Set of Four Vertical


Terminals

E1B08
E1N08
E2S08
E3H08
E3V08

800
800
800
800
800

42
50
85
100
130

$ 7,717
8,605
9,998
10,398
10,554

$ 10,078
10,966
12,359
12,759
12,915

$ 2,572
2,572
3,192
3,890
3,890

$ 837
837
897
1,027
1,027

$ 489
489
1,183
1,643
1,643

E1B10
E1N10
E2N10
E2S10
E3S10
E3H10

1000
1000
1000
1000
1000
1000

42
50
65
85
75
100

9,621
9,717
10,155
10,307
10,988
11,103

11,982
12,078
12,516
12,668
13,349
13,464

2,572
2,572
3,192
3,192
3,890
3,890

837
837
897
897
1,027
1,027

489
489
1,183
1,183
1,643
1,643

E1B12
E1N12
E2N12
E2S12
E2L12
E3S12
E3H12
E3V12

1250
1250
1250
1250
1250
1250
1250
1250

42
50
65
85
130
75
100
130

10,649
11,098
11,372
11,772
14,395
11,906
12,229
15,445

13,010
13,459
13,733
14,133
17,763
14,267
14,590
17,806

2,572
2,572
3,192
3,192
3,192
3,890
3,890
3,890

837
837
897
897
897
1,027
1,027
1,027

489
489
1,183
1,183
1,183
1,643
1,643
1,643

E1B16
E1N16
E2B16
E2N16
E2S16
E2L16
E3S16
E3H16
E3V16

1600
1600
1600
1600
1600
1600
1600
1600
1600

42
50
42
65
85
130
75
100
130

10,812
11,375
11,395
12,873
13,460
17,501
12,472
13,304
18,408

13,173
13,736
13,756
15,234
15,821
22,625
14,833
15,665
20,769

2,572
2,572
3,192
3,192
3,192
3,192
3,890
3,890
3,890

837
837
897
897
897
897
1,027
1,027
1,027

489
489
1,183
1,183
1,183
1,183
1,643
1,643
1,643

E2B20
E2N20
E2S20
E3S20
E3H20
E3V20
E3L20

2000
2000
2000
2000
2000
2000
2000

42
65
85
75
100
130
130

13,851
15,661
16,825
14,873
16,784
19,212
22,714

16,212
18,022
19,186
17,234
19,145
21,573
25,075

3,192
3,192
3,192
3,890
3,890
3,890
3,890

897
897
897
1,027
1,027
1,027
1,027

1,183
1,183
1,183
1,643
1,643
1,643
1,643

E3N25
E3S25
E3H25
E3V25
E3L25

2500
2500
2500
2500
2500

65
75
100
130
130

20,380
22,816
24,938
27,125
29,312

22,741
25,177
27,299
29,486
31,673

3,890
3,890
3,890
3,890
3,890

1,027
1,027
1,027
1,027
1,027

1,643
1,643
1,643
1,643
1,643

E3N32
E3S32
E3H32
E3V32
E4S32
E4H32
E4H/f32 1
E4V32
E6V32

3200
3200
3200
3200
3200
3200
3200
3200
3200

65
75
100
130
75
100
100
150
150

29,555
29,893
32,017
34,141
33,317
32,589
33,523
47,423
49,722

31,916
32,254
34,378
36,502
35,678
34,959
35,884
49,784
52,083

3,890
3,890
3,890
3,890
8,324
8,324
9,513
8,324
9,839

1,027
1,027
1,027
1,027
2,163
2,163
2,472
2,163
3,618

1,643
1,643
1,643
1,643
2,260
2,260
2,583
2,260
3,286

E4S40
E4H40
E4H/f40 1
E4V40
E6H40
E6H/f40 1
E6V40

4000
4000
4000
4000
4000
4000
4000

75
85
85
100
100
100
150

41,350
44,409
45,478
45,930
48,486
50,911
58,496

43,711
46,770
47,839
48,291
60,857
53,272
60,857

8,324
8,324
9,513
8,324
9,839
11,245
9,839

2,163
2,163
2,472
2,163
3,618
4,135
3,618

2,260
2,260
2,583
2,260
3,286
3,756
3,286

E6H50
E6H/f50 1
E6V50

5000
5000
5000

100
100
150

58,680
66,853
56,568

61,041
69,214
71,181

9,839
11,245
9,839

3,618
4,135
3,618

3,286
3,756
3,286

E6H63
E6H/f63
E6V63

6300
6300
6300

100
100
150

82,888
94,017
101,432

85,249
96,378
103,793

9,839
9,839
9,839

3,618
4,135
3,618

3,286
3,756
3,286

Standard features electrically operated breaker


Moving part

Circuit breaker racking position indicator


Sliding contacts

PR121 trip unit with LI protection functions


Spring charging motor
Shunt trip
Closing coil
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Racking device with closed door

1 Special 100% neutral pole rating.

17.24
1SXU000023C0202

Set of Four
Front Terminals

Standard features electrically operated breaker


Fixed part
Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating

Discount schedule ED1 [P1] - ED6 [P6]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Non-automatic switches
Fixed switches (Without trip unit & c.t.s.), 3 pole
IEC

Po

we Em
r b ax
re
ak
e

rs

Fixed switches, 3 pole


IEC

Frame Amps

Rated Short Time Current,


kA

Manually Operated

Electrically Operated

Set of Three Vertical


Terminals

Set of Three
Front Terminals

E1B/MS08
E1N/MS08
E3V/MS08

800
800
800

42
50
85

$ 4,298
4,903
5,883

$ 6,659
7,264
8,244

$ 644
644
790

$ 367
367
1,232

E1B/MS10
E1N/MS10
E2N/MS10
E2S/MS10
E3S/MS10

1000
1000
1000
1000
1000

42
50
55
65
75

4,816
5,101
5,502
5,799
5,921

7,177
7,462
7,863
8,160
8,282

644
644
690
690
790

367
367
888
888
1,232

E1B/MS12
E1N/MS12
E2N/MS12
E2S/MS12
E3S/MS12
E3V/MS12

1250
1250
1250
1250
1250
1250

42
50
55
65
75
85

4,927
5,203
5,585
5,887
5,972
7,089

7,288
7,564
7,946
8,248
8,333
9,450

644
644
690
690
790
790

367
367
888
888
1,232
1,232

E1B/MS16
E1N/MS16
E2B/MS16
E2N/MS16
E2S/MS16
E3S/MS16
E3V/MS16

1600
1600
1600
1600
1600
1600
1600

42
50
42
55
65
75
85

5,203
5,307
5,564
6,285
6,722
6,864
8,145

7,564
7,668
7,925
8,646
9,083
9,225
10,506

644
644
690
690
690
790
790

367
367
888
888
888
1,232
1,232

E2B/MS20
E2N/MS20
E2S/MS20
E3S/MS20
E3V/MS20

2000
2000
2000
2000
2000

42
55
65
75
85

6,780
7,295
8,280
7,981
9,451

9,141
9,556
10,641
10,342
11,812

690
690
690
790
790

888
888
888
1,232
1,232

E3N/MS25
E3S/MS25
E3V/MS25

2500
2500
2500

65
75
85

12,034
13,406
14,246

14,395
15,767
16,607

790
790
790

1,232
1,232
1,232

E3N/MS32
E3S/MS32
E3V/MS32
E4H/MS32

3200
3200
3200
3200

65
75
85
100

16,127
16,826
17,901
18,688

18,488
19,187
20,262
21,049

790
790
790
790

1,232
1,232
1,232
1,232

E4S/MS40
E4H/MS40
E6H/MS40

4000
4000
4000

75
100
100

24,504
28,276
33,114

26,865
30,637
35,475

1,664
1,664
2,783

1,696
1,696
2,464

E6H/MS50

5000

100

39,465

41,826

2,783

2,464

E6H/MS63

6300

100

47,874

50,235

2,783

2,464

17

Standard features manually operated switch







Rear horizontal terminals


Manual mechanical close and open pushbuttons
Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Terminal box

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule ED1 [P1] - ED6 [P6]

17.25
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Non-automatic switches
Fixed switches (Without trip unit & c.t.s.), 4 pole
IEC

Fixed switches, 4 pole

17

IEC

Frame Amps

Rated Short Time Current,


kA

Manually Operated

Electrically Operated

E1B/MS08
E1N/MS08
E3V/MS08

800
800
800

42
50
85

$ 5,533
6,251
7,501

$ 7,894
8,612
9,862

$ 837
837
1,027

$ 489
489
1,643

E1B/MS10
E1N/MS10
E2N/MS10
E2S/MS10
E3S/MS10

1000
1000
1000
1000
1000

42
50
55
65
75

6,139
6,503
6,705
7,350
7,666

8,500
8,864
9,066
9,711
10,027

837
837
897
897
1,027

489
489
1,183
1,183
1,643

E1B/MS12
E1N/MS12
E2N/MS12
E2S/MS12
E3S/MS12
E3V/MS12

1250
1250
1250
1250
1250
1250

42
50
55
65
75
85

6,351
6,633
7,206
7,462
7,221
9,178

8,712
8,994
9,567
9,823
9,582
11,539

837
837
897
897
1,027
1,027

489
489
1,183
1,183
1,643
1,643

E1B/MS16
E1N/MS16
E2B/MS16
E2N/MS16
E2S/MS16
E3S/MS16
E3V/MS16

1600
1600
1600
1600
1600
1600
1600

42
50
42
55
65
75
85

6,633
6,766
7,179
8,117
8,636
8,328
10,444

8,994
9,127
9,540
10,478
10,997
10,689
12,805

837
837
897
897
897
1,027
1,027

489
489
1,183
1,183
1,183
1,643
1,643

E2B/MS20
E2N/MS20
E2S/MS20
E3S/MS20
E3V/MS20

2000
2000
2000
2000
2000

42
55
65
75
85

8,759
9,429
10,059
9,710
12,141

11,120
11,790
12,420
12,071
14,502

897
897
897
1,027
1,027

1,183
1,183
1,183
1,643
1,643

E3N/MS25
E3S/MS25
E3V/MS25

2500
2500
2500

65
75
85

15,586
17,369
18,432

17,947
19,730
20,793

1,027
1,027
1,027

1,643
1,643
1,643

E3N/MS32
E3S/MS32
E3V/MS32
E4H/MS32
E4H/f MS32 1

3200
3200
3200
3200
3200

65
75
85
100
100

20,907
21,815
23,184
24,146
26,368

23,268
24,176
25,545
26,507
28,729

1,027
1,027
1,027
2,163
2,472

1,643
1,643
1,643
2,260
2,583

E4S/MS40
E4H/MS40
E4H/f MS40 1
E6H/MS40
E6H/f MS40 1

4000
4000
4000
4000
4000

75
100
85
100
100

31,815
36,721
39,196
39,352
43,116

34,176
39,082
41,557
41,713
45,477

2,163
2,163
2,472
3,618
4,135

2,260
2,260
2,583
3,286
3,756

E6H/MS50
E6H/f MS50 1

5000
5000

100
100

49,479
56,638

51,480
58,999

3,618
4,135

3,286
3,756

E6H/MS63
E6H/f MS63 1

6300
6300

100
100

59,991
68,802

62,352
71,163

3,618
4,135

3,286
3,756

Standard features manually operated switch

Neutral pole rating

E1 E3 = 100% rating
E4 E6 = 50% rating

Rear horizontal terminals


Manual mechanical close and open pushbuttons
Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Terminal box

Set of Four Vertical


Terminals

Set of Three
Front Terminals

1 Special 100% neutral pole rating.

17.26
1SXU000023C0202

Discount schedule ED1 [P1] - ED6 [P6]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

ow Em
Non-automatic switches
er ax
Withdrawable switches (Without trip unit & c.t.s.), 3 pole break
er
s
IEC
Withdrawable switches, 3 pole
IEC

Frame Amps

Rated Short Time


Current, kA

Manually Operated

Electrically Operated

Cradle w/Rear
Horizontal Terminals

Set of Three Vertical


Terminals

Set of Three
Front Terminals

E1B/MS08
E1N/MS08
E3V/MS08

800
800
800

42
50
85

$ 4,772
4,952
7,060

$ 7,133
7,313
9,421

$ 2,281
2,281
2,925

$ 644
644
790

$ 367
367
1,232

E1B/MS10
E1N/MS10
E2N/MS10
E2S/MS10
E3S/MS10

1000
1000
1000
1000
1000

42
50
55
65
75

5,051
5,152
5,770
5,857
6,716

7,412
7,513
8,131
8,218
9,077

2,281
2,281
2,400
2,400
2,925

644
644
690
690
790

367
367
888
888
1,232

E1B/MS12
E1N/MS12
E2N/MS12
E2S/MS12
E3S/MS12
E3V/MS12

1250
1250
1250
1250
1250
1250

42
50
55
65
75
85

6,028
5,255
6,897
7,718
6,924
7,237

8,389
7,616
9,258
10,079
9,285
9,598

2,281
2,281
2,400
2,400
2,925
2,925

644
644
690
690
790
790

367
367
888
888
1,232
1,232

E1B/MS16
E1N/MS16
E2B/MS16
E2N/MS16
E2S/MS16
E3S/MS16
E3V/MS16

1600
1600
1600
1600
1600
1600
1600

42
50
42
55
65
75
85

6,831
6,968
7,368
8,505
8,331
8,838
9,160

9,192
9,329
9,729
10,866
10,692
11,199
11,521

2,281
2,281
2,400
2,400
2,400
2,925
2,925

644
644
690
690
690
790
790

367
367
888
888
888
1,232
1,232

E2B/MS20
E2N/MS20
E2S/MS20
E3S/MS20
E3V/MS20

2000
2000
2000
2000
2000

42
55
65
75
85

9,258
9,453
9,648
9,525
10,737

11,619
11,814
12,009
11,886
13,098

2,400
2,400
2,400
2,925
2,925

690
690
690
790
790

888
888
888
1,232
1,232

E3N/MS25
E3S/MS25
E3V/MS25
E3N/MS32
E3S/MS32
E3V/MS32
E4H/MS32

2500
2500
2500
3200
3200
3200
3200

65
75
85
65
75
85
100

13,384
16,060
16,611
20,501
21,540
22,281
24,011

15,745
18,421
18,972
22,862
23,865
24,642
26,372

2,925
2,925
2,925
2,925
2,925
2,925
6,259

790
790
790
790
790
790
1,664

1,232
1,232
1,232
1,232
1,232
1,232
1,696

E4S/MS40
E4H/MS40
E6H/MS40

4000
4000
4000

75
100
100

28,030
32,171
36,789

30,391
34,532
39,150

6,259
6,259
6,259

1,664
1,664
2,783

1,696
1,696
2,464

E6H/MS50

5000

100

42,959

45,320

7,398

2,783

2,464

E6H/MS63

6300

100

61,581

63,942

7,398

2,783

2,464

Standard features manually operated switch


Moving part

Standard features manually operated switch


Fixed part

Manual mechanical close and open pushbuttons


Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Discount schedule ED1 [P1] - ED6 [P6]

17

17.27
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Non-automatic switches
Withdrawable switches (Without trip unit & c.t.s.), 4 pole
IEC

Withdrawable switches, 4 pole

17

IEC

Frame Amps

Rated Short Time


Current, kA

Manually Operated

Electrically
Operated

E1B/MS08
E1N/MS08
E3V/MS08

800
800
800

42
50
85

$ 5,775
6,314
7,501

$ 8,136
8,675
9,862

E1B/MS10
E1N/MS10
E2N/MS10
E2S/MS10
E3S/MS10

1000
1000
1000
1000
1000

42
50
55
65
75

6,440
6,569
7,033
7,139
8,696

E1B/MS12
E1N/MS12
E2N/MS12
E2S/MS12
E3S/MS12
E3V/MS12

1250
1250
1250
1250
1250
1250

42
50
55
65
75
85

E1B/MS16
E1N/MS16
E2B/MS16
E2N/MS16
E2S/MS16
E3S/MS16
E3V/MS16

1600
1600
1600
1600
1600
1600
1600

E2B/MS20
E2N/MS20
E2S/MS20
E3S/MS20
E3V/MS20
E3N/MS25
E3S/MS25
E3V/MS25

Cradle w/Rear Horizontal


/ Flat Terminals

Set of Four Vertical


Terminals

Set of Four
Front Terminals

$ 2,572
2,572
3,890

$ 837
837
1,027

$ 489
489
1,643

8,801
8,930
9,394
9,500
11,057

2,572
2,572
3,192
3,192
3,890

837
837
897
897
1,027

489
489
1,183
1,183
1,643

8,707
9,168
9,430
9,610
9,821
10,312

11,068
11,529
11,791
11,971
12,182
12,673

2,572
2,572
3,192
3,192
3,890
3,890

837
837
897
897
1,027
1,027

489
489
1,183
1,183
1,643
1,643

42
50
42
55
65
75
85

8,888
9,065
9,453
10,931
11,733
10,387
11,762

11,249
11,426
11,814
13,292
14,094
12,748
14,123

2,572
2,572
3,192
3,192
3,192
3,890
3,890

837
837
897
897
897
1,027
1,027

489
489
1,183
1,183
1,183
1,643
1,643

2000
2000
2000
2000
2000
2500
2500
2500

42
55
65
75
85
65
75
85

11,909
13,719
14,241
12,788
15,119
18,295
20,731
21,625

14,270
16,080
16,602
15,149
17,480
20,656
23,092
23,986

3,192
3,192
3,192
3,890
3,890
3,890
3,890
3,890

837
897
897
1,027
1,027
1,027
1,027
1,027

1,183
1,183
1,183
1,643
1,643
1,643
1,643
1,643

E3N/MS32
E3S/MS32
E3V/MS32
E4H/MS32
E4H/fMS32 1

3200
3200
3200
3200
3200

65
75
85
100
100

27,470
27,808
28,996
30,738
32,273

29,831
30,169
31,357
33,099
34,634

3,890
3,890
3,890
8,324
9,513

1,027
1,027
1,027
2,163
2,472

1,643
1,643
1,643
2,260
2,583

E4S/MS40
E4H/MS40
E4H/f MS40 1
E6H/MS40
E6H/f MS40 1

4000
4000
4000
4000
4000

75
100
100
100
100

38,555
41,614
45,598
43,359
45,527

40,916
43,975
47,959
45,720
47,888

8,324
8,324
9,513
9,839
11,245

2,163
2,163
2,472
3,618
4,135

2,260
2,260
2,583
3,286
3,756

E6H/MS50
E6H/f MS50

5000
5000

100
100

55,601
62,290

57,962
64,651

9,839
11,245

3,618
4,135

3,286
3,756

E6H/MS63
E6H/f MS63 1

6300
6300

100
100

79,809
88,561

82,170
90,922

9,839
11,245

3,618
4,135

3,286
3,756

Standard features manually operated switch


Moving part

Standard features manually operated switch


Fixed part

Manual mechanical close and open pushbuttons


Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating

1 Special 100% neutral pole rating.

17.28
1SXU000023C0202

Discount schedule ED1 [P1] - ED6 [P6]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

Air circuit breakers


Installed optional features
UL & IEC

rs

1.20 Trip Units1


Catalog number

Factory installation
price adder

PR121/P-LI
PR121/P-LSI
PR121/P-LSIG

$ 515
1,208

$ 1,089 2
1,604 2

PR122/P-LI
PR122/P-LSI
PR122/P-LSIRc (IEC only)
PR122/P-LSIG

1,686
2,210
3,189
2,904

2,775
3,299
4,278
3,993

PR123/P-LSI (Standard with PR120/V)


PR123/P-LSIG (Standard with PR120/V)

6,631
7,323

7,720
8,412

Field installable price

1.21 Rating Plugs


UL

E1

E2

E3

DE0400RP
DE0600RP
DE0800RP
DE1000RP
DE1200RP
DE1600RP
DE2000RP
DE2500RP
DE3000RP
DE3200RP
DE3600RP
DE4000RP
DE5000RP

X
X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

IEC

E1

E2

E3

DE0400RP
DE0630RP
DE0800RP
DE1000RP
DE1250RP
DE1600RP
DE2000RP
DE2500RP
DE3000RP
DE3200RP
DE4000RP
DE5000RP
DE6300RP

X
X
X
X
X
X

X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

E4

E6

Field installable price

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X
X

$ 125
125
125
125
125
125
125
125
125
125
125
125
125

E4

E6

X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X
X

125
125
125
125
125
125
125
125
125
125
125
125
125

17

1 Must order rating plug separately when ordering trip unit separately.
2 Requires PRO30/B to be purchased separately. See item 49 on page 16.36.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule EDX [P0]

17.29
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Air circuit breakers


Installed optional features
UL & IEC
Description

Catalog number

Configuration Test Unit


Signaling Unit
Signaling Module 4 output with independent terminals
Signaling Module 4 + 1 input with common terminal
Voltage Measuring Module
Communication Module (Modbus RTU)
Bluetooth Wireless Communication Module internal
Bluetooth Wireless Communication Module external

PR010/T
PR021/K
PR120/K4
PR120/K4C
PR120/V
PR120/D-M
PR120/D-BT
BT030

List price

$ 12,500
5,000.00
2,500.00
2,500.00
2,125.00
5,000.00
2,500.00
3,335

17

1 Standard connection when ordered with breaker.

17.30
1SXU000023C0202

Discount schedule EDX [P0]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

Air circuit breakers


Installed optional features
UL & IEC

rs

23. 30. Electrical and mechanical accessories



Item


Factory
Field installation
installation
catalog
list price
number
adder

23a. Shunt trip coil (included in the electrically operated breaker)


Rated voltage

24V


30V


48V

60V

110/120V
$ 374

125/127V

220/240V

250V

380/400V

440/480V

KE6S0
KE6S9
KE6S8
KE6S7
KE6S6
KE6S5
KE6S4
KE6S3
KE6S2
KE6S1

Field
installation
list price

$ 374

23b. Second shunt trip coil (includes accessory support) 1











24V

30V

48V
60V
110/120V
456
125/127V
220/240V
250V
380/400V
440/480V

KE6S0-2
KE6S9-2
KE6S8-2
KE6S7-2
KE6S6-2
KE6S5-2
KE6S4-2
KE6S3-2
KE6S2-2
KE6S1-2

456

24. Closing coil (included in the electrically operated breaker)


Rated voltage

24V


30V


48V

60V

110/120V
374

125/127V

220/240V

250V

380/400V

440/480V

KE6C0
KE6C9
KE6C8
KE6C7
KE6C6
KE6C5
KE6C4
KE6C3
KE6C2
KE6C1

374

25. Spring charging motor with limit switch and electrical indication charged spring
(included in the electrically operated breaker)
Rated voltage

24/30V

48/60V
1613

100/130V

220/250V

KE6M9
KE6M7
KE6M5
KE6M3

1,613

73

KE6SC

73

Rated voltage

24V


30V


48V

60V

110/120V
456

125/127V

220/240V

250V

380/400V

440/480V

KE6U0
KE6U9
KE6U8
KE6U7
KE6U6
KE6U5
KE6U4
KE6U3
KE6U2
KE6U1

27. Energized undervoltage release signalling contact



Auxiliary contact normally open
82

Auxiliary contact normally closed

KE6UE10
KE6UE01

Spring charged signal only

26. Instantaneous under voltage trip release

17
456

82

1 Order as alternative to UV trip.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule EDX [P0]

17.31
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Air circuit breakers


Installed optional features
UL & IEC


Item


Factory
Field installation
installation
catalog
list price
number
adder

Field
installation
list price

28. Auxiliary contacts for breakers 1


Rated 5A-250VAC / 0.3A 125VDC
28a. 4 auxiliary open/closed contacts (PR121/ on-automatic switch)
28b. 4 auxiliary open/closed contacts for digital signals (PR121/non-automatic switch)
28c. 4 auxiliary open/closed contacts (2NO+2NC+2PR122-3)
28d. 4 auxiliary open/closed contacts (2NO+2NC+2PR122-3) for digital signals
28e. 10 auxiliary open/closed contacts (PR121/non-automatic switch)
28f. 10 auxiliary open/closed contacts for digital signals (PR121/non-automatic switch)
28g. 10 auxiliary open/closed contacts (5NO+5NC+2PR122-3)
28h. 10 auxiliary open/closed contacts (5NO+5NC+2PR122-3) for digital signals
28i. 15 additional auxiliary contacts for field installation on fixed breakers (connected to breaker with

flexible cable) 2
28j. 15 additional auxiliary contacts for field installation on withdrawable breakers (connected to breaker

with flexible cable) 2
29. Auxiliary contacts for switches
29a. 2NO + 2NC
29b. 5NO + 5NC


297

297
753
753
753
753
1507

KE6A4
KE6A4D
KE6A4-PR122/3
KE6A4-PR122/3D
KE6A10
KE6A10D
KE6A10-PR122/3
KE6A10-PR122/3D
KE6A15

$ 297
297
297
297
1050
1,050
1,050
1,050
1,507

1507

KE6A15-W

1,507

297
1050

KE6A4
KE6A10

297
1,050

30. 33. Electrical and mechanical accessories



Item


30.






Factory
Field installation
installation
catalog
list price
number
adder

Auxiliary contacts for service/test/disconnected position indication


Cradle mounted
30a . 5 auxiliary contacts

30b. 10 auxiliary contacts for E1/2 3 pole
30c. 10 auxiliary contacts for E1/2 4 pole
30d. 10 auxiliary contacts for E3
3 pole
30e. 10 auxiliary contacts for E3
4 pole
30f. 10 auxiliary contacts for E4/6 3/4 pole

Field
installation
list price

377
753
753
753
753
753

KE6PS1
KE2PS3
KE2PS4
KE3PS3
KE3PS4
KE6PS2

377
753
753
753
753
753

31. Mechanical operation counter

418

KE6MC

418

32. Bell alarm


Electrical signalling of overcurrent release tripped, Bell alarm contact


348

DE6TBA

753

DE6TBAR4
DE6TBAR5
DE6TBAR9

545

33.


Bell alarm w/remote reset


33a. Electrical signalling of overcurrent release tripped with remote reset 220-240V AC/DC
33b. Electrical signalling of overcurrent release tripped with remote reset 110-130V AC/DC
545
33c. Electrical signalling of overcurrent release tripped with remote reset 24-30V AC/DC

17

1 For field installation, order auxiliary contacts for corresponding trip unit/
2 For mounting on fixed breaker, also requires accessory 41 (KE6MLP).

17.32
1SXU000023C0202

Discount schedule EDX [P0]

non-automatic switch.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

Air circuit breakers


Optional features
UL & IEC

we Em
r b ax
re
ak
e

rs

34. 39. Locks and interlocks



Item


Factory
Field installation
installation
catalog
list price
number
adder

34. Button guard


35.




$ 48

Key lock in open position


35a. Key lock N. 20005 1
35b. Key lock N. 20006
35c. Key lock N. 20007
202
35d. Key lock N. 20008
35e. Key lock different keys

Field
installation
list price

KE6PG

$ 48

DE6KL2
DE6KL3
DE6KL4
DE6KL5
DE6KL1

202

36a. Padlocking button cover (padlocks not supplied) 3 - 4mm locks

162

KE6PD1

162

36b. 3 - 5/16 locks

350

KE6PDHD2

350

DE6PL2
DE6PL3
DE6PL4
DE6PL5
DE6PL1

202

37.




Key and padlocking device to lock the breaker in disconnected, test or connected position (position lock)
37a. Key + padlocking 20005
37b. Key + padlocking 20006
37c. Key + padlocking 20007
202
37d. Key + padlocking 20008
37e. Key + padlocking different keys

38. Accessory to lock the breaker in test or disconnected position only 2


Position lock

212

KE6PLA

212

39. Padlocking device for the safety shutters on the cradle


Cradle padlock

N/A

KE6SP

43

17

1 Keylock number when factory installed is N3004222.


2 Also requires position lock (accessory 37).

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule EDX [P0]

17.33
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

External accessories
Current transformers, UL & IEC

40a. Neutral current transformer (required for 4 wire ground fault systems)

For breaker
Amps

Catalog
number

List
price





E1 E2


400A
800A
1000A
1200A
KE2NCT
1250A
1600A
2000A

$ 406





E3




400A
800A
1000A
1200A
1250A
KE3NCT
1600A
2000A
2500A
3200A

414





E4


1600A
2000A
2500A
KE4NCT 1
3200A
3600A
4000A

818




E6

3200A
4000A
KE6NCT 1
5000A

6300A

818

17

1 KE4NCT & KE6NCT are 100% rated. For 50% rated neutrals on E4 & E6, use KE2NCT & KE3NCT

17.34
1SXU000023C0202

Discount schedule EDX [P0]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Po

we Em
r b ax
re
ak
e

External accessories
Mechanical interlocks 1

rs

41. Mechanical interlocks (base plate for fixed circuit breaker)



For breaker
Interlock type

E1 E6

Catalog
number

All

KE6MLP

List
price

$ 241

NOTE: order for fixed circuit breaker only; order one accessory for each fixed breaker.

42. Interlock for fixed circuit breaker/fixed part of withdrawable circuit breaker (cable attachment plate)

For breaker
Interlock type


E1 E6

Catalog
number

A, B, D
C

KE6MLA
KE6MLC

List
price

$ 628

NOTE: order one accessory for each fixed circuit breaker/fixed part of withdrawable circuit breaker

43. Interlock for fixed circuit breaker/moving part of withdrawable circuit breaker (internal interlocking shaft)

For breaker
Interlock type

Catalog
number

E1 E2
E3
E4, 3 pole
All
E4, 4 pole/ E6, 3 pole
E6, 4 pole

KE2ML
KE3ML
KE4ML-3
KE6ML-3
KE6ML-4

List
price

$ 145

NOTE: order one accessory for each fixed circuit breaker/mobile part of withdrawable circuit breaker

44. Interlock cables




For breaker
Interlock type



E1 E6

A
B
C
D

Horizontal
Catalog
number

Vertical
Catalog
number

KE6MLC-HA
KE6MLC-HB
KE6MLC-HC
KE6MLC-HD

KE6MLC-VA
KE6MLC-VB
KE6MLC-VC
KE6MLC-VD

List
price

$ 97
193
193
193

NOTE: order one type of cable for each interlock

17

1 Order as an alternative to the Accessory number 15 auxiliary contact (see page 16.32) and kirk key lock.

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule EDX [P0]

17.35
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

External accessories
Other items

45. Electronic time delay for undervoltage release 1





Item

45.





Delay

Time delay
Voltage
24/30V
48V
60V
0.5-1-1.5-2-3.5 s
110/125V
220/250V

Field
installation
catalog
number

KE6TL9
KE6TL8
KE6TL7
KE6TL5
KE6TL3

List
price

$ 428

46. Transparent front cover (IP54)



For breaker

46. Cover

E1 E6

Catalog
number

KE6DC

List
price

$ 557

47. Kirk key lock adaptor plate (in open position)



For breaker

47.











Kirk key lock adaptor plate


47a. E1 E2 fixed breaker, 3-4 pole
47b. E1 E2 withdrawable breaker, 3-4 pole
47c. E3 fixed breaker, 3-4 pole
47d. E3 withdrawable breaker, 3-4 pole
47e. E4 fixed breaker, 3 pole
47f. E4 withdrawable breaker, 3 pole
47g. E6 fixed breaker, 3 pole
47h. E6 withdrawable breaker, 3 pole
47i. E4 fixed breaker, 4 pole
47j. E4 withdrawable breaker, 4 pole
47k. E6 fixed breaker, 4 pole
47l. E6 withdrawable breaker, 4 pole

Catalog
number

KE6KKC-E2F
KE6KKC-E2W
KE6KKC-E3F
KE6KKC-E3W
KE6KKC-E4F
KE6KKC-E4W
KE6KKC-E6F
KE6KKC-E6W
KE6KKC-E4F-4
KE6KKC-E4W-4
KE6KKC-E6F-4
KE6KKC-E6W-4

List
price

$ 1,436
1,195
1,436
1,195
1,436
1,195
1,436
1,195
1,436
1,195
1,436
1,195

NOTE: Provision for kirk lock (kirk key lock not included; use lock Type F 1 inch bolt projection in withdrawn position).

48. Kit for converting fixed breaker with rear horizontal terminals to rear vertical (set of three terminals)

Item

17

48.





Conversion kit
48a. 1/2 3p F HR > F VR E1-A
48b. 1/2 3p F HR > F VR E2-A
48c. 1/2 3p F HR > F VR E3-A (12, 16, 20)
48d. 1/2 3p F HR > F VR E3-A (25)
48e. 1/2 3p F HR > F VR E4-A
48f. 1/2 3p F HR > F VR E6-A

Catalog
number

KE1FHRVR
KE2FHRVR
KE3FHRVR
KE3F25HRVR
KE4FHRVR
KE6FHRVR

List
price

$ 644
690
790
790
1,664
2,783

49. 50. Test kits



Item

49. Hand-held battery (standard w/PR122 & 123)


50. Test and configuration unit SACE PR010/T

PR030/B
PR010/T

51. 54. Spare parts


Item

51.
52.
53.
54.

Catalog
number

Racking crank
Door escutcheon
Support plate for auxiliary releases
Lifting plates

Catalog
number

1SDA038092R1
1SDA038096R1
1SDA038339R1
1SDA038093R1

List
price

275
12,500

List
price

$ 122
153
244
224

1 IEC only.

17.36
1SXU000023C0202

Discount schedule EDX [P0]

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Approximate dimensions (for UL version) 1


E1, fixed with horizontal rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.37
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E1, fixed with horizontal rear terminals
4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.38
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E1, withdrawable with horizontal rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.39
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E1, withdrawable with horizontal rear terminals
4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.40
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E1 - E2, withdrawable with vertical rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.41
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E1 - E2, withdrawable with vertical rear terminals
4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.42
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E2, fixed with horizontal rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.43
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E2, fixed with horizontal rear terminals
4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.44
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E2, withdrawable with horizontal rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.45
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E2, withdrawable with horizontal rear terminals
4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.46
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E3, fixed with horizontal rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.47
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E3, fixed with horizontal rear terminals
4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.48
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E3, withdrawable with horizontal rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.49
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E3, withdrawable with horizontal rear terminals
4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.50
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E3 (2500A), withdrawable with vertical rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.51
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E3 (2500A), withdrawable with vertical rear terminals
00.00
4 pole
00.00

Inches
[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.52
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E3 (1200A/1600A/2000A), withdrawable with
Vertical rear terminals, 3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.53
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E3 (1200A/1600A/2000A), withdrawable with
Vertical rear terminals, 4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.54
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E3 (3200A), fixed with
Vertical rear terminals, 3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.55
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E3 (3200A), fixed with
Vertical rear terminals, 4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.56
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E3 (3200A), withdrawable with
Vertical rear terminals, 3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.57
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E3 (3200A), withdrawable with
Vertical rear terminals, 4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.58
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E3X Draw-out with
Vertical rear terminals, 3 pole, 800-2000A

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.59
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E3X Fixed with
Vertical rear terminals, 3 pole, 800-2000A

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.60
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E3X Draw-out with
Vertical rear terminals, 4 pole, 1600-2000A

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.61
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E3X Fixed with
Vertical rear terminals, 4 pole, 800-2000A

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.62
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E4, fixed with horizontal rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.63
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E4, fixed with horizontal rear terminals
4 pole (50% neutral)

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.64
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E4, fixed with horizontal rear terminals
4 pole (100% neutral)

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.65
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E4, withdrawable with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.66
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E4, withdrawable with horizontal rear terminals
4 pole (50% neutral)

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.67
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E4, withdrawable with horizontal rear terminals
4 pole (100% neutral)

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.68
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E4, withdrawable with vertical rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.69
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E4, withdrawable with vertical rear terminals
4 pole (50% neutral)

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.70
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E4, withdrawable with vertical rear terminals
4 pole (100% neutral)

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.71
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E6, fixed with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.72
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E6, fixed with horizontal rear terminals
4 pole (50% neutral)

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.73
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E6, fixed with horizontal rear terminals
4 pole (100% neutral)

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.74
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E6, withdrawable with horizontal rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.75
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E6, withdrawable with horizontal rear terminals
4 pole (50% neutral)

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.76
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E6, withdrawable with horizontal rear terminals
4 pole (100% neutral)

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.77
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E6, withdrawable with vertical rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.78
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E6, withdrawable with vertical rear terminals
4 pole (50% neutral)

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.79
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E6, withdrawable with vertical rear terminals
4 pole (100% neutral)

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.80
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version) 1


E1 - E6, fixed with vertical rear terminals
3 pole

Po

we Em
r b ax
re
ak
e

rs

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

17.81
1SXU000023C0202

rs
ax ake
m
E bre
er
ow

Approximate dimensions (for UL version) 1


E1 - E6, fixed with vertical rear terminals
4 pole

00.00

Inches

00.00

[Millimeters]

17

1 For IEC dimensions, see Emax technical catalog 1SDC200005D0201 available for download at: http://www.abb-control.com/pdf/catalog/1SDC200005D0201.pdf

17.82
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

Emax circuit breaker submittal sheet


Request for quote form
00.00

Inches

00.00

[Millimeters]

Po

we Em
r b ax
re
ak
e

rs

Date

Customer Name

From

Account No.

Location

Contact Name

Phone No.

Location

Fax No.

Phone No.

Comments

Fax No.
RFQ No.
Due Date

Close Date

Quantity
1=1, 3P

4=4, 3P

B=2, 4P

F=6, 4P 50% neutral

2=2, 3P

6=6, 3P

C=3, 4P

G=4, 4P 100% neutral

3=3, 3P

A=1, 4P

D=4, 4P 50% neutral

H=6, 4P 100% neutral

B=basic

S=standard

V=very high

X=200kA

N=normal

H=high

L=limiting (IEC only)

A=800

D=2000

G=3600

N=6300 (IEC only)

B=1200/1250

E=2500

H=4000

P=1000 (IEC only)

C=1600

F=3200

J=5000

A=400

E=1200/1250

J=3000 (UL only)

N=5000

B=600/630

F=1600

K=3200

P=6300 (IEC only)

C=800

G=2000

L=3600 (UL only)

D=1000

H=2500

M=4000

0=None (non-automatic
only

B = fixed, UL

F=Fixed, IEC

Q = 1000VAC

D = drawout, UL, less


cradle

W=drawout, IEC, less


cradle

R = 750VDC (3P)
1000VDC (4P)

A = PR121/P, LI

D = non-automatic

G = PR122/PD, LSIG

B = PR121/P, LSI

E = PR122/P, LI

H = PR122/PD, LSIRc

C = PR121/P, LSIG

F = PR122/P, LSI

J = PR123/P,LSI+PR120/V

0 = none

F=A+C

M=B+C

T=A+N+C+D

A = PR120/K4C

G=A+D

N = PR120/VT

U=N+C

B = PR120/VB std. on
PR123/P

H=A+B+C

P=A+N

V=B+D

C = PR120/D-M

J=B+C+D

Q=A+N+C

W=N+D

D = PR120/D-BT

K=A+C+D

R=A+N+D

E=A+B

L=A+B+C+D

S=N+C+D

Closing coil:

0 = none

C = 48

F = 125 127

J = 380 400VAC

50/60Hz & VDC:

A = 24VDC

D = 60

G = 220 240

K = 440 480VAC

B = 30

E = 110 120

H = 250

A = 4 aux

D = UV energ.NO

G=A&E

B = 10 aux

E = UV energ.NC

H=B&D

F=A&D

J=B&E

Frame Size

Breaking Capacity

Frame Ampere Rating

Rating Plug:

Version

Trip unit:

Trip unit accessories:

Contacts:

Spring charging motor: (includes spring charged signal,


P/N does not show)

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

0 = none

C = 110-130VAC/VDC,

A = 24 30VAC/VDC,

D = 220 250VAC/VDC,

B = 48 60VAC/VDC

E = spring charged signal only

K = PR123/
P,LSIG+PR120/V

17

17.83
1SXU000023C0202

0 = none

Shunt trip:

rs
ax ake
m
E bre
r
Undervoltage
trip:
we
o
P
50/60Hz
& VDC:

50/60Hz & VDC:

C = 48VAC/DC

F = 125 127VAC/DC

J = 380 400VAC

EmaxB =Circuit
Breaker
Submittal Sheet
30VAC/DC
E = 110 120VAC/DC
H = 250VAC/DC
Request for Quote Form

OR

A = 24VDC

Accessories:

G = 220 240VAC/DC

K = 440 480VAC
L = low Z 120-127VAC/DC

0 = none

C = 48VAC/DC

F = 125 127VAC/DC

A = 24VDC

D = 60VAC/DC

G = 220 240VAC/DC

B = 30VAC/DC

E = 110 120VAC/DC

H = 250VAC/DC

J = 38000.00
400VAC Inches

K = 44000.00
480VAC [Millimeters]

N = 48VAC/DC

R = 125 127VAC/DC

U = 380 400VAC

L = 24VDC

P = 60VAC/DC

S = 220 240VAC/DC

V = 440 480VAC

M = 30VAC/DC

Q = 110 120VAC/DC

T = 250VAC/DC

X = none

F=A+B

A = mechanical counter

G=A+C

B = bell alarm

H=A+D

C = bell alarm w/remote


reset 24-30VAC/DC

J=A+E

Second Shunt trip:


50/60Hz & VDC:

D = 60VAC/DC

D = bell alarm w/remote


reset 110-130VAC/DC
E = bell alarm w/remote
reset 220-240VAC/DC
Locking Provisions

X = none

F=A+B

M=C+D

T = Heavy duty padlock,


KE6PDHD1

A = Keylock

G=A+C

N=C+E

U=A+T

B = button guard

H=A+D

P=A+B+D

V=T+D

C = padlock provision
(open)

J=A+E

Q=A+B+E

W=T+E

D = withdrawable position
lock (connected, test and
disconnected positions)

K=B+D

R=A+C+D

Y=A+T+D

E = withdrawable position
lock ( test and disconnected positions)

L=B+E

S=A+C+E

Z=A+T+E

1 = 1, 3P

6 = 6, 3P

D = 4, 4P (50% neutral)

2 = 2, 3P

A = 1, 4P

F = 6, 4P (50% neutral)

3 = 3, 3P

B = 2, 4P

G = 4, 4P (100% neutral)

4 = 4, 3P

C = 3, 4P

H = 6, 4P (100% neutral)

C = IEC cradle

UL cradle

Cradles
Frame Size:

Version:

N = E1B-A; E1N-A; E2B-A


E2N-A

L = E4V-A; E4L-A

H = E2S-A; E2H-A; E4S-A;


E4H-A; E4H-A/f; E6H-A;
E6H-A/f

X = E3X-A2; E6V-A; E6LA; E6X-A

S = E3N-A; E3S-A;
V=E3H-A; E3V-A
12 = 1200 (E1) UL

25 = 2500 (E3) UL

50 = 5000 (E6) UL

32 = 3200 (E3) IEC

16 = 1600 (E2) UL

32 = 3200 (E3) UL

12 = 1250 (E1) IEC

40 = 4000 (E4) IEC

20 = 2000 (E3) UL

36 = 3600 (E4) UL

20 = 2000 (E4) IEC

63 = 6300 (E6) IEC

Terminal Types:

H = HH

A = HV

E = HL (IEC only)

M = VL (IEC only)

(1st letter is upper terminal, 2nd letter is lower


terminal) H= Rear Horizontal/V = Rear Vertical/F
= Front/L = Rear Flat

V = VV

B = VH

G = LH (IEC only)

N = LV (IEC only)

F = FF (IEC only)

C = HF (IEC only)

J = VF (IEC only)

P = FL (IEC only)

L = LL (IEC only)

D = FH (IEC only)

K = FV (IEC only)

Q = LF (IEC only)

Maximum Ampere Rating:

17

Contacts:

0 = none
A = 5 position auxiliaries,
TOC
B = 10 position auxiliaries,
TOC

Options:

X = none

R = DC rated (750 V 3P,


1000V 4P) IEC only

Approved By:

Date:

Accepted By:

Date:

17.84
1SXU000023C0202

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb.us/lowvoltage

You might also like