Digital Multifunction power meter - RISH Master 6100

Application
Digital Multifunction power meter measures all important electrical parameters in 3 phase Network & replaces the multiple analog panel meters. It measures all electrical parameters like AC current, Voltage, Active, reactive & apparent power, power factor, frequency ,neutral current & active & reactive energy & THD. The measurement is performance is in all 4 quadrants. The instruments has optional output as modbus RS 485 for communication to SCADA & One pulse output for energy measurement.

Product Features:
On site programmable PT/CT ratios THD measurement of Voltage and Currents for Power Quality analysis 3 Phase 3 Wire or 4 Wire version available Nominal input Current 5 A or 1A Electrically isolated Current inputs and Auxiliary Supply Size: 96 mm x 96 mm DIN Quadratic high brightness 3 line 4 digits LED display (Simultaneous display of 3 Parameters) Low back depth of less than 80 mm True RMS measurement Four quadrant operation Optional Output: -MODBUS ( Rs485) RTU Protocol ( 2 Wire) -One Pulse Output (potential free relay) for energy measurement Compliance to International Safety standard: IEC 61010-1- 2001 EMC Compliance: As per IEC 61326
7. 8. 9. Volts Y B Volts B R Current IR

10. Current IY 11. Current IB 12. Neutral Current (only for 4 Wire System ) 13. Active Power (kW) 14. Reactive Power (kVAr) 15. Apparent Power (kVA) 16. System Power Factor 17. System Frequency 18. Active energy (kWh ) 19. Reactive energy (kVArh ) 20. Ampere Demand 21. kW Demand 22. Ampere Demand maximum 23. kW Maximum Demand 24. %THD of system voltage 25. %THD of system current 26. %THD of all the 3 L-N voltages (4 wire system) 27. %THD of all the 3 L-L voltages (3wire system)

28. %THD of all the 3 Line currents

List of Electrical Parameters :


1. 2. 3. 4. 5. 6. System Voltage System Ampere Volts R N Volts Y N Volts B N Volts R Y (only for 4 Wire System ) (only for 4 Wire System ) (only for 4 Wire System )

RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in www.rishabh.co.in

Rishabh Instruments

1 / 06 / XIII / 1206

Digital Multifunction power meter - RISH Master 6100


Technical Specifications:
Nominal input voltage (AC RMS) Max continuous input voltage Input Current: Nominal input current System CT primary values Max continuous input current Auxiliary Supply: Universal Auxiliary Supply AC Auxiliary supply frequency range Optional Auxiliary DC supply Input VA Burden: Nominal input voltage burden Nominal input current burden AC Supply burden DC Supply burden Overload Withstand: Voltage Current Operating Measuring Ranges Voltage Voltage for THD measurement Current Current for THD measurement Apparent power (VA) Active power (W) Reactive power (VAr) Frequency Power Factor Total Harmonic Distortion(Up to 15th Harmonic) Phase Neutral Line-Line 57 - 277V L-N 100 - 480V L-L

120% of rated value 1 or 5A AC RMS Std. values up to 4kA (1 or 5 Amp ) 120% of rated value 100 - 250V AC/DC +/- 10% 40 to 70 Hz 12 - 48V DC +/- 10% 0.25 VA approx. per phase 0.65 VA approx. per phase 3.5 VA 3.5 VA 2x for 1 second, repeated 10 times at 10s 20x for 1 second, repeated 5 times at 5 min 5 .. 120% of rated value 50 .. 120% of rated value 5 120% of rated value 10 120% of rated value 5 .. 120% of rated value, Max 360 Mega VA 5 .. 120% of rated value, Max 360 Mega W 5 .. 120% of rated value, Max 360 Mega VAr 45 66 Hz 0.5 Lag ... 1... 0.8 Lead 0%-40%

Reference conditions for Accuracy: Reference temperature 23C +/- 2C Input waveform Sinusoidal (distortion factor 0.005) Input frequency 50 or 60 Hz 2% Auxiliary supply voltage Rated Value 1% Auxiliary supply frequency Rated Value 1% Accuracy: Voltage Current Neutral current Frequency Active power (W) Reactive power (VAr) Apparent power (VA) Power factor Active energy (W.h) Reactive energy (VAr.h) Total Harmonic Distortion (THD R) 0.5% of range (50... 100% of rated value) 0.5% of range (10... 100% of rated value) 3% of range 0.16% of mid frequency (Rated value 10%) 1% of range (Voltage =Rated value 2%, Current 10 ...100% of rated value, Active power factor 0.866 lagging 1... 0.866 leading) 2% of range (Voltage =Rated value 2%,Current = 10 ...100% of rated value, Reactive power factor 0.866 lagging 1... 0.866 leading) 1% of range (Voltage =rated value 2%,Current=10...100% of rated value) 1% of Unity (Voltage =Rated value 2%,Current=40...100% of rated value) 1% (IEC 62053 ) Active P.F. 0.866 lag... 1...0.866 lead 2% (IEC 62053 ) Reactive P.F 0.866 lag... 1...0.866 lead 1% ( Voltage: 60.100% of rated value,Current: 20.100% of rated value)
RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in www.rishabh.co.in

Rishabh Instruments

1 / 06 / XIII / 1206

Digital Multifunction power meter - RISH Master 6100

Influence of Variations: Te mperature coefficient (for rated value range of use (050C) Display update rate: Response time to step input

0.08%/C for voltage and 0.13%/C for other parameters

550 milliseconds approx.

Applicable Standards: EMC Immunity Safety Protection class: Housing protection: Pollution degree: Installation category: High Voltage Test Environmental Operating temperature Storage temperature Relative humidity Warm up time Shock Vibration Enclosure

IEC 61326 EN61000-4-3. 10V/m min Level 3 industrial low level IEC61010-1 , Permanently connected use IEC60529 2 III 2.2 kV AC, 50Hz for 1 minute between all electrical circuits

-10 to +55C -20 to +65C 0... 95% non condensing Minimum 3 minute 15g in 3 planes 10... 55 Hz, 0.15mm amplitude IP54 (front face only)

Serial Communications Option Protocol Baud rate Parity

Modbus (RS 485) 19200, 9600, 4800 or 2400 (programmable) Odd or Even, with 1 stop bit, or None with 1 or 2 stop bits.

Active Energy Pulsed Output Option Default pulse rate 1 per kW.hr Pulse rate divisors 10 (yielding 1 pulse per 10 kW.hr) and 100 (yielding 1 pulse per 100 kW.hr) Pulse duration 60 ms, 100 ms or 200 ms

RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in www.rishabh.co.in

Rishabh Instruments

1 / 06 / XIII / 1206

Digital Multifunction power meter - RISH Master 6100


Electrical Connections
3 Phase 4 Wire Unbalanced Load

8 11 1

8 11 1

L1 L2 L3 N
For Direct operated meter

L1 L2 L3 N

k K

L
k K
l

For CT operated meter

3 Phase 3 Wire Unbalanced Load

L1 L2 L3
For Direct operated meter

L1 L2 L3

For CT operated meter

It is recommended that the wires used for connections to the instrument should have lugs soldered at the end. That is, the connections should be made with Lugged wires for secure connections. The Maximum diameter of the lug should be 7.0 mm and maximum thickness 3.5 mm. Permissible cross section of the connection wires: <= 4.0 mm2 single wire or 2 2.5 mm2 fine wire.

Dimensions

RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in www.rishabh.co.in

Rishabh Instruments

1 / 06 / XIII / 1206

Digital Multifunction power meter - RISH Master 6100


Ordering Information
Ordering Code RISH MASTER 6100 System Type 3 Phase 4 Wire 3 Phase 3 Wire Input Voltage 100V L-L (57.7V L-N) 110 V L-L (63.5V L-N) 115 V L-L (66.4V L-N) 120 V L-L (69.3V L-N) 139 V L-L (80.2V L-N) 208 V L-L (120V L-N) 240 V L-L (139V L-N) 277 V L-L (160V L-N) 380 V L-L (220V L-N) 400 V L-L (230V L-N) 415 V L-L (240V L-N) 480 V L-L (277V L-N) 600 V L-L (346V L-N) Input Current 1 Amps 5 Amps Auxiliary Voltage 12 48 DC 100 250V AC/DC Optional : RS485 Modbus RTU or Johnson controls Metasys N2 RS485 Modbus Not used Optional: One kWhr Pulsed output Pulsed output Not used E Z R Z D A 1 5 100 110 115 120 139 208 240 277 380 400 415 480 600 4 3

Order Code Example :


RISH MASTER 6100 4 - 415 5 D R E
RISH MASTER 6100 , 3 phase 4wire, 415L-L nominal voltage, 5A CT secondary , 12 48V DC auxiliary supply, with MODBUS (RS485) , with one pulse output option.

RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in www.rishabh.co.in