SINAMICS GM150, SINAMICS SM150 Medium-Voltage Converters


Catalog D 12 2009 Supplement 05/2011

SINAMICS Drives
Answers for industry.

General corrections, supplements SINAMICS GM150 in water-cooled IGBT version SINAMICS GM150 in IGCT version SINAMICS SM150 in IGBT version

1 2 3 4 A B

SINAMICS GM150 SINAMICS SM150


Medium-Voltage Converters

Updated option overview Selection and ordering data SINAMICS GM150

Supplement for Catalog D 12 2009

05/31/2011

The information provided in this catalog supplement contains descriptions and characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.

Siemens AG 2011 All Rights Reserved

Table of contents

05/31/2011

Table of contents

General corrections, supplements.................................................................................. 6 1.1 1.2 1.3 1.3.1 1.3.2 1.4 1.4.1 1.4.2 1.4.3 1.5 Corrections .......................................................................................................... 6 24-pulse infeed for SINAMICS GM150.............................................................. 15 Cooling water requirement for IGCT converters................................................ 16 SINAMICS GM150 in IGCT version .................................................................. 16 SINAMICS SM150 in IGCT-Ausfhrung............................................................ 16 Engineering instructions for transformers.......................................................... 17 Transformer secondary voltages ....................................................................... 18 Leakage reactance, impedance voltage............................................................ 19 Tappings for voltage adjustments...................................................................... 20 General information regarding the operation of high-voltage motors................ 20

SINAMICS GM150 in water-cooled IGBT version......................................................... 21 2.1 2.2 2.3 2.4 2.5 2.6 2.3 kV without sine-wave filter ........................................................................... 22 3,3 kV without Sinusfilter ................................................................................... 24 4,16 kV ohne Sinusfilter..................................................................................... 29 2,3 kV mit Sinusfilter .......................................................................................... 34 3,3 kV mit Sinusfilter .......................................................................................... 36 4,16 kV mit Sinusfilter ........................................................................................ 40

SINAMICS GM150 in IGCT version ................................................................................ 44 3.1 3.2 Selection and ordering data............................................................................... 44 Technical data ................................................................................................... 46

SINAMICS SM150 in IGBT version ................................................................................ 47 4.1 Selection and ordering data............................................................................... 48

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

1 General corrections, supplements

4.1.1 4.1.2 4.2 4.2.1 4.2.2

Air cooling .......................................................................................................... 48 Water cooling..................................................................................................... 48 Technical data ................................................................................................... 49 Air cooling .......................................................................................................... 49 Water cooling..................................................................................................... 50

Updated option overview ............................................................................................... 51

Selection and ordering data SINAMICS GM150 IGBT, water cooling ........................ 53

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

1 General corrections, supplements

05/31/2011

General corrections, supplements

1.1

Corrections
Please note the following corrections to the English edition of the catalog D 12 2009.

Table 1-1 Page


1/8

Corrections to edition D 12 2009 Release July 2009


Table Motor Module Power range (typ.) for SINAMICS GM150 IGBT: 1.0 MVA to 10 MVA

Correction
Table Motor Module Power range (typ.) for SINAMICS GM150 IGBT: 1.0 MVA to 13 MVA Table power ranges Type rating for air cooling: 2.3 kV 3.3 kV 4.16 kV 2.3 kV 3.3 kV 4.16 kV Design Note to be deleted without replacement. SINAMICS GM150 in IGBT version Sector-specific options Individual certification of the converters for use on ships (includes option M66) 1) An inquiry is required for options M66 and E11 up to E71 in combination with option Y15 (sine-wave filter). SINAMICS GM150 in air-cooled IGBT version Supplementary footnote regarding the dimensions and weights:
The specified dimensions and weights include where relevant option Y17 (sine-wave filter), however, no additional options.

2/2

Table power ranges Type rating for air cooling: 2.3 kV 3.3 kV 4.16 kV 2.3 kV 3.3 kV 4.16 kV 1.0 to 2.4 MVA 1.0 to 6.3 MVA 1.3 to 7.9 MVA 2.0 to 3.2 MVA 2.0 to 8.0 MVA 2.0 to 10.1 MVA

1.0 to 3.2 MVA 1.0 to 8.0 MVA 1.3 to 10.1 MVA 2.0 to 4.0 MVA 2.0 to 10.3 MVA 2.0 to 13.0 MVA

Type rating for water cooling:

Type rating for water cooling:

2/3

Design Note: Converters with voltages > 4.16 kV are available on request.

2/13

SINAMICS GM150 in IGBT version Sector-specific options Individual certification of the converters for use on ships (includes option M66) 1) An inquiry is required for options M66 and E11 up to E71 in combination with options Y15 (sine-wave filter) or C30 to C49 (an auxiliary voltage other than 3 AC/N/400 V).

2/21 to 2/48

SINAMICS GM150 in air-cooled IGBT version

(Corresponding footnote for water-cooled SINAMICS GM150 IGBT, see Chapter 2.)

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

1 General corrections, supplements

Page
2/21 to 2/48

Release July 2009


SINAMICS GM150 in IGBT version Cable cross-sections, line-side: 3 x 240 3 x 500 MCM Cable cross-sections, motor-side: 2 x 240 2 x 500 MCM PE connection: 2 x 240 or 3 x 240 2 x 500 MCM or 3 x 500 MCM

Correction
SINAMICS GM150 in IGBT version Cable cross-sections, line-side (for all types): 4 x 240 4 x 500 MCM Cable cross-sections, motor-side (for all types): 3 x 240 3 x 500 MCM PE connection (for all types): 4 x 240 4 x 500 MCM SINAMICS GM150 in IGBT version Technical data, footnote 1):
The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The calculation is based on the rated output current. The kW and hp values are in a power range that is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96%. The rated input current additionally depends on the line power factor; a value between 0.94 and 0.96 is assumed as a typical value. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2/21 to 2/48

SINAMICS GM150 in IGBT version Technical data, footnote 1):


The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2/25

SINAMICS GM150 in IGBT version Air cooling, without sine-wave filter Input voltage: 6SL3810-2LN38-8AA1 6SL3810-2LN41-2AA1 6SL3810-2LN41-4AA1 Rated input current: 6SL3810-2LN38-8AA1 2 x (2 x 405) 2 x 1.7 2 x 1.7 2 x 1.7

SINAMICS GM150 in IGBT version Air cooling, without sine-wave filter Input voltage: 6SL3810-2LN38-8AA1 6SL3810-2LN41-2AA1 6SL3810-2LN41-4AA1 Rated input current: 6SL3810-2LN38-8AA1 2 x (2 x 410) SINAMICS GM150 in IGBT version Air cooling, without sine-wave filter Rated input current: 6SL3810-2LP38-8AA1 2 x (2 x 410) 2 x (2 x 1.7) 2 x (2 x 1.7) 2 x (2 x 1.7)

2/28

SINAMICS GM150 in IGBT version Air cooling, without sine-wave filter Rated input current: 6SL3810-2LP38-8AA1 2 x (2 x 405)

2/31

SINAMICS GM150 in IGBT version Air cooling, with sine-wave filter Input voltage: 6SL3810-2LN31-8AA0 2 x 1.2

SINAMICS GM150 in IGBT version Air cooling, with sine-wave filter Input voltage: 6SL3810-2LN31-8AA0 2 x 1.7 SINAMICS GM150 in IGBT version Air cooling, with sine-wave filter Rated input current: 6SL3810-2LN38-8AA1 2 x (2 x 355)

2/32

SINAMICS GM150 in IGBT version Air cooling, with sine-wave filter Rated input current: 6SL3810-2LN38-8AA1 2 x (2 x 360)

2/34

SINAMICS GM150 in IGBT version Air cooling, with sine-wave filter Rated input current: 6SL3810-2LP38-8AA1 2 x (2 x 360)

SINAMICS GM150 in IGBT version Air cooling, with sine-wave filter Rated input current: 6SL3810-2LP38-8AA1 2 x (2 x 355)

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

1 General corrections, supplements

05/31/2011

Page
3/10

Release July 2009


SINAMICS GM150 in IGCT version Sector-specific options

Correction
SINAMICS GM150 in IGCT version Sector-specific options

Individual certification of the converters for Individual certification of the converters for use on ships (on request, includes option M66) use on ships (includes option M66) 1) An inquiry is required for options M66 and E11 Footnote to be deleted without replacement. up to E71 in combination with options C30 to C49 (an auxiliary voltage other than 3 AC/N/400 V). 3/13 4/16 Standards - DIN EN 61800-3/VDE 0160 T103 (IEC 61800-3) - DIN EN 61800-4/VDE 0160 T104 (IEC 61800-4) - DIN EN 60146-1-1/VDE 0558 T11 (IEC 60146-1-1) - DIN EN 50178/VDE 0160 T103 (IEC 62103) - DIN EN 60204-11/VDE 0113 T11 (IEC 60204-11) 3/17 SINAMICS GM150 in IGCT version Standards - DIN EN 61800-3/VDE 0160 T103 (IEC 61800-3) - DIN EN 61800-4/VDE 0160 T104 (IEC 61800-4) - DIN EN 61800-5-1/VDE 0160T105 (IEC 61800-5-1) - DIN EN 60146-1-1/VDE 0558 T11 (IEC 60146-1-1) - DIN EN 50178/VDE 0160 T103 (IEC 62103) - DIN EN 60204-11/VDE 0113 T11 (IEC 60204-11) SINAMICS GM150 in IGCT version Supplementary footnote regarding the dimensions and weights:
The specified dimensions and weights include the cooling unit, however no options.

3/17

SINAMICS GM150 in IGCT version PE connection, max connection cross-section at enclosure with M12 screw: 6SL3835-2LN41-8AA0 6SL3835-2LN43-6AA0 6SL3835-2LN44-2AA0 mm 2 x 120 2 x 120 6 x 120
2

SINAMICS GM150 in IGCT version PE connection, max connection cross-section at enclosure with M12 screw: 6SL3835-2LN41-8AA0 6SL3835-2LN43-6AA0 6SL3835-2LN44-2AA0 mm 3 x 120 6 x 120 9 x 120
2

AWG/MCM 2 x 250 MCM 2 x 250 MCM 6 x 250 MCM

AWG/MCM 3 x 250 MCM 6 x 250 MCM 9 x 250 MCM

4/20 to 4/22

SINAMICS SM150 in IGCT version

SINAMICS SM150 in IGCT version Supplementary footnote regarding the dimensions and weights:
The specified dimensions and weights include the cooling unit, however, no options.

4/20 to 4/22

SINAMICS SM150 in IGCT version Technical data, footnote 1):


The figures for the rated input current and the power figures in hp and kW are approximate values which were determined for operation with synchronous motors, for the power factor cos phi=1 and taking into account the efficiency of the motor. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 500. Both approximate values need to be adapted to the motor which is actually used.

SINAMICS SM150 in IGCT version Technical data, footnote 1):


The figures for the rated input current and the power figures in hp and kW are approximate values which were determined for operation with synchronous motors, for the power factor cos phi=1 and taking into account a 96 % motor efficiency. The calculation is based on the rated output current. The rated input current also depends on the line power factor; a value of 1 has been assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 500. Both approximate values need to be adapted to the motor which is actually used.

(SINAMICS SM150 in IGBT version see chapter 4.) 5/5 5/27 M36 Cable entry, brass M36 Cable entry, brass for power cables

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

1 General corrections, supplements

Page
5/8

Release July 2009


C30 to C49 Auxiliary voltage other than 3 AC/N/400 V (SINAMICS GM150) Note: The combination with option M66 (suitable for marine applications) or options E11 to E71 (individual certification) is only available on request.

Correction
C30 to C49 Auxiliary voltage other than 3 AC/N/400 V (SINAMICS GM150) Note to be deleted without replacement.

5/10 5/28

E11 to E71 (SINAMICS GM150 , water-cooled) M66 Suitable for marine applications (SINAMICS GM150, water-cooled) Note: The combination with options Y15 (sine-wave filter) or C30 to C49 (an auxiliary voltage other than 3 AC /N/ 400 V) on request.

E11 to E71 (SINAMICS GM150 , water-cooled) M66 Suitable for marine applications (SINAMICS GM150, water-cooled) Note: For SINAMICS GM150 in IGBT version, the combination with option Y15 (sine-wave filter) is only available on request. L08 Output reactor The table "Max. cable lengths" shows obsolete information; you can find the current information on catalog page 7/12 or below:

5/16

L08 Output reactor

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

1 General corrections, supplements

05/31/2011

Page
5/16

Release July 2009


L08 Output reactor Attention: Option L08 increases the width of the cabinet as follows: SINAMICS GM150 in IGBT version: Single circuit configuration: 600 mm Parallel circuit configuration: 2 x 600 mm SINAMICS GM150 in IGCT version and SINAMICS SM150: 700 mm for each converter unit When options L49 or L51/L52 are simultaneously selected the width does not have to be increased. L08 Output reactor

Correction

Attention: Option L08 increases the width of the cabinet as follows : SINAMICS GM150 in IGBT version: Single circuit configuration: 600 mm Parallel circuit configuration: 2 x 600 mm When options L49, M13 or M78 are simultaneously selected the width does not have to be increased. SINAMICS GM150 in IGCT version and SINAMICS SM150: 700 mm for each converter unit When options L49 or L51/L52 are simultaneously selected the width does not have to be increased. L48 Make-proof grounding switch at converter input (motor-operated) Attention: Option L48 increases the width of the cabinet as follows: SINAMICS GM150 in IGBT version: 600 mm SINAMICS GM150 in IGCT version: 2 x 700 mm per converter unit L72 Braking Module The following should be ensured when engineering: Shielded cables should be used just the same as at the converter output. The same maximum cable lengths as for SINAMICS GM150 in IGBT version apply (without sine-wave filter or output reactor; refer to Power cables in Section 7). Regarding inductance L, the following requirements apply to the braking resistor and cable routing: The time constant L/R must not exceed 20 s, i.e. L must be less than R x 20 s. Table: Braking power of the Braking Module with external braking resistor: SINAMICS GM150 (IGCT) and SINAMICS SM150: Braking resistor required: 2 x 2. 2

5/18

L48 Make-proof grounding switch at converter input (motor-operated) Attention: Option L48 increases the width of the cabinet as follows: SINAMICS GM150 in IGBT version: 600 mm SINAMICS GM150 in IGCT version: 4 x 700 mm per converter unit

5/21

L72 Braking Module The following should be ensured when engineering: Shielded cables should be used just the same as at the converter output. The same maximum cable lengths as for SINAMICS GM150 in IGBT version apply (without sine-wave filter or output reactor; refer to Power cables in Section 7).

Table: Braking power of the Braking Module with external braking resistor: SINAMICS GM150 (IGCT) and SINAMICS SM150: Braking resistor required: 3.2

10

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

1 General corrections, supplements

Page
5/21

Release July 2009


L72 Braking Module L72 Braking Module Supplement:

Correction

Braking resistor, power connections:


SINAMICS GM150 and SINAMICS SM150 in the IGBT version Terminal 1C1 1D1 Significance Power cable connection (+) Power cable connection ()

SINAMICS GM150 and SINAMICS SM150 in the IGCT version Terminal 1C1 1D1 1M1 Significance Power cable connection (+) Power cable connection () Power cable connection (0)

Braking resistor, temperature monitoring connections:


SINAMICS GM150 and SINAMICS SM150 in the IGBTversion Terminal =.CG-X11:1 =.CG-X11:2 =.CG-X11:3 =.CG-X11:5 =.EF-X22:8 Significance 24 V DC supply Braking resistor temperature too high, fault Braking resistor temperature too high, alarm Wind vane switch ON (option Y73) Reference ground

SINAMICS GM150 and SINAMICS SM150 in the IGCTversion Terminal =.CG-X11:1 =.CG-X11:2 =.CG-X11:3 =.EF-X22:4 Significance 24 V DC supply Braking resistor temperature too high, fault Braking resistor temperature too high, alarm Reference ground

5/25

M03 Rittal TS8 cabinet (static excitation unit, see Accessories) With option M03, the excitation equipment is supplied in a Rittal TS8 cabinet system instead of a Siemens 8MF cabinet system.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

11

1 General corrections, supplements

05/31/2011

Page
5/27

Release July 2009

Correction

M34 M34 Connection of auxiliary voltage and signal cables Connection of auxiliary voltage and signal cables from the top (SINAMICS GM150 in IGBT version) from the top (SINAMICS GM150 in IGBT version) For the appropriate installation conditions, option M34 enables the auxiliary supply and the signal cables to be introduced into the cabinet from the top. For the appropriate installation conditions, option M34 enables the auxiliary supply and the signal cables to be introduced into the cabinet from the top. Note: Option M34 requires that one of the options M32 (customer's terminal strip with spring-loaded terminals for signal cables up to 2 2.5 mm ) or M33 (customer's terminal strip with 2 screw terminals for signal cables up to 2.5 mm ) is simultaneously ordered.

5/27

M61 Redundant fan in power section (SINAMICS GM150 in air-cooled IGBT version) Excluded converter types 2.3 kV 3.3 kV 4.16 kV 6SL3810-2LM36-0AA0 6SL3810-2LN36-0AA0 6SL3810-2LN41-1AA0 6SL3810-2LP36-0AA0

M61 Redundant fan in power section (SINAMICS GM150 in IGBT version) For the following converter types, the cabinet is 600 mm wider: 2.3 kV 6SL3810-2LM36-0AA0 6SL3810-2LM37-0AA1 6SL3810-2LM38-0AA1 6SL3810-2LN36-0AA0 6SL3810-2LN37-0AA1 6SL3810-2LN38-0AA1 6SL3810-2LP35-3AA1

3.3 kV

4.16 kV

For the following converter types, the cabinet is 600 mm wider and the air intake temperature must be limited to a maximum of +35 C: 4.16 kV 6SL3810-2LP36-0AA0 6SL3810-2LP37-0AA1 6SL3810-2LP38-0AA1

The following converter types cannot be ordered with option M61: 3.3 kV 4.16 kV 6SL3810-2LN41-4AA1 6SL3810-2LP41-1AA0 6SL3810-2LP41-2AA1 6SL3810-2LP41-4AA1

5/29

Description of option N15

Description of option N15

5/33

W11 Cooling unit with a redundant titanium plate-type heat exchanger

W11 Cooling unit with a titanium plate-type heat exchanger

12

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

1 General corrections, supplements

Page
5/34

Release July 2009


Y15 Sine-wave filter (SINAMICS GM150 in IGBT version) It should also be noted that only driven loads with a variable torque may be operated (e.g. pumps, fans). Field weakening operation is not permitted. Possible rated output frequencies are limited to the range 30 Hz to max. 66 Hz. The frequency setting range is 1:10.

Correction
Y15 Sine-wave filter (SINAMICS GM150 in IGBT version) It should be noted that only driven loads with a square-law load torque (e.g. pumps, fans) can be operated and that operation in the field weakening range is not permitted. The possible rated output frequencies are 50 Hz and 60 Hz. The frequency setting range is 1:10. Y73 Braking resistor Note: When ordering, the following data must be specified in plain text: Brake output, braking duration and cycle. The technical data are obtained based on this data (for example, dimensions, weight), whereby the following basis data apply to all resistors: Degree of protection IP20 with perforated sheet steel roof cover V2A Cooling using an internal fan Digital feedback signal from the wind vane switch and temperature switch Mounted outside the converter, but inside electrical equipment rooms

5/34

Y73 Braking resistor Note: When ordering, the following data must be specified in plain text: Brake output, braking duration and cycle.

Ambient temperature: maximum converter


ambient temperature

Painted enclosure, RAL 7035


7/3 Connection of circuit-breaker =.EF-X22 17 A 7/4 7/7 Incorporating an external safety shutdown, SINAMICS SM150 =.EF-X21 6 7 =.EF-X22 6 7 7/12 Motor cables SINAMICS GM150 in IGBT version Shielded three-core medium-voltage cables for 3.6/6 kV must be used to connect the converter to the motor. Connection of circuit-breaker =.EF-X21 17 A Incorporating an external safety shutdown, SINAMICS SM150 =.EF-X21 16 17 =.EF-X22 16 17 Motor cables SINAMICS GM150 in IGBT version Shielded three-core medium-voltage cables for 6/10 kV must be used to connect the converter to the motor.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

13

1 General corrections, supplements

05/31/2011

Page
7/13

Release July 2009


Operation of Siemens high-voltage motors The protection concept for high-voltage motors when fed from converters involves two insulating bearings to avoid damaging bearing currents. Moreover, shaft grounding is absolutely necessary so that no voltage can be established at the motor shaft with respect to ground. The shaft is either grounded using a rotary pulse encoder with integrated grounding track at the non-drive end, or using a separate grounding brush at the motor drive end. In the second case, the rotary pulse encoder must be mounted at the non-drive end. In order to additionally protect the bearings of the driven load, we recommend that an insulated coupling is used. Operating standard line motors (only SINAMICS GM150 in IGBT version) It should be noted that only driven loads with a square-law load torque (e.g. fans, pumps, compressors) can be operated and that operation in the field weakening range is not permitted. The possible rated output frequencies (corner frequencies) are limited to a range of 30 Hz to max. 66 Hz. The frequency setting range is 1:10.

Correction
Operation of Siemens high-voltage motors The protection concept for high-voltage motors when fed from converters involves two insulating bearings to avoid damaging bearing currents. Moreover, shaft grounding is absolutely necessary so that no voltage can be established at the motor shaft with respect to ground. The shaft is either grounded using a rotary pulse encoder with integrated grounding track at the non-drive end, or using a separate grounding brush at the motor drive end. In the first case, an insulated coupling is required in order to additionally and reliably protect the bearings of the driven machine. In the second case, the rotary pulse encoder must be mounted at the non-drive end; an insulated coupling is not required. Operating standard line motors (only SINAMICS GM150 in IGBT version) It should be noted that only driven loads with a square-law load torque (e.g. fans, pumps, compressors) can be operated and that operation in the field weakening range is not permitted. The possible rated output frequencies are 50 Hz and 60 Hz. The frequency setting range is 1:10. Scope of delivery 1. Basic unit In the basic unit, SINAMICS SM150 has a Voltage Sensing Module VSM10. The VSM10 senses the line supply voltage regarding phase position, frequency and amplitude. To realize this, a potential transformer is used that is provided on the primary side of the circuit-breaker on the plant side.

7/14

Scope of delivery 1. Basic unit

The following items are not included in the standard scope of delivery: Cables between the transformer and converter, motor cables, circuit-breakers, transformer, motor, cable ducts, filter systems and piping for the raw water supply of the cooling.

The following items are not included in the standard scope of delivery: Cables between the transformer and converter, motor cables, circuit-breakers, transformer, motor, cable ducts, filter systems and piping for the raw water supply of the cooling, potential transformer for the synchronizing voltage of the VSM10.

14

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

1 General corrections, supplements

1.2

24-pulse infeed for SINAMICS GM150


For SINAMICS GM150 in the IGBT and IGCT versions the circuit for the 24pulse infeed (Option N15) is realized in various ways. However, as a result of the more general representation of the circuit versions and in the catalog this cannot be identified. The following two diagrams are intended to show the principle difference between the parallel circuit configuration (in the case of IGBTs) and the series circuit (in the case of IGCTs). The Basic Line Modules (each with two diode rectifiers) are fed from two three-winding transformers with 7.5 offset on the primary side. A 12-pulse configuration is obtained as a result of the 30 phase shift between the two rectifiers of one DC link half. As the infeeds of the two DC link halves are phase-shifted through 15 with respect to one another, a 24-pulse configuration is achieved when the two halves have the same load. In the IGBT case, in addition the difference between the secondary voltages of one transformer must be less than 1 % under load.

SINAMICS GM150 in the IGBT version

Figure 1-1

Option N15: 24-pulse infeed using a parallel circuit configuration of two Basic Line Modules for SINAMICS GM150 in the IGBT version (absolute values of the individual phase offset angles as example)

SINAMICS GM150 in the IGCT version

Figure 1-2

Option N15: 24-pulse infeed using a series circuit configuration of two Basic Line Modules for SINAMICS GM150 in the IGCT version (absolute values of the individual phase offset angle as example)

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

15

1 General corrections, supplements

05/31/2011

1.3

Cooling water requirement for IGCT converters


Please note the updated information regarding the cooling water flowrate and fine water requirement for water-cooled IGCT converters in the following tables (watercooled IGBTconverters, see Chapters 2 and 4.2.2).

1.3.1
Table 1-2

SINAMICS GM150 in IGCT version


SINAMICS GM150 in IGCT version, cooling water requirement
Order no.: 6SL3835- ...-2LN41-8AA0 ...-2LN42-8AA0 15500 417 170 9 ...-2LN43-6AA0 18000 417 170 9 ...-2LN44-2AA0 21000 667 255 10

Type rating Raw water flowrate Deionized water, approx. Circuit design

kVA l/min l

10000 208 135 7

1.3.2
Table 1-3

SINAMICS SM150 in IGCT-Ausfhrung


SINAMICS SM150 in IGCT version, cooling water requirement
Order no.: 6SL3845- ...-7NN4[]-[]AA0 ...-7NN4[]-[]AA0 20000 667 250 12 ...-7NN4[]-[]AA0 30000 1000 300 13 ...-7NN4[]-[]AB0 10000 667 225 14

Type rating Raw water flowrate Deionized water, approx. Circuit design

kVA l/min l

10000 333 150 11

Table 1-4

SINAMICS SM150 in IGCT version, cooling water requirement


Order no.: 6SL3845- ...-7NN4[]-[]AC0 ...-7NN4[]-[]AD0 10000 1000 275 16 ...-7NN4[]-[]AF0 10000 1000 275 17 ...-7NN4[]-[]AG0 10000 1000 300 18

Type rating Raw water flowrate Deionized water, approx. Circuit design

kVA l/min l

10000 667 250 15

Table 1-5

SINAMICS SM150 in IGCT version, cooling water requirement


Order no.: 6SL3845- ...-7NN4[]-[]AF0 ...-7NN4[]-[]AA0 10500 333 150 11 ...-7NN4[]-[]AA0 21000 667 250 12 ...-7NN4[]-[]AA0 31500 1000 300 13

Type rating Raw water flowrate Deionized water, approx. Circuit design

kVA l/min l

20000 1000 300 19

16

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

1 General corrections, supplements

1.4

Engineering instructions for transformers


Hinweis The section about engineering transformers on Pages 7/10 and 7/11 of Catalog D 12 2009 will be replaced by the following text. For additional information on selecting and dimensioning transformers, please contact your sales partner.

Overview
The SINAMICS GM150 and SINAMICS SM150 converters are always connected to the medium-voltage system through a converter transformer. By using the transformer the drive (converter and motor) is disconnected from the network and electrically isolated: The short-circuit power is limited to the maximum permissible values. Converter and motor are operated ungrounded. The line harmonic distortions and the voltage ripple are limited. A ground-fault monitor integrated in the converter monitors the insulation resistance against ground.

Configurations for SINAMICS GM150


For the 12-pulse Basic Line Module of the SINAMICS GM150 converter, a threewinding transformer is required. The secondary windings of the three-winding transformer have a phase shift around 30el, resulting in a 12-pulse infeed with accordingly lower line harmonic distortions. For the 24-pulse Basic Line Module, two three-winding transformers are required. Two transformers with primary windings offset by 15 degrees should be used. It should be ensured that the individual secondary windings have the same voltage. This is to reduce the line harmonics and to guarantee a symmetrical current distribution. In this case, a maximum deviation of 1 % between the two secondary windings connected in parallel is permissible. Instead of the two three-winding transformers a five-winding transformer can also be used in consultation with the transformer manufacturer.

Configurations for SINAMICS SM150


A two-winding transformer is required for each Active Line Module. In the case of a parallel operation of two or three complete converter units, it is also possible to use a three- or four-winding transformer with shifted windings for the suppression of line harmonics.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

17

1 General corrections, supplements

05/31/2011

1.4.1

Transformer secondary voltages

SINAMICS GM150
Table 1-6 Transformer secondary voltages using three-winding or five-winding transformers SINAMICS GM150 (IGBT) und SINAMICS GM150 (IGCT) Circuit Infeed Circuit design (figure number) Infeed transformers Single-circuit configuration 12-pulse (1), (7) 1 threewinding transformer Dy5 Dd0 24-pulse (2), (8) 2 three-winding transformers Dy5 Dd0 with 15 shift between the transformers 12-pulse 1 three-w. transformer, 4 line reactors Dy5 Dd0 (3) 2 three-w. transformers Dy5 Dd0 with 15 shift between the transformers SINAMICS GM150 (IGBT) Parallel circuit 24-pulse 1 five-winding transformer Dd0+7,5 Dy5+7,5 Dd07,5 Dy57,5

Recommended vector group

Converter: VN conv in kV 2.3 3.3 (IGBT) 3.3 (IGCT) 4.16 2 x 1.2 2 x 1.7 2 x 1.7 2 x 2.2

Transformer: secondary voltage in kV (no-load voltage) 2 x (2 x 1.2) 1) 2 x (2 x 1.7) 1) 2 x (2 x 0.85)1)2) 2 x (2 x 2.2)


1)

2 x 1.7 2 x 2.2

2 x (2 x 1.7) 2 x (2 x 2.2)

4 x 1.7 4 x 2.2

1) Option N15 2) Parallel operation of two or three converter units for SINAMICS GM150 in IGCT version (circuit designs (9) and (10) in Catalog): 2 x (2 x 1.7) or 3 x (2 x 1.7) respectively Table 1-7 Transformer secondary voltages using two-winding transformers SINAMICS GM150 (IGBT) and SINAMICS GM150 (IGCT) Infeed Circuit version (figure number) Infeed transformers Recommended vector group Converter: VN conv in kV 2.3 3.3 (IGBT) 3.3 (IGCT) 4.16 12-pulse (single circuit) 2 two-winding transformers Dy5 Dd0 24-pulse (parallel circuit) 4 two-winding transformers Dy5+7,5 Dy57.5 Dd0+7,5 Dd07,5

Transformer: secondary voltage in kV (no-load voltage) 2 x 1.2 2 x 1.7 2 x 1.7 2 x 2.2 4 x 1.2 4 x 1.7 4 x 0.85 4 x 2.2

18

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

1 General corrections, supplements

SINAMICS SM150
Transformer secondary voltage (phase-phase, conductor-conductor): SINAMICS SM150 in the IGCT version: 3.3 kV SINAMICS SM150 in the IGBT version: 3.3 kV or 4.16 kV If, in addition, the converter is to supply a noticeable level of capacitive reactive power to compensate other inductive loads connected to the line supply, then the secondary no-load voltage of the transformer must be dimensioned lower. This is necessary to ensure that the converter voltage of 3.3 kV or 4.16 kV is sufficiently high. As a consequence, the maximum power that can be transferred is reduced. For extremely high surge powers, the secondary no-load voltage must also be dimensioned somewhat lower.

1.4.2

Leakage reactance, impedance voltage

Transformer leakage reactances


The required minimum protection values of the leakage reactance for the various converter types can be taken from the following table. These values include all of the inductances between the line supply and converter: line short-circuit inductance, transformer inductance, reactor inductance.
Table 1-8 Minimum transformer leakage reactances (short-circuit impedance of the line supply 1 % has been taken into account) Converter Version Rated output voltage in V Transformer Secondary voltage per winding system Vsec in V 1200 1700 2200 1700 3300 3300 Min. leakage reactance XS,min in 1) 0.068 0.101 0.143 0.058 0.314 0.179

SINAMICS GM150 IGBT version 2300 3300 4160 IGCT version SINAMICS SM150 IGBT version IGCT version 3300 3300 3300

1) The minimum leakage inductances LS,min can be calculated according to the following formula: XS,min = 2*fNline* LS,min (with fNline = line frequency).

Transformer impedance voltage


For the selected leakage reactance XS (see above), the required impedance voltage ratio vK (for each secondary winding) depends on the rated apparent power rating of the transformer SNTrans (for each secondary winding) and can be calculated using the following formula.

vK =

X S [ ] S NTrans [MVA] ( Vsec [kV ] )2

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

19

1 General corrections, supplements

05/31/2011

1.4.3

Tappings for voltage adjustments


Normally, the winding taps are located on the upper side of the transformer.

SINAMICS GM150
Recommended taps to adapt the voltage: 2 x 2.5 % or 5 % when operating with a sine-wave filter

SINAMICS SM150
Recommended taps to adapt the voltage: 2 x 2.5 %

1.5

General information regarding the operation of highvoltage motors


High-voltage motors can generate voltages when they are driven by the load itself as a result of the plant or system configuration. The magnitude of the voltage that is fed back essentially depends on the speed and the type of motor excitation employed. The following must be carefully observed so that the work can be safely carried out on the converter power section when the high-voltage motor is turning:

For permanent-magnet synchronous motors, options L49 (make-proof grounding switch at the converter output) and L52 (circuit breaker at the converter output) must be selected. For induction motors and permanently excited synchronous motors, if the motor is driven by the load, then one of the options L49 or L52 should be selected.

20

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

SINAMICS GM150 in water-cooled IGBT version

New types with water cooling


In the following you find an updated overview of the technical data of water-cooled SINAMICS GM150 IGBT types. This includes, in green lettering, order numbers -.AA1 that could not yet be included in the 2009 catalog edition. These are replacing some of the former types (with order numbers -.AA0) and are extending the power range. Further corrections/supplements to the 2009 catalog edition are in green lettering as well. Note An updated overview of the selection and ordering data of all available watercooled types is shown in Appendix B.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

21

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

2.1
Table 2-1

2.3 kV without sine-wave filter


SINAMICS GM150 in IGBT version (water-cooled), 2.3 kV without sine-wave filter
Rated data 2.3 kV Order no.: 6SL3815- ...-2LM35-0AA0 ...-2LM35-5AA0 ...-2LM36-0AA1 ...-2LM36-6AA1 kVA
1)

Type rating Shaft output

2000 1650 2250 500 2 x 1.2 2 x 444 28 98.4 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2600

2200 1800 2500 550 2 x 1.2 2 x 494 31 98.4 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2650

2400 2000 2750 600 2 x 1.2 2 x 519 33 98.4 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2650

2600 2150 2950 660 2 x 1.2 2 x 575 34 98.4 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2650

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

22

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-2

SINAMICS GM150 in IGBT version (water-cooled), 2.3 kV without sine-wave filter


Rated data 2.3 kV Order no.: 6SL3815- ...-2LM37-4AA0 ...-2LM38-0AA0 ...-2LM38-8AA1 ...-2LM41-0AA1 kVA
1)

Type rating Shaft output

2900 2450 3250 740 2 x 1.2 2 x 650 38 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2700

3200 2650 3500 800 2 x 1.2 2 x 717 42 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2700

3500 2900 3850 880 2 x 1.2 2 x 771 42 98.6 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2700

4000 3300 4400 1000 2 x 1.2 2 x 870 44 98.7 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2700

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

23

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

2.2
Table 2-3

3,3 kV without Sinusfilter


SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV without sine-wave filter
Rated data 3.3 kV Order no.: 6SL3815- ...-2LN33-5AA0 ...-2LN34-0AA0 kVA
1)

...-2LN34-5AA0 2600 2150 3000 450 2 x 1.7 2 406 34 98.5 10 14 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2800

...-2LN35-0AA0 2900 2400 3250 500 2 x 1.7 2 453 38 98.5 10 14 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2800

Type rating Shaft output

2000 1650 2250 350 2 x 1.7 2 309 28 98.4 10 14 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2750

2300 1900 2500 400 2 x 1.7 2 360 32 98.4 10 14 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2800

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

24

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-4

SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV without sine-wave filter


Rated data 3.3 kV Order no.: 6SL3815- ...-2LN35-5AA0 ...-2LN36-0AA1 kVA
1)

...-2LN36-6AA1 3800 3150 4200 660 2 x 1.7 2 x 575 48 98.6 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

...-2LN37-4AA0 4200 3500 4500 740 2 x 1.7 2 656 55 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

Type rating Shaft output

3100 2650 3500 550 2 x 1.7 2 484 40 98.6 10 14 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

3400 2800 3800 600 2 x 1.7 2 x 521 45 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

25

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

Table 2-5

SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV without sine-wave filter


Rated data 3.3 kV Order no.: 6SL3815- ...-2LN38-0AA0 ...-2LN38-8AA1 kVA
1)

...-2LN41-0AA1 5700 4700 6150 1000 2 x 1.7 2 x 870 63 98.7 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

...-2LN41-1AA1 6300 5300 7000 2 x 550 2 x (2 x 1.7) 2 x (2 x 492) 80 98.6 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200

Type rating Shaft output

4600 3800 5000 800 2 x 1.7 2 719 60 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

5100 4250 6000 880 2 x 1.7 2 x 756 61 98.6 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

26

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-6

SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV without sine-wave filter


Rated data 3.3 kV Order no.: 6SL3815- ...-2LN41-2AA1 ...-2LN41-3AA0 kVA
1)

...-2LN41-4AA0 8000 6700 9000 2 x 700 2 x (2 x 1.7) 2 x (2 x 625) 104 98.5 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200

...-2LN41-6AA1 9100 7600 10200 2 x 800 2 x (2 x 1.7) 2 x (2 x 671) 119 98.6 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200

Type rating Shaft output

6800 5600 7400 2 x 600 2 x (2 x 1.7) 2 x (2 x 519) 87 98.6 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200

7400 6200 8000 2 x 650 2 x (2 x 1.7) 2 x (2 x 578) 96 98.5 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

27

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

Table 2-7

SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV without sine-wave filter


Rated data 3.3 kV 6SL3815- ...-2LN41-8AA1 kVA
1)

Type rating Shaft output

10300 8600 11500 2 x 900 2 x (2 x 1.7) 2 x (2 x 784) 135 98.6 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200
2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

28

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

2.3
Table 2-8

4,16 kV ohne Sinusfilter


SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV without sine-wave filter
Rated data 4.16 kV ...-2LP32-8AA0 kVA
1)

Order no.: 6SL3815- ...-2LP33-1AA0 2200 1850 2500 310 2 x 2.2 2 x 273 31 98.4 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2800 ...-2LP33-5AA0 2500 2100 2750 350 2 x 2.2 2 x 310 33 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2800 ...-2LP34-0AA0 2900 2400 3000 400 2 x 2.2 2 x 359 38 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2800

Type rating Shaft output

2000 1700 2250 280 2 x 2.2 2 x 245 28 98.4 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2750

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

29

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

Table 2-9

SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV without sine-wave filter


Rated data 4.16 kV ...-2LP34-5AA0 kVA
1)

Order no.: 6SL3815- ...-2LP35-0AA0 3600 3000 4000 500 2 x 2.2 2 x 446 47 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850 ...-2LP35-5AA0 4000 3300 4500 550 2 x 2.2 2 x 496 52 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850 ...-2LP36-0AA1 4300 3600 4850 600 2 x 2.2 2 x 519 56 98.6 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

Type rating Shaft output

3200 2700 3500 450 2 x 2.2 2 x 397 42 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

30

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-10

SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV without sine-wave filter


Rated data 4.16 kV ...-2LP36-6AA1 kVA
1)

Order no.: 6SL3815- ...-2LP37-4AA0 5300 4500 6000 740 2 x 2.2 2 x 657 69 98.5 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850 ...-2LP38-0AA0 5800 4800 6500 800 2 x 2.2 2 x 719 75 98.6 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850 ...-2LP38-8AA1 6400 5300 7150 880 2 x 2.2 2 x 772 75 98.7 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

Type rating Shaft output

4800 4000 5450 660 2 x 2.2 2 x 575 58 98.6 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

31

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

Table 2-11

SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV without sine-wave filter


Rated data 4.16 kV ...-2LP41-0AA1 kVA
1)

Order no.: 6SL3815- ...-2LP41-1AA1 7900 6600 9000 2 x 550 2 x (2 x 2.2) 2 x (2 x 490) 98 98.6 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200 ...-2LP41-2AA1 8600 7150 9500 2 x 600 2 x (2 x 2.2) 2 x (2 x 519) 106 98.6 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200 ...-2LP41-3AA0 9400 7900 10000 2 x 650 2 x (2 x 2.2) 2 x (2 x 583) 122 98.5 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200

Type rating Shaft output

7200 5900 8000 1000 2 x 2.2 2 x 870 78 98.8 10 25 183 90 73 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 3620 2280 1275 1 2850

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

32

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-12

SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV without sine-wave filter


Rated data 4.16 kV ...-2LP41-4AA0 kVA
1)

Order no.: 6SL3815- ...-2LP41-6AA1 11500 9600 13000 2 x 800 2 x (2 x 2.2) 2 x (2 x 694) 143 98.6 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200 13000 11250 15300 2 x 900 2 x (2 x 2.2) 2 x (2 x 785) 156 98.7 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 3 4200 ...-2LP41-8AA1

Type rating Shaft output

10100 8500 11000 2 x 700 2 x (2 x 2.2) 2 x (2 x 627) 131 98.5 10 31 283 100 76 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 5420 2280 1275 1 4200

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

33

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

2.4
Table 2-13

2,3 kV mit Sinusfilter


SINAMICS GM150 in IGBT version (water-cooled), 2.3 kV with sine-wave filter
Rated data 2.3 kV Order no.: 6SL3815- ...-2LM35-0AA0 ...-2LM35-5AA0 ...-2LM36-0AA1 ...-2LM37-4AA0 kVA
1)

Type rating Shaft output

1500 1250 1500 380 2 x 1.2 2 x 331 29 97.8 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4540 2280 1275 4 3750

1650 1350 1750 410 2 x 1.2 2 x 364 30 97.9 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4540 2280 1275 4 3850

2150 1790 2400 540 2 x 1.2 2 x 467 31 98.0 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4540 2280 1275 4 3900

2200 1850 2500 550 2 x 1.2 2 x 491 39 98.0 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4540 2280 1275 4 3950

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

34

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-14

SINAMICS GM150 in IGBT version (water-cooled), 2.3 kV with sine-wave filter


Rated data 2.3 kV ...-2LM36-6AA1 kVA
1)

Order no.: 6SL3815- ...-2LM38-0AA0 2400 2000 2750 600 2 x 1.2 2 x 540 41 98.1 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4540 2280 1275 4 3950
2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

Type rating Shaft output

2350 1950 2550 590 2 x 1.2 2 x 513 34 98.0 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4540 2280 1275 4 3950

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

35

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

2.5
Table 2-15

3,3 kV mit Sinusfilter


SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV with sine-wave filter
Rated data 3.3 kV Order no.: 6SL3815- ...-2LN33-5AA0 ...-2LN34-0AA0 kVA
1)

...-2LN34-5AA0 2000 1650 2250 350 2 x 1.7 2 x 307 36 98.0 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4200

...-2LN35-0AA0 2150 1800 2500 380 2 x 1.7 2 x 346 40 98.0 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4200

Type rating Shaft output

1550 1300 1750 270 2 x 1.7 2 x 234 29 97.8 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4540 2280 1275 4 4000

1750 1450 2000 310 2 x 1.7 2 x 269 32 97.9 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4200

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

36

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-16

SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV with sine-wave filter


Rated data 3.3 kV Order no.: 6SL3815- ...-2LN35-5AA0 ...-2LN36-0AA1 kVA
1)

...-2LN37-4AA0 3200 2700 3500 560 2 x 1.7 2 x 501 54 98.1 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4400

...-2LN36-6AA1 3400 2800 3700 590 2 x 1.7 2 x 513 49 98.2 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4400

Type rating Shaft output

2350 1950 2750 410 2 x 1.7 2 x 370 42 98.1 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4300

3100 2550 3400 540 2 x 1.7 2 x 467 44 98.2 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4400

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

37

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

Table 2-17

SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV with sine-wave filter


Rated data 3.3 kV Order no.: 6SL3815- ...-2LN38-0AA0 ...-2LN41-1AA1 kVA
1)

...-2LN41-3AA0 5600 4700 6250 980 2 x (2 x 1.7) 2 x (2 x 441) 90 98.2 10 43 283 120 78 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 7860 2280 1275 6 7100

...-2LN41-4AA0 6050 5100 6500 1060 2 x 1.7 2 x (2 x 477) 97 98.2 10 43 283 120 78 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 7860 2280 1275 6 7300

Type rating Shaft output

3500 2900 4000 610 2 x 1.7 2 x 549 60 98.1 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4400

5500 4550 6000 960 2 x (2 x 1.7) 2 x (2 x 429) 78 98.3 10 43 283 120 78 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 7860 2280 1275 6 7100

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

38

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-18

SINAMICS GM150 in IGBT version (water-cooled), 3.3 kV with sine-wave filter


Rated data 3.3 kV ...-2LN41-2AA1 kVA
1)

Order no.: 6SL3815-

Type rating Shaft output

6100 5100 7000 1080 2 x (2 x 1.7) 2 x (2 x 479) 82 98.3 10 43 283 120 78 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 7860 2280 1275 6 7300
2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

39

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

2.6
Table 2-19

4,16 kV mit Sinusfilter


SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV with sine-wave filter
Rated data 4.16 kV ...-2LP32-8AA0 kVA
1)

Order no.: 6SL3815- ...-2LP33-1AA0 1750 1450 2000 240 2 x 2.2 2 x 210 31 97.9 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4250 ...-2LP33-5AA0 1950 1600 2250 270 2 x 2.2 2 x 240 35 98.0 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4250 ...-2LP34-0AA0 2250 1850 2500 310 2 x 2.2 2 x 282 41 98.0 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4250

Type rating Shaft output

1600 1300 1750 220 2 x 2.2 2 x 190 30 97.8 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4200

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

40

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-20

SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV with sine-wave filter


Rated data 4.16 kV ...-2LP34-5AA0 kVA
1)

Order no.: 6SL3815- ...-2LP35-0AA0 2800 2350 3000 390 2 x 2.2 2 x 350 48 98.1 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4300 ...-2LP35-5AA0 3100 2600 3500 430 2 x 2.2 2 x 388 53 98.1 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4350 ...-2LP36-0AA1 3900 3250 4450 540 2 x 2.2 2 x 471 57 98.2 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4850

Type rating Shaft output

2500 2100 2750 350 2 x 2.2 2 x 311 43 98.1 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4300

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

41

2 SINAMICS GM150 in water-cooled IGBT version

05/31/2011

Table 2-21

SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV with sine-wave filter


Rated data 4.16 kV ...-2LP37-4AA0 kVA
1)

Order no.: 6SL3815- ...-2LP36-6AA1 4250 3550 4750 590 2 x 2.2 2 x 513 59 98.3 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4850 ...-2LP38-0AA0 4500 3800 5000 625 2 x 2.2 2 x 562 72 98.2 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4850 ...-2LP41-1AA1 7150 5900 7950 960 2 x (2 x 2.2) 2 x (2 x 431) 95 98.3 10 43 283 120 78 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 7860 2280 1275 6 7200

Type rating Shaft output

4100 3450 4500 570 2 x 2.2 2 x 514 66 98.2 10 31 183 100 74 18 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4840 2280 1275 4 4850

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

42

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

2 SINAMICS GM150 in water-cooled IGBT version

Table 2-22

SINAMICS GM150 in IGBT version (water-cooled), 4.16 kV with sine-wave filter


Rated data 4.16 kV ...-2LP41-3AA0 kVA
1)

Order no.: 6SL3815- ...-2LP41-2AA1 ...-2LP41-4AA0 7700 6350 8600 1080 2 x (2 x 2.2) 2 x (2 x 464) 103 98.3 10 43 283 120 78 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 7860 2280 1275 6 8200 7950 6600 9000 1100 2 x (2 x 2.2) 2 x (2 x 491) 126 98.2 10 43 283 120 78 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 7860 2280 1275 6 8200

Type rating Shaft output

7350 6200 8000 1020 2 x (2 x 2.2) 2 x (2 x456) 117 98.2 10 43 283 120 78 19 4 x 240 4 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 7860 2280 1275 6 8200

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth
7) 7)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 7) The specified dimensions and weights include the cooling unit and option Y17 (sine-wave-filter), however no additional options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

43

3 SINAMICS GM150 in IGCT version

05/31/2011

SINAMICS GM150 in IGCT version

Correction and supplement to the technical data


Below you will find an updated overview of the selection and ordering data as well as type-specific technical data for SINAMICS GM150 in the IGCT version. Modified and new data are highlighted in green.

3.1

Selection and ordering data

Standard dimensioning
If the motor data are not precisely known, then the converter should be selected and dimensioned based on the rated output current for typical induction motors (refer to the following table). If current derating is required, then the derating factors are applied to this rated output current. The current derating when operating converter units in parallel has already been taken into account for the values listed in the following table. Under certain conditions, output currents higher than those specified in the table are possible; also refer to the section Detailed dimensioning".
Table 3-1 Type rating [kVA] SINAMICS SM150 in IGCT version, standard dimensioning Shaft output Rated output current for typical induction motors [A] Order No. #

[kW] 8000 13000 15000 17000

[hp] 11000 17000 20000 23000 1750 min. 2 x 1360 min. 2 x 1570 min. 3 x 1220

Output voltage 3.3 kV 10000 15500 18000 21000 6SL3835-2LN41-8AA0 6SL3835-2LN42-8AA0 6SL3835-2LN43-6AA0 6SL3835-2LN44-2AA0 7 9 9 10

# = circuit design

Detailed dimensioning
When the motor data are precisely known, then the converters can also be operated with higher output currents. In this case, the rated motor current must be below the maximum thermal converter output current and the motor short-circuit current must be less than the maximum permissible motor short-circuit current of the converter (for both limit values, refer to the following table).

44

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

3 SINAMICS GM150 in IGCT version

In so doing, it should be noted that the motor short-circuit current is defined as follows: The motor short-circuit current is the current that flows in the first 100 ms in a system if all sub-systems are short-circuited and the leakage paths are saturated. For higher rated output currents, the type-specific technical data can differ (refer to the tables in the following section). If you have any questions in this regard, please contact your Siemens sales partner. For detailed dimensioning, the current derating factors should be applied to the maximum thermal output current of the converter. The required current derating when converter units are connected in parallel has already been taken into account for the values specified in the following table.
Table 3-2 Type rating [kVA] SINAMICS SM150 in IGCT version, detailed dimensioning Shaft output Max. therm. output current [A] Max. motor shortcircuit current for induction motor [A] Order No. #

[kW] 8000 13000 15000 17000

[hp] 11000 17000 20000 23000 1750

Output voltage 3,3 kV 10000 15500 18000 21000 8700 7200 8300 8100 6SL3835-2LN41-8AA0 7 6SL3835-2LN42-8AA0 9 6SL3835-2LN43-6AA0 9 6SL3835-2LN44-2AA0 10 2 x 1440 2 x 1660 3 x 1630

# = circuit design

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

45

3 SINAMICS GM150 in IGCT version

05/31/2011

3.2
Table 3-3

Technical data
SINAMICS GM150 in IGCT version
Rated data Output voltage 3.3 kV Order no.: 6SL3835- ...-2LN41-8AA0 ...-2LN42-8AA0 10000 8000 11000 1750 1750 8700 2 x 1.7 2 x 1550 80 99.1 3 15500 13000 17000 2 x 1360 2 x 1440 7200 2 x (2 x 1.7) 2 x (2 x 1240) 128 99.1 6 ...-2LN43-6AA0 ...-2LN44-2AA0 18000 15000 20000 2 x 1570 2 x 1660 8300 2 x (2 x 1.7) 2 x (2 x 1550) 160 99.1 6 21000 17000 23000 3 x 1220 3 x 1630 8100 3 x (2 x 1.7) 3 x (2 x 1240) 192 99.1 9

Type rating Shaft output


1)

kVA kW hp

Rated output current Max. therm. output current Max. motor short-circuit current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A A A kV A kW % A

Max. current demand of the auxiliary supply 50/60 Hz 230 V 1 AC Max. current demand of the auxiliary supply 50/60 Hz 400 V 3 AC Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, 4) 5) max. connectable per phase

17

20

20

23

l/min l

208 135 75 22 6 x 240 6 x 500 MCM 6 x 240 6 x 500 MCM 3 x 120 3 x 250 MCM IP43 5300 2540 1600 7 5400

417 170 77 23 6 x 240 6 x 500 MCM 6 x 240 6 x 500 MCM 6 x 120 6 x 250 MCM IP43 9400 2540 1600 9 9800

417 170 77 23 6 x 240 6 x 500 MCM 6 x 240 6 x 500 MCM 6 x 120 6 x 250 MCM IP43 9400 2540 1600 9 9800

667 255 79 24 6 x 240 6 x 500 MCM 6 x 240 6 x 500 MCM 9 x 120 9 x 250 MCM IP43 14300 2540 1600 10 15000

dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 Cable cross-sections motormm side, max. connectable per (DIN VDE) 4) 5) phase AWG/MCM (NEC,CEC) 2 PE connection, max. connection mm cross-section at enclosure with (DIN VDE) 4) M12 screw AWG/MCM (NEC,CEC) Degree of protection Dimensions Width Height Depth
6) 6)

mm mm mm kg

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with induction motors and for a typical power factor cos phi and motor efficiency. The rated output current is used as basis for the calculation. The kW and hp values lie in a power range, which is obtained by selecting the following values: A motor power factor between 0.85 and 0.88 as well as a motor efficiency of 96 %. The rated input current also depends on the line power factor, for which a typical value of between 0.94 and 0.96 was assumed.

The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 500. Both approximate values need to be adapted to the motor which is actually used. 2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) Figures refer to a subsystem; see "Circuit designs" for the number of subsystems to be connected on the line and motor side. 5) The maximum permissible cable length must be observed (see Power cables in Section 7 of the catalog). 6) The specified dimensions and weights include the cooling unit, however no options.

46

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

4 SINAMICS SM150 in IGBT version

SINAMICS SM150 in IGBT version

New product versions


The medium-voltage drive converter series is extended with a new air-cooled and water-cooled regenerative IGBT version. The converters are equipped on the line side with an Active Line Module, allowing full regeneration of power into the line (as with SINAMICS SM150 in IGCT version). Both the Active Line Module and the motor-side Motor Module utilize HV-IGBT as power device. In the following, you can find selection and ordering data as well as technical data of the types already released for sale. In further steps, additional air-cooled and water-cooled types with enhanced power rating will follow. Note Sine-wave filters (option Y15) and corresponding data are available on request.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

47

4 SINAMICS SM150 in IGBT version

05/31/2011

4.1
4.1.1
Table 4-1 Type rating [kVA]

Selection and ordering data


Air cooling
SINAMICS SM150 in IGBT version, air cooling Shaft output [kW] 2800 3800 3600 4800 [hp] 3600 4950 4700 6500 600 800 600 800 Rated output current [A] Order no. Circuit design from catalog

Output voltage 3.3 kV 3400 4600 4300 5800 6SL3810-7NN36-0AA0 6SL3810-7NN38-0AA1 6SL3810-7NP36-0AA0 6SL3810-7NP38-0AA1 11 11 11 11

Output voltage 4.16 kV

4.1.2
Table 4-2 Type rating [kVA]

Water cooling
SINAMICS SM150 in IGBT version, water cooling Shaft output [kW] 3800 4700 4800 5900 [hp] 4950 6350 6500 8000 800 1000 800 1000 Rated output current [A] Order no. Circuit design from catalog

Output voltage 3.3 kV 4600 5700 5800 7200 6SL3815-7NN38-0AA0 6SL3815-7NN41-0AA1 6SL3815-7NP38-0AA0 6SL3815-7NP41-0AA1 11 11 11 11

Output voltage 4.16 kV

48

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

4 SINAMICS SM150 in IGBT version

4.2
4.2.1
Table 4-3

Technical data
Air cooling
SINAMICS SM150 in IGBT version, air cooling, 3.3 kV and 4.16 kV
Rated data 3.3 kV and 4.16 kV Order no.: 6SL3810- ...-7NN36-0AA0 ...-7NN38-0AA1 ...-7NP36-0AA0 ...-7NP38-0AA1 kV kVA
1)

Output voltage Type rating Shaft output

3.3 3400 2800 3600 600 3.3 616 76 97.3 10 43 20

3.3 4600 3800 4950 800 3.3 822 94 97.5 10 43 20 4.7 85 19 3 x 240 3 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP22 3020 2570 1275 11 2850

4.16 4300 3600 4700 600 4.16 616 98 97.3 10 43 20 4.7 85 19 3 x 240 3 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP22 3020 2570 1275 11 2850

4.16 6500 4800 6500 800 4.16 822 118 97.5 10 43 20 4.7 85 19 3 x 240 3 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP22 3020 2570 1275 11 2850

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
2) 2) 1)

A kV A kW % A A A m /s dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg
3

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 3) supply 50/60 Hz 400 V 3 AC Precharging current requirement, temp. for approx. 25 s Cooling air requirement Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
4) 5)

4.7 85 19 3 x 240 3 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP22 3020 2570 1275 11 2850

Cable cross-sections motorside, max. connectable per 4) 5) phase PE connection, max. crosssection at enclosure with M12 4) screw Degree of protection Dimension Width Height Depth
6) 6)

Circuit design Weight

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with synchronous motors, for a motor power factor cos phi = 1 and for a 96 % motor efficiency. The rated output current is used as basis for the calculation. The rated input current also depends on the line power factor, for which a typical value of 1 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) 3) 4)

5) 6)

The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used. Without cooling system. In addition, 20 A pre-charging current for 25 s. Figures refer to a subsystem; see Circuit designs for the number of subsystems to be connected on the line and motor side. The maximum permissible cable lengths must be observed (see Power cables in Section 7 of catalog). The specified dimensions and weights include no options.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

49

4 SINAMICS SM150 in IGBT version

05/31/2011

4.2.2
Table 4-4

Water cooling
SINAMICS SM150 in IGBT version, water cooling, 3.3 kV and 4.16 kV
Rated data 3.3 kV and 4.16 kV Order no.: 6SL3815- ...-7NN38-0AA0 ...-7NN41-0AA1 ...-7NP38-0AA0 ...-7NP41-0AA1 kV kVA
1)

Output voltage Type rating Shaft output

3.3 4600 3800 4950 800 3.3 822 102 97.3 11 20 20 283 95 76 19 3 x 240 3 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4220 2280 1275 11 3500

3.3 5700 4700 6350 1000 3.3 1027 115 97.6 11 20 20 283 95 76 19 3 x 240 3 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4220 2280 1275 11 3500

4.16 5800 4800 6500 800 4.16 822 132 97.3 11 20 20 283 95 76 19 3 x 240 3 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4220 2280 1275 11 3500

4.16 7200 5900 8000 1000 4.16 1027 145 97.6 11 20 20 283 95 76 19 3 x 240 3 x 500 MCM 3 x 240 3 x 500 MCM 4 x 240 4 x 500 MCM IP43 4220 2280 1275 11 3500

kW hp

Rated output current Input voltage Rated input current Power loss Efficiency
3) 2) 3) 1)

A kV A kW % A A A l/min l dB(A) dB(A) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) 2 mm (DIN VDE) AWG/MCM (NEC,CEC) mm mm mm kg

Max. current requirement aux. supply 50/60 Hz 230 V 1 AC Max. current requirement aux. 4) supply 50/60 Hz 400 V 3 AC Precharging current requirement, temp. for approx. 25 s Raw water flow rate Deionized water, approx. Sound pressure level LpA Measuring surface level LS Cable cross-sections line-side, max. connectable per phase
5) 6)

Cable cross-sections motorside, max. connectable per 5) 6) phase PE connection, max. crosssection at enclosure with M12 5) screw Degree of protection Dimension Width Height Depth Circuit design Weight
7)

1) The specifications for the rated input current and the power data in hp and kW are approximate values only; these have been calculated for operation with synchronous motors, for a motor power factor cos phi = 1 and for a 96 % motor efficiency. The rated output current is used as basis for the calculation. The rated input current also depends on the line power factor, for which a typical value of 1 was assumed. The hp specifications are based on the NEC and CEC guidelines for the North American market. The kW values are specified in multiples of 50. Both approximate values need to be adapted to the motor which is actually used.

2) Approx. 5 % of the power loss is dissipated into the atmosphere. 3) Without cooling system. 4) In addition, 20 A pre-charging current for 25 s. 5) Figures refer to a subsystem; see Circuit designs for the number of subsystems to be connected on the line and motor side. 6) The maximum permissible cable lengths must be observed (see Power cables in Section 7 of catalog). 7) The specified dimensions and weights include the cooling unit, however no options.

50

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

A Updated option overview

Updated option overview


An updated overview of all of the options of the various versions of SINAMICS GM150 and SINAMICS SM150 is provided on the following pages. This replaces the overview of catalog pages 5/2 to 5/6 and, for the first time, also includes the range of options for the SINAMICS SM150 in the IGBT version.

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

51

Description of options
SINAMICS GM150/SINAMICS SM150
The following tables list a complete overview of the availability of options for the four converter versions SINAMICS GM150 and SINAMICS SM150, each in IGBT and IGCT version.

Overview
Order code B00 B43 B44 B45 C30 C33 C34 C35 C36 C37 C38 C39 C40 C41 C42 C43 C44 C46 C48 C49 D00 D02 D15 D55 D56 D57 D72 Option NAMUR terminal strip Documentation, production flowchart: Generated once Documentation, production flowchart: Updated every two weeks Documentation, production flowchart: Updated every month Auxiliary voltage 50 Hz 200 V 3 AC Auxiliary voltage 60 Hz 220 V 3 AC Auxiliary voltage 60 Hz 230 V 3 AC Auxiliary voltage 60 Hz 240 V 3 AC Auxiliary voltage 50 Hz 380 V 3 AC Auxiliary voltage 60 Hz 380 V 3 AC Auxiliary voltage 50 Hz 400 V 3 AC Auxiliary voltage 50 Hz 415 V 3 AC Auxiliary voltage 60 Hz 440 V 3 AC Auxiliary voltage 60 Hz 460 V 3 AC Auxiliary voltage 60 Hz 480 V 3 AC Auxiliary voltage 50 Hz 500 V 3 AC Auxiliary voltage 50 Hz 550 V 3 AC Auxiliary voltage 60 Hz 575 V 3 AC Auxiliary voltage 50 Hz 690 V 3 AC Auxiliary voltage 60 Hz 690 V 3 AC Documentation in German Circuit diagrams, terminal diagrams and dimension drawings in DXF format One set of printed documentation Documentation in Polish Documentation in Russian Documentation in Japanese Documentation in Italian on request on request on request on request on request on request on request on request SINAMICS GM150 SINAMICS GM150 SINAMICS SM150 SINAMICS SM150 IGBT version IGCT version IGBT version IGCT version

Options that can be ordered Options that cannot be ordered

5/ 5/2
Siemens D 12 2009

Description of options
SINAMICS GM150/SINAMICS SM150
Overview (continued)
Order code D76 D77 D78 D79 D84 E00 E01 E02 E03 E11 E21 E31 E51 E61 E71 E86 E87 F03 F73 F77 F97 G20 G21 G22 G23 G24 Option Documentation in English Documentation in French Documentation in Spanish Documentation in Portuguese (Brazil) Documentation in Chinese Closed-loop control for separately excited synchronous motors Closed-loop control for separately excited synchronous motors with slip-ring excitation Closed-loop control for separately excited synchronous motors with brushless reverse field excitation Closed-loop control for permanently excited synchronous motors Suitable for marine applications with individual certificate from Germanischer Lloyd (GL) Suitable for marine applications with individual certificate from Lloyds Register (LR) Suitable for marine applications with individual certificate from Bureau Veritas (BV) Suitable for marine applications with individual certificate from Det Norske Veritas (DNV) Suitable for marine applications with individual certificate from the American Bureau of Shipping (ABS) Suitable for marine applications with individual certificate from the Chinese Classification Society (CCS) Additional analog inputs Additional analog outputs Visual acceptance Functional acceptance of converter with inductive load Acceptance of insulation test of the converter Customer-specific system acceptance tests CAN bus interface Modbus Plus interface Modbus RTU slave interface DeviceNet interface PROFINET interface (via CBE20) on request on request on request on request on request on request on request on request on request on request on request on request on request on request on request on request on request on request only for water cooling only for water cooling only for water cooling only for water cooling only for water cooling only for water cooling SINAMICS GM150 SINAMICS GM150 SINAMICS SM150 SINAMICS SM150 IGBT version IGCT version IGBT version IGCT version

Options that can be ordered Options that cannot be ordered

Siemens D 12 2009

5/3

Description of options
SINAMICS GM150/SINAMICS SM150
Overview (continued)
Order code G25 G34 G35 G30 G61 G62 G63 G66 G70 G71 K20 K21 K22 K50 K80 L08 L21 L29 L32 L48 L49 L50 L51 L52 L53 L55 L60 L72 L80 L81 L82 Option TeleService connection TS Adapter II analog modem PROFINET interface (via CBE30) TeleService connection TS Adapter II ISDN modem PROFIBUS master Additional TM31 Terminal Module Second additional TM31 Terminal Module Additional TM15 Terminal Module PADU8 diagnostics module Pulse distributor for transferring the speed encoder signal Optical bus terminal (OBT) for PROFIBUS Indicator lights in the cabinet door Display instruments in the cabinet door for voltage, current, speed and power as well as indicator lights Display instruments in the cabinet door for current, speed, power and winding temperature as well as indicator lights Sensor Module Cabinet-Mounted SMC30 Control of Safe Torque Off function Output reactor Overvoltage protection AC Bidirectional synchronized bypass operation Automatic restart Make-proof grounding switch at converter input Make-proof grounding switch at converter output Cabinet lighting and service socket outlet in the closed-loop control section Disconnector at the converter output Circuit-breaker at the converter output UPS for the power supply of the open-loop and closed-loop control Anti-condensation heating for the cabinet EMERGENCY STOP, Stop Category 1 for controlled stopping Braking Module 2 thermistor protection relays for alarm and fault 2 x 2 thermistor protection relays for alarm and fault 3 x 2 thermistor protection relays for alarm and fault on request on request only for static excitation unit only with induction motor only for static excitation unit on request on request only for static excitation unit on request on request included as standard included as standard on request on request on request on request only for static excitation unit SINAMICS GM150 SINAMICS GM150 SINAMICS SM150 SINAMICS SM150 IGBT version IGCT version IGBT version IGCT version only for static excitation unit on request

Options that can be ordered Options that cannot be ordered

5/ 5/4
Siemens D 12 2009

Description of options
SINAMICS GM150/SINAMICS SM150
Overview (continued)
Order code L87 L90 L91 L92 L93 L94 L95 L96 M03 M10 M11 M13 M32 M33 M34 M36 M42 M54 M61 M64 M66 M78 N13 N15 N20 N21 N22 N30 N31 N32 N33 Option Rotor ground-fault monitoring PT100 evaluation unit with 3 inputs 2 PT100 evaluation units with 3 inputs each 3 PT100 evaluation units with 3 inputs each PT100 evaluation unit with 6 inputs and 2 analog outputs 2 PT100 evaluation units each with 6 inputs and 2 analog outputs PT100 evaluation unit with 6 inputs for explosion-protected motors and 2 analog outputs 2 PT100 evaluation units each with 6 inputs for explosionprotected motors and each with 2 analog outputs Rittal TS8 cabinet Safety interlocking system Dust protection Power cable connected at the converter input from the top Customer's terminal strip with spring-loaded terminals for signal cables up to 2.5 mm2 Customer's terminal strip with screw terminals for signal cables up to 2.5 mm2 Auxiliary voltage and signal cables connected from the top Cable entry, brass Degree of protection IP42 IP54 degree of protection Redundant fan in the power unit Converter prepared for connection to an external air discharge system, with internal cabinet fans Suitable for marine applications Power cable connected at the converter output from the top Circuit-breaker at the converter input 24-pulse Basic Line Module Capacitor tripping device 110 V to 120 V DC Capacitor tripping device 230 V DC Switch on the input side Controlled motor feeder for auxiliaries 400 V 3 AC / 480 V 3 AC, max. 4/4.8 kW Controlled motor feeder for auxiliaries 400 V 3 AC / 480 V 3 AC, max. 7/8 kW Controlled motor feeder for auxiliaries 400 V 3 AC / 480 V 3 AC, max. 11/12.7 kW Controlled motor feeder for auxiliaries 400 V 3 AC / 480 V 3 AC, max. 15/17.5 kW only for static excitation unit only for static excitation unit 24-pulse only on request only for air cooling only for water cooling not for parallel circuit only for air cooling only for water cooling on request only for static excitation unit only for air cooling only for air cooling included as standard SINAMICS GM150 SINAMICS GM150 SINAMICS SM150 SINAMICS SM150 IGBT version IGCT version IGBT version IGCT version

only for static excitation unit only for static excitation unit only for static excitation unit

Options that can be ordered Options that cannot be ordered

Siemens D 12 2009

5/5

Description of options
SINAMICS GM150/SINAMICS SM150
Overview (continued)
Order code N35 N36 N37 N38 T58 T60 T80 T82 T85 T86 T90 T91 U01 W02 W11 W12 W14 W20 W80 W81 W82 W83 W84 W85 W86 Y09 Y10 Y15 Y17 Y40 Y73 Option Controlled outgoing feeder for auxiliaries 230 V 1 AC / 120 V 1 AC, max. 1,2/1 kW Controlled outgoing feeder for auxiliaries 230 V 1 AC / 120 V 1 AC, max. 2,2/1,5 kW Controlled outgoing feeder for auxiliaries 230 V 1 AC / 120 V 1 AC, max. 3,5/2,1 kW Controlled outgoing feeder for auxiliaries 230 V 1 AC / 120 V 1 AC, max. 4,5/2,8 kW Rating plate in English/French Rating plate in English/Spanish Rating plate in English/Italian Rating plate in English/Portuguese Rating plate in English/Russian Rating plate in English/Polish Rating plate in English/Japanese Rating plate in English/Chinese Converter version for NAFTA with UL listing Cooling unit with redundant stainless steel plate-type heat exchangers Cooling unit with titanium plate-type heat exchanger Cooling unit with redundant titanium plate-type heat exchangers Converter without cooling unit, provided on the plant side Raw-water connection from the bottom Warranty extension of 6 months to 24 months (2 years) after delivery Warranty extension of 12 months to 30 months (2 years) after delivery Warranty extension of 18 months to 36 months (3 years) after delivery Warranty extension of 24 months to 42 months (3 years) after delivery Warranty extension by 30 months to 48 months (4 years) after delivery Warranty extension by 42 months to 60 months (5 years) after delivery Warranty extension by 54 months to 72 months (6 years) after delivery Special paint finish according to RAL... Customer-specific circuit diagrams Sine-wave filter Line reactor Raw-water data that deviates from the catalog data Braking resistor only for static excitation unit only for water cooling, on request only for static excitation unit on request on request on request only for static excitation unit on request on request on request on request on request on request on request only for air cooling only for water cooling only for water cooling only for water cooling only for water cooling only for water cooling on request on request on request on request on request only for water cooling only for water cooling only for water cooling only for water cooling included as standard included as standard on request on request on request on request on request SINAMICS GM150 SINAMICS GM150 SINAMICS SM150 SINAMICS SM150 IGBT version IGCT version IGBT version IGCT version

Options that can be ordered Options that cannot be ordered

5/ 5/6
Siemens D 12 2009

A Updated option overview

05/31/2011

57

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

05/31/2011

B Selection and ordering data SINAMICS GM150 IGBT, water cooling

Selection and ordering data SINAMICS GM150 IGBT, water cooling


An overview of the selection and ordering data for water-cooled SINAMICS GM150 in the IGBT version is provided on the following page (updated of catalog page 2/9).

Siemens AG 2011 All Rights Reserved SINAMICS GM150 SINAMICS SM150 Supplement for Catalog D 12 2009

58


IGBT version Water cooling, without sine-wave filter Selection and ordering data (continued)
Type rating kVA 2.3 kV 2000 2200 2400 2600 2900 3200 3500 4000 3.3 kV 2000 2300 2600 2900 3100 3400 3800 4200 4600 5100 5700 6300 6800 7400 8000 9100 10300 4.16 kV 2000 2200 2500 2900 3200 3600 4000 4300 4800 5300 5800 6400 7200 7900 8600 9400 10100 11500 13000 Shaft output Rated output current A 500 550 600 660 740 800 880 1000 350 400 450 500 550 600 660 740 800 880 1000 2 x 550 2 x 600 2 x 650 2 x 700 2 x 800 2 x 900 280 310 350 400 450 500 550 600 660 740 800 880 1000 2 x 550 2 x 600 2 x 650 2 x 700 2 x 800 2 x 900 Order No. #
1)

SINAMICS GM150 Medium-Voltage Converters


IGBT version Water cooling, with sine-wave filter

Type rating kVA

Shaft output

kW 1650 1800 2000 2150 2450 2650 2900 3300 1650 1900 2150 2400 2650 2800 3150 3500 3800 4250 4700 5300 5600 6200 6700 7600 8600 1700 1850 2100 2400 2700 3000 3300 3600 4000 4500 4800 5300 5900 6600 7150 7900 8500 9600 11250

hp 2250 2500 2750 2950 3250 3500 3850 4400 2250 2500 3000 3250 3500 3800 4200 4500 5000 6000 6150 7000 7400 8000 9000 10200 11500 2250 2500 2750 3000 3500 4000 4500 4850 5450 6000 6500 7150 8000 9000 9500 10000 11000 13000 15300

kW 1250 1350 1790 1850 1950 2000 1300 1450 1650 1800 1950 2550 2700 2800 2900 4550 4700 5100 5100 1300 1450 1600 1850 2100 2350 2600 3250 3450 3550 3800 5900 6200 6350 6600

hp 1500 1750 2400 2500 2550 2750 1750 2000 2250 2500 2750 3400 3500 3700 4000 6000 6250 6500 7000 1750 2000 2250 2500 2750 3000 3500 4450 4500 4750 5000 7950 8000 8600 9000

Rated output current A 380 410 540 550 590 600 270 310 350 380 410 540 560 590 610 960 980 1060 1080 220 240 270 310 350 390 430 540 570 590 625 960 1020 1080 1100

Order No.

1)

6SL3815-2LM35-0AA0 6SL3815-2LM35-5AA0 6SL3815-2LM36-0AA1 6SL3815-2LM36-6AA1 6SL3815-2LM37-4AA0 6SL3815-2LM38-0AA0 6SL3815-2LM38-8AA1 6SL3815-2LM41-0AA1 6SL3815-2LN33-5AA0 6SL3815-2LN34-0AA0 6SL3815-2LN34-5AA0 6SL3815-2LN35-0AA0 6SL3815-2LN35-5AA0 6SL3815-2LN36-0AA1 6SL3815-2LN36-6AA1 6SL3815-2LN37-4AA0 6SL3815-2LN38-0AA0 6SL3815-2LN38-8AA1 6SL3815-2LN41-0AA1 6SL3815-2LN41-1AA1 6SL3815-2LN41-2AA1 6SL3815-2LN41-3AA0 6SL3815-2LN41-4AA0 6SL3815-2LN41-6AA1 6SL3815-2LN41-8AA1 6SL3815-2LP32-8AA0 6SL3815-2LP33-1AA0 6SL3815-2LP33-5AA0 6SL3815-2LP34-0AA0 6SL3815-2LP34-5AA0 6SL3815-2LP35-0AA0 6SL3815-2LP35-5AA0 6SL3815-2LP36-0AA1 6SL3815-2LP36-6AA1 6SL3815-2LP37-4AA0 6SL3815-2LP38-0AA0 6SL3815-2LP38-8AA1 6SL3815-2LP41-0AA1 6SL3815-2LP41-1AA1 6SL3815-2LP41-2AA1 6SL3815-2LP41-3AA0 6SL3815-2LP41-4AA0 6SL3815-2LP41-6AA1 6SL3815-2LP41-8AA1

2.3 kV 1500 1650 2150 2200 2350 2400 3.3 kV 1550 1750 2000 2150 2350 3100 3200 3400 3500 5500 5600 6050 6100 4.16 kV 1600 1750 1950 2250 2500 2800 3100 3900 4100 4250 4500 7150 7350 7700 7950

6SL3815-2LM35-0AA0-Z Y15 6SL3815-2LM35-5AA0-Z Y15 6SL3815-2LM36-0AA1-Z Y15 6SL3815-2LM37-4AA0-Z Y15 6SL3815-2LM36-6AA1-Z Y15 6SL3815-2LM38-0AA0-Z Y15 6SL3815-2LN33-5AA0-Z Y15 6SL3815-2LN34-0AA0-Z Y15 6SL3815-2LN34-5AA0-Z Y15 6SL3815-2LN35-0AA0-Z Y15 6SL3815-2LN35-5AA0-Z Y15 6SL3815-2LN36-0AA1-Z Y15 6SL3815-2LN37-4AA0-Z Y15 6SL3815-2LN36-6AA1-Z Y15 6SL3815-2LN38-0AA0-Z Y15 6SL3815-2LN41-1AA1-Z Y15 6SL3815-2LN41-3AA0-Z Y15 6SL3815-2LN41-4AA0-Z Y15 6SL3815-2LN41-2AA1-Z Y15 6SL3815-2LP32-8AA0-Z Y15 6SL3815-2LP33-1AA0-Z Y15 6SL3815-2LP33-5AA0-Z Y15 6SL3815-2LP34-0AA0-Z Y15 6SL3815-2LP34-5AA0-Z Y15 6SL3815-2LP35-0AA0-Z Y15 6SL3815-2LP35-5AA0-Z Y15 6SL3815-2LP36-0AA1Z Y15 6SL3815-2LP37-4AA0-Z Y15 6SL3815-2LP36-6AA1Z Y15 6SL3815-2LP38-0AA0-Z Y15 6SL3815-2LP41-1AA1Z Y15 6SL3815-2LP41-3AA0-Z Y15 6SL3815-2LP41-2AA1Z Y15 6SL3815-2LP41-4AA0-Z Y15

1) # = circuit design

1) # = circuit design

Siemens AG 2011

SINAMICS D 12 2009

2/9