ABB is a global leader in power and automation technologies that enable utility and industry customers to improve their performance while lowering environmental impact. The ABB Group of companies operates in around 100 countries and employs about 107,000 people.
Contents
Page
1 2 3 4 5 6 7 8
General information Aluminum motors Steel motors Cast iron motors Open drip proof motors Global motors Brake motors Single phase motors
1 1 2 3 4 5 6 7 8
ABB reserves the right to change the design, technical specication and dimensions without prior notice.
General information
Standards
ABB motors are of the totally enclosed and open drip proof, single or three phase squirrel cage type, built to comply with international IEC and EN standards. Motors conforming to other national and international specications are also available on request. IEC / EN Electrical IEC/EN 60034-1 IEC/EN 60034-2 IEC 60034-8 IEC 60034-12 Mechanical IEC 60072 IEC/EN 60034-5 IEC/EN 60034-6 IEC/EN 60034-7 IEC/EN 60034-9 IEC 60034-14
All production units are certied to ISO 9001 international quality standard as well ISO 14000 environmental standard and conrm to all applicable EU Directives.
M000001
M000003
M000329
M000002
1
M000005
EFF1/EFF2 82.8 84.1 85.6 86.7 87.6 88.6 89.5 90.5 91.3 91.8 92.2 92.9 93.3 93.7 94.0 94.6 95.0
4-pole Boarderline EFF2/EFF3 76.2 78.5 81.0 82.6 84.2 85.7 87.0 88.4 89.4 90.0 90.5 91.4 92.0 92.5 93.0 93.6 93.9 EFF1/EFF2 83.8 85.0 86.4 87.4 88.3 89.2 90.1 91.0 91.8 92.2 92.6 93.2 93.6 93.9 94.2 94.7 95.0
Product code pos. 12 A = foot-mounted, term.box top R = foot-mounted, term.box RHS L = foot-mounted, term.box LHS B = ange mounted, large ange
1
Flange-mounted motor, large ange
Foot- and ange-mounted IM B35 IM V15 IM V36 *) *) *) motor with feet, IM 2001 IM 2011 IM 2031 IM 2051 IM 2061 IM 2071 large ange
M000010
Foot-mounted motor, shaft with free extensions IM 1002 IM 1012 IM 1032 IM 1052 IM 1062 IM 1072
M000012
M000011
Foot- and ange-mounted IM B34 IM V17 motor with feet, IM 2101 IM 2111 IM 2131 IM 2151 IM 2161 IM 2171 small ange
Cooling
Designation system concerning methods of cooling refers to standard IEC 60034-6.
Example
IC
International Cooling Circuit arrangement 0: Free circulation (open circuit) 4: Frame surface cooled
(A)
(A)
Primary coolant A for air (omitted for simplied designation) Method of movement of primary coolant 0: Free convection 1: Self-circulation 6: Machine-mounted independent component Secondary coolant A for air (omitted for simplied designation) W for water Method of movement of secondary coolant 0: Free convection 1: Self-circulation 6: Machine-mounted independent component 8: Relative displacement
IK code : Classication of degrees of protection provided by enclosure for motors against external mechanical impacts.
IK International mechanical protection Characteristic group Relation between IK code and impact energy: IK cod IK 0 IK 01 IK 02 IK 03 IK 04 Impact * 0.15 0.2 0.35 0.5 energy Joule * not protected according to EN 50102 IK 05 0.7 IK 06 1 IK 07 2 IK 08 5
ABB Standard
08
IK 09 10
IK 10 20
Insulation
ABB uses class F insulation systems, which, with temperature rise B, is the most common requirement among industry today. The use of Class F insulation with Class B temperature rise gives ABB products a 25 C safety margin. This can be used to increase the loading by up to 12 per cent for limited periods, to operate at higher ambient temperatures or altitudes, or with greater voltage and frequency tolerances. It can also be used to extend insulation life. For instance, a 10 K temperature reduction will extend the insulation life. Class F insulation system Max ambient temperature 40 C Max permissible temperature rise 105 K Hotspot temperature margin + 10 K Class B rise Max ambient temperature 40 C Max permissible temperature rise 80 K Hotspot temperature margin + 10 K Insulation system temperature class Class F 155 C Class B 130 C Class H 180 C
M000013
Guideline values of maximum speeds for General purpose aluminum motors described in gure 1. Exact values are available on request.
Figure 1. Guideline values of maximum speeds for General purpose motor in aluminum frame: Motor size 63-80 90-100 112-200 225-280 Speed r/min 2-pole 4-pole 6000 6000 4500 3600 4500 6000 4500 3600
At low speed operation the cooling capacity of the fan decreases, which may cause higher temperature rises in the motor. A separate constant speed fan can be used to increase cooling capacity and loadability at low speed. It is also important to check the performance of the grease at low speeds. 3. Lubrication Variable speed operation affects on the bearing temperature, which must be taken into account when selecting the lubrication method and grease type. For example the life time of sealed bearings can be remarkably shorter than in direct on line operation. 4. Insulation protection Frequency converter supply causes higher voltage stresses at the windings of the motor than the sinusoidal supply. Thus, the insulation system and possible lters must be selected according to the used voltage and converter type. For selection of insulation system and lters, see gure 2. 5. Bearing currents Bearing voltages and currents must be avoided in all motors. For reliability issues, insulated bearings and/or properly dimensioned lters at the converter output must be used according to the instructions in gure 2. When ordering, clearly state which alternative will be used. For more information about bearing currents and voltages, please contact ABB.
6. Cabling, grounding and EMC The use of a frequency converter puts higher demands on the cabling and grounding of the drive system. The motor must be cabled by using shielded symmetrical cables and cable glands providing 360 bonding (also called EMC-glands). For motors up to 30 kW unsymmetrical cables can be used, but shielded cables are always recommended. More information about grounding and cabling of a variable speed drive can be found from the manual
Grounding and cabling of the drive system (Code: 3AFY 61201998 R0125 REV B) and the ABBs Low Voltage Motors Manual. For fullling the EMC requirements, special EMC cable(s) must be used in addition to the correct cable gland mounting, with special, extra earthing pieces. Please refer to the manuals of the frequency converter.
Validity of gure 2 Measures mentioned in Figure 2 apply to the applicable motors within the General motors range (not high-output versions) with ACS 800 and ACS 550 drives with uncontrolled DC-voltage. For other alternatives and converter types, please contact ABB.
Figure 2. Selection rules for insulation and ltering in variable speed drives
Motor nominal power PN or frame size PN < 100 kW UN 500 V Standard motor PN 100 kW or IEC 315 Frame size IEC 355 Standard motor + Insulated N-bearing Standard motor + dU/dt-lter (reactor) + Insulated N-bearing OR Reinforced insulation + Insulated N-bearing PN 350 kW or IEC 400 Standard motor + Insulated N-bearing + Common mode lter Standard motor + Insulated N-bearing + dU/dt-lter (reactor) + Common mode lter OR Reinforced insulation + Insulated N-bearing + Common mode lter Reinforced insulation + Insulated N-bearing + dU/dt-lter (reactor) + Common mode lter
UN 600 V
UN 690 V
dU/dt lter (reactor) Series reactor. DU/dt -lter decreases the changing rate of the phase and main voltages and thus reduces voltage stresses in the windings. DU/dt -lters also decrease so-called common mode currents and the risk of bearing currents. Common mode Common mode lters reduce so-called common mode currents in VSD applications and thus decrease the risk of bearing currents. Common mode lters do not signicantly affect the phase or main voltages on the motor terminals. Insulated Bearings Bearings with insulated inner or outer races are used as the standard solution. So-called hybrid bearings, i.e. bearings with non-conductive ceramic balls, can also be used in special applications. More information for spare part selection is available on request.
Figure 3. Motor loadability with ACS 800, Field weakening point 50 Hz.
10
M000014
5
www.abb.com/motors&drives
> Motors > Low voltage motors > General purpose motors
Mechanical design ..............................146 Ordering information...........................151 Technical data......................................152 Variant codes .......................................157 Dimension drawings............................159 Rating plates........................................163 Open drip proof motors in brief .........164
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
145
Mechanical design
Stator
The stator frame is made of prole-pressed sheet steel, giving the motor high mechanical stregth, low weight and a good surface nish. The stator core is welded into the stator frame and contributes to its excellent mechanical properties. Feet and lifting eyes are welded to the stator frame. The terminal box and end shields are of cast iron.
Drain holes
Motors that will be operated in very humid or wet environments, and especially under intermittent duty, should be provided with drain holes. The appropriate IM designation, such as IM V3 (IM 3031), is specied, on the basis of the method of motor mounting. M2FA motors are tted with drain holes and plugs. The plugs are open on delivery. Check that the drain holes and grease outlet face downwards, when mounting designation differs from standard horizontal mounting. In the case of vertical mounting, the upper plug must be hammered home completely. In very dusty environments the drain hole plug should be knocked in.
closed
5
open open
Terminal box
Terminal boxes are mounted either on the top of the motor, or on either side of the motor, see ordering information page . In basic version the terminal box can be rotated 2x180 to allow cable entry from either side of the motor. The terminal box is equipped with cable glands or cable boxes as standard, and terminations are suitable for Cu- and Al-cables. Cables are connected to the terminals by cable lugs which are not included with the motor. To enable us to supply suitable terminations for the motor please state cable type, quantity and size when ordering. For dimension drawings of terminal boxes, see drawings.
146
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
M000103
M2FA 280 to 400 motors with top-mounted terminal box Standard cable entries and cable boxes
Motor size M2CA
280 315 355 SA 355 M_ 355 L_
Terminal box
122/4 142/4 142/4 162/4 142/4 162/4
Flange or adapter
3GZF 294730-749 3GZF 294730-753 3GZF 294730-753 3GZF 294730-944 3GZF 294730-944
Gland thread
Cable diameter
2x 32-49 2x 32-49 2x 32-49 2x 48-60 2x 48-60 2x 48-60
D E
D E
D E
Voltage/frequency codes: D - 380-420 VD 50 Hz, 660-690 VY 50 Hz, 440-480 VD 60 Hz E - 500 VD 50 Hz, 575 VD 60 Hz
Examples:
Terminal box Flange with cable gland Flange with cable box
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
147
M000065
able for cable boxes and cable entries. Other types on request.
Cable entry mm 1xPg29...42 2xPg29...42 1xPg36...42 2xPg36...48 1xPg36...42 2xPg36...48 1xPg36...42 2xPg36...48 2x1Pg36...42 2x2Pg36...48
Cable box
Blank plate
1x36...52/48...60 1x36...52/48...60 1x36...52/48...60 2x48...60/50...68 1x36...52/48...60 2x48...60/50...68 1x36...52/48...60 2x48...60/50...68 2x268.. .80 2x1x36...52/48...60 2x2x48...60/50...68 2x268...80
E-2D1)
550/950
4x240
1)
Terminal box type 162/4 is used with a combination of one E-opening and one or two D-openings, as described below:
Terminal box 162 with adapting ange 3GZF 294730-501 (E-D) or optional 3GZF 294730-301 (E-2D):
E-opening Adapter E-2D
5
Adapter E-D D-openings
Adaptor E - D
M000088
c 62 100 115
f 62 80 100
d M8 M10 M12
148
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
Bearings
The motors are normally tted with single-row deep groove ball bearings as listed in the table on the right. The complete ball bearing designation is stated on the rating plate. If the bearing at the D-end is replaced with a roller bearing (NU- or NJ-), higher radial forces can be handled. Roller bearings are suitable for belt drive applications. When there are high axial forces, angular-contact ball bearings should be used. This option is available on request. When a motor with angular-contact ball bearings is ordered, the method of mounting and direction and magnitude of the axial force must be specied. For special bearings, please see variant codes.
Version with roller bearings, variant code 037 D-end (NU 319/C3) (NU319/C3) (NU 322/C3) (NU 322/C3)
deep groove ball bearings D-end 6316/C4 6319/C3 6316/C4 6319/C3 6322/C3 6322/C3 N-end 6316/C4 6316/C3 6316/C4 6316/C3 6319/C3 6319/C3
4-8
Bearing seals
M2FA motors have, as standard, V-rings at both ends. The size and type of suitable seals are in accordance with the table below:
Motor size Number of poles 2 4-8 2 4-8 2 4-8 4-8 d1 d2 B1 b Standard design Axial seal D-end N-end VS 80 VS 80 VS 80 VS 95 VS 95 VS 110 VS 110 VS 80 VS 80 VS 80 VS 80 VS 95 VS 95 VS 95 Alternative design Radial seal (DIN 3760) 80x100x10 1) 95x120x12 80x100x10 1) 95x120x12 95x120x12 1) 110x140x12 1) 110x140x12 1)
80 95 80 95 95 110 110
10 12 10 12 12 12 12
Viton-seal
V-Ring
Radial seal
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
M000072
149
Permissible radial and axial force for a bearing life of 40,000 hours
Permissible radial force for: Horizontal mounting, sideways direction of force Length of shaft extension E (mm) 140 170 170 170 140 170 170 170 140 210 210 210 170 210 210 210 Ball bearing at point of application: FXmax FX0 N N 5850 8900 10200 11200 5800 9000 10200 11300 6200 12100 13800 15200
2)
Permissible axial force for 1): Horizontal Vertical mounting with shaf mounting extension downwards Direction of force Outwards Upwards N N 3800 5300 6500 7450 3700 5000 6350 7300 2100 4100 5500 6900
2)
Number of poles 2 4 6 8 2 4 6 8 2 4 6 8 2 4 6 8
Roller bearing at point of application: FX0 FXmax N N 26100 29500 32100 26200 29600 32300 36500 41500 45000 37500
2) 2)
4500 7050 8100 8900 4800 7300 8350 9200 5400 9800 11200 12300
2)
11400 11300 11100 14000 14200 14300 18100 20200 21000 13500
2) 2)
315
355
400
5
1)
12200
2) 2)
10500
2) 2)
3900
2) 2)
Flange-mounted motors with deep groove ball bearings at D-end. Other designs on request. No simultaneuous radial forces allowed. 2) On request. If the radial force is applied between points X0 and Xmax, the permissible force FR can be calculated from the following formula: FR = Fxo - X (Fxo - Fx max) E E = length of shaft extension in basic version
150
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
M000145
Ordering information
Sample order
When placing an order, please state the following minimum data in the order, as in the example. The product code of the motor is composed in accordance with the following example. Motor type M2FA 315SMA Pole number 2 Mounting arrangement (IM-code) IM B3 (IM 1001) Rated output 200 kW Product code 3GFA312210-ASB Variant codes if needed
A Motor type B Motor size C Product code D Mounting arrangement code E Voltage and frequency code F Generation code G Variant codes
T 660 V 50 Hz
Code letters for supplementting the product code for voltage and frequency two-speed motors: A 220 V 50 Hz B 380 V 50 Hz D 380-400 V 50 Hz 440-480 V 60 Hz E 500 V 50 Hz 575 V 60 Hz H 400-415 V 50 Hz 460-480 V 60 Hz S 220-230 V 50 Hz
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
151
Output kW
Motor type
400 V 50 Hz
3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 281 210-A 311 110-A 311 210-A 311 320-A 311 330-A 311 510-A 311 520-A 351 110-A 351 310-A 351 320-A 351 510-A 2971 2977 2975 2975 2977 2969 2969 2982 2978 2973 2981 94.5 94.2 94.4 94.5 94.6 94.9 94.8 94.7 95.0 95.1 95.5 0.84 0.86 0.86 0.87 0.84 0.89 0.88 0.88 0.89 0.90 0.89 241 289 353 431 573 606 700 680 765 851 956
Basic design
7.0 6.7 7.1 7.1 7.8 6.8 7.3 7.1 7.4 6.7 8.7 424 513 643 804 1012 1142 1288 1280 1443 1606 1794 2.1 1.6 1.8 1.9 2.1 2.0 2.0 1.1 1.3 1.2 1.5 2.4 2.5 2.6 2.6 2.8 2.5 2.6 2.6 3.0 2.7 3.1
1)
M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA
280 SMA 315 SA 315 SMA 315 MB 315 MC 315 LA 315 LB 355 SA 355 MA 355 MB 355 LA
5) 5) 5) 5)
400 V 50 Hz
2971 94.9 0.88 279
High-output design
7.0 514 2.0 2.7
400 V 50 Hz
1476 1477 1483 1482 1481 1477 1484 1485 1484 1485 1486
4) 4) 4)
Basic design
0.83 0.84 0.83 0.83 0.83 0.83 0.85 0.82 0.82 0.83 0.81 211 245 297 366 452 577 555 653 733 810 920 5.8 5.9 6.5 6.5 6.7 6.7 6.4 6.6 5.9 6.5 7.7 713 853 1030 1287 1611 2036 2027 2282 2574 2896 3213 1.8 1.8 1.8 1.8 1.7 2.2 1.7 1.9 1.7 1.8 2.0 2.4 2.3 2.5 2.3 2.3 2.5 2.4 2.5 2.2 2.4 2.8
93.1 93.8 94.6 94.7 94.9 94.5 95.0 95.4 95.3 95.4 95.4
1)
2) 2) 2) 1)2)
400 V 50 Hz
1480 94.0 0.81 305
High-output design
7.2 1032 2.5 2.6
The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page).
1) 2) 3) 4) 5)
Temperature rise class F. Special winding for 415V 50 Hz. 415 V 50 Hz and 440 V 60 Hz on request. On request. Please check technical construction with ABB.
152
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
Output kW
Motor type
Speed r/min
Speed r/min
380 V 50 Hz
2969 2975 2974 2974 2974 2965 2966 2980 2975 2970 2978 94.4 94.2 94.3 94.4 94.6 94.8 94.7 94.6 94.9 95.1 95.5 0.86 0.87 0.87 0.88 0.86 0.89 0.88 0.90 0.90 0.90 0.90 246 302 370 449 576 635 720 700 795 880 980
415 V 50 Hz
2966 2978 2978 2976 2971 2970 2970 2983 2979 2974
4)
Basic design
0.87 0.84 0.84 0.85 0.88 0.86 0.85 0.87 0.87 0.87 227 282 344 420 530 591 683 663 746 830 0.8 1.2 1.4 1.7 1.7 2.1 2.1 3.2 3.5 3.5 4.8 540 695 770 840 840 975 975 1220 1320 1320 1530 87 92 92 92 92 92 92 93 93 93 93
1)
M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA M2FA
280 SMA 315 SA 315 SMA 315 MB 315 MC 315 LA 315 LB 355 SA 355 MA 355 MB 355 LA
94.1 94.2 94.4 94.5 94.6 94.9 94.8 94.7 95.0 95.1
5) 5) 5) 5)
380 V 50 Hz
2968 94.8 0.88 288
415 V 50 Hz
2973 94.9 0.86 269
High-output design
1.15 580 89
380 V 50 Hz
1474 1474 1481 1480 1479 1475 1482 1484 1482 1483 1484
4) 4) 4)
415 V 50 Hz
0.85 0.86 0.85 0.85 0.86 0.85 0.86 0.84 0.85 0.85 0.84 217 255 306 379 470 596 584 670 746 835 949 1477 1478 1481 1483 1482 1473 1485 1485 1483 1484 1486 93.1 93.8 94.6 94.8 94.9 93.5 95.0 95.4 95.1 95.4 95.4 0.82 0.83 0.84 0.82 0.83 0.86 0.83 0.83 0.84 0.83 0.83 206 239 283 360 441 540 541 622 685 798 880
Basic design
1.15 1.4 2 2.3 2.9 3.5 5.5 5.5 5.5 6.5 7.8 9.8 445 490 680 735 850 970 1220 1220 1220 1350 1550 1820 2700 2700 81 81 86 86 86 87 89 89 89 89 89
92.8 93.2 94.5 94.6 94.7 94.5 94.8 95.3 95.2 95.3 95.3
1)
2) 2) 2) 1)2)
380 V 50 Hz
1478 93.9 0.84 310
415 V 50 Hz
1481 94.0 0.81 298
High-output design
1.7 550 87
The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page).
1) 2) 3) 4) 5)
Temperature rise class F. Special winding for 415V 50 Hz. 415 V 50 Hz and 440 V 60 Hz on request. On request. Please check technical construction with ABB.
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
153
Output kW
Motor type
400 V 50 Hz
3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 283 110-A 283 210-A 313 110-A 313 210-A 313 320-A 313 510-A 353 110-A 353 120-A 353 310-A 987 987 988 988 988 987 990 990 990 92.8 93.1 93.5 94.0 94.1 94.4 94.7 94.8 95.1 0.76 0.76 0.81 0.83 0.82 0.83 0.82 0.83 0.81 155 187 210 248 300 346 373 457 541
Basic design
5.8 6.1 7.4 7.6 8.2 8.5 7.1 7.3 7.2 725 870 1062 1275 1545 1788 1927 2409 2894 1.9 2.0 1.7 1.8 1.9 1.9 1.6 1.6 1.7 2.2 2.3 2.6 2.7 2.8 2.9 2.5 2.5 2.4
M2FA 280 SA M2FA 280 SMA M2FA M2FA M2FA M2FA 315 SA 315 SMA 315 MB 315 LA
1)
400 V 50 Hz
3GFA 283 320-A 987 93.6 0.76 227
High-output design
6.5 1063 2.1 2.3
M2FA 280 MB
400 V 50 Hz
3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 3GFA 284 110-A 284 210-A 314 210-A 314 320-A 314 510-A 354 110-A 354 120-A 738 738 739 739 739 740 740 91.2 91.8 92.9 93.4 93.3 93.4 93.9 0.78 0.76 0.79 0.78 0.78 0.75 0.76 117 161 183 224 268 318 381
Basic design
5.6 6.1 6.8 7.3 7.2 5.3 5.6 711 970 1162 1420 1706 1934 2385 1.2 1.4 1.7 1.8 1.8 1.3 1.4 2.0 2.1 2.5 2.6 2.6 2.0 2.0
M2FA 280 SA M2FA 280 SMA M2FA 315 SMA M2FA 315 MB M2FA 315 LA M2FA 355 SA M2FA 355 SB
1)
1)
400 V 50 Hz
3GFA 284 320-A 739 92.6 0.75 192
High-output design
6.7 1162 1.6 2.2
M2FA 280 MB
The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page).
1) 2)
154
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
Output kW
Motor type
Speed r/min
Speed r/min
380 V 50 Hz
985 986 986 986 986 986 989 989 988 92.7 92.9 93.4 93.7 94.0 94.2 94.5 94.7 94.9 0.79 0.79 0.85 0.85 0.85 0.85 0.84 0.84 0.85 158 190 212 256 310 352 385 478 546
415 V 50 Hz
986 987 989 989 989 988 990 991 991 92.7 93.1 93.5 94.0 94.1 94.4 94.7 94.8 95.1 0.79 0.78 0.78 0.81 0.8 0.79 0.81 0.81 0.82 146 178 209 242 300 340 364 446 528
Basic design
1.65 2.6 2.9 3.8 4.5 5.4 8.7 10.2 12.5 440 475 630 720 810 915 1220 1320 1550
2) 2) 2) 2) 2) 2) 2) 2) 2)
M2FA 280 SA M2FA 280 SMA M2FA M2FA M2FA M2FA 315 SA 315 SMA 315 MB 315 LA
1)
380 V 50 Hz
986 93.4 0.79 231
415 V 50 Hz
988 93.6 0.77 219
High-output design
2.9 545
2)
M2FA 280 MB
380 V 50 Hz
736 736 738 738 737 739 739 89.9 91.7 92.7 93.2 93.1 93.3 93.7 0.81 0.79 0.80 0.80 0.80 0.77 0.78 119 161 186 233 275 322 393
415 V 50 Hz
739 739 740 740 740 741 741 91.2 91.8 92.9 93.4 93.3 93.4 93.9 0.77 0.75 0.76 0.76 0.76 0.73 0.74 114 157 179 219 262 311 372
Basic design
1.85 2.2 3.8 4.5 5.4 8.7 10.2 460 500 720 810 915 1220 1320
2) 2) 2) 2) 2) 2) 2)
M2FA 280 SA M2FA 280 SMA M2FA 315 SMA M2FA 315 MB M2FA 315 LA M2FA 355 SA M2FA 355 SB
1)
1)
380 V 50 Hz
738 92.5 0.78 192
415 V 50 Hz
740 92.6 0.74 188
High-output design
2.9 575
2)
M2FA 280 MB
The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page).
1) 2)
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
155
310/103 7.3/6.3 362/130 7.7/7.4 473/171 6.3/7.0 620/199 7.0/6.5 680/240 7.0/8.8
120/80
150/100 M2FA 315 MB 185/125 M2FA 315 LA 200/130 M2FA 355 SA 240/160 M2FA 355 MA
M2FA 315 SMA 3GFA 319 219-A M2FA 315 MB 3GFA 319 329-A 3GFA 319 519-A 3GFA 359 319-A 3GFA 359 519-A
The two bullets in the product code indicate choice of mounting arrangement, voltage and frequency (see ordering information page). Data for other number of poles and bigger frame sizes on request.
156
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
Balancing
052 417 424 Vibration acc. to grade A (IEC 60034-14). Vibration acc. to grade B (IEC 60034-14). Full key balancing. S P P S P P S P P S P P
Coupling
035 Assembly of customer supplied coupling-half. P P P P
Heating elements
450 451 Heating element, 100-120 V. Heating element, 200-240 V. P P P P P P P P
Insulation system
014 Winding insulation class H. R R R R
Mounting arrangements
009 066 IM 2001 foot/ange mounted, from IM 1001 (B35 from B3). Modied for non-standard mounting position (please specify IM xxxx). (must be ordered for all mounting arrangements excluding IM B3 (1001) and B5 (3001). P P P P P P P P
Painting
114 Special paint colour, standard grade. P P P P
Protection
005 072 Protective roof, vertical motor, shaft down. Radial seal at D-end. P P P P P P P P
1)
M = On modication of a stocked motor, or on new manufacture, the number per order may be limited. R = On request S = Included as standard P = New manufacture only
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
157
Code 1)
Variant
355
400
Terminal box
021 180 022 468 Terminal box LHS, seen from D-end (= L prod.code). Terminal box RHS, seen from (reconnection from D). Cable entry LHS (seen from D-end). Cable entry from D-end. P P P P P P P P P P P P P P P P
Testing
145 146 147 148 149 222 153 760 761 762 763
Type test report from a catalogue motor, 400 V 50 Hz. Type test with report for motor from specic delivery batch. Type test with report for motor from specic delivery batch, customer witnessed. Routine test report. Testing according to separate test specication. Torque/speed curve, type test and multi-point load test with report for motor from specic delivery batch. Reduced test for classication society. Vibration level test. Vibration spectrum test. Noise level test. Noise spectrum test.
P P P P R P P P P P P
P P P P R P P P P P P
P P P P R P P P P P P
P P P P R P P P P P P
1)
M = On modication of a stocked motor, or on new manufacture, the number per order may be limited. R = On request S = Included as standard P = New manufacture only
158
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
Foot-mounted; IM B3 (IM 1001), IM B6 (IM 1051), IM B8 (IM 1071), IM V5 (IM 1011) Terminal box top-mounted
M000104
Motor size 280 SA 280 SMA 280 SMA 280 MB 280 MB 315 SA 315 SA 315 SMA 315 SMA 315 MB, MC 315 MB 315 LA, LB 315 LA, LB Motor size 280 SA 280 SMA 280 SMA 280 MB 280 MB 315 SA 315 SA 315 SMA 315 SMA 315 MB, MC 315 MB 315 LA, LB 315 LA, LB
Poles 4-8 2 4-8 2 4-8 2 4-6 2 4-8 2 4-8 2 4-8 Poles 4-8 2 4-8 2 4-8 2 4-6 2 4-8 2 4-8 2 4-8
A 457 457 457 457 457 508 508 508 508 508 508 508 508 F 22 18 22 18 22 20 25 20 25 20 25 20 25
AA 80 80 80 80 80 100 100 100 100 100 100 100 100 G 71 58 71 58 71 62.5 81 62.5 81 62.5 81 62.5 81
AB 545 545 545 545 545 622 622 622 622 622 622 622 622 GA 85 69 85 69 85 74.5 95 74.5 95 74.5 95 74.5 95
AC 555 555 555 555 555 624 624 624 624 624 624 624 624 GD 14 11 14 11 14 12 14 12 14 12 14 12 14
B 368 368 368 419 419 406 406 406 406 457 457 508 508 H 280 280 280 280 280 315 315 315 315 315 315 315 315
BA 100 100 100 100 100 100 100 100 100 100 100 100 100 HC 556 556 556 556 556 625 625 625 625 625 625 625 625
BB 450 501 501 501 501 535 535 540 540 540 540 592 592 HD 730 730 730 730 730 820 820 820 820 820 820 820 848
C 190 190 190 190 190 216 216 216 216 216 216 216 216 K 24 24 24 24 24 28 28 28 28 28 28 28 28
D 80 65 80 65 80 70 90 70 90 70 90 70 90 L 1020 1060 1090 1120 1150 1123 1153 1223 1153 1223 1253 1293 1323
DB M20 M20 M20 M20 M20 M20 M24 M20 M24 M20 M24 M20 M24 LD 415 385 415 385 415 392 422 392 422 392 422 392 422
E 170 140 170 140 170 140 170 140 170 140 170 140 170
EG 40 40 40 40 40 40 48 40 48 40 48 40 48
Tolerances: A,B D F ISO js 14 ISO m6 ISO h9 H 0, -0.5 (M2FA 250) 0, -1.0 (M2FA 280-315) Above table gives the main dimensions in mm. For detailed drawings please see our web-site www.abb.com/motors&drives or contact us. 159
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
Motor size 280 SA 280 SMA 280 SMA 280 MB 280 MB 315 SA 315 SA 315 SMA 315 SMA 315 MB, MC 315 MB 315 LA 315 LA 315 LB Motor size 280 SA 280 SMA 280 SMA 280 MB 280 MB 315 SA 315 SA 315 SMA 315 SMA 315 MB, MC 315 MB 315 LA 315 LA 315 LB
Poles 4-8 2 4-8 2 4-8 2 4-6 2 4-8 2 4-8 2 4-8 2 Poles 4-8 2 4-8 2 4-8 2 4-6 2 4-8 2 4-8 2 4-8 2
AC 551 551 551 551 551 620 620 620 620 620 620 620 620 620 L 1020 1060 1090 1120 1150 1123 1153 1223 1153 1223 1253 1293 1323 1293
D 80 65 80 80 80 70 90 70 90 70 90 70 90 70 LA 25 25 25 25 25 25 25 25 25 25 25 25 25 25
DB M20 M20 M20 M20 M20 M20 M24 M20 M24 M20 M24 M20 M24 M20 LB 850 920 920 980 980 983 983 1083 983 1083 1083 1153 1153 1153
E 170 140 170 140 170 140 170 140 170 140 170 140 170 140 LD 410 380 410 380 410 390 420 390 420 390 420 390 420 390
EG 40 40 40 40 40 40 48 40 48 40 48 40 48 10 M 600 600 600 600 600 740 740 740 740 740 740 740 740 740
F 22 18 22 18 22 20 25 20 25 20 25 20 25 20 N 550 550 550 550 550 680 680 680 680 680 680 680 680 680
G 71 58 71 58 71 62.5 81 62.5 81 62.5 81 62.5 81 62.5 P 660 660 660 660 660 800 800 800 800 800 800 800 800 800
GD 14 11 14 11 14 12 14 12 14 12 14 12 14 12 T 6 6 6 6 6 6 6 6 6 6 6 6 6 6
HB 450 450 450 450 450 505 505 505 505 505 505 505 505 533
Above table gives the main dimensions in mm. For detailed drawings please see our web-site www.abb.com/motors&drives or contact us. ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
M000106
Motor size 355 S_ 355 SA 355 SB,SC 355 SB,SC 355 M_ 355 M_ 355 M_ 355 L_ 355 L_ 355 L_ 355 LK_ 355 LK_ 400 LK_ 400 LK_ Motor size 355 S_ 355 SA 355 SB,SC 355 SB,SC 355 M_ 355 M_ 355 M_ 355 L_ 355 L_ 355 L_ 355 LK_ 355 LK_ 400 LK_ 400 LK_ Tolerances: A,B D F H
Poles 2 4-8 4 6-8 2 4 6-8 2 4 6-8 2 4-8 2 4-8 Poles 2 4-8 4 6-8 2 4 6-8 2 4 6-8 2 4-8 2 4-8
A 610 610 610 610 610 610 610 610 610 610 610 610 686 686 F 20 28 28 28 20 28 28 20 28 28 20 28 25 28
AA 110 110 110 110 110 110 110 110 110 110 110 110 140 140 G 67.5 90 90 90 67.5 90 90 67.5 90 90 67.5 90 81 90
AB 714 714 714 714 714 714 714 714 714 714 714 714 820 820 GA 79.5 106 106 106 79.5 106 106 79.5 106 106 79.5 106 95 106
AC 716 716 716 716 716 716 716 716 716 716 716 716 810 810 GD 12 16 16 16 12 16 16 12 16 16 12 16 14 16
B 500 500 500 500 560 560 560 630 630 630 630 630 710 710 H 355 355 355 355 355 355 355 355 355 355 355 355 400 400
BA 100 100 100 100 100 100 100 100 100 100 100 100 140 140 HC 713 713 713 713 713 713 713 713 713 713 713 713 805 805
BB 584 584 584 584 644 644 644 714 714 714 802 802 935 935 HD 920 892 920 892 920 920 892 920 920 892 920 920 1003 1003
C 254 254 254 254 254 254 254 254 254 254 254 254 280 280 L 1310 1380 1380 1380 1370 1440 1440 1450 1520 1520 1590 1660 1786 1826
D 75 100 100 100 75 100 100 75 100 100 75 100 90 100 LD 397 467 467 467 397 467 467 397 467 467 397 467 438 478
DB M20 M24 M24 M24 M20 M24 M24 M20 M24 M24 M20 M24 M24 M24
E 140 210 210 210 140 210 210 140 210 210 140 210 170 210
M000105
EG 40 48 48 48 40 48 48 40 48 48 40 48 48 48
Above table gives the main dimensions in mm. For detailed drawings please see our web-site www.abb.com/motors&drives or contact us.
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
161
Motor size 355 S_ 355 SA 355 SB,SC 355 SB,SC 355 M_ 355 M_ 355 M_ 355 L_ 355 L_ 355 L_ 355 LK_ 355 LK_ 400 LK_ 400 LK_ Motor size 355 S_ 355 SA 355 SB,SC 355 SB,SC 355 M_ 355 M_ 355 M_ 355 L_ 355 L_ 355 L_ 355 LK_ 355 LK_ 400 LK_ 400 LK_ Tolerances: D F N ISO m6 ISO h9 ISO js6
Poles 2 4-8 4 6-8 2 4 6-8 2 4 6-8 2 4-8 2 4-8 Poles 2 4-8 4 6-8 2 4 6-8 2 4 6-8 2 4-8 2 4-8
AC 716 716 716 716 716 716 716 716 716 716 716 716 810 810 L 1310 1380 1380 1380 1370 1440 1440 1450 1520 1520 1590 1660 1786 1826
DB M20 M24 M24 M24 M20 M24 M24 M20 M24 M24 M20 M24 M24 M24 LB 1170 1170 1170 1170 1230 1230 1230 1310 1310 1310 1450 1450 1616 1616
E 140 210 210 210 140 210 210 140 210 210 140 210 170 210 LD 395 465 465 465 395 465 465 395 465 465 395 465 438 478
EG 40 48 48 48 40 48 48 40 48 48 40 48 48 48 M 740 740 740 740 740 740 740 740 740 740 740 740 940 940
F 20 28 28 28 20 28 28 20 28 28 20 28 25 28 N 680 680 680 680 680 680 680 680 680 680 680 680 880 880
G 67.5 90 90 90 67.5 90 90 67.5 90 90 67.5 90 81 90 P 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000
GA 79.5 106 106 106 79.5 106 106 79.5 106 106 79.5 106 95 106 S 23 23 23 23 23 23 23 23 23 23 23 23 28 28
GD 12 16 16 16 12 16 16 12 16 16 12 16 14 16 T 6 6 6 6 6 6 6 6 6 6 6 6 6 6
HB 565 537 565 537 565 565 537 565 565 537 565 565 565 565
Above table gives the main dimensions in mm. For detailed drawings please see our web-site www.abb.com/motors&drives or contact us.
162
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
M000107
Motor size
A1
B1
H1
Top-mounted terminal box: 122/4 142/4 162/4, 162/9 + Adapter 280 315 - 355 315 - 400 455 536 787 280 349 410 177 197 226
Side-mounted terminal box: 122/5 142/6 162/7, 162/10 280 315 - 355 315 - 400 383 426 508 280 347 412 180 201 226 Further details on terminal boxes on earlier pages. For motor dimensions please see dimension drawings on earlier pages.
Rating plate
The rating plate is in table form giving values for speed, current and power factor for six voltages.
M000109
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
163
Prole-pressed sheet steel Blue, Munsell 8B 4.5/3.25 / NCS 4822-B05G / RAL 5014 Two-pack epoxy paint, thickness 70 m Cast iron GG 20/GRS 200 Blue, Munsell 8B 4.5/3.25 / NCS 4822-B05G / RAL 5014 Two-pack epoxy paint, thickness 70 m 6316/C4 6319/C3 6316/C4 6316/C3 6316/C4 6319/C4 6316/C4 6316/C3 on request 6322/C3 on request 6319/C3 on request 6322/C3 on request 6319/C3
Bearings
As standard, locked at D-end V-ring as standard, radial seal on request Regreasing nipples, M10x1 Grease for bearing temperatures -30C to +120C Stainless steel, with individual serial number On request Cast iron GG 15 / GRS 150 Cast iron GG 15 / GRS 150 Steel 5G, coated with zinc and yellow chromated 2 x M63 2 x 50/80 2 x 80 2 x M63 2 x 60 2 x 60/80 6 terminals for connection with cable lugs (not included) Siluminium Sheet steel Blue, Munsell 8B 4.5/3.25 / NCS 4822-B05G / RAL 5014 Two-pack epoxypolyester paint, thickness 80 m Copper Insulation class F; temperature rise class B unless otherwise stated. PTC-thermistors 150C, 3 in series, as standard Pressure die-cast aluminium Half key balancing as standard Closed key way
Connections
Material Material Paint colour shade Paint thickness Material Insulation Winding protection
Stator winding
Rotor winding Balancing method Key way Heating elements Drain holes Enclosure Cooling method
Material
On request
50 W
2x50 W
2x65 W
2x65 W
164
ABB LV Motors / Low Voltage General Purpose Motors / Open drip proof EN 12-2006
234
Motors & Drives > Motors >> Low Voltage Motors >>> General purpose motors Aluminum motors Steel motors Cast iron motors Open drip proof motors Global motors Brake motors Single phase motors >>> Process performance motors >>> Motors for hazardous areas >>> Marine motors >>> Other applications NEMA motors Permanent magnet motors Smoke venting motors Roller table motors Water cooled motors Fan application motors Roller table motors > Generators