TECHNICAL GUIDE
SERIES 40
SINGLE PACKAGE ROOFTOP UNITS
V32, V33 & V34 (R-410A)
FEATURING:
ISO 9001
Certified Quality
Management System
355278-JTG-D-0110
TABLE OF CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURING: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT CONTROL BOARD FEATURES: . . . . . . . . . . . . . . 1
OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . 5
INSTALLATION FEATURES . . . . . . . . . . . . . . . . . . . . . . 6
CONSTRUCTION FEATURES . . . . . . . . . . . . . . . . . . . . 7
LIST OF FEATURES AND BENEFITS . . . . . . . . . . . . . . . 8
STANDARD FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . 8
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . 8
SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . 11
SELECT UNIT: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SELECT FAN SPEED AND HORSEPOWER
REQUIREMENTS OF SUPPLY AIR FAN . . . . . . . . . . . 11
SIZE OVERCURRENT PROTECTION DEVICE AND
DETERMINE CIRCUIT AMPACITY . . . . . . . . . . . . . . . . 11
STEAM HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . 25
PHYSICAL DATA STEAM COIL - 1 ROW . . . . . . . . . . . 25
PIPING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . 25
ECONOMIZER (OPTIONAL) . . . . . . . . . . . . . . . . . . . . . .
RELIEF SYSTEM (OPTIONAL) . . . . . . . . . . . . . . . . . . . .
BAROMETRIC RELIEF (OPTIONAL) . . . . . . . . . . . . . . .
EXHAUST AIR FANS (OPTIONAL) . . . . . . . . . . . . . . . .
76
76
76
76
HEATING SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
GAS-FIRED HEATING SECTION (OPTIONAL) . . . . . . .
ELECTRIC HEATING SECTION . . . . . . . . . . . . . . . . . . .
HOT WATER HEATING COIL . . . . . . . . . . . . . . . . . . . . .
STEAM HEATING COIL . . . . . . . . . . . . . . . . . . . . . . . . .
76
77
77
77
REFRIGERATION SYSTEM . . . . . . . . . . . . . . . . . . . . . 77
EVAPORATOR COILS . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSER COILS . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSER FANS AND MOTORS . . . . . . . . . . . . . . .
REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . .
HOT GAS BYPASS (OPTIONAL ON CV; STANDARD
ON VAV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
77
78
78
78
78
78
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR CONTROL . . . . . . . . . . . . . . . . . . . . . .
FAN CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EQUIPMENT CONTROL FEATURES . . . . . . . . . . . . . .
78
78
79
79
OPTIONAL CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . 81
JOHNSON COMMERCIAL COMFORT SYSTEM
(CCS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
AVAILABLE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . 81
PARTIAL PERIMETER ROOF CURBS . . . . . . . . . . . . . . 81
BURGLAR BARS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
FIELD INSTALLED BAROMETRIC RELIEF . . . . . . . . . . 81
PROGRAMMABLE THERMOSTAT, WITH OR WITHOUT
REMOTE SENSOR (REQUIRED FOR CONSTANT
VOLUME UNITS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
REMOTE WALL MOUNTED TEMPERATURE
SENSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
DIRTY FILTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . 81
PROPANE CONVERSION KITS . . . . . . . . . . . . . . . . . . . 81
HIGH ALTITUDE CONVERSION KITS . . . . . . . . . . . . . . 81
ENERGY RECOVERY VENTILATORS . . . . . . . . . . . . . 81
355278-JTG-D-0110
LIST OF FIGURES
Fig.#
Pg.#
Fig.#
Pg.#
21 ALTITUDE/TEMPERATURE CONVERSION
FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
27 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 64
28 COMPONENT LOCATION . . . . . . . . . . . . . . . . . . . . 66
355278-JTG-D-0110
LIST OF TABLES
Tbl.#
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Pg.#
Tbl.#
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Pg.#
355278-JTG-D-0110
SERIES 40
OVERVIEW
Introducing the Johnson Controls 25, 30, & 40 ton Series 40
rooftop line - units designed to provide peak performance and
value both today and for years to come. When we asked our
customers what they wanted in a new rooftop line, we were
careful to listen to both the needs of today and tomorrow. So,
you'll find that Series 40 units not only help you solve today's
problems, but can handle tomorrow's difficulties as well:
Industry Leading Efficiency - The Series 40's (10.5 EER) rating makes it the most frugal energy consumer in its class.
When it comes to lower operating costs, they simply outperforms the competition.
Double Wall Construction - Series 40 units come double
walled as standard. The galvanized sheet metal liner provides the best protection against microbial growth, helping
both the unit and the indoor air stay fresh and clean. And, the
rigid sheet metal inner liner keeps the insulation completely
out of the air stream, eliminating concerns about fiberglass
particles.
Drain Pan Whisks Away Condensate - Condensate is frequently the source of microbial contamination. Competitive
drain pans often are insufficiently sloped to properly drain all
of the condensate, causing drain pan corrosion and bacterial
growth to begin almost immediately. The Johnson Controls
design is sloped at the 1/4 per foot recommended by the
ASHRAE 62.1-2004 ventilation draft standard, with an extra
large drain connection capable of removing up to three gallons of condensate per minute. It is available in either powder
coat painted steel or stainless steel for long life.
355278-JTG-D-0110
INSTALLATION FEATURES
Enhanced Filtration Options - Series 40 units give designers
the flexibility to meet various IAQ requirements with a full
range of rigid and throwaway filters at different efficiency levels.
Vibration Isolation - The Series 40's neoprene mounts are
typically sufficient for most applications but when sound and
vibration transmission are a major concern, Johnson Controls
offers 1" and 2" isolation springs for even greater protection
from supply air fan noise and vibration.
Corrosion Resistant Coils- Many industrial and seacoast
applications require enhanced protection from corrosive environments.
Optional TechniCoated Coated Condenser and Evaporator Coils - Many industrial and seacoast applications
require enhanced protection from corrosive environments. The special dipped phenolic coating process
provides a high level of protection for the exposed condenser coil.
Optional Copper-Copper Condenser and Evaporator
Coils - For corrosion resistance.
Variety of Exhaust Air Options - Johnson Controls Series 40
offers a wide variety of exhaust air options, including barometric relief, non-modulating power exhaust, and modulating
power exhaust. And, because Series 40 units use forwardcurved blowers for power exhaust fans, they can exhaust up
to 100% of the nominal supply air at much greater static pressure loads than competitive units. Not available on end
return.
NOTE: In most applications, the supply fan will keep the
return at negative pressure. A barometric relief will
function better when ducted to building space, not
the return.
355278-JTG-D-0110
CONSTRUCTION FEATURES
Johnson Controls Series 40 rooftop line is built for the long
haul, with high end features and construction offered at a
competitive price. Series 40 units are manufactured at an ISO
9001 registered facility, and each rooftop is completely computer-run tested prior to shipment. Some of the valuable construction features of the Series 40 which are not found on
competitive units include:
Double Wall Construction - Each unit has both an exterior
and an interior wall, which make for a more rigid design with
panels and doors that are solid, not flimsy. The unit features a
fully framed construction for even greater stability.
Powder Paint - Industry leading 1000 salt spray hour paint
keeps the unit in great condition for years to come.
Low Profile - Units stand only 64 above their curb, minimizing potential aesthetic conflicts.
355278-JTG-D-0110
10.5 EER
R-410A Refrigerant
Double wall construction
Major components have hinged and latched access
doors
Industrial duty scroll compressors
Sturdy framed construction
Sloped stainless steel or powder coated drain pan
Intertwined evaporator coil
Angled condenser coils for superior protection
Single power point connection
Through-the-curb or through-the-base utility connections
Retractable outside air hoods
Powder paint tested to 1000 salt spray hours
Mechanical cooling from 40 F to 125 F
1-1/2 insulation
Sloped unit roof with drip lip
High and low refrigerant pressure protection
Polyurethane sleeves to protect small diameter tubing
Steel framing around blowers with deflection springs or
rubber isolators for low vibration
Fully factory packaged and run-tested
10 year gas heat exchanger warranty
One year compressor warranty
One year warranty on all parts
3
2
3
6
4
7
T = C, G, J
U = D, E, H
I = D, F, I
J = D, F, J
7 = C, E, J
8 = C, F, H
9 = D, G, H
2 = B, E, J
3 = B, F, H
4 = C, E, H
6 = C, E, I
Z = B, E, I
Y = B, E, H
X = D, F, H
W = D, E, J
10
FILTERS
A = STAND.
B = 65%
C = 95%
D = 2" HI-EFF
A
11
I = 1,3,5,8
D = 2,4,5,7
A = 1,3,5,7
B = 2,3,5,7
C = 1,4,5,7
S = 1,4,9,7
T = 2,4,9,7
L = 2,4,5,8
Q = 1,3,9,7
R = 2,3,9,7
K = 1,4,5,8
7 = 1,4,9,8
9 = Non-Std
Config
2 = 2,4,9,8
Y = 1,3,9,8
Z = 2,3,9,8
REFRIGERATION
HEAT CAPACITY
0 (ZERO) NO HEAT
1 = 1 ROW
2 = 2 ROW
1 = 1 ROW
2 = 15 HP STD
3 = 20 HP STD
1 = 10 HP STD
(See note 4)
5 = STANDARD
9 = STD W/TECHNICOAT
Evaporator Coil
Piping
3 = 267 MBH
5 = 533 MBH
8 = 800 MBH (40T ONLY)
4 = 40 KW
8 = 80 KW
1 = 108 KW (1)
12
7 = YES
8 = NO
NOTES:
Condenser Coil
1 = STANDARD
2 = TECHNICOAT
Blower Mount
a = CV
b = VAV (VFD-FACTORY INSTALLED)
c = BYPASS FACTORY VFD
d = VAV (VFD-CUSTOMER) (3)
Air Volume
V = D, E, I
P = B, G, J
Q = C, F, I
R = C, F, J
S = C, G, I
E = A, E, H
F = A, E, I
G = A, E, J
H = A, F, H
K = D, G, I
N = B, F, J
O = B, G, I
D = A, G, J
M = B, F, I
B = A, G, I
C = A, F, J
L = D, G, J
7 = 380/415-50
(30T/40T)
2 = 208/230-60
3 = 380-60
4 = 460-60
5 = 575-60
VOLTAGE
A = A, F, I
h = Neoprene
X = STEAM COIL
J = 2,3,5,8
HEAT EXCHANGER
E = ELECTRIC HEAT
C = COOLING ONLY
W = HOT WATER COIL
N = NATURAL GAS
S = NATURAL GAS, SS HEAT EXCHANGER
HEAT SOURCE
D = 3,2
E = 3,4
F = 3,5
4 - REAR SUPPLY
5 - FRONT SUPPLY
2 - BOTTOM SUPPLY
3 - END RETURN (5)
B = 1,4
C = 1,5
1 - BOTTOM RETURN
A = 1,2
CONFIGURATION
2 = 25 TON
3 = 30 TON
4 = 40 TON
BASIC UNIT
GENERATION
S = Underfloor R-410A
PACKAGE
D
1
CONTROL
14
ECONOMIZER
110V OUTLET
S = CCS-VAV CONTROL
110V OUTLET
N = CCS CONTROL
J = STANDARD CONTROL,
DISC, NO 110V OUTLET
H = STANDARD CONTROL
E = SYNTHESYS CONTROL,
D = SYNTHESYS CONTROL
13
L = 2, 7
M = 2, 8
N = NONE
O = 1, 9
P = 1, 0
Q = 2, 9
R = 2, 0
C = 1, 4
D = 1, 5
E = 1, 6
F = 1, 7
G = 1, 8
H = 2, 3
I = 2, 4
Z = A, 0
2 = 8,000 CFM ERV
Y = A, 9
U = A, 5
V = A, 6
W = A, 7
X = A, 8
S = A, 3
T = A, 4
9 = 5 HP (25T Only)
6 = 7.5 HP HI-EFF
7 = 10 HP HI-EFF
8 = 15 HP HI-EFF (Except 25 Ton)
5 = 15 HP (Except 25 Ton)
Motor
Power Exhaust
J = 2, 5
K = 2, 6
A = BARO
B = 1, 3
E = NONE
F = DUAL ENTH Std type
G = SINGLE ENTH Std type
in these options
ADDITIONAL
CONFIGURATION
OPTIONS
355278-JTG-D-0110
NOMENCLATURE
355278-JTG-D-0110
UNIT SIZE
267 MBH CAPACITY STEPS (CV/VAV)
533 MBH CAPACITY STEPS (CV/VAV)
800 MBH CAPACITY STEPS (CV/VAV)
267 MBH MODULATING CAPACITY STEPS (CV ONLY)
533 MBH MODULATING CAPACITY STEPS (CV ONLY)
800 MBH MODULATING CAPACITY STEPS (CV ONLY)
SIZE (INCHES)
CAPACITY
25 TON
30 TON
40 TON
10.5 / 12.3
10.5 / 11.0
10.5 / 11.2
4 x 7 Ton
Scroll
25%, 50%, 75%, 100%
4 x 8.6 Ton
Scroll
25%, 50%, 75%, 100%
1 / FC
22 x 20
10 - 25
6,000 - 15,000
0.2" - 4.0
1 / FC
25 x 22
10 - 25
8,000 - 18,000
0.2" - 4.0"
2/FC
7.5 - 15
4,000 - 15,000
2/FC
7.5 - 15
4,000 - 18,000
26.0
4 / 16
30.4
4 / 16
78
2 /16
104
2 /16
4 / 24
7,200
1.5
4 / 30
9,600
1.5
40 - 108
1
2/1
3 / 1*
40 - 108
1
2/1
3 / 1*
30 TON
1/1
2/1
6/1
12 / 2
-
40 TON
1/1
2/1
3 / 1*
6/1
12 / 2
17 / 3
22.5" X 65
30 Ton
22.5" X 65
40 Ton
COMPRESSOR DATA
4 x 5.7Ton
Scroll
25%, 50%, 75%, 100%
INDOOR FAN AND DRIVE
1 / FC
22 x20
7.5 - 20
6,000 - 12,500
0.2 - 4.0
EXHAUST FAN
1/FC
5 - 10
3,000 - 9,000
EVAPORATOR COIL
26.0
3 / 16
CONDENSER COIL
65
2/16
CONDENSER FANS
4 / 24
6,800
1.0
ELECTRIC HEAT
40 - 108
1
2/1
3 / 1*
NATURAL GAS HEAT
25 TON
1/1
2/1
6/1
12 / 2
HOT WATER COIL
22.5 x 65
25 Ton
STEAM COIL
SIZE (INCHES)
TYPE
NUMBER / SIZE
FACE AREA (SQ. FT.)
NUMBER / SIZE
FACE AREA (SQ. FT.)
NUMBER / SIZE
FACE AREA (SQ. FT.)
NUMBER / SIZE
FACE AREA (SQ. FT.)
*
10
21" X 65"
Steam Coil
FILTERS 2" TA
4 / 16 x 25 & 6 / 20 x 25
4 / 16 x 25 & 6 / 20 x 25
30.4
30.4
FILTERS 2" PLEATED, 30%
4 / 16 x 25 & 6 / 20 x 25
4 / 16 x 25 & 6 / 20 x 25
30.4
30.4
FILTERS 65% RIGID W/ 2 TA PREFILTERS
4 / 16 x 25 & 6 / 20 x 25
4 /16 x 25 & 6 / 20 x 25
30.4
30.4
FILTERS 95% RIGID W/ 2 TA PREFILTERS
4 ea. 16 x 25 / 6 ea. 20 x 25
4 ea. 16 x 25 / 6 ea. 20 x 25
30.4
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
4 ea. 16 x 25 / 6 ea. 20 x 25
30.4
Unit Control Board with 3 heating outputs only, all other Unit Control Boards 2 / 1.
355278-JTG-D-0110
MODEL
25
25
30
30
40
40
wo/HGBP
w/HGBP
wo/HGBP
w/HGBP
wo/HGBP
w/HGBP
CHARGE
SYSTEM #1
12lb 6oz
12lb 14oz
16lb
16lb 8oz
17lb 10oz
18lb 2oz
SYSTEM #2
12lb 9oz
13lb 1oz
16lb 8oz
17lb
17lb 10oz
18lb 2oz
SELECTION PROCEDURE
c.
GIVEN:
Required Cooling Capacity
460,000 Btuh
390,000 Btuh
320,000 Btuh
83 F DB/ 67 F WB
95 F
1.25 IWG
460-3-60
SYSTEM #4
10lb 14oz
11lb 6oz
18lb 4oz
18lb 12oz
19lb 13oz
20lb 5oz
13,000 CFM
SYSTEM #3
10lb 9oz
11lb 1oz
14lb
14lb 8oz
19lb 13oz
20lb 5oz
1.25 IWG
Economizer Required
2 Throw Away Filters
Constant Volume
b.
SELECT UNIT:
2.0 IWG
1.
BHP = 11.8
NOTE: Either Class I or Class II blower could be used.
a.
b.
c.
d.
Read 493 MBH total capacity and 403 MBH sensible capacity.
c.
b.
c.
d.
e.
f.
b.
Find output which exceeds 320,000 Btuh requirement. The N5 option gives 426 MBH output.
11
355278-JTG-D-0110
GAS HEAT
OPTION
AVAILABLE ON
MODELS
1ST STAGE
TOTAL
N3
N5
N8
V32/V33/V34
V32/V33/V34
V34 ONLY
267
267
2674
267
533
800
1.
OUTPUT
CAPACITY
(MBH)2
213
426
638
1ST STAGE
TOTAL
247
247
247
247
495
742
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
Blower motor heat not included.
Based on a heat content of 1075 Btu/Ft.3
2.
3.
4.
Unit Control Board with 3 heating outputs only. For all other Unit Control Boards the 1st Stage is 533 MBH.
25
30
40
MODULES
1
5-35
5-35
5-30
2
25-55
20-50
10-45
3
25-55
TON
25
30
40
MODULES
1
5,644
5,644
6,584
2
7,183
7,901
8,779
3
13,169
AVAILABLE ON
MODELS
D32
D52
D82
V32/V33/V34
V32/V33/V34
V34 ONLY
1.
2.
12
STEPS
6
12
17
OUTPUT CAPACITY
(MBH)1
213
426
638
355278-JTG-D-0110
D3
(Turn down ratio
3.8 to 1)
D5
(Turn down ratio
7.7 to 1)
D8
(Turn down ratio
11.5 to 1)
% OF TOTAL OUTPUT
26%
40%
62%
76%
86%
100%
13%
20%
31%
38%
43%
50%
61%
68%
73%
80%
93%
100%
9%
13%
21%
25%
29%
33%
41%
45%
49%
53%
62%
67%
73%
82%
87%
95%
100%
1.
2.
3.
4.
AVAILABLE ON
MODELS
RATED
VOLTAGE
NOMINAL KW
NOMINAL
MBH1
STAGE 2
KW
MBH
KW
MBH
E4
V32, V33,
V34
2403/4804/
575
40
137
40
137
E8
V32, V33,
V34
2402/4803/
575
80
273
40
137
40
137
E1
V32, V33,
V34 (460 &
575 volt only)
4803/575
108
369
72
246
36
123
13
355278-JTG-D-0110
For all hot water coils the entering water temperature should
not exceed 200F.
10
20
30
40
1.
10
0.9
20
3.0
30
6.0
40
10.0
6000
0.07
0.14
8000
0.11
0.23
10000
0.16
0.33
15000
0.32
0.65
CFM
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
Based on 60F entering air temperature, 2.00 maximum pressure drop across the hot water coil.
PIPING CONNECTIONS
The hot water piping must enter the unit through the floor of
the heat section compartment. The access doors to the compartment are gasketed so the compartment can be sealed.
However, as added protection for water leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic (see the following illustration for approximate
location of the compartment and piping connections.
14
355278-JTG-D-0110
GPM
CONDENSING
SECTION
HOT WATER
COIL
26"
INLET (2")
OUTLET (2")
10
OUTSIDE OF
BASE RAIL
15.8"
11.88"
8.38"
2.25"
2.55"
88.75"
HEAT SECTION
COMPARTMENT
FIGURE 1 -
20
CL
8000
0.11
0.23
11000
0.19
0.39
14000
0.29
0.58
20000
0.52
1.06
40
1.
CFM
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
Based on 60F entering air temperature, 2.00 maximum pressure drop across the hot water coil.
15
355278-JTG-D-0110
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
CAPACITY (MBH)
1 8 0 .0
1 7 0 .0
140
160
180
200
1 6 0 .0
1 5 0 .0
F
F
F
F
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
9 0 .0
8 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 2 -
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
2 3 0 .0
2 2 0 .0
CAPACITY (MBH)
2 1 0 .0
2 0 0 .0
1 9 0 .0
140
160
180
200
1 8 0 .0
1 7 0 .0
F
F
F
F
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
9 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 3 -
16
355278-JTG-D-0110
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
2 3 0 .0
CAPACITY (MBH)
2 2 0 .0
2 1 0 .0
140
160
180
200
2 0 0 .0
1 9 0 .0
1 8 0 .0
F
F
F
F
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 4 -
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
CAPACITY (MBH)
2 3 0 .0
2 2 0 .0
140
160
180
200
2 1 0 .0
2 0 0 .0
1 9 0 .0
F
F
F
F
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 5 -
17
355278-JTG-D-0110
2 5 0 .0
2 4 0 .0
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
CAPACITY (MBH)
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
140
160
180
200
F
F
F
F
140
160
180
200
F
F
F
F
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
9 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 6 -
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
CAPACITY (MBH)
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 7 -
18
355278-JTG-D-0110
3 2 0 .0
3 1 0 .0
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
CAPACITY (MBH)
2 4 0 .0
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
140
160
180
200
F
F
F
F
140
160
180
200
F
F
F
F
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 8 -
3 4 0 .0
3 3 0 .0
3 2 0 .0
3 1 0 .0
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
CAPACITY (MBH)
2 6 0 .0
2 5 0 .0
2 4 0 .0
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 9 -
19
355278-JTG-D-0110
CFM
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
60
80
1.
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Based on 60F entering air temperature, 2.00 maximum pressure drop across the hot water coil.
20
40
60
80
PRESSURE
DROP
0.9
3.0
6.0
10.0
6000
8000
10000
15000
0.07
0.11
0.16
0.32
0.14
0.23
0.33
0.65
20
40
20
CFM
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
40
60
80
1.
CFM
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
0.11
0.23
11000
0.19
0.39
14000
0.29
0.58
20000
0.52
1.06
20
0.9
40
3.0
60
6.0
80
10.0
355278-JTG-D-0110
4 8 0 .0
4 6 0 .0
4 4 0 .0
4 2 0 .0
4 0 0 .0
3 8 0 .0
CAPACITY (MBH)
3 6 0 .0
3 4 0 .0
3 2 0 .0
3 0 0 .0
140
160
180
200
F
F
F
F
140
160
180
200
F
F
F
F
2 8 0 .0
2 6 0 .0
2 4 0 .0
2 2 0 .0
2 0 0 .0
1 8 0 .0
1 6 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
5 8 0 .0
5 6 0 .0
5 4 0 .0
5 2 0 .0
5 0 0 .0
4 8 0 .0
4 6 0 .0
CAPACITY (MBH)
4 4 0 .0
4 2 0 .0
4 0 0 .0
3 8 0 .0
3 6 0 .0
3 4 0 .0
3 2 0 .0
3 0 0 .0
2 8 0 .0
2 6 0 .0
2 4 0 .0
2 2 0 .0
2 0 0 .0
1 8 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
21
355278-JTG-D-0110
6 1 0 .0
5 9 0 .0
5 7 0 .0
5 5 0 .0
5 3 0 .0
5 1 0 .0
4 9 0 .0
CAPACITY (MBH)
4 7 0 .0
4 5 0 .0
4 3 0 .0
4 1 0 .0
3 9 0 .0
3 7 0 .0
140
160
180
200
F
F
F
F
140
160
180
200
F
F
F
F
3 5 0 .0
3 3 0 .0
3 1 0 .0
2 9 0 .0
2 7 0 .0
2 5 0 .0
2 3 0 .0
2 1 0 .0
1 9 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
CAPACITY (MBH)
4 8 0 .0
4 6 0 .0
4 4 0 .0
4 2 0 .0
4 0 0 .0
3 8 0 .0
3 6 0 .0
3 4 0 .0
3 2 0 .0
3 0 0 .0
2 8 0 .0
2 6 0 .0
2 4 0 .0
2 2 0 .0
2 0 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
22
355278-JTG-D-0110
5 3 0 .0
5 1 0 .0
4 9 0 .0
4 7 0 .0
4 5 0 .0
4 3 0 .0
CAPACITY (MBH)
4 1 0 .0
3 9 0 .0
3 7 0 .0
3 5 0 .0
140
160
180
200
F
F
F
F
140
160
180
200
F
F
F
F
3 3 0 .0
3 1 0 .0
2 9 0 .0
2 7 0 .0
2 5 0 .0
2 3 0 .0
2 1 0 .0
1 9 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
4 9 0 .0
4 7 0 .0
4 5 0 .0
4 3 0 .0
4 1 0 .0
3 9 0 .0
3 7 0 .0
3 5 0 .0
3 3 0 .0
3 1 0 .0
2 9 0 .0
2 7 0 .0
2 5 0 .0
2 3 0 .0
2 1 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
23
355278-JTG-D-0110
7 0 0 .0
6 8 0 .0
6 6 0 .0
6 4 0 .0
6 2 0 .0
6 0 0 .0
5 8 0 .0
5 6 0 .0
5 4 0 .0
CAPACITY (MBH)
5 2 0 .0
5 0 0 .0
4 8 0 .0
4 6 0 .0
4 4 0 .0
140
160
180
200
F
F
F
F
140
160
180
200
F
F
F
F
4 2 0 .0
4 0 0 .0
3 8 0 .0
3 6 0 .0
3 4 0 .0
3 2 0 .0
3 0 0 .0
2 8 0 .0
2 6 0 .0
2 4 0 .0
2 2 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
7 3 0 .0
7 1 0 .0
6 9 0 .0
6 7 0 .0
6 5 0 .0
6 3 0 .0
6 1 0 .0
5 9 0 .0
5 7 0 .0
CAPACITY (MBH)
5 5 0 .0
5 3 0 .0
5 1 0 .0
4 9 0 .0
4 7 0 .0
4 5 0 .0
4 3 0 .0
4 1 0 .0
3 9 0 .0
3 7 0 .0
3 5 0 .0
3 3 0 .0
3 1 0 .0
2 9 0 .0
2 7 0 .0
2 5 0 .0
2 3 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
24
355278-JTG-D-0110
STEAM HEATING
CFM
8000
11000
14000
17000
20000
1.
8000
0.18
11000
0.31
14000
0.48
17000
0.67
20000
0.88
PIPING CONNECTIONS
The steam piping must enter the unit through the floor of the
heat section compartment. The access doors to the compartment are gasketed to the compartment can be sealed. However, as added protection for condensate leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic. The following figure illustrates the approximate location of the compartment and piping connections.
T O P V IE W
C O N D E N S IN G
S E C T IO N
S T E A M
C O IL
2 6 "
O U T L E T (1 1 /2 ")
1 5 .8 "
IN L E T (2 ")
8 "
2 .5 5 "
9 "
H E A T S E C T IO N
C O M P A R T M E N T
*Hot water, steam coil or electric heat not available for front or
rear supply.
O U T S ID E O F
B A S E R A IL
8 .3 8 "
8 8 .7 5 "
CL
6000
0.11
8000
0.18
10000
0.26
12000
0.36
15000
0.54
25
355278-JTG-D-0110
350
340
330
320
310
300
CAPACITY (MBH)
290
280
2 psi
6 psi
10 psi
15 psi
270
260
250
240
230
220
210
200
190
180
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
CAPACITY (MBH)
330
320
310
2 psi
6 psi
10 psi
15 psi
300
290
280
270
260
250
240
230
220
210
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
26
355278-JTG-D-0110
25
Ton
30
Ton
40
Ton
Motor Pulley
Blower Pulley
Belts
Blower
RPM
Range
HP
Frame
Size
Motor Eff
(Std.
Motor)
Motor
Eff (Hi
Eff opt)
Pitch Dia
(Inches)
Bore
(Inches)
Pitch Dia
(Inches)
Bore
(Inches)
Designation
Qty
758
852
976
852
976
1069
852
976
1069
5
7.5
10
7.5
10
15
7.5
10
15
213T
215T
215T
213T
215T
254T
184T
215T
254T
87.5
88.5
89.5
84
86.5
85.7
84
86.5
85.7
89.5
91.7
91
86.5
89.5
89.5
86.5
89.5
89.5
4.9
5.5
6.3
5.5
6.3
6.9
5.5
6.3
6.9
1-3/8
1-3/8
1-5/8
1-3/8
1-3/8
1-3/8
1-3/8
1-3/8
1-3/8
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
2-3/16
2-3/16
2-3/16
1-11/16
1-11/16
1-11/16
1-11/16
1-11/16
1-11/16
BX63
BX63
BX63
B65
B65
B65
B65
B65
B65
2
2
2
2
2
2
2
2
2
25 Ton
30 Ton
40 Ton
Blower
RPM
Range
567
692
793
894
617
743
856
907
617
652
728
780
Motor Pulley
Blower Pulley
Belts
HP
Frame
Size
Motor
Efficiency
(Std. Motor)
Motor
Efficiency
(Ultra Hi
Eff Opt)
Pitch Dia
(Inches)
Bore
(Inches)
Pitch Dia
(Inches)
Bore
(Inches)
Designation
Qty
7.5
10
15
20
10
15
20
25
10
15
20
25
213T
215T
254T
256T
215T
254T
256T
284T
215T
254T
256T
284T
88.5
89.5
91
91
89.5
91
91
91.7
89.5
91
91
91.7
91.7
91
91.7
93
91
91.7
93
93.6
91
91.7
93
93.6
4.5
5.5
6.3
7.1
4.9
5.9
6.7
7.1
4.9
5.1
5.7
6.1
1-3/8
1-3/8
1-5/8
1-5/8
1-3/8
1-5/8
1-5/8
1-7/8
1-3/8
1-5/8
1-5/8
1-7/8
13.9
13.9
13.9
13.9
13.9
13.9
13.7
13.7
13.9
13.7
13.7
13.7
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-7/16
2-7/16
2-7/16
2-7/16
BX56
BX56
BX56
BX56
BX56
BX56
5VX610
5VX610
BX67
5VX710
5VX710
5VX710
2
2
2
2
2
2
2
2
2
2
2
2
27
355278-JTG-D-0110
Failure to properly adjust the total system air quantity can result in extensive blower damage.
28
355278-JTG-D-0110
5.3
50
93.2
5.5
52
88.1
5.9
58
91.8
6.5
64
96.6
5.7
(Std.)
5.9
54
91.0
6.1
60
94.5
6.7
66
56
94.0
6.3
62
97.3
6.9
68
(Std.)
7.1
70
100.0
112.2
5.5
52
103.4
6.1
58
97.0
116.3
5.7
54
106.8
6.3
60
100.0
120.4
124.5
-
5.9
6.1
-
56
58
-
110.2
113.6
116.9
120.3
123.7
6.5
6.7
6.9
7.1
7.3
62
64
66
68
70
103.0
106.0
112.0
120.9
129.9
6.5
64
100.0
(Std.)
6.7
6.9
7.1
7.5
8.1
8.7
66
105.5
7.5
74
68
70
74
80
86
113.7
121.9
-
8.1
8.7
-
80
86
-
4.9
48
89.5
5.1
50
90.2
5.5
54
50
93.0
5.3
52
93.4
5.7
56
5.5
(Std.)
5.7
5.9
6.1
6.3
6.5
6.7
6.9
54
96.7
100.0
58
60
62
64
66
68
103.3
106.6
109.8
113.1
116.4
119.7
5.9
(Std.)
6.1
6.3
6.5
6.7
6.9
7.1
7.5
58
56
104.1
5.1
48
100.0
108.2
5.3
50
103.9
(Std.)
5.1
5.3
52
96.5
112.2
5.5
52
107.8
5.5
54
100.0
116.3
-
5.7
-
54
-
111.7
115.6
119.5
123.4
127.4
-
5.7
5.9
6.1
6.3
6.5
-
56
58
60
62
64
66
103.5
107.0
110.5
114.0
117.5
121.1
60
62
64
66
68
70
74
29
355278-JTG-D-0110
%RPM
& CFM
Reqd
PD
Browning
2b5v_ _
%RPM
& CFM
Reqd
PD
Browning
2b5v_ _
%RPM
& CFM
Reqd PD
Browning
2b5v_ _
100
104
109
113
117
122
4.9 (Std.)
5.1
5.3
5.5
5.7
5.9
46
48
50
52
54
56
92
96
100
104
108
112
5.1
5.3
5.5 (Std.)
5.7
5.9
6.1
48
50
52
54
56
58
93
97
100
103
107
110
5.9
6.1
6.3 (Std.)
6.5
6.7
6.9
56
58
60
62
64
66
30
355278-JTG-D-0110
Air on Evaporator
Coil
CFM
7500
8750
10000
11250
12500
7500
8750
10000
11250
12500
7500
8750
10000
11250
12500
1.
2.
WB
(F)
75F
Total Total2
Cap.1 Input
(MBH) (kW)
85F
Total Total2
Cap.1 Input
(MBH) (kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
365.8
342.4
311.7
300.0
376.3
352.0
320.6
308.6
386.7
361.7
329.5
317.2
400.1
374.2
340.9
328.2
413.5
386.8
352.3
339.1
21.0
20.5
20.4
19.7
21.2
20.7
20.6
19.9
21.4
20.9
20.8
20.1
21.5
21.0
20.9
20.2
21.6
21.1
21.0
20.3
202.1
248.8
302.2
300.0
214.5
263.3
315.9
308.6
226.9
277.8
329.5
317.2
248.4
304.4
340.9
328.2
269.8
331.0
352.3
339.1
183.9
230.6
284.0
299.5
193.8
242.6
298.4
308.4
203.7
254.6
312.8
317.2
223.6
279.6
332.5
328.2
243.4
304.6
352.3
339.1
147.5
194.2
247.6
263.1
152.4
201.2
257.0
273.2
157.3
208.2
266.4
283.2
173.9
229.9
294.0
298.0
190.5
251.7
321.6
312.7
129.3
176.1
229.4
244.9
131.7
180.5
236.3
252.5
134.1
185.0
243.2
260.0
149.1
205.1
269.2
273.1
164.1
225.3
295.2
286.2
157.9
211.2
226.7
159.8
215.6
231.8
161.8
220.0
236.8
180.3
244.4
248.3
198.8
268.8
259.8
139.7
193.0
208.6
139.1
194.9
211.1
138.6
196.8
213.6
155.5
219.5
223.5
172.4
242.3
233.4
352.2
325.5
299.6
289.8
357.7
330.6
304.3
294.3
363.2
335.7
309.0
298.8
377.0
348.5
320.7
310.2
390.8
361.2
332.4
321.5
23.2
22.9
22.4
22.0
23.5
23.2
22.6
22.2
23.7
23.4
22.9
22.5
23.7
23.4
22.9
22.5
23.7
23.4
22.8
22.5
192.9
239.4
286.0
289.8
205.1
253.8
297.5
294.3
217.3
268.1
309.0
298.8
237.8
293.8
320.7
310.2
258.3
319.4
332.4
321.5
174.9
221.5
268.0
284.4
184.6
233.3
282.0
291.6
194.3
245.2
296.0
298.8
213.3
269.3
314.2
310.2
232.2
293.4
332.4
321.5
120.9
167.5
214.0
230.5
123.2
171.9
220.6
237.8
125.6
176.4
227.3
245.2
139.8
195.8
251.8
257.3
154.0
215.2
276.4
269.4
149.5
196.0
212.5
151.5
200.2
217.4
153.4
204.3
222.3
171.3
227.3
232.8
189.1
250.3
243.3
131.5
178.0
194.5
131.0
179.7
196.9
130.5
181.4
199.3
146.8
202.8
208.3
163.0
224.2
217.3
338.5
308.7
287.4
279.5
339.0
309.2
287.9
280.0
339.6
309.7
288.4
280.4
353.9
322.7
300.5
292.2
368.1
335.7
312.6
304.0
25.4
25.4
24.4
24.3
25.7
25.7
24.7
24.6
26.1
26.0
25.0
24.9
25.9
25.8
24.8
24.8
25.8
25.7
24.7
24.6
183.8
230.1
269.9
279.5
195.7
244.2
279.1
280.0
207.7
258.4
288.4
280.4
227.2
283.1
300.5
292.2
246.8
307.9
312.6
304.0
166.0
212.3
252.1
269.4
175.5
224.0
265.7
274.9
185.0
235.7
279.3
280.4
203.0
259.0
295.9
292.2
221.1
282.2
312.6
304.0
130.3
176.7
216.4
233.8
135.0
183.5
225.2
243.4
139.7
190.4
234.0
253.0
154.7
210.6
258.6
265.6
169.7
230.8
283.2
278.3
112.5
158.9
198.6
216.0
114.8
163.3
205.0
223.2
117.0
167.8
211.3
230.4
130.5
186.4
234.4
241.5
144.0
205.1
257.5
252.6
141.1
180.8
198.2
143.1
184.8
202.9
145.1
188.7
207.7
162.2
210.3
217.3
179.4
231.8
226.9
123.2
163.0
180.4
122.9
164.5
182.7
122.5
166.0
185.0
138.1
186.1
193.1
153.7
206.1
201.2
310.7
286.0
266.3
264.1
310.9
286.1
266.4
264.2
311.0
286.2
266.5
264.3
324.0
298.2
277.6
275.4
337.1
310.2
288.8
286.5
28.6
28.3
27.5
27.5
28.7
28.5
27.7
27.6
28.9
28.6
27.8
27.8
28.9
28.7
27.9
27.8
29.0
28.7
27.9
27.9
171.7
219.1
257.5
264.1
184.1
234.0
262.0
264.2
196.5
248.9
266.5
264.3
214.9
272.6
277.6
275.4
233.2
296.3
288.8
286.5
154.3
201.6
241.5
252.8
164.1
214.0
251.7
258.5
173.9
226.3
261.9
264.3
190.8
248.6
275.4
275.4
207.7
270.8
288.8
286.5
119.3
166.7
206.6
217.8
124.0
173.9
215.9
227.8
128.7
181.2
225.3
237.7
142.7
200.5
243.4
249.3
156.7
219.7
261.5
261.0
101.9
149.2
189.1
200.4
104.0
153.9
195.9
207.7
106.1
158.6
202.7
215.1
118.6
176.4
219.3
225.3
131.1
194.2
235.9
235.5
131.7
171.6
182.9
133.8
175.9
187.7
136.0
180.1
192.5
152.3
195.3
201.2
168.7
210.4
209.9
114.3
154.2
165.4
113.8
155.8
167.7
113.4
157.5
169.9
128.3
171.2
177.2
143.2
184.9
184.4
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
283.0
263.3
245.1
248.8
282.7
263.0
244.8
248.5
282.4
262.7
244.5
248.2
294.2
273.7
254.8
258.6
306.0
284.8
265.0
269.0
31.7
31.3
30.7
30.6
31.8
31.3
30.7
30.7
31.8
31.3
30.7
30.7
32.0
31.5
30.9
30.9
32.2
31.7
31.1
31.1
159.7
208.0
245.1
248.8
172.6
223.8
244.8
248.5
185.4
239.5
244.5
248.2
202.5
262.1
254.8
258.6
219.6
284.7
265.0
269.0
142.6
190.9
230.9
236.1
152.7
203.9
237.7
242.2
162.9
217.0
244.5
248.2
178.6
238.2
254.8
258.6
194.3
259.4
265.0
269.0
108.3
156.7
196.7
201.9
113.1
164.3
206.6
212.2
117.8
171.9
216.6
222.4
130.7
190.3
228.2
233.1
143.6
208.7
239.7
243.7
91.2
139.5
179.5
184.7
93.2
144.4
186.8
192.3
95.3
149.3
194.1
199.9
106.8
166.4
204.2
209.1
118.3
183.4
214.4
218.3
122.4
162.4
167.6
124.6
167.0
172.5
126.8
171.5
177.4
142.4
180.3
185.2
158.1
189.0
193.0
105.3
145.3
150.5
104.8
147.2
152.7
104.3
149.0
154.8
118.5
156.4
161.3
132.7
163.7
167.7
255.3
240.6
223.9
233.4
254.5
239.9
223.3
232.8
253.7
239.2
222.6
232.1
264.4
249.2
232.0
241.8
275.0
259.3
241.3
251.6
34.9
34.2
33.8
33.8
34.8
34.1
33.7
33.7
34.6
34.0
33.6
33.5
35.0
34.3
33.9
33.9
35.4
34.7
34.3
34.3
147.7
197.0
223.9
233.4
161.0
213.5
223.3
232.8
174.3
230.0
222.6
232.1
190.2
249.2
232.0
241.8
206.1
259.3
241.3
251.6
130.9
180.2
220.4
219.5
141.3
193.9
223.3
225.8
151.8
207.6
222.6
232.1
166.4
227.8
232.0
241.8
180.9
248.0
241.3
251.6
156.9
203.5
250.0
266.5
164.2
212.8
261.6
278.8
171.4
222.2
273.1
291.1
188.8
244.8
300.8
306.3
206.2
267.3
328.5
321.5
105F
136.8
184.1
224.0
235.3
144.1
193.9
236.0
247.8
151.3
203.8
247.9
260.3
166.8
224.5
267.4
273.4
182.2
245.3
287.0
286.5
125F
114.1
163.5
203.6
202.7
121.7
174.3
217.0
216.2
129.3
185.1
222.6
229.6
142.5
204.0
232.0
240.6
155.7
222.9
241.3
251.6
138.9
185.5
232.0
248.5
143.7
192.4
241.1
258.3
148.5
199.3
250.2
268.1
164.3
220.3
276.3
281.8
180.1
241.2
302.4
295.5
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
165.7
212.4
265.8
281.3
173.1
221.9
277.7
293.9
180.5
231.4
289.6
306.4
198.7
254.8
318.8
322.8
217.0
278.1
348.1
339.1
95F
148.2
194.5
234.2
251.6
155.2
203.8
245.5
263.6
162.3
213.1
256.7
275.7
178.9
234.8
282.8
289.8
195.4
256.5
308.9
304.0
115F
125.5
173.8
213.8
219.0
132.9
184.1
226.5
232.0
140.3
194.4
239.2
245.0
154.6
214.2
252.1
257.0
169.0
234.1
265.0
269.0
97.3
146.7
186.8
185.9
102.1
154.6
197.4
196.5
106.9
162.6
207.9
207.2
118.7
180.2
212.9
216.8
130.6
197.7
218.0
226.4
80.5
129.9
170.0
169.1
82.5
135.0
177.7
176.9
84.4
140.1
185.5
184.7
94.9
156.3
189.1
193.0
105.4
172.6
192.8
201.2
113.1
153.2
152.3
115.4
158.1
157.3
117.6
163.0
162.2
132.5
165.3
169.1
147.4
167.6
176.1
96.3
136.4
135.6
95.7
138.5
137.6
95.2
140.5
139.7
108.7
141.5
145.3
122.2
142.5
150.9
These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
31
355278-JTG-D-0110
Air on Evaporator
Coil
CFM
9000
10500
12000
13500
15000
9000
10500
12000
13500
15000
9000
10500
12000
13500
15000
1.
2.
32
75F
85F
WB
(F)
Total
Cap.1
(MBH)
Total2
Input
(kW)
86
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
438.1
411.1
383.5
381.2
449.0
421.4
393.2
390.8
460.0
431.7
402.8
400.3
466.7
438.0
408.7
406.2
473.5
444.4
414.6
412.1
25.5
25.1
24.6
24.6
25.7
25.3
24.8
24.7
25.8
25.5
25.0
24.9
25.9
25.5
25.0
25.0
26.0
25.6
25.1
25.1
255.0
316.7
383.5
381.2
276.2
342.4
393.2
390.8
297.5
368.1
402.8
400.3
316.2
391.0
408.7
406.2
335.0
413.8
414.6
412.1
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
396.9
371.8
349.7
350.0
406.4
380.6
358.0
358.3
415.8
389.5
366.3
366.6
421.9
395.2
371.7
372.0
428.0
400.9
377.0
377.4
30.0
29.6
29.3
29.3
30.1
29.7
29.4
29.4
30.3
29.8
29.5
29.5
30.4
29.9
29.6
29.6
30.4
30.0
29.7
29.7
239.6
298.5
349.7
350.0
260.1
323.6
358.0
358.3
280.6
348.6
366.3
366.6
301.2
373.6
371.7
372.0
321.8
398.7
377.0
377.4
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
354.6
332.4
318.2
318.2
362.6
339.8
325.3
325.3
370.6
347.3
332.5
332.4
375.5
351.9
336.9
336.9
380.5
356.6
341.3
341.3
35.8
35.4
35.1
35.1
35.9
35.5
35.3
35.3
36.0
35.6
35.4
35.4
36.1
35.7
35.4
35.4
36.1
35.7
35.5
35.5
222.3
280.8
318.2
318.2
242.6
305.8
325.3
325.3
263.0
330.9
332.5
332.4
282.3
343.8
336.9
336.9
301.6
356.6
341.3
341.3
83
80
231.9 208.9
293.6 270.6
357.8 334.8
372.6 349.6
250.1 224.0
316.3 290.2
380.3 359.1
386.5 374.9
268.3 239.2
339.0 309.8
402.8 383.3
400.3 400.3
284.7 253.1
359.4 327.9
408.7 399.0
406.2 406.2
301.0 267.0
379.9 345.9
414.6 414.6
412.1 412.1
95F
216.9 194.3
275.9 253.2
337.0 314.3
340.4 317.8
234.7 209.2
298.1 272.6
351.7 338.5
353.5 342.2
252.4 224.1
320.3 292.1
366.3 362.7
366.6 366.6
270.0 238.8
342.4 311.2
371.7 369.8
372.0 372.0
287.6 253.4
364.5 330.3
377.0 377.0
377.4 377.4
115F
200.1 177.9
258.5 236.3
308.2 286.0
308.2 286.0
217.5 192.3
280.7 255.5
320.3 309.2
320.3 309.2
234.9 206.8
302.8 274.7
332.5 332.5
332.4 332.4
251.5 220.7
324.0 293.2
336.9 336.9
336.9 336.9
268.1 234.6
345.1 311.7
341.3 341.3
341.3 341.3
Total2
Input
(kW)
86
77
74
71
68
Total
Cap.1
(MBH)
185.8
247.5
311.7
326.5
197.9
264.1
333.0
348.8
210.0
280.7
354.2
371.2
221.6
296.3
367.4
374.6
233.1
311.9
380.6
378.1
162.8
224.5
288.7
303.5
171.8
238.0
306.9
322.7
180.9
251.5
325.1
342.0
190.0
264.8
335.9
343.1
199.1
278.0
346.7
344.1
201.4
265.6
280.4
211.9
280.8
296.6
222.4
295.9
312.9
233.2
304.3
311.5
244.0
312.7
310.2
178.4
242.6
257.3
185.8
254.7
270.5
193.3
266.8
283.7
201.6
272.8
280.0
210.0
278.7
276.2
417.5
391.4
366.6
365.6
427.7
401.0
375.6
374.5
437.9
410.6
384.5
383.5
444.3
416.6
390.2
389.1
450.7
422.6
395.8
394.7
27.8
27.4
27.0
26.9
27.9
27.5
27.1
27.1
28.1
27.6
27.3
27.2
28.1
27.7
27.3
27.3
28.2
27.8
27.4
27.4
247.3
307.6
366.6
365.6
268.2
333.0
375.6
374.5
289.0
358.3
384.5
383.5
308.7
382.3
390.2
389.1
328.4
406.2
395.8
394.7
171.6
230.5
291.6
295.1
183.7
247.2
313.0
316.7
195.9
263.9
334.4
338.4
207.6
280.0
338.6
340.8
219.3
296.1
342.8
343.2
148.9
207.8
268.9
272.4
158.3
221.7
287.6
291.3
167.7
235.6
306.2
310.2
176.4
248.8
307.4
309.6
185.1
261.9
308.7
309.0
185.1
246.2
249.7
196.2
262.1
265.8
207.4
277.9
281.9
217.6
276.2
278.4
227.7
274.5
274.8
162.4
223.6
227.0
170.8
236.6
240.3
179.1
249.7
253.7
186.4
245.0
247.1
193.6
240.3
240.6
375.8
352.1
333.9
334.1
384.5
360.2
341.7
341.8
393.2
368.4
349.4
349.5
398.7
373.6
354.3
354.4
404.2
378.7
359.2
359.3
32.9
32.5
32.2
32.2
33.0
32.6
32.3
32.3
33.2
32.7
32.5
32.5
33.2
32.8
32.5
32.5
33.3
32.9
32.6
32.6
231.0
289.7
333.9
334.1
251.4
314.7
341.7
341.8
271.8
339.8
349.4
349.5
291.7
358.7
354.3
354.4
311.7
377.6
359.2
359.3
155.7
214.1
263.8
263.8
167.2
230.4
284.1
284.1
178.7
246.6
304.4
304.3
189.9
262.4
306.1
306.1
201.1
278.2
307.8
307.8
133.4
191.9
241.6
241.6
142.0
205.2
258.9
258.9
150.6
218.5
276.3
276.2
159.1
231.6
275.3
275.3
167.6
244.7
274.3
274.3
169.7
219.4
219.3
180.0
233.8
233.7
190.4
248.2
248.1
200.8
244.5
244.5
211.2
240.9
240.8
147.5
197.1
197.1
154.9
208.6
208.6
162.3
220.0
220.0
170.0
213.7
213.7
177.7
207.4
207.3
333.5
312.7
302.4
302.3
340.7
319.5
309.0
308.8
347.9
326.2
315.5
315.3
352.3
330.3
319.5
319.3
356.7
334.4
323.5
323.3
38.7
38.3
38.0
38.0
38.8
38.4
38.2
38.2
38.9
38.5
38.3
38.3
38.9
38.6
38.3
38.3
39.0
38.6
38.3
38.3
213.6
271.9
302.4
302.3
233.9
297.0
309.0
308.8
254.2
322.1
315.5
315.3
272.8
328.8
319.5
319.3
291.4
334.4
323.5
323.3
83
80
224.4 201.6
284.7 261.9
347.4 324.6
356.5 333.7
242.4 216.6
307.2 281.4
366.0 348.8
370.0 358.6
260.3 231.7
329.7 301.0
384.5 373.0
383.5 383.5
277.3 245.9
350.9 319.5
390.2 384.4
389.1 389.1
294.3 260.2
372.2 338.1
395.8 395.8
394.7 394.7
105F
208.5 186.1
267.2 244.7
322.6 300.2
324.3 301.9
226.1 200.8
289.4 264.1
336.0 323.9
336.9 325.7
243.6 215.5
311.6 283.4
349.4 347.6
349.5 349.5
260.7 229.7
333.2 302.2
354.3 353.4
354.4 354.4
277.8 244.0
354.8 321.0
359.2 359.2
359.3 359.3
125F
191.7 169.7
249.9 227.9
293.8 271.8
292.1 270.1
208.9 183.9
272.0 247.0
304.7 294.6
303.7 292.7
226.1 198.1
294.1 266.0
315.5 315.5
315.3 315.3
242.2 211.6
314.8 284.2
319.5 319.5
319.3 319.3
258.3 225.1
334.4 302.3
323.5 323.5
323.3 323.3
77
74
71
68
178.7
239.0
301.7
310.8
190.8
255.6
323.0
332.8
203.0
272.3
344.3
354.8
214.6
288.1
353.0
357.7
226.2
304.0
361.7
360.6
155.8
216.1
278.8
287.9
165.0
229.9
297.2
307.0
174.3
243.6
315.6
326.1
183.2
256.8
321.6
326.3
192.1
270.0
327.7
326.6
193.3
255.9
265.0
204.1
271.4
281.2
214.9
286.9
297.4
225.4
290.3
294.9
235.9
293.6
292.5
170.4
233.1
242.2
178.3
245.7
255.4
186.2
258.2
268.7
194.0
258.9
263.6
201.8
259.5
258.4
163.6
222.3
277.7
279.4
175.4
238.8
298.5
300.4
187.3
255.2
319.4
321.4
198.7
271.2
322.4
323.4
210.2
287.1
325.3
325.5
141.2
199.8
255.3
257.0
150.1
213.5
273.2
275.1
159.1
227.1
291.2
293.2
167.7
240.2
291.4
292.4
176.3
253.3
291.5
291.7
177.4
232.8
234.5
188.1
247.9
249.8
198.9
263.0
265.0
209.2
260.4
261.4
219.5
257.7
257.8
154.9
210.3
212.1
162.8
222.6
224.5
170.7
234.9
236.9
178.2
229.3
230.4
185.6
223.8
224.0
147.7
205.9
249.9
248.1
158.9
222.0
269.6
267.7
170.1
238.0
289.3
287.3
181.0
253.6
289.8
288.7
192.0
269.2
290.3
290.2
125.7
183.9
227.9
226.1
133.9
196.9
244.6
242.7
142.0
210.0
261.3
259.3
150.4
223.0
259.2
258.1
158.8
236.0
257.2
257.0
162.0
205.9
204.2
171.9
219.6
217.7
181.9
233.3
231.2
192.4
228.6
227.5
202.9
224.0
223.8
140.0
183.9
182.2
146.9
194.6
192.7
153.9
205.2
203.2
161.8
198.1
196.9
169.7
190.9
190.7
These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
355278-JTG-D-0110
Air on Evaporator
Coil
CFM
12000
14000
16000
18000
20000
12000
14000
16000
18000
20000
12000
14000
16000
18000
20000
1.
2.
75F
85F
WB
(F)
Total
Cap.1
(MBH)
Total2
Input
(kW)
86
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
570.6
532.3
495.7
495.9
584.8
545.5
508.0
508.2
598.9
558.7
520.3
520.5
608.2
567.4
528.3
528.6
617.4
576.0
536.4
536.6
32.2
31.6
31.1
31.1
32.4
31.8
31.3
31.3
32.6
32.0
31.5
31.5
32.7
32.2
31.6
31.6
32.9
32.3
31.7
31.7
340.7
420.3
495.7
495.9
369.1
454.7
508.0
508.2
397.6
489.0
520.3
520.5
422.8
525.1
528.3
528.6
448.0
561.2
536.4
536.6
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
514.0
479.8
454.7
454.7
525.9
490.9
465.3
465.2
537.8
502.0
475.8
475.8
545.4
509.1
482.5
482.5
552.9
516.2
489.2
489.2
38.7
38.1
37.7
37.7
38.9
38.3
37.9
37.9
39.0
38.4
38.0
38.0
39.2
38.6
38.1
38.1
39.3
38.7
38.3
38.3
319.4
398.4
454.7
454.7
346.9
432.0
465.3
465.2
374.4
465.6
475.8
475.8
399.2
490.9
482.5
482.5
424.1
516.2
489.2
489.2
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
457.9
427.9
412.8
412.8
467.6
437.0
421.6
421.6
477.4
446.1
430.4
430.4
484.2
452.5
436.6
436.6
491.0
458.9
442.7
442.7
46.7
46.2
45.8
45.8
46.8
46.3
45.9
45.9
46.9
46.4
46.1
46.1
47.0
46.5
46.2
46.2
47.1
46.6
46.3
46.3
298.1
375.7
412.8
412.8
325.2
409.2
421.6
421.6
352.3
442.7
430.4
430.4
376.8
450.8
436.6
436.6
401.2
458.9
442.7
442.7
83
80
309.3 277.8
388.9 357.4
474.7 443.3
484.4 453.0
333.8 298.5
419.4 384.1
497.5 476.3
502.5 486.7
358.4 319.3
449.8 410.7
520.3 509.3
520.5 520.5
380.6 338.4
477.5 435.4
528.3 522.8
528.6 528.6
402.8 357.6
505.2 460.0
536.4 536.4
536.6 536.6
95F
288.2 256.9
367.1 335.9
443.1 411.8
443.0 411.8
311.9 276.9
397.0 361.9
459.4 443.8
459.4 443.8
335.6 296.8
426.8 388.0
475.8 475.8
475.8 475.8
357.5 315.8
454.6 412.9
482.5 482.5
482.5 482.5
379.5 334.8
482.3 437.7
489.2 489.2
489.2 489.2
115F
267.3 236.5
344.9 314.1
400.4 369.5
400.3 369.5
290.6 256.0
374.6 339.9
415.4 400.0
415.4 400.0
313.9 275.4
404.2 365.8
430.4 430.4
430.4 430.4
335.3 293.9
431.6 390.3
436.6 436.6
436.6 436.6
356.8 312.4
458.9 414.8
442.7 442.7
442.7 442.7
Total2
Input
(kW)
86
77
74
71
68
Total
Cap.1
(MBH)
246.4
326.0
411.8
421.5
263.2
348.8
441.0
451.4
280.1
371.5
470.2
481.4
296.3
393.2
480.7
486.4
312.5
414.9
491.2
491.4
215.0
294.5
380.4
390.1
227.9
313.5
405.7
416.1
240.9
332.4
431.0
442.2
254.1
351.0
438.5
444.2
267.3
369.7
446.0
446.2
263.1
348.9
358.6
278.2
370.4
380.8
293.2
391.9
403.0
308.9
396.3
402.0
324.5
400.8
401.0
231.7
317.5
327.2
242.9
335.1
345.5
254.1
352.7
363.9
266.7
354.2
359.9
279.3
355.6
355.9
542.3
506.1
475.2
475.3
555.3
518.2
486.6
486.7
568.3
530.4
498.0
498.1
576.8
538.2
505.4
505.5
585.2
546.1
512.8
512.9
35.4
34.9
34.4
34.4
35.6
35.0
34.6
34.6
35.8
35.2
34.7
34.7
35.9
35.4
34.9
34.9
36.1
35.5
35.0
35.0
330.1
409.3
475.2
475.3
358.0
443.3
486.6
486.7
386.0
477.3
498.0
498.1
411.0
508.0
505.4
505.5
436.0
538.7
512.8
512.9
225.7
304.6
380.5
380.5
241.9
326.9
408.8
408.7
258.1
349.3
437.0
437.0
274.1
371.2
440.8
440.8
290.2
393.1
444.6
444.6
194.4
273.3
349.3
349.3
206.8
291.9
373.7
373.7
219.3
310.5
398.2
398.2
232.4
329.5
399.1
399.1
245.6
348.5
400.0
400.0
242.1
318.0
318.0
256.9
338.7
338.7
271.7
359.4
359.4
287.8
357.4
357.4
303.9
355.4
355.4
210.8
286.8
286.8
221.9
303.7
303.7
232.9
320.6
320.6
246.1
315.7
315.7
259.3
310.8
310.7
485.9
453.8
433.8
433.8
496.8
463.9
443.4
443.4
507.6
474.0
453.1
453.1
514.8
480.8
459.5
459.5
522.0
487.5
466.0
466.0
42.7
42.1
41.7
41.7
42.8
42.3
41.9
41.9
43.0
42.4
42.0
42.0
43.1
42.5
42.2
42.2
43.2
42.7
42.3
42.3
308.8
387.0
433.8
433.8
336.1
420.6
443.4
443.4
363.4
454.1
453.1
453.1
388.0
470.8
459.5
459.5
412.6
487.5
466.0
466.0
205.7
283.3
338.7
338.7
221.4
305.3
365.4
365.3
237.0
327.4
392.0
392.0
252.5
348.9
395.1
395.1
267.9
370.4
398.3
398.3
174.9
252.5
307.9
307.9
186.7
270.7
330.7
330.7
198.6
288.9
353.5
353.5
211.0
307.4
353.7
353.7
223.5
326.0
353.9
353.8
221.7
277.1
277.1
236.1
296.1
296.1
250.5
315.1
315.1
266.0
312.3
312.2
281.5
309.4
309.4
190.8
246.3
246.3
201.5
261.5
261.5
212.1
276.7
276.6
224.6
270.8
270.8
237.1
265.0
265.0
429.9
402.0
391.9
391.9
438.5
410.1
399.8
399.8
447.2
418.2
407.7
407.7
453.6
424.2
413.6
413.6
460.1
430.2
419.5
419.5
50.6
50.2
49.8
49.8
50.8
50.3
50.0
50.0
50.9
50.4
50.1
50.1
51.0
50.5
50.2
50.2
51.1
50.6
50.3
50.3
287.5
364.4
391.9
391.9
314.4
397.8
399.8
399.8
341.3
418.2
407.7
407.7
365.5
424.2
413.6
413.6
389.8
430.2
419.5
419.5
83
80
298.7 267.4
378.0 346.6
458.9 427.5
463.7 432.4
322.9 287.7
408.2 373.0
478.5 460.0
480.9 465.3
347.0 308.0
438.3 399.4
498.0 492.6
498.1 498.1
369.1 327.1
466.1 424.1
505.4 502.7
505.5 505.5
391.1 346.2
493.8 448.9
512.8 512.8
512.9 512.9
105F
277.7 246.7
356.0 325.0
421.7 390.7
421.7 390.7
301.2 266.4
385.8 350.9
437.4 421.9
437.4 421.9
324.8 286.1
415.5 376.9
453.1 453.1
453.1 453.1
346.4 304.9
443.1 401.6
459.5 459.5
459.5 459.5
368.1 323.6
470.6 426.3
466.0 466.0
466.0 466.0
125F
256.9 226.3
333.8 303.2
379.0 348.4
379.0 348.4
279.9 245.5
363.4 328.9
393.4 378.1
393.3 378.1
303.0 264.8
393.0 354.7
407.7 407.7
407.7 407.7
324.2 282.9
420.1 379.0
413.6 413.6
413.6 413.6
345.5 301.1
430.2 403.4
419.5 419.5
419.5 419.5
77
74
71
68
236.0
315.3
396.2
401.0
252.6
337.8
424.9
430.1
269.1
360.4
453.6
459.2
285.2
382.2
460.7
463.6
301.3
404.0
467.9
468.0
204.7
283.9
364.8
369.7
217.4
302.7
389.7
394.9
230.1
321.4
414.6
420.2
243.3
340.3
418.8
421.6
256.4
359.1
423.0
423.1
252.6
333.5
338.3
267.5
354.6
359.8
282.5
375.6
381.2
298.3
376.9
379.7
314.2
378.1
378.2
221.2
302.1
307.0
232.4
319.4
324.6
243.5
336.7
342.3
256.4
334.9
337.8
269.3
333.2
333.3
215.7
293.9
359.6
359.6
231.6
316.1
387.1
387.0
247.5
338.3
414.5
414.5
263.3
360.0
418.0
417.9
279.1
381.7
421.5
421.4
184.6
262.9
328.6
328.6
196.8
281.3
352.2
352.2
208.9
299.7
375.9
375.9
221.7
318.5
376.4
376.4
234.6
337.2
376.9
376.9
231.9
297.6
297.6
246.5
317.4
317.4
261.1
337.3
337.2
276.9
334.8
334.8
292.7
332.4
332.4
200.8
266.5
266.5
211.7
282.6
282.6
222.5
298.7
298.6
235.3
293.3
293.2
248.2
287.9
287.9
195.7
272.6
317.8
317.8
211.1
294.5
343.7
343.6
226.5
316.4
369.5
369.4
241.6
337.7
372.3
372.3
256.8
359.0
375.2
375.1
165.1
242.0
287.3
287.2
176.7
260.1
309.2
309.2
188.2
278.2
331.2
331.2
200.3
296.4
331.0
331.0
212.4
314.7
330.8
330.8
211.4
256.7
256.7
225.7
274.8
274.8
239.9
293.0
292.9
255.1
289.7
289.7
270.3
286.5
286.4
180.9
226.1
226.1
191.3
240.4
240.4
201.7
254.7
254.7
213.8
248.4
248.4
226.0
242.1
242.1
These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
33
355278-JTG-D-0110
order to use the indoor blower tables for high altitude applications, certain corrections are necessary.
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
ALTITUDE (FEET)
4000
5000
0.916
0.882
0.898
0.864
0.880
0.848
0.864
0.832
0.848
0.817
0.833
0.802
0.817
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
The examples below will assist in determining the airflow performance of the product at altitude.
34
355278-JTG-D-0110
35
355278-JTG-D-0110
0.2
4000
5000
6000
7000
8000
9000
10000
11000
12000
12500
1.4
BHP3
1.8
2.4
2.9
3.6
4.4
5.3
6.3
7.7
9.1
10.0
RPM
568
582
596
615
633
658
682
713
743
760
RPM
609
621
633
650
666
688
710
739
767
784
2.2
2.4
BHP3
3.5
4.3
5.0
5.8
6.7
7.8
8.9
10.5
12.0
12.9
RPM
743
754
766
777
788
804
819
841
863
876
AIRFLOW CFM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
RPM
365
396
427
459
491
527
563
605
647
664
1.2
AIRFLOW CFM
4000
5000
6000
7000
8000
9000
10000
11000
12000
12500
BHP3
0.5
0.9
1.2
1.8
2.3
3.2
4.2
5.5
6.8
7.4
RPM
302
341
380
416
452
492
532
578
623
639
AIRFLOW CFM
0.4
RPM
770
783
795
806
817
831
845
866
887
899
3.2
RPM
867
885
903
914
924
934
944
961
978
986
3.4
BHP3
5.4
6.4
7.3
8.3
9.3
10.6
11.9
13.6
15.2
16.2
RPM
890
909
928
939
949
959
968
984
1000
1008
RPM
523
540
557
578
600
626
653
686
719
736
RPM
713
724
735
747
759
776
793
816
839
853
BHP3
4.6
5.5
6.4
7.3
8.2
9.5
10.7
12.3
13.9
14.8
RPM
844
861
878
888
898
909
920
938
956
965
BHP3
6.6
7.6
8.7
9.9
11.2
12.5
13.8
15.6
17.3
18.2
RPM
958
979
1000
1012
1023
1030
1037
1051
1064
1070
1.0
BHP3
1.5
2.0
2.5
3.2
3.9
4.9
5.8
7.2
8.6
9.5
2.0
BHP3
3.2
3.9
4.5
5.4
6.2
7.3
8.4
9.9
11.4
12.3
3.0
BHP3
5.0
5.9
6.8
7.8
8.8
10.0
11.3
12.9
14.5
15.5
4.0
BHP3
6.9
8.0
9.1
10.5
11.8
13.2
14.5
16.2
18.0
19.0
1.
Fan performance is based on wet evaporator coils, clean 2 throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
Refer to Tables 10, 15, 21 and 38 for component additions and deductions to fan performance tables.
3.
BHP includes drive losses.
4. Shaded RPMs require Class II blower.
2.
36
355278-JTG-D-0110
7.0
M
RP
6.5
6.0
20
00
10
15
5.0
BH
P
0
90
4.5
10
5.5
7.5
4.0
80
0
3.5
3.0
70
0
2.5
600
2.0
1.5
500
1.0
0.5
0.0
0
10
11
12
13
CFM (x1000)
A - Standard Unit
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system
and cabinet effects at standard air density and 0' elevation.
37
355278-JTG-D-0110
0.2
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
1.
2.
3.
1.4
BHP3
3.1
3.8
4.6
5.6
6.7
8.2
9.7
11.5
13.3
15.6
RPM
612
634
655
680
704
735
766
798
830
864
RPM
649
668
687
710
732
761
790
820
851
884
2.2
2.4
BHP3
5.1
6.1
7.0
8.3
9.5
11.0
12.5
14.6
16.6
18.9
RPM
779
793
807
823
839
862
884
909
935
963
RPM
808
822
836
850
865
886
907
931
956
982
3.2
AIRFLOW (CFM)
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
RPM
450
485
519
554
588
629
671
709
748
786
1.2
AIRFLOW (CFM)
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
BHP3
1.3
1.9
2.6
3.5
4.5
5.7
7.0
8.9
10.7
12.7
RPM
405
444
483
520
558
603
647
687
728
767
AIRFLOW (CFM)
0.4
RPM
916
928
941
952
964
981
997
1017
1037
1059
3.4
BHP3
7.4
8.6
9.8
11.2
12.6
14.1
15.7
17.9
20.2
22.6
RPM
940
953
965
976
987
1003
1019
1038
1056
1078
0.8
1.0
BHP3
2.3
3.0
3.7
4.7
5.7
7.2
8.6
10.4
12.2
14.4
RPM
575
599
623
649
676
709
742
776
809
845
BHP3
4.3
5.1
6.0
7.2
8.3
9.8
11.4
13.3
15.2
17.6
RPM
748
763
779
796
813
837
861
887
914
943
BHP3
6.4
7.5
8.6
10.0
11.3
12.9
14.4
16.5
18.7
21.1
RPM
890
903
916
928
940
957
975
996
1017
1040
BHP3
8.8
10.1
11.5
13.0
14.5
16.1
17.8
20.1
22.4
24.9
RPM
1011
1023
1035
1045
1055
1069
1082
1097
1113
1134
1.8
BHP3
2.7
3.4
4.2
5.2
6.2
7.7
9.2
10.9
12.7
15.0
2.0
2.8
BHP3
4.7
5.6
6.5
7.7
8.9
10.4
12.0
13.9
15.9
18.3
3.0
3.8
BHP3
6.9
8.1
9.2
10.6
12.0
13.5
15.0
17.2
19.4
21.8
4.0
BHP3
9.3
10.7
12.0
13.6
15.1
16.8
18.5
20.8
23.1
25.7
Fan performance is based on wet evaporator coils, clean 2 throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
Refer to Tables 10, 15, 21 and 38 for component additions and deductions to fan performance tables.
BHP includes drive losses.
38
355278-JTG-D-0110
R
00
11
7.0
PM
6.5
6.0
BH
P
15
5.0
0
90
4.5
10
4.0
80
3.5
20
00
10
5.5
3.0
70
2.5
2.0
600
1.5
500
1.0
0.5
0.0
0
10
11
12
13
14
15
CFM (x1000)
A - Standard Unit
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system
and cabinet effects at standard air density and 0' elevation.
39
355278-JTG-D-0110
AIRFLOW (CFM)
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
1.
2.
3.
1.4
BHP3
4.2
5.0
5.7
6.8
7.9
9.1
10.3
11.9
13.5
15.4
17.3
RPM
552
567
582
602
621
639
657
678
699
720
740
RPM
583
596
610
628
647
664
681
700
720
740
760
2.2
2.4
BHP3
6.7
7.7
8.7
9.9
11.1
12.5
14.0
15.6
17.3
19.4
21.5
RPM
690
701
712
726
740
755
769
785
801
819
836
AIRFLOW (CFM)
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
RPM
409
433
458
486
513
535
557
584
612
635
659
1.2
AIRFLOW (CFM)
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
BHP3
1.9
2.5
3.1
4.0
5.0
5.9
6.9
8.4
9.8
11.7
13.6
RPM
367
396
424
454
484
507
530
560
589
613
638
AIRFLOW (CFM)
0.4
RPM
713
725
736
749
762
776
790
805
820
837
855
3.2
RPM
799
811
823
834
846
858
870
882
895
910
925
3.4
BHP3
9.3
10.6
11.9
13.3
14.6
16.3
17.9
19.7
21.5
23.8
26.0
RPM
819
831
843
855
866
877
889
901
913
928
-
0.8
1.0
BHP3
3.3
4.0
4.6
5.6
6.6
7.8
8.9
10.4
12.0
13.8
15.7
RPM
519
536
553
574
596
614
633
655
678
699
721
BHP3
5.7
6.6
7.4
8.6
9.8
11.1
12.5
14.1
15.8
17.8
19.7
RPM
665
677
688
703
718
733
748
765
781
799
818
BHP3
8.2
9.4
10.6
11.9
13.2
14.7
16.3
18.0
19.8
22.0
24.2
RPM
779
790
802
814
826
838
851
864
877
892
908
BHP3
11.2
12.6
13.9
15.4
16.8
18.6
20.3
22.2
24.2
-
RPM
879
891
902
913
924
934
944
955
966
-
1.8
BHP3
3.8
4.5
5.2
6.2
7.2
8.4
9.6
11.2
12.7
14.6
16.5
2.0
2.8
BHP3
6.2
7.1
8.0
9.2
10.4
11.8
13.2
14.9
16.5
18.6
20.6
3.0
3.8
BHP3
8.8
10.0
11.2
12.6
13.9
15.5
17.1
18.9
20.6
22.9
25.1
4.0
BHP3
11.9
13.3
14.6
16.1
17.5
19.3
21.1
23.1
25.1
-
Fan performance is based on wet evaporator coils, clean 2 throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
Refer to Tables 12, 18, 23 and 38 for component additions and deductions to fan performance tables.
BHP includes drive losses.
40
355278-JTG-D-0110
5.5
B
25
P
20
4.5
80
0
4.0
15
5.0
3.5
10
70
0
3.0
2.5
600
2.0
500
1.5
400
1.0
300
0.5
0.0
0
10
12
14
16
18
20
CFM (x1000)
A - Standard Unit
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system
and cabinet effects at standard air density and 0' elevation.
41
355278-JTG-D-0110
CFM
4,000
6,000
8,000
10,000
12,000
14,000
16,000
18,000
-0.14
Baseline
-0.18
Baseline
-0.24
Baseline
-0.34
Baseline
-0.45
Baseline
-0.18
Baseline
-0.22
Baseline
-0.32
Baseline
-0.45
Baseline
-0.60
Baseline
-0.76
Baseline
-0.15
Baseline
-0.22
Baseline
-0.26
Baseline
-0.31
Baseline
-0.42
Baseline
-0.53
Baseline
-.0.65
Baseline
-0.79
Baseline
FILTER LOSSES
2 TA or HI EFF.
Rigid 6, 65%
Rigid 6, 95%
Baseline
0.06
0.13
Baseline
0.12
0.26
Baseline
0.19
0.41
Baseline
0.27
0.60
Baseline
0.36
0.81
Baseline
0.46
1.04
Baseline
0.58
1.29
Baseline
0.70
1.57
IGV LOSSES
25 & 30 Ton F.C.
40 Ton F.C.
0.02
0.01
0.05
0.03
0.08
0.05
0.13
0.08
0.19
0.11
0.26
0.15
0.34
0.19
0.43
0.25
GAS HEAT
267 MBH Heat
533 MBH Heat
800 MBH Heat
0.07
0.14
0.21
0.11
0.21
0.32
0.14
0.28
0.42
0.18
0.35
0.53
0.21
0.42
0.64
0.25
0.49
0.74
0.28
0.57
0.85
0.32
0.64
0.95
ELECTRIC HEAT
40KW
80KW
108KW
0.01
0.01
0.02
0.02
0.04
0.05
0.04
0.08
0.10
0.06
0.13
0.15
0.10
0.20
0.31
0.20
0.31
0.43
0.31
0.44
0.53
0.40
0.56
0.68
ECONOMIZER
0.03
0.06
0.10
0.15
0.21
0.28
0.35
0.43
POWER EXHAUST
0.02
0.05
0.08
0.13
0.18
0.25
0.32
0.41
1.
2.
42
Baseline losses based on system/cabinet effects, wet standard coil and 2 throwaway filters at 70F, 0 feet elevation with standard air.
See Tables 10, 12, 15, 18 and 21 for hot water and steam water coil static resistance.
355278-JTG-D-0110
BHP2
----0.7
1.2
1.9
3.0
3.8
5.8
8.4
RPM
2000
3000
4000
5000
6000
7000
8000
9000
10000
----442
524
612
703
791
877
967
RPM
1.
2.
RPM
--450
496
566
646
731
821
911
1004
754
736
743
768
806
857
921
995
1077
BHP2
--0.4
0.8
1.4
2.2
3.3
4.3
6.2
8.8
RPM
524
531
562
609
679
759
844
932
1022
BHP2
0.3
0.5
0.9
1.5
2.4
3.5
4.8
6.5
9.1
RPM
609
605
626
663
717
787
868
953
1041
1.0
BHP2
0.4
0.7
1.1
1.7
2.6
3.7
5.2
6.9
9.4
BHP2
0.7
1.0
1.4
2.0
2.9
4.2
5.7
7.6
10.1
RPM
819
797
799
818
850
895
953
1020
1096
BHP2
0.8
1.1
1.5
2.2
3.1
4.4
6.0
8.0
10.4
RPM
878
854
850
865
895
933
985
1048
1119
BHP2
0.9
1.3
1.7
2.4
3.3
4.6
6.2
8.3
10.8
RPM
933
909
900
911
937
972
1018
1075
1143
BHP2
0.6
0.8
1.2
1.8
2.7
4.0
5.5
7.3
9.8
RPM
685
672
687
717
762
820
892
974
1059
1.2
AIRFLOW CFM
2000
3000
4000
5000
6000
7000
8000
9000
10000
0.2
AIRFLOW CFM
2.0
BHP2
1.1
1.5
1.9
2.6
3.6
4.8
6.5
8.5
11.1
RPM
986
961
948
955
978
1010
1052
1103
1167
BHP2
1.2
1.7
2.1
2.8
3.8
5.0
6.8
8.8
11.4
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet of elevation.
BHP includes 5% drive losses.
43
355278-JTG-D-0110
8.0
7.5
7.0
6.5
1600
6.0
5.5
1500
10 BHP
5.0
7.5 BHP
1400
4.5
5 BHP
1300
4.0
1200
3.5
1100
3.0
1000
2.5
900
2.0
800
700
1.5
600
1.0
500
0.5
400
300
0.0
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
CFM (x1000)
44
355278-JTG-D-0110
TABLE 40: POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TON1
0.2
AIRFLOW CFM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
16000
RPM
BHP2 3
RPM
363
402
445
494
544
597
651
705
761
817
874
932
989
0.3
0.5
0.8
1.3
1.8
2.4
3.3
4.3
5.5
6.9
8.5
10.4
12.6
468
494
527
565
609
654
703
753
805
858
912
967
1022
1.2
AIRFLOW CFM
RPM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
16000
1.
2.
3.
0.4
783
788
798
814
837
866
900
936
976
1018
1061
1107
---
BHP2 3
0.5
0.7
1.1
1.6
2.1
2.8
3.7
4.7
5.9
7.4
9.0
10.9
13.2
1.4
BHP2 3
1.5
1.8
2.2
2.8
3.5
4.3
5.3
6.4
7.8
9.3
11.1
13.2
---
RPM
844
848
855
869
889
915
945
979
1016
1055
1098
1141
---
BHP2 3
0.7
1.1
1.4
1.8
2.4
3.2
4.0
5.1
6.3
7.8
9.6
11.6
13.8
RPM
903
906
911
922
938
961
989
1020
1055
1093
1133
1175
---
BHP2 3
1.9
2.4
2.9
3.5
4.2
5.1
6.2
7.4
8.7
10.4
12.3
14.4
---
RPM
956
959
963
972
987
1007
1032
1061
1094
1129
1167
1208
---
1.0
BHP2 3
0.9
1.3
1.7
2.1
2.7
3.5
4.4
5.6
6.8
8.3
10.0
12.1
14.3
641
652
670
697
729
765
805
847
893
939
988
1037
1088
0.8
RPM
BHP2 3
1.2
1.5
2.0
2.5
3.2
3.9
4.8
6.0
7.2
8.8
10.5
12.6
---
RPM
716
722
735
757
784
817
853
893
934
979
1025
1072
---
1.8
2
BHP2 3
2.2
2.6
3.3
3.9
4.6
5.6
6.6
7.9
9.2
10.9
12.9
14.9
---
RPM
1008
1011
1014
1021
1033
1050
1073
1101
1131
1165
1202
1240
---
BHP2 3
2.4
2.9
3.6
4.2
5.0
6.0
7.1
8.3
9.8
11.6
13.4
15.5
---
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet of elevation.
BHP includes the sum of both exhaust fan blowers.
BHP includes 5% drive losses.
45
355278-JTG-D-0110
46
355278-JTG-D-0110
OD Fan Motors
Supply Blower
Motor
HP
FLA
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
24.2
30.8
46.2
59.4
22.0
28.0
42.0
54.0
11.0
14.0
21.0
27.0
9.0
11.0
17.0
22.0
Voltage
Qty
RLA
LRA
MCC
Qty
FLA
208-3-60
23.0
160
36.0
4.5
230-3-60
23.0
160
36.0
4.3
460-3-60
12.2
87
19.0
2.2
575-3-60
8.6
62
13.5
1.7
1.
2.
3.
MCA1
(Amps)
140
149
168
184
137
144
162
177
72
75
84
91
52
55
62
69
Max Fuse2/
Breaker3
Size
(Amps)
150
175
200
225
150
150
200
225
80
80
100
110
60
60
70
90
OD Fan Motors
Supply Blower
Motor
Qty
HP
FLA
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
Voltage
Qty
RLA
LRA
MCC
FLA
208-3-60
25.0
164
39.0
5.8
230-3-60
25.0
164
39.0
5.2
460-3-60
12.2
100
19.0
2.6
575-3-60
9.0
78
14.0
2.2
1.
2.
3.
MCA1
(Amps)
162
181
197
217
156
173
188
206
78
87
94
103
59
66
72
79
Max Fuse2/
Breaker3
Size
(Amps)
175
225
250
250
175
200
225
250
90
100
110
125
60
80
90
100
47
355278-JTG-D-0110
OD Fan Motors
Supply Blower
Motor
HP
FLA
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
Voltage
Qty
RLA
LRA
MCC
Qty
FLA
208-3-60
30.1
225
47.0
5.8
230-3-60
30.1
225
47.0
5.2
460-3-60
16.7
114
26.0
2.6
575-3-60
12.2
80
19.0
2.2
1.
2.
3.
48
MCA1
(Amps)
182
201
218
237
177
194
209
228
98
105
112
121
72
79
85
91
Max Fuse2/
Breaker3
Size
(Amps)
200
225
250
300
200
225
250
250
110
125
125
150
80
90
100
110
355278-JTG-D-0110
Compressors
(each)
Voltage
Qty
RLA
LRA
MCC
FLA
208-3-60
23.0
160
36.0
4.5
230-3-60
23.0
160
36.0
4.3
460-3-60
12.2
87
19.0
2.2
575-3-60
8.6
62
13.5
1.7
1.
2.
3.
Supply Blower
Motor
MCA1
(Amps)
HP
FLA
Option
KW
Applied
Stages
Amps
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
24.2
30.8
46.2
59.4
24.2
30.8
46.2
59.4
22.0
28.0
42.0
54.0
22.0
28.0
42.0
54.0
11.0
14.0
21.0
27.0
11.0
14.0
21.0
27.0
11.0
14.0
21.0
27.0
9.0
11.0
17.0
22.0
9.0
11.0
17.0
22.0
9.0
11.0
17.0
22.0
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
40
40
40
40
80
80
80
80
40
40
40
40
80
80
80
80
40
40
40
40
80
80
80
80
108
108
108
108
40
40
40
40
80
80
80
80
108
108
108
108
30
30
30
30
60
60
60
60
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
3
3
3
3
1
1
1
1
2
2
2
2
3
3
3
3
83.4
83.4
83.4
83.4
166.8
166.8
166.8
166.8
92.2
92.2
92.2
92.2
184.4
184.4
184.4
184.4
46.1
46.1
46.1
46.1
92.2
92.2
92.2
92.2
124.5
124.5
124.5
124.5
40.2
40.2
40.2
40.2
80.3
80.3
80.3
80.3
108.4
108.4
108.4
108.4
140
149
168
184
197
205
225
241
148
155
173
188
220
227
245
260
76
80
89
96
110
114
122
130
144
147
156
164
59
62
69
78
88
91
98
104
115
118
125
136
Max Fuse2/
Breaker3
Size
(Amps)
150
175
200
225
225
225
250
300
150
175
200
225
250
250
250
300
80
90
100
110
125
125
125
150
175
175
175
175
60
70
70
90
100
100
110
125
125
150
150
150
49
355278-JTG-D-0110
Compressors
(each)
Voltage
Qty
RLA
LRA
MCC
FLA
208-3-60
25.0
164
39.0
5.8
230-3-60
25.0
164
39.0
5.2
460-3-60
12.2
100
19.0
2.6
575-3-60
9.0
78
14.0
2.2
1.
2.
3.
50
Supply Blower
Motor
MCA1
(Amps)
HP
FLA
Option
KW
Applied
Stages
Amps
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
40
40
40
40
80
80
80
80
40
40
40
40
80
80
80
80
40
40
40
40
80
80
80
80
108
108
108
108
40
40
40
40
80
80
80
80
108
108
108
108
30
30
30
30
60
60
60
60
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
3
3
3
3
1
1
1
1
2
2
2
2
3
3
3
3
83
83
83
83
167
167
167
167
92
92
92
92
184
184
184
184
46
46
46
46
92
92
92
92
125
125
125
125
40
40
40
40
80
80
80
80
108
108
108
108
162
181
197
217
205
225
241
260
156
173
188
206
227
245
260
277
78
87
94
103
114
122
130
139
147
156
164
172
62
69
76
82
91
98
104
111
118
129
131
142
Max Fuse2/
Breaker3
Size
(Amps)
175
225
250
250
225
250
300
300
175
200
225
250
250
250
300
300
90
100
110
125
125
125
150
150
175
175
175
200
70
80
90
100
100
110
125
125
150
150
150
150
355278-JTG-D-0110
Compressors
(each)
Voltage
Qty
RLA
LRA
MCC
FLA
208-3-60
30.1
225
47.0
5.8
230-3-60
30.1
225
47.0
5.2
460-3-60
16.7
114
26.0
2.6
575-3-60
12.2
80
19.0
2.2
1.
2.
3.
Supply Blower
Motor
MCA1
(Amps)
HP
FLA
Option
KW
Applied
Stages
Amps
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
40
40
40
40
80
80
80
80
40
40
40
40
80
80
80
80
40
40
40
40
80
80
80
80
108
108
108
108
40
40
40
40
80
80
80
80
108
108
108
108
30
30
30
30
60
60
60
60
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
3
3
3
3
1
1
1
1
2
2
2
2
3
3
3
3
83
83
83
83
167
167
167
167
92
92
92
92
184
184
184
184
46
46
46
46
92
92
92
92
125
125
125
125
40
40
40
40
80
80
80
80
108
108
108
108
182
201
218
237
205
225
241
260
177
194
209
226
227
245
260
277
97
105
112
121
114
122
130
139
147
156
164
172
72
79
85
91
91
98
104
111
118
125
131
138
Max Fuse2/
Breaker3
Size
(Amps)
200
225
250
300
225
250
300
300
200
225
250
250
250
250
300
300
110
125
125
150
125
125
150
150
175
175
175
200
80
90
100
110
100
110
125
125
150
150
150
150
51
355278-JTG-D-0110
208-3-60
230-3-60
460-3-60
575-3-60
1.
2.
3.
52
OD Fan
Motors
(each)
Compressors
(each)
RLA
23.0
23.0
12.2
8.6
LRA
160
160
87
62
MCC
36.0
36.0
19.0
13.5
FLA
Supply Blower
Motor
HP
FLA
7.5
24.2
10
30.8
15
46.2
20
59.4
7.5
22.0
10
28.0
15
42.0
20
54.0
7.5
11.0
10
14.0
15
21.0
20
27.0
7.5
9.0
10
11.0
15
17.0
20
22.0
4.5
4.3
2.2
1.7
FLA
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
MCA1
(Amps)
157
165
173
165
173
180
185
192
199
201
209
215
152
159
166
159
166
172
177
184
190
192
199
205
79
83
86
83
86
89
91
95
98
99
102
105
59
61
64
61
64
66
69
71
73
75
78
80
Max Fuse2/
Breaker3
Size
(Amps)
175
175
200
175
200
200
225
225
225
250
250
250
175
175
175
175
175
200
200
225
225
225
250
250
90
90
100
90
100
100
110
110
110
125
125
125
60
70
70
70
70
70
80
80
90
90
90
100
355278-JTG-D-0110
208-3-60
230-3-60
460-3-60
575-3-60
1.
2.
3.
OD Fan
Motors
(each)
Compressors
(each)
RLA
25.0
25.0
12.2
9.0
LRA
164
164
100
78
MCC
39.0
39.0
19.0
14.0
Qty
Supply Blower
Motor
FLA
HP
FLA
10
30.8
15
46.2
20
59.4
25
74.8
10
28.0
15
42.0
20
54.0
25
68.0
10
14.0
15
21.0
20
27.0
25
34.0
10
11.0
15
17.0
20
22.0
25
27.0
5.8
5.2
2.6
2.2
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
22
28
42
22
28
42
22
28
42
22
28
42
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
MCA1
(Amps)
186
193
212
205
212
227
222
228
244
241
248
263
178
184
201
195
201
215
210
216
230
228
234
248
89
92
101
98
101
108
105
108
115
114
117
124
68
70
77
75
77
83
81
83
89
88
90
96
Max Fuse2/
Breaker3
Size
(Amps)
200
200
250
250
250
250
250
250
300
300
300
300
200
200
225
225
225
250
250
250
250
250
300
300
100
100
110
110
110
125
125
125
125
125
150
150
70
80
90
90
90
100
100
100
110
110
110
110
53
355278-JTG-D-0110
208-3-60
230-3-60
460-3-60
575-3-60
1.
2.
3.
54
OD Fan
Motors
(each)
Compressors
(each)
RLA
30.1
30.1
16.7
12.2
LRA
225
225
114
80
MCC
47.0
47.0
26.0
19.0
Qty
Supply Blower
Motor
FLA
HP
FLA
10
30.8
15
46.2
20
59.4
25
74.8
10
28.0
15
42.0
20
54.0
25
68.0
10
14.0
15
21.0
20
27.0
25
34.0
10
11.0
15
17.0
20
22.0
25
27.0
5.8
5.2
2.6
2.2
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
24
31
46
24
31
46
24
31
46
24
31
46
22
28
42
22
28
42
22
28
42
22
28
42
11
14
21
11
14
21
11
14
21
11
14
21
9
11
17
9
11
17
9
11
17
9
11
17
MCA1
(Amps)
206
213
232
226
232
248
242
249
264
261
268
283
199
205
222
216
222
236
231
237
251
248
254
268
108
111
119
116
119
126
123
126
133
132
135
142
81
83
90
88
90
96
94
96
102
100
102
108
Max Fuse2/
Breaker3
Size
(Amps)
225
225
250
250
250
250
300
300
300
300
300
350
225
225
250
250
250
250
250
250
300
300
300
300
110
125
125
125
125
150
150
150
150
150
150
175
90
90
100
100
100
110
110
110
110
125
125
125
355278-JTG-D-0110
TABLE 50: ELECTRICAL DATA 25 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A
Compressors
(each)
E4
KW
40
Stages
Amps
83.4
Qty
RLA
23.0
LRA
160
OD Fan Motors
(each)
MCC
36.0
Qty
FLA
Supply Blower
Motor
HP
FLA
7.5
24.2
10
30.8
15
46.2
20
59.4
7.5
24.2
10
30.8
15
46.2
20
59.4
7.5
22.0
10
28.0
15
42.0
20
54.0
7.5
22.0
10
28.0
15
42.0
20
54.0
4.5
208-3-60
E8
E4
80
40
166.8
92.2
23.0
23.0
160
160
36.0
36.0
4.5
4.3
230-3-60
E8
80
184.4
23.0
160
36.0
4.3
FLA
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
MCA1
(Amps)
157
165
173
165
173
180
185
192
199
201
209
215
214
221
229
222
229
236
241
249
255
258
265
272
163
170
177
170
177
183
188
195
201
203
210
216
235
242
249
243
249
255
260
267
273
275
282
288
Max Fuse2/
Breaker3
Size
(Amps)
175
175
200
175
200
200
225
225
225
250
250
250
225
225
250
250
250
250
250
250
300
300
300
300
175
175
200
175
200
200
200
225
225
225
250
250
250
250
250
250
250
300
300
300
300
300
300
300
55
355278-JTG-D-0110
TABLE 50: ELECTRICAL DATA 25 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A (CONT.)
Compressors
(each)
E4
460-3-60
E8
E1
56
KW
40
80
108
Stages
Amps
46.1
92.2
124.5
Qty
RLA
12.2
12.2
12.2
LRA
87
87
87
OD Fan Motors
(each)
MCC
19.0
19.0
19.0
Qty
FLA
Supply Blower
Motor
HP
FLA
7.5
11.0
10
14.0
15
21.0
20
27.0
7.5
11.0
10
14.0
15
21.0
20
27.0
7.5
11.0
10
14.0
15
21.0
20
27.0
2.2
2.2
2.2
FLA
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
7.6
11.0
14.0
MCA1
(Amps)
84
87
91
88
91
94
96
100
103
104
107
110
118
121
125
121
125
128
130
133
136
138
141
144
151
155
158
155
158
161
164
167
170
171
175
178
Max Fuse2/
Breaker3
Size
(Amps)
90
90
100
100
100
100
110
110
110
125
125
125
125
125
125
125
125
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
175
175
200
200
355278-JTG-D-0110
TABLE 50: ELECTRICAL DATA 25 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A (CONT.)
Compressors
(each)
E4
575-3-60
E8
E1
1.
2.
3.
KW
40
80
108
Stages
Amps
40.2
80.3
108.4
Qty
RLA
8.6
8.6
8.6
LRA
62
62
62
OD Fan Motors
(each)
MCC
13.5
13.5
13.5
Qty
FLA
Supply Blower
Motor
HP
FLA
7.5
9.0
10
11.0
15
17.0
20
22.0
7.5
9.0
10
11.0
15
17.0
20
22.0
7.5
9.0
10
11.0
15
17.0
20
22.0
1.7
1.7
1.7
FLA
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
6.1
9.0
11.0
MCA1
(Amps)
69
68
75
68
71
73
75
78
80
82
85
87
94
97
100
97
100
102
104
107
109
111
113
122
121
124
127
124
127
129
131
134
136
138
140
149
Max Fuse2/
Breaker3
Size
(Amps)
70
70
80
70
80
80
80
80
90
90
90
100
100
100
110
100
110
110
110
110
125
125
125
125
150
150
150
150
150
150
150
150
150
150
150
150
57
355278-JTG-D-0110
TABLE 51: ELECTRICAL DATA 30 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A
Compressors
(each)
E4
KW
40
Stages
Amps
83.4
Qty
RLA
25.0
LRA
164
OD Fan Motors
(each)
MCC
39.0
Qty
FLA
Supply Blower
Motor
HP
FLA
10
30.8
15
46.2
20
59.4
25
74.8
10
30.8
15
46.2
20
59.4
25
74.8
10
28.0
15
42.0
20
54.0
25
68.0
10
28.0
15
42.0
20
54.0
25
68.0
5.8
208-3-60
E8
E4
80
40
166.8
92.2
25.0
25.0
164
164
39.0
39.0
5.8
5.2
230-3-60
E8
58
80
184.4
25.0
164
39.0
5.2
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
MCA1
(Amps)
186
193
212
205
212
227
222
228
244
241
248
263
229
236
255
249
255
271
265
272
287
284
291
308
178
184
201
195
201
215
210
216
230
228
234
248
249
255
273
267
273
287
282
288
302
299
305
319
Max Fuse2/
Breaker3
Size
(Amps)
200
200
250
250
250
250
250
250
300
300
300
300
250
250
300
250
300
300
300
300
300
350
350
350
200
200
225
225
225
250
250
250
250
250
300
300
250
300
300
300
300
300
300
300
350
350
350
350
355278-JTG-D-0110
TABLE 51: ELECTRICAL DATA 30 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A (CONT.)
Compressors
(each)
E4
460-3-60
E8
E1
KW
40
80
108
Stages
Amps
46.1
92.2
124.5
Qty
RLA
12.2
12.2
12.2
LRA
100
100
100
OD Fan Motors
(each)
MCC
19.0
19.0
19.0
Qty
FLA
Supply Blower
Motor
HP
FLA
10
14.0
15
21.0
20
27.0
25
34.0
10
14.0
15
21.0
20
27.0
25
34.0
10
14.0
15
21.0
20
27.0
25
34.0
2.6
2.6
2.6
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
MCA1
(Amps)
89
92
101
98
101
108
105
108
115
114
117
124
125
128
136
133
136
143
141
144
151
150
153
160
158
161
170
167
170
177
175
178
185
183
186
193
Max Fuse2/
Breaker3
Size
(Amps)
100
100
110
110
110
125
125
125
125
125
150
150
125
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
175
200
200
200
200
200
200
225
59
355278-JTG-D-0110
TABLE 51: ELECTRICAL DATA 30 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A (CONT.)
Compressors
(each)
E4
575-3-60
E8
E1
1.
2.
3.
60
KW
40
80
108
Stages
Amps
40.2
80.3
108.4
Qty
RLA
9.0
9.0
9.0
LRA
78
78
78
OD Fan Motors
(each)
MCC
14.0
14.0
14.0
Qty
FLA
Supply Blower
Motor
HP
FLA
10
11.0
15
17.0
20
22.0
25
27.0
10
11.0
15
17.0
20
22.0
25
27.0
10
11.0
15
17.0
20
22.0
25
27.0
2.2
2.2
2.2
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
MCA1
(Amps)
71
73
80
78
80
86
85
87
93
91
93
99
100
102
109
107
109
115
113
115
121
120
122
128
127
129
136
134
136
142
140
142
148
147
149
155
Max Fuse2/
Breaker3
Size
(Amps)
80
80
90
90
90
100
100
100
110
110
110
110
110
110
125
110
125
125
125
125
125
125
125
150
150
150
150
150
150
150
150
150
150
150
175
175
355278-JTG-D-0110
TABLE 52: ELECTRICAL DATA 40 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A
Compressors
(each)
E4
KW
40
Stages
Amps
83.4
Qty
RLA
30.1
LRA
225
OD Fan Motors
(each)
MCC
47.0
Qty
FLA
Supply Blower
Motor
HP
FLA
10
30.8
15
46.2
20
59.4
25
74.8
10
30.8
15
46.2
20
59.4
25
74.8
10
28.0
15
42.0
20
54.0
25
68.0
10
28.0
15
42.0
20
54.0
25
68.0
5.8
208-3-60
E8
E4
80
40
166.8
92.2
30.1
30.1
225
225
47.0
47.0
5.8
5.2
230-3-60
E8
80
184.4
30.1
225
47.0
5.2
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
24
31
46
24
31
46
24
31
46
24
31
46
24
31
46
24
31
46
24
31
46
24
31
46
22
28
42
22
28
42
22
28
42
22
28
42
22
28
42
22
28
42
22
28
42
22
28
42
MCA1
(Amps)
206
213
232
226
232
248
242
249
264
261
268
283
229
236
255
249
255
271
265
272
287
284
291
306
199
205
222
216
222
236
231
237
251
248
254
268
249
255
273
267
273
287
282
288
302
299
305
319
Max Fuse2/
Breaker3
Size
(Amps)
225
225
250
250
250
250
300
300
300
300
300
350
250
250
300
250
300
300
300
300
300
350
350
350
225
225
250
250
250
250
250
250
300
300
300
300
250
300
300
300
300
300
300
300
350
350
350
350
61
355278-JTG-D-0110
TABLE 52: ELECTRICAL DATA 40 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A (CONT.)
Compressors
(each)
E4
460-3-60
E8
E1
62
KW
40
80
108
Stages
Amps
46.1
92.2
124.5
Qty
RLA
16.7
16.7
16.7
LRA
114
114
114
OD Fan Motors
(each)
MCC
26.0
26.0
26.0
Qty
FLA
Supply Blower
Motor
HP
FLA
10
14.0
15
21.0
20
27.0
25
34.0
10
14.0
15
21.0
20
27.0
25
34.0
10
14.0
15
21.0
20
27.0
25
34.0
2.6
2.6
2.6
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
11
14
21
11
14
21
11
14
21
11
14
21
11
14
21
11
14
21
11
14
21
11
14
21
11
14
21
11
14
21
11
14
21
11
14
21
MCA1
(Amps)
108
111
119
116
119
126
123
126
133
132
135
142
125
128
136
133
136
143
141
144
151
150
153
160
158
161
170
167
170
177
175
178
185
183
186
193
Max Fuse2/
Breaker3
Size
(Amps)
110
125
125
125
125
150
125
150
150
150
150
175
125
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
175
200
200
200
200
200
200
200
355278-JTG-D-0110
TABLE 52: ELECTRICAL DATA 40 TON w/ELECTRIC HEAT and POWER EXHAUST R-410A (CONT.)
Compressors
(each)
E4
575-3-60
E8
E1
1.
2.
3.
KW
40
80
108
Stages
Amps
40.2
80.3
108.4
Qty
RLA
12.2
12.2
12.2
LRA
80
80
80
OD Fan Motors
(each)
MCC
19.0
19.0
19.0
Qty
FLA
Supply Blower
Motor
HP
FLA
10
11.0
15
17.0
20
22.0
25
27.0
10
11.0
15
17.0
20
22.0
25
27.0
10
11.0
15
17.0
20
22.0
25
27.0
2.2
2.2
2.2
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
MCA1
(Amps)
81
83
90
88
90
96
94
96
102
100
102
108
100
102
109
107
109
115
113
115
121
120
122
128
127
129
136
134
136
142
140
142
148
147
156
155
Max Fuse2/
Breaker3
Size
(Amps)
90
90
100
100
100
110
110
110
110
125
125
125
110
110
125
110
125
125
125
125
125
150
150
150
150
150
150
150
150
150
150
150
150
150
175
175
63
355278-JTG-D-0110
25 TON
30 TON
Basic Unit
4410
4565
Gas Heat
267 MBH
180
180
533 MBH
320
320
800 MBH
Electric Heat
40KW
40
40
80KW
105
105
108KW
110
110
Hot Water Heat
1 Row Coil
70
70
2 Row Coil
85
85
Steam Heat
1 Row Coil
85
85
Blower
Forward Curve Fan (Std Fan)
0
0
FC IGV
155
155
Air Foil Fan
135
135
AF IGV
155
155
Motor - Supply Fan
7.5hp
110
10hp
145
145
15hp
200
200
20hp
240
240
25hp
300
Supply Fan Motor VFD
See Table 54
Refrigeration
T-Coat Evap.
32
30
T-Coat cond.
32
30
Hot Gas Bypass
10
10
Low Ambient Head Pressure Control
208-230/380/460
5
5
575
25
25
Filters
6" Rigid
70
70
40 TON
4845
230V
460V
575V
W/O Bypass
180
320
450
7.5hp
60
25
30
10hp
60
25
30
15hp
75
50
60
40
105
110
20hp
75
50
60
25hp
115
50
60
70
85
7.5hp
155
90
120
10hp
155
90
120
85
15hp
185
140
155
20hp
185
140
155
25hp
255
140
155
0
175
155
180
W/Bypass
145
200
240
300
40
40
10
230V
460V
575V
W/O Bypass
5hp
15
10
20
7.5hp
50
15
20
10hp
50
15
20
15hp
65
40
50
NOTE: If the unit is VAV with ERV, add the weight of an exhaust
VFD - it will be in the unit.
5
25
70
Exhaust1
Exhaust Type
Barometric
Modulated
Exhaust Motor
5hp
7.5hp
10hp
15hp
Exhaust Motor VFD
Std. Econ.
Econ. w/ERV
Disconnect
110V outlet
Optilogic
Partial Curb
1.
64
45
140
65
275
65
275
80
110
145
200
80
110
145
200
See Table 55
80
110
145
200
235
50
235
50
15
55
20
15
55
20
415
415
Economizer
235
50
Control
15
55
20
Roof Curb
415
If ERV and Supply Fan VAV are selected, add the weight of an
Exhaust VFD, Table 54.
MODEL
BASIC UNIT
BASIC UNIT /W
ECON.
BASIC UNIT /W
ECON. & GAS OR
ELECT. HEAT,
STEAM OR HOT
WATER HEAT
BASIC UNIT /W
ECON. & GAS OR
ELECT. HEAT, &
POWER EXHAUST
25 TON
X*
Y
99
48
30 TON
X*
Y
100
47
40 TON
X*
Y
96
46"
110
48
110
47
100
46"
104
48
104
46
99
45"
118
47
114
46
111
45"
355278-JTG-D-0110
A
870
25 TON
B
C
949
1352
D
1239
A
930
B
972
30 TON
C
1360
D
1303
A
969
B
969
40 TON
C
1454
D
1454
1018
1111
1313
1203
1076
1124
1328
1272
1058
1058
1482
1482
994
1084
1418
1300
1073
1073
1403
1403
1102
1055
1503
1570
1220
1275
1318
1262
1275
1275
1410
1410
1335
1278
1485
1551
CFM
10,000
12750
17500
ESP
IWG
1.5
1.5
1.3
BLOWER
RPM
750
840
800
BHP
7.5
12.8
20
63
90
93
95
8000
68
71
72
dba
87
90
91
The sound ratings above occur at the blower wheel. To determine the sound rating at a units supply and return air duct
connection, subtract the attenuation factors listed below.
63
11
13
125
4000
8000
13
15
23
29
23
29
18
22
21
25
65
355278-JTG-D-0110
65
125
250
V32
V33
V34
88
87
88
91
90
91
89
88
89
4000
8000
db(A)
76
77
77
72
73
73
88
88
88
66
355278-JTG-D-0110
67
355278-JTG-D-0110
68
355278-JTG-D-0110
69
355278-JTG-D-0110
70
355278-JTG-D-0110
259.68
35.42
39.31
93.43
241.22
CONDENSER SECTION
BLOWER
SECTION
EVAPORATOR
SECTION
FILTER
SECTION
ECONOMIZER POWER
EXHAUST SECTION
255.00
40 TON ONLY
15.00
15.00
71
355278-JTG-D-0110
Hinged,
Tool-Free
Door
Optional
Hinged,
Tool-Free
Door
Hinged,
Tool-Free
Door
Hinged, Tool-Free
w/PE Option
BACK VIEW
Hinged,
Tool-Free
Door
Optional
Hinged,
Tool-Free
Door
Hinged,
Tool-Free
Door
Hinged,
Tool-Free
w/Gas
or Other
Heat Source
Hinged, Tool-Free
w/PE Option
FRONT VIEW
1. STD Cabinet Option includes Hinged, Tool-Free
Doors # 1, 3, 6, 8.
72
355278-JTG-D-0110
73
355278-JTG-D-0110
2 3 5 .0 0
9 5 .0 9
3 8 .5 9
7 1 .6 1
R E T U R N
A IR
O P E N IN G
8 3 .0 0
2 6 .0 0
S U P P L Y
A IR
O P E N IN G
8 7 .0 0
1 1 .3 9
4 .0 0
2 .0 0
1 4 .0 0
In s u la tio
P ro te
(S h e e t
N o s e P
n E
c to
M e
ie c
r
d g e
ta l
e )
A
A
F IE L D
S U P P L IE D
D U C T
T y p ic a l In s u la tio n
B
A
S E E S E C T IO N "A -A "
- IF
- IF
U N IT
U N IT
IS
IS
N O T IN S T A L L E D
A L R E A D Y IN S T A L L E D
N O T E : P r o te c t in s u la tio n w ith a s h e e t m e ta l
n o s e p ie c e w h e n in s ta llin g a in te r n a lly in s u la te d
d u c t w o rk .
T Y P IC A L D U C T IN S T A L L A T IO N S
B A S E R A IL
(Y O R K U N IT )
C U R B G A S K E T
B A S E R A IL C R O S S -S E C T IO N
1 .2 5 "
1 .7 5 "
4 .6 3 "
2 " X 4 "
N A IL E R
2 .5 0 "
1 .5 0 "
(1 4 .0 0 )
1 4 G A . G A L V S T E E L
R O O F C U R B
2 .0 0 "
S E C T IO N "A -A "
74
355278-JTG-D-0110
DESCRIPTION
Supply Johnson Controls Series 40 packaged rooftop system
in accordance with the capacities in the plans. Units shall be
rated by the manufacturer at a minimum 10.5 EER according
to ARI 360. Units shall be shipped in a single package, fully
charged with R-410A refrigerant. The manufacturing facility
shall be registered under ISO 9001 Quality Standards for
Manufacturing. Units shall carry both ETL and CSA safety
approval ratings. Tags and decals to aid in the service or indicate caution areas shall be provided. Installation and maintenance manuals shall be supplied with each unit. Units shall
be capable of providing mechanical cooling down to 40F
(0F with low ambient kit). Unit shall be capable of starting
and running at 125F. Unit electric and gas connections shall
be either through the curb or the side of the unit.
CONSTRUCTION
Base
The base rail shall be constructed of 12 gauge galvanized
steel, extending the full perimeter of the unit. All components
shall be supported from the base, and the base shall include
integral lifting lugs. The unit base rail shall overhang the roof
curb for water runoff and shall have a fabricated recess with a
continuous flat surface to seat on the roof curb gasket, providing a positive, weather tight seal between the unit and the
curb.
Casing
The unit cabinet shall be double wall construction to provide
both maximum resistance to bacterial growth in the air stream
and superior structural integrity. All sheet metal shall be G90
mill galvanized sheet metal, formed and reinforced to provide
a rigid assembly. Sheet metal shall be cleaned in an alkaline
and zinc phosphate bath, and the exterior surfaces shall be
coated with a 1.5 mil powder paint, capable of withstanding
75
355278-JTG-D-0110
General
Outside Air inlet openings shall be covered by a factory
installed rain hood permanently attached to the cabinet to
prevent windblown precipitation from entering the unit. The
rain hoods on the front and back of the unit shall be rotated
into the cabinet and secured for shipment so that upon installation they need only be rotated upwards and screwed into
place. The outside air hood shall contain a removable and
cleanable filter with an efficiency rating of 50% based on
ASHRAE 52- 76. All damper assemblies shall be of low leak
design. Damper blades shall be fabricated from a minimum of
16 gauge galvanized steel. Blade ends and edges shall be
covered with vinyl seals. Damper shafts shall be fabricated
from solid steel and mounted in the frame with bronze bearings.
Economizer (Optional)
An economizer shall have outdoor air and return air dampers
that are interlocked and positioned by fully modulating, solid
state damper actuators. The actuators shall be spring loaded
so that the outside air damper will close when power to the
unit is interrupted. The operation of the economizer shall be
fully integrated into the cooling control system. The economizer shall be available for control via a dry bulb sensor
(Optional: single or dual enthalpy sensors).
RELIEF SYSTEM (Optional)
All units with relief must have an economizer.
76
HEATING SYSTEM
Gas-fired Heating Section (Optional)
One or more gas-fired heating modules shall be installed to
provide the heating requirements per the schedule shown on
the plans. The heat exchanger shall be of tubular design.
Tubes shall be 2-1/4 OD and constructed of minimum 20
gauge, G160 aluminized steel (1.6 mil aluminum silicone
alloy) for corrosion resistance (Optional: 409 Stainless Steel).
355278-JTG-D-0110
Flue baffles shall be made of 430 stainless steel. Each gasfired heat module shall have an induced draft combustion fan
with energy efficient intermittent pilot spark ignition and
redundant main gas valves with pressure regulator. Units with
standing pilot ignition shall not be acceptable. An induced
draft fan shall be provided to maintain a positive flow of air
through each tube, to expel the flue gas and to maintain a
negative pressure within the heat exchanger relative to the
conditioned space. Induced draft fans shall be direct-drive.
One (1) high limit controller per heating module, with automatic reset to prevent the heat exchanger from operating at
an excessive temperature will be installed. A pressure switch
on the combustion section must be provided to prevent ignition until sufficient air flow is established through the heat
exchanger. Secondary airflow safety shall be provided by rollout switch protection. The rollout switch shall discontinue furnace operation if the flue becomes restricted. Units shall ship
with an external flue to be shipped in the unit and mounted on
the job site. The flue shall discharge products of combustion
above the unit, preventing recycling of corrosive combustion
gases back through the heat exchanger. Gas heating sections shall be both ETL and CSA approved to both US and
Canadian safety standards.
Optional Modulating Furnace control or Single Stage control
available.
Electric Heating Section
An electric slip-in heater shall be installed within the rooftop
unit to provide the heating requirements per the schedule
shown on the plans. The electric heater shall be wired in such
a manner as to provide two equal steps of capacity (80 and
108 kW) or a single step of capacity (40 kW). The furnace
shall be an industrial grade design using an open coil(s)
made of the highest grade resistance wire containing 80%
nickel and 20% chromium. The resistance coil(s) shall be
adequately supported in the air stream using ceramic bushings in the supporting framework. Terminals of the coil(s)
shall be stainless steel with high temperature ceramic bushings. The primary high temperature protection shall be an
automatic reset type thermal cut out. Secondary protection
shall be an automatic reset type thermal cut out. Secondary
protection shall be a replaceable thermal link. The operation
of the electric heater shall be an integral part of the roof top
control system. Power connection to the strip heater shall be
through the single power point connection for the entire unit.
Electric heat shall be ETL certified to both US and Canadian
safety standards.
Hot Water Heating Coil
The manufacturer shall furnish and factory install a hot water
coil in the rooftop units, as described in the following specifications. Water coil capacities and pressure drops shall be
certified in accordance with ARI Standard 410. The hot water
coil shall have eight fins per inch, 2 tubes per circuit, and 2"
inlet and outlet connection. Primary surface shall be 1/2" OD
copper tube, staggered in direction of airflow. Tubes shall be
mandrel expanded to form fin bond and provide burnished,
REFRIGERATION SYSTEM
Units shall have four independent refrigerant circuits for maximum load-matching capability. Each refrigerant circuit shall
be controlled with a balance-port thermal expansion valve for
maximum control at low load conditions.
Evaporator Coils
Evaporator coils shall be direct expansion type with intertwined circuiting to assure complete coil face activity during
part load operation. Coil fins shall be enhanced aluminum
77
355278-JTG-D-0110
Refrigerant Piping
Compressors
Units shall have four industrial duty hermetic scroll compressors, independently piped and charged. Compressors shall
have an enlarged liquid carrying capacity to withstand rugged
operating conditions. Compressor frame shall be cast iron,
with cast iron fixed and orbiting scrolls. Each compressor
shall feature a solid state protection module, designed to protect the compressor from over temperature and overcurrent
conditions. Each compressor shall include the following
safety and convenience devices: replaceable suction screen,
discharge line check valve, and oil sight glass. Compressors
shall be vibration isolated from the unit, and installed in an
easily accessible area of the unit.
Condenser Coils
CONTROLS
GENERAL DESCRIPTION
The control shall monitor the High Pressure switch, the Low
Pressure switch, and the Compressor Overloads separately
for each refrigeration circuit. The control shall have a 30 second Low Pressure Switch bypass when it starts any compressor.
Condenser fans shall be direct drive, propeller type, discharging vertically. Condenser fan motors shall be 3 phase, totally
enclosed air over (TEAO) type, with built in thermal overload
protection.
78
355278-JTG-D-0110
79
355278-JTG-D-0110
The control will use two setpoints for Supply Air Temperature
for the Economizer operation. One will be for a small space
cooling demand and one for a large space cooling demand.
The control will have the ability to do Demand Ventilation
using one CO2 sensor.
The control will have a programmable maximum Outside Air
Damper Position for IAQ operation.
The control will have the ability to temper the ventilation air
during times when heating or cooling is not required.
The control will have the ability to offset the operating setpoint based on high Humidity in the Space.
The control will use a Wall Senor that has a means of overriding the unoccupied mode for a programmable amount of
time.
The control must be able to lockout Cooling below a programmable Outside Air Temperature Setpoint.
The control will be able to lockout Heating above a programmable Outside Air Temperature Setpoint.
The control will have a Space Temperature Alarm.
The control will have a Supply Air Temperature Alarm for
Heating and Cooling. The Alarm temperature will be programmable
The control will use the Return Air Sensor in place of the
Space Sensor if the Space Sensor fails for any reason, the
control will have a 365 day Real Time Clock.
The control will have the ability to read a dirty filter switch.
The control will have the capability of reading a Fan proving
switch.
The control will have an intelligent recovery function that will
bring the space to the Occupied Setpoint just before or at the
beginning of the first Occupied schedule each day. The control will learn and apply the minimum run time required to heat
or cool the space to setpoint for the first Occupied period of a
day.
The control will have Software controllable Mode Switches
(Heat, Cool, and Fan).
The control will meter and track Unoccupied Override Time
for billing purposes.
80
355278-JTG-D-0110
Burglar Bars
Overview
Programmable thermostat, with or without remote sensor (required for constant volume units)
OPTIONAL CONTROL
Johnson Commercial Comfort System (CCS)
Contains the necessary orifices and gas valve parts to convert from natural gas to propane. Propane cannot be used on
modulating gas heat units.
AVAILABLE ACCESSORIES
81
355278-JTG-D-0110
Supersedes: 355278-JTG-C-0509