FIRE DETECTION AND ALARM SYSTEMS

PART 3: FIRE DETECTION AND ALARM SYSTEMS


Fire maims, kills and destroys. Fire Protection products that are correctly designed, manufactured, installed and maintained can save lives and property. We recommend that specifiers select/recommend the following: Products that are tested and approved by LPCB to an appropriate standard eg. smoke detectors to EN 54-7, heat detectors to EN 54-5 (refer to Sections 3, 4, 5, 6, 7) Fire and alarm systems that are tested and approved for system compatibility by LPCB to an appropriate standard eg. control and indicating equipment, power supply, detectors, sounders are tested and approved to their appropriate standard and then tested together against EN 54-13 or LPS 1054 (refer to Section 2) Companies that are approved and take single point responsibility for design, installation and commissioning. The LPS 1014 scheme ensures companies are able to design, install and commission a fire detection and alarm systems against an appropriate code of practice such as BS 5839-1, BS 5839-8 etc.

For maximum protection, you should look for all three of the elements above. In other words, companies approved to design, install and commission LPCB approved products and systems.

January 2009

SECTION 1: PART

LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

WHY USE AN LPS 1014 APPROVED COMPANY? Even with the best equipment, fire detection and alarm systems are only effective if correctly designed, installed, commissioned and maintained. It is therefore important that specifiers select only competent firms with a proven track record to undertake the work. LPS 1014 Requirements for Certificated Fire Detection and Alarm System Firms meets these requirements in full. LPS 1014 requires one encompassing Certificate of Conformity for the project, i.e. single point responsibility, which benefits all parties concerned, i.e. the insurer, the fire brigade, the building owner, etc. It is based on BS 5839-1 and also requires, where available, the use of third party approved products. For each system specifiers should request the issue of an LPCB Certificate of Conformity as part of the contract which: certifies that the fire detection and fire alarm system was designed, installed and commissioned in accordance with the installation rules applied, and ensures that the system is recorded by LPCB as a certificated fire detection and fire alarm installation.

The availability of more varied and sophisticated fire detection and alarm equipment means that it is even more important that firms listed to LPS 1014 are regularly assessed by LPCB for their competence to design, install, commission and service fire detection and fire alarm systems in accordance with acceptable installation rules or codes of practice. Where a firm has more than one office, each office is also required to meet the appropriate requirements of LPS 1014 to be eligible for certification, and is listed separately.

ADT Fire and Security


Security House, The Summit, Hanworth Road, Sunbury on Thames, Middlesex TW16 5DB UK Tel: +44 (0)1932 743456 Fax: +44 (0)1932 743222
Certificate No. CFA-105 to LPS 1014

ADT Fire and Security


ADT House, Unit 61, Stephenson Way, Wavertree Technology Park, Liverpool L13 1HD UK Tel: +44 (0)151 5514000 Fax: +44 (0)151 5514100 E-mail: dcarmstrong@tycoint.com Website: www.adt.co.uk
Certificate No. CFA-155 to LPS 1014

ADT Fire and Security


1 Bowling Green Terrace, Off Jack Lane, Leeds LS11 9SX UK Tel: +44 (0)1132 911000 Fax: +44 (0)1132 425933
Certificate No. CFA-110 to LPS 1014

January 2009

PART 3: SECTION 1
LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

ADT Fire and Security


180 Aztec West, Almondsbury, Bristol BS32 4TH UK Tel: +44 (0)1454 843434 Fax: +44 (0)1454 843484
Certificate No. CFA-107 to LPS 1014

ADT Fire and Security


ADT House, Mucklow Hill, Halesowen, Birmingham, West Midlands B62 8DA UK Tel: +44 (0)1212 556000 Fax: +44 (0)1212 556100
Certificate No. CFA-108 to LPS 1014

ADT Fire and Security


Quay House, City Park Business Village, Manchester M16 9UN UK Tel: +44 (0)1612 525500 Fax: +44 (0)1612 525688
Certificate No. CFA-109 to LPS 1014

ADT Fire and Security


Turnberry House, 100 Bunhill Row, London EC1Y 8ND UK Tel: +44 (0)2079 418700 Fax: +44 (0)2079 418717
Certificate No. CFA-119 to LPS 1014

ADT Fire and Security


ADT House, Tannochside Park, Uddingston, Glasgow G71 5PH UK Tel: +44 (0)1698 486000 Fax: +44 (0)1698 486100
Certificate No. CFA-113 to LPS 1014

ADT Fire and Security


Unit 8, Prospect Business Park, Langston Road, Loughton, Essex IG10 3TR UK Tel: +44 (0)2082 724700 Fax: +44 (0)2082 724709
Certificate No. CFA-112 to LPS 1014

January 2009

SECTION 1: PART

LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

ADT Fire and Security


ADT House, 5th Avenue Business Park, Team Valley Trading Estate, Gateshead, Tyne and Wear NE11 0HF UK Tel: +44 (0)1914 515000 Fax: +44 (0)1914 515001
Certificate No. CFA-111 to LPS 1014

Argus Fire Protection Company Limited


Hendglade House, 46 New Road, Stourbridge, West Midlands DY8 1PA UK Tel: +44 (0)1384 376256 Fax: +44 (0)1384 393955 E-mail: info@argusfire.co.uk Website: www.argusfire.co.uk
Certificate No. CFA-148 to LPS 1014

BBC Fire Protection Limited


St Florian House, Ayton Road, Wymondham, Norfolk NR18 0RA UK Tel: +44 (0)1953 857700 Fax: +44 (0)1953 857750 E-mail: sales@bbcfire.co.uk Website: www.bbcfire.co.uk
Certificate No. CFA-126 to LPS 1014

Chubb Fire Limited


2 Carlton Court, Brown Lane West, Leeds LS12 6LT UK Tel: +44 (0)113 2469641 Fax: +44 (0)113 2469634 E-mail: fire.leeds@chubb.co.uk Website: www.chubb.co.uk
Certificate No. CFA-120 to LPS 1014

Chubb Fire Limited


Chubb House, Staines Road West, Sunbury-on-Thames, Middlesex TW16 7AR UK Tel: +44 (0)1932 785588 Fax: +44 (0)1932 777222 E-mail: Feltham.firesystems@chubb.co.uk Website: www.chubb.co.uk
Certificate No. CFA-121 to LPS 1014

Clymac Limited
Cloudway Court, Belton Road, Loughborough LE11 1LB UK Tel: +44 (0)1509 232651 Fax: +44 (0)1509 232665 E-mail: sales@clymac.co.uk Website: www.clymac.co.uk
Certificate No. CFA-154 to LPS 1014

January 2009

PART 3: SECTION 1
LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

Cooper Controls Limited (trading as Integrated Solutions)


26 Greenhill Crescent, Watford Business Park, Watford, Hertfordshire WD18 8XG UK Tel: +44 (0)1923 495495 Fax: +44 (0)1923 228796 E-mail: sales@polaron.com Website: www.polaron.com
Certificate No. CFA-162 to LPS 1014

CTM Fire and Security Limited (Leyland & London Offices)


Unit 2, Osprey Place, Moss Side Industrial Estate, Leyland PR26 7EW UK Tel: +44 (0)800 5872753 Fax: +44 (0)1772 641227 E-mail: ctmfire@btconnect.com Website: www.firealarmuk.com Including the following satellite offices: BBC Television Centre, Arch 118, Dodds Yard, Wood Lane, London W12 7RJ Tel: +44 (0)208 225 9427 Fax: +44 (0)208 225 9446
Certificate No. CFA-156 to LPS 1014

Daemon Fire and Security Limited


Daemon House, 41-42 Albert Road, Tamworth, Staffs B79 7JS UK Tel: +44 (0)1827 69266 Fax: +44 (0)1827 53584 E-mail: sales@daemonfire.co.uk
Certificate No. CFA-145 to LPS 1014

Dalkia Energy & Technical Services Limited


Limeharbour Court, 5 Limeharbour, London E14 9TS UK Tel: +44 (0)20 7001 7000 Fax: +44 (0)20 7001 7272 E-mail: info@dalkiarail.co.uk
Certificate No. CFA-129 to LPS 1014

Defensor Group Ltd


11-15 Kingsley Street, Leicester LE2 6DY UK Tel: +44 (0)116 244 8689 Fax: +44 (0)116 244 8884 E-mail: j.kyte@defensorfds.co.uk
Certificate No. CFA-161 to LPS 1014

January 2009

SECTION 1: PART

LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

EMCOR Facilities Services Limited, EMCOR Specialist Services


Premier House, Tollgate, Eastleigh, Hampshire SO53 3YE UK Tel: +44 (0)2380 648028 Fax: +44 (0)2380 648191 E-mail: david.parker@emcoruk.com
Certificate No. CFA-151 to LPS 1014

EMCOR Rail Limited


EMCOR House, 1 Mastmaker Road, London E14 9WT UK Tel: +44 (0)207 536 6800 Fax: +44 (0)207 536 6801
Certificate No. CFA-153 to LPS 1014

FFE Fire & Security Limited


Unit 20, Tait Road Industrial Estate, Tait Road, Croydon CR0 2DP UK Tel: +44 (0)845 60 999 06 Fax: +44 (0)20 8665 4125 E-mail: enquiries@ffe.co.uk Website: www.ffe.co.uk
Certificate No. CFA-152 to LPS 1014

Firetecnics Systems Limited


142 Vauxhall Street, London SE11 5RH UK Tel: +44 (0) 20 7587 0927 Fax: +44 (0) 20 7582 3496 E-mail: info@firetecnics.co.uk Website: www.firetecnics.com
Certificate No. CFA-146 to LPS 1014

Grainger Fire Systems


Thornley House, Carrington Business Park, Carrington, Manchester M31 4XL UK Tel: +44 (0)161 777 6700 Fax: +44 (0)161 777 6638 E-mail: info@grainger-fire.co.uk The following location is included within the scope of certification for servicing: Unit 1A, Newton Court, Wavertree Technology Park, Wavertree, Liverpool L13 1EJ Tel: +44 (0)151 220 4068 Fax: +44 (0)151 259 4365
Certificate No. CFA-125 to LPS 1014

January 2009

PART 3: SECTION 1
LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

Hall & Kay Fire Engineering (Windsor)


1st Floor, Sefton Lodge, Clewer Hill Road, Windsor SL4 4FT UK Tel: +44 (0)1753 833444 Fax: +44 (0)1753 833434 E-mail: windsor@hkfire.co.uk Website: www.hkfire.co.uk
Certificate No. CFA-147 to LPS 1014

Hallmark Fire Limited


Systems House, Stoke Road, Hoo, Rochester, Kent ME3 9NT UK Tel: +44 (0)8700 111150 Fax: +44 (0)8700 111160 E-mail: sales@hallmarkfire.co.uk Website: www.hallmarkfire.co.uk
Certificate No. CFA-140 to LPS 1014

I.C. Service & Maintenance Limited


Unit K3 Temple Court, Knights Park, Knight Road, Strood, Kent ME2 2LT UK Tel: +44 (0)1634 290300 Fax: +44 (0)1634 290700 E-mail: sales@icservice.biz Website: www.icservice.biz
Certificate No. CFA-158 to LPS 1014

Kingfell Plc
Capitol Tower, 12th Floor, 91 Waterloo Road, London SE1 8RT UK Tel: +44 (0)845 60 61 999 Fax: +44 (0)845 25 81 999 E-mail: enquiries@kingfell.com Website: www.kingfell.com
Certificate No. CFA-138 to LPS 1014

M. J. Quinn Integrated Services Limited


Oak House, Overbrook Lane, Knowsley Business Park, Knowsley, Merseyside L34 9FB UK Tel: +44 (0)151 547 8800 Fax: +44 (0)151 547 8801 E-mail: enquiries@mjquinn.co.uk Website: www.mjquinn.co.uk
Certificate No. CFA-137 to LPS 1014

M. J. Quinn Integrated Services Limited


Gormley House, Waxlow Road, London NW10 7NU UK Tel: +44 (0)20 8453 0450 Fax: +44 (0)20 8453 0455 E-mail: enquiries@mjquinn.co.uk Website: www.mjquinn.co.uk
Certificate No. CFA-143 to LPS 1014

January 2009

SECTION 1: PART

LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

MECE Fire & Security Limited


Courtlodge, Kemsley Street Road, Bredhurst, Gillingham, Kent ME7 3LS UK Tel: +44 (0)1634 260607 Fax: +44 (0)1634 260278 E-mail: enquiries@mecefireandsecurity.co.uk Website: www.mecefireandsecurity.co.uk
Certificate No. CFA-159 to LPS 1014

MITIE Engineering Maintenance Limited


Mitie House, Kelper, Lichfield Road Industrial Estate, Tamworth B79 7XE UK Tel: +44 (0)1827 309791 Fax: +44 (0)1827 309798 E-mail: group@mitie.co.uk Website: www.mitie.co.uk
Certificate No. CFA-163 to LPS 1014

Niscayah Limited
Roding House, 970 Romford Road, London E12 5LP UK Tel: +44 (0)20 8553 5932 Fax: +44 (0)20 8478 8052 E-mail: info@niscayah.co.uk Website: www.niscayah.co.uk
Certificate No. CFA 169 to LPS 1014

Protec Fire Detection plc


Protec House, Churchill Way, Nelson, Lancashire BB9 6RT UK Tel: +44 (0)1282 717171 Fax: +44 (0)1282 717273 E-mail: sales@protec.co.uk Website: www.protec.co.uk Including the following satellite offices: Unit 4, White Oak Square, London Road, Swanley, Kent BB8 1AG UK Tel: +44 (0)845 456 5394 Fax: +44 (0)845 456 5395 Unit 10, Fulcram 4, Solent Way, Whiteley, Fareham, Hampshire PO15 7FT UK Tel: +44 (0)845 456 5392 Fax: +44 (0)845 456 5393 5 Morston Court, Blakeney Way, Kingswood Lakeside, Cannock, Staffordshire WS11 8JB UK Tel: +44 (0845 456 5398 Fax: +44 (0845 456 5399 Unit 1, Ashfield Court, Whitehall Road, Leeds LS12 5JB UK Tel: +44 (0)845 456 53388 Fax: +44 (0)845 456 53389
Certificate No. CFA-132 to LPS 1014

January 2009

PART 3: SECTION 1
LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

R&S Fire & Security Limited


Trident House, Neptune Business Park, Dolphin Way, West Thurrock, Essex RM19 1NZ UK Tel: +44 (0)1708 683040 Fax: +44 (0)1708 689648 E-mail: sales@rsfire.com Website: www.rsfire.com
Certificate No. CFA-172 to LPS 1014

Raysil Security Systems Limited


Unit 16, Red Lion Business Centre, 218 Red Lion Road, Surbiton, Surrey KT6 7QD UK Tel: +44 (0)20 8391 0202 Fax: +44 (0)20 8391 4758 E-mail: enquiries@raysil.co.uk Website: www.raysil.co.uk
Certificate No. CFA-127 to LPS 1014

Siemens plc, Building Technologies, Fire Safety Division


Brunel House, Sir William Siemens Square, Frimley, Camberley, Surrey GU16 8QD UK Tel: +44 (0)1276 696000 Fax: +44 (0)1276 696133 E-mail: sales.uk.sbt@siemens.com Website: www.siemens.co.uk/buildingtechnologies
Certificate No. CFA-100 to LPS 1014

Static Systems Group Plc


Heath Mill Road, Wombourne, Staffordshire WV5 8AN UK Tel: +44 (0)1902 895551 Fax: +44 (0)1902 324969 E-mail: sales@staticsystems.co.uk Website: www.staticsystems.co.uk
Certificate No. CFA-135 to LPS 1014

Thameside Fire Protection Co. Limited


Unit 4, Sovereign Business Park, Cranes Farm Road, Basildon, Essex SS14 3JD UK Tel: +44 (0)1268 597999 Fax: +44 (0)1268 597998 E-mail: enquiries@thamesidefire.co.uk Website: www.thamesidefire.co.uk
Certificate No. CFA-171 to LPS 1014

Trinity Protection Systems Limited


121A Milton Park, Abingdon, Oxfordshire OX14 4SA UK Tel: +44 (0)1235 862456 Fax: +44 (0)1235 834450 E-mail: info@trinityprotection.co.uk Website: www.trinityprotection.co.uk
Certificate No. CFA-168 to LPS 1014

10

January 2009

SECTION 1: PART

LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

Trinity Protection Systems Limited


Unit B12a, Holly Farm Business Park, Honiley, Warwickshire CV8 INP UK Tel: +44 (0)1926 485080 Fax: +44 (0)1926 485090 E-mail: info@trinityprotection.co.uk Website: www.trinityprotection.co.uk
Certificate No. CFA-167 to LPS 1014

Trinity Protection Systems Limited


Little Bridge Business Park, Oil Mill Lane, Clyst St.Mary, Exeter, Devon EX5 1AG UK Tel: +44 (0)1392 874455 Fax: +44 (0)1392 875546 E-mail: info@trinityprotection.co.uk Website: www.trinityprotection.co.uk
Certificate No. CFA-160 to LPS 1014

TVF (UK) plc


59-69 Queens Road, High Wycombe, Buckinghamshire HP13 6AH UK Tel: +44 (0)1494 450641 Fax: +44 (0)1494 465378 E-mail: info@tvfplc.co.uk Website: www.tvfplc.co.uk
Certificate No. CFA-128 to LPS 1014

Tyco Fire and Integrated Solutions (the trading company for Tyco Fire and Integrated Solutions (UK) Limited and Tyco Fire and Integrated Solutions (Ireland) Limited)
1A Unity Street, Old Market, Bristol BS2 0HX UK Tel: +44 (0)117 927 7271 Fax: +44 (0)117 929 7586 Website: www.wormald.co.uk
Certificate No. CFA-170 to LPS 1014

Tyco Fire and Integrated Solutions (the trading company for Tyco Fire and Integrated Solutions (UK) Limited and Tyco Fire and Integrated Solutions (Ireland) Limited)
Hillcrest Business Park, Cinderbank, Dudley, West Midlands DY2 9AP UK Tel: +44 (0)1384 458993 Fax: +44 (0)1384 458981 E-mail: howfire@howfire.co.uk Website: www.howfire.co.uk
Certificate No. CFA-103 to LPS 1014

January 2009

11

PART 3: SECTION 1
LPS 1014 CERTIFIED FIRE DETECTION AND ALARM SYSTEM FIRMS

Tyco Fire and Integrated Solutions (the trading company for Tyco Fire and Integrated Solutions (UK) Limited and Tyco Fire and Integrated Solutions (Ireland) Limited)
206 Bedford Avenue, Slough Trading Estate, Slough SL1 4RY Tel: +44 (0)1753 574111 Fax: +44 (0)1753 824226 Website: www.wormald.co.uk
Certificate No. CFA-157 to LPS 1014

12

January 2009

SECTION 2: PART

FIRE DETECTION AND ALARM SYSTEMS

A fire detection and fire alarm system is typically made up of a number of inter-linked components including detectors, manual call points, and alarm sounders connected to a control and indicating equipment by means of one or more transmission paths. All system components, including the control and indicating equipment are also connected to a power supply directly or indirectly. A fire detection and alarm system may be linked to other systems such as fire protection, or building management systems. These other systems are not considered as part of the fire detection and alarm systems. The fire detection and alarm systems may be networked together. Each of the components that constitute the fire detection and alarm system may be individually tested and approved against their appropriate standard to demonstrate their own performance and reliability but in order to ensure their compatibility and performance together within the system, certain systems tests and requirements must be fulfilled. The system standard specifies the requirements for compatibility and connectability assessment of system components that either comply with the requirements of EN 54 and/or with a manufacturers specification. The standard also includes requirements for the integrity of the fire detection and fire alarm system when connected to other systems. This section lists approved fire detection and alarm systems suitable for use in buildings for the protection of people and property. The system requirements ensure the compatibility of the different components of the system work reliably together. Each component of the fire detection and alarm systems listed in this section are approved to the applicable product standard and are listed in Part 3 sections 3, 4.1, 5, 6, and 7. The approval process for the system is outlined in scheme document SD040. Products listed in this section have been approved to LPS 1054:2001 Requirements for the evaluation of component compatibility for fire alarm systems This standard was designed for the UK market and applies to systems incorporating control and indicating equipment and power supply equipment complying with EN 54-2 Fire detection and fire alarm systems Control and indicating equipment and EN 54-4 Fire detection and fire alarm systems - Power supply equipment respectively. Networked systems are evaluated by ensuring that each control panel connected to the network can operate as a stand alone unit, in the event of failure of the network connections, and that failure of a control panel will not affect other control panels on the network. LPCB is now accepting products for approval to EN 54-13:2005 Compatibility assessment for system components which is applicable to the EU market. Note: Since LPCB uses national and international standards for the listing of products, in some instances, the requirements of these standards may conflict with the recommendations of local codes of practice. We recommend that specifiers seek advice from the relevant local authorities and amend their specifications accordingly.

Control Equipment Limited


Hillcrest Business Park, Dudley, West Midlands DY2 9AP UK Tel: +44 (0)1384 458651 Fax: +44 (0)1384 458972 E-mail: celsales@controlequipment.co.uk Website: www.controlequipment.com
Certificate No: 018b to LPS 1054-1 Certificate No: 018d to LPS 1054-1

January 2009

13

PART 3: SECTION 2
FIRE DETECTION AND ALARM SYSTEMS
Certificated Products Precept fire alarm system Comprising the following products: Control Equipment Limited Precept 2, 4, 8, 16 and 32 zone control and indicating equipment. Apollo Fire Detectors Limited 55000-100 grade 1 rate of rise heat detector (45681-200 base) 55000-200 ionization smoke detector (45681-200 base) 55000-300 photoelectic smoke detector (45681-200 base) 53531-221 grade 1 rate of rise heat detector (45681-007 base) continued 53541-151 ionization smoke detector (45681-007 base) 53541-200 photoelectric smoke detector (45681-007 base) 55000-101 grade 2 rate of rise heat detector (45681-200 base) 55000-102 grade 3 rate of rise heat detector (45681-200 base) 55000-103 range 1 rate of rise heat detector (45681-200 base) 55000-104 range 2 rate of rise heat detector (45681-200 base) 55000-210 integrating ionization smoke detector (45681-200 base) Hochiki Corporation DFE-60 grade 2 fixed temperature heat detector (YBF-RL/4H5 base) DFE-90 range 1 fixed temperature heat detector (YBF-RL/4H5 base) DCC-1EL grade 1 rate of rise heat detector (YBF-RL/4H5 base) DCC-2EL grade 2 rate of rise heat detector (YBF-RL/4H5 base) DCC-R1EL range 1 rate of rise heat detector (YBF-RL/4H5 base) Hochiki Europe SLK-E photoelectric smoke detector (YBF-RL/4H5 base) SIH-E ionization smoke detector (YBF-RL/4H5 base) KAC Alarm Company Limited KR72 manual call point. Photain Controls Limited ISD-P91 ionization smoke detector PRR-P91 grade 1 rate of rise heat detector PHD-P90 range 1 fixed temperature heat detector Signature Industries - Clifford and Snell Alarms. MCP/R/F manual call point MCP/R/S manual call point System Sensor, St. Charles, Illinois, USA. 1151E ionization smoke detector (B401 base) 2151E photoelectric smoke detector (B401 base) Comprising the following products: Control Equipment Limited Discovery analogue addressable control and indicating equipment Apollo Fire Detectors Limited 55000-400 grade 2 analogue temperature monitor 55000-420 grade 2 analogue temperature monitor 58000-400 Discovery temperature monitor 55000-600 analogue photoelectric smoke monitor 55000-620 analogue photoelectric smoke monitor 58000-600 Discovery optical smoke monitor 55000-500 analogue ionisation smoke monitor 55000-520 analogue ionisation smoke monitor 58000-500 Discovery ionisation smoke monitor 58000-700 Discovery multisensor monitor 55000-900 surface and flush mounted manual call point 55000-910 flush mounted manual call point 55000-950 waterproof addressable manual call point 58000-900 flush and surface mounted manual call point 58000-910 flush mounted manual call point 58000-920 surface mounted manual call point 55000-700 XP95 short circuit isolator 45681-321 XP95 negative isolating base 45681-210 XP95 addressable mounting base LPCB Ref. No. 018b/S1

Discovery fire alarm system

018d/01

14

January 2009

SECTION 2: PART

FIRE DETECTION AND ALARM SYSTEMS

GE Security (Africa) trading as Ziton


Ziton House, 555 Voortrekker Road, Maitland 7405, Republic of South Africa Tel: +27 21 5066000 Fax: +27 21 5066100 Website: www.ziton.com UK Sales enquiries: Ziton Limited Tel: +44 (0)1908 281981 Fax: +44 (0)1908 282554

Certificate No: 092f to LPS 1054 Certificated Products ZP5 Mark 5 analogue addressable fire alarm system Comprising the following products: ZP5 Mark 5 control and indicating equipment 092e/01 ZP710-2 analogue ionisation smoke detector (ZP7-SB1 base) 092n/01 ZP730-2 analogue optical smoke sensor (ZP7-SB1 base) 092n/02 ZP720-3 grade 1 analogue heat sensor (ZP7-SB1 base) 092p/01 ZP785-2 addressable flush and surface mounted call point 092d/01 Comprising of the following products: ZP3 analogue addressable control and indicating equipment 092h/01 ZP710-2 analogue addressable ionisation smoke detector 092n/01 ZP730-2 analogue addressable optical smoke detector 092n/02 ZP720-3 analogue addressable grade 1 heat detector 092p/01 ZP785-2 addressable flush and surface mounted manual call point 092d/01 ZP760-2 short circuit isolator 092j/01 LPCB Ref. No. 092f/S1

ZP3 analogue addressable fire alarm system

092f/S2

Notifier By Honeywell
Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@notifiersystems.co.uk Website: www.notifierfiresystems.co.uk
Certificate No: 154e to LPS 1054: Issue 2.1 Certificated Products Notifier NFS2-8 Fire Alarm System Comprising the following products: Notifier Fire Systems Ltd 124-345-002 NFS2-8, 2 Zone Conventional Control and Indicating Equipment 124-345-004 NFS2-8, 4 Zone Conventional Control and Indicating Equipment 124-345-008 NFS2-8, 8 Zone Conventional Control and Indicating Equipment Morley-IAS Fire Systems ECO 1002 Photoelectric smoke and heat detector ECO 1003 Photoelectric smoke detector ECO 1004T High Temperature 78C heat detector class BS ECO 1005 Heat detector class A1R ECO 1005T Fixed temperature heat detector class A2S KAC Alarm Company Ltd MCP1A-Rxxxxx Indoor/outdoor surface/flush mounting conventional manual call point NS4/R Sounder 4 tone wall mounting conventional (red) NS4/W Sounder 4 tone wall mounting conventional (white) NS14/R Sounder 14 tones wall mounting conventional (red) NS14/W Sounder 14 tones wall mounting conventional (white) LPCB Ref. No. 154e/S1

January 2009

15

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT Control and Indicating Equipment (CIE) is a component of a fire detection and alarm system through which other components may be connected to it such as detectors, manual call points, sounders, routing equipment, voice alarm equipment and fire protection equipment. It is supplied with power from power supply equipment which may be housed within the CIE enclosure or a separate enclosure. CIE is used to receive and send out signals that are related to fire. CIE also monitors the system for faults (short and open circuit or power supply faults) and indicate the status of the fire detection and alarm system. CIE designed to meet a European standard such as EN 54-2 or international standard such as ISO 7240-2 has certain options with requirements. For example, it may be designed to provide a signal to fire protection equipment or have dependencies on more than one alarm signal. Some CIEs have other functions which are not specified in the standard. These additional features are normally assessed such that they do not jeopardise compliance. The choice of CIE is dependant on the specific applications as recommended in the application guidelines for a specific job or building. Some CIEs have associated repeaters or mimic panels. These are normally used to repeat the indications given on the main CIE and sometimes they have control functions such as silencing sounders. There are no published standards that these repeaters or mimics can be tested against. This section lists Control and Indicating Equipment, and power supply equipment approved for use in fire detection and fire alarm systems in buildings. Repeaters or mimics that are listed in this section are only approved with their associated CIE and are subjected to the same environmental tests as the CIE. The initial approval and continued approval processes of these type of equipment are outlined in scheme document SD040. Products listed in this section have been approved to: EN 54-2:1997 Control and Indicating Equipment; EN 54-2:1997 + A1: 2006 and A2: 2007 Control and Indicating Equipment; EN 54-4:1997 Power supply equipment; EN 54-4:1997 + A1: 2002 and A2: 2006 Power supply equipment; ISO 7240-2:2003 Control and Indicating Equipment; ISO 7240-4:2003 Power supply equipment;

Audit: Regular product auditing and regular factory inspections are carried out by LPCB ensuring high manufacturing standards and continued compliance with the applicable product standard. Notes: 1. EN 54-2:1997 is a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market from 1 August 2009. It is therefore recommended that control and Indicating Equipment are certificated to EN 54-2:1997 + A1:2002 and A2:2007. 2. EN 54-4:1997 is a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market from 1 August 2009. It is therefore recommended that power supply equipment are certificated to EN 54-4:1997 + A1:2002 and A2:2006. 3. Since the LPCB uses national and international standards for the listing of products, in some instances the requirements of these standards may conflict with the recommendations of local codes of practice. We recommend that specifiers seek advice from the relevant local authorities and amend their specifications accordingly. 4. Where the Control and Indicating Equipment is of modular construction, and the use of certain modules (or printed circuit boards PCBs) is optional, these are listed with the applicable equipment.

16

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

Advanced Electronics Limited


34 Moorland Way, Nelson Park, Cramlington, Northumberland NE23 1WE UK Tel: +44 (0)1670 707111 Fax: +44 (0)1670 707222 Website: www.Advel.co.uk
Certificate No: 018c to EN 54:Part 2 and 4: 1997 Certificated Products Mx-1002 2 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 4 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 8 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 16 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 32 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1629 Display board C1632 16 Zone Expansion board C1652 5A Power supply board C1631 Repeater interface board (option) Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs LPCB Ref. No. 018c/02

Mx-1004

018c/03

Mx-1008

018c/04

Mx-1016

018c/05

Mx-1032

018c/06

January 2009

17

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 8.9 Output to fault warning equipment 10 Test condition 8 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board 16 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board 32 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1629 Display board C1631 Repeater interface board LPCB Ref. No. 018c/R01

Mx-1108

Mx-1116

018c/R02

Mx-1132

018c/R03

Bardic by Honeywell
140 Waterside Road, Hamilton Industrial Estate, Leicester LE5 1TN UK Tel: +44 (0) 116 246 2212 Fax: +44 (0) 116 246 2210 Website: www.bardic.co.uk
Certificate No: 154d to EN 54-2: 1997 and EN 54-4: 1997 Certificated Products Bardic Zircon 2 Zone conventional controls and indicating equipment Including the following versions: 002-509-229 Language region 2, black & grey 4 Zone conventional controls and indicating equipment Including the following versions: 002-509-249 Language region 2, black & grey 8 Zone conventional controls and indicating equipment Including the following versions: 002-509-289 Language region 2, black & grey Certified with the following options with requirements from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 10 Test condition LPCB Ref. No. 154d/09

Bardic Zircon

154d/10

Bardic Zircon

154d/11

CEAG
Postfach 11 16, D-59491 Soest, Germany Tel: +44 (0)1302 303397 Fax: +44 (0)1302 303220 Website: www.ceag.de
Certificate No: 714a to EN 54-2 :1997 and EN 54-4 :1997 Certificated Products CF 3000 Analogue addressable 2 and 4 Loop control and indicating equipment Incorporating the following units: ADF6 Back Assembled back box YPCB2153 Motherboard PCB LPCB Ref. No. 714a/01

18

January 2009

SECTION 3: PART
Certificated Products YPCB2147 PSU PCB YPCB2148 2 Loop Card (2 off) ADF6Screen Touch Screen YPCB2185 Complete Display + Micro PCB ADF6 DISPCOVER Display PCB Cover ADF6FACIA Front Moulding ADF6PRINTDOOR Printer Door Moulding BAT-NP12-12 Batteries (2 off) ADF6HINGE Door Hinges ADF6OPFACIA Optional Anti Tamper Cover ADF6PRINTER Printer YPCB2187 Fire Brigade Interface Certified with the following options with requirements from EN54-2:1997: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12 Coincidence detection 7.13 Alarm counter 8.9 Output to fault warning routing equipment 9.5 Disablement of each address point 10 Test condition LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

Chubb Securit
10 Avenue du Centaure, B.P.38408-95806, Cergy-Pontoise Cedex, France Tel: +33 1 30173737 Fax: +33 1 30173707 Website: www.chubbsecurite.com
Certificate No: 747a to EN 54-2: 1997 and EN 54-4: 1997 Certificated Products Control Master 1000M-M Control Master 1000M-S 4 loop analogue addressable control indicating equipment (Medium enclosure) 4 loop analogue addressable control indicating equipment (Small enclosure) Incorporating the following units: CE00504 Main CPU CE00505 Main board display CE00506 Connection board CE00490 100W PSU and as optional modular units: CE00508 16 Zone LED module CE00507 32 Zone LED module CE00513 4 alarm zone control and indicating module CE00447 2 Way network interface CE00446 4 Way network interface CE00435A Lon high integrity isolator CE00514 16 fire protection zone control and indicating module CE00503 2 Loop System sensor interface CE00520 2 Loop Apollo interface Certified with the following options with requirements from EN 54-2: 7.8 Output to fire alarm devices 7.11 Delays to outputs 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition 2 loop analogue addressable control indicating equipment (Medium enclosure) 2 loop analogue addressable control indicating equipment (Small enclosure) Incorporating the following units: CE00504 Main CPU CE00505 Main board display CE00506 Connection board CE00490 100W PSU and as optional modular units: LPCB Ref. No. 747a/01 747a/01

Control Master 1020 M Control Master 1020 S

747a/02 747a/02

January 2009

19

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products CE00508 16 Zone LED module CE00507 32 Zone LED module CE00447 2 Way network interface CE00446 4 Way network interface CE00435A Lon high integrity isolator CE00513 4 alarm zone control and indicating module CE00514 16 fire protection zone control and indicating module Certified with the following options with requirements from EN 54-2: 7.8 Output to fire alarm devices 7.11 Delays to outputs 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition 1 loop, analogue addressable control indicating equipment Incorporating the following units: CE00510 Main CPU CE00505 Main board display CE00506 Connection board CE00490 100W PSU and as optional modular units: CE00508 16 Zone LED module CE00436A 4 Way sounder board CE00437A 8 Way sounder board CE00507 32 Zone LED module CE00435A Lon high integrity isolator CE00513 4 alarm zone control and indicating module CE00514 16 fire protection zone control and indicating module Certified with the following options with requirements from EN 54-2: 7.8 Output to fire alarm devices 7.11 Delays to outputs 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition Remote unit Incorporating the following units: CE00509 Display board CE00484B Main board CE00489 40 W PSU and as optional modular units: CE00508 16 Zone LED module CE00507 32 Zone LED module CE00447 2 way network interface CE00446 4 way network interface CE00435A Lon high integrity isolator CE00513 4 alarm zone control and indicating module CE00514 16 Fire protection zone control and indicating module Remote unit Incorporating the following units: CE00509 Display board CE00484B Main board CE00490 100 W PSU and as optional modular units: CE00508 16 Zone LED module CE00507 32 Zone LED module CE00513 4 alarm zone control and indicating module CE00447 2 Way network interface CE00446 4 Way network interface CE00435A Lon high integrity isolator CE00514 16 fire protection zone control and indicating module The following repeaters and the remote units are approved for use with the Control Master 1000 range of control and indicating equipment (incorporating 1020 and 1010): RS Repeater 747a/R03 RS Repeater with LCD display 747a/R04 Lon Repeater with LCD display 747a/R05 Remote unit 747a/E01 Incorporating the following units: CE00503 2 Loop System sensor interface LPCB Ref. No.

Control Master 1010S

747a/03

Control master 1000R-S

747a/R01

Control master 1000R-M

747a/R02

20

January 2009

SECTION 3: PART
CE00489 40W PSU and as optional modular units: CE00490 100W PSU CE00435A Lon high integrity isolator

CONTROL AND INDICATING EQUIPMENT

Computionics Limited (Trading as C-Tec)


Stephens Way, Goose Green, Wigan, Lancashire WN3 6PH UK Tel: +44 (0)1942 322744/42444 Fax: +44 (0)1942 829867 E-mail: sales@C-tec.co.uk Website: www.c-tec.co.uk
Certificate No: 176a to EN 54: Part 2 and 4: 1997 Certificated Products CFP 2 CFP 4 CFP 8 Conventional 2 zone control and indicating equipment Conventional 4 zone control and indicating equipment Conventional 8 zone control and indicating equipment LPCB Ref. No. 176a/01 176a/02 176a/03

Certificated with the following options from BS EN 54 Part 2: 7.8 Output to sounders 7.11 Delays to outputs 10 Test condition

Certificate No: 176b to EN 54-2: 1997 + A1: 2006 + A2: 2007 and EN 54-4: 1997 + A1: 2002 Certificated Products XFP502/H 2 loop, 32 zone analogue addressable control and indicating equipment using Hochiki Protocol, metal housing Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501202 XFP Hochiki 2 loop, main motherboard SPF0501200 Display board "keypad display" Certified with the following options with requirements from EN 54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality. 2 loop, 32 zone analogue addressable control and indicating equipment using Hochiki Protocol, metal housing + Keyswitch Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501202 XFP Hochiki 2 loop, main motherboard SPF0501199 Display board "keyswitch display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: LPCB Ref. No. 176b/01

XFP502K/H

176b/01

January 2009

21

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products XFP502/X 1) Scope of approval does not include the operation of the network functionality. 2 Loop, 32 zone analogue addressable control and indicating equipment using Apollo Protocol, metal housing Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501201 XFP Apollo 2 loop, main motherboard SPF0501200 Display board "Keypad display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality. 2 Loop, 32 zone analogue addressable control and indicating equipment using Apollo Protocol, metal housing Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501201 XFP Apollo 2 loop, main motherboard SPF0501200 Display board "Keypad display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 2 Loop, 32 zone analogue addressable control and indicating equipment using Apollo Protocol, metal housing + Keyswitch Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501201 XFP Apollo 2 loop, main motherboard SPF0501199 Display board "Keyswitch display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality. 2 Loop, 32 zone analogue addressable control and indicating equipment using Apollo Protocol + Keyswitch, metal housing Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501201 XFP Apollo 2 loop, main motherboard SPF0501199 Display board "Keyswitch display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter LPCB Ref. No. 176b/02

XFP502/X/CON

176b/02

XFP502K/X

176b/02

XFP502K/X/CON

176b/02

22

January 2009

SECTION 3: PART
Certificated Products 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 1 Loop, 32 zone analogue addressable control and indicating equipment using Hochiki Protocol, metal housing Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501212 XFP Hochiki 1 loop, main motherboard SPF0501200 Display board "Keypad display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality. 1 Loop, 32 zone analogue addressable control and indicating equipment using Hochiki Protocol, metal housing + Keyswitch Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501212 XFP Hochiki 1 loop metal case, main motherboard SPF0501199 Display board "Keyswitch display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality. 1 Loop, 32 zone analogue addressable control and indicating equipment using Apollo Protocol, metal housing Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501211 XFP Apollo 1 loop, main motherboard SPF0501200 Display board "keypad display" Certified with the following options with requirements from EN 54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality. 1 Loop, 32 zone analogue addressable control and indicating equipment using Apollo Protocol, metal housing Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501211 XFP Apollo 1 loop, main motherboard SPF0501200 Display board "keypad display" Certified with the following options with requirements from EN 54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

XFP501/H

176b/03

XFP501K/H

176b/03

XFP501/X

176b/04

XFP501/X/CON

176b/04

January 2009

23

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 1 Loop, 32 zone analogue addressable control and indicating equipment using Apollo Protocol, metal housing + Keyswitch Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501211 XFP Apollo 1 loop, main motherboard SPF0501199 Display board "Keyswitch display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 1 Loop, 32 zone analogue addressable control and indicating equipment using Apollo Protocol + Keyswitch, metal housing Incorporating the following units: SPF0706000 Switch mode power supply board SPF0501211 XFP Apollo 1 loop, main motherboard SPF0501199 Display board "Keyswitch display" Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal - Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 1 Loop, 16 zone analogue addressable control and indicating equipment using Hochiki protocol, plastic housing Incorporating the following units: SPF0702480 Switch mode power supply board SPF0501102 XFP Hochiki 1 loop, main motherboard Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal -Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 1 Loop, 16 zone analogue addressable control and indicating equipment using Hochiki protocol, plastic housing + Keyswitch Incorporating the following units: SPF0702480 Switch mode power supply board SPF1501102 XFP Hochiki 1 loop, main motherboard Certified with the following options with requirements from EN54-2: 1997 LPCB Ref. No.

XFP501K/X

176b/04

XFP501K/X/CON

176b/04

XFP501E/H

176b/05

XFP501EK/H

176b/05

24

January 2009

SECTION 3: PART
Certificated Products 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal -Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 1 Loop, 16 zone analogue addressable control and indicating equipment using Apollo Protocol, plastic housing Incorporating the following units: SPF0702480 Switch mode power supply board SPF0501101 XFP Apollo 1 loop, main motherboard Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal -Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 1 Loop, 16 zone analogue addressable control and indicating equipment using Apollo Protocol, plastic housing Incorporating the following units: SPF0702480 Switch mode power supply board SPF0501101 XFP Apollo 1 loop, main motherboard Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal -Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 1 Loop, 16 zone analogue addressable control and indicating equipment using Apollo Protocol, plastic housing + Keyswitch Incorporating the following units: SPF0702480 Switch mode power supply board SPF1501101 XFP Apollo 1 loop, main motherboard Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal -Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality One Loop, 16 zone analogue addressable control and indicating equipment using Apollo Protocol, Plastic housing Incorporating the following units: SPF0702480 Switch mode power supply board LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

XFP501E/X

176b/06

XFP501E/X/CON

176b/06

XFP501EK/X

176b/06

XFP501KE/X/CON

176b/06

January 2009

25

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products SPF1 501101 XFP Apollo 1 loop, Main motherboard Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm device(s) 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12.1 Dependencies on more than one alarm signal - Type A 7.12.2 Dependencies on more than one alarm signal -Type B 7.12.3 Dependencies on more than one alarm signal - Type C 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality LPCB Ref. No.

Certificate No: 176c to EN 54-2:1997 + A1:2006 + A2:2007 and EN 54-4:1997 + A1:2002 Certificated Products EP203 Incorporating the following units: SPF0000203 SPF0000212 SPF0003613 SPF0000214 Main extinguisher control External relay interface Power supply unit EP214 terminator LPCB Ref. No. 176c/01

Incorporating as modular units: EP210S EP211 Remote Status Unit Surface Mount optional (See Note 1) Economy Status Unit optional (See Note 1)

Certified with the following options with requirements from EN 12094-1:2003 4.17 4.18 4.19 4.20 4.21 4.23 4.26 4.27 4.30 Delay of extinguishing signal Signal representing the flow of extinguishing agent Monitoring of the status of components Emergency hold device Control of flooding time Manual only mode Triggering of equipment outside the system Emergency abort device Activation of alarm devices with different signals

Certified with the following options with requirements from EN-54-2:1997 7.8 Output to fire alarm device(s) 7.11 Delays to the auctioning of outputs fire alarm devices and fire routing equipment 7.13 Alarm counter 10 Test condition Notes: 1) Optional Remote Status Unit part No. EP21OS & Economy Status Unit part No. EP211 are not certified as meeting the requirements of the standards specified. 2) Meets the requirements of EN12094-3:2003, Class A - i.e. operational temperature range of -5C to +40C.

26

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

Control Equipment Limited


Hillcrest Business Park, Dudley, West Midlands DY2 9AP UK Tel: +44 (0)1384 458651 Fax: +44 (0)1384 458972 E-mail: celsales@controlequipment.co.uk Website: www.controlequipment.com
Certificate No: 018a to BS 5839: Part 4. This certificate is to a withdrawn standard. Control and indicating equipment conforming to this standard is not suitable for use within the jurisdiction of the European Union (EU). This certificate, to the withdrawn standard, is maintained because control and indicating equipment meeting the withdrawn standard is still requested by some regulators outside of the EU. Certificate No: 018c to EN 54: Part 2 and 4: 1997 Certificated Products Precept 2 zone control and indicating equipment Incorporating as modular units C1423 Motherboard C1440 Display Board 4 zone control and indicating equipment Incorporating as modular units C1423 Motherboard C1441 Display Board 8 zone control and indicating equipment Incorporating as modular units C1427 Motherboard C1462 Display Board 16 zone control and indicating equipment Incorporating as modular units C1425 Motherboard C1426 Display Board 32 zone control and indicating equipment Incorporating as modular units C1425 Motherboard C1426 Display Board C1464 Display Board 2 zone control and indicating equipment Incorporating as modular units C1423 Motherboard C1440 Display Board 4 zone control and indicating equipment Incorporating as modular units C1423 Motherboard C1441 Display Board 8 zone control and indicating equipment Incorporating as modular units C1427 Motherboard C1462 Display Board 16 zone control and indicating equipment Incorporating as modular units C1425 Motherboard C1426 Display Board 32 zone control and indicating equipment Incorporating as modular units C1425 Motherboard C1426 Display Board C1464 Display Board 4 loop analogue addressable control and indicating equipment Incorporating: A1579 Motherboard A1580 Display board A1585 Loop cards A1584 230 Vac power supply control card A1599 Printer board 2 zone conventional control and indicating equipment Incorporating as modular units:C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 4 zone conventional control and indicating equipment Incorporating as modular units:LPCB Ref. No. 018a/01

Precept

018a/02

Precept

018a/03

Precept

018a/04

Precept

018a/05

Series 600

018a/06

Series 600

018a/07

Series 600

018a/08

Series 600

018a/09

Series 600

018a/10

Discovery

018c/01

Precept En2 (2605-100)

018c/02

Precept En4 (2605-101)

018c/03

January 2009

27

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 8 zone conventional control and indicating equipment Incorporating as modular units:C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 16 zone conventional control and indicating equipment Incorporating as modular units:C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 32 zone conventional control and indicating equipment Incorporating as modular units:C1627 Mother board C1629 Display board C1631 Repeater interface board (option) C1632 16 Zone Expansion board C1652 5A Power supply board 8 zone conventional repeater unit Incorporating as modular units:C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 16 zone conventional repeater unit Incorporating as modular units:C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 32 zone conventional repeater unit Incorporating as modular units:C1627 Mother board C1628 Display board C1631 Repeater interface board (option) LPCB Ref. No.

Precept En8 (2605-102)

018c/04

Precept En16 (2605-103)

018c/05

Precept En32 (2605-104)

018c/06

Precept En8 (2605-110)

018c/R01

Precept En16 (Repeater (2605-111)

018c/R02

Precept En32 (Repeater (2605-112)

018c/R03

Certificate Nos. 018a and 018c: Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.11 Delays to outputs 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition Certificate Nos. 018c/02-06: Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition

28

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

Cooper Industries Inc


Wheatley Hall Road, Doncaster, South Yorkshire DN2 4NB UK Tel: +44 (0)1302 303303 Fax: +44 (0)1302 367155 E-mail: sales@cooper-ls.com Website: www.cooper-ls.com UK Sales: Menvier & JSB Tel: +44 (0)1302 303202 Fax: +44 (0)1302 367155 E-mail: enquiries@cooper-ls.com Website: www.cooper-ls.com

UK Sales: Tel: +44 (0)1594 541900 Fax: +44 (0)1594 541910 E-mail: sales@cooperfire.co.uk Website: www.cooperfire.co.uk

Certificate No: 714a to EN 54 Part 2 and 4 :1997 Certificated Products CF3000 32 zone conventional repeater unit Incorporating the following units: ADF6 Assembled back box YPCB2153 Motherboard PCB YPCB2147 PSU PCB YPCB2148 2 Loop card (2 off) ADF6 Screen Touch Screen YPCB2185 Complete Display + Micro PCB ADF6DISPCOVER Display PCB Cover ADF6FACIA Front Moulding ADF6PRINTDOOR Printer Door Moulding BAT-NP12-12 Batteries (2 off) ADF6HINGE Door Hinges ADF6OPFACIA Optional Anti Tamper Cover ADF6PRINTER Printer YPCB2187 Fire Brigade Interface Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12 Coincidence detection 7.13 Alarm counter 8.9 Output to fault warning routing equipment 9.5 Disablement of each address point 10 Test condition Analogue addressable 2 and 4 loop control and indicating equipment Incorporating the following units: ADF6 Assembled back box YPCB2153 Motherboard PCB YPCB2147 PSU PCB YPCB2148 2 Loop card (2 off) ADF6Screen Touch Screen YPCB2185 Complete Display + Micro PCB ADF6DISPCOVER Display PCB Cover ADF6FACIA Front Moulding ADF6PRINTDOOR Printer Door Moulding BAT-NP12-12 Batteries (2 off) ADF6HINGE Door Hinges ADF6OPFACIA Optional Anti Tamper Cover ADF6PRINTER Printer YPCB2187 Fire Brigade Interface Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment LPCB Ref. No. 714a/01

DF6000

714a/01

January 2009

29

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 7.10 Output to automatic fire protection equipment 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12 Coincidence detection 7.13 Alarm counter 8.9 Output to fault warning routing equipment 9.5 Disablement of each address point 10 Test condition Analogue addressable 2 and 4 Loop control and indicating equipment Incorporating the following units: ADF6 Back Assembled back box YPCB2153 Motherboard PCB YPCB2147 PSU PCB YPCB2148 2 Loop Card (2 off) ADF6Screen Touch Screen YPCB2185 Complete Display + Micro PCB ADF6 DISPCOVER Display PCB Cover ADF6FACIA Front Moulding ADF6PRINTDOOR Printer Door Moulding BAT-NP12-12 Batteries (2 off) ADF6HINGE Door Hinges ADF6OPFACIA Optional Anti Tamper Cover ADF6PRINTER Printer YPCB2187 Fire Brigade Interface Certified with the following options with requirements from EN54-2: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12 Coincidence detection 7.13 Alarm counter 8.9 Output to fault warning routing equipment 9.5 Disablement of each address point 10 Test condition Analogue addressable 2 Loop control and indicating equipment Incorporating the following units: PR202-50-2209 Power supply board PR202-50-2206 Main motherboard PR202-50-2205 Display board Certified with the following options with requirements from EN 54-2: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to the actioning of outputs fire alarm devices and fire routing equipment 7.12 Coincidence detection 7.13 Alarm counter 8.9 Output to fault warning routing equipment 9.5 Disablement of each address point 10 Test condition LPCB Ref. No.

FX6000

714a/01

CF2000

714a/02

Fireguard Safety Equipment Co Ltd


2nd Floor, 145-147 St Johns Street, London EC1V 4PY UK Tel: +44 (0)8450 751042 Fax: +44 (0)8450 751043 E-mail: info@fireguard-uk.com Website: www.fireguard-uk.com
Certificate No: 018c to EN 54: Part 2 and 4: 1997 Certificated Products FireGuard Excel Series 4 loop analogue addressable control and indicating equipment Incorporating as modular units: A1579 Motherboard A1580 Display board A1585 Loop cards LPCB Ref. No. 018c/01

30

January 2009

SECTION 3: PART
Certificated Products A1584 230Vac power supply control card A1599 Printer board Certified with the following options from EN54 Part 2: 7.8 Output to fire alarm devices 7.11 Delays to outputs 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition 2 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 4 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 8 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 16 zone conventional control and indicating equipmentII Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 32 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1629 Display board C1632 16 Zone expansion board C1652 5A Power Supply board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 8 zone conventional repeater unit Incorporating as modular units: LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

FireGuard Excel Series

018c/02

FireGuard Excel Series

018c/03

FireGuard Excel Series

018c/04

FireGuard Excel Series

018c/05

FireGuard Excel Series

018c/06

FireGuard Excel Series

018c/R01

January 2009

31

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products C1627 Mother board C1628 Display board C1631 Repeater interface 16 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface 32 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1629 Display board C1631 Repeater interface LPCB Ref. No.

FireGuard Excel Series

018c/R02

FireGuard Excel Series

018c/R03

FIREX Protection System Technology Ltd


28-38 Desborough Street, High Wycombe, Bucks UK Tel: +44 (0)1494 601077 Fax: +44 (0)1494 601011 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 548j to EN 54-2: 1997 and EN54-4: 1997 Certificated Products FX200 Intelligent 1 loop, 30 zone, analogue addressable control and indicating equipment Incorporating the following units: F7.820.826 Main board F7.908.312 Zone indication board F7.820.827 Switch board F7.820.828 Loop interface board F7.820.829 Power Supply unit F2.910.093 Mains filter R150 Transformer CGM12864 Alphanumeric Display F2.828.630a Printer board (option) Incorporating as optional modular units: P-9901 Printer module kit F7.820.170 RS232 board for configuration Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.10 Output to automatic Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection 8.3 Fault signals from points 9.5 Disablement of addressable points Single zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Two zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Four zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Eight zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Sixteen zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs LPCB Ref. No. 548j/01

FX1

548j/02

FX2

548j/03

FX4

548j/04

FX8

548j/05

FX16

548j/06

32

January 2009

SECTION 3: PART
Certificated Products 10 Test condition LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

GE Security (Africa) trading as Ziton


Ziton House, 555 Voortrekker Road, Maitland 7405, Republic of South Africa Tel: +27 21 5066000 Fax: +27 21 5066100 Website: www.ziton.com UK Sales Enquiries: Tel: +44 (0)1908 281981 Fax: +44 (0)1908 282554

Certificate No: 092h to EN 54: Part 2 and 4:1997 Certificate No: 018c to EN 54: Part 2 and 4: 1997 Certificate No: 092e to BS 5839-4: 1988 This certificate is to a withdrawn standard. Control and indicating equipment conforming to this version of the standard is not suitable for use within the jurisdiction of the European Union (EU). This certification, to the withdrawn version of the standard, is maintained because control and indicating equipment meeting the withdrawn version of the standard is still requested by some regulators outside of the EU. Certificated Products ZC3-EN2 2 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 4 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) Certificated with the following options from EN 54-2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to fire protection equipment 7.11 Delays to outputs 8.9 Output to fault routing equipment 10 Test condition 8 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) Certificated with the following options from EN 54-2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to fire protection equipment 7.11 Delays to outputs 8.9 Output to fault routing equipment 10 Test condition 16 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) Certificated with the following options from EN 54-2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to fire protection equipment 7.11 Delays to outputs 8.9 Output to fault routing equipment 10 Test condition 32 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1629 Display board LPCB Ref. No. 018c/02

ZC3-EN4

018c/03

ZC3-EN8

018c/04

ZC3-EN16

018c/05

ZC3-EN32

018c/06

January 2009

33

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products C1632 16 Zone Expansion board C1652 5A Power supply board C1631 Repeater interface board (option) Certificated with the following options from EN 54-2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to fire protection equipment 7.11 Delays to outputs 8.9 Output to fault routing equipment 10 Test condition 8 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 16 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 32 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface board (option) 2,4 and 8 loop analogue addressable control and indicating equipment Incorporating as modular units: ZP-PS230V4A-3 power supply unit ZP-MCB5 main control board ZP-LD8-4 line driver board ZP-DU81L-2 LCD ZP-DU81P-2 plasma display board ZP-PR1 printer kit ZP-RL8-1 8 way programmable relay board Note: This product is certificated to a withdrawn standard. Control and indicating equipment conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. 1, 2 and 4 loop analogue addressable control and indicating equipment Incorporating as modular units: ZP3-MB2-4L 4 Loop Main board ZP3-MB2-2L 2 Loop Main board ZP3-MB2-1L 1 Loop Main board ZP3-CPU1 CPU board ZP3-DB1 Display board ZP3-ZB50 50 Zone LED board ZP3-CB1 Commissioning key switch board ZP3-PR1 Printer Kit ZP3AB-SCB-D Control bus drive ZP3AB-RL8 Programmable relay output board, 8 way ZP3-AB-MA8 Programmable monitored output board, 8 way ZP3AB-OP24 Programmable transistor output board, 24 way ZP3AB-MIP8 Programmable input board, 8 way ZP3-xL 230V ac Power supply unit Approved with the following options from EN54-2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to fire protection equipment 7.11 Delays to outputs 7.12 Co-incidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to fault routing equipment 9.5 Disablement of addressable points 10.0 Test condition 11.0 Standardised input/output interface LPCB Ref. No.

ZC3-RDU230-8

018c/R01

ZC3-RDU230-16

018c/R02

ZC3-RDU230-32 32 zone conventional repeater unit

018c/R03

ZP5 Mark 5

092e/01

ZP3

092h/01

34

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

GE Security Inc
5 North Main Street, Pittsfield, ME 04967, USA Tel: +1 207 487 3104 Fax: +1 207 487 5526 E-mail: leon.newsome@ge.com Website: www.gesecurity.com
Certificate No: 262v to EN 54: Part 2 and 4: 1997 Certificated Products EST3 Control and indicating equipment Incorporating as modular units: 3-PPS/M 230E Primary power supply 3-BPS/M 230E Power supply booster 3-CPU Central processor module 3-LCD Main LCD display for 3 CPU1. 3-LDSM LED display support local rail module. 3-SSDC Single Signature driver controller module 3-AADC System Sensor driver controller module 3-IDC8/4 Traditional zone I/O module. 3-RS485 Network communications card 3-RS232 Ancillary communications card 3-24Y 24 yellow LED card 3-24R 24 red LED card 3-24RY 24 red/yellow LED card Repeater Incorporating as modular units: 3-ANNCPU1 Central Processor Module 3-LCD Main LCD Display for 3 CPU The following options with requirements are certified with this equipment: 7.8 Output to fire alarm devices 7.13 Alarm counter 8.3 Fault Signals from points. 10 Test condition LPCB Ref. No. 262v/01

EST3

262v/01

Gent By Honeywell
140 Waterside Road, Hamilton Industrial Park, Leicester LE5 1TN UK Tel: +44 (0)116 246 2000 Fax: +44 (0)116 246 2300 E-mail: gent_enquiry@gent.co.uk Website: www.gent.co.uk Middle East Sales Enquiries E-mail: gent.export@honeywell.com

Certificate No: 042bb to EN 54-2:1997 and EN 54-4: 1997 Certificate No: 042x to EN 54: Parts 2 & 4: 1997

AS-2000 Two Loop analogue addressable control and indicating equipment


Certificated Products AS-2000 Two loop analogue addressable control and indicating equipment Incorporating as modular units: 2434-824 Power supply 2434-710 Loop Processor Card 2434-833 Master Control Card 2434-825 Optical Network Card* 2434-821 Message Store Card* 2434-822 Mother board 2434-835 H.M.I 2434-840 Cold fire card 2434-796 Addressable speaker card (Optional Card)* LPCB Ref. No. 042bb/01

January 2009

35

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 2434-826 Addressable daughter speaker card (Optional Card)* 2434-780 Audio Input Card (Optional Card)* 2434-781 Audio Output Card (Optional Card)* Note: Scope of approval does not include the functionality of the network card and optional voice alarm system cards) 1 zone conventional control and indicating equipment Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Delays of actioning to outputs to fire alarm routing equipment 10 Test condition 2 zone conventional control and indicating equipment Certified with the following options from EN 54 Part 2: 1997 7.8 Output to fire alarm devices 7.9 Delays of actioning to outputs to fire alarm routing equipment 10 Test condition 4 zone conventional control and indicating equipment Certified with the following options from EN 54 Part 2: 1997 7.8 Output to fire alarm devices 7.9 Delays of actioning to outputs to fire alarm routing equipment 10 Test condition 8 zone conventional control and indicating equipment Certified with the following options from EN 54 Part 2: 1997 7.8 Output to fire alarm devices 7.9 Delays of actioning to outputs to fire alarm routing equipment 10 Test condition Single loop analogue addressable control and indicating equipment Incorporating as modular units: 2434-334 Power supply PCB VIG-LPC 1 Loop processor card VIG-MCC Master Controller Card 2434-766 Display PCB 2434-578 Terminal PCB 2434-581 GENT backpanel VIG-IOC-DOM Output card 2434-591 Printer PCB VIG-NC-FO Fibre optic Network card Scope of approval does not include the operation of the network card) 2 loop analogue addressable control and indicating equipment Incorporating as modular units: 2434-334 Power supply PCB VIG-LPC 2 Loop processor card VIG-MCC Master controller card 2434-766 Display PCB 2434-578 Terminal PCB 2434-581 GENT backpanel VIG-IOC-DOM Output card 2434-591 Printer PCB VIG-NC-FO Fibre optic Network card Scope of approval does not include the operation of the network card) 3 loop analogue addressable control and indicating equipment Incorporating as modular units: 2434-334 Power supply PCB VIG-LPC 3 Loop processor card VIG-MCC Master controller card 2434-766 Display PCB 2434-578 Terminal PCB 2434-581 GENT backpanel VIG-IOC-DOM Output card 2434-591 Printer PCB VIG-NC-FO Fibre optic Network card Scope of approval does not include the operation of the network card) 4 loop analogue addressable control and indicating equipment Incorporating as modular units: 2434-334 Power supply PCB VIG-LPC 4 Loop processor card VIG-MCC Master controller card 2434-766 Display PCB 2434-578 Terminal PCB 2434-581 GENT backpanel VIG-IOC-DOM Output card 2434-591 Printer PCB LPCB Ref. No.

13270-01

042x/01

13270-02

042x/02

13270-04

042x/03

13270-08

042x/04

VIG 1

042x/06

VIG 2

042x/07

VIG 3

042x/08

VIG 4

042x/09

36

January 2009

SECTION 3: PART
Certificated Products VIG-NC-FO Fibre optic Network card Scope of approval does not include the operation of the network card) Incororating as modular units: 2434-824 Power supply 2434-710 Loop Processor card 2434-833 Master Control card 2434-825 Optical Network card* 2434-821 Message Store card* 2434-822 Mother board 2434-835 H.M.I. 2434-840 Cold fire card 2434-796 Addressable speak card (Optional Card)* 2434-826 Addressable daughter speaker card (Optional Card)* 2434-780 Audio Input Card (Optional Card)* 2434-781 Audio Output Card (Optional Card)* (*Note: Scope of approval does not include the functionality of the network card and optional voice alarm system cards) Certified with the following options from EN 54 Part 2: 1997 7.8 Output to fire alarm devices 7.11 Delays to outputs 8.3 Fault signals from points 9.5 Disablement of each address point 10 Test condition LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

Certificate No: 042d to BS 5839-4: 1988 This certificate is to a withdrawn standard. Control and indicating equipment conforming to this version of the standard is not suitable for use within the jurisdiction of the European Union (EU). This certification, to the withdrawn version of the standard, is maintained because control and indicating equipment meeting the withdrawn version of the standard is still requested by some regulators outside of the EU. Certificated Products 3404 Control and indicating equipment Incorporating as modular units13430-01V3 Local Controller Card (LCC)13431-01V3 Loop Processor Card (LPC)13432-03V3 Input Output Card (IOC)13433-01V3 Random Access Memory (RAM) card 1 loop control and indicating equipment Note: This product is certificated to a withdrawn standard. Control and indicating equipment conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. 2 loop control and indicating equipment Note: This product is certificated to a withdrawn standard. Control and indicating equipment conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. 3 loop control and indicating equipment Note: This product is certificated to a withdrawn standard. Control and indicating equipment conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. 4 loop control and indicating equipment Incorporating as modular units: VIG-LCC V3+ Loop Controller Card (LCC) VIG-LPC V3+ Loop Processor Card (LPC) VIG-IOC V3+ Input Output Card (IOC) VIG-RAM Random Access Memory Card (RAM) Note: This product is certificated to a withdrawn standard. Control and indicating equipment conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. LPCB Ref. No. 042d/05

VIG1-V3+

042d/07

VIG2-V3+

042d/08

VIG3-V3+

042d/09

VIG4-V3+

042d/10

January 2009

37

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificate No: 042at Certificated Products 8000 M 7 loop analogue addressable control and indicating equipment Incorporating as modular units: 771690 Power Supply Module 772414 Basic Module 772441 Display Card 772411 LED Module 772412 Group Individual Indication 128 Zones 772413 Group Individual Indication 384 Zones 772418 Peripheral Module 772419 Peripheral Module 772420 Peripheral Module 772421 Extension Module 787530 4 Relay Module 787531 3 Relay Module 787532 3 Relay SaS Module 787533 BSL Module 787680 7 Output Module Positive 787681 7 Output Module Negative 784382 Analogue Ring Module 784385 CIE Triggering Module 802426 Powered Loop power pack module 804382 Analogue Ring Module powered loop 804383 Analogue Ring Module powered loop Approved with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing devices 7.10 Output to automatic fire protection equipment 7.12 Coincidence detection 7.13 Alarm counter 8.4 Total loss of the power supply 10 Test Condition 11 Output to standardised input/output interface 2 loop analogue addressable control and indicating equipment Incorporating as modular units: 771690 Power Supply Module 772414 Basic Module 772441 Display Card 772411 LED Module 772412 Group Individual Indication 128 Zones 772413 Group Individual Indication 384 Zones 772418 Peripheral Module 772419 Peripheral Module 772420 Peripheral Module 787530 4 Relay Module 787531 3 Relay Module 787532 3 Relay SaS Module 787533 BSL Module 787680 7 Output Module Positive 787681 7 Output Module Negative 784382 Analogue Ring Module 784385 CIE Triggering Module 802426 Powered Loop power pack module 804382 Analogue Ring Module powered loop 804383 Analogue Ring Module powered loop Approved with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing devices 7.10 Output to automatic fire protection equipment 7.12 Coincidence detection 7.13 Alarm counter 8.4 Total loss of the power supply 10 Test Condition 11 Output to standardised input/output interface LPCB Ref. No. 042at/01

8000 C

042at/02

38

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

Global System Technology Plc


Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire LE65 1RT UK Tel: +44 (0)1283 225 478 Fax: +44 (0)1283 222 039 E-mail: info@gst.uk.com Website: www.gst.uk.com
Certificate No: 548j to EN 54: Parts 2 and 4 :1997 Certificated Products GST 200 Intelligent 1 loop, 30 zone analogue addressable control and indicating equipment Incorporating the following units: F7.820.826 Main board F7.820.827 Switch board F7.820.828 Loop interface board F7.820.829 Power supply unit F7.908.312 Zone indication board CGM12864 Alphanumeric display F2.910.093 Mains filter R150 Transformer F2.828.630a Printer board (option) Incorporating as optional modular units: F7.820.170 RS-232 board for configuration P-9901 Printer module kit Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.10 Output to automatic Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection 8.3 Fault signals from points 9.5 Disablement of addressable points Single zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Two zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Four zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Eight zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Sixteen zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition LPCB Ref. No. 548j/01

GST 101

548j/02

GST 102

548j/03

GST 104

548j/04

GST 108

548j/05

GST 116

548j/06

GLT Exports Limited


Detection House, 72-78 Morfa Road, Swansea SA1 2EN UK Tel: +44 (0)1792 455175 Fax: +44 (0)1792 455176 E-mail: ghassan@gltexports.com Website: www.gltexports.com
Certificate No: 330d to EN 54: Part 2 and 4: 1997

January 2009

39

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products Premier SX Premier SX Premier SX Premier SX Premier SX 1 zone conventional control and indicating equipment 2 zone conventional control and indicating equipment 4 zone conventional control and indicating equipment 6 zone conventional control and indicating equipment 8 zone conventional control and indicating equipment Certified with the following options with requirements from EN 54: Part 2: 7.8 Output to fire alarm devices 7.11 Delays to the actioning of outputs 10 Test condition 2 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 4 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 8 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 16 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 32 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1629 Display board C1632 16 Zone expansion board C1652 5A Power Supply board C1631 Repeater interface (option) Certified with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 8 zone conventional repeater unit LPCB Ref. No. 330d/01 330d/02 330d/03 330d/04 330d/05

Premier MX

330d/06

Premier MX 4

330d/07

Premier MX 8

330d/08

Premier MX 16

330d/09

Premier MX 32

330d/10

Premier MX Repeater 8

330d/R01

40

January 2009

SECTION 3: PART
Certificated Products Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface 16 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface 32 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1629 Display board C1631 Repeater interface LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

Premier MX Repeater 16

330d/R02

Premier MX Repeater 32

330d/R03

Certificate No: 018c to EN 54-2 and 4:1997 Certificated Products Prem1er AL 4 loop analogue addressable control and indicating equipment Incorporating: A1579 Motherboard A1580 Display board A1585 Loop cards A1584 230V AC power supply control card A1599 Printer board Certified with the following options from EN 54:Part 2 7.8 Output to fire alarm devices 7.11 Delays to outputs 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition LPCB Ref. No. 018c/01

Group 4 Securicor Plc


Manor Royal, The Manor, Crawley, West Sussex RH10 9UN UK Tel: +44 (0)20 87707000 Fax: +44 (0)20 87722531 E-mail: allan.rignall@uae.g4s.com Website: www.g4s.com
Certificate No: 548j to EN 54-2: 1997 and EN54-4: 1997 Certificated Products GS200 Intelligent 1 loop, 30 zone, analogue addressable control and indicating equipment Incorporating the following units: F7.820.826 Main board F7.908.312 Zone indication board F7.820.827 Switch board F7.820.828 Loop interface board F7.820.829 Power Supply unit F2.910.093 Mains filter R150 Transformer CGM12864 Alphanumeric Display F2.828.630a Printer board (option) Incorporating as optional modular units: P-9901 Printer module kit F7.820.170 RS232 board for configuration Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.10 Output to automatic Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection LPCB Ref. No. 548j/01

January 2009

41

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 8.3 Fault signals from points 9.5 Disablement of addressable points Single zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Two zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Four zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Eight zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Sixteen zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition LPCB Ref. No. 548j/02

GS101

GS102

548j/03

GS104

548j/04

GS108

548j/05

GS116

548j/06

Gulf Security Technology Co. Ltd (Manufacturing Division of Global System Technology PLC)
No. 80 Changjiang East Road, Economic & Technological Development Zone, Qinhuangdao, Hebei Province 066004, Peoples Republic of China Tel: +86 0335 8502528 Fax: +86 0335 8508942 E-mail: gst@gst.com.cn Website: www.gst.com.cn Sales Beijing: Tel: +86 (10) 6439 1866 Fax: +86 (10) 6439 1787

Sales Hong Kong: Tel: +852 2877 8566 Fax: +852 2511 8699

Certificate No: 548j to EN 54-2:1997 & EN54-4:1997 Certificated Products GST-200 Intelligent 1 loop, 30 zone, analogue addressable control and indicating equipment Incorporating the following units: F7.820.826 Main board F7.908.312 Zone indication board F7.820.827 Switch board F7.820.828 Loop interface board F7.820.829 Power Supply unit F2.910.093 Mains filter R150 Transformer CGM12864 Alphanumeric Display F2.828.630a Printer board (option) Incorporating as optional modular units: P-9901 Printer module kit F7.820.170 RS232 board for configuration Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.10 Output to automatic Fire Protection Equipment LPCB Ref. No. 548j/01

42

January 2009

SECTION 3: PART
Certificated Products 7.11 Delays to outputs 7.12 Coincidence detection 8.3 Fault signals from points 9.5 Disablement of addressable points Single zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Two zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Four zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Eight zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Sixteen zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

GST 101

548j/02

GST 102

548j/03

GST 104

548j/04

GST 108

548j/08

GST 116

548j/09

Kidde Products Limited


Unit 2 Admiral Point, Dawdon Enterprise Park, Seaham, County Durham SR7 PP UK Tel: +44 (0)191 513 6100 Fax: +44 (0)191 513 6102 Website: www.kiddeproducts.com
Certificate No: 054d to EN 54: Parts 2 and 4 Certificated Products Sirius II SE8000 Sirius II SE4000 8 zone conventional control and indicating equipment 4 zone conventional control and indicating equipment Certified with the following options from EN 54-2:1997: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 10 Test condition 2 zone conventional control and indicating equipment Certified with the following options from EN 54-2:1997: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 10 Test condition LPCB Ref. No. 054d/03 054d/04

Sirius II SE2000

054d/05

January 2009

43

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT

Morley-IAS Fire Systems By Honeywell


Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@morleyias.co.uk Website: www.morley-ias.co.uk
Certificate No: 429a to EN 54: Part 2 and 4: 1997 Certificated Products ZX2e 1-2 loop analogue addressable control and indicating equipment Incorporating the following units: 124-206 Processor card 124-327 ZX2/5e 20 zone display 124-231 Apollo Discovery loop driver card 124-195 Hochiki loop driver 124-249-003 Morley IAS loop driver card 124-207-003 2A PSU 124-209-002 2 loop base card 124-196 230V filter card 1-5 loop analogue addressable control and indicating equipment Incorporating the following units: 124-206 Processor card 124-327 ZX2/5e 20 zone display 124-205-002 3A PSU 124-330-001 60 zone extender 124-354 5 loop base card 124-231 Apollo Discovery loop driver card 124-195 Hochiki loop driver 124-249-003 Morley IAS loop driver card The ZX model range Certified with the following options with requirements from EN 54 part 2: 7.8 Output to fire alarm devices 7.11 Delays to outputs 7.12 Coincidence detection 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition 1-2 loop analogue addressable control and indicating equipment Incorporating the following units: 124-206 Processor card 124-231 Apollo Discovery loop driver card 124-195 Hochiki loop driver card 124-329 320b/380b 20 zone display 124-207-003 2A PSU 124-209-002 2 loop base card 124-196 230V filter card 1-5 loop analogue addressable control and indicating equipment Incorporating the following units: 124-206 Processor card 124-205-002 3A PSU 124-330-001 60 zone extender 124-354 5 loop base card 124-231 Apollo Discovery loop driver card 124-195 Hochiki loop driver card 124-329 320B/380B 20 zone display The 3xxx model range Certified with the following options with requirements from EN 54 part 2: 7.8 Output to fire alarm devices 7.11 Delays to outputs 7.12 Coincidence detection 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition DX1e-40M 1 loop, 40 zone, analogue addressable control indicating equipment Incorporating the following units: 429a/07 LPCB Ref. No. 429a/01

ZX5e

429a/02

320b

429a/05

380b

429a/06

44

January 2009

SECTION 3: PART
Certificated Products 124-336 Loop base card 124-335 Display card 124-337 Printer module (DX1e-40MP only) Note: The CIE is compatible with Apollo, Hochiki and System sensor protocols 1 loop 20 zone, analogue addressable control indicating equipment. Incorporating the following units: 124-336 Loop base card 124-335 Display card Note: The CIE is compatible with Apollo, Hochiki and System sensor protocols 2 loop, 40 zone, analogue addressable control indicating equipment Incorporating the following units: 124-344 Loop base card 124-335 Display card 124-337 Printer module (DX2e-40MP and DX2e-40LP only) Note: The CIE is compatible with Morley protocol 2 loop, 40 zone, analogue addressable control indicating equipment Incorporating the following units: 124-344 Loop base card 124-335 Display card 124-337 Printer module (DX2e-40MP and DX2e-40LP only) Note: The CIE is compatible with Apollo, Hochiki and System sensor protocols 4 loop, 40 zone, analogue addressable control indicating equipment Incorporating the following units: 124-344 Loop base card 124-351 Two loop plug in cards 124-335 Display card 124-337 Printer module (DX4e-40LP only) Note: The CIE is compatible with Apollo, Hochiki and System sensor protocols The DX model range Certified with the following options with requirements from EN 54 part 2: 7.8 7.11 7.12 8.3 9.5 Output to fire alarm devices Delays to outputs Coincidence detection Fault signals from points Disablement of addressable points 10 Test condition LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

DXIe-206

429a/07

DX2e-40L-M

429a/08

DX2e-40M

429a/08

DX4e-40L

429a/09

All of the above are certified with the following options with requirements from EN 54: Part 2 7.8 Output to fire alarm devices 7.11 Delays to outputs 7.12 Coincidence detection 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition

Certificate No: 154d to EN 54:Part 2 and 4: 1997 Certificated Products Horizon HRZ2-8 Horizon HRZ2-8 Horizon HRZ2-8 HRZ2-8 002-479-322 Morley-IAS Horizon, 2 zone, dual relay, Danish, Finish, Norwegian, Swedish (Region 3) 002-492-222 Morley-IAS Horizon, 2 zone, 2w relay, English, French, Spanish, Portuguese, Italian (Region 2) + UK user manual 002-506-222 Morley-IAS Horizon, 2 zone, English, French, Spanish, Portuguese, Italian (Region 2) + UK user manual Horizon 2 Zone conventional control and indicating equipment Including the following versions: 002-479-122 Language region 1, English manual 002-479-222 Language region 2 002-479-322 Language region 3, dual relay 002-492-222 Language region 2, dual relay, English manual 002-506-222 Language region 2, English manual 002-479-342 Morley-IAS Horizon, 4 zone, dual relay, Danish, Finish, Norwegian, Swedish (Region 3) 002-492-242 Morley-IAS Horizon, 4 zone, 2w relay, English, French, Spanish, LPCB Ref. No. 154d/09 154d/09 154d/09 154d/09

Horizon HRZ2-8 Horizon HRZ2-8

154d/10 154d/10

January 2009

45

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products Horizon HRZ2-8 HRZ2-8 Portuguese, Italian (Region 2) + UK user manual 002-506-242 Morley-IAS Horizon, 4 zone, English, French, Spanish, Portuguese, Italian (Region 2) + UK user manual Horizon 4 zone conventional control and indicating equipment Including the following versions: 002-479-142 Language region 1, English manual 002-479-242 Language region 2 002-479-342 Language region 3, dual relay 002-492-242 Language region 2, dual relay, English manual 002-506-242 Language region 2, English manual 002-479-382 Morley-IAS Horizon, 8 zone, dual relay, Danish, Finish, Norwegian, Swedish (Region 3) 002-492-282 Morley-IAS Horizon, 8 zone, 2w relay, English, French, Spanish, Portuguese, Italian (Region 2) + UK user manual 002-506-282 Morley-IAS Horizon, 8 zone, English, French, Spanish, Portuguese, Italian (Region 2) + UK user manual Horizon 8 zone conventional control and indicating equipment Including the following versions: 002-479-182 Language region 1, English manual 002-479-282 Language region 2 002-479-382 Language region 3, dual relay 002-492-282 Language region 2, dual relay, English manual 002-506-282 Language region 2, English manual The HRZ model range Certified with the following options with requirements from EN 54 part 2: 7.8 7.9 7.11 7.12 10 Output to fire alarm devices Output to fire routing equipment Delays to outputs Coincidence detection Test condition LPCB Ref. No. 154d/10 154d/10

Horizon HRZ2-8 Horizon HRZ2-8 Horizon HRZ2-8 HRZ2-8

154d/11 154d/11 154d/11 154d/11

Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 10 Test condition

Napco Gulf Security Group


P.O. Box 54533, Dubai Airport Free Zone, UAE Tel: +971 4 2997703 Fax: +971 4 2997704 E-mail: info@napcogulfsecurity.com Website: www.napcogulfsecurity.com
Certificate No: 548j to EN 54-2: 1997 and EN54-4: 1997 Certificated Products NGSG200 Intelligent 1 loop, 30 zone, analogue addressable control and indicating equipment Incorporating the following units: F7.820.826 Main board F7.908.312 Zone indication board F7.820.827 Switch board F7.820.828 Loop interface board F7.820.829 Power Supply unit F2.910.093 Mains filter R150 Transformer CGM12864 Alphanumeric Display LPCB Ref. No. 548j/01

46

January 2009

SECTION 3: PART
Certificated Products F2.828.630a Printer board (option) Incorporating as optional modular units: P-9901 Printer module kit F7.820.170 RS232 board for configuration Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.10 Output to automatic Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection 8.3 Fault signals from points 9.5 Disablement of addressable points Single zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Two zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Four zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Eight zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Sixteen zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

NGSG101

548j/02

NGSG102

548j/03

NGSG104

548j/04

NGSG108

548j/05

NGSG116

548j/06

Nitin Ventures FZE


P.O. Box 262294, Jabel Ali Free Zone, Dubai, UAE Tel: +97 148865858/859 Fax: +97 148865800 E-mail: sales@nitinventures.com Website: www.nitinventures.com
Certificate No: 018c to EN 54-2: 1997 and EN 54-4: 1997 Certificated Products Discovery 4 loop analogue addressable control and indicating equipment Incorporating as modular units: A1579 Motherboard A1580 Display board A1585 Loop cards A1584 230Vac power supply control card A1599 Printer board Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm devices 7.11 Delays to outputs 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition 2 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options with requirements from EN54-2: 1997 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment LPCB Ref. No. 018c/01

NV 2

018c/02

January 2009

47

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 4 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options with requirements from EN54-2: 1997: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 8 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options with requirements from EN54-2: 1997: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 16 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface (option) Certified with the following options with requirements from EN54-2: 1997: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 32 zone conventional control and indicating equipment Incorporating as modular units: C1627 Mother board C1629 Display board C1632 16 Zone expansion board C1652 5A Power supply board C1631 Repeater interface (option) Certified with the following options with requirements from EN54-2: 1997: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 8.9 Output to fault warning equipment 10 Test condition 8 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface 16 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface 32 zone conventional repeater unit Incorporating as modular units: C1627 Mother board C1628 Display board C1631 Repeater interface LPCB Ref. No.

NV 4

018c/03

NV 8

018c/04

NV 16

018c/05

NV 32

018c/06

NV 8R

018c/R01

NV 16R

018c/R02

NV 32R

018c/R03

48

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

Notifier By Honeywell
Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@notifiersystems.co.uk Website: www.notifierfiresystems.co.uk
Certificate No: 154d to EN 54: Part 2 and 4: 1997 Certificated Products ID2000 2-8 loop analogue addressable control and indicating equipment 020-628 Language Group 0 basic equipment kit 020-628-001 Language Group 1 basic equipment kit Fixed 2 loop analogue addressable control and indicating equipment 002-459 Language Group 0 002-459-001 Language Group 1 002-472 Languarge Group 0, red cover Incorporating as modular units: 020-469-009 Extension Chassis with 17-80 Zone LED Display 020-708-009 Extension Chassis with Printer 020-644-009 Printer Assembly 020-588 LIB, Loop Interface Board 020-478 RS232 Communications Kit 020-479 RS485 Communications Kit 020-484 PSU2.5A Power Supply 020-648 PSU3A Power Supply 020-579 PSU7A Power Supply (Requires DTP / Booster Interface) 020-543 DTP Dual Transmission Path / Booster Interface 020-541-009 78Ah Battery and PSU7A Enclosure 020-472-009 Standard Back Box Kit 020-473-009 Extended Back Box Kit 020-474-009 Extended Deep Back Box Kit 020-475-009 Double Extended Back Box Kit 020-476-009 Double Extended Deep Back Box Kit 020-508-009 Standard Back Box Extension Kit 020-509-009 Deep Back box Extension Kit 020-480-009 Main Cover Kit 020-481-009 Extension Cover Kit 020-513-009 High Security Main Cover 020-514-009 High Security Extension Cover Certified with the following options with requirements from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition 2-8 loop analogue addressable control and indicating equipment 002-538 Language Group 0 basic equipment kit 020-538-001 Language Group 1 basic equipment kit Certified with the following options with requirements from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to Fault warning routing equipment 9.5 Disablement of addressable points 10 Test condition Fixed 2 loop analogue addressable control and indicating equipment 002-474 Language Group 0 002-474-001 Language Group 1 LPCB Ref. No. 154d/01

ID2002

154d/01

ID3000

154d/02

ID3002

154d/02

January 2009

49

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 002-473 Language Group 0, red cover LPCB Ref. No. Incorporating as modular units: 020-559-001 Extension Chassis with 1-64 Zone LED Display 020-559-002 Extension Chassis with 65-128 Zone LED Display 020-612 Extension Chassis with 1-256 Zone LED Display 020-708-009 Extension Chassis with Printer 020-644-009 Printer Assembly 020-588 LIB Loop Interface Board 020-549 ELIB, Enhanced Loop Interface Board 020-478 RS232 Communications Kit 020-479 RS485 Communications Kit 020-484 PSU2.5A Power Supply 020-648 PSU3A Power Supply 020-579 PSU7A Power Supply (Requires DTP / Booster Interface) 020-543 DTP Dual Transmission Path / Booster Interface 020-541-009 78Ah Battery and PSU7A Enclosure 020-472-009 Standard Back Box Kit 020-473-009 Extended Back Box Kit 020-474-009 Extended Deep Back Box Kit 020-475-009 Double Extended Back Box Kit 020-476-009 Double Extended Deep Back Box Kit 020-508-009 Standard Back Box Extension Kit 020-509-009 Deep Backbox Extension Kit 020-480-009 Main Cover Kit 020-481-009 Extension Cover Kit 020-513-009 High Security Main Cover 020-514-009 High Security Extension Cover 020-621-009 256 Zone LED Display Cover 020-647 NGM ID2net Network Gateway Module 020-643 Fibre Optic Interface Module 2 Zone conventional control and Indicating equipment 002-477-129 Notifier 2 zone, English, French, German, Dutch, Swedish, Icelandic (Region 1) 2 Zone conventional control and Indicating equipment 002-477-229 Notifier 2 zone, English, French, Spanish, Portuguese, Italian (Region 2) 2 Zone conventional control and Indicating equipment 002-477-329 Notifier 2 zone, dual relay, Danish, Finish, Norwegian, Swedish (Region 3) 2 Zone conventional control and Indicating equipment 002-490-129 Notifier 2 zone, dual relay, English, French, German, Dutch, Swedish, Icelandic (Region 1) + UK user manual 2 Zone conventional control and Indicating equipment 002-490-229 Notifier 2 zone, dual relay, English, French, Spanish, Portuguese, Italian (Region 2) + UK user manual 4 Zone conventional control and Indicating equipment 002-477-149 Notifier 4 zone, English, French, German, Dutch, Swedish, Icelandic (Region 1) 4 Zone conventional control and Indicating equipment 002-477-249 Notifier 4 zone, English, French, Spanish, Portuguese, Italian (Region 2) 4 Zone conventional control and Indicating equipment 002-477-349 Notifier 4 zone, dual relay, Danish, Finish, Norwegian, Swedish (Region 3) 4 Zone conventional control and Indicating equipment 002-490-149 Notifier 4 zone, dual relay, English, French, German, Dutch, Swedish, Icelandic (Region 1) + UK user manual 4 Zone conventional control and Indicating equipment 002-490-249 Notifier 4 zone, dual relay, English, French, Spanish, Portuguese, Italian (Region 2) + UK user manual 8 Zone conventional control and Indicating equipment 002-477-189 Notifier 8 zone, English, French, German, Dutch, Swedish, Icelandic (Region 1) 8 Zone conventional control and Indicating equipment 002-477-289 Notifier 8 zone, English, French, Spanish, Portuguese, Italian (Region 2) 8 Zone conventional control and Indicating equipment 002-477-389 Notifier 8 zone, dual relay, Danish, Finish, Norwegian, Swedish (Region 3) 8 Zone conventional control and Indicating equipment 002-490-189 Notifier 8 zone, dual relay, English, French, German, Dutch, Swedish, Icelandic (Region 1) + UK user manual 8 Zone conventional control and Indicating equipment 002-490-289 Notifier 8 zone, dual relay, English, French, Spanish, Portuguese, Italian (Region 2) + UK user manual Network Gateway Unit

NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 NFS2-8 002-467 NGU, ID(2)net

154d/09 154d/09 154d/09 154d/09 154d/09 154d/10 154d/10 154d/10 154d/10 154d/10 154d/11 154d/11 154d/11 154d/11 154d/11 154d/N02

50

January 2009

SECTION 3: PART
Certificated Products Incorporating the following modular units, is approved for use with the ID3000 control and indicating equipment: 2 020-647 NGM, ID net Network Gateway Module 020-643 Fibre Optic Interface Module 020-648 PSU3A Power Supply Module ID300x panel and associated units are certified with the following options with requirements from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition Single loop analogue addressable control and indicating equipment Incorporating the following units: 002-455 Language Group 0, 1.5A PSU, 12Ah batteries 002-455-001 Language Group 1, 1.5A PSU, 12Ah batteries 020-553 RS485 Communication Kit Single loop analogue addressable control and indicating equipment Incorporating the following units: 002-462 Language Group 0, 3A PSU, 12Ah Batteries, Printer Option 002-462-001 Language Group 1, 3A PSU, 12Ah Batteries, Printer Option 020-553 RS485 Communication Kit 020-644-009 PRN-ID Printer Kit Single loop analogue addressable control and indicating equipment Incorporating the following units: 002-460 Language Group 0, 3A PSU, 42Ah Batteries, Printer Option 002-460-001 Language Group 1, 3A PSU, 42Ah Batteries, Printer Option 020-553 RS485 Communication Kit 020-644-009 PRN-ID Printer Kit Single loop analogue addressable control and indicating equipment Incorporating the following units: 002-456 Language Group 0, 1.5A PSU, 12Ah batteries, VIEW 002-456-001 Language Group 1, 1.5A PSU, 12Ah batteries, VIEW 020-553 RS485 Communication Kit Single loop analogue addressable control and indicating equipment Incorporating the following units: 002-463 Language Group 0, 3A PSU, 42Ah Batteries, VIEW, Printer Option 002-463-001 Language Group 1, 3A PSU, 12Ah Batteries, VIEW, Printer Option 020-553 RS485 Communication Kit 020-644-009 PRN-ID Printer Kit Single loop analogue addressable control and indicating equipment Incorporating the following units: 002-461 Language Group 0, 3A PSU, 42Ah Batteries, VIEW, Printer Option 002-461-001 Language Group 1, 3A PSU, 42Ah Batteries, VIW, Printer Option 020-553 RS485 Communication Kit 020-644-009 PRN-ID Printer Kit The ID5x/6x models are certified with the following options with requirements from EN 54 part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm Counter 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition 2 Zone conventional control and indicating equipment Including the following versions: 002-477-122 Language region 1, light grey 002-477-129 Language region 1, black & grey 002-490-222 Language region 2, light grey 002-477-229 Language region 2, black & grey 002-477-322 Language region 3, light grey, dual relay 002-477-329 Language region 3, black & grey, dual relay, English manual 002-490-129 Language region 1, black & grey, dual relay, English manual 002-490-229 Language region 2, black & grey, dual relay, English manual 002-490-222 Language region 2, light grey, English manual 4 Zone conventional control and indicating equipment LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

ID50

154d/03

ID51

154d/04

ID52

154d/05

ID60

154d/06

ID61

154d/07

ID62

154d/08

NFS2-8

154d/09

NFS2-8

154d/10

January 2009

51

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products Including the following versions: 002-477-142 Language region 1, light grey 002-477-149 Language region 1, black & grey 002-490-242 Language region 2, light grey 002-477-249 Language region 2, black & grey 002-477-342 Language region 3, light grey, dual relay 002-477-349 Language region 3, black & grey, dual relay, English manual 002-490-149 Language region 1, black & grey, dual relay, English manual 002-490-249 Language region 2, black & grey, dual relay, English manual 002-490-242 Language region 2, light grey, English manual 8 Zone conventional control and indicating equipment Including the following versions: 002-477-182 Language region 1, light grey 002-477-189 Language region 1, black & grey 002-477-282 Language region 2, light grey 002-477-289 Language region 2, black & grey 002-477-382 Language region 3, light grey, dual relay 002-477-389 Language region 3, black & grey, dual relay, English manual 002-490-189 Language region 1, black & grey, dual relay, English manual 002-490-289 Language region 2, black & grey, dual relay, English manual 002-490-282 Language region 2, light grey, English manual LPCB Ref. No.

NFS2-8

154d/11

The NFS2-8 (2-8 zones) panels are certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 10 Test condition

Certificate No: 154f to ISO 7240: Part 2 & 4: 2003 Certificated Products NFS2-8 2 zone conventional control and indicating equipment Including the following versions: 002-477-122 Language region 1, light grey 002-477-129 Language region 1, black & grey 002-477-222 Language region 2, light grey 002-477-229 Language region 2, black & grey 002-477-322 Language region 3, light grey, dual relay 002-477-329 Language region 3, black & grey, dual relay, English manual 002-490-129 Language region 1, black & grey, dual relay, English manual 002-490-229 Language region 2, black & grey, dual relay, English manual 002-490-222 Language region 2, light grey, English manual 4 zone conventional control and indicating equipment Including the following versions: 002-477-142 Language region 1, light grey 002-477-149 Language region 1, black & grey 002-477-242 Language region 2, light grey 002-477-249 Language region 2, black & grey 002-477-342 Language region 3, light grey, dual relay 002-477-349 Language region 3, black & grey, dual relay, English manual 002-490-149 Language region 1, black & grey, dual relay, English manual 002-490-249 Language region 2, black & grey, dual relay, English manual 002-490-242 Language region 2, light grey, English manual 8 zone conventional control and indicating equipment Including the following versions: 002-477-182 Language region 1, light grey 002-477-189 Language region 1, black & grey 002-477-282 Language region 2, light grey LPCB Ref. No. 154f/01

NFS2-8

154f/02

NFS2-8

154f/03

52

January 2009

SECTION 3: PART
Certificated Products Language region 2, black & grey Language region 3, light grey, dual relay Language region 3, black & grey, dual relay, English manual 002-490-189 Language region 1, black & grey, dual relay, English manual 002-490-289 Language region 2, black & grey, dual relay, English manual 002-490-282 Language region 2, light grey, English manual The NFS2-8 (2 -8 zones) panels are certified with the following options from ISO 7240 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire routing equipment 7.11 Delays to outputs 7.12 Dependency detection 11 Test condition 002-477-289 002-477-382 002-477-389 LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

Novar GmbH
Security and Building Management Systems, Dieseltrasse 2, D-41469, Neuss, Germany Tel: +49 (0)2137 170 Fax: +49 (0)2137 17286 E-mail: info@esser-systems.de Website: www.esser-systems.de
Certificate No: 400f to EN 54: Part 2 and 4: 1997 Certificated Products 8000M 7 loop analogue addressable control and indicating equipment Incorporating as modular units 771690 Power Supply Module 772414 Basic Module 772441 Display Card 772411 LED Module 772412 Group Individual Indication 128 Zones 772413 Group Individual Indication 384 Zones 772418 Peripheral Module 772419 Peripheral Module 772420 Peripheral Module 772421 Extension Module 787530 4 Relay Module 787531 3 Relay Module 787532 3 Relay SaS Module 787533 BSL Module 787680 7 Output Module Positive 787681 7 Output Module Negative 784382 Analogue Ring Module 784385 CIE Triggering Module 802426 Powered Loop power pack module 804382 Analogue Ring Module powered loop 804383 Analogue Ring Module powered loop 2 loop analogue addressable control and indicating equipment Incorporating as modular units 771690 Power Supply Module 772441 Display Card 772411 LED Module 772412 Group Individual Indication 128 Zones 772413 Group Individual Indication 384 Zones 772414 Basic Module 772418 Peripheral Module 772419 Peripheral Module 772420 Peripheral Module 787530 4 Relay Module 787531 3 Relay Module 787532 3 Relay SaS Module 787533 BSL Module 787680 7 Output Module Positive LPCB Ref. No. 400f/01

8000C

400f/02

January 2009

53

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 787681 7 Output Module Negative 784382 Analogue Ring Module 784385 CIE Triggering Module 802426 Powered Loop power pack module 804382 Analogue Ring Module powered loop 804383 Analogue Ring Module powered loop 7 loop analogue addressable control and indicating equipment Incorporating as modular units 772441 Display Card 772411 LED Module 772412 Group Individual Indication 128 Zones 772413 Group Individual Indication 384 Zones 808004 Base package IQ8Control M 772480 Interface (IF)-Board IQ8Control X 772482 Interface (IF)-Board IQ8Control M 772485 CPU-Module CF Processor 772477 Peripheral Module 772478 Peripheral Module 772479 Peripheral Module 772476 Extension Module 787530 4 Relay Module 787531 3 Relay Module 787532 3 Relay SaS Module 787533 BSL Module 787680 7 Output Module Positive 787681 7 Output Module Negative 784382 Analogue Ring Module 784385 CIE Triggering Module 802426 Powered Loop power pack module 804382 Analogue Ring Module powered loop 804383 Analogue Ring Module powered loop 784842 RS232/TTY Module 2 loop analogue addressable control and indicating equipment Incorporating as modular units 772441 Display Card 772411 LED Module 772412 Group Individual Indication 128 Zones 772413 Group Individual Indication 384 Zones 808003 Base package IQ8Control C 772480 Interface (IF)-Board IQ8Control X 772481 Interface (IF)-Board IQ8Control C 772485 CPU-Module CF Processor 772477 Peripheral Module 772478 Peripheral Module 772479 Peripheral Module 787530 4 Relay Module 787531 3 Relay Module 787532 3 Relay SaS Module 787533 BSL Module 787680 7 Output Module Positive 787681 7 Output Module Negative 784382 Analogue Ring Module 784385 CIE Triggering Module 802426 Powered Loop power pack module 804382 Analogue Ring Module powered loop 804383 Analogue Ring Module powered loop 784842 RS232/TTY Module LPCB Ref. No.

IQ8 Control M

400f/03

IQ8 Control C

400f/04

Certified with the following options from EN 54 Part 2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing devices 7.10 Output to automatic fire protection equipment 7.12 Coincidence detection 7.13 Alarm counter 8.4 Total loss of the power supply 10 Test Condition 11 Output to standardised input/output interface

54

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

Pelco Finland Oy
Kalkkipellontie 6, 02650 Espoo, Finland Tel: +358 10 446 511 Fax: +358 10 446 5103
Certificate No: 883a to EN 54-2 :1997 & EN 54-4 :1997 Certificated Products FX 8 Loop Analogue addressable CIE Basic unit incorporate the following modules: FX-MC FX-UI FX-PSB or FX-PSA Master controller User interface 4.5 A Power Supply 2.2 A Power Supply LPCB Ref. No. 883a/01

Optional Modules -The following modules are optional additions to the basic unit: FX-ALCB FX-ALCA FX-LC FX-CLC FX-IOC FX-SAA Two loop addressable controller - Apollo protocol card One loop addressable controller - Apollo protocol card Two loop addressable controller - System sensor protocol card Sixteen loop conventional Controller I/O controller board Serial communications adapter for communication with external systems

(BSM or Alarm Management Systems). FX-SAB Serial communications adapter for communication in a networked FX system and with external systems (BSM or Alarm Management Systems). FX-LB80 80 Zone LED indication card FX-LB32 32 Zone LED indication card FX-BAT Separate battery box (4x17Ah, 12V) FXM-BAT Separate battery box (4x12Ah, 12V) Certified with the following options with requirements from EN 54-2:1997 7.8 Outputs to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.4 Complete failure of power supply 8.9 Output to fault warning routing equipment 9.5 Disablement of addressable point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality 8 Loop Analogue addressable CIE Basic unit incorporate the following modules: FX-MC Master controller FX-UI User interface FX-PSB 4.5 A Power Supply or FX-PSA 2.2 A Power Supply Optional Modules - The following modules are optional additions to the basic unit: FX-ALCB Two loop addressable controller - Apollo protocol card FX-ALCA One loop addressable controller - Apollo protocol card FX-LC Two loop addressable controller - System sensor protocol card FX-CLC Sixteen loop conventional Controller FX-IOC I/O controller board FX-SAA Serial communications adapter for communication with external systems (BSM or Alarm Management Systems). FX-SAB Serial communications adapter for communication in a networked FX system and with external systems (BSM or Alarm Management Systems).

FXL

883a/02

January 2009

55

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products FX-LB80 80 Zone LED indication card FX-LB32 32 Zone LED indication card FX-BAT Separate battery box (4x17Ah, 12V) FXM-BAT Separate battery box (4x12Ah, 12V) Certified with the following options with requirements from EN 54-2:1997 7.8 Outputs to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.4 Complete failure of power supply 8.9 Output to fault warning routing equipment 9.5 Disablement of addressable point 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality. 4 Loop Analogue addressable CIE Basic unit incorporate the following modules: FX-MC Master Controller FX-UI User Interface FX-PSB 4.5 A Power Supply or FX-PSA 2.2 A Power Supply Optional Modules -The following modules are optional additions to the basic unit: FX-ALCB FX-ALCA FX-LC FX-CLC FX-IOC FX-SAA Two loop addressable controller - Apollo protocol card One loop addressable controller - Apollo protocol card Two loop addressable controller - System sensor protocol card Sixteen loop conventional Controller I/O controller board Serial communications adapter for communication with external systems LPCB Ref. No.

FXM

883a/03

(BSM or Alarm Management Systems) FX-SAB Serial communications adapter for communication in a networked FX system and with external systems (BSM or Alarm Management Systems). FX-LB80 80 Zone LED indication card FX-LB32 32 Zone LED indication card FX-BAT Separate battery box (4x17Ah, 12V) FXM-BAT Separate battery box (4x12Ah, 12V) Certified with the following options with requirements from EN 54-2:1997 7.8 Outputs to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.4 Complete failure of power supply 8.9 Output to fault warning routing equipment 9.5 Disablement of addressable points 10 Test condition Notes: 1) Scope of approval does not include the operation of the network functionality. Analogue addressable Repeater Panel Incorporating the following modules: FX-MC Master Controller FX-UI User Interface Optional Modules -The following modules are optional additions to the basic unit: FX-IOC I/O Controller

FXS

883a/R01

56

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

Protec Fire Detection plc


Protec House, Churchill Way, Nelson, Lancashire BB9 6RT UK Tel: +44 (0)1282 717171 Fax: +44 (0)1282 717273 E-mail: sales@protec.co.uk Website: www.protec.co.uk
Certificate No: 201k to EN 54-2 and 4 Certificated Products 6301 Analogue addressable 1 Loop control and indicating equipment Incorporating the following units: 41-860-52 Main Board 41-850-50 Terminal Board 40-877-65 CP250 Printer Board 31-100-22 Backbox 31-243-36 Inner Plate 62-407-57 Door 04-701-38 Printer Mechanism 40-465-43 Series 9000 Power Supply Unit 31-275-44 Optional external 24 AH battery box 40-879-67 Network Card (Note: Scope of approval does not include the operation of the network card) Analogue addressable 2 Loop control and indicating equipment Incorporating the following units: 41-860-52 Main Board 41-850-50 Terminal Board 40-879-67 CP250 Printer Board 31-100-22 Backbox 31-243-36 Inner Plate 62-407-57 Door 04-701-38 Printer Mechanism 40-465-43 Series 9000 Power Supply Unit 31-275-44 Optional external 24 AH battery box 40-879-67 Network Card (Note: Scope of approval does not include the operation of the network card) Analogue addressable 4 Loop control and indicating equipment Incorporating the following units: 41-860-52 Main Board 41-850-50 Terminal Board 40-879-67 CP250 Printer Board 31-100-22 Backbox 31-243-36 Inner Plate 62-407-57 Door 04-701-38 Printer Mechanism 40-465-43 Series 9000 Power Supply Unit 41-913-56 SMT Dual 6000 Loop Card 31-275-44 Optional external 24 AH battery box 40-879-67 Network Card (Note: Scope of approval does not include the operation of the network card) Display and Control node Incorporating the following units: WEFA 312E Display control unit WEFA 168E Local display unit WEFA 233D PF Terminal unit Certified with the following options with requirements from EN 54: Part 2: 1997: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.11 Delays of the actioning of outputs to fire alarm devices and fire alarm routing equipment 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to fault warning routing equipment 9.5 Disablement of each address point 10 Test condition Notes: 1) This unit does not meet the requirements of EN 54-2 & 4 as a stand alone unit. It is intended for use as part of the 6400 distributed network fire alarm system. In order to LPCB Ref. No. 201k/01

6302

201k/02

6304

201k/03

6400/DCN

201k/04

January 2009

57

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products meet the requirements of EN 54-2 & 4 the unit must be used in conjunction with the following units: 6400/DCN Display and Control node 6400/PSU 8A Power supply with charger 2) Scope of approval does not include the operation of the network functionality. 2 loop processing node Incorporating the following units: WEFA 169E2 SSU WEFA 315B Dual loop driver WEFA 160D Local IO WEFA 230C Terminal board WEFA 232C Loop terminal board WEFA 237A LPN display board WEFA 288C OPTO 485 board Notes: 1) This unit does not meet the requirements of EN 54-2 & 4 as a stand alone unit. It is intended for use as part of the 6400 distributed network fire alarm system. In order to meet the requirements of EN 54-2 & 4 the unit must be used in conjunction with the following units: 6400/DCN Display and Control node 6400/PSU 8A Power supply with charger 2) Scope of approval does not include the operation of the network functionality. 4 loop processing node Incorporating the following units: WEFA 169E2 SSU WEFA 315B 2 x Dual loop driver WEFA 160D Local IO WEFA 230C Terminal board WEFA 232C Loop terminal board WEFA 237A LPN display board WEFA 288C OPTO 485 board Notes: 1) This unit does not meet the requirements of EN 54-2 & 4 as a stand alone unit. It is intended for use as part of the 6400 distributed network fire alarm system. In order to meet the requirements of EN 54-2 & 4 the unit must be used in conjunction with the following units: 6400/DCN Display and Control node 6400/PSU 8A Power supply with charger 2) Scope of approval does not include the operation of the network functionality. Display and control node plus 2 Loop processing node Incorporating the following units: WEFA 312E Display control unit WEFA 168E Local display unit WEFA 169E2 SSU WEFA 315B Dual loop driver WEFA 160D Local IO WEFA 230C Terminal board WEFA 232C Loop terminal board WEFA 288C OPTO 485 board Certified with the following options with requirements from EN 54: Part 2: 1997: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.11 Delays of the actioning of outputs to fire alarm devices and fire alarm routing equipment 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to fault warning routing equipment 9.5 Disablement of each address point 10 Test condition Notes: 1) This unit does not meet the requirements of EN 54-2 & 4 as a stand alone unit. It is intended for use as part of the 6400 distributed network fire alarm system. In order to meet the requirements of EN 54-2 & 4 the unit must be used in conjunction with the following unit: 6400/PSU 8A Power supply with charger 2) Scope of approval does not include the operation of the network functionality. LPCB Ref. No.

6400/2LPN

201k/05

6400/4LPN

201k/06

6400/DCN/2LPN

201k/07

58

January 2009

SECTION 3: PART
Certificated Products 6400/DCN/4LPN Display and control node plus 4 Loop processing node Incorporating the following units: WEFA 312E Display control unit WEFA 168E Local display unit WEFA 169E2 SSU WEFA 315B 2 x Dual loop driver WEFA 160D Local IO WEFA 230C Terminal board WEFA 232C Loop terminal board WEFA 288C OPTO 485 board Certified with the following options with requirements from EN 54: Part 2: 7.8 Output to fire alarm device(s) 7.9 Output to fire alarm routing equipment 7.11 Delays of the actioning of outputs to fire alarm devices and fire alarm routing equipment 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to fault warning routing equipment 9.5 Disablement of each address point 10 Test condition Notes: 1) This unit does not meet the requirements of EN 54-2 & 4 as a stand alone unit. It is intended for use as part of the 6400 distributed network fire alarm system. In order to meet the requirements of EN 54-2 & 4 the unit must be used in conjunction with the following unit: 6400/PSU 8A Power supply with charger 2) Scope of approval does not include the operation of the network functionality. Power supply with charger Incorporating the following unit: 9000/BC8/40 8A Power supply with charger Notes: 1) This unit does not meet the requirements of EN 54-2 & 4 as a stand alone unit. It is intended for use as part of the 6400 distributed network fire alarm system. In order to meet the requirements of EN 54-2 & 4 the unit must be used in conjunction with the following units: 6400/DCN Display and Control node 6400/2LPN 2 Loop processing node and/or 6400/4LPN 4 Loop processing node 2) Scope of approval does not include the operation of the network functionality. 3) Certified to EN 54-4 only. LPCB Ref. No. 201k/08

CONTROL AND INDICATING EQUIPMENT

6400/PSU 8A

201k/09

Rafiki Protection Limited


Unit 31, Springvale Industrial Estate, Cwmbran, Gwent NP44 5BD UK Tel: +44 (0)1633 865558 Fax: +44 (0)1633 866656 Website: www.rafikiprotection.com
Certificate No: 331c to EN 54 - 2 :1997 and EN54 - 4: 1997 Certificated Products 503/0001 Sita 200 plus Single loop 32 zone analogue addressable control and indicating equipment Incorporating as modular units: 10-0026 Main PCB Stadium SA60 Type s Power supply LMG6381QHGE LCD Display unit Certificated with the following options with requirements from EN 54 - 2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delay to outputs 7.12 Coincidence detection LPCB Ref. No. 331c/01

January 2009

59

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 8.3 8.9 9.5 10 Fault signals from points Output to fault warning routing equipment Disablement of addressable point Test condition LPCB Ref. No.

Shield Fire Safety & Security Ltd


29th Floor, Regus Suite, One Canada Square, Canary Wharf, London E14 5DY UK Tel: +44 (0)207 712 1722 Fax: +44 (0)870 734 5579 E-mail: info@shielduk.com Website: www.shielduk.com
Certificate No: 548j to EN 54-2:1997 & EN54-4:1997 Certificated Products P-A300 Intelligent 1 loop, 30 zone analogue addressable control and indicating equipment Incorporating the following units: F7.820.826 Main board F7.820.827 Switch board F7.820.828 Loop interface board F7.820.829 Power supply unit F7.908.312 Zone indication board CGM12864 Alphanumeric display F2.910.093 Mains filter R150 Transformer F2.828.630a Printer board (option) Incorporating as optional modular units: F7.820.170 RS-232 board for configuration P-9901 Printer module kit Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.10 Output to automatic Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection 8.3 Fault signals from points 9.5 Disablement of addressable points Single zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Two zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 10 Test condition Four zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Eight zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition Sixteen zone conventional control and indicating equipment Certified with the following options with requirements from EN 54 part 2: 7.8 Output to Fire Alarm Devices 7.11 Delays to outputs 10 Test condition LPCB Ref. No. 548j/01

P-C201

548j/02

P-C202

548j/03

P-C204

548j/04

P-C208

548j/05

P-C216

548j/06

60

January 2009

SECTION 3: PART

CONTROL AND INDICATING EQUIPMENT

Siemens Switzerland Limited, Building Technologies Division


International Headquarters, Fire Safety & Security Products, Gubelstrasse 22, CH-6301 Zug, Switzerland Tel: +41 (0) 41 724 24 24 Fax: +41 (0) 41 724 35 22 Manufacturing at: Volketswil Factory, Industriestrasse 22, CH-8604 Volketswil, Switzerland Tel: +41 1 922 6111 Fax: +41 1 922 6450

UK Sales: Fire Safety and Security Limited Tel: +44 (0)1734 783703 Fax: +44 (0)1734 775750

Certificate No: 126h to EN 54: Part 2 and 4: 1997 Certificated Products CS1140 Control and indicating equipment Comprising the following products: CC1140 Control and indicating equipment CT11 Operators console CI1140 Integrated central unit Incorporating as modular units: E3X100 Master module E3X102 Master Module E3X103 Master Module E3X120 Master card Cl1145 E3C010 Battery charging module E3C011 Battery charging module B2F020 Converter B2F040 Converter E3M140 Line module FD20 E3M070 Line module "Interactive" E3M071 Line module Interactive K3M140 Line card FD20 K3M071 Line card Interactive to E3X120 K3M080 Line card Collective B3Q460 Control console Algopilot "CT11" B3Q321 Fire department control panel (Swiss) E3G050 Contacts control unit E3G070 Universal control unit E3I020 RS232 unit K3I060 RS232 module E3L020 I/O control unit E3M080 Group line unit K3R071 Synoptic - Algo pilot K3R070 Synoptic - Algo pilot K3I050 LON/Synoptic converter E3M060 MS9i module E3G091 Remote TX i/face E3M110 AnalogPLUS module E3M111 Line module AnaloguPLUS K3M111 Line card AnalogPLUS B3R051 Parallel indicator panel (24 x 2 LED) E3G080 Control module Extinguishing B3Q440 Control console Extinguishing module E3G060 Control monitored module E3H020 C-Bus Gateway module E3I040 I-Bus/LON module B3Q560/B3Q600 Terminals China B3Q580 Text display terminal B3Q590 Text control terminal Nordic B3Q660 Operator console Standard Algopilot "CT11" B3Q661 Operator console Standard Algopilot "CT11" B3Q680 Control console Nordic Algopilot "CT11" LPCB Ref. No. 126h/01

January 2009

61

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products B3Q565 Operator control Asia Pacific Algopilot "CT11" K3N010 RAM - Extension K3I110 LON Input/Output Box E3M171 Line Module Ex Interactive K5L020 Multi-Sect. Extinguishing P.C.B K3G060 Relay Card to Synptic BUS E3G100 Emergency Operation Link E3G110 Emergency Link to E3G080 K3R072 Synoptical Driver M3C080 Horn Monitoring Module Notes: 1) The following options with requirements are approved with this equipment: 7.8 Outputs to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to Fire Protection Equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.4 Complete failure of power supply 9.5 Disablement of addressable points 10 Test condition 11 Standardised input/output interface 1) Compliance with clause 12.6.2 of EN 54-2:1997 requires LCD screen saving feature to be disabled for the alarm condition. Fire Detection Control Unit Incorporating: B3Q510 Control Panel K3X010 Master card collective K3M010 line extension card K3M020 line extension card B3R 080 parallel indicator card Approved with the following options from EN 54: Part 2 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.9 Output to fault warning routing equipment 10 Test condition Fire Detection Control Unit Incorporating: B3Q580 Text Display Terminal B3Q590 Text Control Terminal B3R051 Parallel Indicator Unit B3R080 Parallel indicator card (32 LED) K3G050 Relay card K3G060 Relay p.c.b K3I050 LON Synoptic p.c.b K3I080 Serial LON ITF K3I090 PSA Interface K3I110 LON I/O Box K3L070 VdS Interface K3L100 LED driver card K3M010 Line extension card "Collector 4 line" K3M020 Line extension card "Collector 8 line" K3M030 Line extension card "Analogue Plus" K3R071 Synoptic-Driver K3R072 Synoptic-Driver K3X020 Master Board Analogue Plus K3X030 Master Module M3C080 Impedance translator M3P140 Monitoring Card 24V Z3S020 key switch nordic Z3S030 key switch KABA Z3l1020 Akku extension set. Approved with the following options from EN 54-2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.11 Delays to outputs 7.12 Coincidence detection LPCB Ref. No.

CS1110 AlgoControl

126h/02

CS1115 AlgoControl

126h/03

62

January 2009

SECTION 3: PART
Certificated Products 7.13 Alarm Counter 8.3 Fault signals from points 8.4 Total loss of power supply 8.9 Output to fault warning routing equipment 9.5 Disablement of each addressable point 10 Test condition Fire detection control unit Incorporating: B3Q580 Text Display Terminal B3Q590 Text Control Terminal B3R051 Parallel Indicator Unit B3R070 Parallel indicator card B3R080 Parallel indicator card K3G050 Relay card K3G060 Relay p.c.b K3I050 LON Synoptic p.c.b K3I080 Serial LON ITF K3I090 PSA Interface K3I110 LON I/O Box K3L070 VdS Interface K3L100 LED driver card K3M010 Line extension card K3M020 Line extension card K3M030 Line Card K3R071 Synoptic-Driver K3R072 Synoptic-Driver K3X020 Master Board Analogue Plus K3X030 Master Module M3C080 Impedance translator M3P140 Monitoring Card 24V Z3S020 key switch nordic Z3S030 key switch KABA Approved with the following options from EN 54-2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm Counter 8.3 Fault signals from points 8.4 Total loss of power supply 8.9 Output to fault warning routing equipment 9.5 Disablement of each addressable point 10 Test condition Control and indicating equipment Incorporating as modular units. FCM2002-A2 Control unit with, display, keyboard, coloured keys, LED indicator(FTO2002) FP2001-A1 70W Power supply and as optional modular units. FCM2001-A2 Control unit with, display, keyboard, coloured keys FCM2004-A1 PMI- & Mainboard FCM2005-A2 Empty Operating add-on module FCM2006-A2 Operating add-on module with 2 LED indicator unit FTO2002 and optional event printer FTO2001-A1 FTO2001-A1 Event printer FCI2003-A1 FDnet/SynoNET Loop extension FTO2002-A1 24 LED module FN2001-A1 SAFEDLINK Networking module (See Note 2) FCA2001-A1 Isolated RS232 module FCA2002-A1 Isolated RS485 module FCI2001-D1 Fire brigade periphery module FCI2002-A1 Periphery board (2-Loop) FCM2003-C2 Operating unit (incl. FBA-Term.CH) FCM2003-N2 Operating unit (incl. EVAC-Term.NL) FTO2004-C1 PCB compl. FBA-Terminal (CH) FTO2007-N1 PCB compl. EVAC-module (NL) FHA2002-A1 Rear housing FCA20xx Relay module FCA20xx[DE] Shielded termination SV 24V-150W 150W Power supply REDUX Redundancy module Certified with the following options with requirements from EN 54-2: LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

FC330A AlgoControl

126h/03

FC2020

126h/04

January 2009

63

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to fault warning routing equipment 9.5 Disablement of addressable points 10 Test condition 11 Standardised input/output interface Notes: 1) Scope of approval does not include the operation of the network functionality. Control and indicating equipment Incorporating as modular units. FCM2002-A2 Control unit with, display, keyboard, coloured keys, LED indicator (FTO2002) SV 24V-150W 150W Power supply and as optional modular units. FCM2001-A2 Control unit with, display, keyboard, coloured keys FCM2004-A1 PMI- & Mainboard FCM2005-A2 Empty Operating add-on module FCM2006-A2 Operating add-on module with 2 LED indicator unit FTO2002 and optional event printer FTO2001-A1 FT02001-A1 Event printer FCM2007-A2 Operating add-on module with 4 LED indicator unit FTO2002 FCI2003-A1 FDnet/SynoNET Loop extension FTO2002-A1 24 LED module FN2001-A1 SAFEDLINK Networking module (See Note 2) FCA2001-A1 Isolated RS232 module FCA2002-A1 Isolated RS485 module FCI2004-A1Periphery board (4-Loop) FCI2001-D1Fire brigade periphery module FCM2003-C2 Operating unit (incl. FBA-Term.CH) FCM2003-N2 Operating unit (incl. EVAC-Term.NL) FTO2004-C1 PCB compl. FBA-Terminal (CH) FTO2007-N1 PCB compl. EVAC-module (NL) FHA2003-A1 Rear housing FCA20xx Relay module FCA20xx[DE] Shielded termination REDUX Redundancy module Certified with the following options with requirements from EN 54-2: 7.8 Output to fire alarm devices 7.9 Output to fire alarm routing equipment 7.10 Output to automatic fire protection equipment 7.11 Delays to outputs 7.12 Coincidence detection 7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to fault warning routing equipment 9.5 Disablement of addressable points 10 Test condition 11 Standardised input/output interface Notes: 1) Scope of approval does not include the operation of the network functionality. Fire detection terminal Incorporating as modular units. FCM2002-A2 Control unit with, display, keyboard, coloured keys, LED indicator (FTO2002) FP2001-A1 70W Power supply and as optional modular units. FCM2001-A2 Control unit with, display, keyboard, coloured keys FCM2004-A1 PMI & mainboard FTI2001-A1 Fire detection terminal board FN2001-A1 SAFEDLINK Networking module (See Note 2) FCA2001-A1 Isolated RS232 module FCA2002-A1 Isolated RS485 module FTO2001-A1 Event printer FTO2002-A1 24 LED module FCM2003-C2 Operating unit (incl. FBA-Term.CH) FCM2003-N2 Operating unit (incl. EVAC-Term.NL) LPCB Ref. No.

FC2040

126h/05

FT2040

126h/06

64

January 2009

SECTION 3: PART
Certificated Products FTO2004-C1 PCB compl. FBA-Terminal (CH) FTO2007-N1 PCB compl. EVAC-module (NL) FHA2001-A1 Rear housing REDUX Redundancy module 1) Scope of approval does not include the operation of the network functionality. LPCB Ref. No.

CONTROL AND INDICATING EQUIPMENT

Thorn Security Products Limited Trading As Tyco Safety Products


Melbourne Road, Cork, Ireland Tel: +44 (0) 1462 667700 Fax: +44 (0) 1462 667777 Website: www.tycosafetyproducts-europe.com
Certificate No: 763b to EN 54-2:1997 and EN 54-4: 1997 Certificated Products MXR Repeater Panel Incorporating the following as modular units, is approved for use with the MX4000 Control and indicating equipment. OCM800 (Operator Control Module) ODM800 (Operator Display Module) PSM800 (Power Supply Module) and as optional modular units: ANN840 (40 + 40 LED Annunciator ANN880 (80 LED Annunciator) MPM800 (Multi Purpose Interface Module) IOB800 (Input/Output Expansion Board) FB800 (Fuse Board) LPCB Ref. No. 763b/R01

Certificate No: 763b to EN 54-2:1997 and EN 54-4: 1997

Tyco Safety Products Cork (Sensormatic Electronics Corporation (IRL.) Limited


Melbourne Road, Bishopstown, Cork, Ireland Tel: +353 21 480 1000 Fax: +353 21 480 1050 Website: www.tycosafetyproducts-europe.com
Certificate No: 763b to EN 54-2:1997 and EN 54-4:1997 Certificated Products MX4000 2/4 loop Analogue Addressable Control and Indicating Equipment Incorporating as modular units: OCM800 Operator Control Module ODM800 Operator Display Module CPU800 main CPU module FIM800 Field Interface Module drives 1 or 2 loops XLM800 Expansion Loop Module drives 1 or 2 additional loops PSB800 Power Supply Module with Loop Booster and as optional modular units: ANN840 40 + 40 LED Annunciator module ANN880 80 LED Annunciator module COM820 20 way Status Command Module MPM800 Multi Purpose Interface Module LPCB Ref. No. 763b/01

January 2009

65

PART 3: SECTION 3
CONTROL AND INDICATING EQUIPMENT
Certificated Products IOB800 FB800 Input/Output Expansion Board Fuse Board LPCB Ref. No.

Certified with the following options with requirements from EN 54-2: 1997 Output to fire alarm devices Output to fire alarm routing equipment Output to fire protection equipment Delays to outputs Co-incidence detection Alarm counter 8.3 Fault signals from points 9.5 Disablement of addressable points 10 Test condition 11 Standardized input/output interface Incorporating the following as modular units, is approved for use with the MX4000 Control and indicating equipment: OCM800 (Operator Control Module) ODM800 (Operator Display Module) PSM800 (Power Supply Module) and as optional modular units: ANN840 (40 + 40 LED Annunciator) ANN880 (80 LED Annunciator) MPM800 (Multi Purpose Interface Module) IOB800 (Input/Output Expansion Board) FB800 (Fuse Board) 7.8 7.9 7.10 7.11 7.12 7.13

MXR Repeater Panel

763b/R01

Certificate No: 763-cl-(1) to EN 54-2: 1997 and EN54-4: 1997 Product Name Control and Indicating Equipment Repeater Panel Model No MX 4000 Alternative MX 4000 Labelled Thorn Security Ltd t/a Tyco Safety Products Thorn Security Ltd t/a Tyco Safety Products Distributor Ref No 763-(cl-1) LPCB Ref. No. 763b/01

MXR Repeater

MXR Repeater

763b-(cl-1)

763b/R01

66

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

There are many types of detectors on the market designed to work on different principles and fire parameters (e.g. smoke, flame radiation, convective heat etc). The selection of a detector for a particular area or application should be based on a number of factors including the following: The nature of the fire hazard The speed of response required The need to minimize false alarms

There are other factors to be taken into account such as architecture of the building, ease of maintenance and cost. Guidance on the selection of appropriate types of detectors should be sought from the applicable installation rule or code of practice (e.g. BS 5839-1). Where a particular type of detector is not covered by the installation rule or code of practice then guidance should be sought from the manufacturers literature. In any case, account should be given to the notes or limitations given with the listed detector in this section. This section lists fire detectors approved for use in fire detection and fire alarm systems in buildings. The initial approval and continued approval processes for detectors are outlined in scheme document SD021. The list includes detectors certified to recognised standards or to special test schedules which are developed by LPCB for detector types where suitable standards are not available or were not available at the time of the evaluation. Products listed in this section have been approved to: EN 54-5:2000 Heat detectors - point detectors EN 54-5:2000 + A1: 2002 Heat detectors - point detectors EN 54-7:2000 Smoke detectors - point detectors using scattered light, transmitted light or ionisation EN 54-7:2000 +A1: 2002 and A2: 2006 Smoke detectors - point detectors using scattered light, transmitted light or ionisation EN 54-10:2002 Flame detectors - point detectors EN 54-10:2002 + A1: 2005 Flame detectors - point detectors EN 54-12:2002 Smoke detectors - line detectors using an optical light beam EN 54-20:2006 Aspirating smoke detectors ISO7240-5:2003 Point -type heat detectors ISO7240-6:2004 Carbon monoxide fire detectors using electro-chemical cells ISO7240-7:2003 Point-type smoke detectors using scattered light, transmitted light or ionization ISO7240-12:2005 Line type smoke detectors using transmitting light beam ISO7240-15:2004 Multisensor fire detectors ISO 7240-6:2008 Carbon monoxide fire detectors using electro-chemical cells and heat sensors. CEA 4021:1999 Requirements and test methods for multisensor detectors, which respond to smoke and heat, and smoke detectors with more than one smoke sensor CEA 4021:2003 Requirements and test methods for multisensor detectors, which respond to smoke and heat, and smoke detectors with more than one smoke sensor CEA 4022:1999 Requirements and test methods for aspirating smoke detectors LPS 1265-1.1:2005 Requirements and Testing Procedures for the LPCB Approval and Listing of Carbon Monoxide Fire Detectors Using Electrochemical Cells LPS 1274-1.0:2005 Testing Procedures for the LPCB Approval and Listing of Carbon Monoxide / Heat Multisensor Fire Detectors Using Electrochemical Cells LPS 1279:2006 Testing Procedures for the LPCB Approval and Listing of Point Multisensor Fire Detectors using Optical or Ionization Smoke Sensors and Electrochemical Cell CO Sensors and, optionally, Heat Sensors

Approval can also be obtained for other detection principles not detailed above. In such circumstances, LPCB can develop test criteria to evaluate products, which in time may be used for the development of standards. Audit:

January 2009

67

PART 3: SECTION 4.1


COMMERCIAL DETECTORS Regular product auditing and regular factory inspections are carried out by LPCB ensuring high manufacturing standards and continued compliance with the applicable product standard. Notes: 1. EN 54-5:2000 is now a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market since 30 June 2005. It is therefore recommended that heat detectors are certificated to EN 54-5:2000 + A1:2002 2. EN 54-7:2000 is now a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market since 30 June 2005. It is therefore recommended that smoke detectors are certificated to EN 54-7:2000 + A1:2002 and A2:2006 3. EN 54-10:2002 is now a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market since 1 September 2008. It is therefore recommended that flame detectors are certificated to EN 54- 10:2002 + A1:2005 4. EN 54-12:2002 is now a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market since 31 December 2005. It is therefore recommended that beam detectors are certificated to EN 54- 12:2002. 5. CEA 4021:2003 supersedes CEA 4021:1999 which was withdrawn in June 2003 (i.e. at the same time as the national versions of EN 54-5:1976 and EN 54-7:1982 were officially withdrawn and replaced with EN 545:2000 and EN 54-7:2000). 6. EN 54-20: 2006 supersedes CEA 4022:1999 which will be withdrawn by June 2009. It is therefore recommended that aspirating detectors are certificated to EN 54-20:2006 as soon as possible. EN 54-20:2006 is now a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market from 1 July 2009. 7. The bases with which a detector has been evaluated and shown to meet the relevant standards, are listed with each detector. Bases are not approved/certificated in their own right unless they are combined with another device (e.g. short circuit isolator or sounder). 8. Since LPCB uses national and international standards for the listing of products, in some instances the requirements of these standards may conflict with the recommendations of local codes of practice. We recommend that specifiers seek advice from the relevant local authorities and amend their specifications accordingly.

Aguilera Electronica S.L


C / Julian Camarillo 26, Madrid 28037, Spain Tel: +34 917545511 Fax: +34 917545098 E-mail: aguilera@aguileraelectronica.es
Certificate No: 512d to EN 54-5: 2000

Point Heat Detectors


Certificated Products AE/C5-TV Conventional 2 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector with LED output (P/N854001 base) LPCB Ref. No. 512d/04

Bases: P/N854001 4-Wire detector base

Certificate No: 512a to EN 54-7: 2000

68

January 2009

SECTION 4.1: PART


Point Smoke Detectors
Certificated Products AE/C5-OP Conventional 2 wire photoelectric smoke detector with remote LED output (P/N854001 base) LPCB Ref. No. 512a/02

COMMERCIAL DETECTORS

Bases: P/N854001 4-Wire detector base

Certificate No: 512b to EN54-5:2000, EN54-7:2000 & CEA 4021:1999

Multi-criteria Detectors
Certificated Products AE/C5-OPT Conventional 2 wire photoelectric smoke and heat detector with remote LED output (P/N854001 base) LPCB Ref. No. 512b/02

Bases: P/N854001 4 Wire detector base

AirSense Technology Limited


Unit 1, Caxton Place, Caxton Way, Stevenage, Hertfordshire SG1 2UG UK Tel: +44 (0)1462 751296 Fax: +44 (0)1462 729137 E-mail: tech@airsense.co.uk Website: www.airsense.co.uk/airsense
Certificate No: 404b to CEA 4022: 1999-12 Certificated Products Stratos HSSD 2 High sensitivity aspirating standard smoke detector Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with Airsense Technology Limited Installers Handbook (LM80004) with per hole sensitivities of better than 5%/m, as predicted by the PipeCAD system. High sensitivity aspirating command module smoke detector Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with Airsense Technology Limited Installers Handbook (LM80004) with per hole sensitivities of better than 5%/m, as predicted by the PipeCAD system. Stand alone command module Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with Airsense Technology Limited Installers Handbook (LM80004) with per hole sensitivities of better than 5%/m, as predicted by the PipeCAD system. High sensitivity aspirating minimum display version smoke detector Notes: LPCB Ref. No. 404b/01

Stratos HSSD 2

404b/02

Stratos HSSD 2

404b/03

Stratos HSSD 2

404b/04

January 2009

69

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with Airsense Technology Limited Installers Handbook (LM80004) with per hole sensitivities of better than 5%/m, as predicted by the PipeCAD system. LPCB Ref. No.

Certificate No: 404c to EN54-20: 2006 Certificated Products Stratos Micra 25 High sensitivity aspirating smoke detector Notes: 1) For compliance with Clause 5.10 of EN54-20:2006, the detector shall be supplied with power from a power supply complying with EN54-4. 2) The approval of the detector is conditional upon the following requirements: - Design, installation and commissioning are performed in accordance with the system design manual and instructions. 3) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.31%/m. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD. High sensitivity aspirating smoke detector. Notes: 1) For compliance with Clause 5.10 of EN54-20:2006, the detector shall be supplied with power from a power supply complying with EN54-4. 2) The approval of the detector is conditional upon the following requirements: - Design, installation and commissioning are performed in accordance with the system design manual and instructions. 3) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD. LPCB Ref. No. 404c/01

Stratos Micra 100

404c/02

Alarm Supply Pte Ltd


63 Jalan Pemimpin, 03-07 Pemimpin Industrial Building, Singapore 577219, Singapore Tel: +65 625 83445 Fax: +65 625 86428
Certificate No: 512a to EN 54-7: 2000

Smoke Detectors
Certificated Products EA318-2L Conventional 2 wire photoelectric smoke detector with remote LED output (E300-Base) LPCB Ref. No. 512a/02

Bases: E300-Base 4-wire detector base

Certificate No: 512d to EN 54 - 5: 2000

Heat Detectors
Certificated Products EA323-2L/A2R Conventional 2 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector with LED output (E300-Base) LPCB Ref. No. 512d/04

Bases: E300-Base 4-wire detector base

70

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Certificate No: 512a

Point Smoke Detectors


Certificated Products EA318-2 Conventional 2 wire photoelectric smoke detector (P/N852001 base) LPCB Ref. No. 512a/01

Bases: P/N852001 2-wire detector base

Certificate No: 512d

Point Heat Detectors


Certificated Products EA323-2 Conventional 2 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector (P/N852001 base) LPCB Ref. No. 512d/02

Bases: P/N852001 2-wire detector base

Apollo Fire Detectors Limited


36 Brookside Road, Havant, Hampshire PO9 1JR UK Tel: +44 (0)2392 492412 Fax: +44 (0)2392 492754 E-mail: enquiries@apollo-fire.co.uk Sales Enquiries Germany, Apollo Deutschland GmbH Tel: +49 5241 330 60 Fax: +49 5241 330 629 E-mail: info@apollo-feuer.de

Sales Enquiries Spain, Apollo Espana Tel: +34 627 988 061 Fax: +34 949 335 289 E-mail: apollo.espana@apollo-fire.com

Sales Enquiries China, Apollo Fire Detectors Limited, Shanghai representative office Tel: +86 21 5237 0922 Fax: +86 21 5237 0920 E-mail: tony.ye@apollo-fire.com

Certificate No: 010ab to EN 54-5: 2000 + A1: 2002 Certificate No: 010p to EN 54: Part 5: 2000 Certificate No: 010r to EN 54: Part 5: 2000

Point Heat Detectors


Certificated Products XPA-HT-11170-APO Xpander addressable radio linked Class A1R heat detector (XPA-WB-10022-APO mounting base) Notes: LPCB Ref. No. 010ab/01

January 2009

71

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products 1) Meets the requirements of EN 54-5 for Class A1R. 2) The complete radio base/detector combination is available as Apollo Part No.: XPACB-11170-APO. 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells. 4) The radio link functionality of this device is not included within the scope of approval. Xpander addressable radio linked Class CS heat detector (XPA-WB-10022-APO mounting base) Notes: 1) Meets the requirements of EN 54-5 for Class CS. 2) The complete radio base/detector combination is available as Apollo Part No.: XPACB-11171-APO. 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells. 4) The radio link functionality of this device is not included within the scope of approval. Conventional Class A1R heat detector - Flashing LED/Reed switch (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class A1R Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class A1R heat detector - Flashing LED (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class A1R Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class A1R heat detector - Standard (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class A1R Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class BR heat detector - Flashing LED/Reed switch (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class BR Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class BR heat detector - Flashing LED (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class BR Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class BR heat detector - Standard (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class BR Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class CR heat detector- Flashing LED/Reed switch (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class CR Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class CR heat detector - Flashing LED (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class CR Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class CR heat detector - Standard (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class CR Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class CS heat detector - Flashing LED/Reed switch (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class CS Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class CS heat detector - Flashing LED (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class CS Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional Class CS heat detector - Standard (45681-200 mounting base) Note: Meets the requirements of EN 54: Part 5 - Class CS Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Analogue addressable Class A2S heat detector (45681-209 and 45681-210 mounting 2 base) Certificated with Apollo Discovery, XP95, and S90 digital communications protocols configured for the Discovery heat detector in accordance with manufacturers instructions. Analogue addressable Class CS heat detector (45681-209 and 45681-210 mounting LPCB Ref. No.

XPA-HT-11171-APO

010ab/02

55000-120 Series 65

010p/04

55000-121 Series 65

010p/05

55000-122 Series 65

010p/06

55000-125 Series 65

010p/07

55000-126 Series 65

010p/08

55000-127 Series 65

010p/09

55000-130 Series 65

010p/10

55000-131 Series 65

010p/11

55000-132 Series 65

010p/12

55000-135 Series 65

010p/13

55000-136 Series 65

010p/14

55000-137 Series 65

010p/15

55000-400 XP95

010p/20

55000-401 XP95

010p/21

72

January 2009

SECTION 4.1: PART


Certificated Products base) Certificated with Apollo Discovery, XP95, and S90 digital communications protocols configured for the Discovery heat detector in accordance with manufacturers instructions. Analogue addressable Class A2S heat detector (45681-209 and 45681-210 mounting 2 base) Certificated with Apollo Discovery, XP95, and S90 digital communications protocol configured for the Discovery heat detector in accordance with manufacturers instructions. Analogue addressable intrinsically safe Class A2S heat detector (45681-215 mounting base) Certified with Apollo Series 90 and XP95 digital communications protocol 2 Analogue addressable heat detector (45681-209 and 45681-210 mounting base) Note: Meets the requirements of EN 54: Part 5 for the following settings Class A1R in mode 1 and in conventional mode. Class A2 in mode 2 and in conventional mode. Class A2S in mode 3 and in conventional mode. Class CR in mode 4 and in conventional mode. Class CS in mode 5 and in conventional mode. Certificated with Apollo, Discovery, XP95 and S90 digital communication protocols when the Discovery heat detector has been configured in accordance with manufacturer's instructions. Analogue addressable Class A2S heat detector (45681-500 and 45681-501 mounting bases) Certificated with Apollo Series 90 and XP95 digital communication protocols Analogue addressable Class CS heat detector (45681-500 and 45681-501 mounting bases) Certificated with Apollo Series 90 and XP95 digital communication protocols Heat detectors with Apollo Approval Reference* 00001 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) Heat detectors with Apollo Approval Reference* 00009 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) Heat detectors with Apollo Approval Reference* 00002 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) Heat detectors with Apollo Approval Reference* 00003 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) Heat detectors with Apollo Approval Reference* 00004 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) Heat detectors with Apollo Approval Reference* 00005 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) Heat detectors with Apollo Approval Reference* 00006 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) Intrinsically safe heat detectors with Apollo Approval Reference* 50001 (Approved for use with base styles OB (+ATEX marking) and ORB-BA-50008 adapter base) Intrinsically safe heat detectors with Apollo Approval Reference* 50009 (Approved for use with base styles OB (+ATEX marking) and ORB-BA-50008 adapter base) Intrinsically safe heat detectors with Apollo Approval Reference* 50002 (Approved for use with base styles OB (+ATEX marking) and ORB-BA-50008 adapter base) Intrinsically safe heat detectors with Apollo Approval Reference* 50003 (Approved for use with base styles OB (+ATEX marking) and ORB-BA-50008 adapter base) Intrinsically safe heat detectors with Apollo Approval Reference* 50004 (Approved for use with base styles OB (+ATEX marking) and ORB-BA-50008 adapter base) Intrinsically safe heat detectors with Apollo Approval Reference* 50005 (Approved for use with base styles OB (+ATEX marking) and ORB-BA-50008 adapter base) Intrinsically safe heat detectors with Apollo Approval Reference* 50006 (Approved for use with base styles OB (+ATEX marking) and ORB-BA-50008 adapter base)
2

COMMERCIAL DETECTORS
LPCB Ref. No.

55000-420 XP95

010p/22

55000-440 XP95 IS 58000-400 Discovery

010p/23 010p/03

59000-400 XPlorer 59000-410 XPlorer Orbis Class A1R Orbis Class A1S Orbis Class A2S Orbis Class BR Orbis Class BS Orbis Class CR Orbis Class CS Orbis IS Class A1R Orbis IS Class A1S Orbis IS Class A2S Orbis IS Class BR Orbis IS Class BS Orbis IS Class CR Orbis IS Class CS

010p/01 010p/02 010r/01 010r/07 010r/02 010r/03 010r/04 010r/05 010r/06 010r/08 010r/14 010r/09 010r/10 010r/11 010r/12 010r/13

Bases: 45681-200 Series 60 mounting base 45681-200 Series 60/65 Mounting Base 45681-201 Series 60 diode mounting base 45681-201 Series 60/65 Diode Mounting Base 45681-207 Series 60 intrinsically safe mounting base 45681-209 XP95/Discovery standard deep mounting base 45681-210 XP95 mounting base 45681-215 XP95 intrinsically safe mounting base 45681-245 Series 65 Relay mounting base 45681-246 Series 65 Auxiliary relay mounting base 45681-247 Series 65 EOL 12 Volt mounting base 45681-248 Series 65 EOL 24 Volt mounting base 45681-500 XPlorer standard mounting base 45681-501 XPlorer remote LED mounting base TimeSaver bases with Apollo Approval Reference* OB TimeSaver LX bases with Apollo Approval Reference* OL

January 2009

73

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
TimeSaver diode bases with Apollo Approval Reference* OD TimeSaver relay bases with Apollo Approval Reference* OR TimeSaver LX diode bases with Apollo Approval Reference* DX TimeSaver IS bases with Apollo Approval Reference* OB (+ATEX marking) TimeSaver deep bases with Apollo Approval Reference* EB: ORB-MB-00019-APO TimeSaver deep base ORB-BA-50008 Orbis intrinsically safe adapter base (to be used in conjunction with the following bases only: 45681-207) ORB-BA-10008-APO Orbis adaptor base (to be used in conjunction with the following bases only: 45681-200 & 45681-201) XPA-WB-10022-APO Radio link mounting base** * The Apollo Approval Reference Number identifies a group of detectors that all have the same physical construction, but have features enabled or disabled via their software, and/or regional marking variations. **Base manufactured by EMS

Certificate No: 010ac to EN 54-7: 2000 + A1: 2002 Certificate No: 010q to EN 54: Part 7: 2000 Certificate No: 010s to EN 54: Part 7: 2000

Point Smoke Detectors


Certificated Products XPA-OP-12034-APO Xpander addressable radio linked photoelectric smoke detector (XPA-WB-10022-APO mounting base) Notes: 1) The complete radio base/detector combination is available as Apollo Part No.: XPACB-12034-APO. 2) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells. 3) The radio link functionality is not included within the scope of approval. Conventional ionisation smoke detector - Flashing LED/Reed switch (45681-200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional ionisation smoke detector - Flashing LED (45681-200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional ionisation smoke detector - Standard (45681-200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional integrating ionisation smoke detector - Flashing LED/Reed switch (45681200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional integrating ionisation smoke detector - Flashing LED (45681-200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional integrating ionisation smoke detector - Standard (45681-200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional optical smoke detector - Flashing LED/Reed switch (45681-200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional optical detector - Flashing LED (45681-200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Conventional optical smoke detector - Standard (45681-200 mounting base) Also Certificated for use with 45681-245, 45681-246, 45681-247, 45681-248 and 45681201 mounting bases Analogue addressable ionisation smoke detector (45681-209 and 45681-210 mounting 2 base) Certificated with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery ionisation smoke detectors in accordance with manufacturers instructions . Analogue addressable ionisation smoke detector (45681-209 and 45681-210 mounting 2 base) Certificated with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery ionisation smoke detectors in accordance LPCB Ref. No. 010ac/01

55000-215 Series 65

010q/04

55000-216 Series 65 55000-217 Series 65 55000-218 Series 65

010q/05 010q/06 010q/07

55000-219 Series 65

010q/08

55000-220 Series 65

010q/09

55000-315 Series 65

010q/10

55000-316 Series 65 55000-317 Series 65 55000-500 XP95

010q/11 010q/12 010q/16

55000-520 XP95

010q/17

74

January 2009

SECTION 4.1: PART


Certificated Products 55000-540 XP95 IS 55000-560 XP95 with manufacturers instructions . Analogue addressable intrinsically safe ionisation smoke detector (45681-215 mounting base) Certified with Apollo Series 90 and XP95 digital communications protocol Analogue addressable ionisation smoke detector (45681-209 and 45681-210 mounting 2 base) Certificated with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery ionisation smoke detectors in accordance with manufacturers instructions . Analogue addressable optical smoke detector (45681-209 and 45681-210 mounting 2 base) Certificated with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery optical smoke detectors in accordance with manufacturers instructions. Analogue addressable optical smoke detector (45681-209 and 45681-210 mounting 2 base) Certificated with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery optical smoke detectors in accordance with manufacturers instructions. Analogue addressable intrinsically safe optical smoke detector (45681-215 mounting base) Certified with Apollo Series 90 and XP95 digital communications protocol Analogue addressable optical smoke detector (45681-209 and 45681-210 mounting 2 base) Certificated with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery optical smoke detectors in accordance with manufacturers instructions. Analogue addressable ionisation smoke detector (45681-209 and 45681-210 mounting 2 base) Note: Meets the requirements of EN 54:Part 7 in modes 1, 2, 3, 4, 5 and in conventional mode. Certificated with Apollo, Discovery, XP95 and S90 digital communication protocols that have been configured for the Discovery ionisation smoke detectors has been configured in accordance with manufacturer's instructions. Analogue addressable photoelectric smoke detector (45681-209 and 45681-210 2 mounting base) Certificated with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery optical smoke detectors in accordance with manufacturers instructions. Analogue addressable optical smoke detector (45681-500 and 45681-501 mounting bases) Certificated with Apollo Series 90 and XP95 digital communication protocols Optical smoke detectors with Apollo Approval Reference* 00007 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) Intrinsically safe optical smoke detectors with Apollo Approval Reference* 50007 (Approved for use with base styles OB (+ATEX marking) and ORB-BA-50008-APO adapter base) LPCB Ref. No. 010q/22 010q/20

COMMERCIAL DETECTORS

55000-600 XP95

010q/18

55000-620 XP95

010q/19

55000-640 XP95 IS 55000-660 XP95

010q/23 010q/21

58000-500 Discovery

010q/02

58000-600 Discovery

010q/03

59000-600 Xplorer Orbis Orbis IS

010q/01 010s/01 010s/02

Bases: 45681-200 Series 60 mounting base 45681-200 Series 60/65 Mounting Base 45681-201 Series 60 diode mounting base 45681-201 Series 60/65 Diode Mounting Base 45681-207 Series 60 intrinsically safe mounting base 45681-209 XP95/Discovery standard deep mounting base 45681-210 XP95 mounting base 45681-215 XP95 intrinsically safe mounting base 45681-245 Series 65 Relay mounting base 45681-246 Series 65 Auxiliary mounting base 45681-247 Series 65 EOL 12 Volt mounting base 45681-248 Series 65 EOL 24 Volt mounting base 45681-500 XPlorer standard mounting base 45681-501 XPlorer remote LED mounting base TimeSaver bases with Apollo Approval Reference* OB TimeSaver LX bases with Apollo Approval Reference* OL TimeSaver diode bases with Apollo Approval Reference* OD TimeSaver relay bases with Apollo Approval Reference* OR TimeSaver LX diode bases with Apollo Approval Reference* DX TimeSaver IS bases with Apollo Approval Reference* OB (+ATEX marking) ORB-BA-50008 Orbis intrinsically safe adapter base (to be used in conjunction with the following bases only: 45681-207) ORB-BA-10008-APO Orbis adaptor base (to be used in conjunction with the following bases only: 45681-200 & 45681-201) XPA-WB-10022-APO Radio link mounting base**

January 2009

75

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
* The Apollo Approval Reference Number identifies a group of detectors that all have the same physical construction, but have features enabled or disabled via their software, and/or regional marking variations. **Base manufactured by EMS

Certificate No: Certificate No: Certificate No: Certificate No:

010ad to EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003 010h to EN 54-5:2000 + A1:2002, EN 54-7:2000 + A1:2002 & CEA 4021:2003 010m to CEA 4021: 1999-06(en) 010t to EN 54-7: 2000 & CEA 4021: 1999-06

Multi-criteria Detectors
Certificated Products XPA-OH-13032-APO Xpander addressable radio linked photoelectric multisensor smoke detector (XPA-WB10022-APO mounting base) Notes: 1) The complete radio base/detector combination is available as Apollo Part No.: XPACB-13032-APO. 2) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells. 3) The radio link functionality is not included within the scope of approval. Intrinsically safe multisensor detectors with Apollo Approval Reference* 50008 (Approved for use with base styles OB (+ATEX marking) and ORB-MB-50008-APO adapter base) 1 Analogue addressable multisensor detector (45681-209 and 45681-210 mounting base) Certificated with Apollo, Discovery, XP95 and S90 digital communication protocols that have been configured for the Discovery multisensor detector in accordance with manufacturer's instructions. Analogue addressable multisensor detector (45681-209 and 45681-210 mounting base) Note: Certificated at the following settings. Mode 1 - High sensitivity smoke detector with standard heat enhancement. Mode 2 - Smoke detection only. Mode 3 - Medium sensitivity smoke detector with standard heat enhancement. Mode 4 - Low sensitivity smoke detector with high heat enhancement. Mode 5 - Class A1 heat detector. Also Certificated in conventional alarm modes 1, 2, 3, 4 and 5. Certificated with Discovery XP95 and S90 digital communication protocols that have been configured for the Discovery multisensor detector in accordance with manufacturer's instructions. Multisensor smoke detectors with Apollo Approval Reference* 00008 (Approved for use with base styles OB, OL, OD, DX, OR, EB and ORB-BA-10008-APO adaptor base) LPCB Ref. No. 010ad/01

Orbis IS 55000-885 XP95

010t/02 010m/01

58000-700 Discovery

010h/01

Orbis

010t/01

Bases: 45681-209 XP95/Discovery standard deep mounting base 45681-210 XP95 mounting base TimeSaver bases with Apollo Approval Reference* OB TimeSaver LX bases with Apollo Approval Reference* OL TimeSaver diode bases with Apollo Approval Reference* OD TimeSaver relay bases with Apollo Approval Reference* OR TimeSaver LX diode bases with Apollo Approval Reference* DX TimeSaver IS bases with Apollo Approval Reference* OB (+ATEX marking) ORB-BA-50008 Orbis intrinsically safe adapter base (to be used in conjunction with the following bases only: 45681-207) ORB-BA-10008-APO Orbis adaptor base (to be used in conjunction with the following bases only: 45681-200 & 45681-201) XPA-WB-10022-APO Radio link mounting base** * The Apollo Approval Reference Number identifies a group of detectors that all have the same physical construction, but have features enabled or disabled via their software, and/or regional marking variations. **Base manufactured by EMS

76

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Argus-Spectrum
65 Serdobolskaya St, St. Petersburg 197342, Russia Tel: +7 812 7037500 Fax: +7 812 7037501 E-mail: mail@argus-spectr.ru Website: www.argus-spectr.ru
Certificate No: 603a to EN 54-7:2000

Smoke Detector
Certificated Products AURORA S100 Bases: BS100 Standard base BSD100 Schottky Diode base Conventional photoelectric smoke detector (BS100 and BSD100 mounting bases) LPCB Ref. No. 603a/01

Certificate No: 603b to EN 54-5:2000

Point Heat Detectors


Certificated Products AURORA S300 AURORA S400 Bases: BS100 Standard base BSD100 Schottky Diode base Conventional Class BS fixed temperature heat detector (BS100 and BSD100 bases) Conventional Class A1R rate-of-rise heat detector (BS100 and BSD100 bases) LPCB Ref. No. 603b/01 603b/02

Bardic by Honeywell
140 Waterside Road, Hamilton Industrial Estate, Leicester LE5 1TN UK Tel: +44 (0) 116 246 2212 Fax: +44 (0) 116 246 2210 Website: www.bardic.co.uk
Certificate No: 199n to EN 54-5: 2000

Heat Detectors
Certificated Products ZF03 class A2S ZF04 class BS ZF05 class A1R Conventional fixed temperature heat detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) Conventional fixed temperature heat detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) Conventional rate of rise heat detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) LPCB Ref. No. 199n/10 199n/11 199n/12

Bases: 2020B Standard base 2020DB Deep base 2020BSD Standard base with schottky diode 2020DBSD Deep base with schottky diode

Certificate No: 199m to EN 54-7: 2000

January 2009

77

PART 3: SECTION 4.1


COMMERCIAL DETECTORS Photoelectric Detectors
Certificated Products ZF01 Conventional photoelectric detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) LPCB Ref. No. 199m/05

Bases: 2020B Standard base 2020DB Deep base 2020BSD Standard base with schottky diode 2020DBSD Deep base with schottky diode

Certificate No: 199p to EN 54-5: 2000, EN 54-7: 2000 & CEA 4021 1999

Multi-criteria Detectors
Certificated Products ZF02 Conventional photo thermal detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) LPCB Ref. No. 199p/04

Bases: 2020B Standard base 2020DB Deep base 2020BSD Standard base with schottky diode 2020DBSD Deep base with schottky diode

Ceasefire Industries Ltd


"Doli Chambers", Flat 602 6th Floor behind strand cinema, Colaba, Mumbai-400 005, India Tel: +91 -22-22854677, 22854678 Fax: +91-22-66349069 E-mail: response@ceasefire.in Website: www.ceasefire.in
Certificate No: 117g to EN54-5:2000

Point Heat Detectors


Certificated Products DFJ-AE3 DCD-CE3 ACB-E Class A1S conventional fixed temperature heat detector (YBN-R/6 base) Class CR conventional rate of rise high temperature heat detector (YBN-R/6 base) Analogue addressable Class P heat detector (YBN-R/3 and YBO-R/SCI bases) Meets requirements of EN 54-5:2000 for classes A1R, A1S, BR, BS, CR and CS when used with ACB-E protocol and classes A1S, BS and CS when used with ATG-E protocol. LPCB Ref. No. 117g 117g/06 117g/09

Bases YBN-R/3 base YBN-R/6 standard base YBO-R/SCI isolator base

Chubb Fire Ltd


Chubb House, Staines Road West, Sunbury on Thames TW16 7AR UK Tel: +44 (0)1274 866920 Website: www.chubb.co.uk
Certificate No: 199m to EN 54-7: 2000 Certificate No: 118h to EN 54-7: 2000

78

January 2009

SECTION 4.1: PART


Point Smoke Detectors
Certificated Products Resonance High Sensitivity Laser Resonance Optical Resonance Ionisation Analogue addressable photoelectric laser smoke detector (B501, B501DG and B5241EFT & B524IEFT-1 bases) Note: meets the requirements of EN 54-7: 2000 at sensitivities 7 to 9 inclusive Analogue addressable optical smoke detector (B501, B501DG and B5241EFT bases) Note: Meets EN 54-7: 2000 at Low, Normal & High sensitivity settings Analogue addressable ionisation smoke detector (B501, B501DG and B5241EFT bases) Note: Meets EN 54-7: 2000 at Low, Normal & High sensitivity settings LPCB Ref. No. 118h/01 199m/02 199m/06

COMMERCIAL DETECTORS

Bases: B501 Analogue sensor base B501DG Analogue sensor deep base B524IEFT Analogue sensor isolator base

Certificate No: 199p to EN 54-5: 2000, EN 54-7: 2000 & CEA 4021: 1999

Multi-criteria Detectors
Certificated Products Resonance Combined Analogue addressable optical/thermal smoke & heat detector (B501, B501DG and B5241EFT bases) Note: Meets the requirements of EN 54-5: 2001 at class A1R & EN 54-7: 2000 at sensitivity settings 1 to 5 LPCB Ref. No. 199p/02

Bases: B501Analogue sensor base B501DG Analogue sensor deep base B524IEFT Analogue sensor isolator base

Certificate No: 199n to EN 54-5: 2000

Point Heat Detectors


Certificated Products Resonance Static Resonance Rate-of-Rise Heat Class A1S analogue addressable fixed temperature heat detector (B501, B501DG and B5241EFT bases) Class A1R analogue addressable high temperature rate of rise heat detector (B501, B501DG and B5241EFT bases) LPCB Ref. No. 199n/03 199n/04

Bases: B501 Analogue sensor base B501DG Analogue sensor deep base B524IEFT Analogue sensor isolator base

Cofem S.A.
Ctra. Molins de Rei a Rubi, Km 8.4, 08191 Rubi, Barcelona, Spain Tel: +34 935862690 Fax: +34 936999261 E-mail: cofem@cofem.com Website: www.cofem.com
Certificate No: 693a to EN 54-7: 2000

Point Smoke Detectors


Certificated Products DIH-4 Bases: Conventional ionisation smoke detector (ZDR base) LPCB Ref. No. 693a/01

January 2009

79

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
ZDR Standard Base

Cooper Fire Systems


Wheatley Hall Road, Doncaster, South Yorkshire DN2 4NB UK Tel: +44 (0)1302 321541 Fax: +44 (0)1392 303220
Certificate No: 685g to EN 54-5:2000 + A1:2002, EN 54-7:2000 + A1:2002 + A2:2006, CEA 4021: 2003

Multi-criteria Detectors
Certificated Products CPT341 CPTB341 Conventional opto/heat multisensor and Class A2S heat detector (CDB300 base) Conventional opto/heat multisensor and Class A2S heat detector (CDB300 base) LPCB Ref. No. 685g/01 685g/01

Bases: CDB300 Standard conventional mounting base CDBB300 Standard conventional mounting base

Certificate No: 685h to EN 54-7: 2000 + A1: 2002 + A2: 2006

Point Smoke Detectors


Certificated Products CPD321 CPDB321 Conventional photoelectric smoke detector (CDB300 base) Conventional photoelectric smoke detector (CDBB300 base) LPCB Ref. No. 685h/01 685h/01

Bases: CDB300 Standard conventional mounting base. CDBB300 Standard conventional mounting base.

Cooper Industries Inc


Wheatley Hall Road, Doncaster, South Yorkshire DN2 4NB UK Tel: +44 (0)1302 303303 Fax: +44 (0)1302 367155 E-mail: sales@cooper-ls.com Website: www.cooper-ls.com UK Sales: Menvier & JSB Tel: +44 (0)1302 303222 Fax: +44 (0)1302 367155 E-mail: enquiries@cooper-ls.com Website: www.cooper.ls.com

UK Sales: Tel: +44 (0)1594 541900 Fax: +44 (0)1594 541910

Certificate No: 685h to EN 54-7:2000 + A1:2002 + A2:2006 Certificate No: 685b to EN 54-7: 2000 Certificate No: 685d to EN 54-7: 2000

Point Smoke Detectors


Certificated Products CID310 COP1310 FXN521 MID810 Conventional ionisation smoke detector (CFS version) (CDB300 base) Conventional ionisation smoke detector (CFS version) (COPC800 base) Conventional ionisation smoke detector (JSB version) (FXN520 base) Conventional ionisation smoke detector (MDB800 base) LPCB Ref. No. 685b/01 685b/01 685b/01 685b/01

80

January 2009

SECTION 4.1: PART


Certificated Products COPP320 CPD320 CPDB320 FXN523 MPD820 CAP320 CAPB320 COPP420 FXN723 MAP820 CAI310 COP1410 FXN721 MAI810 FXN533 MPD821 Conventional photoelectric smoke detector (CFS version) (COPC800 base) Conventional photoelectric smoke detector (CFS version) (CDB300 base) Conventional photoelectric smoke detector (CFS version) (CDBB300 base) Conventional photoelectric smoke detector (JSB version) (FXN520 base) Conventional photoelectric smoke detector (MDB800 base) Analogue addressable photoelectric smoke detector (CFS version) (CAB300 base) Analogue addressable photoelectric smoke detector (CFS version) (CABB300 base) Analogue addressable photoelectric smoke detector (CFS version) (COPA800 base) Analogue addressable photoelectric smoke detector (JSB version) (FXN720 base) Analogue addressable photoelectric smoke detector (MAB800 base) Analogue addressable ionisation smoke detector (CFS version) (CAB300 base) Analogue addressable ionisation smoke detector (CFS version) (COPA800 base) Analogue addressable ionisation smoke detector (JSB version) (FXN720 base) Analogue addressable ionisation smoke detector (MAB800 base) Conventional photoelectric smoke detector (JSB version) (FXN520 base) Conventional photoelectric smoke detector (Menvier version) (MDB800 base) LPCB Ref. No. 685b/02 685b/02 685b/02 685b/02 685b/02 685d/01 685d/01 685d/01 685d/01 685d/01 685d/02 685d/02 685d/02 685d/02 685h/01 685h/01

COMMERCIAL DETECTORS

Bases: FXN520 standard conventional mounting base (JSB version) CDB300 standard conventional mounting base (CFS version) CDBB300 standard conventional mounting base (CFS version) COPC800 standard conventional mounting base (CFS version) MAB800 standard analogue addressable mounting base FXN720 standard analogue addressable mounting base (JSB version) COPA800 standard analogue addressable mounting base (CFS version) CAB300 standard analogue addressable mounting base (CFS version) CABB300 standard analogue addressable mounting base (CFS version) MDB800 standard conventional mounting base MDB800 Standard conventional mounting base (Menvier version) FXN520 Standard conventional mounting base (JSB version)

Certificate No: 685c to EN 54-5: 2000 Certificate No: 685e to EN 54-5: 2000, EN 54-7: 2000, GEI 1-052, Draft 2.0, 11/06/97 and CEA 4021: 1999 Certificate No: 685a to EN 54-5: 2000

Point Heat detectors


Certificated Products CFR330 CFRB330 COPR330 FXN525 MFR830 CMT360 CMTB360 COPT360 FXN524 MMT860 CHT390 CHTB390 COPT390 FXN526 MHT890 CAH330 CAHB330 COPH430 FXN725 MAH830 CAPT340 CAPTB340 COPOH450 FXN722 MAOH850 Conventional Class A2R heat detector (CFS version) (CDB300 base) Conventional Class A2R heat detector (CFS version) (CDBB300 base) Conventional Class A2R heat detector (CFS version) (COPC800 base) Conventional Class A2R heat detector (JSB version) (FXN520 base) Conventional Class A2S heat detector (MDB800 base) Conventional Class BS heat detector (CFS version) (CDB300 base) Conventional Class BS heat detector (CFS version) (CDBB300 base) Conventional Class BS heat detector (CFS version) (COPC800 base) Conventional Class BS heat detector (JSB version) (FXN520 base) Conventional Class BS heat detector (MDB800 base) Conventional Class CS heat detector (CFS version) (CDB300 base) Conventional Class CS heat detector (CFS version) (CDBB300 base) Conventional Class CS heat detector (CFS version) (COPC800 base) Conventional Class CS heat detector (JSB version) (FXN520 base) Conventional Class CS heat detector (MDB800 base) Analogue addressable Class P heat detector (CFS version) (CAB300 base) Note: meets requirements of EN 54 Part 5:2000 at Classes A1R, BS, CS. Analogue addressable Class P heat detector (CFS version) (CABB300 base) Note: meets requirements of EN 54 Part 5:2000 at Classes A1R, BS, CS. Analogue addressable Class P heat detector (CFS version) (COPA800 base) Note: meets requirements of EN 54 Part 5:2000 at Classes A1R, BS, CS. Analogue addressable Class P heat detector (JSB version) (FXN720 base) Note: meets requirements of EN 54 Part 5:2000 at Classes A1R, BS, CS. Analogue addressable Class P heat detector (MAB800 base) Note: meets requirements of EN 54 Part 5:2000 at Classes A1R, BS, CS. Analogue addressable Class P heat detector (CFS version) (CAB300 base) Analogue addressable Class P heat detector (CFS version) (CABB300 base) Addressable heat detector (CFS version) (COPA800 base) Analogue addressable heat detector (JSB version) (FXN720 base) Analogue addressable Class A2S multisensor opto/heat detector (MAB800 base) LPCB Ref. No. 685a/01 685a/01 685a/01 685a/01 685a/01 685a/02 685a/02 685a/02 685a/02 685a/02 685a/03 685a/03 685a/03 685a/03 685a/03 685c/01 685c/01 685C/01 685c/01 685c/01 685e/01 685e/01 685e/01 685e/01 685e/01

January 2009

81

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Bases: FXN720 standard analogue addressable mounting base (JSB version) COPA800 standard analogue addressable mounting base (CFS version) CAB300 standard analogue addressable mounting base (CFS version) CABB300 standard analogue addressable mounting base (CFS Version) MAB800 standard analogue addressable mounting base FXN520 standard conventional mounting base (JSB version) CDB300 standard conventional mounting base (CFS version) CDBB300 standard conventional mounting base (CFS version) COPC800 standard conventional mounting base (CFS version) NDFXN520 standard conventional mounting base (without diode)

Certificate No: 685g to EN 54-5:2000 + A1:2002, EN 54-7:2000 + A1:2002 + A2:2006, CEA 4021:2003

Multi-Criteria Dectectors
Certificated Products FXN632 MPT951 Conventional opto/heat multisensor and Class A2S heat detector (JSB version) (FXN520 base) Conventional opto/heat multisensor and Class A2S heat detector (Menvier version) (MDB800 base) LPCB Ref. No. 685g/01 685g/01

Bases: MDB800 Standard conventional mounting base (Menvier version) FXN520 Standard conventional mounting base (JSB version)

Detectomat GmbH
An Der Strusbek 5, D-22926 Ahrensburg, Hamburg, Germany Tel: +49 4102 2114 636 Fax: +49 4102 2114 670 E-mail: approval@detectomat.com
Certificate No: 632a to EN 54-7: 2000

Point Smoke Detectors


Certificated Products PL 3300 O TL 3300 O PL 3200 O TL 3200 O Analogue addressable photoelectric smoke detector with integral short circuit isolator function (30301 base) Analogue addressable photoelectric smoke detector with integral short circuit isolator function (30301 base) Analogue addressable photoelectric smoke detector (30301 base) Analogue addressable photoelectric smoke detector (30301 base) LPCB Ref. No. 632a/01 632a/02 632a/03 632a/04

Bases: 30301 Standard mounting base

Certificate No: 632b to EN 54-5: 2000

Point Heat Detectors


Certificated Products PL 3300 T PL 3200 T Analogue addressable Class A1 heat detector with integral short circuit isolator function (30301 base) Analogue addressable Class A1 heat detector (30301 base) LPCB Ref. No. 632b/01 632b/02

Bases: 30301 Standard mounting base

82

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Certificate No: 632c to EN 54-5: 2000, EN 54-7: 2000, CEA 4021: 2003 & CEA GEI 1-052: Draft 2.0, 11.06.97 Certificate No: 632d to EN 54-5: 2000, EN 54-7: 2000 & CEA 4021: 2003

Multi-criteria Detectors
Certificated Products PL 3300 OT PL 3200 OT Analogue addressable multisensor detector with short circuit isolator (30301 base) Note: Meets the requirements of EN 54-5: 2000 at Class A1 and EN 54-7: 2000 at standard sensitivity setting Analogue addressable multisensor detector (30301 base) Note: Meets the requirements of EN 54-5: 2000 at Class A1 and EN 54-7: 2000 at standard sensitivity setting LPCB Ref. No. 632c/01 632d/01

Bases: 30301 Standard mounting base

Emergi-Lite Safety Systems (Thomas & Betts Ltd)


Bruntcliffe Lane, Morley, Leeds LS27 9LL UK Tel: +44 (0)113 2810600 Fax: +44 (0)113 2810601 Website: www.emergi-lite.co.uk
Certificate No: 010p to EN 54-5:2000 + A1:2002

Point Heat Detectors


Certificated Products FADY-TEM Analogue addressable heat detector (FA95-ACB mounting base) Notes: 1) Meets the requirements of EN54: Part 5 Class A1R in mode 1 and in conventional mode Class A2 in mode 2 and in conventional mode Class A2S in mode 3 and in conventional mode Class CR in mode 4 and in conventional mode Class CS in mode 5 and in conventional mode 2) Certificated with Apollo Discovery, XP95, and S90 digital communications protocols configured for the Discovery heat detector in accordance with manufacturers instructions. Conventional Class A1R heat detector (FAP6-STB mounting base) Notes: 1) Meets the requirements of EN54: Part 5 - Class A1R Conventional Class BR heat detector (FAP6-STB mounting base) Notes: 1) Meets the requirements of EN54: Part 5 - Class BR Conventional Class CR heat detector (FAP6-STB mounting base) Notes: 1) Meets the requirements of EN54: Part 5 - Class CR Conventional Class CS heat detector (FAP6-STB mounting base) Notes: 1) Meets the requirements of EN54: Part 5 - Class CS LPCB Ref. No. 010p/03

FAP6-RR6 FAP6-RR75 FAP6-RR90 FAP6-FT8

010p/06 010p/09 010p/12 010p/15

Bases: FAP6-STB Mounting base

Certificate No: 010q to EN 54 - 7:2000 + A1:2002

Point Smoke Detectors


Certificated Products FADY-OPT Analogue addressable optical smoke detector (FA95-ACB mounting base) Notes: 1) Meets the requirements of EN54: Part 7 in modes 1, 2, 3, 4 and 5 and in conventional mode. 2) Certificated with Apollo Discovery, XP95, and S90 digital communications protocols LPCB Ref. No. 010q/03

January 2009

83

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products FAP6-ION FAP6-OPT Bases; FAP6-STB Mounting base configured for the Discovery heat detector in accordance with manufacturers instructions. Conventional ionisation smoke detector (FAP6-STB mounting base) Conventional optical smoke detector (FAP6-STB mounting base) LPCB Ref. No. 010q/06 010q/12

Certificate No: 010h to EN 54-5:2000 + A1:2002, EN 54-7:2000 + A1:2002, CEA 4021:2003

Multi-criteria Detectors
Certificated Products FADY-MUS Analogue addressable multisensor detector (FA95-ACB mounting base) Notes: 1) Certificated at the following settings: Mode 1 - High sensitivity smoke detector with standard heat enhancement Mode 2 - Smoke detection only Mode 3 - Medium sensitivity smoke detector with standard heat enhancement Mode 4 - Low sensitivity smoke detector with high heat enhancement Mode 5 - Class A1 heat detector Also approved in conventional alarm modes 1, 2, 3, 4 and 5 2) Certificated with Apollo Discovery, XP95, and S90 digital communications protocols configured for the Discovery heat detector in accordance with manufacturers instructions. LPCB Ref. No. 010h/01

Bases: FA95-ACB Mounting base FAP6-STB Diode mounting base

Emirates Fire Fighting Equipment Factory (FIREX)


Industrial Area 13, P.O.Box 22436, Sharjah, UAE Tel: +971 6 5340300 Fax: +971 6 5340090 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 506a to EN54-7: 2000

Point Smoke Detectors


Certificated Products FX-0311-2 FX-0311-3 FX-0311-4 Bases: AHMB-031 mounting base (2 - wire) Conventional photoelectric smoke detector (AHMB-031 Base) (3 - wire) Conventional photoelectric smoke detector (AHMB-031 Base) (4 - wire) Conventional photoelectric smoke detector (AHMB-031 Base) LPCB Ref. No. 506a/02 506a/03 506a/04

Certificate No: 506b to EN43-7: 2000 & CEA 4021: 1999

Multi-criteria Detectors
Certificated Products FX-0315-2 FX-0315-3 FX-0315-4 Bases: AHMB-031 mounting base (2 - wire) Optical smoke and Class A2 heat detector (AHMB-31 Base) (3 - wire) Optical smoke and Class A2 detector (AHMB-31 Base) (4 - wire) Optical smoke and Class A2 heat detector (AHMB-31 Base) LPCB Ref. No. 506b/01 506b/02 506b/03

84

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Certificate No: 506c to EN54-5: 2000

Point Heat Detector


Certificated Products FX-0316-2 FX-0316-3 FX-0316-4 (2 wire) Conventional Class A2 rate of rise and fixed temperature heat detector (AHMB31 Base) (3 wire) Conventional Class A2 rate of rise and fixed temperature heat detector (AHMB031 Base) (4 wire) Conventional Class A2 rate of rise and fixed temperature heat detector (AHMB31 Base) LPCB Ref. No. 506c/01 506c/02 506c/03

Bases: AHMB-031 mounting base

EMS Radio Fire & Security Limited


Technology House, Herne Bay West Trading Estate, Herne Bay, Kent CT6 8JZ UK Tel: +44 (0)1227 369570 Fax: +44 (0)1227 369679 E-mail: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Certificate No: 786e to EN 54-7: 2000 + A1: 2002 Certificate No: 786c to EN 54-7: 2000 + A1: 2002 and CEA 4021: 2003

Smoke Detectors
Certificated Products XP-174-001 Fire-Cell addressable radio linked photoelectric multisensor smoke detector (XP-170-001 mounting base) Notes: 1) The complete radio base/detector combination is available as EMS Part No.: XP-130001 2) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells 3) The radio link functionality is not included within the scope of approval Fire-Cell addressable radio linked photoelectric smoke detector (XP-170-001 Radio link mounting base) Notes: 1) The complete radio base/detector combination is available as EMS Part No.: XP-100001 2) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells 3) The radio link functionality is not included within the scope of approval LPCB Ref. No. 786c/01

XP-177-001

786e/01

Bases: XP-170-001 Radio link mounting base

Certificate No: 786d to EN 54-5:2000 + A1: 2002

Heat Detectors
Certificated Products XP-175-001 Fire-Cell addressable radio linked Class A1R heat detector (XP-170-001 Radio link mounting base) Notes: 1) Meets the requirements of EN 54-5 for Class A1R 2) The complete radio base/detector combination is available as EMS Part No.: XP-120001 3. The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells 4) The radio link functionality of this device is not included within the scope of approval Fire-Cell addressable radio linked Class CS heat detector (XP-170-001 Radio link mounting base) LPCB Ref. No. 786d/01

XP-176-001

786d/02

January 2009

85

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products Notes: 1) Meets the requirements of EN 54-5 for Class A1R 2) The complete radio base/detector combination is available as EMS Part No.: XP-120011 3. The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells 4) The radio link functionality of this device is not included within the scope of approval Bases: XP-170-001 Radio link mounting base LPCB Ref. No.

Everday Technology Co. Limited


No.8, Lane, 492 Ba-Der Street, Shulin 238, Taipei Hsien, Taiwan ROC Tel: +886 2 2668 9668 Fax: +862 2 2668 9666 E-mail: sales@everday.com Website: www.everday.com
Certificate No: 512a to EN 54-7: 2000

Smoke Detectors
Certificated Products EA318-2 EA318-2(LED) EA318-4-12 EA318-4-24 Conventional 2 wire photoelectric smoke detector (P/N852001 base) Conventional 2 wire photoelectric smoke detector with remote LED output (P/N854001 base) Conventional 4 wire photoelectric smoke detector (P/N854001 base) Conventional 4 wire photoelectric smoke detector (P/N854001 base) LPCB Ref. No. 512a/01 512a/02 512a/03 512a/04

Bases: P/N854001 4-wire detector base P/N852001 2-wire detector base

Certificate No: 512b to EN 54-5 and 7: 2000 and CEA4021: 1999

Multi-criteria Detectors
Certificated Products EA318-2H EA318-2H-LED EA318-4H-12 EA318-4H-24 Conventional 2 wire photoelectric smoke and heat detector (P/N852001 base) Conventional 2 wire photoelectric smoke and heat detector with remote LED output (P/N854001 base) Conventional 4 wire photoelectric smoke and heat detector (P/N854001 base) Conventional 4 wire photoelectric smoke and heat detector (P/N854001 base) LPCB Ref. No. 512b/01 512b/02 512b/03 512b/04

Bases: P/N854001 4-wire detector base P/N852001 2-wire detector base

Certificate No: 512d to EN 54-5: 2000

86

January 2009

SECTION 4.1: PART


Point Heat Detectors
Certificated Products EA323-2 EA323-2 EA323-2L EA323-2L EA323-4 EA323-4 EA323-4 EA323-4 Conventional 2 wire 24VDC class A2S fixed temperature and rate-of-rise heat detector (P/N852001 base) Conventional 2 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector (P/N852001 base) Conventional 2 wire 24VDC class A2S fixed temperature and rate-of-rise heat detector with LED output (P/N854001 base) Conventional 2 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector with LED output (P/N854001 base) Conventional 4 wire 12VDC class A2S fixed temperature and rate-of-rise heat detector (P/N854001 base) Conventional 4 wire 12VDC class A2R fixed temperature and rate-of-rise heat detector (P/N854001 base) Conventional 4 wire 24VDC class A2S fixed temperature and rate-of-rise heat detector (P/N854001 base) Conventional 4 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector (P/N854001 base) LPCB Ref. No. 512d/01 512d/02 512d/03 512d/04 512d/05 512d/06 512d/07 512d/08

COMMERCIAL DETECTORS

Bases: P/N852001 2-Wire detector base P/N854001 4-Wire detector base

Fire Fighting Enterprises Ltd


9 Hunting Gate, Hitchin, Hertfordshire SG4 0TJ UK Tel: 0845 4024242 Fax: 0845 4024201 E-mail: sales@ffeuk.com Website: www.ffeuk.com
Certificated Products Fireray 5000 Fireray 5000 50m Conventional self aligning optical beam detector (0020-017 mounting bracket) Notes: 1) Meets the requirements of EN 54-12 :2002 when configured with the following settings: Compensation limit of 0%/hour only Delay to fire setting between 2 and 20 seconds only Sensitivity level setting from 25% to 35% only 2) The device must be installed with the protective cage (Part No.: 0052-001). 3) The device is approved over a range of 8 to 50m LPCB Ref. No. 831a/01

Fireguard Safety Equipment Co Ltd


2nd Floor, 145-147 St Johns Street, London EC1V 4PY UK Tel: +44 (0)8450 751042 Fax: +44 (0)8450 751043 E-mail: info@fireguard-uk.com Website: www.fireguard-uk.com
Certificate No: 512a/02 to EN 54-7: 2000 + A1: 2002 Certificated Products Fireguard FG18-2L Conventional 2 wire photoelectric smoke detector with remove LED output (Fireguard P/N FG854001 base) Bases: Fireguard P/N FG854001 4 wire detector base LPCB Ref. No. 512a/02

January 2009

87

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificate No: 512d/04 to EN54-5: 2000 + A1: 2002 Certificated Products Fireguard FG323-2L Conventional 2 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector with LED output (Fireguard P/N FG854001 base) Bases: Fireguard P/N FG854001 4 wire detector base LPCB Ref. No. 512d/04

FIREX Protection System Technology Ltd


28-38 Desborough Street, High Wycombe, Bucks UK Tel: +44 (0)1494 601077 Fax: +44 (0)1494 601011 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 548c to EN 54-5: 2000

Heat Detectors
Certificated Products FX9103 FX9103I Conventional heat detector Class A1R (DZ-03 base) Intelligent Rate of Rise Heat Detector Class A1R (DZ-03 base) LPCB Ref. No. 548c/01 548c/02

Bases: DZ-03 Standard detector base

Certificate No: 548d to EN 54-7: 2000

Smoke Detectors
Certificated Products FX9102 FX9102I Conventional Photoelectric Smoke Detector (DZ-03 base) Intelligent Photoelectric Smoke Detector (DZ-03 base) LPCB Ref. No. 548d/01 548d/02

Bases: DZ-03 Standard detector base

Certificate No: 548k to EN 54-12:2002

Beam Detectors
Certificated Products FX9105RI Intelligent optical beam detector Notes: 1) Meets the requirements of EN 54-12 at the following sensitivity settings: Level 1 - 1.61 dB Level 2 - 2.31dB LPCB Ref. No. 548k/01

88

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

GE Security (Africa) trading as Ziton


Ziton House, 555 Voortrekker Road, Maitland 7405, Republic of South Africa Tel: +27 21 5066000 Fax: +27 21 5066100 Website: www.ziton.com UK Sales Enquiries: Tel: +44 (0)1908 281981 Fax: +44 (0)1908 282554

Certificate No: 092n to EN 54-7: 2000 Certificate No: 092s to CEA 4022: 1999-12

Point Smoke Detectors


Certificated Products ZP710-2 ZP730-2 Z610-3 Z630-3 LaserSense Analogue addressable ionisation smoke detector (ZP7-SB1 mounting base) Note: Approved for use at 'Standard' sensitivity setting only. Analogue addressable photoelectric smoke detector (ZP7-SB1 mounting base) Note: Approved for use at 'Standard' sensitivity setting only. Conventional ionisation smoke detector (Z6-BS1 and Z6-BS5 bases) Conventional photoelectric smoke detector (Z6-BS1 and Z6-BS5 bases) Ultra High Sensitivity aspirating smoke detector Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with GE Security (Africa) Installers Handbook (UD1616.5) with per hole sensitivities of better than 5%/m, as predicted by the PipeCAD system LPCB Ref. No. 092n/01 092n/02 092n/03 092n/04 092s/01

Bases: ZP7-SB1 standard base Z6-BS1 conventional surface base Z6-BS5 conventional diode base

Certificate No: 092p to EN 54-5: 2000

Point Heat Detectors


Certificated Products ZP720-3 Z620-581-3 Z620-582-3 Z620-771-3 Analogue addressable Class P heat detector (ZP7-SB mounting base) Note: Approved for use at heat Class sensitivity settings 1 (Class A2) and 2 (Class A1) only. Conventional Class A1heat detector (Z6-BS1 and Z6-BS5 bases) Conventional Class A1R heat detector (Z6-BS1 and Z6-BS5 bases) Conventional Class B heat detector (Z6-BS1 and Z6-BS5 bases) LPCB Ref. No. 092p/01 092p/02 092p/03 092p/04

Bases: ZP7-SB1 standard base Z6-BS1 conventional surface base Z6-BS5 conventional diode base

Certificate No: 092k to EN 54:Part 5: 2000, EN 54:Part 7: 2000 and CEA 4021: 2003

Multi-criteria Detectors
Certificated Products ZP732-2 Analogue addressable combined photoelectric smoke and class A1 heat detector (ZP7SB1 base) LPCB Ref. No. 092k/01

January 2009

89

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products Note: Certificated at sensitivity profiles 1-4 for EN 54:Part 7 and sensitivity profiles 5 (A1) for EN54:Part 5. Bases: ZP7-SB1 standards base LPCB Ref. No.

GE Security Inc
5 North Main Street, Pittsfield, ME 04967, USA Tel: +1 207 487 3104 Fax: +1 207 487 5526 E-mail: leon.newsome@ge.com Website: www.gesecurity.com European Sales: Rudford Estate, Ford Aerodrome, Arundel, West Sussex BN18 0BE UK Tel: +44 (0)1903 711 440 Fax: +44 (0)1903 711 448 E-mail: info@estinternational.com

Certificate No: 262t to EN 54-7: 2000 Certificate No: 092n to EN 54-7: 2000 + A1:2002

Point Smoke Detectors


Certificated Products EA10E-2 EA30E-2 E610-3 E630-3 SIGA-ISI Analogue addressable ionization smoke detector (ZP7-SB1 base) Note: Approved for use at Standard sensitivity setting only. Analogue addressable photoelectric smoke detector (ZP7-SB1 base) Note: Approved for use at Standard sensitivity setting only. Conventional ionisation smoke detector (E6-BS1 base) Conventional photoelectric smoke detector (E6-BS1 base) Intelligent ionisation smoke detector (SIGI-IBS, SIGI-SB, SIGI-SB4, SIGI-RB, and SIGIRB4 bases) Note: Meets the requirements of EN 54-7:2000 at sensitivity settings 1.0%/ft, 2%/ft, 2.5%/ft, 3%/ft, and 3.5%/ft. Intelligent photoelectric smoke detector (SIGI-IBS, SIGI-SB, SIGI-SB4, SIGI-RB, and SIGI-RB4 bases) Note: Meets the requirements of EN 54-7:2000 at sensitivity settings 1.0%/ft, 2%/ft, 2.5%/ft, 3%/ft, and 3.5%/ft. LPCB Ref. No. 092n/01 092n/02 092n/03 092n/04 262t/01

SIGA-PSI

262t/02

Bases: E6-BS1 Conventional surface base ZP7-SB1 Standard base

Certificate No: 262u to EN 54-5: 2000 Certificate No: 092p to EN 54-5: 2000

Point Heat Detectors


Certificated Products E620-581-3 E620-582-3 E620-771-3 SIGA-HFSI SIGA-HRSI Conventional Class A1 heat detector (E6-BS1 base) Conventional Class A1R heat detector (E6-BS1 base) Conventional Class B heat detector (E6-BS1 base) Intelligent class A2S fixed heat detector (SIGI-IBS, SIGI-SB, SIGI-SB4, SIGI-RB, and SIGI-RB4 bases) Intelligent class A1 rate of rise heat detector (SIGI-IBS, SIGI-SB, SIGI-SB4, SIGI-RB, and SIGI-RB4 bases) LPCB Ref. No. 092p/02 092p/03 092p/04 262u/01 262u/02

Bases: E6-BS1 Conventional surface base

90

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Certificate No: 092k to EN 54-5: 2000, EN54-7: 2000, A1: 2002 and CEA 4021: 2003 Certificate No: 262s to EN 54-7: 2000 and CEA 4021: 1999

Multi-criteria Detectors
Certificated Products EA32E-2 Analogue addressable combined photoelectric smoke and Class A1 heat detector (ASBE-2 base) Note: Certificated at sensitivity profiles 1-4 for EN 54: Part 7 and sensitivity profiles 5 (A1) and 6 (A2) for EN 54: Part 5. Intelligent thermally enhanced photoelectric and ionisation smoke detector (SIGI-IBS, SIGI-SB, SIGI-SB4, SIGI-RB, and SIGI-RB4 bases) Note: Meets the requirements of EN 54-7:2000 at sensitivity settings 1.0%/ft, 2%/ft, 2.5%/ft, 3%/ft, and 3.5%/ft. Intelligent thermally enhanced photoelectric smoke detector (SIGI-IBS, SIGI-SB, SIGI-SB4, SIGI-RB, and SIGI-RB4 bases) Note: Meets the requirements of EN 54-7:2000 at sensitivity settings 1.0%/ft, 2%/ft, 2.5%/ft, 3%/ft, and 3.5%/ft. LPCB Ref. No. 092k/01

SIGA-IPHSI

262s/01

SIGA-PHSI

262s/02

Bases: SIGA-SB standard base SIGA-SB4 standard base and trim skirt SIGA-RB relay base SIGA-RB4 relay base and trim skirt SIGA-IBS Isolator base SIGA-IBS4 Isolator base and trim skirt SIGI-IBS Isolator base SIGA-SB Standard base SIGA -SB4 Standard base with trim skirt SIGA -RB Relay base SIGA -RB4 Relay base with trim skirt

Gent By Honeywell
140 Waterside Road, Hamilton Industrial Park, Leicester LE5 1TN UK Tel: +44 (0)116 246 2000 Fax: +44 (0)116 246 2300 E-mail: gent_enquiry@gent.co.uk Website: www.gent.co.uk Middle East Sales Enquiries: E-mail: gent.export@honeywell.com

Certificate No: 400j to EN 54-7: 2000 Certificate No: 567a to BS 5445: Part 7: 1984 This certificate is to a withdrawn standard. Detectors conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). This certificate, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. Certificate No: 042as to EN 54-7: 2000 + A1: 2002 and GEI 1 - 084

Point Smoke Detectors


Certificated Products S4-710 S-Quad analogue addressable optical smoke and Class A1 heat multisensor detector (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Note: 1) Meets the requirement of EN 54: Part 5 and requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical / Class A1 heat S4-770 S-Quad analogue addressable optical smoke and Class A1 heat multisensor detector with sounder (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Note: 1) Meets the requirement of EN 54: Part 5 and requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical / Class A1 heat LPCB Ref. No. 042am/04

S4-770

042an/04

January 2009

91

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products 2) Meets the requirements of EN 54: Part 3 at the following sounder tone settings: High - Continuous 933 Hz Alternate - High 933 Hz for 0.25 secs / Low 700 Hz for 0.25 secs S-Quad analogue addressable optical smoke detector (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Note: 1) Meets the requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical Analogue addressable optical smoke detector (805590 and 805591 bases) Conventional ionisation smoke detector (17800-01, 17801-01, 17800-02 and 17801-02 bases) Note: This product is certificated to a withdrawn standard. Detectors conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. Conventional photoelectric smoke detector (17800-01, 17801-01, 17800-02 and 1780102 bases) Note: This product is certificated to a withdrawn standard. Detectors conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. LPCB Ref. No.

S4-715

042as/01

O-803371 17830-01

400j/03 567a/01

17840-01

567a/02

Bases: 78200-01NM standard base 17800-01 standard base 17801-01 standard base with diode 17800-02 low profile base 17801-02 low profile base with diode 805590 vase for series 1Q8quad detectors 805591 base for series 1Q8quad detectors with relay output

Certificate No: 567b to BS 5445: Part 5: 1977 This certificate is to a withdrawn standard. Detectors conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). This certificate, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. Certificate No: 042aj to EN 54-5: 2000 + A1: 2002 & CEA GEI 1 - 084 Certificate No: 042ak to EN 54-5: 2000 + A1: 2002, EN 54-3: 2001 + A1: 2002 & CEA GEI 1 - 084

Point Heat Detectors


Certificated Products S4-720 S-Quad analogue addressable Class P heat detector (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Note: 1) Meets the requirement of EN 54: Part 5 at the following settings: State 0 - Class A1 State 5 - Class B S-Quad analogue addressable Class P heat detector with sounder (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Notes: 1) Meets the requirements of EN 54: Part 5 at the following settings: State 0 - Class A1 State 5 - Class B 2) Meets the requirements of EN 54: Part 3 at the following sounder tone settings: High - Continuous 933 Hz Alternate - High 933 Hz for 0.25 secs / Low 700 Hz for 0.25 secs Conventional grade 1 fixed temperature heat detector (17800-01, 17801-01, 17800-02 and 17801-02 bases) Note: This product is certificated to a withdrawn standard. Detectors conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. Conventional grade 1 rate-of-rise heat detector (17800-01, 17801-01, 17800-02 and 17801-02 bases) Note: This product is certificated to a withdrawn standard. Detectors conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the LPCB Ref. No. 042aj/01

S4-780

042ak/01

17850-01

567b/01

17860 -01

567b/02

92

January 2009

SECTION 4.1: PART


Certificated Products 34720 withdrawn standard requirements are still requested by some regulators outside the EU. Analogue addressable heat sensor (34700 and 34761 bases) Note: This product is certificated to a withdrawn standard. Detectors conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). The certification, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. LPCB Ref. No. 567b/03

COMMERCIAL DETECTORS

Bases: 34700 standard base 17800-01 standard base 17801-01 standard base with diode 17800-02 low profile base 17801-02 low profile base with diode S4-700 standard base S4-FLUSH semi-flush fixing kit

Certificate No: 567d to BS 5445: Part 5: 1977 and BS 5445: Part 7: 1984 This certificate is to a withdrawn standard. Detectors conforming to this standard are not suitable for use within the jurisdiction of the European Union (EU). This certificate, to the withdrawn standard, is maintained because detectors meeting the withdrawn standard requirements are still requested by some regulators outside the EU. Certificate No: 042am to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002, CEA 4021: 2003-07 & CEA GEI 1 - 084 Certificate No: 042an to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2000, EN 54-3: 2001 + A1:2002, CEA 4021: 2003-07 & CEA GEI 1 - 084

Multi-criteria Detectors
Certificated Products S4-711 S-Quad analogue addressable dual optical smoke and Class P heat multisensor detector (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Note: 1) Meets the requirement of EN 54: Part 5 and requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical / Class A1 heat State 5 - Medium optical / Class B heat State 8 - Delayed medium optical / Class A1 heat S-Quad analogue addressable dual optical smoke and Class P heat multisensor detector with strobe (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Notes: 1) Meets the requirement of EN 54: Part 5 and requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical / Class A1 heat State 5 - Medium optical / Class B heat State 8 - Delayed medium optical / Class A1 heat 2) The strobe function is not included within the scope of this approval S-Quad analogue addressable dual optical smoke, Class P heat and carbon monoxide multisensor detector (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Notes: 1) Meets the requirement of EN 54: Part 5 and requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical / Class A1 heat 2) Meets the requirements of EN 54: Part 5 at the following settings: State 9 - Class A1 heat 3) Carbon monoxide detection is not included within the scope of this approval S-Quad analogue addressable dual optical smoke and Class P heat multisensor detector with speech and strobe (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Notes: 1) Meets the requirement of EN 54: Part 5 and requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical / Class A1 heat State 5 - Medium optical / Class B heat State 8 - Delayed medium optical / Class A1 heat 2) Meets the requirements of EN 54: Part 3 at the following sounder tone settings: High - Continuous 933 Hz Alternate - High 933 Hz for 0.25 secs / Low 700 Hz for 0.25 secs 3) Speech and strobe not included in scope of approval S-Quad analogue addressable dual optical smoke and Class P heat multisensor detector LPCB Ref. No. 042am/01

S4-711-ST

042am/02

S4-911

042am/03

S4-711-ST-VO

042an/01

S4-771

042an/02

January 2009

93

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products with sounder (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Notes: 1) Meets the requirement of EN 54: Part 5 and requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical / Class A1 heat State 5 - Medium optical / Class B heat State 8 - Delayed medium optical / Class A1 heat 2) Meets the requirements of EN 54: Part 3 at the following sounder tone settings: High - Continuous 933 Hz Alternate - High 933 Hz for 0.25 secs / Low 700 Hz for 0.25 secs S4-911-ST-VO S-Quad analogue addressable optical smoke, heat and carbon monoxide multisensor detector with speech and strobe (S4-700 Standard base with or without S4-FLUSH semi-flush mounting kit) Notes: 1) Meets the requirements of EN 54: Part 5 and requirements of EN 54: Part 7 at the following settings: State 0 - Medium optical / Class A1 heat 2) Meets the requirements of EN 54: Part 5 at the following settings: State 9 - Class A1 heat 3) Meets the requirements of EN 54: Part 3 at the following sounder tone settings: High - Continuous 933 Hz Alternate - High 933 Hz for 0.25 secs / Low 700 Hz for 0.25 secs 4) Carbon monoxide detection, speech and strobe not included within the scope of this approval 042an03 LPCB Ref. No.

Bases: 34700 standard base S4-700 standard base S4-FLUSH semi-flush fixing kit

Global System Technology Plc


Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire LE65 1RT UK Tel: +44 (0)1283 225 478 Fax: +44 (0)1283 222 039 E-mail: info@gst.uk.com Website: www.gst.uk.com
Certificate No: 548k to EN 54-12:2002

Beam Detectors
Certificated Products I-9105R Intelligent Reflective Beam Detector Notes: 1) Meets the requirements of EN 54-12 at the following sensitivity settings: Level 1 - 1.61 dB Level 2 - 2.31 dB LPCB Ref. No. 548k/01

Certificate No: 548c to EN 54-5:2000

Point Heat Detectors


Certificated Products C9103 I-9103 Bases: DZ-03 Standard detector base Conventional Class A1R heat detector (DZ-03 base) Intelligent Class A1R heat detector (DZ-03 base) LPCB Ref. No. 548c/01 548c/02

94

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Certificate No: 548d to EN 54-7:2000

Smoke Detectors
Certificated Products C-9102 I-9102 Bases: DZ-03 Standard detector base Conventional Photoelectric Smoke Detector (DZ-03 base) Intelligent Photoelectric Smoke Detector (DZ-03 base) LPCB Ref. No. 548d/01 548d/02

GLT Exports Limited


Detection House, 72-78 Morfa Road, Swansea SA1 2EN UK Tel: +44 (0)1792 455175 Fax: +44 (0)1792 455176 E-mail: ghassan@gltexports.com Website: www.gltexports.com
Certificate No: 010v to EN 54-7:2000

Point Smoke Detectors


Certificated Products 80-020 Fyreye FEO2000 80-120 Fyreye FEAO2000 Conventional optical smoke detector (80-50, 80-052, 80-054 mounting bases) Analogue addressable optical smoke detector (80-50, 80-080, 80-090 mounting bases) LPCB Ref. No. 010v/01 010v/02

Bases: 80-050 FE CB Common mounting base 80-052 FE DB Diode mounting base 80-054 FE RB Relay mounting base 80-080 FEA RB Addressable relay mounting base 80-090 FE IB Negative switching isolating base

Certificate No: 010u to EN 54-5:2000

Point Heat Detectors


Certificated Products 80-030 Fyreye FEHR2000 80-032 Fyreye FEHBR2000 80-040 Fyreye FEFH2000 80-130 Fryeye FEAH2000 80-131 Fyreye FEAHH2000 Conventional Class A1R heat detector (80-50, 80-052, 80-054 mounting bases) Conventional Class BR heat detector (80-050,80-052,80-054 mounting bases) Conventional Class C heat detector (80-50, 80-052, 80-054 mounting bases) Analogue addressable Class A2S heat detector (80-50, 80-080, 80-090 mounting bases) Analogue addressable Class CS heat detector (80-50, 80-080, 80-090 mounting bases) LPCB Ref. No. 010u/01 010u/02 010u/03 010u/04 010u/05

Bases: 80-050 FE CB Common mounting base 80-052 FE DB Diode mounting base 80-054 FE RB Relay mounting base 80-080 FEA RB Addressable relay mounting base 80-090 FE IB Negative switching isolating base

January 2009

95

PART 3: SECTION 4.1


COMMERCIAL DETECTORS

Group 4 Securicor Plc


Manor Royal, The Manor, Crawley, West Sussex RH10 9UN UK Tel: +44 (0)20 87707000 Fax: +44 (0)20 87722531 E-mail: allan.rignall@uae.g4s.com Website: www.g4s.com
Certificate No: 548c to EN 54-5: 2000

Heat Detectors
Certificated Products GS104C GS104I Conventional heat detector Class A1R (DZ-03 base) Intelligent rate of rise heat detector Class A1R (DZ-03 base) LPCB Ref. No. 548c/01 548c/02

Bases DZ-03 Standard detector base

Certificate No: 548d to EN54-7: 2000

Smoke Detectors
Certificated Products GS102C GS102I Conventional photoelectric smoke detector (DZ-03 base) Intelligent photoelectric smoke detector (DZ-03 base) LPCB Ref. No. 548d/01 548d/02

Bases DZ-03 Standard detector base

Certificate No: 548k to EN 54-12:2002

Beam Detectors
Certificated Products GS105RI Intelligent optical beam detector Notes: 1) Meets the requirements of EN 54-12 at the following sensitivity settings: Level 1 - 1.61 dB Level 2 - 2.31dB LPCB Ref. No. 548k/01

96

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Gulf Security Technology Co. Ltd (Manufacturing Division of Global System Technology PLC)
No. 80 Changjiang East Road, Economic & Technological Development Zone, Qinhuangdao, Hebei Province 066004, Peoples Republic of China Tel: +86 0335 8502528 Fax: +86 0335 8508942 E-mail: gst@gst.com.cn Website: www.gst.com.cn Sales Enquiries: Tel: +852 28778566 Fax: +852 25118699 Tel: +86 (10)64392919 Fax: +86 (10)64391767

Certificate No: 548c to EN 54-5: 2000

Point Heat Detectors


Certificated Products JTWB-ZCD-G1 (A) JTW-ZCD-G3N Bases: DZ-03 Standard detector base Conventional Class A1R heat detector (DZ-03 base) Intelligent Class A1R Rate of Rise Heat Detector (DZ-03 base) LPCB Ref. No. 548c/01 548c/02

Certificate No: 548d to EN 54-7: 2000

Point Smoke Detector


Certificated Products JTY-GF-GST104 JTY-GD-G3 Bases: DZ-03 standard detector base Conventional Photoelectric Smoke Detector (DZ-03 base) Intelligent Photoelectric Smoke Detector (DZ-03 base) LPCB Ref. No. 548d/01 548d/02

Certificate No: 548k to EN 54-12:2002

Beam Detectors
Certificated Products JTY-HM-GST102 Intelligent optical beam detector Notes: 1) Meets the requirements of EN 54-12 at the following sensitivity settings: Level 1 - 1.61 dB Level 2 - 2.31 dB LPCB Ref. No. 548k/01

HDR
Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260133 Fax: +44 (0)1634 260132 E-mail: info@hochikieurope.com Website: www.hochikieurope.com
Certificate No: 117f to EN54-7: 2000 + A1: 2002 EN54-5: 2000 + A1: 2002 CEA 4021: 1999

January 2009

97

PART 3: SECTION 4.1


COMMERCIAL DETECTORS Multi-Criteria Detectors
Certificated Products 1410010 Analogue addressable multisensor base) Note: Meets EN 54-5 class A1 and B and EN 54-7 at 3.0%/m sensitivity setting in normal and low power mode. LPCB Ref. No. 177f/01

Certificate No: 177g to EN 54 Part 5: 2000

Point Heat Detectors/Sensors


Certificated Products 1215110 1215120 1217180 1217190 1410020 Class A1S conventional fixed temperature heat detector (YCA-RL/3H2M, YBN-R/6SK and 1226150) Class CS conventional fixed temperature heat detector (YCA-RL/3H2M, YBN-R/6SK and 1226150 bases) Class A1R conventional rate of rise temperature heat detector (YCA-RL/3H2M, YBNR/6SK and 1226150 bases) Conventional Class CR rate of rise high temperature heat detector (YBN-R/6SK and 1226150 bases) Analogue addressable Class P heat detector (1426010 and 1226110 bases) Note: Meets requirements of EN54-5: 2000 for classes A1R, A1S, BR, BS, CR and CS when used with ACB-E protocol and classes A1S, BS and CS when used with ATG-E protocol. LPCB Ref. No. 117g/02 117g/03 117g/04 117g/06 117g/09

Bases: 1226150 Standard base 1426010 Standard base YCA-RL/3H2M Addressable base YBN-R/6SK Schottky diode base

Certificate No: 117j to EN 54-12: 2002

Beam Detectors
Certificated Products 1213060 1213080 Optical Beam Smoke Detector Note: Certified at a sensitivity setting of 30% obscuration Conventional 2 wire optical beam smoke detector Notes: 1) Approved at sensitivity setting 25% and 50%. 2) Approved for use with 1213080 2WI interface kit. LPCB Ref. No. 117j/01 117j/03

Certificate No: 164g to EN 54-7:2000

Point Smoke Detectors


Certificated Products 1412040 1212250 Analogue Addressable Photoelectric Smoke Detector (1426010, 1226110 bases) Note: Meets the requirements of EN54-7 in low and high sensitivity settings Conventional Photoelectric Smoke Detector (1226150, YBN-R/6 SK bases) LPCB Ref. No. 164g/05 164g01

Bases: 1226110 Short circuit isolating base 1226150 Standard base 1426010 Standard base YBN-R/6SK Schottky Diode base

98

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Hiltron srl
Via Caserta al Bravo, 218 Napoli 80144, Italy Tel: +39 081 7050912 Fax: +39 081 7050125 E-mail: v.demaggio@hiltron.it Website: www.hiltron.it
Certificate No: 512a to EN 54-7: 2000

Point Smoke Detectors


Certificated Products FRF318 Conventional 2 wire photoelectric smoke detector with remote LED output (P/N854001 base) LPCB Ref. No. 512a/02

Bases: P/N854001 4-wire detector base

Certificate No: 512b to EN 54-5: 2000, EN 54-7: 2000 & CEA 4021: 1999

Multi-criteria Detectors
Certificated Products FRFT318 FRFT318R Conventional 2 wire photoelectric smoke and heat detector with remote LED output (P/N854001 base) Conventional 4 wire photoelectric smoke and heat detector (P/N854001 base) LPCB Ref. No. 512b/02 512b/03

Bases: P/N854001 4-wire detector base

Certificate No: 512d to EN 54-5: 2000

Point Heat Detectors


Certificated Products FRT323 Conventional 2 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector with LED output (P/N854001 base) LPCB Ref. No. 512d/04

Bases: P/N854001 4-wire detector base

January 2009

99

PART 3: SECTION 4.1


COMMERCIAL DETECTORS

Hochiki Europe (UK) Limited


Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260133 Fax: +44 (0)1634 260132 Website: www.hochikieurope.com All Enquires to: Hochiki Europe UK Limited, Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260131 Fax: +44 (0)1634 260132

Manufacturing at: Hochiki Corporation, 141-1 Maehara Ejiri, Kakuda-shi, Miyagi 971-15, Japan Tel: +81 3 3444 4111 Fax: +81 3 3444 4167 E-mail: overseas@hochiki.co.jp Website: www.hochiki.co.jp

Hochiki Europe (UK) Limited Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (01634 260131 Fax: +44 (0)1634 260132 E-mail: sales@hochikieurope.com Website: www.hochikieurope.com

Hochiki America Corporation 7051 Village Drive, Buena Park, California 90621, USA Tel: +1 714 522 2246 Fax: +1 714 522 2268 E-mail: sales@hochiki.com Website: www.hochiki.com

Certificate No: 117h to EN 54-7: 2000 Certificate No: 164g to EN 54-7: 2000 Certificate No: 358c to EN 54-7: 2000

Point Smoke Detectors/Sensors


Certificated Products SLV-E(J) SLR-E3 SLR-E3M SLR-R-IS SLK-EN ALG-E(NP) ALG-E AIE-E AIE-E(NP) Conventional photoelectric smoke detector (YBN-R/4C base) Conventional photoelectric smoke detector (YBN-R/6, YBN-R/6SK bases) Conventional photoelectric smoke detector (YBN-R/6M) Conventional photoelectric smoke detector (YBN-R/4IS base) Conventional photoelectric smoke detector (YBF-RL/4H3, YBF-RL/4H5, YBF-RL/4H5H bases) Analogue addressable photoelectric smoke detector (non polling) (YBN-R/3 & YBOLP R/SCI bases) Note: Meets the requirements of EN54-7 in low and high sensitivity settings LP Analogue addressable photoelectric smoke detector (YBN-R/3, YBO-R/SCI bases) Note: Meets the requirements of EN54-7 in low and high sensitivity settings 1 LP Analogue addressable ionisation smoke sensor (YBN-R/3, & YBO-R/SCI bases ) Note: Meets the requirements of EN-54-7 in low and high sensitivity settings in normal and low power mode Analogue addressable ionisation smoke sensor (non polling) (YBN-R/3 and YBO-R/SCI 1 LP bases ) Note: Meets the requirements of EN-54-7 in low and high sensitivity settings in normal and low power mode
1

LPCB Ref. No. 117h/01 164g/01 164g/01 164g/02 164g/03 164g/04 164g/05 358c/01 358c/02

Certificate No: 117g to EN 54 Part 5: 2000

100

January 2009

SECTION 4.1: PART


Point Heat Detectors/Sensors
Certificated Products DCD-1E-IS/CDX DFJ-AE3 (HFP) DFJ-AE3/CDX DFJ-CE3 DFJ-CE3 (HFP) DCD-AE3 (HFP) DCD-AE3/CDX DCD-AE3M DFG-60BLKJ DCD-CE3(HFP) DCD-CE3/CDX DCD-CE3M ATG-E ATG-E(NP) Class A1 conventional intrinsically safe fixed temperature and rate of rise heat detector 1 (YBN-R/4IS base) Class A1S conventional fixed temperature heat detector (YBN-R/6(HFP) base) Class A1S conventional fixed temperature heat detector (YCA-RL/3H2M, YBN-R/6SK and YBN-R/6 bases) Class CS conventional fixed temperature heat detector (YCA-RL/3H2M, YBN-R/6SK Schottky and YBN-R/6 bases) Class CS conventional fixed temperature heat detector (YBN-R/6(HFP)base) Class A1R conventional rate of rise temperature heat detector (YBN-R/6 (HFP)base) Class A1R conventional rate of rise temperature heat detector (YCA-RL/3H2M, YBNR/6SK and YBN-R/6 bases) Conventional Class A1R rate of rise temperature heat detector (YBN-R/6M base) Class A2 conventional fixed temperature water resistant heat detector Class CR conventional rate of rise high temperature heat detector (YBN-R/6(HFP)base) CDX Class CR conventional rate of rise high temperature heat detector (YCA-RL/3H2M, 1 YBN-R/6SK and YBN-R/6 bases) Conventional Class CR rate of rise high temperature heat detector (YBN-R/6M base) 1 1, LP Analogue addressable heat sensor (YBN-R/3 and YBO-R/SCI bases ) Note: meets the requirements of EN 54-5 at heat classes A1S, BS and CS in normal and low power mode. 1 1 1, LP Analogue addressable heat sensor (YBO-R/3 , YBO-RSCI/NS and YBO-R/SCI bases) Note: meets the requirements of EN 54-5 at heat classes A1S, BS and CS in normal and low power mode. 1 Analogue addressable Class P heat detector (YBN-R/3 and YBO-R/SCI bases) Note: Meets requirements of EN 54-5:2000 for classes A1R, A1S, BR, BS, CR and CS when used with ACB-E protocol and classes A1S, BS and CS when used with ATG-E protocol. 1 1 Weather proof analogue addressable Class P heat detector (YBN-R/3 and YBO-R/SCI bases) Note: Meets requirements of EN 54-5:2000 for classes A1R, A1S, BR, BS, CR and CS when used with ACB-E protocol and classes A1S, BS and CS when used with ATG-E protocol. 1 1 Conventional Class A2R rate of heat detector (YBF-RL/4H3H and YBF-RL/4H5H bases) Conventional Class A2 fixed temperature water resistant heat detector LPCB Ref. No. 117g/01 117g/02 117g/02 117g/03 117g/03 117g/04 117g/04 117g/04 117g/05 117g/06 117g/06 117g/06 117g/07 117g/08

COMMERCIAL DETECTORS

ACB-E

117g/09

ACB-EW

117g/10

DCC-1EL DFG-60BLJ

117g/11 117g/12

Certificate No: 117f to prEN 54: Part 7 Draft A3 (1/4/97), prEN 54: Part 5 Draft F1 (21/7/97) and CEA GEI 1-049 (11/2/97)

Multi-criteria Detectors
Approved Products ACA-E(HFP) ACA-E/ASX Analogue addressable multisensor (YBN-R/3(HFP) base) Meets EN 54-5 class A1 and B and EN 54-7 at 3.0%/m sensitivity setting in normal and low power mode. 1 Analogue addressable multisensor (YBN-R/3 base) Note: Meets EN 54: Part 5 class A1 and B and EN 54: Part 7 at 3.0%/m sensitivity setting in normal and low power mode. LPCB Ref. No. 117f/01 117f/01

Bases: 1 YBN-R/3 base YBN-R/2NA base 1 YBO-R/SCI isolator base 1 YBN-R/4IS intrinsically safe mounting base YCA-RL/3H2 addressable base YCA-RL/5H2 master addressable base AMU-B2 addressable base AMU-MB master addressable base YBC-RL/4H5 base YBF-RL/3J slave base 1 YBF-RL/4H5 base 1 YBK-RL/4H1A base 1 YBK-RL/4H2 base YCA-RL/3H2M addressable base YBN-R/6SK Schottky diode base YBN-R/6 Standard base

January 2009

101

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
YBN-R/4 base YBN-R/6M Standard base 1 YBO-R/5 base 1 YBN-R/4M base 1 YBO-R/5M base YBO-RSCI/NS Negative Switching Short circuit isolating base YBF-RL/4H3H 2 wire mounting base YBF-RL/4H5H 2 wire mounting base
1 LP 1

Bases manufactured buy Hochiki Europe. All other bases manufactured by Hochiki Corporation. denotes detector/base combination is approved in low power mode also.

Certificate No: 164e to BS 5839: Part 5 Certificate No: 164k to EN 54-12: 2002 Certificate No: 117j to EN 54-12: 2002

Beam Detectors
Certificated Products SRA-ET SRA-ET (HFP) SPC-E SPC-ET Optical Beam Smoke Detector Note: Certified at a sensitivity setting of 30% obscuration Optical Beam Smoke Detector Certified at a sensitivity setting of 30% obscuration. Conventional 4 wire optical beam smoke detector Notes: 1) Approved at sensitivity settings 25% and 50%. Conventional 2 wire optical beam smoke detector Notes: 1) Approved at sensitivity setting 25% and 50%. 2) Approved for use with SPC-ET2WI interface kit. Conventional 2 wire optical bem smoke detector. 1) Approved at sensitivity setting 25% and 50% 2) Approved for use with SPC-ET2WI interface kit Optical beam smoke detector Note: 1) Certificated at a sensitivity setting of 25% and when installed as option 2 as specified in DS0203 issue 1.2. Optical beam smoke detector Note: 1) Certificated at sensitivity setting of 25% and with SPB-ET2WI interface kit. Conventional optical beam smoke detector Note: 1) Approved at sensitivity setting 50%. Conventional optical beam smoke detector Notes: 1) Approved at sensitivity setting 50%. 2) Approved for use with SPB-ET2WI interface kit. LPCB Ref. No. 117j/01 117j/01 117j/02 117j/03

SPC-ET(HFP) SPB-E

117j/03 164e/01

SPB-ET SPB-E SPB-ET

164e/01 164k/01 164k/02

Certificate No: 164m to EN54-10:2002

Flame Detectors
Certificated Products IFD-E IFD-E(IS) IFD-E(EXD) Conventional IR Flame detector Note: Meets EN 54-10: 2002 at Class 1 only 3 Conventional IR Intrinsically Safe Flame Detector Note: Meets EN 54-10: 2002 at Class 1 only 3 Conventional IR (Exd) Flameproof Flame Detector Note: Meets EN 54-10: 2002 at Class 1 only
3

LPCB Ref. No. 164m/01 164m/02 164m/03

102

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Honeywell Automation (I) Pvt. Ltd


53, 54, 55 Hadapasar Indl. Estate, Hadapsar, Pune-411013, India Tel: +91 020 66780200 Fax: +91 020 66780172 E-mail: rahul.dwivedi@honeywell.com Website: www.myhoneywell.com
Certificate No: 550b to EN 54-5: 2000, EN 54-7: 2000 & CEA 4021:1999

Multi-criteria Detectors
Certificated Products TC840ME Analogue optical/thermal smoke & heat detector (14506414-007 base) Notes: 1) Meets the requirements of EN 54-7:2000 at sensitivity settings 1 to 5 2) Meets the requirements of EN 54-5:2000 at Class A1R LPCB Ref. No. 550b/03

Bases; 1450614-007 Standard analogue detector base

Certificate No: 550c to EN 54-5: 2000

Point Heat Detectors


Certificated Products TC808E1002M01 TC808E1028M01 Analogue addressable Class A1S fixed temperature heat detector (14506414-007 base) Analogue addressable Class A1R high temperature rate of rise heat detector (14506414007 base) LPCB Ref. No. 550c/04 550c/05

Bases: 14506414-007 Standard analogue detector base

Certificate No: 550a to EN 54-7: 2000

Point Smoke Detectors


Certificated Products TC806E1012M01 Analogue addressable optical smoke detector (14506414-007 base) Notes: 1) Meets EN 54-7 with low, medium and high sensitivity settings LPCB Ref. No. 550a/03

Bases: 14506414-007 standard analogue detector base

Honeywell Control Systems Limited


Lovelace Road, Southern Industrial Estate, Bracknell, Berkshire RG12 8WD UK Tel: +44 (0)1344 655609 Fax: +44 (0)1344 655474 Website: www.honeywell.com
Certificate No: 199t to LPS 1279 - 1.0: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003

Multi-criteria Detectors

Certificate No: 199p to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1 2002 & CEA 4021: 2003

January 2009

103

PART 3: SECTION 4.1


COMMERCIAL DETECTORS Multi-criteria Detectors
Certificated Products TC840MFE Analogue addressable multi-criteria detector incorporating photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: Normal Mode: Alarm Levels 1 to 5 (Multi-criteria): EN54-5 Class A1R, EN54-7, LPS 1279 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Analogue addressable multi-criteria fire detector incorporating CO, photoelectric, thermal and IR sensors (B501, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: Normal Mode: Alarm Levels 1 to 5 (Multi-criteria): EN54-5 Class A1R, EN54-7, LPS 1279 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Nuisance Environment Applications: Application 0, Alarm Level 4 Application 1, Alarm Level 5 Application 2, Alarm Level 4 or 5 Application 3, Alarm Level 5 Application 4, Alarm Level 5 Application 5, Alarm Level 5 Application 6, Alarm Level 5 Bases: B501 standard analogue detector base B501AP intelligent detector base B501DG analogue sensor deep base B524IEFT-1 analogue short circuit isolator base EN54-7, LPS 1279 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-7 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA LPCB Ref. No. 199p/05

TC850E1009

199t/01

4021 4021 4021 4021 4021

Certificate No: 199s to EN 54-12: 2002 & GEI 1-052

Beam Detectors

Certificate No: 199p to EN 54-7: 2000, EN 54-5: 2000 & CEA 4021: 1999 Certificate No: 262s to EN 54-7: 2000

Multi-criteria Detectors
Certificated Products TC840ME Analogue addressable optical/thermal smoke & heat detector (B501, B501DG & B524IEFT bases) Note: Meets the requirements of EN54-5: 2000 at class A1R and EN54-7: 2000 at sensitivity settings 1 to 5 Intelligent thermally enhanced photoelectric smoke detector (SIGI-IBS, SIGA-SB, SIGASB4, SIGA-RB and SIGA-RB4 bases) Note: Meets the requirements of EN54-7-:2000 at sensitivity settings 1.0%/ft, 2%/ft, 2.5%/ft, 3%/ft and 3.5%/ft. Intelligent thermally enhanced photoelectric smoke detector SIGA-SB, SIGA-SB4, SIGARB and SIGA-RB4 bases) Note: Meets the requirements of EN 54-7: 2000 at sensitivity settings 1.0%/ft, 2%/ft, 2.5%/ft, and 3/5%/ft. LPCB Ref. No. 199p/02

XLS-IPHSI

262s/01

XLS-PHSI

262s/02

Bases: SIGI-IBS SIGA-SB SIGA-SB4 SIGA-RB SIGA-RB4 B501 B501DG B524IEFT

Isolator base Standard base Standard base with trim skirt Relay base Relay base analogue detector base analogue deep base analgoue short circuit isolator base

104

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Certificate No: 199n to EN 54-5: 2000 Certificate No: 262u to EN 54-5: 2000

Point Heat Detectors


Certificated Products TC808E 1002M01 TC808E 1028M01 TC808E1051M01 XLS-HFSI XLS-HRSI Class A1S analogue addressable fixed temperature heat detector (B501, B501DG and B524IEFT bases) Class A1R analogue addressable rate of rise heat detector (B501, B501DG and B524IEFT bases) Class BS analogue addressable high temperature heat detector (B501, B501DG and B524IEFT bases) Intelligent class A2S fixed heat detector (SIGI-IBS, SIGA-SB, SIGA-SB4, SIGA-RB and SIGA-RB4 bases) Intelligent class A1 rate of rise heat detector (SIBI-IBS, SIGA-SB, SIGA-SB4, SIGA-RB, and SIGA-RB4 bases) LPCB Ref. No. 199n/03 199n/04 199n/05 262u/01 262u/02

Bases: SIGI-IBS Isolator base SIGA-SB Standard base SIGA-SB4 Standard base with trim skirt SIGA-RB Relay base B501 analogue detector base B501DG analogue deep base B524IEFT analogue short circuit isolator base

Certificate No: 199m to EN 54-7:2000 Certificate No: 262t to EN 54-7: 2000 Certificate No: 118h to EN 54-7: 2000

Point Smoke Detectors/Sensors


Certificated Products TC846A1005 TC806E1012M01 TC806E1012M01 TC807E1011 TC842B1007 XLS-ISI Analogue addressable laser optical detector (B501, B501DG & B524IEFT bases) Note: meets requirements of EN 54 Part 7 at sensitivity settings of 7 to 9 inclusive Analogue addressable optical detector 9B501, B501DG and B524IEFT bases) Note: Meets EN54-7: 2000 with 'low', 'medium' and 'high' sensitivities Analogue addressable optical detector (B501, B501DG and B524IEFT bases) Note: Meets EN54-7: 2000 with 'low', 'medium' and 'high' sensitivities Analogue addressable ionisation smoke detector (B501 and B524IEFT-1 bases) Note: Meets EN54-7: 2000 at High, Normal & Low sensitivity settings Instrinsically safe analogue addressable photelectric smoke detector (501 base) Note: Meets EN54-7: 2000 at High, Normal and Low sensitivity settings Intelligent ionisation smoke detector (SIGI-IBS, SIGA-SB, SIGA-SB4, SIGA-RB and SIGA-RB4 bases) Note: Meets the requirements of EN54-7:2000 at sensitivity settings 1.0%/ft, 2%/ft, 2.5%/ft, 3%/ft and 3.5%/ft Intelligent photoelectric smoke detector (SIGI-IBS, SIGA-SB4, SIGA-RB and SIGA-RB4 bases) Note: Meets the requirements of EN54-7: 2000 at sensitivity settings 10%/ft, 2%/ft, 2/5%/ft, 3%/ft and 3/5%/ft LPCB Ref. No. 118h/01 199m/02 199m/02 199m/06 199m/07 262t/01

XLS-PSI

262t/02

Bases: B501 analogue detector base B501DG analogue deep base B524IEFT analogue short circuit isolator base B524IEFT-1 analogue short circuit isolator base SIGI-IBS Isolator base SIGA-SB Standard Base SIGA-SB4 Standard base with trim skirt SIGA-RB Relay base SIGA-RB4 Relay base with trim skirt

January 2009

105

PART 3: SECTION 4.1


COMMERCIAL DETECTORS

Horing LIH Industrial Co Ltd


No. 17-6, Ai-Chien Road, Hu-Hsi Village, Yuan-Shan Hsiang (264), Ilan Hsien, Taiwan ROC Tel: +886 2 22487599 Fax: +886 2 22407752
Certificate No: 506a to EN 54-7: 2000

Point Smoke Detectors


Certificated Products AHS-871 AH-0311-2 AH-0311-3 AH-0311-4 Bases: AHMB-031 mounting base AHMB-L mounting base Conventional photoelectric smoke detector (AHMB-L mounting base) (2 wire) Conventional photoelectric smoke detector (AHMB-031 Base) (3 wire) Conventional photoelectric smoke detector (AHMB-031 Base) (4 wire) Conventional photoelectric smoke detector (AHMB-031 Base) LPCB Ref. No. 506a/01 506a/02 506a/03 506a/04

Certificate No: 506b to EN 54-7: 2000 & CEA 4021:1999

Multi-criteria Detectors
Certificated Products AH-0315-2 AH-0315-3 AH-0315-4 Bases: AHMB-031 mounting base (2 wire) Optical smoke and class A2 heat detector (AHMB-031 Base) (3 wire) Optical smoke and class A2 heat detector (AHMB-031 Base) (4 wire) Optical smoke and class A2 heat detector (AHMB-031 Base) LPCB Ref. No. 506b/01 506b/02 506b/03

Certificate No: 506c to EN 54-Part 5: 2000

Point Heat Detector


Certificated Products AH-0316-2 AH-0316-3 AH-0316-4 (2 wire) Conventional Class A2 rate of rise and fixed temperature heat detector (AHMB031 Base) (3 wire) Conventional three wire rate of rise and fixed temperature heat detector (AHMB031 Base) (4 wire) Conventional four wire rate of rise and fixed temperature heat detector (AHMB031 Base) LPCB Ref. No. 506c/01 506c/02 506c/03

Bases: AHMB-031 mounting base

ICAM Limited
Spring Gardens, London Road, Washington, West Sussex RH20 3BS UK Tel: +44 (0)1903 892222 Fax: +44 (0)1903 892277 Website: www.icam.ltd.uk
Certificate No: 451a to CEA 4022: 1999-1

Smoke Detectors
Certificated Products FireTracer 1 Aspirating smoke detector with display LPCB Ref. No. 451a/01

106

January 2009

SECTION 4.1: PART


Certificated Products Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. Aspirating smoke detector without display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) This detector must be fitted with the beacon assembly option. 4) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. Aspirating smoke detector with display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. Aspirating smoke detector without display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) This detector must be fitted with the beacon assembly option. 4) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. Aspirating smoke detector with display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with LPCB Ref. No.

COMMERCIAL DETECTORS

FireTracer 1

451a/01

FireTracer 4

451a/02

FireTracer 4

451a/02

FireTracer 6

451a/03

January 2009

107

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products FireTracer 6 the manufacturer's installation manual. Aspirating smoke detector without display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) This detector must be fitted with the beacon assembly option. 4) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. Aspirating smoke detector with display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. Aspirating smoke detector without display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) This detector must be fitted with the beacon assembly option. 4) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. Aspirating smoke detector with display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) Approval of the device is conditional upon the following requirements: The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. Aspirating smoke detector without display Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire Sensitivity (Room Protection) 2) The detector also approved for use with the following options: 4 Channel relay module (E606-01) Beacon assembly (E610) Mains PSU E-Series 110V AC (EP01) Mains PSU E-Series 230V AC (EP02) 3) This detector must be fitted with the beacon assembly option. 4) Approval of the device is conditional upon the following requirements: LPCB Ref. No. 451a/03

FireTracer 8

451a/04

FireTracer 8

451a/04

FireTracer 15

451a/05

FireTracer 15

451a/05

108

January 2009

SECTION 4.1: PART


Certificated Products The detector shall be supplied with power from a power supply complying with the requirements of EN 54-4. Design, installation and commissioning shall be performed in accordance with the manufacturer's installation manual. LPCB Ref. No.

COMMERCIAL DETECTORS

Johnson Controls
Johnson Controls Holding Italia Srl., Via Manzoni,, 44, 20095 Cusano, Milan, Italy Tel: +39 (0)2 280421 Fax: +44 (0)1283 220690 E-mail: sergio.bellano@jci.com Website: www.johnsoncontrols.com
Certificate No: 199t to LPS1279 - 1.0: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003

Multi-Criteria Detectors
Certificated Products 2251TEMJ Analogue addressable optical/thermal smoke and heat detector (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Meets the requirements of EN 54-5: 2000 at class A1R and EN 54-7: 2000 at sensitivity settings 1 to 5 Analogue addressable mult-criteria fire detector incorporating CO, photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: Normal Mode: Alarm Levels 1 to 5 (Multi-criteria) EN54-5 Class A1R, EN54-7, LPS1279 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Nuisance Environment Applications: Application 0, Alarm Level 4 Application 1, Alarm Level 5 Application 2, Alarm Level 4 or 5 Application 3, Alarm Level 5 Application 4, Alarm Level 5 Application 5, Alarm Level 5 Application 6, Alarm Level 5 Bases: B501standard analogue detector base B501AP intelligent detector base B501DG analogue detector deep base B524IEFT-1 analogue short circuit isolator base EN54-7, LPS1279 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-7 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA LPCB Ref. No. 199p/02

2251CTLEJ

199t/01

4021 4021 4021 4021 4021

Beam detectors

Certificate No: 118h to EN 54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products 7251J 2251EMJ 2251EISJ Analogue addressable photoelectric laser smoke detector (B501, B501AP, B501DG, B524IEFT, B524IEFT-1 bases) Note: meets requirements of EN 54-7 at sensitivities 7 to 9 inclusive Analogue optical smoke detector (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Meets EN 54-7 with 'low', 'medium' and 'high' sensitivity settings Intrinsically safe analogue addressable photoelectric smoke detector (B501, B501AP base) Note: Meets EN 54-7: 2000 at High, Normal & Low sensitivity settings LPCB Ref. No. 118h/01 199m/02 199m/07

Bases: B501 standard analogue detector base

January 2009

109

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
B501AP intelligent detector base B501DG analogue detector deep base B524IEFT-1 analogue detector isolator base

Certificate No: 199n to EN 54-5: 2000 + A1: 2002

Point Heat Detectors


Certificated Products 5251EMJ 5251REMJ 5251HTEMJ Class A1S analogue addressable fixed temperature heat detector (B501, B501AP, B501DG and B524IEFT-1 bases) Class A1R analogue addressable high temp rate of rise heat detector (B501, B501AP, B501DG and B524IEFT-1 bases) Class BS analogue addressable high temperature heat detector (B501, B501AP, B501DG and B524IEFT-1 bases) LPCB Ref. No. 199n/03 199n/04 199n/05

Bases: B501 standard analogue detector base B501AP intelligent detector base B501DG analogue detector deep base B524IEFT-1 short circuit isolator base

Kidde Products Limited


Unit 2 Admiral Point, Dawdon Enterprise Park, Seaham, County Durham SR7 PP UK Tel: +44 (0)191 513 6100 Fax: +44 (0)191 513 6102 Website: www.kiddeproducts.com
Certificate No: 054e to CEA 4022: 1999-12 (en) Certificated Products HART XL High sensitivity smoke detector (HSSD) Approved configurations: Detection unit / integral LED display or LCD display Detection unit / integral LED display / remote LCD display LPCB Ref. No. 054e/01

Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (room protection). 2) The detector has been assessed with PVC (P10.0250) and ABS (B000931) sampling pipes. 3) The approval of the detector is conditional upon the following requirements: -The detector shall be supplied with power from a power supply complying with the requirements of BS EN 54-4. -Design, Installation and commissioning shall be performed in accordance with Kidde Fire Protection Limited Installation, operation & maintenance manual (TM0042) with per hole sensitivities of better than 5%/m, as predicted by the SNIFF Version 3.0 design tool.

Labor Strauss Sicherungsanlagenbau GmbH


Wiegelestrasse 36, A-1230 Vienna, Austria Tel: +43 1 52114-0 Fax: +43 1 52114-27 E-mail: andreas.schumacher@lst.at Website: www.lst.at
Certificate No: 603a to EN 54-7: 2000

Smoke Detectors
Certificated Products FC600/O Conventional photoelectric smoke detector (FC600/BR1000 Resistor mounting base) LPCB Ref. No. 603a/01

110

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Bases; FC600/BR1000 Resistor mounting base

Certificate No: 603b to EN 54-5: 2001

Point Heat Detector


Certificated Products FC600/TMAX/78 FC600/TDIFF/57 Conventional Class BS fixed temperature heat detector FC600/BR1000 Resistor mounting base) Conventional Class A1R rate of rise heat detector (FC600/BR1000 Resistor mounting base) LPCB Ref. No. 603b/01 603b/02

Bases: FC600/BR1000 Resistor mounting base

Lichfield Fire & Safety Equipment Co. Ltd


2nd Floor, Suite 4, Saturn Centre, Spring Lane, Ettingshall, Wolverhampton WV4 6JX UK Tel: +44 (0)8700 664401 Fax: +44 (0)8700 664402 E-mail: info@lifeco-uk.com Website: lifeco-uk.com
Certificate No: 506c to EN 54-5: 2000

Point Heat Detectors


Certificated Products LFHD60 (2 wire) Conventional Class A2 rate of rise and fixed temperature heat detector (AHMB031 base) LPCB Ref. No. 506c/01

Bases: AHMB-031 mounting base

Certificate No: 506a to EN 54-7: 2000

Photoelectric Smoke Detectors


Certificated Products LF-PE-4100 Bases: AHMB-L mounting base LF-PE-4100 Conventional photoelectric smoke detector (AHMB-L base) LPCB Ref. No. 506a/01

Matrix FZC
PO Box 10559, Ras al Kaymah, UAE Tel: +971 7 2077846 Fax: +971 7 2041010
Certificate No: 603b to EN54-5: 2000 + A1:2002

Point Heat Detectors


Certificated Products MAT/HH/01 MAT/RH/01 Conventional Class BS fixed temperature heat detector (MAT/DB-UK/01 base) Conventional class A1R rate-or-rise heat detector (MAT/DB-UK/01 base) LPCB Ref. No. 603b/01 603b/02

January 2009

111

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Bases: MAT/DB-UK/01 Diode base

Certificate No: 603a to EN 54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products MAT/OS/01 Bases: MAT/DB-UK/01 Diode base Conventional photoelectric smoke detector (MAT/DB-UK/01 base) LPCB Ref. No. 603a/01

Morley-IAS Fire Systems By Honeywell


Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@morleyias.co.uk Website: www.morley-ias.co.uk
Certificate No: 199n to EN 54-5: 2000

Point Heat Detectors


Certificated Products MI-FHSE MI-RHSE MI-HTSE HRZ-1005T HRZ-1004T HRZ-1005 Class A1S analogue addressable fixed temperature heat detector (B501, B501DG and B524IEFT bases) Class AIR analogue addressable rate of rise heat detector (B501, B501DG and B524IEFT bases) Class BS analogue addressable high temperature heat detector (B501, B501DG and B524IEFT bases) Class A2S conventional fixed temperature heat detector (HRZ-1000BSD base) Class BS conventional fixed temperature heat detector (HRZ-1000BSD base) Conventional rate of rise heat detector (HRZ-1000BSD base) LPCB Ref. No. 199n/03 199n/04 199n/05 199n/10 199n/11 199n/12

Bases: B501 standard analogue detector base B501DG analogue deep base B524IEFT analogue short circuit isolator base HRZ-1000BSD standard base with Schottky diode

Certificate No: 199p to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003

Multi-criteria Detectors
Certificated Products MI-PTSE Analogue addressable optical/thermal smoke & heat detector (B501, B501DG & B524IEFT bases) Meets the requirements of EN54-5: 2000 at class A1R and EN54-7: 2000 at sensitivity settings 1 to 5 Conventional photo thermal detector (HRZ-1000BSD base) Analogue addressable multi-criteria detector incorporating photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Certified at the following settings:Normal mode: Alarm Levels 1 to 5 (Multi-criteria): EN54-5 Class A1R, EN54-7 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R LPCB Ref. No. 199p/02

HRZ-1002 MI-PTIR

199p/04 199p/05

112

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Bases: B501 standard analogue detector base B501AP intelligent detector base B501DG analogue sensor deep base B524IEFT analogue short circuit isolator base HRZ-1000BSD standard base with Schottky diode

Certificate No: 199m & 118h to EN 54-7: 2000

Point Smoke Detectors


Certificated Products MI-LZR MI-PSE HRZ-1003 MI-ISE Analogue addressable photoelectric laser smoke detector (B501, B501DG and B524IEFT bases) Meets the requirements of EN 54-7 at sensitivity settings of 7 to 9 inclusive.Analogue optical detector (B501, B501DG and B524IEFT bases) Meets EN 54-7: 2000 with 'low', 'medium' and 'high' sensitivities Conventional photoelectric detector (HRZ-1000BSD base) Analogue addressable ionisation smoke detector (B501 & B524IEFT-1 bases) Note: Meets EN54-7: 2000 at High, Normal & Low sensitivity settings LPCB Ref. No. 118h/01 199m/02 199m/05 199m/06

Bases: B501 analogue detector base B501DG analogue deep base B524IEFT analogue short circuit isolator base HRZ-1000BSD standard base with Schottky diode

Morley-IAS Fire Systems By Honeywell


Honeywell Fire Systems, BSEL Tech Park, Floor 6,Sector 30A, Opposite Vshi Station, Vashi, New Mumbai, India Tel: +91 022 67122427 Fax: +91 022 67122422 E-mail: rk.raman@honeywell.com Website: www.myhoneywell.com
Certificate No: 550b to EN 54-5: 2000, EN 54-7: 2000 & CEA 4021:1999

Multi-criteria Detectors
Certificated Products MI-PTSE Analogue optical/thermal smoke & heat detector (MI-B501 base) Notes: 1) Meets the requirements of EN 54-7:2000 at sensitivity settings 1 to 5 2) Meets the requirements of EN 54-5:2000 at Class A1R LPCB Ref. No. 550b/03

Bases: MI-B501 Standard analogue detector base

Certificate No: 550c to EN 54-5: 2000 + A1: 2002

Point Heat Detectors


Certificated Products MI-FHSE MI-RHSE Analogue addressable Class A1S fixed temperature heat detector (MI-B501 base) Analogue addressable Class A1R high temperature rate of rise heat detector (MI-B501 base) LPCB Ref. No. 550c/04 550c/05

Bases: MI-B501 Standard analogue detector base

January 2009

113

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificate No: 550a to EN 54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products MI-PSE Analogue addressable optical smoke detector (MI-B501 base) Note: Meets EN 54-7 with low, medium and high sensitivity settings LPCB Ref. No. 550a/03

Bases MI-B501 standard analogue detector base

Multron Systems Pte Ltd


115 Kallang Way 2, Singapore 349 144, Singapore Tel: +65 6743 2555 Fax: +65 6743 2777 E-mail: info@multron.com Website: www.multron.com
Certificate No: 548c to EN 54-5:2000 Certificated Products DET-C103 Bases: DZ-03 Standard detector base Conventional Class A1R heat detector (DZ-03 base) LPCB Ref. No. 548c/01

Certificate No: 548d to EN 54-7:2000 Certificated Products DET-C102 Bases: DZ-03 Standard detector base Conventional photoelectric smoke detector base) LPCB Ref. No. 548d/01

Napco Gulf Security Group


P.O. Box 54533, Dubai Airport Free Zone, UAE Tel: +971 4 2997703 Fax: +971 4 2997704 E-mail: info@napcogulfsecurity.com Website: www.napcogulfsecurity.com
Certificate No: 548c to EN 54-5: 2000

Heat Detectors
Certificated Products NC-103 NI-103 Conventional heat detector Class A1R (DZ-03 base) Intelligent Rate of Rise Heat Detector Class A1R (DZ-03 base) LPCB Ref. No. 548c/01 548c/02

Bases: DZ-03 Standard detector base

114

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Certificate No: 548d to EN54-7:2000

Smoke Detectors
Certificated Products NC-102 NI-102 Conventional Photoelectric Smoke Detector (DZ-03 base) Intelligent Photoelectric Smoke Detector (DZ-03 base) LPCB Ref. No. 548d/01 548d/02

Bases: DZ-03 Standard detector base

Certificate No: 548k to EN 54-12:2002

Beam Detectors
Certificated Products NI-105/R Intelligent optical beam detector Notes: 1) Meets the requirements of EN 54-12 at the following sensitivity settings: Level 1 - 1.61 dB Level 2 - 2.31 dB LPCB Ref. No. 548k/01

Nitin Ventures FZE


P.O. Box 262294, Jabel Ali Free Zone, Dubai, UAE Tel: +97 148865858/859 Fax: +97 148865800 E-mail: sales@nitinventures.com Website: www.nitinventures.com
Certificate No: 010h to EN 54-7: 2000 + A1: 2002, EN 54-5: 2000 + A1: 2002, CEA 4021: 2003

Multi-Criteria Detectors
Certificated Products NV-I-MS Analogue addressable multisensor detector (NV-IA-SB mounting base) Notes: 1) Certificated at the following settings: Mode 1 - High sensitivity smoke detector with standard heat enhancement Mode 2 - Smoke detection only Mode 3 - Medium sensitivity smoke detector with standard heat enhancement Mode 4 - Low sensitivity smoke detector with high heat enhancement Mode 5 - Class A1 heat detector Also approved in conventional alarm modes 1, 2, 3, 4 and 5. LPCB Ref. No. 010h/01

Bases: NV-IA-SB Mounting Base

Certificate No: 010p to EN 54-5: 2000 +A1: 2002

Point Heat Detectors


Certificated Products NV-I-H Analogue addressable heat detector (NV-IA-SB mounting base) Notes: 1) Meets the requirements of EN54: Part 5 Class A1R in mode 1 and in conventional mode Class A2 in mode 2 and in conventional mode Class A2S in mode 3 and in conventional mode Class CR in mode 4 and in conventional mode LPCB Ref. No. 010p/03

January 2009

115

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products NV-C-H-A1R Class CS in mode 5 and in conventional mode. Conventional class A1R heat detector - flashing LED (NV-C-SB mounting base) Notes: 1) Meets the requirements of EN54: Part 5 - Class A1R LPCB Ref. No. 010p/05

Bases: NV-IA-SB mounting base NV-C-SB mounting base

Certificate No: 010q to EN 54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products NV-I-I NV-I-O NV-C-I NV-C-O Bases: NV-IA-SB mounting base NV-C-SB mounting base Analogue addressable ionisation smoke detector (NV-IA-SB mounting base) Notes: 1) Meets the requirements of EN54-7: 2000 in modes 1,2,3,4 and 5 in conventional mode Analogue addressable optical smoke detector (NV-IA-SB mounting base) Notes: 1) Meets the requirements of EN54-7:2000 in modes 1,2,3 4 and 5 in conventional mode Conventional ionisation smoke detector - flashing LED (NV-C-SB mounting base) Conventional optical smoke detector- flashing LED (NV-C-SB mounting base) LPCB Ref. No. 010q/02 010q/03 010q/05 010q/11

Nittan (UK) Limited


Hipley Street, Old Woking, Surrey GU22 9LQ UK Tel: +44 (0)1483 769555/8 Fax: +44 (0)1483 756686 E-mail: sales@nittan.co.uk Website: www.nittan.co.uk
Certificate No: 041f to EN54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products EV-P EV-DP EVC-P Analogue addressable optical smoke detector (STB-4EV and STB-4SE-EV bases) Note: Meets the requirements of EN 54-7 at 'Lowest' and 'Highest' sensitivity settings only. Analogue addressable double optical smoke detector (STB-4EV and STB-4SE-EV bases) Note: Meets the requirements of EN 54-7 at 'Highest' sensitivity setting only. Conventional optical smoke detector (STB-4, STB-4-SE, STB-4-SE24VR bases) LPCB Ref. No. 041f/01 041f/02 041f/03

Bases; STB - 4EV Mounting base STB - 4SE-EV Mounting base STB - 4 - SE Deep base STB - 4 - SE24VR - Relay base STB - 4 Standard Base

Certificate No: 041h to EN 54-5: 2000 + A1: 2002

Point Heat Detectors


Certificated Products EV-H-A1R EV-H-CS Analogue addressable class A1R heat detector (STB-4EV and STB-4SE-EV bases) Analogue addressable class CS heat detector (STB-4EV and STB-4SE-EV bases) LPCB Ref. No. 041h/01 041h/02

116

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Bases: STB-4EV mounting base STB-4SE-EV mounting base

Certificate No: 041g to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1:2002 and CEA4021: 1999

Multi-criteria Detectors
Certificated Products EV-PH Analogue addressable optical smoke/class A1R heat detector (STB-4EV and STB-4SEEV bases) Note: Meets the requirements of EN 54-7 at 'Lowest' and 'Highest' sensitivity settings. LPCB Ref. No. 041g/01

Bases: STB-4EV mounting base STB-4SE-EV mounting base

Notifier By Honeywell
Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@notifiersystems.co.uk Website: www.notifierfiresystems.co.uk
Certificate No: 199m to EN 54-7: 2000 + A1: 2002 Certificate No: 118h to EN 54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products FSL-751E SDX-751EM SD-851E CPX-751E IDX-751 Analogue addressable photoelectric laser smoke detector (B501, B501DG & B5241EFT bases) Note: meets the requirements of EN 54:Part 7 at sensitivity settings of 7 to 9 inclusive. Analogue optical smoke detector smoke detector (B501, B501DG and B5241EFT bases) Note: Meets EN54-7 with 'low', 'medium' and 'high' sensitivity settings Conventional photoelectric smoke detector (B401 base) Analogue addressable ionisation smoke detector (B501 & B524IEFT-1 bases) Note: Meets EN54-7: 2000 at High, Normal & Low sensitivity settings Intrinsically safe analogue addressable photoelectric smoke detector (B501 base) Note: Meets EN54-7: 2000 at High, Normal & Low sensitivity settings LPCB Ref. No. 118h/01 199m/02 199m/03 199m/06 199m/07

Bases: B501 base B401 base B501DG deep base B5241EFT short circuit isolator base

Certificate No: 199n to EN 54-5: 2000 + A1:2002

Point Heat Detectors


Certificated Products FDX-551EM FDX-551REM FDX-551HTEM FD-851RE Class A1S analogue addressable fixed temperature heat detector (B501, B501DG and B5241EFT bases) Class A1R analogue addressable high temp rate of rise heat detector (B501, B501DG and B5241EFT bases) Class BS analogue addressable high temperature heat detector (B501, B501DG and B5241EFT bases) Conventional Class A1R rate of rise heat detector (B401 base) LPCB Ref. No. 199n/03 199n/04 199n/05 199n/07

January 2009

117

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products FD-851HTE FD-851TE Conventional Class BS heat detector (B401 base) Conventional class A2S fixed temperature heat detector (B401, B401R, B401RSD, B401SD, B401DG bases) LPCB Ref. No. 199n/08 199n/14

Bases: B501 base B401 base B401R standard base with resistor B401RSD standard base with resistor and schottky diode B401SD standard base with schottky diode B401DG deep base

Certificate No: 199p to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003 Certificate No: 199t to LPS 1279 - 1.0: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003

Multi-criteria Detectors
Certificated Products SDX-751TEM SD-851TE IRX-751TEM Analogue addressable optical/thermal smoke & heat detector (B501, B501DG and B5241EFT bases) Conventional photoelectric/thermal detector (B401 base) Note: Meets the requirements of EN54-7: 2000 at "High", 'Medium' and 'Low' sensitivity settings Analogue addressable multi-criteria detector incorporating photoelectric, thermal and IR sensors (B501, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: Normal Mode: Alarm Levels 1 to 5 (Multi-criteria): EN54-5 Class A1R, EN54-7 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Analogue addressable multi-criteria fire detector incorporating CO, photoelectric, thermal and IR sensors (B501, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: Normal Mode: Alarm Levels 1 to 5 (Multi-criteria): EN54-5 Class A1R, EN54-7, LPS1279 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Nuisance Environment Applications: Application 0, Alarm Level 4 Application 1, Alarm Level 5 Application 2, Alarm Level 4 or 5 Application 3, Alarm Level 5 Application 4, Alarm Level 5 Application 5, Alarm Level 5 Application 6, Alarm Level 5 Bases: B501 base B401 base B501DG deep base B524IEFT-1 analogue short circuit isolator base EN54-7, LPS1279 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-7 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA LPCB Ref. No. 199p/02 199p/03 199p/05

IRX-751CTEM

199t/01

4021 4021 4021 4021 4021

Notifier Fire Systems India


Honeywell Fire Systems, BSEL Tech Park, Floor 6, 603, Sector 30A, opposite Vashi Station, Vashi, New Mumbia, India Tel: +91 022 67122427 Fax: +91 02267122422 E-mail: rk.raman@honeywell.com Website: www.myhoneywell.com
Certificate No: 550b to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021:1999

118

January 2009

SECTION 4.1: PART


Multi-criteria Detectors
Certificated Products SDX-751TEM Analogue optical/thermal smoke & heat detector (B501, B501DG and B5241EFT-1 bases) Notes: 1) Meets the requirements of EN 54-7:2000 at sensitivity settings 1 to 5 2) Meets the requirements of EN 54-5:2000 at Class A1R LPCB Ref. No. 550b/03

COMMERCIAL DETECTORS

Bases: B501 Standard base B501DG Deep analogue detector base B5242EFT-1 Short circuit islolator base

Certificate No: 550c to EN 54-5: 2000 + A1: 2002

Point Heat Detectors


Certificated Products FDX-551EM FDX-551REM Analogue addressable Class A1S fixed temperature heat detector (B501, B501DG and B5241EFT-1 bases) Analogue addressable Class A1R high temperature rate of rise heat detector (B501, B501DG and B5241EFT-1 bases) LPCB Ref. No. 550c/04 550c/05

B501 Standard base B501DG Deep analogue detector base B542IEFT-1 Short circuit islolator base

Certificate No: 550a to EN 54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products SDX-751EM Analogue addressable optical smoke detector (B501, B501DG and B5241EFT-1 bases) Notes: 1) Meets EN 54-7 with low, medium and high sensitivity settings LPCB Ref. No. 550a/03

Bases: B501 standard analogue detector base B501DG deep analogue detector base B5241EFT-1 analogue short circuit isolator base

Novar GmbH
Security and Building Management Systems, Dieseltrasse 2, D-41469, Neuss, Germany Tel: +49 (0)2137 170 Fax: +49 (0)2137 17286 E-mail: info@esser-systems.de Website: www.esser-systems.de
Certificate No: 400m to EN 54-7: 2000 & pr EN 54-17 Draft (July 2002) Certificate No: 400j to EN 54-7:2000

Point Smoke Detectors


Certificated Products I-1071 O-1371 O-803371 O-802371 Analogue addressable ionization smoke detector (781590, 781591, 781592 and 801593 bases) Analogue addressable optical smoke detector (781590, 781591, 781592 and 801593) Analogue addressable optical smoke detector (805590 and 805591 bases) Analogue addressable optical smoke detector with integral short circuit isolator function (805590 and 805591 bases) LPCB Ref. No. 400j/01 400j/02 400j/03 400m/01

January 2009

119

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Bases: 781591 detector base with relay output 781590 standard base 781592 detector base with open collector output 805590 base for series IQ8quad detectors 805591 base for serial IQ8 quad detector with relay output 801593 detector base with isolator

Certificate No: 400h to EN 54-5: 2000 Certificate No: 400k to EN 54-5: 2000 & pr EN 54-17 Draft (July 2002)

Point Heat Detectors


Certificated Products TM-803171 TD-803271 TM-802171 TM-802271 Analogue addressable Class A1S heat detector (805590 and 805591 base) Analogue addressable Class A1 heat detector (805590 and 805591 base) Analogue addressable Class A1S heat detector with integral short circuit isolator function (805590 and 805591 bases) Analogue addressable Class A1 heat detector with integral short circuit isolator function (805590 and 805591 bases) LPCB Ref. No. 400h/03 400h/04 400k/01 400k/02

Bases: 781590 standard base 781592 detector base with open collector output 805590 base for series IQ8quad detectors 805591 base for series IQ8quad detectors with relay output

Certificate No: 400g to EN 54-7: 2000 + A1:2002, EN 54-5: 2000 + A1:2002 & CEA4021: 1999 Certificate No: 400n to EN 54-5: 2000, EN 54-7: 2000, pr EN 54-17 Draft (July 2002) & CEA 4021: 1999

Multi-criteria Detectors
Certificated Products OTI-1973 OT-1373 O2T-1374 O2T-803374 O2T-802374 Analogue addressable optical, heat & ionisation multi-sensor detector (781590, 781591 and 781592 bases). Note:Meets EN 54-5: 2000 at class A2S. Analogue addressable optical heat multi-sensor detector (781590, 781591 and 781592 bases) Note:Meets EN 54-5:2000 at class A2S Analogue addressable optical heat multi-sensor detector (781590, 781591 and 781592 bases) Note:Meets EN 54-5:2000 at class A2S. Analogue addressable smoke & heat detector (805590 and 805591 bases) Note:Meets EN 54-5:2000 at class A2S. Analogue addressable smoke & heat detector (805590 and 805591 bases) Note: Meets EN 54-5: 2000 at Class B LPCB Ref. No. 400g/01 400g/02 400g/03 400g/04 400n/01

Bases: 781591 detector base with relay output 805590 base for series IQ8quad detectors 805591 base for series IQ8quad detectors with relay output

OY ESMI AB
Kalkkipellontie 6, PO Box 415, Fl-02601, Espoo, Finland Tel: +358 10 446 511 Fax: +358 10 446 5103 E-mail: Jari.Ollila@esmi.com Website: www.esmi.com
Certificate No: 199p to EN54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003 Certificate No: 199t to LPS 1279 - 1.0: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003

120

January 2009

SECTION 4.1: PART


Multi-Criteria Detectors
Certificated Products ESMI2251TLE Analogue addressable multi-criteria detector incorporating photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Certified at the following settings:Normal Mode: Alarm Levels 1 to 5 (Mult-criteria): EN54-5 Class A1R, EN54-7 AND CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Analogue addressable multi-criteria fire detector and incorporating CO, photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: Normal Mode: Alarm Levels 1 to 5 (Multi-criteria) EN54-5 Class A1R, EN54-7, LPS1279 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Nuisance Environment Applications: Application 0, Alarm Level 4 Application 1, Alarm Level 5 Application 2, Alarm Level 4 or 5 Application 3, Alarm Level 5 Application 4, Alarm Level 5 Application 5, Alarm Level 5 Application 6, Alarm Level 5 Bases: B501 standard analogue detector base B501AP intelligent detector base B501DG analogue sensor deep base B524IEFT-1 analogue short circuit isolator base EN54-7, LPS1279 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-7 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA LPCB Ref. No. 199p/05

COMMERCIAL DETECTORS

ESMI2251CTLE

199t/01

4021 4021 4021 4021 4021

Photain Controls
8 New Market Court, Chippenham Drive, Kingston, Milton Keynes BN18 0BE UK Tel: 01908 281981 Fax: 01908 282554 E-mail: john.davies@ge.com
Certificate No: 092p to EN 54-5: 2000

Heat Detectors
Certificated Products PHDP2004 PRRP2004 PHDP2004HT Conventional Class A1heat detector (FSBP 2000 base) Conventional Class A1R heat detector (FSBP 2000 base) Conventional Class B heat detector (FSBP 2000 base) LPCB Ref. No. 092p/02 092p/03 092p/04

Base: FSBP2000 Conventional surface base

Certificate No: 092n to EN 54-7: 2000

Smoke Detectors
Certificated Products ISDP2004 PPDP2004 Conventional ionisation smoke detector (FSBP2000 base) Conventional photoelectric smoke detector (FSBP2000 base) LPCB Ref. No. 092n/03 092n/04

Base: FSBP2000 Conventional surface base

January 2009

121

PART 3: SECTION 4.1


COMMERCIAL DETECTORS

Pittway Tecnologica Srl.


Via Caboto 19/3, 34147 Trieste, Italy Tel: +39 040 94 90111 Fax: +39 040 38 2137 E-mail: sandro_bonin@systemsensor.com Website: www.systemsensoreurope.com
Certificate No: 199m to EN 54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products ECO1003 2251EM 2351E Conventional photoelectric smoke detector (ECO1000DB, ECO1000DBR and ECO1000DBRSD) Analogue optical smoke detector (B501, B501AP, B501DG and B5241EFT bases) Note: Meets EN54-7 with 'low', 'medium' and 'high' sensitivity settings Conventional photoelectric smoke detector (B401, B40DG, B401R, B401SD and B401RSD bases) Note: Meets the requirements of EN54-7:2000 at 'low', 'medium' and 'high' sensitivity settings Conventional photoelectric detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) Analogue addressable ionisation smoke detector (B501, B501AP, & B524IEFT-1 bases) Note: Meets EN54-7: 2000 at High, Normal & Low sensitivity settings Intrinsically safe analogue addressable photoelectric smoke detector (B501, B501AP bases) Note: Meets EN54-7: 2000 at High, Normal & Low sensitivity settings. Intrinsically safe conventional ionisation smoke detector (B401 base) Conventional photoelectric smoke detector (B401, B401R and B401SD bases) LPCB Ref. No. 199m/01 199m/02 199m/03

Vision 2020P 125IE 2251EIS 1151EIS 2151E

199m/05 199m/06 199m/07 199m/08 199m/09

Bases: 2020B standard base 2020DB deep base 2020BSD standard base with schottky diode 2020DBSD deep base with schottky diode B401 standard base B401DG deep base B401R standard base with 470 ohm resistor B401SD standard base with schottky diode B401RSD standard base with 470 ohm resistor and schottky diode B501 standard analogue detector base B501AP intelligent detector base B501DG analogue sensor deep base B524IEFT analogue sensor isolator base B524IEFT-1 analogue short circuit isolator base ECO1000B standard base. ECO1000BSD standard base with schottky diode. ECO1000BR standard base, 470 ohm resistor. ECO1000BRSD standard base, 470 ohm resistor and schottky diode. ECO1000BR680 standard base, 680 ohm resistor. ECO1000BR680SD standard base, 680 ohm resistor and schottky diode. ECO1000BR1000 standard base, 1000 ohm resistor. ECO1000BR1000SD standard base, 1000 ohm resistor and schottky diode. ECO1000DB deep base ECO1000DBR deep base with 470 ohm resistor ECO1000DBRSD deep base with 470 ohm resistor and schottky diode ECO2000B mounting base.

Certificate No: 199n to EN 54-5: 2000 + A1: 2002

Point Heat Detectors


Certificated Products ECO1005 5251EM Class A1R conventional thermal detector (ECO1000B, ECO1000BSD, ECO1000BR, ECO1000BRSD, ECO1000BR680, ECO1000BR680SD, ECO1000BR1000, ECO1000BR1000SD, ECO1000DB, ECO1000DBR and ECO1000DBRSD bases) Class A1S analogue addressable fixed temperature heat detector (B501, B501AP, B501DG and B5241EFT bases) LPCB Ref. No. 199n/01 199n/03

122

January 2009

SECTION 4.1: PART


Certificated Products 5251REM 5251HTEM ECO1005T Class A1R analogue addressable high temp rate of rise heat detector B501AP, B501DG and B5241EFT bases) Class BS analogue addressable high temperature heat detector B501AP, B501DG and B5241EFT bases) Class A2S conventional fixed temperature heat detector (ECO1000B, ECO1000BSD, ECO1000BR, ECO1000BRSD, ECO1000BR680, ECO1000BR680SD, ECO1000BR1000, ECO1000BR1000SD, ECO1000DB, ECO1000DBR and ECO1000DBRSD bases) Class A1R conventional rate of rise heat detector (B401, B401DG, B401R, B401SD, & B401RSD bases) Class BS conventional heat detector (B401, B401 DG, B401R, B401SD, & B401RSD bases) Class BS conventional high temperature heat detector (ECO1000DB, ECO1000DBR, ECO1000DBRSD, ECO1000B, ECO1000BSD, ECO1000BR, ECO1000BRSD, ECO1000BR680, ECO1000BR680SD, ECO1000BR1000 & ECO1000BR1000SD bases) Class A2S conventional fixed temperature heat detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) Class BS conventional fixed temperature heat detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) Conventional rate of rise heat detector (2020B, 2020DB, 2020BSD, 2020DBSD bases) Intrinsically safe conventional A1R heat detector (B401 base) Conventional class A2S fixed temperature heat detector (B401, B401R, B401RSD, B401SD, B401DG bases) LPCB Ref. No. 199n/04 199n/05 199n/06

COMMERCIAL DETECTORS

5351E 4351E ECO1004T Vision 2020F Vision 2020HF Vision 2020R 5451EIS 5351TE

199n/07 199n/08 199n/09 199n/10 199n/11 199n/12 199n/13 199n/14

Bases: 2020B standard base 2020DB deep base 2020BSD standard base with schottky diode 2020DBSD deep base with schottky diode B401 standard base B401DG deep base B401R standard base with 470 ohm resistor B401SD standard base with schottky diode B401RSD standard base with 470 ohm resistor and schottky diode B401R1000 standard base with 1000 ohm resistor B401DGR deep base with 470 ohm resistor B401DGR1000 deep base with 1000 ohm resistor B401DGSD deep base with schottky diode B501 standard analogue detector base B501AP intelligent detector base B501DG analogue sensor deep base B524IEFT analogue sensor isolator base ECO1000B standard base. ECO1000BSD standard base with schottky diode. ECO1000BR standard base, 470 ohm resistor. ECO1000BRSD standard base, 470 ohm resistor and schottky diode. ECO1000BR680 standard base, 680 ohm resistor. ECO1000BR680SD standard base, 680 ohm resistor and schottky diode. ECO1000BR1000 standard base, 1000 ohm resistor. ECO1000BR1000SD standard base, 1000 ohm resistor and schottky diode. ECO2000B mounting base. ECO1000DB deep base. ECO1000DBR deep base with 470 ohm resistor ECO1000DBRSD deep base with 470 ohm resistor and schottky diode.

Certificate No: 199p to EN 54-5: 2000 + A1:2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003 Certificate No: 199t to LPS 1279 - 1.0: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003

Multi-criteria Detectors
Certificated Products ECO1002 Conventional photo-thermal detector (ECO1000B, ECO1000BSD, ECO1000BR, ECO1000BRSD, ECO1000BR680, ECO1000BR680SD, ECO1000BR1000, ECO1000BR1000SD, ECO1000DB, ECO1000DBR and ECO1000DBRSD bases) Note :Meets the requirements of EN54:5-2000 at class A1R and EN54:7:2000 at pre-set sensitivity Analogue addressable optical/thermal smoke & heat detector B501AP, B501DG and B5241EFT bases) Note: Meets the requirements of EN 54-5:2000 at class A1R and EN 54-7:2000 at LPCB Ref. No. 199p/01

2251TEM

199p/02

January 2009

123

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products 2351TEM sensitivity settings 1 to 5 Conventional optical/thermal detector (B401, B401DG, B401R, B401SD, & B401RSD bases) Note: Meets the requirements of EN54-5:2000 at class A1R and EN54-7:2000 at 'High' 'Medium' and 'Low' sensitivity settings. Conventional photo thermal detector (2020B, 2020DB, 2020BSD and 2020DBSD bases) Analogue addressable multi-criteria detector incorporating photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: Normal Mode: Alarm Levels 1 to 5 (Multi-criteria): EN54-5 Class A1R, EN54-7 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Analogue addressable multi-criteria fire detector incorporating CO, photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases) Note: Certified at the following settings: Normal Mode: Alarm Levels 1 to 5 (Multi-criteria) EN54-5 Class A1R, EN54-7, LPS1279 and CEA 4021 Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R Nuisance Environment Applications: Application 0, Alarm Level 4 Application 1, Alarm Level 5 Application 2, Alarm Level 4 or 5 Application 3, Alarm Level 5 Application 4, Alarm Level 5 Application 5, Alarm Level 5 Application 6, Alarm Level 5 EN54-7, LPS1279 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-5 Class A1R, EN54-7 & CEA EN54-7 & CEA 4021 EN54-5 Class A1R, EN54-7 & CEA LPCB Ref. No. 199p/03

Vision 2020PT 2251TLE

199p/04 199p/05

2251CTLE

199t/01

4021 4021 4021 4021 4021

Bases: 2020B standard base 2020DB deep base 2020BSD standard base with schottky diode 2020DBSD deep base with schottky diode B401 standard base B401DG deep base B401R standard base with 470 ohm resistor B401SD standard base with schottky diode B401RSD standard base with 470 ohm resistor and schottky diode B401R1000 standard base with 1000 ohm resistor B401DGR deep base with 470 ohm resistor B401DGR1000 deep base with 1000 ohm resistor B401DGSD deep base with schottky diode B501 standard analogue detector base B501AP intelligent detector base B501DG analogue sensor deep base B524IEFT analogue sensor isolator base ECO1000B standard base ECO1000BSD standard base with schottky diode ECO1000BR standard base, 470 ohm resistor ECO1000BRSD standard base, 470 ohm resistor and schottky diode ECO1000BR680 standard base, 680 ohm resistor ECO1000BR680SD standard base, 680 ohm resistor and schottky diode ECO1000BR1000 standard base, 1000 ohm resistor ECO1000BR1000SD standard base, 1000 ohm resistor and schottky diode ECO1000DB deep base ECO1000DBR deep base with 470 ohm resistor ECO1000DBRSD deep base with 470 ohm resistor and schottky diode ECO2000B mounting base B524IEFT-1 analogue short circuit isolator base

124

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Plana Fabrega
Rudford Estate, Ford Aerodrome, Arundel, West Sussex BN18 0BE UK Tel: +44 (0)1908 281981 Fax: +44 (0)1908 282554
Certificate No: 092p to EN 54-5: 2000

Heat Detectors
Certificated Products T-7004 TV-7003 T-7005 Conventional Class A1 heat detector (BD-21 and BD-22 bases) Conventional Class A1R heat detector (BD-21 and BD-22 bases) Conventional Class B heat detector (BD-21 and BD-22 bases) LPCB Ref. No. 092p/02 092p/03 092p/04

Bases: BD-21 Conventional surface base BD-22 Conventional diode base

Certificate No: 092n to EN 54-7: 2000

Smoke Detectors
Certificated Products I-7001 O-7002 Conventional ionisation smoke detector (BD-21 and BD-22 bases) Conventional photoelectric smoke detector (BD-21 and BD-22 bases) LPCB Ref. No. 092n/03 092n/04

Bases: BD-21 Conventional surface base BD-22 Conventional diode base

Protec Fire Detection plc


Protec House, Churchill Way, Nelson, Lancashire BB9 6RT UK Tel: +44 (0)1282 717171 Fax: +44 (0)1282 717273 E-mail: sales@protec.co.uk Website: www.protec.co.uk
Certificate No: 201f to EN 54-7: 2000 Certificate No: 201p to EN 54-7: 2000

Point Smoke Detectors


Certificated Products 3000/ION 3000/OP 6000/OP Mk II 3000/OP Mk II 6000/OP Conventional ionisation smoke detector (3000/BASE) Conventional optical smoke detector (3000/BASE) Analogue addressable optical smoke detector (6000/BASE and 6000/DIB bases) Note: Meets requirements of EN 54: 7: 2000 at medium 'office' sensitivity only. Conventional optical smoke detector (3000/BASE) MK II Analogue addressable optical smoke detector (6000/BASE and 6000/DIB bases) Note: Meets requirements of EN 54-7: 2000 at the following mode settings: i. Normal sensitivity mode LPCB Ref. No. 201f/01 201f/02 201f/03 201f/04 201p/01

Bases: 6000/BASE standard low profile base 6000/DIB isolator base 3000/BASE Standard Base

January 2009

125

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificate No: 201g to EN 54-5: 2000 + A1: 2002 Certificate No: 201r to EN 54-5: 2000

Point Heat Detectors


Certificated Products 3000/TEMP56 3000/TEMP64 6000/TEMP Mk II 6000/TEMP Conventional class A1 rate of rise and fixed temperature heat detector (3000/BASE) Conventional class A2 rate of rise fixed temperature (3000/BASE) Analogue addressable heat detector (6000/BASE and 6000/DIB bases) Note: Meets requirements of EN 54: 5: 2000 at A1 and A2 classification settings only. Analogue addressable heat detector (6000/BASE & 6000/DIB bases) Note: Meets requirements of EN 54-5: 2000 at Class A1 (High sensitivity) and A2 (Normal sensitivity). LPCB Ref. No. 201g/01 201g/02 201g/03 201r/01

Bases: 3000/BASE standard base 6000/BASE standard low profile base 6000/DIB isolator base

Certificate No: Certificate No: Certificate No: Certificate No:

201h to EN 54- 7: 2000 + A1: 2002 and CEA 4021: 2003 201j to EN 54: Part 5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 and CEA 4021: 2003 201q to EN 54-5: 2000, EN 54-7: 2000 and CEA 4021 201s to EN 54-5: 2000, EN 54-7: 2000 and CEA 4021

Multi-criteria Detectors
Certificated Products 6000/OPHT Analogue addressable optical smoke detector with thermal enhancement (6000/BASE and 6000/DIB bases) Note: 1) Meets requirements of EN 54: 7: 2000 and CEA 4021 at the following mode settings only: i. Medium sensitivity combination ii. Low sensitivity combination iii. High performance optical mode Conventional optical smoke and Class A2 heat detector (3000/BASE) Analogue addressable optical smoke and Class A2 heat multisensor detector (6000/BASE & 6000/DIB bases). Note: 1) Meets requirements of EN 54-7: 2000 and CEA 4021 at the following mode settings only: i. Normal sensitivity mode ii. Low sensitivity mode Analogue addressable optical smoke, CO and Class A2 heat multisensor detector (6000/BASE & 6000/DIB bases) Notes: 1) Meets requirements of EN 54-7: 2000 and CEA 4021 at the following mode settings only: i. Normal sensitivity mode ii. Low sensitivity mode 2) The CO element is not LPCB approved LPCB Ref. No. 201h/01

3000/OPHT Mk II 6000/OPHT Mk II

201j/01 201q/01

6000/OPHTCO

201s/01

Bases: 3000/BASE standard base 6000/BASE standard low profile base 6000/DIB isolator base

126

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Rafiki Protection Limited


Unit 31, Springvale Industrial Estate, Cwmbran, Gwent NP44 5BD UK Tel: +44 (0)1633 865558 Fax: +44 (0)1633 866656 Website: www.rafikiprotection.com
Certificate No: 331b to EN 54: Part 3: 2001, EN 54: Part 5: 2000, EN 54-7: 2000, GEI-052: Draft 2.0 and CEA 4021: 1999-06

Multi-criteria Detectors
Certificated Products 203-0001 Sita200plus Multipoint Intelligent Addressable Optical smoke, heat detector and sounder, incorporating short circuit isolator and auxiliary input/output. Notes: Approved for use with smoke sensitivities SM1-SM3, heat sensitivity HM1(Class A2), HM2(Class A2) and HM3(Class C), sound output settings SP1-SP7 when set to medium and high volume only. Multipoint Intelligent Addressable Optical smoke, heat detector and sounder, incorporating short circuit isolator and auxiliary input/output Notes: Approved for use with smoke sensitivities SM1-SM3 and heat sensitivity HM1(Class A2), HM2(Class A2) and HM3(Class C). LPCB Ref. No. 331b/01

203-0003 Sita200plus

331b/02

Ravel Electronics Pvt. Ltd


150-A, Electronics Industrial Estate, Perungudi, Chennai 600096, India Tel: +91 44 24961004 Fax: +91 44 42049599 E-mail: marketing@ravelfirepanels.com Website: www.ravelfirepanels.com
Certificate No: 550a to EN 54-7: 2000 + A1: 2002

Smoke Detectors
Certificated Products RE-1003 P Bases: RE-1000B Standard base Conventional photoelectric smoke detector (RE-1000B base) LPCB Ref. No. 550a/02

Certificate No: 550b to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 1999

Multi-criteria Detectors
Certificated Products RE-1002 PT Conventional photo-thermal detector (RE-1000B base) Note: Meets the requirements of EN54-5:2000 at class A1R at pre-set sensitivity LPCB Ref. No. 550b/02

Bases: RE-1000B Standard base

Certificate No: 550c to EN 54-5: 2000 + A1: 2002

Heat Detectors
Certificated Products RE-1005 R Bases: Conventional A1R rate-of-rise heat detector (RE-1000B base) LPCB Ref. No. 550c/03

January 2009

127

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
RE-1000B Standard base

Sareme UAB
Naugarduko str. 32/2, Vilnius LT2006, Lithuania Tel: +3705 2135047 Fax: +3705 2333567 E-mail: sareme@sareme.lt
Certificate No: 512d to EN 54-5: 2000

Heat Detectors
Certificated Products EA323-2 EA323-4 Conventional 2 wire 24 VDC class A2S fixed temperature and rate-of-rise heat detector (P/N854001 base) Conventional 4 wire 12VDC class A2S fixed temperature and rate-of-rise heat detector (P/N854001 base) LPCB Ref. No. 512d/01 512d/05

Bases: P/N854001 4-Wire detector base

Sensor Highway Ltd (trading as Sensa)


Gamma House, Enterprise Road, Chilworth Science Park, Southampton, Hants SO16 7NS UK Tel: +44 (0)23 8076 5500 Fax: +44 (0)23 8076 5501 E-mail: enquiries@sensa.org Website: www.sensa.org
Certificate No: 648a to LPCB Test Schedule 109819/1.1 Certificate No: 648b to LPCB Test Schedule E120263/1.3

Linear Heat Detection System


Certificated Products LTS200 Fibre Optic Linear Heat Detection System consisting of:- LTS200 Sensor Control Unit. - SensorTube (Part No. 00.000011) Optical Fibre sensor. The approval is conditional on the following: - The linear heat detection system is installed, configured and commissioned in accordance with the manufacturer's instructions. - The optical fibre sensor does not exceed a maximum length of 2 km and is connected in a loop configuration with the break detect option enabled. - The zone/alarm configuration parameters are set, in accordance with the manufacturer's instructions (User Manual Page 40), to give an alarm response equivalent to Class A1R specified in EN 54-5: 2000. Fibre Optic Linear Heat Detection System consisting of: - DTS240 Sensor Control Unit. - SensorTube (Part No. 00.000011) Optical Fibre sensor. The approval is conditional on the following: -The linear heat detection system is installed, configured and commissioned in accordance with the manufacturer's instructions. - The optical fibre sensor does not exceed a maximum length of 4 km and is connected in a loop configuration with the break detect option enabled. - The zone/alarm configuration parameters are set, in accordance with the manufacturer's instructions(User Manual Page 30), to give an alarm response equivalent to Class A1R specified in EN 54-5: 2000. LPCB Ref. No. 648a/01

LTS240

648b/01

128

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Shield Fire Safety & Security Ltd


29th Floor, Regus Suite, One Canada Square, Canary Wharf, London E14 5DY UK Tel: +44 (0)207 712 1722 Fax: +44 (0)870 734 5579 E-mail: info@shielduk.com Website: www.shielduk.com
Certificate No: 548d to EN 54-7: 2000 Certificate No: 548k to EN 54-12: 2002

Beam Detectors
Certificated Products D-A430/R Intelligent optical beam detector Notes: 1) Meets the requirements of EN 54-12 at the following sensitivity settings: Level 1 - 1.61 dB Level 2 - 2.31dB LPCB Ref. No. 548k/01

Smoke Detectors
Certificated Products D-C401 D-A411 Bases: DZ-03 Standard detector base Conventional photoelectric smoke detector (DZ-03 base) Intelligent photoelectric smoke detector (DZ-03 base) LPCB Ref. No. 548d/01 548d/02

Certificate No: 548c to EN 54-5: 2000

Heat Detectors
Certificated Products D-C402 D-A412 Bases: DZ-03 Standard detector base Conventional Class A1R heat detector (DZ-03 base) Intelligent Class A1R heat detector (DZ-03 base) LPCB Ref. No. 548c/01 548c/02

January 2009

129

PART 3: SECTION 4.1


COMMERCIAL DETECTORS

Siemens Switzerland Limited, Building Technologies Division


International Headquarters, Fire Safety & Security Products, Gubelstrasse 22, CH-6301 Zug, Switzerland Tel: +41 (0) 41 724 24 24 Fax: +41 (0) 41 724 35 22 Manufacturing at: Volketswil Factory, Industriestrasse 22, CH-8604 Volketswil, Switzerland Tel: +41 1 922 6111 Fax: +41 1 922 6450

UK Sales: Siemens Building Technologies Limited, FSP Division Tel: +44 (0)1784 461616 Fax: +44 (0)1784 464646

Certificate No: Certificate No: Certificate No: Certificate No:

126x to EN 54:7: 2000 126ab to EN 54-7: 2000 + A1: 2002 + A2: 2006 and CEA GEI 1-052: DRAFT 2.0, 11/06/97 126am to EN 54-7: 2000 + A1: 2002 531c

Point Smoke Detectors


Certificated Products FDO241 FDO221 DO1101A DO1101A-Ex DO1131A DO1151A DO1152A DOT1131A DOT1151A DOT1151A-Ex DOT1152A R970 OH620 OP620 OP820 Analogue addressable photoelectric smoke detector (FDB221, FDB201, FDB291 and FDB292 bases) Analogue addressable photoelectric smoke detector (FDB221, FDB201, FDB291 and FDB292 bases) Conventional photoelectric smoke detector (DB1101A base) Intrinsically safe conventional photoelectric smoke detector (DB1101A base) Addressable photoelectric smoke detector (DB1131A base) Note: Meets EN54-7: 2000 at Standard and High sensitivity settings Addressable photoelectric smoke detector (DB1151A) Note: Meets EN54-7: 2000 at Personen/life sensitivity settings Addressable photoelectric smoke detector (DB1151A base) Note: Meets EN54-7: 2000 at Personen/life and Immobilien/property sensitivity settings Addressable photoelectric smoke detector with thermal enhancement (DB1131A base) Note: Meets EN54-7: 2000 at Standard and High sensitivity settings Addressable photoelectric smoke detector with thermal enhancement (DB1151A base) Note: Meets EN54-7: 2000 at Personen/life and Immobilien/property sensitivity settings Intrinsically safe addressable photoelectric smoke detector with thermal enhancement (DB1151A) Note: Meets EN54-7: 2000 at Personen/life and Immobilien/property sensitivity settings Addressable photoelectric smoke detector with thermal enhancement (DB1151A base) Note: Meets EN54-7: 2000 at Personen/life and Immobilien/property sensitivity settings Scattered light smoke detector (Z94 base) Note: Meets requirements of EN 54-7 at standard (2.5%m) and increased (1.7%/m) sensitivity setting Analogue addressable photoelectric smoke detector with thermal enhancement (SO620 base) Note: Meets the requirements of EN54-7: 2000 at Standard and High sensitivity settings Analogue addressable photoelectric smoke detector (SO620 base) Note: Meets the requirements of EN54-7: 2000 at Standard and High sensitivity settings Analogue addressable photoelectric smoke detector (SO820 base) Note: Meets the requirements of EN54-7: 2000 at Personen/life and Immobilien/property sensitivity settings LPCB Ref. No. 126ab/01 126ab/02 126am/01 126am/02 126am/03 126am/04 126am/05 126am/06 126am/07 126am/08 126am/09 126x/01 531c/05 531c/06 531c/07

Bases: Z94 base FDB221 base FDB201 base "Collective" FDB291 base attachment surface FDB292 base attachment surface wet DB1101A base DB1131A base DB1151A base DBZ1191 base attachment

130

January 2009

SECTION 4.1: PART


SO620 Analogue addressable (AnalogPLUS) detector base SO820 Analogue addressable (Interactive) detector base

COMMERCIAL DETECTORS

Certificate No: 126aa to EN 54-5: 2000 + A1: 2002 and CEA GEI 1-052: Draft 2.0, 11/06/97 Certificate No: 126an to EN 54-5: 2000 + A1: 2002 Certificate No: 531b to EN 54-5: 2000 + A1: 2002

Point Heat Detectors


Certificated Products FDT241 FDT221 DT1101A DT1101A-Ex DT1102A DT1102A-Ex DT1131A DT1151A-Ex DT1152A HI320A HI322A HI320C HI322C HI620 HI820 Analogue addressable rate of rise heat detector (FDB221, FDB201, FDB291 and FDB292 bases) Note: Meets EN 54-5: 2000 at Class A1R, A1S, BR and BS. Analogue addressable rate of rise heat detector (FDB221, FDB201, FDB291 and FDB292 bases) Note: Meets EN 54-5: 2000 at Class A1R and BR. Conventional class A1R heat detector (DB1101A base) Conventional intrinsically safe class A1R heat detector (DB1101A base) Conventional class B heat detector (DB1101A base) Conventional intrinsically safe class B heat detector (DB1101A base) Analogue addressable class A1R heat detector (DB1131A base) Analogue addressable intrinsically safe heat detector (DB1151A base) Note: Meets EN54-5: 2000 at class A1R and class B Analogue addressable intrinsically safe heat detector (DB1151A base) Note: Meets EN54-5: 2000 at class A1R and class B Analogue addressable class A1R heat detector (SO320 base) Analogue addressable class A2 heat detector (SO320 base) Conventional class A1R heat detector (SO320 base) Conventional class A2 heat detector (SO320 base) Analogue addressable (AnalogPLUS) Class A1R heat detector (SO620 base) Analogue addressable (Interactive) heat detector (SO820 base) Note: Meets the requirements of EN54-5: 2000 at class A1R and class BR LPCB Ref. No. 126aa/01 126aa/02 126an/01 126an/02 126an/03 126an/04 126an/05 126an/06 126an/06 531b/01 531b/02 531b/03 531b/04 531b/05 531b/06

Bases: Z94 base DFB1190 base FDB221 base FDB201 base Collective FDB291 base attachment surface FDB292 base attachment surface wet DB1101A base for conventional addressing DB1131A base for analogue addressing DB1151A base for interactive fire detectors TM SO320 base for Synova 300 series detectors SO620 Analogue addressable (AnalogPLUS) detector base SO820 Analogue addressable (Interactive) detector base

Certificate No: 126ag to EN 54-12: 2002 and CEA GEI 1-052: Draft 2.0, 11/06/97 Certificate No: 126ak to EN 54-12: 2002

Beam Detectors
Certificated Products FDL241-9 DLO1191 Analogue addressable beam detector (FDLB291 base) Note: Certified at sensitivity setting 30%, 50% and 65% Optical beam smoke detector (DLB1191A base) Note: Certified at sensitivity setting 30%, 50% and 65% LPCB Ref. No. 126ag/01 126ak/01

Bases: FDLB291 base DLB1191A base

Certificate No: 126s to EN 54-10: 2002 Certificate No: 126af to EN 54-10: 2002 and CEA GEI 1-052: Draft 2.0, 11/06/97

January 2009

131

PART 3: SECTION 4.1


COMMERCIAL DETECTORS Flame Detectors
Certificated Products FDF241-9 FDF221-9 DF1192 DF1191 DF1101-Ex DF1151-Ex Analogue addressable infra red flame detector (FDFB291 base) Note: Meets EN 54-10: 2002 at Class 1 and 2 only Analogue addressable infra red flame detector (FDF291 base) Note: Meets EN54-10: 2002 at class 1 and 2 only Analogue addressable infra red flame detector (DFB 1190 base) Note: Certificated in "increased" & "standard" sensitivity settings - Class 1 and 2 respectively. Analogue addressable infra red flame detector (DFB 1190 base) Note: Certificated in "increased" & "standard" sensitivity settings - Class 1 and 2 respectively. Conventional I.S. infra red flame detector (DFB 1190 base) Note: Certificated in "increased" & "standard" sensitivity settings - Class 1 and 2 respectively. Analogue addressable I.S. infra red flame detector (DFB 1190 base) Note: Certificated in "increased" & "standard" sensitivity settings - Class 1 and 2 respectively. LPCB Ref. No. 126af/01 126af/02 126s/01 126s/02 126s/03 126s/04

Bases: Z94 base DFB 1190 base FDFB291 base

Certificate No: 126ah to EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002, CEA 4021: 2003 & CEA GEI 1-052: Draft 2.0, 11.06.97

Multi-criteria Detectors
Certificated Products FDOOT241-9 Analogue addressable multisensor detector with short circuit isolator (FDB221, FDB201, FDB291 and FDB292 bases) Note: Meets the requirements of EN 54-5: 2000 at Class A2R & A2S and EN 54-7: 2000 at sensitivity settings: Parameter No. 1 Universal Parameter No. 2 Robust with thermal enhancement Parameter No. 3 Sensitive Parameter No. 4 balanced with thermal enhancement Parameter No. 5 Suppression with thermal enhancement Parameter No. 6 Response with thermal enhancement Parameter No. 7 Robust / BGD with thermal enhancement Analogue addressable multisensor detector with short circuit isolator (FDB221, FDB201, FDB291 and FDB292 bases) Note: Meets the requirements of EN 54-5: 2000 at Class A2R & A2S and EN 54-7: 2000 at sensitivity settings: Parameter No. 2 Robust with thermal enhancement Parameter No. 4 balanced with thermal enhancement LPCB Ref. No. 126ah/01

FDOOT221

126ah/02

Bases: FDB221 base FDB201 base Collective FDB291 base attachment surface FDB292 base attachment surface wet

Certificate No: 531c to EN 54-7: 2000 + A1: 2002

Photoelectric Smoke Detectors


Certificated Products OH320A OH320C OP320A OP320C Analogue addressable photoelectric smoke detector with thermal enhancement (SO320 base) Note: Meets EN54-7: 2000 at Standard and High sensitivity settings Conventional photoelectric smoke detector with thermal enhancement (SO320 base) Analogue addressable photoelectric smoke detector (SO320 base) Note: Meets EN54-7: 2000 at Standard and High sensitivity settings Conventional photoelectric smoke detector (SO320 base) LPCB Ref. No. 531c/01 531c/02 531c/03 531c/04

132

January 2009

SECTION 4.1: PART

COMMERCIAL DETECTORS

Bases: TM SO320 base for Synova 300 series detectors

System Sensor
3825 Ohio Avenue, Saint Charles, Illinois 60174, USA Tel: +1 630 377 6580 Fax: +1 630 377 7245 Website: www.systemsensor.com European Sales Enquiries: System Sensor Europe Tel: +44 (0)1403 891920 Fax: +44 (0)1403 891921

Certificate No: 118h to EN 54-7: 2000 + A1: 2002

Point Smoke Detectors


Certificated Products 7251 Analogue addressable photoelectric laser smoke detector (B501, B501AP, B501DG, B524IEFT, B524IEFT-1 bases) Note: meets requirements of EN 54: Part 7 at sensitivities 7 to 9 inclusive LPCB Ref. No. 118h/01

Bases: B501 analogue sensor base B501AP intelligent detector base B501DG deep base B524IEFT short circuit isolator base B524IEFT-1 short circuit isolator base

System Sensor (India)


Sector 36, Pace City - II, Gurgaon - 122 004, Haryana, India Tel: +91 124 6371770 Fax: +91 124 6371713
Certificate No: 550a to EN 54-7: 2000 + A1 2002

Point Smoke Detectors


Certificated Products 2351E Conventional photoelectric smoke detector (B401, B401DG, B401R, B401SD, B401RSD, B401R1000, B401DGR, B401DGR1000 & B401DGSD bases) Note: Meets the requirements of EN54-7:2000 at low, medium & high sensitivity settings. Conventional photoelectric smoke detector (ECO1000B, ECO1000BSD, ECO1000BR, ECO1000BRSD, ECO1000BR680, ECO1000BR680SD, ECO1000BR1000 & ECO1000BR1000SD bases) Analogue addressable optical smoke detector (B501, B501DG and B5241EFT-1 bases) Notes : Meets EN 54-7 with low, medium and high sensitivity settings LPCB Ref. No. 550a/01

EC01003 2251EM

550a/02 550a/03

January 2009

133

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Bases: B401 standard base B401DG deep base B401R standard base with schottky diode B401SD standard base with schottky diode B401RSD standard base with 470 ohm resistor and schottky diode B401R1000 standard base with 1000 ohm resistor B401DGR deep base with 470 ohm resistor B401DGR1000 deep base with 1000 ohm resistor B401DGSD deep base with schottky diode ECO1000B standard base ECO1000BSD standard base with schottky diode ECO1000BR standard base, 470 ohm resistor ECO1000BRSD standard base, 470 ohm resistor and schottky diode ECO1000BR680 standard base, 680 ohm resistor ECO1000BR680SD standard base, 680 ohm resistor and schottky diode ECO1000BR1000 standard base, 1000 ohm resistor ECO1000BR1000SD standard base, 1000 ohm resistor and schottky diode B501 standard analogue detector base B501DG deep analogue detector base B5241EFT-1 analogue short circuit isolator base

Certificate No: 550b to EN 54-5: 2000 + A1: 2002, EN 54-7:2000 + A1: 2002 & CEA 4021: 1999

Multi Criteria Detectors


Certificated Products 2351TEM Conventional optical/thermal detector (B401, B401DG, B401R, B401SD, B401RSD, B401R1000, B401DGR, B401DGR1000 & B401DGSD bases) Note: Meets the requirements of EN54-5:2000 at Class A1R and EN54-7:2000 at low, medium & high sensitivity settings. Conventional photo-thermal detector (ECO1000B, ECO1000BSD, ECO1000BR, ECO1000BRSD, ECO1000BR680, ECO1000BR680SD, ECO1000BR1000 & ECO1000BR1000SD bases) Note: Meets the requirements of EN 54-5:2000 at class A1R at pre-set sensitivity. Analogue optical/thermal smoke & heat detector (B501, B501DG and B5241EFT-1 bases) Notes : 1) Meets the requirements of EN 54-7: 2000 at sensitivity settings 1 to 5 2) Meets the requirements of EN 54-5: 2000 at Class A1R LPCB Ref. No. 550b/01

ECO1002

550b/02

2251TEM

550b/03

Bases: B401 standard base B401DG deep base B401R standard base with schottky diode B401SD standard base with schottky diode B401RSD standard base with 470 ohm resistor and schottky diode B401R1000 standard base with 1000 ohm resistor B401DGR deep base with 470 ohm resistor B401DGR1000 deep base with 1000 ohm resistor B401DGSD deep base with schottky diode ECO1000B standard base ECO1000BSD standard base with schottky diode ECO1000BR standard base, 470 ohm resistor ECO1000BRSD standard base, 470 ohm resistor and schottky diode ECO1000BR680 standard base, 680 ohm resistor ECO1000BR680SD standard base, 680 ohm resistor and schottky diode ECO1000BR1000 standard base, 1000 ohm resistor ECO1000BR1000SD standard base, 1000 ohm resistor and schottky diode B501 standard analogue detector base B501DG deep analogue detector base B5241EFT-1 analogue short circuit isolator base

Certificate No: 550c to EN 54-5: 2000 + A1: 2002

134

January 2009

SECTION 4.1: PART


Point Heat Detectors
Certificated Products 5351E Class A1R conventional rate of rise heat detector (B401, B401DG, B401R, B401SD, B401RSD, B401R1000, B401DGR, B401DGR1000 & B401DGSD bases) Note: Meets the requirements of EN54-5:2000 at class A1R. Class BS conventional heat detector (B401, B401DG, B401R, B401SD, B401RSD, B401R1000, B401DGR, B401DGR1000 & B401DGSD bases) Note: Meets the requirements of EN54-5:2000 at class BS. Conventional A1R rate-of-rise heat detector (ECO1000B, ECO1000BSD, ECO1000BR, ECO1000BRSD, ECO1000BR680, ECO1000BR680SD, ECO1000BR1000 & ECO1000BR1000SD bases) Analogue addressable Class A1S fixed temperature heat detector (B501, B501DG and B5241EFT-1 bases) Analogue addressable Class A1R high temperature rate of rise heat detector (B501, B501DG and B5241EFT-1 bases) LPCB Ref. No. 550c/01

COMMERCIAL DETECTORS

4351E

550c/02

ECO1005 5251EM 5251REM

550c/03 550c/04 550c/05

Bases: B401 standard base B401DG deep base B401R standard base with schottky diode B401SD standard base with schottky diode B401RSD standard base with 470 ohm resistor and schottky diode B401R1000 standard base with 1000 ohm resistor B401DGR deep base with 470 ohm resistor B401DGR1000 deep base with 1000 ohm resistor B401DGSD deep base with schottky diode ECO1000B standard base ECO1000BSD standard base with schottky diode ECO1000BR standard base, 470 ohm resistor ECO1000BRSD standard base, 470 ohm resistor and schottky diode ECO1000BR680 standard base, 680 ohm resistor ECO1000BR680SD standard base, 680 ohm resistor and schottky diode ECO1000BR1000 standard base, 1000 ohm resistor ECO1000BR1000SD standard base, 1000 ohm resistor and schottky diode

Talentum Developments Limited


Beal Lane, Shaw, Oldham, Lancashire OL2 8PF UK Tel: +44 (0)1706 844714 Fax: +44 (0)1706 882612 E-mail: info@talentum.co.uk Website: www.talentum.co.uk
Certificate No: 729a to EN 54-10: 2002

Flame Detectors
Certificated Products 016589 016689 016579 016679 016519 016619 016581 016681 016571 Conventional IR Flame Detector (007127) Note: Meets EN 54-10:2002 at Class 1 only 3 Analogue Addressable IR Flame Detector (007127) Note: Meets EN 54-10:2002 at Class 1 only 3 Conventional IR Intrinsically Safe Flame Detector (007127) Note: Meets EN 54-10:2002 at Class 1 only 3 Analogue Addressable IR Intrinsically Safe Flame Detector (007127) Note: Meets EN 54-10:2002 at Class 1 only 3 Conventional IR (Exd) Flameproof Flame Detector (007127) Note: Meets EN 54-10:2002 at Class 1 only 3 Analogue Addressable IR (Exd) Flameproof Flame Detector (007127) Note: Meets EN 54-10:2002 at Class 1 only 2 Conventional IR Flame Detector (007127) Note: Meets EN 54-10: 2002 at Class 1 only 2 Analogue Addressable IR Flame Detector (007127) Note: Meets EN 54-10: 2002 at Class 1 only 2 Conventional IR Intrinsically Safe Flame Detector (007127) Note: Meets EN 54-10: 2002 at Class 1 only
3

LPCB Ref. No. 729a/01 729a/02 729a/03 729a/04 729a/05 729a/06 729a/07 729a/08 729a/09

January 2009

135

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products 016511 016611 Conventional IR (Exd) Flameproof Flame Detector (007127) Note: Meets EN 54-10: 2002 at Class 1 only 2 Analogue Addressable IR (Exd) Flameproof Flame Detector (007127) Note: Meets EN 54-10: 2002 at Class 1 only
2

LPCB Ref. No. 729a/10 729a/11

Ancillaries 007127 Mounting Bracket

Tamlite Emergency & Fire


Pipers Road, Park Farm Industrial Estate, Redditch, Worcestershire B98 0HU UK Tel: +44 (0)1527 510523 Fax: +44 (0)1527 510592 E-mail: firetech@tamlite.co.uk Website: www.tamlite.co.uk
Certificate No: 603a to EN54-7: 2000 + A1: 2002

Smoke Detector
Certificated Products FSV-OPT Bases: FSV-CDB Standard base Conventional photoelectric smoke detector (FSV-CDB base) LPCB Ref. No. 603a/01

Certificate No: 603b to EN 54-5: 2000 + A!: 2002

Point Heat Detectors


Certificated Products FSV-FH78 FSV-RR58 Bases: FSV-CDB Standard base Conventional class BS fixed temperature heat detector (FSV-CDB base) Conventional class A1R rate-of-rise heat detector (FSV-CDB base) LPCB Ref. No. 603b/01 603b/02

Thorn Security Limited, trading as Tyco Safety Products


Dunhams Lane, Letchworth SG6 1BE UK Tel: +44 (0)1462 667700 Fax: +44 (0)1462 667777 E-mail: mashbury@tycoint.com Website: www.tycosafetyproducts-europe.com
Certificate No: 681c to EN 54 -5: 2000 + A1: 2002

Heat Detectors
Certificated Products 801H 601H-R 601H-F MD601Ex MD611Ex 816H MX Digital addressable heat detector (801B, 801IB, 801RB and 801SB Bases) Note: Meets EN54 Part 5 for classes A1R, A2S and CR. Conventional Class A1R heat detector (MUB and 5B mounting bases) Conventional Class A1S heat detector (MUB and 5B mounting bases) Conventional intrinsically safe Class A1R rate of rise heat detector (MUBEx base, 5BEx base) Conventional intrinsically safe Class A1S fixed temperature heat detector (MUBEx base, 5BEx base) MX Digital addressable heat detector (801B, 801IB, 801RB, 801SB and 5BI 5 bases) Note: Meets EN54 Part 5 for classes A1R, A2S and CR. LPCB Ref. No. 681c/01 681c/02 681c/03 681c/04 681c/05 681c/06

Bases:

136

January 2009

SECTION 4.1: PART


801B Minerva universal mounting base 801IB addressable isolator base 801RB addressable relay base 801SB addressable sounder base MUB Universal mounting base MUBEx Intrinsically safe detector base 5B 5 Universal mounting base 5BI 5 isolator base 5BI Isolator base 5BEX Intrinsically safe detector base

COMMERCIAL DETECTORS

Certificate No: 681q to LPS 1274 Issue 1, CEA 4021:2003, EN 54-7:2000, and EN 54-5:2000 Certificate No: 681j to EN 54-7:2000 and CEA 4021:1999 and AI:2002

Multi-criteria Detectors
Certificated Products 601PH MR601Tex 816PH 801PC Conventional high performance optical smoke detector (MUB and 5B mounting bases) Conventional intrinsically safe high performance optical smoke detector with heat enhancement (MUBEx base, 5BEx base) MX Digital addressable photoelectric detector with heat enhancement (801B, 801IB, 801RB, 801SB and 5BI 5 bases) Note: Meets EN54 Part 7 at Normal sensitivity Analogue addressable combined optical, heat and CO fire detector 5B, 5BI, 801SB, 801RB, 802SB, 901SB, and DHM-5B bases) Notes: 1) Certificated at the following modes: Mode 0 - Universal multi-criteria (smoke /heat/CO) wide spectrum fire detection with Class A2S heat detection Mode 1 - Multi-criteria (smoke /heat/CO) fire detection with high false alarm immunity with Class A2S heat detection Mode 2 - Class A1R heat detection Mode 3 - Thermally enhanced smoke detection Mode 4 - Thermally enhanced CO detection 2) Meets the requirements of LPS 1274 at modes 0 and 4, CEA 4021 and EN 547 at modes 0, 1 and 3, and EN 54-5 at modes 0, 1, and 2. Analogue addressable combined optical, heat and CO fire detector( marine version) (MUB, 5B, 5BI, 801SB, 801RB, 802SB, 901SB, and DHM-5B bases) Notes: 1) Certificated at the following modes: Mode 0 - Universal multi-criteria (smoke /heat/CO) wide spectrum fire detection with Class A2S heat detection Mode 1 - Multi-criteria (smoke /heat/CO) fire detection with high false alarm immunity with Class A2S heat detection Mode 2 - Class A1R heat detection Mode 3 - Thermally enhanced smoke detection Mode 4 - Thermally enhanced CO detection 2) Meets the requirements of LPS 1274 at modes 0 and 4, CEA 4021 and EN 547 at modes 0, 1 and 3, and EN 54-5 at modes 0, 1, and 2. LPCB Ref. No. 681j/01 681j/02 681j/03 681q/01

811PC

681q/02

Bases: MUBEx intrinsically safe detector base 801B Minerva universal mounting base 801IB addressable isolator base 801RB addressable relay base 801SB addressable sounder base 5BI 5 Isolator base MUB Universal mounting base 5B 5 Universal mounting base 802SB - Mk II Sounder base 901SB - Mk II Sounder base DHM-5B - Deck head mounting adaptor for 5" base 5BEx Intrinsically safe mounting base

Certificate No: 763a to EN 54-10: 2002 Certificate No: 681r to EN 54-10: 2002

January 2009

137

PART 3: SECTION 4.1


COMMERCIAL DETECTORS Flame Detectors
Certificated Products 601F 601FEx 801F 801FEx S231i+ S231f+ S241i+ S241f+ S251i+ S251f+ S261f+ S271i+ S271f+ Conventional Class 2 flame detector (5B and MUB bases) Conventional Class 2 intrinsically safe flame detector (5B and MUB bases) MX addressable Class 2 flame detector (5B, 5IB, 801IB and MUB bases) MX addressable Class 2 intrinsically safe flame detector (5B, 5IB, 801IB and MUB bases) Conventional class 1 2-wire intrinsically safe IR flame detector Conventional class 1 2-wire flame proof IR flame detector 4-20mA current class 1 intrinsically safe IR flame detector 4-20mA current class 1 flame proof IR flame detector Analogue addressable class 1 intrinsically safe IR flame detector Analogue addressable class 1 flame proof IR flame detector Relay class 1 flame proof IR flame detector Analogue class 1 triple IR flame detector with MX interface Analogue class 1 flame proof triple IR flame detector with MX interface LPCB Ref. No. 681r/01 681r/02 681r/03 681r/04 763a/01 763a/02 763a/03 763a/04 763a/05 763a/06 763a/07 763a/08 763a/09

Bases: MUB standard mounting base 5B standard mounting base 5BI addressable isolator base 801IB addressable isolator base

Certificate No: 681d to EN 54-7: 2000 + A1: 2002

Smoke Detectors
Certificated Products 801I 601I 601P 816P MX Digital addressable ionisation smoke detector (801B, 801IB, 801RB and 801SB bases) Note: Meets EN54 Part 7 in normal and high sensitivity settings only. Conventional ionisation smoke detector (MUB and 5B 5" mounting bases) Conventional optical smoke detector (MUB and 5B 5" mounting bases) MX Digital addressable photoelectric detector (801B, 801IB, 801RB, 801SB and 5BI 5 bases) Note: Meets EN54 Part 7 at normal and high sensitivity LPCB Ref. No. 681d/01 681d/02 681d/03 681d/05

Bases: 801B Minerva universal mounting base 801IB addressable isolator base 801RB addressable relay base 801SB addressable sounder base MUB Universal mounting base 5B 5 Universal mounting base 5BI 5 Isolator base

VRC Terofire Products


Lion House, Lion Street, Congleton, Cheshire CW12 4BH UK Tel: +44 (0)1260 297578 Fax: +44 (0)1260 290078 E-mail: sales@terofire.com
Certificate No: 512d to EN 54-5: 2000

Point Heat Detectors


Certificated Products 10-0003 10-0003 Conventional 2 wire 24VDC class A2S fixed temperature and rate-of-rise heat detector with LED output (P/N854001 base) Conventional 2 wire 24VDC class A2R fixed temperature and rate-of-rise heat detector with LED output (P/N854001 base) LPCB Ref. No. 512d/03 512d/04

Bases:

138

January 2009

SECTION 4.1: PART


P/N854001 4-Wire detector base

COMMERCIAL DETECTORS

Wagner Alarm-und Sicherungssysteme GMBH


Schleswigstrasse 5, D-30853 Langenhagen, Germany Tel: +49 511 97383 0 Fax: +49 511 73338 6
Certificate No: 574a to CEA 4022: 1999-12-(en)

Aspirating Smoke Detectors


Certificated Products TITANUS 3000 Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room Protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply conforming with the requirements of BS EN 54-4 The detector shall be installed with sampling pipe conforming to EN 50086-1 to at least Class 1131 Design, installation and commissioning shall be performed in accordance with Wagner technical manual (69-30-176 for TITANUS SUPER.SENS and 69-300165 for TITANUS 3000). TITANUS SUPER.SENS/rev.a Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room Protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply conforming with the requirements of BS EN 54-4 The detector shall be installed with sampling pipe conforming to EN 50086-1 to at least Class 1131 Design, installation and commissioning shall be performed in accordance with Wagner technical manual (69-30-176 for TITANUS SUPER.SENS and 69-300165 for TITANUS 3000). TITANUS SUPER.Sens/a.G Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room Protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply conforming with the requirements of BS EN 54-4 The detector shall be installed with sampling pipe conforming to EN 50086-1 to at least Class 1131 Design, installation and commissioning shall be performed in accordance with Wagner technical manual (69-30-176 for TITANUS SUPER.SENS and 69-300165 for TITANUS 3000). TITANUS SUPER.SENS X Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room Protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply conforming with the requirements of BS EN 54-4 The detector shall be installed with sampling pipe conforming to EN 50086-1 to at least Class 1131 Design, installation and commissioning shall be performed in accordance with Wagner technical manual (69-30-176 for TITANUS SUPER.SENS and 69-300165 for TITANUS 3000). 574a/04 574a/03 574a/02 LPCB Ref. No. 574a/01

January 2009

139

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificate No: 524b to CEA 4022: 1999-12(en) Aspirating Smoke Detectors Certificated Products TITANUS TOP-SENS (TT1) TITANUS Top-Sens (TT1F) Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room Protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply conforming with the requirements of BS EN 54-4. The detector shall be installed with sampling pipe conforming to EN 50086-1 to at least Class 1131. 3) The detector must incorporate one of the following detector modules: DM-05 L with sensitivity of 0.05% DM-25 L with sensitivity of 0.25% DM-80 L with sensitivity of 0.8% LPCB Ref. No. 524b/01 524b/02

Certificate No: 767a to CEA 4022: 1999-12(en)

Aspirating Smoke Detectors


Certificated Products TITANUS PRO-SENS-net (TP-3) Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room Protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply conforming with the requirements of BS EN 54-4. The detector shall be installed with sampling pipe conforming to EN 50086-1 to at least Class 1131. 3) The detector must incorporate one of the following detector modules which are manufactured by Wagner Alarm-und Sicherungssysystem GmbH: DM-05 L with sensitivity of 0.05% DM-25 L with sensitivity of 0.25% DM-80 L with sensitivity of 0.8% 4) The network functionality is not included in the scope of this approval TITANUS TOP-SENS Rev.a (TT-1/a) Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room Protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply conforming with the requirements of BS EN 54-4. The detector shall be installed with sampling pipe conforming to EN 50086-1 to at least Class 1131. 3) The detector must incorporate one of the following detector modules which are manufactured by Wagner Alarm-und Sicherungssysystem GmbH: DM-05 L with sensitivity of 0.05% DM-25 L with sensitivity of 0.25% DM-80 L with sensitivity of 0.8% TITANUS TOP-SENS Rev.a (TT-1-F/a) Notes: 1) The detector has been assessed for compliance with clause 5.15 Fire sensitivity (Room Protection). 2) The approval of the detector is conditional upon the following requirements: The detector shall be supplied with power from a power supply conforming with the requirements of BS EN 54-4. The detector shall be installed with sampling pipe conforming to EN 50086-1 to at least Class 1131. 3) The detector must incorporate one of the following detector modules which are manufactured by Wagner Alarm-und Sicherungssysystem GmbH: 767a/03 767a/02 LPCB Ref. No. 767a/01

140

January 2009

SECTION 4.1: PART


Certificated Products DM-05 L with sensitivity of 0.05% DM-25 L with sensitivity of 0.25% DM-80 L with sensitivity of 0.8% LPCB Ref. No.

COMMERCIAL DETECTORS

Xtralis Pty Limited


Manufacturing at: Xtralis Pty Limited, 4 North Drive, Victoria Park, 236-262 East Boundary Road, Bentleigh East, Victoria 3165, Australia Tel: +61 3 9211 7200 Fax: +61 3 9211 7201

European Operations at: Xtralis (UK) Limited, Vision House, Focus 3, Mark Road, Hemel Hempstead, Hertfordshire HP2 7BW UK Tel: +44 (0)1442 242330 Fax: +44 (0)1442 249327

Certificate No: 305b to GEI 1 - 048 30-01-97 Certificate No: 305c to CEA 4022: 1999

Aspirating Smoke Detectors


Certificated Products VESDA LaserPLUS High sensitivity aspirating smoke detector Approved Configurations: VLP-012 LaserPLUS detector with Display & Programmer VLP-002 LaserPLUS detector with Display VLP-400 LaserPLUS detector with Fire/OK LEDs only VLP-401 LaserPLUS detector with Programmer & Fire/OK LEDs VLP-100 LaserPLUS detector with OEM cover Approved remote units: VRT-100 Remote Programmer VRT-200 Remote LaserPLUS Display unit (with 7 relays) VRT-300 VESDAnet socket VRT-500 Remote Relay unit (with 7 relays) VRT-600 Remote LaserPLUS Display unit (without relays) High sensitivity aspirating smoke detector Approved Configurations: VLS-600 LaserSCANNER with 7 relays and Fire/OK LEDs VLS-204 LaserSCANNER with 7 Relays and Display Module VLS-214 LaserSCANNER with 7 Relays, Display and Program Module VLS-700 LaserSCANNER with 12 relays and Fire/OK LEDs VLS-304 LaserSCANNER with 12 Relays and Display Module VLS-314 LaserSCANNER with 12 Relays, Display and Program Module VLS-100 LaserSCANNER with 7 Relays and OEM cover VLS-500 LaserSCANNER with 12 Relays and OEM cover Approved Remote Units: VRT-400 Remote Scanner Display with 7 relays VRT-700 Remote Scanner Display with no relays VRT-800 Remote Scanner Display with 12 relays VRT-900 Remote Scanner Relays -12 relays VRT-E00 Remote Scanner Relays - 7 relays The following note applies to the LaserSCANNER detector. 1. Scanner valve functionality and endurance was assessed as described in LPCB test schedule 68087/1. High sensitivity aspirating smoke detector Approved Configurations: VLC-500 LaserCOMPACT Relays only (RO) version VLC-505 LaserCOMPACT VESDAnet (VN) version VLC-400 LaserCOMPACT Apollo (AP) version VLC-800 LaserCOMPACT Tyco (MX) version LPCB Ref. No. 305b/01

VESDA LaserSCANNER

305b/02

VESDA LaserCOMPACT

305b/03

January 2009

141

PART 3: SECTION 4.1


COMMERCIAL DETECTORS
Certificated Products Approved remote units with the VLC-505 LaserCOMPACT VESDAnet (VN) version: VRT-J00 Remote LaserCOMPACT display (with 7 relays) VRT-K00 Remote LaserCOMPACT display (no relays) VRT-500 Remote Relay unit (with 7 relays) The following notes apply to LaserPLUS, LaserSCANNER and LaserCOMPACT detectors. 1. For compliance with clause 4.13 of GEI-1-048 the detectors shall be supplied with power from a power supply complying with the requirements of EN54 Part 4. 2. The approval of the detectors is conditional upon the following requirements: Design, Installation and Commissioning are performed in accordance with VESDA System Design Manual by installers accredited by the manufacturer. Each area is protected by a minimum of 2 holes. 3. The detectors have been assessed for compliance with clause 5.15 Fire Sensitivity (room protection). 4. Remote Display, Programme, Relay modules are also approved for mounting in a 19" sub rack. High sensitivity aspirating smoke detector The following notes apply to LaserFOCUS detectors 1. For compliance with CEA 4022, the detector shall be supplied with power from a power supply complying with EN54-4. 2. The approval of the detector is conditional upon the following requirements: Design, installation and commissioning are performed in accordance with the VESDA system design manual by installers accredited by the manufacturer. Each area is protected by a minimum of 2 holes. 3. The detector has been assessed for compliance with clause 5.15 Fire sensitivity (room protection). High sensitivity aspirating smoke detector Notes: 1. For compliance with CEA 4022, the detector shall be supplied with power from a power supply complying with EN 54-4. 2. The approval of the detector is conditional upon the following requirements: Design, installation and commissioning are performed in accordance with the VESDA system design manual by installers accredited by the manufacturer. Each area is protected by a minimum of 2 holes. 3. The detector has been assessed for compliance with clause 5.15 Fire sensitivity (room protection). LPCB Ref. No.

LaserFOCUS VLF 250

305c/01

LaserFOCUS VLF500

305c/02

Certificate No: 305d to EN 54-20: 2006 Certificated Products VESDA VLF-250 high sensitivity aspirating smoke detector Incorporating the following ancilliary equipment: - VIC-010 VESDAnet network card - VRT-V00 Remote VLF display (with 7 relays) - VRT-W100 Remote VLF display (no relays) - VRT-500 Remote relay unit (with 7 relays) 1) For compliance with clause 5.10 of EN 54-20 the detector shall be supplied with power from a power supply conforming with the requirements of EN 54-4. 2) The device is approved for sensitivity Classes A, B and C. The Class of any pipe/hole configuration and detector sensitivity must be determined using ASPIRE2. 3) System design, installation and commissioning shall be performed in accordance with the VESDA VLF product guide. Incorporating the following ancillary equipment: - VIC-010 VESDAnet network card - VRT-V00 Remote LaserFOCUS display (with 7 relays) - VRT-W00 Remote LaserFOCUS display (no relays) - VRT-500 Remote relay unit (with 7 relays) 1) For compliance with clause 5.10 of EN 54-20 the detector shall be supplied with power from a power supply conforming with the requirements of EN 54-4. 2) The device is approved for sensitivity Classes A, B and C. The Class of any pipe/hole configuration and detector sensitivity must be determined using ASPIRE2. 3) System design, installation and commissioning shall be performed in accordance with the VESDA VLF product guide. 4) Remote display, programmer and relay modules are also approved in a 19" LPCB Ref. No. 305d/01

VESDA VLF-500 high sensitivity aspirating smoke detector

305d/02

142

January 2009

SECTION 4.1: PART


Certificated Products VESDA VLC aspirating smoke detector sub rack. Approved configurations: - VLC-500 VLC Relays only (RO) version - VLC-505 VLC VESDAnet (N+VN) version - VLC-400 VLC Apollo (AP) version - VLC-800 VLC Tyco (MX) version - VLC-700 VLC Esser (EB) version Approved remote units with the VLC-505 VESDAnet (VN) version: - VRT-J00 Remote VLC display (with 7 relays) -VRT-K00 Remote VLC display (no relays) - VRT-500 Remote relay unit (with 7 relays) 1) For compliance with clause 5.10 of EN 54-20 the detector shall be supplied with power from a power supply conforming with the requirements of EN 54-4. 2) The device is approved for sensitivity Classes A, B and C. The Class of any pipe/hole configuration and detector sensitivity must be determined using ASPIRE2. 3) System design, installation and commissioning shall be performed in accordance with the VESDA VLF product guide. 4. Remote display, programmer and relay modules are also approved in a 19" sub rack. Approved Configurations: VLP-012 VLP detector with Display & Programme VLP-002 VLP detector with Display VLP-400 detector with Fire/OK LEDs only VLP-401 VLP detector with Programmer & Fire/OK LEDs VLP-100 VLP detector with OEM cover Approved remote units: VRT-100 Remote Programmer VRT-200 Remote VLP Display unit (with 7 relays) VRT-300 VESDAnet socket VRT-500 Remote Relay unit (with 7 relays) VRT-600 Remote VLP Display unit (without relays) 1) For compliance with clause 5.10 of EN 54-20 the detector shall be supplied with power from a power supply conforming with the requirements of EN 54-4. 2) The device is approved for sensitivity Classes A, B and C. The Class of any pipe/hole configuration and detector sensitivity must be determined using ASPIRE2. 3) System design, installation and commissioning shall be performed in accordance with the VESDA VLF product guide. 4) Remote display, programmer and relay modules are also approved in a 19" sub rack. Approved Configurations: VLS-600 VLS with 7 relays and Fire/OK LEDs VLS-204 VLS with 7 Relays and Display Module VLS-214 VLS with 7 Relays, Display and Program Module VLS-700 VLS with 12 relays and Fire/OK LEDs VLS-304 VLS with 12 Relays and Display Module VLS-314 VLS with 12 Relays, Display and Program Module VLS-100 VLS with 7 Relays and OEM cover VLS-500 VLS with 12 Relays and OEM cover Approved Remote Units: VRT-400 Remote VLS Display with 7 relays VRT-700 Remote VLS Display with no relays VRT-800 Remote VLS Display with 12 relays VRT-900 Remote VLS Relays -12 relays VRT-E00 Remote VLS Relays - 7 relays Notes: 1) For compliance with clause 5.10 of EN 54-20 the detector shall be supplied with power from a power supply conforming with the requirements of EN 54-4. 2) The device is approved for sensitivity Classes A, B and C. The Class of any pipe/hole configuration and detector sensitivity must be determined using ASPIRE2. 3) System design, installation and commissioning shall be performed in accordance with the VESDA VLS product guide. 4) Remote display, programmer and relay modules are also approved in a 19 sub rack. LPCB Ref. No. 305d/03

COMMERCIAL DETECTORS

VESDA VLP High sensitivity aspirating smoke detector

305d/04

VESDA VLS High sensitivity aspirating smoke detector

305d/05

January 2009

143

PART 3: SECTION 4.2


DOMESTIC ALARMS - SMOKE, HEAT AND CARBON MONOXIDE Statistics show that Government initiatives which have increased the amount of self-contained smoke alarms fitted in domestic dwellings have had a significant impact in reducing the amount of deaths and injuries caused by fire in the UK. Section 1: Fire detection and fire alarm systems of the Building Regulations 2000, Document B1 Fire Safety in Dwellings states that All new dwelling houses shall be provided with a fire detection and fire alarm system in accordance with the relevant recommendations of BS 5839-6:2004 to at least a Grade D, Category LD3 standard BS 5839-6:2004 Grade D requires a system of one or more mains-powered smoke alarms each with an integral standby supply (i.e. battery back-up). The system may in addition incorporate one or more mainspowered heat alarms, each with an integral standby supply. LPCBs list of approved products in this section is intended to help you select equipment that complies with these regulatory requirements. The initial approval and continued approval processes of these type of detectors are outlined in scheme document SD078. Products listed in this section have been approved to: BS 5446-1:2000 Fire detection and fire alarm devices for dwellings Part 1 Specification for smoke alarms BS 5446-2:2003 Fire detection and fire alarm devices for dwellings Part 2 Specification for heat alarms BS 5446-3:2005 Specification for smoke alarm kits for deaf and hard of hearing people EN 14604:2005 Smoke alarm devices EN 50291:2001 Carbon monoxide detectors (electrical) in domestic premises

For domestic applications, care needs to be taken over the correct choice of the type of detector, its siting and the condition of batteries in order to maintain the alarm in accordance with the manufacturers requirements. Further guidance is available from LPCB if required. Audit: Regular product auditing and regular factory inspections are carried out by LPCB ensuring high manufacturing standards and continued compliance with the applicable product standard. Note: 1. EN 14604:2005 supersedes BS 5446-1:2000 which was withdrawn in July 2008. Information concerning the date of withdrawal of conflicting standards in the foreword to EN 14604:2005 is incorrect. The correct data is given in the Foreword to the UK version of BS EN 14604:2005 and gives the date of withdrawal of BS 5446:1:2000 as July 2008. However, EN 14604:2005 is now a harmonised standard for the Construction Products Directive and CE marking will be required for most of the European market by 01 August 2008. It is therefore recommended that detectors are certificated to EN 14604:2005 as soon as possible.

Everday Technology Co. Limited


No.8, Lane, 492 Ba-Der Street, Shulin 238, Taipei Hsien, Taiwan ROC Tel: +886 2 2668 9668 Fax: +862 2 2668 9666 E-mail: sales@everday.com Website: www.everday.com
Certificate No: 512c to BS 5446-1: 2000

Smoke Alarm
Certificated Products M816VS Stand alone photoelectric smoke alarm detector with RF transmitter. Note: The RF transmitter is not approved. LPCB Ref. No. 512c/01

144

January 2009

SECTION 4.2: PART

DOMESTIC ALARMS - SMOKE, HEAT AND CARBON MONOXIDE

Eyston Company Ltd


27 Zhen Tian South Road, Wei Xing Industrial Zone, Yan Tian, Feng Gang, Dongguan, Guangdong, Peoples Republic of China Tel: +852 25573135 Fax: +852 28970249 E-mail: tracylo@eyston.com Website: www.eyston.com
Certificate No: 679a to BS 5446-1: 2000

Smoke Alarms
Certificated Products SD-176H SD-196H SD-170H SD-1982 SD-1782 Battery operated ionisation smoke alarm with alarm silence feature Battery operated photoelectric smoke alarm with alarm silence feature Battery operated ionization smoke alarm 9v battery operated photoelectric smoke alarm with alarm silence feature 9v battery operated ionisation smoke alarm with alarm silence feature LPCB Ref. No. 679a/01 679a/02 679a/03 679a/04 679a/05

Certificate No: 679b to EN 14604: 2005

Smoke Alarm
Certificated Products SD-176H SD-170H Battery operated ionisation smoke alarm with alarm silence feature Battery operated ionisation smoke alarm LPCB Ref. No. 679b/01 679b/02

FireAngel Ltd (A Division of Sprue Aegis plc)


The TechnoCentre, Puma Way, Coventry CV1 2TT UK Tel: +44 (0)24 7623 6600 Fax: +44 (0)24 7623 6603 Website: www.fireangel.co.uk
Certificate No: 651c to EN 50291: 2001

Carbon Monoxide Alarms


Certificated Products CO-828 CO-808 Carbon Monoxide Alarm - LCD Carbon Monoxide Alarm - LED LPCB Ref. No. 651c/01 651c/02

Certificate No: 651d to EN 14604: 2005 Certificate No: 651a to BS 5446-1: 2000

Smoke Alarms
Certificated Products EZ-212 SI-1 SO-1 SI-6 SO-6 SI-10 SO-10 BI-1 SI 601 SI 610 WSI 601 Hard Wired Smoke Alarm 9v battery operated ionisation smoke alarm with alarm silence feature 9v battery operated photoelectric smoke alarm with alarm silence feature 9v battery operated ionisation smoke alarm with alarm silence feature and 10 year lithium battery 9v battery operated photoelectric smoke alarm with alarm silence feature and 10 year lithium battery Battery operated ionisation smoke alarm with alarm silence feature Battery operated photoelectric smoke alarm with alarm silence feature 9v battery operated ionisation smoke alarm Battery operated ionisation smoke alarm Battery operated ionisation smoke alarm Battery operated ionisation smoke alarm with RF transmitter module LPCB Ref. No. 651a/01 651a/02 651a/03 651a/04 651a/05 651a/06 651a/07 651a/08 651d/01 651d/02 651d/03

January 2009

145

PART 3: SECTION 4.2


DOMESTIC ALARMS - SMOKE, HEAT AND CARBON MONOXIDE
Certificated Products SO 601 SO 610 WSO 610 Note: The RF transmitter module is not covered within the scope of this approval Battery operated optical smoke alarm Battery operated optical smoke alarm Battery operated optical smoke alarm - with RF transmitter module Note: The RF transmitter module is not covered within the scope of this approval LPCB Ref. No. 651d/04 651d/05 651d/09

Visonic
24 Habarzel Street, Tel Aviv 69710, Israel Tel: +44 (0)870 7300810 Fax: +44 (0)870 7300801 E-mail: DalitS@visonic.com Website: www.visonic.com
Certificate No: 512e to EN 50291: 2001

Carbon Monoxide Alarms


Certificated Products MCT-442 Type A battery operated carbon monoxide alarm LPCB Ref. No. 512e/01

146

January 2009

SECTION 5: PART

MANUAL CALL POINTS

The purpose of a manual call point is to enable a person discovering a fire to initiate the operation of a fire alarm system so that appropriate measures can be taken. Therefore it is important for the manual call point to be recognizable and simple to use. For this reason, the European standard has attempted to standardised their appearance and function. There are basically two types of manual call points which are related to the method of operation. - Type A: direct operation (single action). - Type B: indirect operation (double action). Both types require the breaking or the visible displacement by change of position of a frangible element forming part of the front face. Guidance on the selection, siting and speed of response should be sought from the applicable installation rule or code of practice (e.g. BS 5839-1). For example BS 5839-1 recommends only type A with a speed of evacuation signal within 3 seconds. Other codes of practice, may require a type B installation. This section lists manual call points approved for use in fire detection and fire alarm systems in buildings. The initial approval and continued approval processes for manual call points are outlined in scheme document SD041. Products listed in this section have been approved to: EN 54-11:2001 Manual call points EN 54-11:2001 + A1:2005 Manual call points ISO 7240-11:2005 Manual call points

Audit: Regular product auditing and regular factory inspections are carried out by LPCB ensuring high manufacturing standards and continued compliance with the applicable product standard. Notes: 1. EN 54-11:2001 supersedes BS 5839-2:1983 which was withdrawn in November 2003. EN 54-11:2001 is now a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market from 1 September 2008. 2. Since the LPCB uses national and international standards for the listing of products, in some instances the requirements of these standards may conflict with the recommendations of local codes of practice. We recommend that specifiers seek advice from the relevant local authorities and amend their specifications accordingly.

Advanced Electronics Limited


34 Moorland Way, Nelson Park, Cramlington, Northumberland NE23 1WE UK Tel: +44 (0)1670 707111 Fax: +44 (0)1670 707222 Website: www.Advel.co.uk
Certificate No: 010w to EN 54-11:2001 and EN 54-17:2005 Certificated Products 58100-908 ADV Analogue addressable manual call point with short circuit isolator and surface mounting box. LPCB Ref. No. 010w/03

January 2009

147

PART 3: SECTION 5
MANUAL CALL POINTS

AMPAC Industries
97 Walters Drive, Osbourne Park, Western Australia 6017, Australia Tel: +618 (9242) 3333 Fax: +618 (9242) 3334 Website: www.ampac.net
Certificate No: 010n to EN 54-11:2001 Certificate No: 010w to EN 54-11:2001 and EN 54-17:2005 Certificated Products 213-0050 213-0052 213-0051 213-0053 Analogue addressable manual call point with surface mounting box Analogue addressable manual call point with surface mounting box Analogue addressable manual call point with short circuit isolator and surface mounting box Analogue addressable manual call point with short circuit isolator and surface mounting box LPCB Ref. No. 010n/02 010n/06 010w/01 010w/03

Apollo Fire Detectors Limited


36 Brookside Road, Havant, Hampshire PO9 1JR UK Tel: +44 (0)2392 492412 Fax: +44 (0)2392 492754 E-mail: enquiries@apollo-fire.co.uk Sales Enquiries Germany, Apollo Deutschland GmbH Tel: +49 5241 330 60 Fax: +49 5241 330 629 E-mail: info@apollo-feuer.de

Sales Enquiries Spain, Apollo Espana Tel: +34 627 988 061 Fax: +34 949 335 289 E-mail: apollo.espana@apollo-fire.com

Sales Enquiries, China Apollo Fire Detectors Limited, Shanghai representative office Tel: +86 21 5237 0922 Fax: +86 21 5237 0920 E-mail: tony.ye@apollo-fire.com

Certificate No: 010d to BS 5839: Part 2:1983 Certificate No: 010n to EN 54-11: 2001 Certificate No: 010w to EN 54-11: 2001 and EN 54-17: 2005 Certificated Products 55000-900 XP95 55000-940 XP95 IS 55000-950 XP95 58000-900 Discovery 58000-910 Discovery 58000-920 Discovery Analogue addressable flush and surface mounted manual call point Certificated with Apollo, Series 90 and XP95 communication protocols Analogue addressable intrinsically safe manual call point Certificated with Apollo, Series 90 and XP95 communication protocols Analogue addressable waterproof manual call point Certificated with Apollo, Series 90 and XP95 communication protocols Analogue addressable flush and surface mounted manual call point Certificated with Series 90, XP95 and Discovery digital communication protocols Analogue addressable flush mounted manual call point Certificated with Series 90, XP95 and Discovery digital communication protocols Analogue addressable surface mounted manual call point Certificated with Series 90, XP95 and Discovery digital communication protocols LPCB Ref. No. 010d/06 010d/03 010d/04 010d/05 010d/05 010d/05

148

January 2009

SECTION 5: PART
Certificated Products 59000-910 XPlorer 55100-905 XP95 58100-910 Discovery 55100-908 XP95 58100-908 Discovery 58100-905 Discovery XPA-MC-14006-APO Analogue addressable surface mounted manual call point Certificated with Series 90 and XP95 digital communication protocols Certificated with the Burgess V3NCSET7 Mk 1 microswitch Analogue addressable manual call point with surface mounting box Analogue addressable manual call point with surface mounting box Analogue addressable manual call point with short circuit isolator and surface mounting box Analogue addressable manual call point with short circuit isolator and surface mounting box Analogue addressable manual call point with short circuit isolator, glass frangible element and surface mounting box Xpander addressable radio linked manual call point Notes: 1) The device must be used with the following batteries only: - MN1500 LR6 - 1.5 volt alkaline AA cells 2) The radio link functionality is not included within the scope of approval Analogue addressable waterproof manual call point Analogue addressable intrinsically safe manual call point. Analogue addressable waterproof manual call point with short circuit isolator LPCB Ref. No. 010n/01 010n/02 010n/06 010w/01 010w/03 010w/05 010ae/01

MANUAL CALL POINTS

58100-950 Discovery 55100-940 XP95IS 58100-951 Discovery

010n/08 010n/09 010w/06

Bentel Security s.r.l.


Via Gabbiano, n.22, Z.Ind. Le S.Scolastica, Corropoli, Teramo 64013, Italy Tel: +39 0861 839060 Fax: +39 0861 839065 E-mail: info@bentelsecurity.com Website: www.bentelsecurity.com
Certificate No: 681n to EN 54-11: 2001 + A1: 2005 Certificated Products FC420CP FC421CP Addressable Type A indoor manual call point Addressable Type A outdoor manual call point LPCB Ref. No. 681n/01 681n/02

Cooper Industries Inc


Wheatley Hall Road, Doncaster, South Yorkshire DN2 4NB UK Tel: +44 (0)1302 303303 Fax: +44 (0)1302 367155 E-mail: sales@cooper-ls.com Website: www.cooper-ls.com
Certificate No: 378d to EN 54-11: 2001 and EN 54-17: 2005 Certificated Products CBG 370S CBG 370 PAJ3034900 CBG 370WP PAJ3035100 Addressable type A glass indoor manual call point, with surface mount back box Addressable type A glass indoor manual call point, flush mounted Addressable type A plastic re-settable indoor manual call point with surface mount back box Addressable weatherproof type A glass indoor/outdoor manual call point Addressable weatherproof type A plastic re-settable indoor/outdoor manual call point LPCB Ref. No. 378d/05 378d/06 378d/07 378d/08 378d/09

January 2009

149

PART 3: SECTION 5
MANUAL CALL POINTS

Emergi-Lite Safety Systems (Thomas & Betts Ltd)


Bruntcliffe Lane, Morley, Leeds LS27 9LL UK Tel: +44 (0)113 2810600 Fax: +44 (0)113 2810601 Website: www.emergi-lite.co.uk
Certificate No: 010n to EN 54-11:2001 Certificate No: 010w to EN 54-11:2001 and EN 54-17:2005 Certificated Products FA95-400 FADY-400-ISO Analogue addressable manual call point with surface mounting box Analogue addressable manual call point with short circuit isolator and surface mounting box LPCB Ref. No. 010n/02 010w/03

Emirates Fire Fighting Equipment Factory (FIREX)


Industrial Area 13, P.O.Box 22436, Sharjah, UAE Tel: +971 6 5340300 Fax: +971 6 5340090 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 506d to EN 54-11: 2001 Certificated Products FX-0217 Conventional indoor surface/flush mounting manual call point Note: Approved for surface mount use when used with the AHMB-0217 back box LPCB Ref. No. 506d/01

Accessories: AHMB-0217 back box for surface mounting

EMS Radio Fire & Security Limited


Technology House, Herne Bay West Trading Estate, Herne Bay, Kent CT6 8JZ UK Tel: +44 (0)1227 369570 Fax: +44 (0)1227 369679 E-mail: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Certificate No: 786a to EN 54-11: 2001 + A1: 2005 Certificated Products XP-200-002 Fire-Cell addressable radio linked manual call point Notes: 1) The device must be used with the following batteries only: - MN1500 LR6 - 1.5 volt alkaline AA cells 2) The radio link functionality is not included within the scope of approval LPCB Ref. No. 786a/01

Everday Technology Co. Limited


No.8, Lane, 492 Ba-Der Street, Shulin 238, Taipei Hsien, Taiwan ROC Tel: +886 2 2668 9668 Fax: +862 2 2668 9666 E-mail: sales@everday.com Website: www.everday.com
Certificate No: 512f to EN 54-11: 2001 + A1: 2005

150

January 2009

SECTION 5: PART
Manual Call Points
Certificated Products EM921 EM921-F EM921-TC EM921-FTC Accessories: EM921B1 EM921B2 EM921B3 Conventional manual call point with LED Conventional manual call point with flashy LED Convetnional manual call point with LED and transparent cover Conventional manual call point with flashy LED and transparent cover LPCB Ref. No. 512f/01 512f/02 512f/03 512f/04

MANUAL CALL POINTS

Regular mounting base, 28mm High mounting base, 40mm High mounting base, 55m

Fireguard Safety Equipment Co Ltd


2nd Floor, 145-147 St Johns Street, London EC1V 4PY UK Tel: +44 (0)8450 751042 Fax: +44 (0)8450 751043 E-mail: info@fireguard-uk.com Website: www.fireguard-uk.com
Certificate No: 512f to EN 54-11: 2001 + A1: 2005 Certificated Products Fireguard FG921-FTC Conventional manual call point with flashy LED and transparent cover LPCB Ref. No. 512f/04

Accessories: Fireguard FG921B1 Regular mounting base, 28mm Fireguard FG921B2 High mounting base, 40mm Fireguard FG921B3 High mounting base, 55m

FIREX Protection System Technology Ltd


28-38 Desborough Street, High Wycombe, Bucks UK Tel: +44 (0)1494 601077 Fax: +44 (0)1494 601011 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 548g to EN 54-11: 2001 Certificated Products FX9201 FX9201I Conventional manual call point Intelligent manual call point LPCB Ref. No. 548g/01 548g/02

Fulleon Limited
Llantarnam Park, Cwmbran, Gwent NP44 3AW UK Tel: +44 (0)1633 628500 Fax: +44 (0)1633 866346 E-mail: sales@fulleon.co.uk Website: www.fulleon.com
Certificate No: 378c to EN 54: Part 11: 2001 Certificated Products CX/G/R/BB CX/P/R/NB CX/P/R/BB CXL/GP/R/BB CXL/GP/R/NB Conventional re-settable indoor manual call point, with surface mount back box* Conventional indoor manual call point, flush mounted* Conventional indoor manual call point, with surface mount back box* Conventional type A glass or plastic re-settable indoor manual call point, with surface mount back box Conventional type A glass or plastic re-settable indoor manual call point, flush mounted LPCB Ref. No. 378c/01 378c/02 378c/02 378c/03 378c/03

January 2009

151

PART 3: SECTION 5
MANUAL CALL POINTS
Certificated Products CXL/GP/R/WP CXL/GP/R/BB CXL/GP/R/NB CXL/GP/R/WP Conventional type A Conventional type A mount back box Conventional type A Conventional type A glass or plastic re-settable indoor/outdoor manual call point glass or plastic re-settable indoor manual call point, with surface glass or plastic re-settable indoor manual call point, flush mounted glass or plastic re-settable indoor/outdoor manual call point LPCB Ref. No. 378c/04 378c/05 378c/05 378c/06

* Approved with V4NCSET7 Mk1 or V4NSET7-UL micro switches only. Accessories: /BB surface mounted (plastic back box)

GE Security (Africa) trading as Ziton


Ziton House, 555 Voortrekker Road, Maitland 7405, Republic of South Africa Tel: +27 21 5066000 Fax: +27 21 5066100 Website: www.ziton.com
Certificate No: 092r to EN 54-11: 2001 Certificated Products ZP785-3 Analogue addressable manual call point LPCB Ref. No. 092r/01

GE Security (Aritech)
Kelvinstraat, 7, NL-6003 DH Weert, The Netherlands Tel: +31 (495) 456735 Fax: +31 (495) 550042 Website: www.gesecurity.com
Certificate No: 010n to EN 54-11: 2001 Certificate No: 010w to EN 54-11: 2001 and EN 54-17: 2005 Certificated Products DMN 960 DMN 990 DMN 960I DMN 990I Analogue addressable manual call point with surface mounting box Analogue addressable manual call point with surface mounting box Analogue addressable manual call point with short circuit isolator and surface mounting box Analogue addressable manual call point with short circuit isolator and surface mounting box LPCB Ref. No. 010n/02 010n/06 010w/01 010w/03

GE Security Inc
5 North Main Street, Pittsfield, ME 04967, USA Tel: +1 207 487 3104 Fax: +1 207 487 5526 E-mail: leon.newsome@ge.com Website: www.gesecurity.com European Sales: Rudford Estate, Ford Aerodrome, Arundel, West Sussex BN18 0BE UK Tel: +44 (0)1903 711 440 Fax: +44 (0)1903 711 448 E-mail: info@estinternational.com

Certificate No: 262p to EN 54-11: 2001 Certificate No: 092r to EN 54-11: 2001

152

January 2009

SECTION 5: PART
Certificated Products SIGI-271 EA785-3 Accessories SR3T-P Surface mounted box ETT1-P Flush mounted box Digital addressable indoor manual call point, surface or flush mounted Analogue addressable manual call point LPCB Ref. No. 262p/01 092r/01

MANUAL CALL POINTS

Gent By Honeywell
140 Waterside Road, Hamilton Industrial Park, Leicester LE5 1TN UK Tel: +44 (0)116 246 2000 Fax: +44 (0)116 246 2300 E-mail: gent_enquiry@gent.co.uk Website: www.gent.co.uk Middle East Sales Enquiries: E-mail: gent.export@honeywell.com

Certificate No: 042c to BS 5839: Part 2 Certificate No: 567c to BS 5839: Part 2 Certificate No: 042aq to EN 54-11: 2001 Certificated Products 1195 OR 34800 78150-52NM 34800 34800-EN Vigilon 34842-EN Vigilon S4-34800 Flush and surface mounted manual call point Flush and surface mounted addressable manual call point Note: Approved for flush mounting when using 13480-29 flush mounting plate Flush and surface mounted addressable manual call point. Note: Approved for flush mounting when using 78150-98NM flush mounting plate Flush and surface mounted addressable manual call point (indoor) Note: Approved for flush mounting when using 13480-29 flush mounting plate Analogue addressable Type A surface mount manual call point Analogue addressable Type A surface mount manual call point with protective cover Analogue addressable Type A indoor manual call point (S4-34895 surface mount back box) Notes: 1) Approved for use with re-settable and non re-settable element Analogue addressable Type A indoor manual call point with protective cover (S4-34895 surface mount back box) Notes: 1) Approved for use with re-settable and non re-settable element LPCB Ref. No. 042c/01 042c/03 042c/05 567c/01 042aq/03 042aq/04 042aq/01

S4-34842

042aq/02

Accessories: S4-34895 surface mount back box

Global System Technology Plc


Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire LE65 1RT UK Tel: +44 (0)1283 225 478 Fax: +44 (0)1283 222 039 E-mail: info@gst.uk.com Website: www.gst.uk.com
Certificate No: 548g to EN 54-11: 2001 Certificated Products C-9202 I-9202 Conventional manual call point Intelligent manual call point LPCB Ref. No. 548g/01 548g/02

January 2009

153

PART 3: SECTION 5
MANUAL CALL POINTS

Group 4 Securicor Plc


Manor Royal, The Manor, Crawley, West Sussex RH10 9UN UK Tel: +44 (0)20 87707000 Fax: +44 (0)20 87722531 E-mail: allan.rignall@uae.g4s.com Website: www.g4s.com
Certificate No: 548g to EN 54-11: 2001 Certificated Products GS202C GS202I Conventional manual call point Intelligent manual call point LPCB Ref. No. 548g/01 548g/02

Gulf Security Technology Co. Ltd (Manufacturing Division of Global System Technology PLC)
No. 80 Changjiang East Road, Economic & Technological Development Zone, Qinhuangdao, Hebei Province 066004, Peoples Republic of China Tel: +86 0335 8502528 Fax: +86 0335 8508942 E-mail: gst@gst.com.cn Website: www.gst.com.cn
Certificate No: 548g to EN 54-11: 2001 Certificated Products J-SAF-GST9211 (E) J-SAM-GST9111 (E) Conventional manual call point Intelligent manual call point LPCB Ref. No. 548g/01 548g/02

HDR
Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260133 Fax: +44 (0)1634 260132 E-mail: info@hochikieurope.com Website: www.hochikieurope.com
Certificate No: 164j to EN 54-11:2001 Certificated Products 1440270 1440300 Addressable Manual Call Point (SR and SR1T mounting boxes) Weatherproof Addressable Manual Call Point (SR and SR1T mounting boxes) LPCB Ref. No. 164j/01 164j/04

Ancillaries: SR Surface mounting plastic box SR1T Surface mounting plastic box c/w 1 terminal

Hochiki Europe (UK) Limited


Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260133 Fax: +44 (0)1634 260132 Website: www.hochikieurope.com
Certificate No: 164j to EN 54-11: 2001

154

January 2009

SECTION 5: PART
Certificated Products HCP-E(HFP) HCP-EF HCP-E(DPS) HCP-W(HFP) HCP-W(DPS) Addressable Manual Call Point (SR and SR1T mounting boxes) Addressable Manual Call Point - French - (SR and SR1T mounting boxes) Addressable Manual Call Point - with Dual Pole Switching - (SR and SR1T mounting boxes) Weather Proof Addressable Manual Call Point (SR and SR1T mounting boxes) Weather Proof Addressable Manual Call Point with Dual Pole Switching (SR and SR1T mounting boxes) LPCB Ref. No. 164j/01 164j/02 164j/03 164j/04 164j/05

MANUAL CALL POINTS

Notes: 1) Approved in normal mode only 2) Include Swedish and Finnish language variants Accessories: SR Surface mounting plastic box SR1T Surface mounting plastic box c/w 1 terminal

Horing LIH Industrial Co Ltd


No. 17-6, Ai-Chien Road, Hu-Hsi Village, Yuan-Shan Hsiang (264), Ilan Hsien, Taiwan ROC Tel: +886 2 22487599 Fax: +886 2 22407752
Certificate No: 506d to EN 54-11: 2001 Certificated Products AH-0217 Conventional indoor surface/flush mounting manual call point Note: Approved for surface mount use when used with the AHMB-0217 back box LPCB Ref. No. 506d/01

Accessories: AHMB-0217 back box for surface mounting

IMCI Services Ltd (Context Plus)


Export House, 175 Mauldeth Road, Fallowfield, Manchester M16 6SG UK Tel: +44 (0)161 257 2541 Fax: +44 (0)161 225 8817 Website: www.exportsales.com
Certificate No: 010w to EN 54-11:2001 and EN 54-17:2005 Certificated Products 55100-908 IMC Analogue addressable manual call point with short circuit isolator and surface mounting box. LPCB Ref. No. 010w/01

IP Tec General Trading LLC


Shop 28/34 Gargash Center, Deira, Nasser Square, Dubai, UAE Tel: +971 4 223 4446 Fax: +971 4 221 9395 E-mail: sales@iptecworld.com Website: www.ipteccctv.com
Certificate No: 512F - (CL-2) to EN 54-11:2001 + A1: 2005 Certificated Products Apachi AP921 Conventional manual call point with LED LPCB Ref. No. 512f/01

January 2009

155

PART 3: SECTION 5
MANUAL CALL POINTS
Certificated Products Apachi AP921-TC Accessories: Apachi AP21B1 Apachi AP921B2 Apachi AP921B3 Regular mounting base, 28mm High mounting base, 40mm High mounting base, 55mm Conventional manual call point with LED and transparent cover LPCB Ref. No. 512f/03

KAC Alarm Company Limited


15-19 Trescott Road, Trafford Park, Smallwood, Redditch, Worcester B98 7AH UK Tel: +44 (0)1527 406655 Fax: +44 (0)1527 406677 E-mail: sales@kac.co.uk OR marketing@kac.co.uk Website: www.kac.co.uk
Certificate No: 166b to EN 54-11: 2001 Certificated Products WR2001 WR2012 WR2004 WR2061 WR2072 WR2101 WR3001 WR3101 WR3061 WR3072 WR3631 WR4001 WR4061 WR4061 WR4031 WR4072 WR7/2001 WR7/2004 WR7/2012 WR7/2061 WR7/2072 WR7/2101 WR7/3001 WR7/3061 WR7/3072 WR7/3101 MCP545-1 MCP545-2 MCP545-3 MCP545-4 MCP1A-Rxxxxx MCP1B-Rxxxxx MCP2A-Rxxxxx MCP2B-Rxxxxx Indoor manual call point, flush mounted (single pole changeover). Indoor manual call point, flush mounted. Indoor manual call point, flush mounted. Indoor manual call point, flush mounted. Indoor manual call point, flush mounted. Indoor manual call point, flush mounted. Indoor manual call point, flush mounted (single pole changeover). Indoor manual call point, flush mounted. Indoor manual call point, flush mounted. Indoor manual call point, flush mounted. Indoor manual call point, flush mounted. Outdoor manual call point, (single pole changeover). R1-R2 (2.5W resistors) Outdoor manual call point. Outdoor manual call point with LED and series and shunt resistors. Outdoor manual call point. Outdoor manual call point with series monitoring resistor. Rainproof manual call point (single pole change over, surface mounted). Rainproof manual call point with series monitoring resistor, surface mounted. Rainproof manual call point with two series monitoring resistors, surface mounted. Rainproof manual call point (series monitoring resistors & LED) surface mounted. Rainproof manual call point with series monitoring resistor, surface mounted. Rainproof manual call point, surface mounted. Rainproof manual call point single pole changeover. Rainproof manual call point with LED and series and shunt resistors, surface mounted. Rainproof manual call point with series monitoring resistor, surface mounted. Rainproof manual call point, surface mounted. Indoor surface mounting addressable manual call point Indoor flush mounting addressable manual call point Outdoor surface mounting addressable manual call point Outdoor surface mounting addressable manual call point Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Notes: 1) xxxxx indicates the series resistor value. 039xx (lowest 39 ohms), 4K7xx (highest 4.7 k ohms) 2) xxxSx (Surface mounted) xxxFx (Flush mounted) 3) xxxxG (Glass element) xxxxF (Flexible element) 4) The MCP1-2 Series manual call points LPCB Ref. No. 166b/39-166b/42 are approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting addressable call point (System Sensor 500 series protocol) Indoor/Outdoor surface/flush mounting addressable call point (Honeywell 500 series protocol) Indoor/Outdoor surface/flush mounting conventional call point LPCB Ref. No. 166b/01 166b/02 166b/03 166b/04 166b/05 166b/06 166b/07 166b/08 166b/09 166b/10 166b/11 166b/12 166b/13 166b/14 166b/15 166b/16 166b/25 166b/26 166b/27 166b/28 166b/29 166b/30 166b/31 166b/32 166b/33 166b/34 166b/35 166b/36 166b/37 166b/38 166b/39 166b/40 166b/41 166b/42

MCP3A-R000xx MCP4A-R000xx MCP5A-RP01xx MCP5A-RP03xx MCP7A-RC01xx

166b/43 166b/44 166b/45 166b/47 166b/49

156

January 2009

SECTION 5: PART
Certificated Products MCP7B-RC01xx Indoor/Outdoor surface/flush mounting conventional call point Notes: 1) Sx (Surface mounted) Fx (Flush mounted) 2) xG (Glass element) xF (Flexible element) 3) The MCP3-7 Series manual call points LPCB Ref. No. 166b/43-166b/50 are approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) Outdoor surface mounting conventional waterproof call point Outdoor surface mounting conventional waterproof call point Outdoor surface mounting conventional waterproof call point Outdoor surface mounting conventional waterproof call point Notes: 1) xxx Sx indicates the series resistor value. 039Sx (lowest 39 ohms), 4K7Sx (highest 4.7 k ohms) 2) xxxSG (Glass element) xxxSF (Flexible element) 3) The WCP1-2 Series waterproof manual call points LPCB Ref. No.166b/51-166b/54 are approved with Honeywell micro switch ZW10F90AW1 Outdoor surface mounting conventional waterproof call point Outdoor surface mounting conventional waterproof call point Outdoor surface mounting addressable waterproof call point (System Sensor 500 series protocol) Outdoor surface mounting addressable waterproof call point (Honeywell 500 series protocol) Outdoor surface mounting conventional waterproof call point Outdoor surface mounting conventional waterproof call point Notes: 1) G (Glass element) F (Flexible element) 2) The WCP3-7 Series waterproof manual call points LPCB Ref. No. 166b/55-166b/62 are approved with Honeywell micro switch ZW10F90AW1 Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Notes: 1) xxxxx indicates the series resistor value. 039xx (lowest 39 ohms), 4K7xx (highest 4.7 k ohms) 2) xxxSx (Surface mounted) xxxFx (Flush mounted) 3) xxxxG (Glass element) xxxxF (Flexible element) 4) The MCP1-2 Series manual call points LPCB Ref. No. 166b/39-166b/42 are approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Indoor/Outdoor surface/flush mounting conventional call point Notes: 1) Sx (Surface mounted) Fx (Flush mounted) 2) xG (Glass element) xF (Flexible element) 3) The MCP3-7 Series manual call points LPCB Ref. No. 166b/43-166b/50 are approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) LPCB Ref. No. 166b/50

MANUAL CALL POINTS

WCP1A-RxxxSx WCP1B-RxxxSx WCP2A-RxxxSx WCP2B-RxxxSx

166b/51 166b/52 166b/53 166b/54

WCP3A-R000Sx WCP4A-R000Sx WCP5A-RP01Sx WCP5A-RP03Sx WCP7A-RC01Sx WCP7B-RC01Sx

166b/55 166b/56 166b/57 166b/59 166b/61 166b/62

MCP1A-Rxxxxx-01IS MCP1B-Rxxxxx-01IS MCP2A-Rxxxxx-01IS MCP2B-Rxxxxx-01IS

166b/39 166b/40 166b/41 166b/42

MCP3A-R000xx-01IS MCP4A-R000xx-01IS MCP7A-RC01xx-01IS MCP7B-RC01xx-01IS

166b/43 166b/44 166b/49 166b/50

Accessories: (1) SR Surface mounting plastic box (1) SR1T Surface mounting plastic box c/w 1 terminal (1) SR2T Surface mounting plastic box c/w 2 terminal (1) SR3T Surface mounting plastic box c/w 3 terminal (1) SR4T Surface mounting plastic box c/w 4 terminal (1) MR Surface mounting metal box (1) ETT European Terminal Tray ETT 1, 2 & 3 (1) L Earth Continuity Link (1) BZR/1 Bazel Type 1 (1) BZR/2 Bazel Type 2 (1) BZR/3 Bazel Type 3 (1) M141 Spacer Piece (1) PTR Pattress PTR, PTRE, PTR2T, PTR2TE, PTR3T & PTR3TE (1) C Hinged Cover Note: 1) The above accessories are only supplied with MCP/WCP1-7 Series manual call points LPCB Ref. No. 166b/39-166b/62

January 2009

157

PART 3: SECTION 5
MANUAL CALL POINTS
World Series Manual Call points are approved with the following switch combinations: Otehall Otehall Otehall 382430 95/89S 382431 Honeywell V5T010TB3X144 Honeywell V5T020TBX145 Burgess XG3 Burgess GA43

WR2001 WR7/2001 WR2101 WR7/2101 WR2004 WR7/2004 WR2012 WR7/2012 WR2061 WR7/2061 WR2072 WR7/2072 WR3001 WR7/3001 WR3061 WR7/3061 WR3072 WR7/3072 WR3101 WR7/3101 WR3631

Certificate No: 166e to EN 54-11: 2001 and EN 54-17: 2005 Certificated Products MCP5A-RP02xx MCP5A-RP04xx Indoor/Outdoor surface/flush mounting addressable call point with short circuit isolator (System Sensor 500 series protocol) Indoor/Outdoor surface/flush mounting addressable call point with short circuit isolator (Honeywell 500 series protocol) Notes: 1) Sx (Surface mounted) Fx (Flush mounted) 2) xG (Glass element) xF (Flexible element) 3) The above manual call points are approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) Outdoor surface mounting addressable waterproof call point with short circuit isolator (System Sensor 500 series protocol) Outdoor surface mounting addressable waterproof call point with short circuit isolator (Honeywell 500 series protocol) Notes: 1) G (Glass element) F (Flexible element) 2) The above waterproof manual call points are approved with Honeywell microswitch ZW10F90AW1 LPCB Ref. No. 166e/01 166e/02

WCP5A-RP02Sx WCP5A-RP04Sx

166e/03 166e/04

Accessories: SR Surface mounting plastic box SR1T Surface mounting plastic box c/w 1 terminal SR2T Surface mounting plastic box c/w 2 terminal SR3T Surface mounting plastic box c/w 3 terminal SR4T Surface mounting plastic box c/w 4 terminal MR Surface mounting metal box ETT European Terminal Tray ETT 1, 2 & 3 L Earth Continuity Link BZR/1 Bazel Type 1 BZR/2 Bazel Type 2 BZR/3 Bazel Type 3 M141 Spacer Piece PTR Pattress PTR, PTRE, PTR2T, PTR2TE, PTR3T & PTR3TE C Hinged Cover

158

January 2009

SECTION 5: PART

MANUAL CALL POINTS

Morley-IAS Fire Systems By Honeywell


Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@morleyias.co.uk Website: www.morley-ias.co.uk
Certificate No: 166e to EN 54-11: 2001 and EN 54-17: 2005 Certificated Products M1-MCP-xxxx-1 Indoor/Outdoor surface/flush mounting addressable call point with short circuit isolator (Honeywell 500 series protocol) Notes: 1) Sx (Surface mounted) Fx (Flush mounted) 2) xG (Glass element) xF (Flexible element) 3) The above manual call point is approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) LPCB Ref. No. 166e/02

Accessories: SR Surface mounting plastic box SR1T Surface mounting plastic box c/w 1 terminal SR2T Surface mounting plastic box c/w 2 terminal SR3T Surface mounting plastic box c/w 3 terminal SR4T Surface mounting plastic box c/w 4 terminal MR Surface mounting metal box ETT European Terminal Tray ETT 1, 2 & 3 L Earth Continuity Link BZR/1 Bazel Type 1 BZR/2 Bazel Type 2 BZR/3 Bazel Type 3 M141 Spacer Piece PTR Pattress PTR, PTRE, PTR2T, PTR2TE, PTR3T & PTR3TE C Hinged Cover

Napco Gulf Security Group


P.O. Box 54533, Dubai Airport Free Zone, UAE Tel: +971 4 2997703 Fax: +971 4 2997704 E-mail: info@napcogulfsecurity.com Website: www.napcogulfsecurity.com
Certificate No: 548g to EN 54-11: 2001 Certificated Products NC-202 NI-202 Conventional manual call point Intelligent manual call point LPCB Ref. No. 548g/01 548g/02

Notifier By Honeywell
Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@notifiersystems.co.uk Website: www.notifierfiresystems.co.uk
Certificate No: 166e to EN 54-11: 2001 and EN 54-17: 2005 Certificated Products M700KAC/-xx Indoor/Outdoor surface/flush mounting addressable call point with short circuit isolator (System Sensor 500 series protocol) Notes: LPCB Ref. No. 166e/01

January 2009

159

PART 3: SECTION 5
MANUAL CALL POINTS
Certificated Products 1) Sx (Surface mounted) Fx (Flush mounted) 2) xG (Glass element) xF (Flexible element) 3) The above manual call point is approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) Accessories: SR Surface mounting plastic box SR1T Surface mounting plastic box c/w 1 terminal SR2T Surface mounting plastic box c/w 2 terminal SR3T Surface mounting plastic box c/w 3 terminal SR4T Surface mounting plastic box c/w 4 terminal MR Surface mounting metal box ETT European Terminal Tray ETT 1, 2 & 3 L Earth Continuity Link BZR/1 Bazel Type 1 BZR/2 Bazel Type 2 BZR/3 Bazel Type 3 M141 Spacer Piece PTR Pattress PTR, PTRE, PTR2T, PTR2TE, PTR3T & PTR3TE C Hinged Cover LPCB Ref. No.

Photain Controls
8 New Market Court, Chippenham Drive, Kingston, Milton Keynes BN18 0BE UK Tel: 01908 281981 Fax: 01908 282554 E-mail: john.davies@ge.com
Certificate No: 092r to EN 54-11: 2001 Certificated Products BGU12000LED Analogue addressable manual call point LPCB Ref. No. 092r/01

Protec Fire Detection plc


Protec House, Churchill Way, Nelson, Lancashire BB9 6RT UK Tel: +44 (0)1282 717171 Fax: +44 (0)1282 717273 E-mail: sales@protec.co.uk Website: www.protec.co.uk
Certificate No: 201m to EN 54-11: 2001 Certificated Products 6000/MCP Analogue addressable indoor break glass unit LPCB Ref. No. 201m/01

Accessories: N 63-111-48 Surface mounting back box

Safety Technology International (Europe) Limited


Unit 49G Pipers Road, Park Farm Industrial Estate, Redditch, Worcestershire B98 0HU UK Tel: +44 (0)1527 520999 Fax: +44 (0)1527 501999 E-mail: sales@sti-europe.com Website: www.sti-europe.com
Certificate No: 653a to EN 54-11:2001

160

January 2009

SECTION 5: PART
Certificated Products Series 01 Conventional Type A re-settable indoor flush/surface mounted manual call point Notes: 1) Surface mount approved model RP-RF-01. 2) Flush mount approved model RP-RS-01. 3) Approved colour red only. LPCB Ref. No. 653a/01

MANUAL CALL POINTS

Accessories RS01 red surface mounting box

Sareme UAB
Naugarduko str. 32/2, Vilnius LT2006, Lithuania Tel: +3705 2135047 Fax: +3705 2333567 E-mail: sareme@sareme.lt
Certificate No: 512f to EN 54-11:2001 + A1:2005 Certificated Products SF MCP127 SF MCP127-F SF MCP127-TC SF MCP127-FTC Conventional manual call point with LED Conventional manual call point with flashy LED Conventional manual call point with LED and transparent cover Conventional manual call point with flashy LED and transparent cover LPCB Ref. No. 512f/01 512f/02 512f/03 512f/04

Accessories SF MCP127-B1 Regular mounting base, 28mm SF MCP127-B2 High mounting base, 40mm SF MCP127-B3 High mounting base, 55m

Shield Fire Safety & Security Ltd


29th Floor, Regus Suite, One Canada Square, Canary Wharf, London E14 5DY UK Tel: +44 (0)207 712 1722 Fax: +44 (0)870 734 5579 E-mail: info@shielduk.com Website: www.shielduk.com
Certificate No: 548g to EN 54-11: 2001 Certificated Products BG-A450 BG-C440 Intelligent manual call point Conventional manual call point LPCB Ref. No. 548g/02 548g/01

Siemens Switzerland Limited, Building Technologies Division


International Headquarters, Fire Safety & Security Products, Gubelstrasse 22, CH-6301 Zug, Switzerland Tel: +41 (0) 41 724 24 24 Fax: +41 (0) 41 724 35 22
Certificate No: Certificate No: Certificate No: Certificate No: 126as to EN 54-11: 2001 + A1: 2005 126w to EN 54-11: 2001 166b to EN 54-11: 2001 126ap to EN 54-11: 2001 + A1: EN 54-17: 2005 LPCB Ref. No. 126w/01 126w/02 126w/03

Certificated Products DM1154 Ex DM1101 MT320C Addressable interactive manual call point Conventional indoor/outdoor manual call point Conventional indoor/outdoor manual call point

January 2009

161

PART 3: SECTION 5
MANUAL CALL POINTS
Certificated Products DM1131 DM1151 DM1104 DM1134 DM1154 DM1104H DM1134H DM1154H DM1154H-Ex MT320C DM1101 FDM225-RP FDM225-RG FDM226-RP FDM226-RG FDM224 FDM224H FDM221 FDM223 FDM223H FDM225 RP (F) FDM225-RG (F) FDM1101-RG FDM1101-RP FDM1101A-RG FDM1101A-RP FDM1101-RG(F) FDM1101-RP(F) Analogue addressable indoor/outdoor manual call point. Interactive indoor/outdoor manual call point Conventional indoor and outdoor manual call point Addressable indoor and outdoor manual call point Interactive indoor and outdoor manual call point Conventional indoor and outdoor manual call point (DMZ1197-AC) Analogue addressable indoor and outdoor manual call point (DMZ1197-AC) Interactive indoor and outdoor manual call point (DMZ1197-AC) Addressable interactive manual call point (DMZ1197-AC) Indoor manual call point, flush mounted (DMZ1191 mounting box) Digital addressable Type A indoor/outdoor manual call point with resettable plastic element (FDMH295-R and FDMH295-S Digital addressable Type A indoor/outdoor manual call point with resettable glass element (FDMH295-R and FDMH295-S Digital addressable Type A indoor/outdoor manual call point with resettable plastic element (including housing base) Digital addressable Type A indoor/outdoor manual call point with resettable plastic element (including housing base) Digital addressable Type A indoor/outdoor manual call point with resettable glass element and incorporating short circuit isolator and DMZ1195) Digital addressable Type A indoor/outdoor manual call point with resettable glass element and incorporating short circuit isolator and DMZ1197-AD) Digital addressable Type A indoor/outdoor manual call point with resettable glass element and incorporating short circuit isolator and FDMK291) Digital addressable Type B indoor/outdoor manual call point with resettable glass element and incorporating short circuit isolator and DMZ1195) Digital addressable Type B indoor/outdoor manual call point with resettable glass element and incorporating short circuit isolator (DMZ1197-AC) Digital addressable Type A indoor/outdoor manual call point with re-settable plastic element; French labelling on re-settable plastic element (FDMH295-R and FDMH295-S) Digital addressable Type A indoor/outdoor manual call point with non-resettable glass element; French labelling on non-resettable glass element (FDMH295-R and FDMH295S) Collective Type A Indoor / Outdoor Manual Call Point with Non-Resettable Glass Element Collective Type A Indoor / Outdoor Manual Call Point with Resettable Plastic Element. Conventional Type A Indoor / Outdoor Manual Call Point with Non-Resettable Glass Element. Conventional Type A Indoor / Outdoor Manual Call Point with Resettable Plastic Element. Collective Type A Indoor / Outdoor Manual Call Point with Non-Resettable Glass Element. Collective Type A Indoor / Outdoor Manual Call Point with Resettable Plastic Element; French labelling on Resettable Plastic Element. LPCB Ref. No. 126w/04 126w/05 126w/06 126w/07 126w/08 126w/09 126w/10 126w/11 126w/12 166b/07 166b/11 126ap/01 126ap/02 126ap/03 126ap/04 126ap/05 126ap/06 126ap/07 126ap/08 126ap/09 126ap/10 126ap/11 126as/01 126as/02 126as/03 126as/04 126as/05 126as/06

Accessories: FDMC291 protective cover FDMK291 key with cover DMZ1197-AC protective cover DMZ1195 key FDMH295-R Housing base FDMH295-S Housing base with holes and sockets

System Sensor Europe


15-19 Trescott Road, Trafford Park, Smallwood, Redditch, Worcestershire B98 7AH UK Tel: +44 (0)1527 406700 Fax: +44 (0)1527 406699 Website: www.systemsensoreurope.com
Certificate No: 166b to EN 54-11: 2001 Certificate No: 166e to EN 54-11:2001 and EN54-17:2005 Certificated Products MCP5A-RP11xx Indoor surface/flush mounting addressable call point (Advanced System Sensor protocol) Notes: 1) S x (Surface mounted) F x (Flush mounted) 2) x G (Glass element) x F (Flexible element) LPCB Ref. No. 166b/03

162

January 2009

SECTION 5: PART
Certificated Products 3) The manual call point is approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) Outdoor surface mounting addressable call point (Advanced System Sensor protocol) Notes: 1) G element) F (Flexible element) 2) The manual call point is approved with Honeywell micro switch ZW10F90AW1 Indoor surface/flush mounting addressable call point with short circuit isolator (Advanced System Sensor protocol) Notes: 1) S x (Surface mounted) F x (Flush mounted) 2) x G (Glass element) x F (Flexible element) 3) The manual call point is approved with three micro-switches (Honeywell ZM10E50A01, Otehall 294/20/150/G and Burgess X4G310K1BBAQ) Outdoor surface mounting addressable call point with short circuit isolator (Advanced System Sensor protocol) Notes: 1) G element) F (Flexible element) 2) The manual call point is approved with Honeywell micro switch ZW10F90AW1 LPCB Ref. No. 166b/64

MANUAL CALL POINTS

WCP5A-RP11Sx

MCP5A-RP12xx

166e/05

WCP5A-RP12Sx

166e/06

Thorn Security Limited, trading as Tyco Safety Products


Dunhams Lane, Letchworth SG6 1BE UK Tel: +44 (0)1462 667700 Fax: +44 (0)1462 667777 E-mail: mashbury@tycoint.com Website: www.tycosafetyproducts-europe.com
Certificate No: 681n to EN 54-11: 2001 + A1: 2005 Certificate No: 166b to EN 54-11: 2001 Certificated Products CP820 CP830 MCP200 MCP210 MCP250M MCP230 MCP260M Addressable Type A indoor manual call point Addressable Type A indoor manual call point Indoor / Outdoor surface / flush mounting conventional call point Indoor / Outdoor surface / flush mounting conventional call point Indoor /Outdoor surface / flush mounting conventional call point - Marine model Outdoor surface mounting conventional waterproof call point Outdoor surface mounting conventional waterproof call point - Marine model LPCB Ref. No. 681n/01 681n/02 166b/41 166b/41 166b/41 166b/53 166b/53

January 2009

163

PART 3: SECTION 6
LINE UNITS A Line Unit is the term given to define devices used for functions other than fire detection, which are connected to a fire detection and alarm system transmission path or within other components of the fire detection and alarm system e.g. inside Control and Indicating Equipment. For example, the following devices may be regarded as Line Units: short circuit isolators input/output interfaces

Short-circuit isolators are used to limit the consequences of low parallel resistance faults between the lines of a transmission path of a fire detection and fire alarm system. The transmission path is normally in a loop configuration which is separated into sections by the short circuit isolators, such that a detected fault in a particular section will isolate that particular section allowing other components in other sections on the loop to function correctly. Input/output devices are intended for different applications, and may therefore have different functions. Their functions are specified by the manufacturer and they are tested and approved against this specification. This section lists approved Line Units which are connected to a fire detection and alarm system. The initial approval and continued approval processes for Line Units are outlined in scheme document SD038. Products listed in this section have been approved to: EN 54-17:2005 Short-circuit isolators EN 54-18:2005 Input/output devices

Audit: Regular product auditing and regular factory inspections are carried out by LPCB ensuring high manufacturing standards and continued compliance with the applicable product standard. Notes: 1. It is recommended that short circuit isolators and input/output devices are certificated to EN 54-17:2006 and EN 54-18 respectively. EN 54-17:2006 and EN 54-18:2006 are now harmonised standards for the Construction Products Directive and CE marking is required for most of the European market by 1 December 2008. It is therefore recommended that devices are certificated to EN 54-17:2006 or EN 54-18:2006 where applicable as soon as possible. 2. Since the LPCB uses national and international standards for the listing of products, in some instances the requirements of these standards may conflict with the recommendations of local codes of practice. We recommend that specifiers seek advice from the relevant local authorities and amend their specifications accordingly.

164

January 2009

SECTION 6: PART

LINE UNITS

Apollo Fire Detectors Limited


36 Brookside Road, Havant, Hampshire PO9 1JR UK Tel: +44 (0)2392 492412 Fax: +44 (0)2392 492754 E-mail: enquiries@apollo-fire.co.uk Sales Enquiries Germany Apollo Deutschland GmbH Tel: +49 5241 330 60 Fax: +49 5241 330 629 E-mail: info@apollo-feuer.de

Sales Enquiries Spain, Apollo Espana Tel: +34 627 988 061 Fax: +34 949 335 289 E-mail: apollo.espana@apollo-fire.com

Sales Enquiries China, Apollo Fire Detectors Limited,, Shanghai representative office Tel: +86 21 5237 0922 Fax: +86 21 5237 0920 E-mail: tony.ye@apollo-fire.com

Certificate No: Certificate No: Certificate No: Certificate No:

010e to LPCB test schedule 62449/1.3 010f to EFSG/F/95/007 010k to CEA GEI 1-052:Draft 2: 1997 010aa to EN 54-17:2005 LPCB Ref. No. 010k/04 010k/03 010e/01 010k/01 010k/02 010k/05 010k/05 010k/06 010k/06 010k/10 010k/10 010k/07 010k/07 010k/08 010k/08 010k/09 010k/09 010f/01

Certificated Products 45681-321 XP95 45681-323 XP95 55000-700 XP95 55000-710 XP95 55000-720 XP95 55000-840 XP95 55000-841 XP95 55000-842 XP95 55000-843 XP95 55000-844 XP95 55000-845 XP95 55000-846 XP95 55000-847 XP95 55000-848 XP95 55000-849 XP95 55000-851 XP95 55000-852 XP95 55000-855 XP95 Negative short circuit isolating base Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Positive short circuit isolating base Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Short circuit isolator (45681-211 mounting base) Positive short circuit isolator (45681-211 mounting base) Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Negative short circuit isolator (45681-211 mounting base) Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable switch monitor plus with isolator -flush mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable switch monitor plus with isolator -surface mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable switch monitor with isolator -flush mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable switch monitor with isolator -surface mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable Zone monitor unit with isolator -flush mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable zone monitor unit with isolator -surface mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable input/output unit with isolator flush mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable input/output unit with isolator -surface mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable output unit with isolator flush mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable output unit with isolator -surface mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable sounder controller unit with isolator -flush mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable sounder controller unit with isolator -surface mounted Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Single Channel Protocol Translator

January 2009

165

PART 3: SECTION 6
LINE UNITS
Certificated Products 55000-856 XP95 55000-588 XP95 55000-589 XP95 45681-284 Bases: 45681-211 XP95 isolator base Dual Channel Protocol Translator Analogue addressable 3 Channel Input/Output unit with short circuit isolator Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable 3 Channel Input/Output unit Approved with Apollo Series 90, XP95 and Discovery digital communication protocols XP95/Discovery short circuit isolating base LPCB Ref. No. 010f/02 010k/11 010k/12 010aa/01

Emergi-Lite Safety Systems (Thomas & Betts Ltd)


Bruntcliffe Lane, Morley, Leeds LS27 9LL UK Tel: +44 (0)113 2810600 Fax: +44 (0)113 2810601 Website: www.emergi-lite.co.uk
Certificate No: 010k to CEA GEI 1-052:11.06.97 Draft 2 Certificated Products FA95-LIU FA95-SMUPLUS FA95-1CI/O FA95-1CO FA95-SCC Negative short circuit isolator (FA95-LLB base) Notes: 1) Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable switch monitor plus with isolator surface mounted Notes: 1) Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable input/output unit with isolator surface mounted Notes: 1) Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable output unit with isolator surface mounted Notes: 1) Approved with Apollo Series 90, XP95 and Discovery digital communication protocols Analogue addressable sounder control unit with isolator surface mounted Notes: 1) Approved with Apollo Series 90, XP95 and Discovery digital communication protocols LPCB Ref. No. 010k/02 010k/05 010k/07 010k/08 010k/09

Bases: FA95-LLB Mounting base

FIREX Protection System Technology Ltd


28-38 Desborough Street, High Wycombe, Bucks UK Tel: +44 (0)1494 601077 Fax: +44 (0)1494 601011 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 548f to CEA GEI 1-052-Draft 2.0 Certificate No: 548h to CEA GEI 1-084: 08.08.2000 Certificated Products FX9503 FX9300I FX9301I Loop isolator Analogue addressable input module Analogue addressable input/output module LPCB Ref. No. 548f/01 548h/01 548h/02

166

January 2009

SECTION 6: PART

LINE UNITS

GE Security (Africa) trading as Ziton


Ziton House, 555 Voortrekker Road, Maitland 7405, Republic of South Africa Tel: +27 21 5066000 Fax: +27 21 5066100 Website: www.ziton.com UK Sales Enquiries: Ziton Limited Tel: +44 (0)1908 281981 Fax: +44 (0)1908 282554

Certificate No: 092j to GEI 1-052: Draft 2 Certificated Products ZP760-2 A60E-2 Short circuit isolator (ZP760-SB mounting base) Analogue addressable line isolator module LPCB Ref. No. 092j/01 092j/02

Certificate No: 092q to CEA GEI 1-084 - 08/08/2000 Draft Certificated Products A45E-2 A50E-2 Analogue addressable single input interface module Analogue addressable line relay module LPCB Ref. No. 092q/01 092q/02

GE Security Inc
5 North Main Street, Pittsfield, ME 04967, USA Tel: +1 207 487 3104 Fax: +1 207 487 5526 E-mail: leon.newsome@ge.com Website: www.gesecurity.com European Sales: Rudford Estate, Ford Aerodrome, Arundel, West Sussex BN18 0BE UK Tel: +44 (0)1903 711 440 Fax: +44 (0)1903 711 448 E-mail: info@estinternational.com

Certificate No: 262d to EFSG/F/95/007 Approved Products SIGA-CC1 SIGA-CC2 SIGA-CT1I SIGA-CT2I Single input signal module Note: Approved using personality code 5 Dual input signal module Note: Approved using personality code 7 Single input module Note: Approved using personality codes 3, 4 and 18 Dual input module Note: Approved using personality codes 3, 4 and 18 LPCB Ref. No. 262d/01 262d/02 262d/03 262d/04

Certificate No: 92j to GEI 1-052:Draft 2.0 (11-06-97) Certificated Products EA760-2 Short circuit isolator (EA760-SB mounting base) LPCB Ref. No. 092j/01

January 2009

167

PART 3: SECTION 6
LINE UNITS

Gent By Honeywell
140 Waterside Road, Hamilton Industrial Park, Leicester LE5 1TN UK Tel: +44 (0)116 246 2000 Fax: +44 (0)116 246 2300 E-mail: gent_enquiry@gent.co.uk Website: www.gent.co.uk Middle East Sales Enquiries E-mail: gent.export@honeywell.com

Certificate No: 42b to CEA GEI 1-084: 08-08-2000 Approved Products 808610 808611 808613 808614 12 Relay transponder 32 LED output transponder 4 Detection zones/2 relay output transponder 1 Detection zone transponder LPCB Ref. No. 400b/01 400b/02 400b/03 400b/04

Certificate No: 042ap to prEN 54-18: 2005 Certificated Products 34410 34450 34415 Analogue addressable zone module (loop powered) Analogue addressable four channel interface module (loop powered) Analogue addressable single channel interface module (loop powered) LPCB Ref. No. 042ap/01 042ap/02 042ap/03

Certificate No: 042ba to EN 54-17: 2005 & EN 54-18: 2005 Certificated Products S4-34410 S4-34411 S4-34415 S4-34420 S4-34450 Analogue addressable 1 input interface module with short circuit isolator, low voltage. (S4-34490 and S4-34492 boxes) Analogue addressable 1 output DIN rail mounting interface module with short circuit isolator, medium voltage. Analogue addressable 1 output surface mounting interface module with short circuit isolator, medium voltage. Analogue addressable 1 input and 1 output interface module with short circuit isolator, low voltage. (S4-34490 and S4-34492 boxes) Analogue addressable 4 input / output interface module with short circuit isolator, low voltage. (S4-34490 and S4-34492 boxes) LPCB Ref. No. 042ba/01 042ba/02 042ba/03 042ba/04 042ba/05

Accessories: S4-34490 Plastic Box S4-34492 Metal Box

Global System Technology Plc


Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire LE65 1RT UK Tel: +44 (0)1283 225 478 Fax: +44 (0)1283 222 039 E-mail: info@gst.uk.com Website: www.gst.uk.com
Certificate No: 548h to CEA GEI 1-084: 08.08.2000 Certificate No: 548f to CEA GEI 1-052 - Draft 2.0

168

January 2009

SECTION 6: PART
Certificated Products I-9300 I-9301 C-9503 Analogue addressable input module Analogue addressable single input/output module Loop isolator LPCB Ref. No. 548h/01 548h/02 548f/01

LINE UNITS

Group 4 Securicor Plc


Manor Royal, The Manor, Crawley, West Sussex RH10 9UN UK Tel: +44 (0)20 87707000 Fax: +44 (0)20 87722531 E-mail: allan.rignall@uae.g4s.com Website: www.g4s.com
Certificate No: 548f to CEA GEI 1-052-Draft 2.0 Certificate No: 548h to CEA GEI 1-084: 08.08.2000 Certificated Products GS503C GS300I GS301I Loop isolator Analogue addressable input module Analogue addressable input/output module LPCB Ref. No. 548f/01 548h/01 548h/02

Gulf Security Technology Co. Ltd (Manufacturing Division of Global System Technology PLC)
No. 80 Changjiang East Road, Economic & Technological Development Zone, Qinhuangdao, Hebei Province 066004, Peoples Republic of China Tel: +86 0335 8502528 Fax: +86 0335 8508942 E-mail: gst@gst.com.cn Website: www.gst.com.cn
Certificate No: 548h to CEA GEI 1-084: 08.08.2000 Certificate No: 548f to CEA GEI 1-052 - Draft 2.0 Certificated Products GST-LD-8300 GST-LD-8301 GST-LD-8322 Analogue addressable input module Analogue addressable single input/output module Loop isolator LPCB Ref. No. 548h/01 548h/02 548f/01

HDR
Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260133 Fax: +44 (0)1634 260132 E-mail: info@hochikieurope.com Website: www.hochikieurope.com
Certificate No: 164b to EFSG/F/95/007 Certificate No: 164d to CEA 1-052 Draft 2.0: 11/06/97 Certificate No: 164f to GEI-CEA-1-084 Certificated Products 1433020 1433080 1433120 1433040 1433100 1226110 1433190 Dual Sounder Controller Mini Zone Monitor Dual Relay Controller Dual Switch Monitor Dual Zone Monitor Short Circuit Isolator Base Input/Output Module LPCB Ref. No. 164b/01 164b/02 164b/03 164b/04 164b/05 164d/01 164f/01

January 2009

169

PART 3: SECTION 6
LINE UNITS

Hochiki Europe (UK) Limited


Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260133 Fax: +44 (0)1634 260132 Website: www.hochikieurope.com
Certificate No: 164b to EFSG/F/95/007 Certificate No: 164d to GEI-052 Draft 2.0 Certificate No: 164f to GEI-084 Approved Products CHQ-B CHQ-MZ CHQ-R CHQ-S CHQ-Z CHQ-SCI-S YBO-R/SCI CHQ-SIO Dual sounder controller Mini zone monitor Dual relay controller Dual switch monitor Dual zone monitor Short circuit isolator Isolator base Input/output module LPCB Ref. No. 164b/01 164b/02 164b/03 164b/04 164b/05 164b/06 164d/01 164f/01

Honeywell Control Systems Limited


Lovelace Road, Southern Industrial Estate, Bracknell, Berkshire RG12 8WD UK Tel: +44 (0)1344 655609 Fax: +44 (0)1344 655474 Website: www.honeywell.com
Certificate No: 199d to EFSG/F/92/009 Certificated Products TC809E1019 TC810E1008 TC811E1007 TC809E1027 Analogue addressable monitor module Analogue addressable control module Isolation module Analogue addressable mini monitor module LPCB Ref. No. 199d/01 199d/02 199d/03 199d/04

Morley-IAS Fire Systems By Honeywell


Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@morleyias.co.uk Website: www.morley-ias.co.uk
Certificate No: 199e to EFSG/F/95/007 Certificated Products MI-MM3E Micro monitor module LPCB Ref. No. 199e/01

Certificate No: 199q to CEA GEI 1-052 Draft 2.0,CEA GEI 1-084 Draft (08-08-00) & prEN 54-17 Draft (July 2002) Certificated Products MI-DMMI MI-DMM2I MI-D2ICMO MI-DCMO MI-D240MO Analogue addressable single channel input module with short circuit isolator Analogue addressable dual channel input module with short circuit isolator Analogue addressable dual channel input and single channel output module with short circuit isolator Single channel output module with short circuit isolator Single channel 240V output module with short circuit isolator LPCB Ref. No. 199q/01 199q/02 199q/03 199q/04 199q/05

170

January 2009

SECTION 6: PART
Certificated Products MI-D240CMO-DIN MI-DC2M Single channel 240V output module, DIN rail mount with short circuit isolator Analogue addressable conventional zone interface module LPCB Ref. No. 199q/06 199q/07

LINE UNITS

Certificate No: 199r to CEA GEI 1-052 Draft 2.0: 11.06.97 & prEN 54-17 Draft: July 2002 Certificated Products MI-DISO Short circuit isolator module LPCB Ref. No. 199r/01

Napco Gulf Security Group


P.O. Box 54533, Dubai Airport Free Zone, UAE Tel: +971 4 2997703 Fax: +971 4 2997704 E-mail: info@napcogulfsecurity.com Website: www.napcogulfsecurity.com
Certificate No: 548f to CEA GEI 1-052-Draft 2.0 Certificate No: 548h to CEA GEI 1-084: 08.08.2000 Certificated Products NC-503 NI-300 NI-301 Loop isolator Analogue addressable input module Analogue addressable input/output module LPCB Ref. No. 548f/01 548h/01 548h/02

Nitin Ventures FZE


P.O. Box 262294, Jabel Ali Free Zone, Dubai, UAE Tel: +97 148865858/859 Fax: +97 148865800 E-mail: sales@nitinventures.com Website: www.nitinventures.com
Certificate No: 010k to CEA GEI 1-052: 11.06.97 Draft 2 Certificated Products NV-IA-ISO NV-IAII-SM NV-IAII-IO NV-IAII-O NV-IAII-SC NV-IAII-ZM Bases: NV-IA-ISOB Isolator Base Negative short circuit isolator (NV-IA-ISOB isolator base) Analogue addressable switch monitor with isolator - surface mounted Ananlogue addressable input/output unit with isolator - surface mounted Analogue addressable output unit with isolator - surface mounted Analogue addressable sounder control unit with isolator - surface mounted Analogue addressable zone monitor unit with isolator - surface mounted LPCB Ref. No. 010k/02 010k/06 010k/07 010k/08 010k/09 010k/10

Certificate No: 010aa to EN 54-17:2005 Certificated Products NV-IA-IB Short circuit isolating base LPCB Ref. No. 010aa/01

January 2009

171

PART 3: SECTION 6
LINE UNITS

Notifier By Honeywell
Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230300 Fax: +44 (0)1444 230888 E-mail: sales@notifiersystems.co.uk Website: www.notifierfiresystems.co.uk
Certificate No: 199d to EFSG/F/92/009 Approved Products MMX-1E CMX-2E MMX-101E ISO-XE Monitor module Control module Mini monitor module Short circuit isolator LPCB Ref. No. 199d/01 199d/02 199d/04 199d/03

Certificate No: 199q to CEA GEI 1-052 Draft 2.0, CEA GEI 1-084 Draft (08-08-00) and prEN 54-17 Draft (July 2002) Certificated Products M710 M720 M721 M701 M701-240 M701-240-DIN M710-CZ Analogue addressable single channel input module with short circuit isolator Analogue addressable dual channel input module with short circuit isolator Analogue addressable dual channel input and single channel output module with short circuit isolator Single channel output module with short circuit isolator Single channel 240V output module with short circuit isolator Single channel 240V output module, DIN rail mount with short circuit isolator Analogue addressable conventional zone interface module LPCB Ref. No. 199q/01 199q/02 199q/03 199q/04 199q/05 199q/06 199q/07

Certificate No: 199r to CEA GEI 1-052 Draft 2.0: 11.06.97 & prEN 54-17 Draft: July 2002 Certificated Products M700X Short circuit isolator module LPCB Ref. No. 199r/01

Novar GmbH
Security and Building Management Systems, Dieseltrasse 2, D-41469, Neuss, Germany Tel: +49 (0)2137 170 Fax: +49 (0)2137 17286 E-mail: info@esser-systems.de Website: www.esser-systems.de
Certificate No: 400b to CEA GEI 1-084 Approved Products 808610 808611 808613 808614 12 Relay transponder 32 LED output transponder 4 Detection zones/2 relay output transponder 1 Detection zone transponder LPCB Ref. No. 400b/01 400b/02 400b/03 400b/04

172

January 2009

SECTION 6: PART

LINE UNITS

Pittway Tecnologica Srl.


Via Caboto 19/3, 34147 Trieste, Italy Tel: +39 040 94 90111 Fax: +39 040 38 2137 E-mail: sandro_bonin@systemsensor.com Website: www.systemsensoreurope.com European Sales Enquiries: System Sensor Europe Tel: +44 (0)1527 406700 Fax: +44 (0)1527 406699

Certificate No: Certificate No: Certificate No: Certificate No: Certificate No:

199j to CEA GEI 1-052 Draft 2.0 199e to EFSG/F/95/007 199r to CEA GEI 1-052 Draft 2.0 (11-06-97) and prEN 54-17 Draft (July 2002) 199q to CEA GEI 1-052 Draft 2.0, CEA GEI 1-084 Draft (08-08-00) and prEN 54-17 Draft (July 2002) 199d to EFSG/F192/009 LPCB Ref. No. 199d/01 199d/02 199d/03 199d/04 199e/01 199r/01 199q/01 199q/02 199q/03 199q/04 199q/05 199q/06 199j/02 199j/03 199q/07

Certificated Products M500ME M500CHE M500XE M501ME M503ME M200XE M210E M220E M221E M201E M201E-240 M201E-240-DIN B524IEFT-1 ISO524-1 M210E-CZ Monitor module Control module Short circuit isolator Mini monitor module Micromonitor module Short circuit isolator module Analogue addressable single channel input module with short circuit isolator Analogue addressable dual channel input module with short circuit isolator Analogue addressable dual channel input and single channel output module with short circuit isolator Single channel output module with short circuit isolator Single channel 240V output module with short circuit isolator Single channel 240V output module, DIN rail mount with short circuit isolator Short circuit isolator base Short circuit isolator module Analogue addressable conventional zone interface module

Shield Fire Safety & Security Ltd


29th Floor, Regus Suite, One Canada Square, Canary Wharf, London E14 5DY UK Tel: +44 (0)207 712 1722 Fax: +44 (0)870 734 5579 E-mail: info@shielduk.com Website: www.shielduk.com
Certificate No: 548f to CEA GEI 1 - 052 - Draft 2.0 Certificate No: 548h to CEA GEI 1 - 084: 08.08.2000 Certificated Products AI-520 AI-510 AI-500 Loop isolator Analogue addressable single input/output module Analogue addressable input module LPCB Ref. No. 548f/01 548h/02 548h/01

January 2009

173

PART 3: SECTION 6
LINE UNITS

Siemens Switzerland Limited, Building Technologies Division


International Headquarters, Fire Safety & Security Products, Gubelstrasse 22, CH-6301 Zug, Switzerland Tel: +41 (0) 41 724 24 24 Fax: +41 (0) 41 724 35 22 Manufacturing at: Siemens Building Technologies AG, Volketswil Factory, Industriestrasse 22, CH-8604 Volketswil, Switzerland Tel: +41 1 922 6111 Fax: +41 1 922 6450

UK Sales: Tel: +44 (0)1189 783703 Fax: +44 (0)1189 775750 Website: www.sibt.com/www.uk.cerberus.com

Certificate No: Certificate No: Certificate No: Certificate No:

126j to EFSG/F/94/002 126m to EFSG/F/95/007 126p to CEA GEI 1-052 Draft 2 126t to CEA GEI 1-052 Draft 2 LPCB Ref. No. 126m/01 126m/02 126m/03 126m/04 126j/01 126j/02 126p/01 126p/02 126p/03 126p/04 126p/05 126p/06 126p/01 126p/02 126p/03 126t/02

Approved Products DC1131 DC1134 DC1157 DC1192 DC1151 DC1154 DC1131-AA DC1134-AA DC1136-AA DC1154-AA DC1156-AA DC1157-AA EB322A AB322A ABI322A CB320A Input module Output module Input module Input/output module Input module Output module Input module Output module Output module Output module Output module Input module Input module Output module Output module Input module

Certificate No: 126ae to CEA GEI 1-052: Draft 2.0, 11/06/97 Certificated Products FDCL221 Accessories: TS35 standard top hat rail Analogue addressable line separator LPCB Ref. No. 126ae/01

Certificate No: 126ad to CEA GEI 1-084 : 08/08/00 and CEA GEI 1-052: Draft 2.0, 11/06/97 Certificated Products FDCI222 FDCIO222 Accessories: FDCM291 mounting foot TS35 standard top hat rail Analogue addressable input module (FDCM291) Analogue addressable input/output module (FDCM291) LPCB Ref. No. 126ad/01 126ad/02

174

January 2009

SECTION 6: PART

LINE UNITS

Certificate No: 126aq to EN 54-17:2005 and EN 54-18:2005 Certificated Products FDCIO223 Addressable transponder incorporating short circuit isolators Note: 1) Approved when used in conjunction with housing box FDCH292 LPCB Ref. No. 126aq/01

Accessories: FDCH292 Housing box FDCM291 Mounting foot

Thorn Security Limited, trading as Tyco Safety Products


Dunhams Lane, Letchworth SG6 1BE UK Tel: +44 (0)1462 667700 Fax: +44 (0)1462 667777 E-mail: mashbury@tycoint.com Website: www.tycosafetyproducts-europe.com
Certificate No: 681k to CEA GEI 1-052 11.06.1997 Draft 2.0 Certificate No: 681m to GEI 1-084 -08.08.2000 Certificated Products 5BI 801IB 801RB HVR800 CIM800 DIM800 RIM800 MIM800 SNM800 LAV800 MIO800 BDM800 5" Isolator base Digital addressable isolator base Digital addressable relay base High voltage relay module Note: For use with RIM800 relay interface module Contact input module Detector input module Relay interface module Mini input module Sounder notification module Extinguishing input module Small addressable multi input/output module Loop powered beam detector interface module Note: approved when used in conjunction with the FIRERAY 2000/50R/100R beam detector and BTM800 thermal module. LPCB Ref. No. 681k/01 681k/02 681k/03 681k/04 681k/05 681k/06 681k/07 681k/08 681k/09 681k/10 681k/11 681m/01

January 2009

175

PART 3: SECTION 7
SOUNDERS The purpose of a fire alarm sounder is to warn person(s) within, or in the vicinity of, a building of the occurrence of a fire emergency situation in order to enable such person(s) to take appropriate measures. Fire alarm sounders can be of different construction and may have different frequency ranges, temporal patterns and output levels. Guidance on the type, frequency, temporal pattern, and output levels should be sought from the applicable installation rule or code of practice (e.g. BS 5839-1). For example BS 5839-1 recommends sounders with continuous output and frequency range between 500 Hz to 1 000 Hz. Fire alarm sounders may be used for other type of risk or non-fire emergency alarm. In this case it is always recommended that a different temporal pattern, frequency signal from the fire signal is selected to avoid confusion. This section lists sounders approved for use indoors and outdoors in fire detection and fire alarm systems. The initial approval and continued approval processes for line units are outlined in scheme document SD039. Products listed in this section have been approved to: EN 54-3:2001 Sounders EN 54-3:2001 + A1:2002 + A2:2006 Sounders

Audit: Regular product auditing and regular factory inspections are carried out by LPCB ensuring high manufacturing standards and continued compliance with the applicable product standard. Notes: 1. EN 54-3:2001 is now a harmonised standard for the Construction Products Directive and CE marking is required for most of the European market since 30 June 2005. It is therefore recommended that sounders are certificated to EN 54-3: 2001. 2. Since the LPCB uses national and international standards for the listing of products, in some instances the requirements of these standards may conflict with the recommendations of local codes of practice. We recommend that specifiers seek advice from the relevant local authorities and amend their specifications accordingly.

Apollo Fire Detectors Limited


36 Brookside Road, Havant, Hampshire PO9 1JR UK Tel: +44 (0)2392 492412 Fax: +44 (0)2392 492754 E-mail: enquiries@apollo-fire.co.uk
Certificate No: 010af to EN 54-3: 2001

Wireless Sounders
Certificated Products XPA-SO-14001-APO Xpander addressable sounder (Red ) (XPA-SB-10023-APO mounting base) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as Apollo Part No.: XPA-CB-14001-APO 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval. Xpander addressable sounder (White) (XPA-SB-10024-APO mounting base) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as Apollo Part No.: LPCB Ref. No. 010af/01

XPA-SO-14002-APO

010af/02

176

January 2009

SECTION 7: PART
Certificated Products XPA-CB-14002-APO 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval. Xpander addressable sounder strobe (Red head / red lens) (XPA-SB-10023-APO mounting base) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as Apollo Part No.: XPA-CB-14003-APO 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval. Xpander addressable sounder beacon (Red head / amber lens) (XPA-SB-10024-APO mounting base) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as Apollo Part No.: XPA-CB-14004-APO 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval. Xpander addressable sounder beacon (White head / clear lens) (XPA-SB-10024-APO mounting base) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as Apollo Part No.: XPA-CB-14005-APO 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval. LPCB Ref. No.

SOUNDERS

XPA-SN-14003-APO

010af/03

XPA-SN-14004-APO

010af/04

XPA-SN-14005-APO

010af/05

Bases: XPA-SB-10023-APO Radio link mounting base - red XPA-SB-10024-APO Radio link mounting base - white

Ceasefire Industries Ltd


"Doli Chambers", Flat 602 6th Floor behind strand cinema, Colaba, Mumbai-400 005, India Tel: +91 -22-22854677, 22854678 Fax: +91-22-66349069 E-mail: response@ceasefire.in Website: www.ceasefire.in
Certificate No: 164h-(cl-1) to EN54-3:2001 Certificated Products YBO-BSB (WHT) Loop powered base sounder and beacon (YBN-R/3 and YBO-R/SCI bases). 1) The beacon function of this device is not included in the scope of this approval. 2) Meets the requirements of EN54-3 at the following tones: 1) - 925 Hz : 250 ms / 628 Hz : 250 ms 2) - 925 Hz Continuous 3) - 628 Hz Continuous 4) - (French) 554 Hz : 100 ms/ 440 Hz : 400 ms 5) - (Swedish) 660 Hz : 150 ms/ Off : 150 ms 6) - 925Hz : 15oms / Off : 600 ms 7) - 670 hZ : 250MS / 845 hZ : 370 MS 8) - Whoop 500 Hz - 1200 Hz : 3000 ms / Off : 500 ms 9) - 1200 Hz : 500 ms/ 500 Hz : 500 ms 10) - 970 Hz : 500 ms / Off : 500 ms 11) - Sweet 800 Hz - 970 Hz over 140 ms (7 Hz) 12) - Sweep 800 Hz - 970 Hz over 1000 ms (1 Hz) LPCB Ref. No. 164h/03

January 2009

177

PART 3: SECTION 7
SOUNDERS
Certificated Products 13) - Sweep 800 Hz - 970 Hz over 20 ms (50 Hz) 14) - Sweep 2400 Hz - 2850 Hz over 140 ms (7 Hz) 15) - Sweet 2400 Hz - 2850 Hz over 1000 ms (1 Hz) 16) - Sweep 300 Hz - 1200 Hz over 1000 ms (1 Hz) 17) - ISO8201 : 970 Hz : 500 ms 18) - ISO8201 : 2850 Hz : 500 ms 19) - 800 Hz : 250 ms / 970 Hz : 250 ms 20) - 2850 Hz Continuous 21) - 2400 Hz : 250 ms / 2850 Hz : 250 ms 22) - 800 Hz : 500 ms / 970 Hz : 500 ms 23) - 2850 Hz : 500 ms / Off : 500 ms 24) - 925 Hz : 250 ms / Off : 1000 ms 25) - 970 Hz Continuous 26) - 660 Hz : 1800 ms / Off: 1800 ms 27) - 660 Hz : 6500 ms / Off : 13000 ms 28) - 660 Hz Continuous 29) - 554 Hz : 500 ms / 440 Hz : 500 ms 30) - 660 Hz : 500 ms / Off : 500 ms 31) - 2850 Hz : 150 ms / Off : 100 ms 32) - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz) 33) - Sweep 800 Hz - 970 Hz over 500 ms (2 Hz) 34) - 988 Hz : 250 ms / 645 Hz : 250 ms 35) - 510 Hz : 250 ms / 610 Hz : 250 ms 36) - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz) 37) - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz) 38) - 845 Hz Continuous 39) - 970 Hz : 1000 ms / Off : 1000 ms 40) - 800 Hz : 150 ms / 970 Hz : 150 ms 41) - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz) 42) - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz) 43) - 2850 Hz : 1000 ms / Off : 1000 ms 44) - 2400 Hz : 150 ms / 2850 Hz : 150 ms 45) - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms 46) - 440 Hz : 600 ms / Off : 600 ms 47) - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms 48) - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms 49) - ISO8201 : Sweep 300 Hz - 1200 Hz : 500 ms / Off : 500 ms 50) - ISO8201 : Sweep 1200 Hz - 300 Hz : 500 ms / Off : 500 ms 51) - Whoop 500-1200 3.5s/0.5s Bases YBN -R/3 base YBO-R/SCI isolator base LPCB Ref. No.

Certificate No: 715a-(cl-2) to EN54-3:2001 Certificated Products Banshee MT Sounder (892 shallow base version and 893 deep base version) 1. Certified to EN 54-3: 2001 with the following tones: Sound 2 Banshee LF Sound 143 Banshee HF (and Bedlam) Sound 19 Slow Whoop (Dutch) Sound 20 DIN Klung (German) 2. Approved as Type A when used with shallow base (892) & Type B when used with deep base (B93). 3. Approved voltage range 10-28V. Bases 892 shallow base 893 deep base LPCB Ref. No. 715a/01

178

January 2009

SECTION 7: PART

SOUNDERS

Cranford Controls Limited


Unit 2, Waterbrook Estate, Waterbrook Road, Alton, Hampshire GU34 2UD UK Tel: +44 (0)1420 592444 Fax: +44 (0)1420 592445 E-mail: sales@cranfordcontrols.com Website: www.cranfordcontrols.com
Certificate No: 546a to EN 54-3: 2001 + A1: 2002 Certificated Products VTG-32E-SB Conventional indoor Type A sounder Notes: 1) The sounder is approved in red and white colours (-R and -W suffixes) 2) Certified to EN54-3: 2001 with the following selectable tones: 1 - LF Sweep frequency (800-1000Hz in 0.5sec) 25 - German DIN tone Sweep (1200-500Hz @ 1Hz) 27 - French tone AFNOR (554Hz for 100ms and 440Hz for 400ms) nd 2 Stage tone for all above (800Hz continuous tone) nd 11 - 2 Stage, Dutch sweep tone (500-1200Hz for 3.5s on, 0.5s off) Conventional outdoor Type B sounder Notes: 1) The sounder is approved in red and white colours (-R and -W suffixes) 2) Certified to EN54-3: 2001 with the following selectable tones: 1 - LF Sweep frequency (800-1000Hz in 0.5sec) 25 - German DIN tone Sweep (1200-500Hz @ 1Hz) 27 - French tone AFNOR (554Hz for 100ms and 440Hz for 400ms) nd 2 Stage tone for all above (800Hz continuous tone) nd 11 - 2 Stage, Dutch sweep tone (500-1200Hz for 3.5s on, 0.5s off) Conventional outdoor Type B sounder (116-007FR mounting base) Note: 1) Certified to EN54-3: 2001 with the following selectable tones: 1 - Evacuate Tone (500-1200Hz Rising Sweep over 3.5 Sec 0.5 Sec off) 2 - Alert Tone (970Hz Continuous Tone) 2) Certified at Maximum Volume only. Conventional indoor Type A sounder Notes: 1) This sounder meets the requirements of EN 54-3:2001 for the following tones at low, medium and high volume settings: 1 - LF Sweep (Cranford sweep) (800-1000Hz @ 0.5 Sec) 3 - Alternative Warble (800-1000Hz @ 0.5 Sec) 11 - Dutch Sweep Tone (970Hz Cont) 25 - German DIN Tone (Sweep 1200-500Hz @ 1Hz) 27- French Tone AFNOR (554Hz 100ms and 440Hz for 400 ms) 2) Cover plate (Part No. 116-099) must be used . Conventional indoor Type A sounder base Notes: 1) This sounder meets the requirements of EN 54- 3: 2001 for the following tones at low, medium and high volume settings. 1 - 800-100Hz Rising Sweep 0.5s 3 - 800-100Hz Warble 0.5s 8 - 800Hz Continuous Tone 17 - 800Hz Intermittent 0.5s on, 0.5s off 2) Cover plate (part no. 116-009) must be used Conventional indoor Type A sounder base Notes: 1) This sounder meets the requirements of EN 54-3 : 2001 for the following tones at low, medium and high volume settings: 1 - LF Sweep (800-1000Hz continuous 11 - Dutch Sweep Tone (970Hz Continuous) 25 - German DIN tone (Sweep 1200-500Hz @ 1Hz) 2) Cover plate (part no. 116-009) must be used LPCB Ref. No. 546a/01

VTG-32E-DB

546a/01

VPR-DT

546a/02

VSO-32

546a/04

VSO-4

546a/03

VSO-3

546a/05

Base: 116-007FR Viper Mounting Base

January 2009

179

PART 3: SECTION 7
SOUNDERS

Detectomat GmbH
An Der Strusbek 5, D-22926 Ahrensburg, Hamburg, Germany Tel: +49 4102 2114 636 Fax: +49 4102 2114 670 E-mail: approval@detectomat.com
Certificate No: 546a to EN 54-3: 2001 + A1: 2002 Certificated Products Verso 4 32216 Conventional Indoor Type A sounder base Notes: 1) This sounder meets the requirements of EN 54-3 : 2001 for the following tones at low, medium and high volume settings: 1 - LF Sweep (800-1000Hz continuous 11 - Dutch Sweep Tone (970Hz Continuous) 25 - German DIN tone (Sweep 1200-500Hz @ 1Hz) 2) Cover plate (part no. 116-009) must be used LPCB Ref. No. 546a/05

Emirates Fire Fighting Equipment Factory (FIREX)


Industrial Area 13, P.O.Box 22436, Sharjah, UAE Tel: +971 6 5340300 Fax: +971 6 5340090 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 506e to EN 54-3: 2001 Certificated Products FX-0218 Conventional fire alarm bell LPCB Ref. No. 506e/01

EMS Radio Fire & Security Limited


Technology House, Herne Bay West Trading Estate, Herne Bay, Kent CT6 8JZ UK Tel: +44 (0)1227 369570 Fax: +44 (0)1227 369679 E-mail: enquiries@emsgroup.co.uk Website: www.emsgroup.co.uk
Certificate No: 786f to EN 54-3: 2001 Certificated Products XP-172-002 Fire-Cell addressable sounder (Red) (XP-171-002 mounting base) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as EMS Part No.: XP-300-002 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval Fire-Cell addressable sounder (White) (XP-171-001 mounting base) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as EMS Part No.: XP-300-001 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval Fire-Cell addressable sounder beacon (Red head / red lens) (XP-171-002 mounting LPCB Ref. No. 786f/01

XP-172-001

786f/02

XP-173-002

786f/03

180

January 2009

SECTION 7: PART
Certificated Products base) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as EMS Part No.: XP-310-022 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval Fire-Cell addressable sounder beacon (Red head / amber lens) (XP-171-001 and XP171-002 mounting bases) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as EMS Part No.: XP-310-032 XP-310-031 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval Fire-Cell addressable sounder beacon (Red head / clear lens) (XP-171-001 and XP-171002 mounting bases) Notes: 1) Meets the requirements of EN 54-3: 2001 at tones 1, 2, 3, 4, 5, 6, 7 & 13 2) The complete radio base/sounder combination is available as EMS Part No.: XP-310-012 XP-310-011 3) The device must be used with the following batteries only: MN1500 LR6 - 1.5 volt alkaline AA cells MN1400 LR14 - 1.5 volt alkaline C cells 4) The radio link functionality is not included within the scope of approval LPCB Ref. No.

SOUNDERS

XP-173-003

786f/04

XP-173-004

786f/05

Bases: XP-171-001 Radio link mounting base - white XP-171-002 Radio link mounting base - red

FIREX Protection System Technology Ltd


28-38 Desborough Street, High Wycombe, Bucks UK Tel: +44 (0)1494 601077 Fax: +44 (0)1494 601011 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 548e to EN 54-3: 2001 Certificated Products FX9403 FX9403I Conventional sounder strobe Notes: Meets the requirements of EN 54-3: 2001 at the following tones: Fixed tone: 1.35Hz (400ms on / 340ms off) Intelligent sounder strobe Notes: Meets the requirements of EN 54-3: 2001 at the following tones: Mode I (for pre alarm): 0.61Hz (430ms on / 1200ms off) Mode II (for fire alarm): 1.30Hz (430ms on / 340ms off) LPCB Ref. No. 548e/01 548e/02

January 2009

181

PART 3: SECTION 7
SOUNDERS

Fulleon Limited
Llantarnam Park, Cwmbran, Gwent NP44 3AW UK Tel: +44 (0)1633 628500 Fax: +44 (0)1633 866346 E-mail: sales@fulleon.co.uk Website: www.fulleon.com
Certificate No: 378b to EN 54: Part 3: 2001 Approved Products ROLP Roshni LP Sounder Notes: 1The sounder is approved in red and white colours. 2Using Deep, U-shaped, and shallow sounder bases in red and white colours. 3Meets the requirements of EN 54-3 at tone patterns 3 and 8 only. LPCB Ref. No. 378b/01

Gent By Honeywell
140 Waterside Road, Hamilton Industrial Park, Leicester LE5 1TN UK Tel: +44 (0)116 246 2000 Fax: +44 (0)116 246 2300 E-mail: gent_enquiry@gent.co.uk Website: www.gent.co.uk
Certificate No: 042ah to EN 54-3: 2001 Certificate No: 042ar to EN 54-3: 2001 +A1 , CEA GEI 1-052- Draft 2.0 11-06-97 Certificated Products S3-SN-R S3-SN-W S3IP-SN-R S3IP-SN-W S2IP-SN-R S2IP-SN-W S2IP-SN-R3 S2IP-SN-W3 S3-SN-ST-RR S3-SN-ST-WR S3IP-SN-ST-RR S3IP-SN-ST-WR S3IP-SN-ST-RW S31P-SN-ST-WA S3-VO-R S3-VO-W S3IP-VO-R S3IP-VO-W S2IP-VO-R S2IP-VO-W S3-VO-ST-RR S3-VO-ST-WR S3IP-VO-ST-RR S3IP-VO-ST-WR S3-SN-R S3-SN-W S3IP-SN-R S3IP-SN-W S2IP-SN-R S2IP-SN-W S2IP-SN-R3 Red LP Indoor Analogue Addressable Sounder White LP Indoor Analogue Addressable Sounder Red Outdoor Analogue Addressable Sounder White Outdoor Analogue Addressable System Sounder Red Outdoor Analogue Addressable System Sounder White Outdoor Analogue Addressable System Sounder 3 Way Red Outdoor Analogue Addressable System Sounder 3 Way White LP Outdoor Analogue Addressable Sounder/Strobe Red Lens Red LP Indoor Analogue Addressable Sounder/Strobe Red Lens White LP Indoor Analogue Addressable Sounder/Strobe Red Lens Red Outdoor Analogue Addressable Sounder/Strobe Red Lens White Outdoor LP Analogue Addressable Sounder/Strobe Red Lens Red Outdoor Analogue Addressable Sounder/Strobe 2 Way White Lens White Outdoor Analogue Addressable Sounder/Strobe 2 Way Amber Lens Red LP Indoor Voice Analogue Addressable Sounder White LP Indoor Voice Analogue Addressable Sounder Red LP Outdoor Voice Analogue Addressable Sounder White LP Outdoor Voice Analogue Addressable Sounder Red Outdoor Voice Analogue Addressable Sounder White Outdoor Voice Analogue Addressable Sounder Red LP Indoor Voice Analogue Addressable Sounder/Strobe Red Lens White LP Indoor Voice Analogue Addressable Sounder/Strobe Red Lens Red Outdoor Voice Analogue Addressable Sounder/Strobe Red Lens White LP Outdoor Voice Analogue Addressable Sounder/Strobe Red Lens Analogue Addressable Red LP Indoor Sounder with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable White LP Indoor Sounder with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable Red Outdoor Sounder with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable White Outdoor System Sounder with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable Red Outdoor System Sounder with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable White Outdoor System Sounder 3 Way with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable Red Outdoor System /Sounder 3 Way with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone LPCB Ref. No. 042ah/01 042ah/02 042ah/03 042ah/04 042ah/05 042ah/06 042ah/07 042ah/08 042ah/09 042ah/10 042ah/11 042ah/12 042ah/13 042ah/14 042ah/15 042ah/16 042ah/17 042ah/18 042ah/19 042ah/20 042ah/21 042ah/22 042ah/23 042ah/24 042ar/01 042ar/02 042ar/03 042ar/04 042ar/05 042ar/06 042ar/07

182

January 2009

SECTION 7: PART
Certificated Products S2IP-SN-W3 S3-SN-ST-RR S3-SN-ST-WR S3IP-SN-ST-RR S3IP-SN-ST-WR S3IP-SN-ST-RW S3IP-SN-ST-WA Analogue Addressable White LP Outdoor Sounder/Strobe Red Lens with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable Red LP Indoor Sounder/Strobe Red Lens with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable White LP Indoor Sounder/Strobe Red Lens with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable Red Outdoor Sounder/Strobe Red Lens with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable White Outdoor LP Sounder/Strobe Red Lens with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable Red Outdoor Sounder/Strobe 2 Way White Lens with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone Analogue Addressable White Outdoor Sounder / Strobe 2 Way Amber Lens with short circuit isolator Note: Meets the requirements of EN 54-3:2001 at Low Tone and High Tone LPCB Ref. No. 042ar/08 042ar/09 042ar/10 042ar/11 042ar/12 042ar/13 042ar/14

SOUNDERS

Global System Technology Plc


Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire LE65 1RT UK Tel: +44 (0)1283 225 478 Fax: +44 (0)1283 222 039 E-mail: info@gst.uk.com Website: www.gst.uk.com
Certificate No: 548e to EN 54-3:2001 Certificated Products C-9403 I-9403 Conventional sounder strobe Notes:Meets the requirements of EN 54-3: 2001 at the following tones: Fixed tone: 1.35Hz (400ms on / 340ms off) Intelligent sounder strobe Notes:Meets the requirements of EN 54-3: 2001 at the following tones: Mode I (for pre alarm): 0.61Hz (430ms on / 1200ms off) Mode II (for fire alarm): 1.30Hz (430ms on / 340ms off) LPCB Ref. No. 548e/01 548e/02

GLT Exports Limited


Detection House, 72-78 Morfa Road, Swansea SA1 2EN UK Tel: +44 (0)1792 455175 Fax: +44 (0)1792 455176 E-mail: ghassan@gltexports.com Website: www.gltexports.com
Certificate No: 692-(cl-1) to EN 54-3: 2001 + A1: 2002 Certificated Products ZTB8B - 41-005 ZTB6B/WP - 41-003A ZTB8B/WP - 41-006 8" (200mm) 24Vdc fire alarm bell with aluminimum gong 6" (150mm) fire alarm bell with aluminium gong complete with back box. 8" (200mm) fire alarm bell with aluminium gong complete with back box. LPCB Ref. No. 692a/02 692a/04 692a/05

January 2009

183

PART 3: SECTION 7
SOUNDERS

Group 4 Securicor Plc


Manor Royal, The Manor, Crawley, West Sussex RH10 9UN UK Tel: +44 (0)20 87707000 Fax: +44 (0)20 87722531 E-mail: allan.rignall@uae.g4s.com Website: www.g4s.com
Certificate No: 548e to EN 54-3:2001 Certificated Products GS403C GS403I Conventional sounder strobe Note: Meets the requirements of EN 54-3:2001 at the following tones: Fixed tone: 1.35Hz (400ms on / 340ms off) Intelligent sounder strobe Note: Meets the requirements of EN 54-3:2001 at the following tones: Mode I (for pre alarm): 0.61Hz (430ms on / 1200ms off) Mode II (for fire alarm): 1.30Hz (430ms on / 340ms off) LPCB Ref. No. 548e/01 548e/02

Gulf Security Technology Co. Ltd (Manufacturing Division of Global System Technology PLC)
No. 80 Changjiang East Road, Economic & Technological Development Zone, Qinhuangdao, Hebei Province 066004, Peoples Republic of China Tel: +86 0335 8502528 Fax: +86 0335 8508942 E-mail: gst@gst.com.cn Website: www.gst.com.cn
Certificate No: 548e to EN 54-3:2001 Certificated Products GST-HX-F8502 GST-HX-M8502 Conventional sounder strobe Notes: Meets the requirements of EN 54-3: 2001 at the following tones: Fixed tone: 1.35Hz (400ms on / 340ms off) Intelligent sounder strobe Notes: Meets the requirements of EN 54-3: 2001 at the following tones: Mode I (for pre alarm): 0.61Hz (430ms on / 1200ms off) Mode II (for fire alarm): 1.30Hz (430ms on / 340ms off) LPCB Ref. No. 548e/01 548e/02

HDR
Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260133 Fax: +44 (0)1634 260132 E-mail: info@hochikieurope.com Website: www.hochikieurope.com
Certificate No: 164h to EN 54 3: 2001 Certificated Products 1460040 Loop Powered Base Sounder (1426010 and 1226110 bases) Notes: 1) Meets the requirements of EN 54-3 at the following tones: 1 - 925 Hz : 250 ms / 628 Hz : 250 ms 2 - 925 Hz Continuous 3 - 628 Hz Continuous 4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms 5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms 6 - 925 Hz : 150 ms / Off : 600 ms 7 - 670 Hz : 250 ms / 845 Hz : 370 ms 8 - Whoop 500 Hz - 1200 Hz : 3000 ms / Off : 500 ms LPCB Ref. No. 164h/01

184

January 2009

SECTION 7: PART
Certificated Products 9 - 1200 Hz : 500 ms / 500 Hz : 500 ms 10 - 970 Hz : 500 ms / Off : 500 ms 11 - Sweep 800 Hz - 970 Hz over 140 ms (7 Hz) 12 - Sweep 800 Hz - 970 Hz over 1000 ms (1 Hz) 13 - Sweep 800 Hz - 970 Hz over 20 ms (50 Hz) 14 - Sweep 2400 Hz - 2850 Hz over 140 ms (7 Hz) 15 - Sweep 2400 Hz - 2850 Hz over 1000 ms (1 Hz) 16 - Sweep 300 Hz - 1200 Hz over 1000 ms (1 Hz) 17 - ISO8201 : 970 Hz : 500 ms 18 - ISO8201 : 2850 Hz : 500 ms 19 - 800 Hz : 250 ms / 970 Hz : 250 ms 20 - 2850 Hz Continuous 21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms 22 - 800 Hz : 500 ms / 970 Hz : 500 ms 23 - 2850 Hz : 500 ms / Off : 500 ms 24 - 925 Hz : 250 ms / Off : 1000 ms 25 - 970 Hz Continuous 26 - 660 Hz : 1800 ms / Off: 1800 ms 27 - 660 Hz : 6500 ms / Off : 13000 ms 28 - 660 Hz Continuous 29 - 554 Hz : 500 ms / 440 Hz : 500 ms 30 - 660 Hz : 500 ms / Off : 500 ms 31 - 2850 Hz : 150 ms / Off : 100 ms 32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz) 33 - Sweep 800 Hz - 970 Hz over 500 ms (2 Hz) 34 - 988 Hz : 250 ms / 645 Hz : 250 ms 35 - 510 Hz : 250 ms / 610 Hz : 250 ms 36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz) 37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz) 38 - 845 Hz Continuous 39 - 970 Hz : 1000 ms / Off : 1000 ms 40 - 800 Hz : 150 ms / 970 Hz : 150 ms 41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz) 42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz) 43 - 2850 Hz : 1000 ms / Off : 1000 ms 44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms 45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms 46 - 440 Hz : 600 ms / Off : 600 ms 47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms 48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms 49 - ISO8201 : Sweep 300 Hz - 1200 Hz : 500 ms / Off : 500 ms 50 - ISO8201 : Sweep 1200 Hz - 300 Hz : 500 ms / Off : 500 ms 51 - Whoop 500-1200 3.5s/0.5s Loop Powered Sounder/Base (1426010 and 1226110 bases) Notes 1) The beacon function of this device is not included in the scope of this approval 2) Meets the requirements of EN 54-3 at the following tones: 1 - 925 Hz : 250 ms / 628 Hz : 250 ms 2 - 925 Hz Continuous 3 - 628 Hz Continuous 4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms 5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms 6 - 925 Hz : 150 ms / Off : 600 ms 7 - 670 Hz : 250 ms / 845 Hz : 370 ms 8 - Whoop 500 Hz - 1200 Hz : 3000 ms / Off : 500 ms 9 - 1200 Hz : 500 ms / 500 Hz : 500 ms 10 - 970 Hz : 500 ms / Off : 500 ms 11 - Sweep 800 Hz - 970 Hz over 140 ms (7 Hz) 12 - Sweep 800 Hz - 970 Hz over 1000 ms (1 Hz) 13 - Sweep 800 Hz - 970 Hz over 20 ms (50 Hz) 14 - Sweep 2400 Hz - 2850 Hz over 140 ms (7 Hz) 15 - Sweep 2400 Hz - 2850 Hz over 1000 ms (1 Hz) 16 - Sweep 300 Hz - 1200 Hz over 1000 ms (1 Hz) 17 - ISO8201 : 970 Hz : 500 ms 18 - ISO8201 : 2850 Hz : 500 ms 19 - 800 Hz : 250 ms / 970 Hz : 250 ms 20 - 2850 Hz Continuous 21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms 22 - 800 Hz : 500 ms / 970 Hz : 500 ms 23 - 2850 Hz : 500 ms / Off : 500 ms 24 - 925 Hz : 250 ms / Off : 1000 ms 25 - 970 Hz Continuous LPCB Ref. No.

SOUNDERS

1460070

164h/03

January 2009

185

PART 3: SECTION 7
SOUNDERS
Certificated Products 26 - 660 Hz : 1800 ms / Off: 1800 ms 27 - 660 Hz : 6500 ms / Off : 13000 ms 28 - 660 Hz Continuous 29 - 554 Hz : 500 ms / 440 Hz : 500 ms 30 - 660 Hz : 500 ms / Off : 500 ms 31 - 2850 Hz : 150 ms / Off : 100 ms 32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz) 33 - Sweep 800 Hz - 970 Hz over 500 ms (2 Hz) 34 - 988 Hz : 250 ms / 645 Hz : 250 ms 35 - 510 Hz : 250 ms / 610 Hz : 250 ms 36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz) 37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz) 38 - 845 Hz Continuous 39 - 970 Hz : 1000 ms / Off : 1000 ms 40 - 800 Hz : 150 ms / 970 Hz : 150 ms 41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz) 42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz) 43 - 2850 Hz : 1000 ms / Off : 1000 ms 44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms 45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms 46 - 440 Hz : 600 ms / Off : 600 ms 47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms 48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms 49 - ISO8201 : Sweep 300 Hz - 1200 Hz : 500 ms / Off : 500 ms 50 - ISO8201 : Sweep 1200 Hz - 300 Hz : 500 ms / Off : 500 ms 51 - Whoop 500-1200 3.5s/0.5s Loop Powered Sounder Wall Sounder (1426010 and 1226110 bases) Notes: 1) Meets the requirements of EN 54-3 at the following tones: H1 - 925/628 at 2Hz H4 - French 554: 100ms / 440: 400ms H5 - Swedish 660: 150ms / Off: 150ms 8 - Whoop 500-1200 3s/0.5s 12 - Sweep 800/970 at 1Hz 15 - Sweep 2400-2850 at 1Hz 17 - 970:ISO8201 0.5s 18 - 2850:ISO820 0.5s LPCB Ref. No.

1460050

164h/02

Bases: 1226110 Isolator base 1426010 Standard Base

Hochiki Europe (UK) Limited


Grosvenor Road, Gillingham Business Park, Gillingham, Kent ME8 0SA UK Tel: +44 (0)1634 260133 Fax: +44 (0)1634 260132 Website: www.hochikieurope.com
Certificate No: 164h to EN 54 3: 2001 Certificated Products YBO-BS(HFP) Loop powered base sounder (YBN-R/3 and YBO-R/SCI bases) Note: 1) Meets the requirements of EN 54-3 at the following tones: 1 - 925 Hz : 250 ms / 628 Hz : 250 ms 2 - 925 Hz Continuous 3 - 628 Hz Continuous 4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms 5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms 6 - 925 Hz : 150 ms / Off : 600 ms 7 - 670 Hz : 250 ms / 845 Hz : 370 ms 8 - Whoop 500 Hz - 1200 Hz : 3000 ms / Off : 500 ms 9 - 1200 Hz : 500 ms / 500 Hz : 500 ms 10 - 970 Hz : 500 ms / Off : 500 ms 11 - Sweep 800 Hz - 970 Hz over 140 ms (7 Hz) 12 - Sweep 800 Hz - 970 Hz over 1000 ms (1 Hz) LPCB Ref. No. 164h/01

186

January 2009

SECTION 7: PART
Certificated Products 13 - Sweep 800 Hz - 970 Hz over 20 ms (50 Hz) 14 - Sweep 2400 Hz - 2850 Hz over 140 ms (7 Hz) 15 - Sweep 2400 Hz - 2850 Hz over 1000 ms (1 Hz) 16 - Sweep 300 Hz - 1200 Hz over 1000 ms (1 Hz) 17 - ISO8201 : 970 Hz : 500 ms 18 - ISO8201 : 2850 Hz : 500 ms 19 - 800 Hz : 250 ms / 970 Hz : 250 ms 20 - 2850 Hz Continuous 21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms 22 - 800 Hz : 500 ms / 970 Hz : 500 ms 23 - 2850 Hz : 500 ms / Off : 500 ms 24 - 925 Hz : 250 ms / Off : 1000 ms 25 - 970 Hz Continuous 26 - 660 Hz : 1800 ms / Off: 1800 ms 27 - 660 Hz : 6500 ms / Off : 13000 ms 28 - 660 Hz Continuous 29 - 554 Hz : 500 ms / 440 Hz : 500 ms 30 - 660 Hz : 500 ms / Off : 500 ms 31 - 2850 Hz : 150 ms / Off : 100 ms 32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz) 33 - Sweep 800 Hz - 970 Hz over 500 ms (2 Hz) 34 - 988 Hz : 250 ms / 645 Hz : 250 ms 35 - 510 Hz : 250 ms / 610 Hz : 250 ms 36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz) 37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz) 38 - 845 Hz Continuous 39 - 970 Hz : 1000 ms / Off : 1000 ms 40 - 800 Hz : 150 ms / 970 Hz : 150 ms 41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz) 42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz) 43 - 2850 Hz : 1000 ms / Off : 1000 ms 44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms 45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms 46 - 440 Hz : 600 ms / Off : 600 ms 47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms 48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms 49 - ISO8201 : Sweep 300 Hz - 1200 Hz : 500 ms / Off : 500 ms 50 - ISO8201 : Sweep 1200 Hz - 300 Hz : 500 ms / Off : 500 ms 51 - Whoop 500-1200 3.5s/0.5s Loop powered base sounder white version (YBN-R/3 and YBO-R/SCI bases) Note: 1) Meets the requirements of EN 54-3 at the following tones: 1 - 925 Hz : 250 ms / 628 Hz : 250 ms 2 - 925 Hz Continuous 3 - 628 Hz Continuous 4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms 5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms 6 - 925 Hz : 150 ms / Off : 600 ms 7 - 670 Hz : 250 ms / 845 Hz : 370 ms 8 - Whoop 500 Hz - 1200 Hz : 3000 ms / Off : 500 ms 9 - 1200 Hz : 500 ms / 500 Hz : 500 ms 10 - 970 Hz : 500 ms / Off : 500 ms 11 - Sweep 800 Hz - 970 Hz over 140 ms (7 Hz) 12 - Sweep 800 Hz - 970 Hz over 1000 ms (1 Hz) 13 - Sweep 800 Hz - 970 Hz over 20 ms (50 Hz) 14 - Sweep 2400 Hz - 2850 Hz over 140 ms (7 Hz) 15 - Sweep 2400 Hz - 2850 Hz over 1000 ms (1 Hz) 16 - Sweep 300 Hz - 1200 Hz over 1000 ms (1 Hz) 17 - ISO8201 : 970 Hz : 500 ms 18 - ISO8201 : 2850 Hz : 500 ms 19 - 800 Hz : 250 ms / 970 Hz : 250 ms 20 - 2850 Hz Continuous 21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms 22 - 800 Hz : 500 ms / 970 Hz : 500 ms 23 - 2850 Hz : 500 ms / Off : 500 ms 24 - 925 Hz : 250 ms / Off : 1000 ms 25 - 970 Hz Continuous 26 - 660 Hz : 1800 ms / Off: 1800 ms 27 - 660 Hz : 6500 ms / Off : 13000 ms 28 - 660 Hz Continuous 29 - 554 Hz : 500 ms / 440 Hz : 500 ms 30 - 660 Hz : 500 ms / Off : 500 ms LPCB Ref. No.

SOUNDERS

YBO-BS(WHT)

164h/01

January 2009

187

PART 3: SECTION 7
SOUNDERS
Certificated Products 31 - 2850 Hz : 150 ms / Off : 100 ms 32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz) 33 - Sweep 800 Hz - 970 Hz over 500 ms (2 Hz) 34 - 988 Hz : 250 ms / 645 Hz : 250 ms 35 - 510 Hz : 250 ms / 610 Hz : 250 ms 36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz) 37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz) 38 - 845 Hz Continuous 39 - 970 Hz : 1000 ms / Off : 1000 ms 40 - 800 Hz : 150 ms / 970 Hz : 150 ms 41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz) 42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz) 43 - 2850 Hz : 1000 ms / Off : 1000 ms 44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms 45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms 46 - 440 Hz : 600 ms / Off : 600 ms 47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms 48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms 49 - ISO8201 : Sweep 300 Hz - 1200 Hz : 500 ms / Off : 500 ms 50 - ISO8201 : Sweep 1200 Hz - 300 Hz : 500 ms / Off : 500 ms 51 - Whoop 500-1200 3.5s/0.5s Loop powered wall sounder (YBN-R/3 and YBO-R/SCI bases) Note: 1) Meets the requirements of EN 54-3 at the following tones: H1 - 925/628 at 2Hz H4 - French 554: 100ms / 440: 400ms H5 - Swedish 660: 150ms / Off: 150ms 8 - Whoop 500-1200 3s/0.5s 12 - Sweep 800/970 at 1Hz 15 - Sweep 2400-2850 at 1Hz 17 - 970:ISO8201 0.5s 18 - 2850:ISO820 0.5s Loop powered wall sounder - white version (YBN-R/3 and YBO-R/SCI bases) Note: 1) Meets the requirements of EN 54-3 at the following tones: H1 - 925/628 at 2Hz H4 - French 554: 100ms / 440: 400ms H5 - Swedish 660: 150ms / Off: 150ms 8 - Whoop 500-1200 3s/0.5s 12 - Sweep 800/970 at 1Hz 15 - Sweep 2400-2850 at 1Hz 17 - 970:ISO8201 0.5s 18 - 2850:ISO820 0.5s Loop powered wall sounder - weatherproof version (YBN-R/3, YBO-R/SCI and WS2WPK base) Note: 1) Meets the requirements of EN 54-3 at the following tones: H1 - 925/628 at 2Hz H4 - French 554: 100ms / 440: 400ms H5 - Swedish 660: 150ms / Off: 150ms 8 - Whoop 500-1200 3s/0.5s 12 - Sweep 800/970 at 1Hz 15 - Sweep 2400-2850 at 1Hz 17 - 970:ISO8201 0.5s 18 - 2850:ISO820 0.5s Loop powered base sounder and beacon (YBN-R/3 and YBO-R/SCI bases) Notes: 1) The beacon function of this device is not included in the scope of this approval 2) Meets the requirements of EN 54-3 at the following tones: 1 - 925 Hz : 250 ms / 628 Hz : 250 ms 2 - 925 Hz Continuous 3 - 628 Hz Continuous 4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms 5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms 6 - 925 Hz : 150 ms / Off : 600 ms 7 - 670 Hz : 250 ms / 845 Hz : 370 ms 8 - Whoop 500 Hz - 1200 Hz : 3000 ms / Off : 500 ms 9 - 1200 Hz : 500 ms / 500 Hz : 500 ms 10 - 970 Hz : 500 ms / Off : 500 ms 11 - Sweep 800 Hz - 970 Hz over 140 ms (7 Hz) 12 - Sweep 800 Hz - 970 Hz over 1000 ms (1 Hz) 13 - Sweep 800 Hz - 970 Hz over 20 ms (50 Hz) LPCB Ref. No.

CHQ-WS2(HFP)

164h/02

CHQ-WS2(WHT)

164h/02

CHQ-WS2/W

164h/02

YBO-BSB(HFP)

164h/03

188

January 2009

SECTION 7: PART
Certificated Products 14 - Sweep 2400 Hz - 2850 Hz over 140 ms (7 Hz) 15 - Sweep 2400 Hz - 2850 Hz over 1000 ms (1 Hz) 16 - Sweep 300 Hz - 1200 Hz over 1000 ms (1 Hz) 17 - ISO8201 : 970 Hz : 500 ms 18 - ISO8201 : 2850 Hz : 500 ms 19 - 800 Hz : 250 ms / 970 Hz : 250 ms 20 - 2850 Hz Continuous 21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms 22 - 800 Hz : 500 ms / 970 Hz : 500 ms 23 - 2850 Hz : 500 ms / Off : 500 ms 24 - 925 Hz : 250 ms / Off : 1000 ms 25 - 970 Hz Continuous 26 - 660 Hz : 1800 ms / Off: 1800 ms 27 - 660 Hz : 6500 ms / Off : 13000 ms 28 - 660 Hz Continuous 29 - 554 Hz : 500 ms / 440 Hz : 500 ms 30 - 660 Hz : 500 ms / Off : 500 ms 31 - 2850 Hz : 150 ms / Off : 100 ms 32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz) 33 - Sweep 800 Hz - 970 Hz over 500 ms (2 Hz) 34 - 988 Hz : 250 ms / 645 Hz : 250 ms 35 - 510 Hz : 250 ms / 610 Hz : 250 ms 36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz) 37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz) 38 - 845 Hz Continuous 39 - 970 Hz : 1000 ms / Off : 1000 ms 40 - 800 Hz : 150 ms / 970 Hz : 150 ms 41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz) 42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz) 43 - 2850 Hz : 1000 ms / Off : 1000 ms 44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms 45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms 46 - 440 Hz : 600 ms / Off : 600 ms 47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms 48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms 49 - ISO8201 : Sweep 300 Hz - 1200 Hz : 500 ms / Off : 500 ms 50 - ISO8201 : Sweep 1200 Hz - 300 Hz : 500 ms / Off : 500 ms 51 - Whoop 500-1200 3.5s/0.5s Loop powered base sounder and beacon white version (YBN-R/3 and YBO-R/SCI bases) Notes: 1) The beacon function of this device is not included in the scope of this approval 2) Meets the requirements of EN 54-3 at the following tones: 1 - 925 Hz : 250 ms / 628 Hz : 250 ms 2 - 925 Hz Continuous 3 - 628 Hz Continuous 4 - (French) 554 Hz : 100 ms / 440 Hz : 400 ms 5 - (Swedish) 660 Hz : 150 ms / Off : 150 ms 6 - 925 Hz : 150 ms / Off : 600 ms 7 - 670 Hz : 250 ms / 845 Hz : 370 ms 8 - Whoop 500 Hz - 1200 Hz : 3000 ms / Off : 500 ms 9 - 1200 Hz : 500 ms / 500 Hz : 500 ms 10 - 970 Hz : 500 ms / Off : 500 ms 11 - Sweep 800 Hz - 970 Hz over 140 ms (7 Hz) 12 - Sweep 800 Hz - 970 Hz over 1000 ms (1 Hz) 13 - Sweep 800 Hz - 970 Hz over 20 ms (50 Hz) 14 - Sweep 2400 Hz - 2850 Hz over 140 ms (7 Hz) 15 - Sweep 2400 Hz - 2850 Hz over 1000 ms (1 Hz) 16 - Sweep 300 Hz - 1200 Hz over 1000 ms (1 Hz) 17 - ISO8201 : 970 Hz : 500 ms 18 - ISO8201 : 2850 Hz : 500 ms 19 - 800 Hz : 250 ms / 970 Hz : 250 ms 20 - 2850 Hz Continuous 21 - 2400 Hz : 250 ms / 2850 Hz : 250 ms 22 - 800 Hz : 500 ms / 970 Hz : 500 ms 23 - 2850 Hz : 500 ms / Off : 500 ms 24 - 925 Hz : 250 ms / Off : 1000 ms 25 - 970 Hz Continuous 26 - 660 Hz : 1800 ms / Off: 1800 ms 27 - 660 Hz : 6500 ms / Off : 13000 ms 28 - 660 Hz Continuous 29 - 554 Hz : 500 ms / 440 Hz : 500 ms LPCB Ref. No.

SOUNDERS

YBO-BSB(WHT)

164h/03

January 2009

189

PART 3: SECTION 7
SOUNDERS
Certificated Products 30 - 660 Hz : 500 ms / Off : 500 ms 31 - 2850 Hz : 150 ms / Off : 100 ms 32 - Sweep 2400 Hz - 2850 Hz over 20 ms (50 Hz) 33 - Sweep 800 Hz - 970 Hz over 500 ms (2 Hz) 34 - 988 Hz : 250 ms / 645 Hz : 250 ms 35 - 510 Hz : 250 ms / 610 Hz : 250 ms 36 - Sweep 800 Hz - 970 Hz over 110 ms (9 Hz) 37 - Sweep 800 Hz - 970 Hz over 330 ms (3 Hz) 38 - 845 Hz Continuous 39 - 970 Hz : 1000 ms / Off : 1000 ms 40 - 800 Hz : 150 ms / 970 Hz : 150 ms 41 - Sweep 2400 Hz - 2850 Hz over 110 ms (9 Hz) 42 - Sweep 2400 Hz - 2850 Hz over 330 ms (3 Hz) 43 - 2850 Hz : 1000 ms / Off : 1000 ms 44 - 2400 Hz : 150 ms / 2850 Hz : 150 ms 45 - (German) Whoop 1200 Hz - 500 Hz : 1000ms / Off : 10 ms 46 - 440 Hz : 600 ms / Off : 600 ms 47 - Whoop 500 Hz - 1200 Hz : 3750 ms / Off : 250 ms 48 - ISO8201 : 925 Hz, 628 Hz : 250 ms / Off 500 ms 49 - ISO8201 : Sweep 300 Hz - 1200 Hz : 500 ms / Off : 500 ms 50 - ISO8201 : Sweep 1200 Hz - 300 Hz : 500 ms / Off : 500 ms 51 - Whoop 500-1200 3.5s/0.5s Bases: YBN-R/3 Analogue mounting base (ivory and white) YBO-R/SCI Isolator base LPCB Ref. No.

Horing LIH Industrial Co Ltd


No. 17-6, Ai-Chien Road, Hu-Hsi Village, Yuan-Shan Hsiang (264), Ilan Hsien, Taiwan ROC Tel: +886 2 22487599 Fax: +886 2 22407752
Certificate No: 506e to EN 54-3: 2001 Certificated Products AH-0218 AH-03127S Conventional fire alarm bell Conventional type A electronic sounder Notes: Meets the requirements of EN54-3: 2001 at the following tones: 1-Alternating tones 800/970Hz at 2Hz 2-Sweeping 800/970Hz at 7Hz LPCB Ref. No. 506e/01 506e/02

Hosiden Besson Limited


St Joseph's Close Trading Estate, St Joseph's Close, Hove, East Sussex BN3 7EZ UK Tel: +44 (0)1273 860000 Fax: +44 (0)1273 777501 E-mail: info@hbl.co.uk Website: www.hbl.co.uk
Certificate No: 715a to EN 54-3: 2001 Certificated Products Banshee MT Sounder (892 shallow base version and deep base version) Notes: 1) Certified to EN 54-3: 2001 with the following tones: Sound 2 Banshee LF Sound 13 Banshee HF (and Bedlam) Sound 19 Slow Whoop (Dutch) Sound 20 DIN Klung (German) Sound 21 AFNOR (French) 2) Approved as Type A when used with shallow base (892) & Type B when used with deep base (893) LPCB Ref. No. 715a/01

190

January 2009

SECTION 7: PART
Certificated Products Flashtone Banshee MT 3) Approved voltage range 10-28V Conventional 32 tone sounder with 1 Watt Xenon beacon (shallow & deep bases) Notes: 1) Suitable for Type A indoor application when used with shallow base & deep base 2) Approved with body moulding & lens colour variations 3) Approved at 12 & 24 VDC 4) Meets requirements of EN 54-3: 2001 with the following tones: Sound 2 Banshee LF Fast Sweep - 800Hz - 950Hz Swept @ 9Hz Sound 13 Banshee / Bedlam HF Fast Sweep - 2400Hz - 2900Hz @ 9Hz Sound 15 Banshee / Bedlam HF Continuous - Continuous 2900Hz @ 3Hz Sound 19 Slow Whoop (Dutch) - 500Hz - 1200Hz over 3.5s then silence for 0.5s repeat Sound 20 DIN Tone (DK) - 1200Hz - 500Hz over 1s, silence 10ms repeat Sound 21 French Fire Sound - 554Hz for 100ms & 440Hz for 400ms Conventional 32 tone sounder with LED beacon & deep bases) Notes: 1) Suitable for Type A indoor application when used with shallow or deep base 2) Suitable for Type B outdoor application when used with deep base & sealing gasket 3) Approved at 12 & 24 VDC 4) Approved with body moulding & lens colour variations 5) Meets requirements of EN 54-3: 2001 with the following tones: Sound 2 Banshee LF Fast Sweep - 800Hz - 950Hz Swept @ 9Hz Sound 13 Banshee / Bedlam HF Fast Sweep - 2400Hz - 2900Hz @ 9Hz Sound 15 Banshee / Bedlam HF Continuous - Continuous 2900Hz @ 3Hz Sound 19 Slow Whoop (Dutch) - 500Hz - 1200Hz over 3.5s then silence for 0.5s repeat Sound 20 DIN Tone (DK) - 1200Hz - 500Hz over 1s, silence 10ms repeat Sound 21 French Fire Sound - 554Hz for 100ms & 440Hz for 400ms Conventional 32 Tone Sounder Notes: 1) Suitable for Type A indoor application only 2) Approved at 12 & 24 VDC 3) Approved with body moulding colour variations 4) To be used in conjunction with a suitable detector when supplied without cover 5) Meets requirements of EN 54-3: 2001 with the following tones: Sound 2 Banshee LF Fast Sweep - 800Hz - 950Hz Swept @ 9Hz Sound 13 Banshee / Bedlam HF Fast Sweep - 2400Hz - 2900Hz @ 9Hz Sound 15 Banshee / Bedlam HF Continuous - Continuous 2900Hz @ 3Hz Sound 19 Slow Whoop (Dutch) - 500Hz - 1200Hz over 3.5s then silence for 0.5s repeat Sound 20 DIN Tone (DK) - 1200Hz - 500Hz over 1s, silence 10ms repeat Sound 21 French Fire Sound - 554Hz for 100ms & 440Hz for 400ms Conventional 32 tone sounder with bipolar supply input (shallow & deep bases) Notes: 1) Suitable for Type A indoor application when used with shallow or deep base 2) Suitable for Type B outdoor application when used with deep base & sealing gasket 3) Approved at 12 & 24 VDC 4) Approved with body moulding colour variations 5) Meets requirements of EN 54-3: 2001 with the following tones: Sound 2 Banshee LF Fast Sweep - 800Hz - 950Hz Swept @ 9Hz Sound 13 Banshee / Bedlam HF Fast Sweep - 2400Hz - 2900Hz @ 9Hz Sound 15 Banshee / Bedlam HF Continuous - Continuous 2900Hz @ 3Hz Sound 19 Slow Whoop (Dutch) - 500Hz - 1200Hz over 3.5s then silence for 0.5s repeat Sound 20 DIN Tone (DK) - 1200Hz - 500Hz over 1s, silence 10ms repeat Sound 21 French Fire Sound - 554Hz for 100ms & 440Hz for 400ms Conventional 2 tone sounder Notes: 1) Suitable for Type A indoor application only 2) Approved with body moulding colour variations 3) Meets requirements of EN 54-3: 2001 with the following tones: Sound 1 Continuous 850 Hz Sound 2 Fast Sweep 800 - 950 Hz @ 9 Hz LPCB Ref. No. 715a/02

SOUNDERS

LED Flashtone Banshee MT

715a/03

Wafer MT

715a/04

Bipolar Banshee MT

715a/05

FM Bedrrom

715a/06

Bases: Shallow base (various colour options) Deep base (various colour options)

January 2009

191

PART 3: SECTION 7
SOUNDERS

KAC Alarm Company Limited


15-19 Trescott Road, Trafford Park, Smallwood, Redditch, Worcester B98 7AH UK Tel: +44 (0)1527 406655 Fax: +44 (0)1527 406677 E-mail: sales@kac.co.uk OR marketing@kac.co.uk Website: www.kac.co.uk
Certificate No: 166c to EN 54-3: 2001 Certificate No: 166d to EN 54: Part 3: 2001 and CEA GEI 1-052 Draft 2.0: 11.06.97 Certificated Products EMA1224B4R EMA1224B4W SOU-SSR-4 SOU-SSW-4 SOU-LPR-4 SOU-LPW-4 SOU-SR-4 SOU-SW-4 WMSST-xx-P01 4 Tone wall mounting conventional sounder, red. Note: Meets the requirements of EN 54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v 4 Tone wall mounting conventional sounder, white Note: Meets the requirements of EN 54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v 4 Tone surface mounting conventional sounder with sealing kit, red Note: Meets the requirements of EN 54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v 4 Tone surface mounting conventional sounder with sealing kit, white Note: Meets the requirements of EN 54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v 4 Tone low profile mounting conventional sounder, red Note: Meets the requirements of EN 54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v 4 Tone low profile mounting conventional sounder, white. Note: Meets the requirements of EN 54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v 4 Tone surface mounting conventional sounder, red. Note: Meets the requirements of EN 54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v 4 Tone surface mounting conventional sounder, white. Note: Meets the requirements of EN 54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Intelligent wall mounted sounder strobe Notes: 1) xx indicates body colour. R=Red, W=Bright White 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirements of EN54-3 for all tones and output levels at voltage range 1532v. Intelligent wall mounted sounder Note: 1) xx indicates body colour. RR=Red, WW=Bright White Meets the requirements of EN54-3 for all tones and output levels at voltage range 1532v. Intelligent integrated detector base sounder strobe Notes: 1) xx indicates body colour. R=Red, W=Bright White, D=Detector White, K=Black 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. Intelligent integrated detector base sounder Note: 1) xx indicates body colour. RR=Red, WW=Bright White, DD=Detector White, KK=Black Intelligent non-integrated detector base sounder strobe Notes: 1) xx indicates body colour. R=Red, W=Bright White 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Intelligent non-integrated detector base sounder Note: 1) xx indicates body colour. RR=Red, WW=Bright White Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. Conventional Type A wall mounted sounder (red) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A wall mounted sounder (white) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v LPCB Ref. No. 166c/01 166c/02 166c/03 166c/04 166c/05 166c/06 166c/07 166c/08 166c/09

WMSOU-xx-P01

166c/10

IBSST-xx-P01

166c/11

IBSOU-xx-P01 DBSST-xx-P01-C

166c/12 166c/13

DBSOU-xx-P01-C

166c/14

EMA1224FR EMA1224FW

166c/15 166c/16

192

January 2009

SECTION 7: PART
Certificated Products SOU-LPR-14 SOU-LPW-14 SOU-SR-14 SOU-SW-14 SOU-SSR-14 SOU-SSW-14 DBS-14 DBS-R-14 DBS-W-14 DBS1224FW DBS-4 DBS-R-4 DBS-W-4 DBS1224B4W WMSST-xx-P02 Conventional Type A wall mounted sounder with low profile mounting box (red) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A wall mounted sounder with low profile mounting box (white) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A wall mounted sounder with mounting box (red) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A wall mounted sounder with mounting box (white) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type B wall mounted sounder with mounting box & sealing kit (red) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type B wall mounted sounder with mounting box & sealing kit (white) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A sounder base (white) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A sounder base (white), supplied with red lid Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A sounder base (white), supplied with white lid Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A wall mounted sounder Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A sounder base (white) Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A sounder base (white), supplied with red lid Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A sounder base (white), supplied with white lid Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A wall mounted sounder Note: Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Intelligent wall mounted sounder strobe with short circuit isolator Notes: 1) xx indicates body colour. R=Red, W=Bright White 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirement of EN54-3 for all tones and output levels at voltage range 15.-32v. Intelligent wall mounted sounder with short circuit isolator Note: 1) xx indicates body colour. RR=Red, WW=Bright White Meets the requirements of EN54-3 for all tones and output levels at voltage 15-32v. Intelligent integrated detector base sounder strobe with short circuit isolator Notes: 1) xx indicates body colour. R=Red, W=Bright White, D=Detector White, K=Black 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. Intelligent integrated detector base sounder with short circuit isolator Note: 1) xx indicates body colour. RR=Red, WW=Bright White, DD=Detector White, KK=Black Intelligent non-integrated detector base sounder strobe with short circuit isolator Notes: 1) xx indicates body colour. R=Red, W=Bright White 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Intelligent non-integrated detector base sounder with short circuit isolator Note: 1) xx indicates body colour. RR=Red, WW=Bright White Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. Conventional Type A wall mounted sounder strobe (ELPBR/W, ESBR/W and ESBRS/WS bases) Notes: LPCB Ref. No. 166c/17 166c/18 166c/19 166c/20 166c/21 166c/22 166c/23 166c/24 166c/25 166c/26 166c/27 166c/28 166c/29 166c/30 166d/01

SOUNDERS

WMSOU-xx-P02

166d/02

IBSST-xx-P02

166d/03

IBSOU-xx-P02 DBSST-xx-P02-C

166d/04 166d/05

DBSOU-xx-P02-C

166d/06

EMA12Fxxxx

166c/31

January 2009

193

PART 3: SECTION 7
SOUNDERS
Certificated Products 1) Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 1014v 2) xxxx indicates body colour. RS=Red, WS=White 3) xxxx indicates lens colour. SR=Red, SA=Amber, SC=Clear Conventional Type A wall mounted sounder strobe (ELPBR/W, ESBR/W and ESBRS/WS bases) Notes: 1) Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 2127v 2) xxxx indicates body colour. RS=Red, WS=White 3) xxxx indicates lens colour. S-=Red and Amber supplied, SR=Red, SA=Amber, SB=Blue Conventional Type A wall mounted sounder strobe (white) (ELPBR/W, ESBR/W and ESBRS/WS bases) Notes: 1) Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 1014v 2) xxWx indicates base type. LP=ELPBR/W, -S=ESBR/W, SS=ESBRS/WS. 3) xxWx indicates lens colour. R=Red, A=Amber, B=Blue, G=Green Conventional Type A wall mounted sounder strobe (red) (ELPBR/W, ESBR/W and ESBRS/WS bases) Notes: 1) Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 2127v 2) xxRx indicates base type. LP=ELPBR/W, -S=ESBR/W, SS=ESBRS/WS. 3) xxRx indicates lens colour. R=Red, A=Amber, B=Blue Intelligent wall mounted sounder strobe with short circuit isolator. Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. Intelligent wall mounted sounder strobe. Meets the requirements of EN54-3 for all tones and output levels at voltage range 1532v. Meets the requirements of EN54-3 for all tones and output levels at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. LPCB Ref. No.

EMA24Fxxxx

166c/32

SST-xxWx-14

166c/33

SST-xxRx-14

166c/34

WMSST-RR-P30 WMSST-RR-P29 IBSST-DR-P29

166d/07 166c/35 166c/36

Bases: ELPBR/W Low profile base IP21C, red or white ESBR/W Standard base IP54, red or white ESBRS/WS Standard base and IP66 sealing kit, red or white

Klaxon Signals Limited


Wrigley Street, Oldham, Lancs OL4 1HW UK Tel: +44 (0)161 287 5555 Fax: +44 (0)161 287 5511 E-mail: sales@klaxonsignals.com Website: www.klaxonsignals.com
Certificate No: 717a to EN 54-3: 2001 Certificated Products 18-980502 Conventional Sounder with LED Strobe (Red Head / Red Base) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used the with the shallow base & Type B when used with the deep base only 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Sounder with LED Strobe (Red Head / White Base) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used the with the shallow base Type B when used with the deep base only 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Conventional Sounder with LED Strobe (Amber Head / Red Base) (18-980467, 18980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used the with the shallow base & Type B when LPCB Ref. No. 717a/01

18-980516

717a/02

18-980505

717a/03

194

January 2009

SECTION 7: PART
Certificated Products used with the deep base only 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Conventional Sounder with LED Strobe (Amber Head / White Base) (18-980467, 18980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used the with the shallow base & Type B when used with the deep base only 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Conventional Sounder (Red) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used the with the shallow base Type B when used with the deep base only 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Conventional Sounder (White) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used the with the shallow base & Type B when used with the deep base only 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Universal base sounder (white) Notes: 1) Meets the requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Universal base sounder (cream) Notes: 1)Meets the requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Base sounder Notes: 1) Meets the requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Universal base sounder (Red) Notes: 1) Meets the requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Base sounder with diode Notes: 1) Meets the requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13 Conventional Sounder with (Red Head / Red Base) LED Strobe Common Operation 18-980513, 18-980468 & 18-980514 base) Notes: 1) The above sounder is Type A when used with the shallow base & Type B when used with the deep base only. 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13. Conventional Sounder with Red LED Strobe Common Operation (Clear Lens / White Base) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used with the shallow base & Type B when used with the deep base only. 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13. Conventional Sounder with LED Strobe Common Operation (Amber Head / Red Base) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used with the shallow base & Type B when used with the deep base only. 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13. Conventional Sounder with Red LED Strobe (Clear Lens / White Base) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used with the shallow base & Type B when used with the deep base only. 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13. Conventional Sounder with LED Strobe Common Operation (Red Head / White Base) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used with the shallow base & Type B when used with the deep base only. 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13. Conventional Sounder with LED Strobe Common Operation (Amber Head / White Base) (18-980467, 18-980513, 18-980468 & 18-980514 bases) Notes: 1) The above sounder is Type A when used with the shallow base & Type B when used LPCB Ref. No. 717a/04

SOUNDERS

18-980517

18-980527

717a/05

18-980528

717a/06

18-980532 18-980533 17-970315 18-980634 17-970335 18-980575

717a/07 717a/08 717a/09 717a/14 717a/15 717a/10

18-980582

717a/11

18-980612

717a/12

18-980613

717a/13

18-980723

717a/16

18-980724

717a/17

January 2009

195

PART 3: SECTION 7
SOUNDERS
Certificated Products with the deep base only. 2) Meets requirements of EN 54-3:2001 at tones 1,2,3,6,7 & 13. Bases: 18-980467 Shallow base (red) 18-980513 Shallow base (white) 18-980468 Deep base (red) 18-980514 Deep base (white) LPCB Ref. No.

Morley-IAS Fire Systems By Honeywell


Charles Avenue, Burgess Hill, West Sussex RH15 9UF Tel: +44 (0)1444 235556 Fax: +44 (0)1444 254410 E-mail: sales@morleyias.co.uk Website: www.morley-ias.co.uk

Certificate No: 166c to EN 54-3: 2001 Certificate No: 166d to EN 54-3: 2001 and CEA GEI 1-052 Draft 2.0: 11.06.97 Certificated Products MI-WSDB-X-XX Intelligent wall mounted sounder strobe Notes: 1) x-xx indicates body colour. R=Red, W=Detector White 2) x-xx indicate lens colour. RD=Red, AM=Amber, GR=Green, BL=Blue, CL=Clear Intelligent wall mounted sounder Note: 1) x indicates body colour. R=Red, W=Detector White Intelligent integrated detector base sounder strobe Notes: 1) x-xx indicates body colour. R=Red, W=Detector White, PW=Pure White, B=Black 2) x-xx indicate lens colour. RD=Red, AM=Amber, GR=Green, BL=Blue, CL=Clear Intelligent integrated detector base sounder Note: 1) x indicates body colour. R=Red, W=Detector White, PW=Pure White, B=Black Intelligent wall mounted sounder strobe with short circuit isolator Notes: 1) x-xx indicates body colour. R=Red, W=Detector White 2) x-xx indicate lens colour. RD=Red, AM=Amber, GR=Green, BL=Blue, CL=Clear Intelligent wall mounted sounder with short circuit isolator Note: 1) x indicates body colour. R=Red, W=Detector White Intelligent integrated detector base sounder strobe with short circuit isolator Notes: 1) x-xx indicates body colour. R=Red, W=Detector White, PW=Pure White, B=Black 2) x-xx indicate lens colour. RD=Red, AM=Amber, GR=Green, BL=Blue, CL=Clear Intelligent integrated detector base sounder with short circuit Note: 1) x indicates body colour. R=Red, W=Detector White, PW=Pure White, B=Black LPCB Ref. No. 166c/09

MI-WSD-X MI-IBSDB-X-XX

166c/10 166c/11

MI-IBSD-X MI-WSDB-X-XX-I

166c/12 166d/01

MI-WSD-X-1 MI-IBSDB-X-XX-I

166d/02 166d/03

MI-IBSD-X-I

166d/04

Napco Gulf Security Group


P.O. Box 54533, Dubai Airport Free Zone, UAE Tel: +971 4 2997703 Fax: +971 4 2997704 E-mail: info@napcogulfsecurity.com Website: www.napcogulfsecurity.com
Certificate No: 548e to EN 54-3: 2001 Certificated Products NC-403 Conventional sounder strobe Notes: Meets the requirements of EN 54-3: 2001 at the following tones: LPCB Ref. No. 548e/01

196

January 2009

SECTION 7: PART
Certificated Products NI-403 Fixed tone: 1.35Hz (400ms on / 340ms off) Intelligent sounder strobe Notes: Meets the requirements of EN 54-3: 2001 at the following tones: Mode I (for pre alarm): 0.61Hz (430ms on / 1200ms off) Mode II (for fire alarm): 1.30Hz (430ms on / 340ms off) LPCB Ref. No. 548e/02

SOUNDERS

Notifier By Honeywell
Charles Avenue, Burgess Hill, West Sussex RH15 9UF UK Tel: +44 (0)1444 230230 Fax: +44 (0)1444 230689 E-mail: sales@notifierfiresystems.co.uk Website: www.notifierfiresystems.co.uk

Certificate No: 166c to EN 54-3: 2001 Certificate No: 166d to EN 54-3: 2001 and CEA GEI 1-052 Draft 2.0: 11.06.97 Certificated Products AWSB32/X/X Intelligent wall mounted sounder strobe Notes: 1) x/x indicates body colour. R=Red, W=Detector White 2) x/x indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Intelligent wall mounted sounder Note: 1) x indicates body colour. R=Red, W=Detector White Intelligent integrated detector base sounder strobe Notes: 1) x/x indicates body colour. R=Red, W=Detector White, PW=Pure White, B=Black 2) x/x indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Intelligent integrated detector base sounder Note: 1) x indicates body colour. R=Red, W=Detector White, PW=Pure White, B=Black Intelligent wall mounted sounder strobe with short circuit isolator Notes: 1) x/x indicates body colour. R=Red, W=Detector White 2) x/x indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Intelligent wall mounted sounder with short circuit isolator Note: 1) x indicates body colour. R=Red, W=Detector White Intelligent integrated detector base sounder strobe with short circuit isolator Notes: 1) x/x indicates body colour. R=Red, W=Detector White, PW=Pure White, B=Black 2) x/x indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Intelligent integrated detector base sounder with short circuit isolator Note: 1) x indicates body colour. R=Red, W=Detector White, PW=Pure White, B=Black 4 Tone wall mounting conventional sounder (red) Note: 1) Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v 4 Tone wall mounting conventional sounder (white) Note: 1) Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A wall mounted sounder (red) Note: 1) Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v Conventional Type A wall mounted sounder (white) Note: 1) Meets the requirements of EN54-3 for all tones and output levels at voltage ranges 10-14v and 21-27v LPCB Ref. No. 166c/09

AWS32/X ABSB32/X/X

166c/10 166c/11

ABS32/X AWSB32/X/X-I

166c/12 166d/01

AWS32/X-I ABSB32/X/X-I

166d/02 166d/03

ABS32/X-I NS4/R

166d/04 166c/01

NSR4/W

166c/02

NS14/R

166c/15

NS14/W

166c/16

January 2009

197

PART 3: SECTION 7
SOUNDERS

Protec Fire Detection plc


Protec House, Churchill Way, Nelson, Lancashire BB9 6RT UK Tel: +44 (0)1282 717171 Fax: +44 (0)1282 717273 E-mail: sales@protec.co.uk Website: www.protec.co.uk
Certificate No: 201n to EN 54-3: 2001 Certificated Products 6000/SSR2 Analogue addressable Type A/B sounder - red (Shallow and N29-982-75 base) Notes: 1) The device is supplied with a shallow base. 2) Meets the requirements of EN 54-3: 2001 with the following tones: 1 - Continuous tone - 990 Hz 2 - Warble tone - 990 / 695 Hz Analogue addressable Type A/B sounder - white (Shallow and N29-982-75 base) Notes: 1) This device is supplied with a shallow base. 2) Meets the requirements of EN 54-3: 2001 with the following tones: 1 - Continuous tone - 990 Hz 2 - Warble tone - 990 / 695 Hz Analogue addressable Type A/B sounder - red (Shallow and N29-982-75 base) Notes: 1) This device is supplied with a shallow base. 2) Meets the requirements of EN 54-3: 2001 with the following tones: 1 - Continuous tone - 990 Hz 2 - Warble tone - 990 / 695 Hz 3 - Dutch whoop - 500 / 1500 Hz Analogue addressable Type A/B sounder - white (Shallow and N29-982-75 base) Notes: 1) This device is supplied with a shallow base. 2) Meets the requirements of EN 54-3: 2001 with the following tones: 1 - Continuous tone - 990 Hz 2 - Warble tone - 990 / 695 Hz 3 - Dutch whoop - 500 / 1500 Hz LPCB Ref. No. 201n/01

6000/SSW2

201n/02

6000/SSR2/NL

201n/03

6000/SSW2/NL

201n/04

Bases: N29-982-75 Deep base Shallow base

Shield Fire Safety & Security Ltd


29th Floor, Regus Suite, One Canada Square, Canary Wharf, London E14 5DY UK Tel: +44 (0)207 712 1722 Fax: +44 (0)870 734 5579 E-mail: info@shielduk.com Website: www.shielduk.com
Certificate No: 548e to EN 54-3: 2001 Certificated Products S-A491 Intelligent sounder strobe Notes: Meets the requirements of EN 54-3: 2001at the following tones: Mode I (for pre alarm): 0.61Hz (430ms on / 1200ms off) Mode II (for fire alarm): 1.30Hz (430ms on / 340ms off) Conventional sounder strobe Notes: Meets the requirements of EN 54-3: 2001at the following tones: Fixed tone: 1.35Hz (400ms on / 340ms off) LPCB Ref. No. 548e/02

S-C481

548e/01

198

January 2009

SECTION 7: PART

SOUNDERS

System Sensor Europe


15-19 Trescott Road, Trafford Park, Smallwood, Redditch, Worcestershire B98 7AH UK Tel: +44 (0)1527 406700 Fax: +44 (0)1527 406699 Website: www.systemsensoreurope.com
Certificate No: 166c to EN 54-3: 2001 Certificate No: 166d to EN 54-3: 2001 and CEA GEI 1-052 Draft 2.0: 11.06.97 Certificated Products WMSST-XX-P01 Intelligent wall mounted sounder strobe Notes: 1) xx indicates body colour. R=Red, W=Bright White 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirements of EN54-3 for all tones and output levels at voltage range 1532v. Intelligent wall mounted sounder Note: 1) xx indicates body colour. RR=Red, WW=Bright White Meets the requirements of EN54-3 for all tones and output levels at voltage range 1532v. Intelligent integrated detector base sounder strobe Notes: 1) xx indicates body colour. R=Red, W=Bright White, D=Detector White, K=Black 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. Intelligent integrated detector base sounder Note: 1) xx indicates body colour. RR=Red, WW=Bright White, DD=Detector White, KK=Black Intelligent non-integrated detector base sounder strobe Notes: 1) xx indicates body colour. R=Red, W=Bright White 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Intelligent non-integrated detector base sounder Note: 1) xx indicates body colour. RR=Red, WW=Bright White Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. Intelligent wall mounted sounder strobe with short circuit isolator Notes: 1) xx indicates body colour. R=Red, W=Bright White 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirements of EN54-3 for all tones and output levels at voltage range 1532v. Intelligent wall mounted sounder with short circuit isolator Note: 1) xx indicates body colour. RR=Red, WW=Bright White. Meets the requirements of EN54-3 for all tones and output levels at voltage range 1532v. Intelligent integrated detector base sounder strobe with short circuit isolator Notes: 1) xx indicates body colour. R=Red, W=Bright White, D=Detector White, K=Black 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirements of EN-54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20, which are approved at maximum volume only. Intelligent integrated detector base sounder with short circuit isolator Note: 1) xx indicates body colour. RR=Red, WW=Bright White, DD=Detector White, KK=Black Meets the requirements of EN-54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20, which are approved at maximum volume only. Intelligent non-integrated detector base sounder strobe with short circuit isolator Notes: 1) xx indicates body colour. R=Red, W=Bright White 2) xx indicates lens colour. R=Red, A=Amber, G=Green, B=Blue, C=Clear Meets the requirements of EN-54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20, which are approved at maximum volume only. Intelligent non-integrated detector base sounder with short circuit isolator Note: LPCB Ref. No. 166c/09

WMSOU-XX-P01

166c/10

IBSST-XX-P01

166c/11

IBSOU-XX-P01 DBSST-XX-P01-C

166c/12 166c/13

DBSOU-XX-P01-C

166c/14

WMSST-XX-P02

166d/01

WMSOU-XX-P02

166d/02

IBSST-XX-P02

166d/03

IBSOU-XX-P02

166d/04

DBSST-XX-P02-C

166d/05

DBSOU-XX-P02-C

166d/06

January 2009

199

PART 3: SECTION 7
SOUNDERS
Certificated Products 1) xx indicates body colour. RR=Red, WW=Bright White Meets the requirements of EN-54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20, which are approved at maximum volume only. Intelligent wall mounted sounder strobe Note: 1) Meets the requirements of EN54-3 for all tones and output levels at voltage range 15-28v. Intelligent integrated detector base sounder strobe. Notes: 1) Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20, which are approved at maximum volume only. Intelligent wall mounted sounder strobe Meets the requirements of EN54-3 for all tones and output levels at voltage range 1532v. Intelligent integrated detector base sounder strobe. Meets the requirements of EN54-3 for all tones at voltage range 15-32v with the exception of Tones 4, 10, 11, 17 and 20 which are approved at maximum volume only. LPCB Ref. No.

WMSST-RP-P30

166d/07

IBSST-DR-P30

166d/08

WMSST-RR-P29 IBSST-DR-P29

166c/35 166c/36

Thorn Security Limited, trading as Tyco Safety Products


Dunhams Lane, Letchworth SG6 1BE UK Tel: +44 (0)1462 667700 Fax: +44 (0)1462 667777 E-mail: mashbury@tycoint.com Website: www.tycosafetyproducts-europe.com
Certificate No: 681g to EN 54-3: 2001 Certificate No: 378e to EN 54-3: 2001 & EN 54-17: 2005 Certificated Products 802SB Analogue addressable type A sounder base Notes: 1) Meets the requirements of EN 54-3 at the following tones: Fast Sweep Dutch Slow Whoop 500Hz to 1200Hz Temporal 3 880Hz Conventional type A sounder base Notes: 1) Meets the requirements of EN 54-3 at the following tones: Temporal 3 880Hz Dutch Slow Whoop 500Hz to 1200Hz Continuous 880Hz Conventional type A diode sounder base Notes: 1) Meets the requirements of EN 54-3 at the following tones: Temporal 3 880Hz Dutch Slow Whoop 500Hz to 1200Hz Continuous 880Hz Conventional type A sounder base Notes: 1) Meets the requirements of EN 54-3 at the following tones: Temporal 3 880Hz Dutch Slow Whoop 500Hz to 1200Hz Continuous 880Hz Conventional type A sounder base Notes: 1) Meets the requirements of EN 54-3 at the following tones: Temporal 3 880Hz Dutch Slow Whoop 500Hz to 1200Hz Continuous 880Hz Analogue addressable type A sounder base Notes: 1) Meets the requirements of EN 54-3 at the following tones: Temporal 3 880Hz Dutch Slow Whoop 500Hz to 1200Hz Continuous 880Hz Analogue addressable type A sounder base LPCB Ref. No. 681g/01

601SB

681g/02

601SBD

681g/03

602SB

681g/04

602SBD

681g/05

901SB

681g/06

912SB

681g/07

200

January 2009

SECTION 7: PART
Certificated Products Notes: 1) Meets the requirements of EN 54-3 at the following tones: Temporal 3 880Hz Dutch Slow Whoop 500Hz to 1200Hz Continuous 880Hz Analogue addressable type A sounder base Notes: 1) Meets the requirements of EN 54-3 at the following tones: Temporal 3 880Hz Dutch Slow Whoop 500Hz to 1200Hz Continuous 880Hz Symphoni MX addressable loop powered Type A sounder (red) with short circuit isolator Notes: 1) Meets the requirements of EN 54-3 at tones 1, 2, 6, 9. Symphoni MX addressable loop powered Type A sounder (white) with short circuit isolator Notes: 1) Meets the requirements of EN 54-3 at tones 1, 2, 6, 9. Symphoni MX addressable loop powered Type B sounder (red) with short circuit isolator Notes: 1) Meets the requirements of EN 54-3 at tones 1, 2, 6, 9. Symphoni MX addressable loop powered Type A sounder beacon (red) with short circuit isolator Notes: 1) Meets the requirements of EN 54-3 at tones 1, 2, 6, 9. Symphoni MX addressable loop powered Type A sounder beacon (white) with short circuit isolator Notes: 1) Meets the requirements of EN 54-3 at tones 1, 2, 6, 9. Symphoni MX addressable loop powered Type B sounder beacon (red) with short circuit isolator Notes: 1) Meets the requirements of EN 54-3 at tones 1, 2, 6, 9. LPCB Ref. No.

SOUNDERS

812SB

681g/08

LPSY800-R LPSY800-W

378e/01 378e/02

LPSY865 LPAV800-R

378e/03 378e/04

LPAV800-W

378e/05

LPAV865

378e/06

Vimpex Limited
Star Lane, Great Wakering, Essex SS3 0PJ UK Tel: +44 (0) 1702 216999 Fax: +44 (0) 1702 216699 E-mail: sales@vimpex.co.uk Website: www.vimpex.co.uk
Certificate No: 692a to EN 54-3: 2001 Certificated Products MBF-6EV-24 MBF-8EV MBA-6 + BBX.4 MBA-8 + BBX.4 6" (150mm) 24Vdc fire alarm bell with aluminium gong 8" (200mm) 24Vdc fire alarm bell with aluminium gong 6" (150mm) fire alarm bell with aluminium gong complete with back box 8" (200mm) fire alarm bell with aluminium gong complete with back box LPCB Ref. No. 692a/01 692a/02 692a/04 692a/05

January 2009

201

PART 3: SECTION 8
FIRE RESISTANT CABLES This section lists fire resistant cables for use in fire safety, fire detection and fire alarm systems and other applications where specifications require cables with specific performance in the event of a fire. BS 5839-1:2002 Fire detection and fire alarm systems for buildings. Code of practice for system design, installation, commissioning and maintenance BS 5839-1:2002 includes new requirements for fire resistant cables for fire detection and alarm systems. It calls for Standard and Enhanced fire resistant cables and defines the requirements for these in Clause 26.2. These cables have to comply with BS EN 60702-1 (with a polymeric sheath), BS 7629 or BS 7846, and: - Standard fire resisting cables also have to: a) achieve Class PH30 when tested in accordance with EN 50200:2000. and b) maintain circuit integrity when exposed to a special flame / mechanical shock / water spray sequence equivalent to achieving a duration of 30 minutes when tested in accordance with BS 8434-1:2003. - Enhanced fire resisting cables also have to: a) achieve a 120 minute survival when tested in accordance with EN 50200:2000. and b) maintain circuit integrity when exposed to a special flame / mechanical shock / water spray sequence equivalent to achieving a duration of 120 minutes when tested in accordance with BS 8434-2:2003. Cables complying with these requirements are listed as Standard or Enhanced under BS 5839-1, Clause 26.2. Building Regulations 2000 - Fire Safety - Approved Document B The Building Regulations 2000 - Fire Safety - Approved Document B - Volume 2 - Buildings other than dwelling houses (Amended 2007) defines protected power circuit to be able to continue to function during a fire. A protected circuit for operation of equipment in the event of fire should consist of a cable meeting at least the requirements of PH30 when tested in accordance with EN 50200. Larger or complex buildings may require fire protection systems to operate for extended periods during fire and guidance on such systems is given in BS 5839-1, BS 5266-1 and BS 7346-6. Other Standards Used The other standards and test methods currently used for certification are listed below. This list includes some "withdrawn" standards. Where possible, these will be replaced by the superseding standards when certificates are renewed. However, where withdrawn standards are called up by current standards, certification to the withdrawn standard may need to be maintained until the calling standard is amended to remove the reference: - BS 6207-1:1995 Mineral insulated cables with rated voltage not exceeding 750V - BS 6387:1994 Performance requirements for cables required to maintain circuit integrity under fire conditions - BS 6425-1:1990 Gases evolved during combustion of electric cables. Part 1: Method for determination of amount of halogen acid gas evolved during combustion of polymeric materials taken from cables - BS 7346-6:2005 Components for smoke and heat control systems - Part 6: Specification for cable systems - BS 7622-2:1993 Measurement of smoke density of electric cables burning under defined conditions - BS 7629-1:1997 Thermosetting insulated cables with limited circuit integrity when affected by fire. Part 1: Multicore cables.(This version of the standard will remain current until 31st March 2006) - BS 7629-1:1997 (Incorporating Amendment Nos.1 and 2) - Thermosetting insulated cables with limited circuit integrity when affected by fire. Part 1: Multicore cables.(The provisions introduced by amendment No.1: 2004 are effective from 1st April 2004) - BS 7629-2:1997 Thermosetting insulated cables with limited circuit integrity when affected by fire. Part 2: Multipair cables - BS 7846:2000 Electric cables 600/1000V armoured fire-resistant cables having thermosetting insulation and low emission of smoke and corrosive gases when affected by fire. (This version of the standard will remain current until 31st March 2006) - BS 7846:2000 (Incorporating Amendment No.1) - Electric cables 600/1000V armoured fire-resistant cables having thermosetting insulation and low emission of smoke and corrosive gases when affected by fire. (The provisions introduced by amendment No.1: 2004 are affective from 1st April 2004)

202

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES - BS 8434-1:2003 Method of test for assessment of the fire integrity of electric cables - Part 1: test for unprotected small cables for use in emergency circuits - BS EN 50200 with addition of water spray - BS 8434-2:2003 Method of test for assessment of the fire integrity of electric cables - Part 2: test for unprotected small cables for use in emergency circuits- BS EN 50200 with a 930C flame and with water spray - BS 8491:2008 Method for assessment of fire integrity of large diameter power cables for use as components for smoke and heat control systems and other certain active fire safety systems - EN 50200:2000 Method of test for resistance to fire of unprotected small cables for use in emergency circuits - EN 50200:2006 Method of test for resistance to fire of unprotected small cables for use in emergency circuits - EN 50266:2001 Common test methods for cables under fire conditions - Test for vertical flame spread of vertically mounted bunched wires or cables - EN 50267-2-1:1999 Common test method for cables under fire conditions- tests on gases evolved during combustion of materials from cables - procedures - Determination of the amount of halogen acid gas -EN 50267-2-3:1999 Common test methods for cables under fire conditions - Tests on gases evolved during combustion of materials from cables - Procedure 2-3: Procedures - Determination of degree of acidity of gases for cables by determination of the weighted average of pH and conductivity - EN 50268-2:2000 Common test methods for cables under fire conditions. Measurement of smoke density of cables burning under defined conditions - EN 60702-1:2002 Mineral insulated cables and their terminations with rated voltage not exceeding 750V - EN 61034-2:2005 Measurement of smoke density of cables burning under defined conditions - IEC 331:1970 Fire resisting characteristics of electric cables - IEC 60754-1:1994 Tests on gases evolved during combustion of materials from cables - Part 1: Determination of the amount of halogen acid gas - IEC 60754-2:1991 Tests on gases evolved during combustion of electric cables - Part 2: Determination of degree of acidity of gases evolved during the combustion of materials taken from electric cables by measuring pH and conductivity - IEC 60331-21:1999 Tests for electric cables under fire conditions - Circuit integrity - Part 21 Procedure and requirements - Cables of rated voltage up to and including 0,6/1,0kV

2M KABLO A.S.
Evren Oto Sanayi Sitesi, 1 Kisim, 1585 Sk No.1, Esenyurt, Istanbul, Turkey Tel: +90 212 672 7314 Fax: +90 212 672 7312 E-mail: sales@2mkab.com Website: www.2mkab.com
Certificate No: 711a to BS EN 50200: 2006 Class PH120

FireKab BMK-SH FE 180


Nominal csa of 2 conductors (mm ) 1.0 1.5 2.5 Uo/U 300/500 V Note: 1) Solid conductor only. Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3, 4, 5 & 7 2, 3 & 4 BS 6387 C, W, Z C, W, Z C, W, Z BS EN 50200 Class PH120 Class PH120 Class PH120 LPCB Ref. No. 711a/01

Certificate No: 711b to BS EN 50200: 2006 Class PH120

FireKab JE-H(ST)H...BD FE 180 E30-E90


Nominal csa of conductors (mm) (1, 2) 0.50 (1) 1.50 Uo/U 300/500V Core Construction (excluding earth wire) 1, 2, 4, 8, & 12 pairs 1 & 2 pairs BS EN 50200 Class PH120 Class PH120 LPCB Ref. No. 711b/01

January 2009

203

PART 3: SECTION 8
FIRE RESISTANT CABLES
Notes: 1) Solid conductor only. 2) External diameter of this conductor is 0.80mm.

AC Electrical Wholesalers Ltd


Cobham Road, Ferndowne Industrial Estate, Wimborne, Dorset BH21 7SJ UK Tel: +44 (0)1202 851800 Fax: +44 (0)1202 851818 Website: www.ac-electrical.com
Certificate No: 682a to BS 7629-1:1997 (Incorporating Amendment No.1), BS EN 50200:2000 Class PH30, BS 8434-1:2003 30min and BS 5839-1:2002 Clause 26.2d

NoBurn Platinum
Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5 4.0 Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2 BS 7629-1 (Incorporating Amendments No.1 & 2) Complies Complies Complies Complies
(3)

BS EN 50200

BS 84341
(4)

BS 5839-1 Clause 26.2 Standard Standard


(5)

LPCB Ref. No.

(3)

(3)

(3)

Class PH120 Class PH120 Class PH120 Class PH120

30min 30min

682a/01

(4)

(5)

30min

(4)

Standard

(5)

30min

(4)

Standard

(5)

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), the NoBurn Platinum cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-21:1999. 4) The duration of 30min when tested in accordance with BS 8434-1:2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 5) The NoBurn Platinum cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), met Class PH120 when tested in accordance with BS EN 50200:2006 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.

AEI Cables Limited


Birtley, Chester-le-Street, Co. Durham DH3 2RA UK Tel: +44 (0)191 410 3111 Fax: +44 (0)191 410 8312 E-mail: sales@aeicables.co.uk Website: www.aeicables.co.uk
Certificate No: 221b to BS 6387:1994, BS EN 50267-2-1:1999 and BS EN 50268-2:2000

Firetec Power LSZH Cable


Nominal csa 2 of conductor (mm ) 1.0 1.5 2.5 4.0 6.0 10.0 16 Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 (see note 1) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl BS EN 50268-2 >60% >60% >60% >60% >60% >60% >60% LPCB Ref. No. 221b/02

204

January 2009

SECTION 8: PART
Uo/U 450/750V Note: 1) The Firetec Power LSZH cable also met Category C, W, Z when tested for voltage rating 600/1000V which is not recognised by BS 6387.

FIRE RESISTANT CABLES

Certificate No: 221c to BS 6387:1994, BS EN 50267-2-1:1999 and IEC 60331-21:1999

Firetec Single Core LSZH Cable


Nominal csa 2 of conductor (mm ) 1.0 1.5 2.5 4.0 6.0 10.0 16 25 35 50 70 95 120 185 240 300 400 630 800 1000 Uo/U 450/750 Notes: 1) The Firetec single core LSZH also met IEC 60331 when installed in steel conduit. 2) These cables also met category C,W,Z when tested for voltage rating 600/1000V which is not recognised by BS 6387. 3) Clause 8 (bending) and 9.1 & 9.2 (impact) can not be conducted due to the cable having only one core. 4) To satisfy the requirement of BS 6387, testing for C, W and Z categories was conducted using 20mm steel conduit as the other metallic element. 5) To satisfy the requirement of BS 6387, testing for category C was conducted using 38mm steel conduit as the other metallic element. 2 6) Where single cable is fitted in conduit, only phase to earth voltage was applied with the exception of 1.0mm sample where three cables were tested inside the conduit to allow the possibility of core to core breakdown. 7) For cable with an outside diameter in excess of 20mm, the category Z tests were conducted in accordance with guidance from the manufacturer. 8) Only clause 10 of BS 6387 was conducted. 9) These cables met the requirements of IEC 60331 when tested at a temperature of 950C (which is not recognised by IEC 60331) and at a voltage rating of 600/1000V. Core Construction One One One One One One One One One One One One One One One One One One One One BS 6387 (see notes 2-8) (4) C, W, Z (4) C, W, Z (4) C, W, Z (4) C, W, Z (4) C, W, Z (4) C, W, Z (4) C, W, Z (4) C, W, Z (4) C, W, Z (5) C (5) C (5) C (5) C (5) C (5) C BS EN 50267-1-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl IEC 60331-21 (see notes 1 & 9) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 221c/01

Certificate No: 221a to BS 7629-1: 1997 This certificate is to a withdrawn version of the BS 7629-1: 1997. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU).

Firetec Multicore LSZH Cable


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 UoU/ 300/500V Notes: 1) In meeting the requirements of BS 7629-1:1997, the Firetec Multicore LSZH cables listed met the requirements of smoke density of BS 7622-2:1993, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCI on the (outer covering) when tested in accordance with BS 6425-1:1990. Core Construction (excluding drain wire & earth) 2, 3, 4, 7, 12 & 19 2, 3, 4, 7, 12 & 19 2, 3, 4, 7 & 12 2, 3, 4, & 7 BS 7629-1 (see note 2) (1) Complies (1) Complies (1) Complies (1) Complies LPCB Ref. No. 221a/01

January 2009

205

PART 3: SECTION 8
FIRE RESISTANT CABLES
2) BS 7629-1: 1997 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators.

Certificate No: 221d to BS 7629-1:1997 (Incorporating Amendment No. 1)

Firetec Multicore LSZH


Nominal csa of 2 conductor (mm ) 1.0 Uo/U 300/500V Notes: 1) Solid construction only. 2) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendment No. 1), the Firetec Multicore LSZH cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCI on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1:1999. Core Construction 2, 3 & 4 BS 7629-1 (Incorporating Amendment No. 1) (2) Complies LPCB Ref. No. 221d/01

Certificate No: 221e to BS 7629-1:1997 (Incorporating Amendment No.1), BS EN 50200:2000 Class PH30, BS 8434-1:2003 & BS 5839-1:2002 Clause 26.2d

Firetec Multicore LSZH


Nominal csa of conductor 2 (mm ) 1.5 2.5 4.0 Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only 3) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendment No. 1), the Firetec Multicore LSZH cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCI on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1:1999. 4) The duration of 30min when tested in accordance with BS 8434-1:2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 5) The Firetec Multicore LSZH cables listed conform to BS 7629-1:1997 (Incorporating Amendment No. 1), met class PH30 when tested in accordance with BS EN 50200:2000 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002. Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendment No. 1) (3) Complies (3) Complies (3) Complies BS EN 50200 Class PH30 Class PH30 Class PH30 BS 84341 30min (4) 30min (4) 30min
(4)

BS 5839-1 Clause 26.2 (5) Standard (5) Standard (5) Standard

LPCB Ref. No. 221e/01

Certificate No: 221f to BS 7629-1:1997 (Inc Amdmnt No.1), BS 5839-1:2002 Clause 26.2e, BS EN 50200:2000 Class PH120 BS 8434-2:2003 120min

Firetec Enhanced Multicore LSZH


Nominal csa of conductor 2 (mm ) 1.0 1.5
(1)

Core Construction (excluding drain wire & earth) 2,3 & 4 2,3 & 4 2,3 & 4

BS 7629-1 (Incorporating Amendment No 1) (3) Complies Complies Complies


(3)

BS EN 50200 Class PH120 Class PH120 Class PH120

BS 84342 120min 120min 120min


(4)

BS 5839-1 Clause 26.2 Enhanced Enhanced Enhanced


(5)

LPCB Ref. No. 221f/01

(1)

(4)

(5)

2.5

(1)

(3)

(4)

(5)

206

January 2009

SECTION 8: PART
Nominal csa of conductor 2 (mm ) 4.0
(2)

FIRE RESISTANT CABLES


Core Construction (excluding drain wire & earth) 2,3 & 4 BS 7629-1 (Incorporating Amendment No 1) (3) Complies BS EN 50200 Class PH120 BS 84342 120min
(4)

BS 5839-1 Clause 26.2 Enhanced


(5)

LPCB Ref. No.

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendment No.1), the FIRETEC ENHANCED Multicore LSZH cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 4) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1: 2002. 5) The FIRETEC ENHANCED Multicore LSZH cables listed conform to BS 7629-1: 1997 (Incorporating Amendment No.1), met Class PH120 when tested in accordance with EN 50200: 2000 and met a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 221g to BS 7846: 2000 This certificate is to a withdrawn version of the BS 7846: 2000. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU).

Firetec Armoured LSZH Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo/U 600/1000 V Notes: 1) In meeting the requirements of BS 7846: 2000, the Firetec Armoured LSZH cables listed met the requirements of BS 6387: 1994 Clause 11.1 Category C, W & Z. 2) BS 7846: 2000 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 221j covers cables certified in accordance with BS 7846: 2000 (Incorporating Amendments Nos. 1 & 2) Core Construction (excluding drain wire & earth) 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 2,3, & 4 BS 7846 (see note 2) (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 LPCB Ref. No. 221g/01

Certificate No: 221h to BS 6387: 1994 and BS EN 60702-1: 2002

Mineral Insulated Cable (light duty)


Nominal csa of 2 conductor (mm ) 1.0 1.5 Core Construction 2, 3, 4 & 7 2, 3, 4 & 7 BS 6387 C, W, Z C, W, Z BS EN 60702-1 Complies Complies LPCB Ref. No. 221h/01

January 2009

207

PART 3: SECTION 8
FIRE RESISTANT CABLES
Nominal csa of 2 conductor (mm ) 2.5 4.0 Uo/U 300/500 V Note: 1) The above range is certified in both bare and covered constructions. Core Construction 2, 3, 4 & 7 2 BS 6387 C, W, Z C, W, Z BS EN 60702-1 Complies Complies LPCB Ref. No.

Certificate No: 221h to BS 6387: 1994 and BS EN 60702-1: 2002

Mineral Insulated Cable (single core)


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo/U 450/750V Core Construction One One One One One One One One One One One One One One One One One BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 221h/02

Notes: 1) The above range is certified in both bare and covered constructions. 2) For cables with an outside diameter in excess of 20mm, the category Z tests were conducted in accordance with guidance from the manufacturer.

Certificate No: 221h to BS 6387: 1994 and BS EN 60702-1: 2002

Mineral Insulated Cable (heavy duty)


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 Uo/U 450/750V Core Construction 2, 3, 4, 7, 12 & 19 2, 3, 4, 7 & 12 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 221h/03

Notes: 1) The above range is certified in both bare and covered constructions 2) For cables with an outside diameter in excess of 20mm, the category Z tests were conducted in accordance with guidance from the manufacturer.

Certificate No: 221j to BS 7846: 2000 (Incorporating Amendments Nos 1 & 2)

208

January 2009

SECTION 8: PART
Firetec Armoured LSZH
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo/U 600/1000 V Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 BS 7846 (Incorporating Amendments Nos. 1 & 2) (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 LPCB Ref. No. 221j/01

FIRE RESISTANT CABLES

Note: 1) In meeting the requirements of BS 7846: 2000 (Incorporating Amendments Nos 1 & 2), the Firetec Armoured LSZH cables listed met the requirements of BS 6387: 1994 Clause 11.1 Category C, W & Z.

Certificate No: 221k to BS 7846: 2000 (Incorporating Amendments Nos 1 & 2)

Firetec Armoured
Nominal csa of 2 conductor (mm ) 1.5 4.0 6.0 6.0 10 16 Uo/U 600/1000 V Note: 1) In meeting the requirements of BS 7846: 2000 (Incorporating Amendments Nos. 1 & 2), the Firetec Armoured Cables listed met the requirements of BS 6387: 1994 Clause 11.1 Category C, W & Z. Core Construction 2, 3, 4, 5, 7, 12, 19, 27, 37 & 48 2, 3, 4, 5, 7, 12, 19, 27, 37 & 48 2, 3, 4, 5, 7, 12, 19, 27, 37 & 48 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 BS 7846 (Incorporating Amendments Nos. 1 & 2) (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 LPCB Ref. No. 221k/01

Certificate No: 221m to BS 7846: 2000 N.B. This certificate is to a withdrawn version of the above standard. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU). This certificate, to the withdrawn version of the standard, is maintained because cables meeting the withdrawn version of the standard are still requested by some regulators outside of the EU. (See appendix for further details).

Firetec Armoured
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 Uo/U 600/1000 V Note: 1) In meeting the requirements of BS 7846: 2000, the Firetec Armoured Cables listed met the requirements of BS 6387: 1994 Clause 11.1 Category C, W & Z. Core Construction 2, 3, 4, 5, 7, 12, 19, 27, 37 & 48 2, 3, 4, 5, 7, 12, 19, 27, 37 & 48 2, 3, 4, 5, 7, 12, 19, 27, 37 & 48 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 BS 7846 (see notes 1 & 2) F2 F2 F2 F2 F2 F2 LPCB Ref. No. 221m/01

January 2009

209

PART 3: SECTION 8
FIRE RESISTANT CABLES
2) BS 7846: 2000 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 221k covers cables certified in accordance with BS 7846: 2000 (Incorporating Amendments Nos. 1 & 2).

Alpha Fire Services W.L.L.


P O Box 11741, Manama, Kingdom of Bahrain Tel: +973 1773 8100 Fax: +973 1773 6161 E-mail: info@alphafireservices.com Website: www.alphafireservices.com
Certificate No: 568a to BS 6387: 1994 and BS EN 50267-2-1: 1999

ALPHAFIRE FPC4
Nominal csa of 2 conductors (mm ) 1.0 1.5 2.5 4.0 Uo/U 300/500 V Notes: 1) Solid and stranded conductors. 2) Stranded conductor only. Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl LPCB Ref. No. 568a/01

Bangkok Cable Co Limited


93 Moo. 11 Suksawad Road, Naiklongbangplakod, Prasamutchedee, Samutprakarn, 10290, Thailand Tel: +662 2544550 Fax: +662 2543859

Certificate No: 576a to BS 6387: 1994

450/750V Low Smoke Halogen Free Fire Resistant Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 Core Construction (see note 1) (3) One (3) One (3) One (3) One (2,3) One (2,3) One (2,3) One (2,3) One (2,3) One (2,3) One (2,3) One (2,3) One One One One One One One One BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl BS EN 50268-2 >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% LPCB Ref. No. 576a/01

210

January 2009

SECTION 8: PART
Uo/U = 450/750V Notes: 1) Clause 8 (Bending) and 9.1 & 9.2 (Impact) can not be conducted due to the cable having only one core. 2) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. 3) To satisfy the requirement of BS 6387, testing for C, W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element.

FIRE RESISTANT CABLES

600/1000V XLPE/Armoured/Low Smoke Halogen Free Fire Resistant Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo/U = 450/750V Note: 1) The above named cable also met category C, W, Z when tested for voltage rating 600/1000V which is not recognised by BS 6387 Core Construction (see note 1) One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One, 2, 3 & 4 One & 2 One BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl BS EN 50268-2 >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% LPCB Ref. No. 576a/02

Cableplus (Suzhou) Technologies Co Ltd


No.7, Nanxin Road, Changkun Industrial Park, Shajiabang, Changshu, Jiangsu 215542, Peoples Republic of China Tel: +86 512 5257 8665 Fax: +86 512 5257 1665 E-mail: info@cableplus-sz.com Website: www.cableplus-sz.com
Certificate No: 827a to BS 6387: 1994 and BS EN 50267-2-1: 1999

Firepro
Nominal csa of conductor (mm) 1.5 (1) 10 (1) 16 (1) 2.5 (1) 4.0 (1) 6.0 Uo/U 450/750V Notes: 1) Stranded conductor only. 2) Clause 8 (Bending) and 9.1 & 9.2 (Impact) can not be conducted due to the cable having only one core. 3) To satisfy the requirement of BS 6387, testing for C, W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element. 4) To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element.
(1)

Core Construction One (4, 5) One (4, 5) One (3) One (3) One (3) One
(3)

BS 6387 (see note 2 & 6) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z

BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl

LPCB Ref. No. 827a/01

January 2009

211

PART 3: SECTION 8
FIRE RESISTANT CABLES
5) To satisfy the requirement of BS 6387, testing for W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element. 6) Where a single cable is fitted in a conduit, only phase to earth voltage was applied.

Cavicel SpA
Via Caduti del Lavoro, 18/A 20096 Pioltello, Milan, Italy Tel: +39 02 9216 0521 Fax: +39 02 9216 0753 E-mail: cavicel@cavicel.com Website: www.cavicel.com
Certificate No: 217d to BS 6387:1994 & BS 6425-1: 1990

Firecel SR112 Fire Resistant Cable


Nominal csa of conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 Uo/U 450/750 V Notes: 1) Clause 8 (Bending) and 9.1 & 9.2 (Impact) can not be conducted due to the cable having only one core. 2) To satisfy the requirement of BS 6387, testing for C, W, and Z categories was conducted using a 20mm steel conduit as the other metallic element. 3) For large size cables , the category C testing was conducted using a 38mm steel conduit. 4) Where a single cable is fitted in a conduit, only phase to earth voltage was applied
2

Core Construction One One One One One One One

BS 6387 (see note 1,2,3 & 4) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z

BS 6425-1 (outer covering) <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI

LPCB Ref. No. 217d/01

Certificate No: 217f to BS 7629-1:1997 (Incorporating Amendment No.1), BS EN 50200: 2000 Class PH30 & BS 5839-1: 2002 Clause 26.2

Firecel SR/114 H Fire Resistant Cable


Nominal csa of 2 conductors (mm ) Core Construction (excluding drain wire and earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendment No. 1) Complies (1) Complies (1) Complies (1) Complies
(1)

BS EN 50200

BS 5839-1 Clause 26.2


(2)

LPCB Ref. No.

1.0 1.5 2.5 4.0 Uo/U 300/500V

Class PH30 Class PH30 Class PH30 Class PH30

Standard (2) Standard (2) Standard (2) Standard

217f/01

Notes: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendment No.1), the Firecel SR/114 H cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (binder + insulation + sheath) when tested in accordance with BS EN 50267-2-1: 1999. 2) The Firecel SR/114 H cables listed conform to BS 7629-1: 1997 (Incorporating Amendment No.1), met Class PH30 when tested in accordance with BS EN 50200: 2000 and met the requirements of the additional fire, mechanical shock and water test described in Clause 26.2 d) of BS 5839-1: 2002, and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 217g to BS 7629-1:1997 (Incorporating Amendment No.1), BS EN 50200:2000 Class PH120, BS 8434-2:2003 120min & BS 5839-1:2002 Clause 26.2e

212

January 2009

SECTION 8: PART
Firecel SR 114 E
Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendment No.1), the Firecel SR 114 E cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1: 1999. 2) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2e) of BS 5839-1: 2002. 3) The Firecel SR 114 E cables listed conform to BS 7629-1: 1997 (Incorporating Amendment No.1), met Class PH120 when tested in accordance with BS EN 50200: 2000 and met the 120min duration when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002. Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 BS 7629-1 (Incorporating Amendment No 1) (1) Complies (1) Complies (1) Complies (1) Complies BS EN 50200 BS 8434-2
(2)

FIRE RESISTANT CABLES

BS 5839-1 Clause 26.2 Enhanced (3) Enhanced (3) Enhanced (3) Enhanced
(3)

LPCB Ref. No.

Class PH120 Class PH120 Class PH120 Class PH120

120min (2) 120min (2) 120min (2) 120min

217g/01

Cet Eletric s.r.l.


Via C. Battisti nr 34, Limena (PD), Italy Tel: 0039 049 8849764 Fax: 0039 049 8849728 E-mail: giorgio.pinton@ceteletric.com Website: www.ceteletric.com Head Office Via L. Pierobon nr 32, 35010, Limena (PD), Italy Tel: 0039 049 8849764 Fax: 0039 049 8849728

Certificate No: 076a/01 to BS 7629-1:1997 (Inc. Amd. Nos. 1 and 2) and BS 6387:1994

Fire Cet
Nominal csa of conductor (mm) 1.0 (1) 1.5 (2) 2.5 (3) 4.0 Uo/U 300/500V Notes: 1) Solid conductor only 2) Solid & Stranded conductors 3) Stranded conductor only 4) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), the FIRE CET cables listed met the requirements of smoke density of BS EN 50268-2:2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1:1999.
(1)

Core construction drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (incorporating Amendments Nos. 1 and 2) (4) Complies (4) Complies (4) Complies (4) Complies

BS6387 C, W, Z C, W, Z C, W, Z C, W, Z

LPCB Ref. No. 706a/01

January 2009

213

PART 3: SECTION 8
FIRE RESISTANT CABLES

Context Plus Ltd


175 Mauldeth Road, Fallowfield, Manchester M14 6SG UK Tel: +44 (0)161 257 2541 Fax: +44 (0)161 225 8817 E-mail: xportsales@xportsales.com Website: www.xportsales.com
Certificate No: 682a to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), BS EN 50200:2006 Class PH120, BS 8434-1:2003 30min and BS 5839-1:2002 Clause 26.2

Context Plus
Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5 4.0 Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2 BS 7629-1 (Incorporating Amendments No.1 & 2) Complies Complies Complies Complies
(3)

BS EN 50200

BS 84341

BS 5839-1Clause 26.2

LPCB Ref. No.

(3)

(3)

(3)

Class PH120 Class PH120 Class PH120 Class PH120

30min 30min 30min 30min

(4)

Standard Standard Standard Standard

(5)

682a/01

(4)

(5)

(4)

(5)

(4)

(5)

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), the Context Plus cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-21:1999. 4) The duration of 30min when tested in accordance with BS 8434-1:2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 5) The Context Plus cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), met Class PH120 when tested in accordance with BS EN 50200:2006 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.

Dtwyler Cables
Unit of Dtwyler Switzerland Inc, Gotthardstrasse 31, CH-6460 Altdorf, Switzerland Tel: +41 41 875 1122 Fax: +41 41 875 1860 E-mail: info.ch@daetwyler-cables.com Website: www.daetwyler-cables.com
Certificate No: 172b to BS 7629-1:1997 (Incorporating Amendment No.1),BS 6387:1994, BS EN 50200:2000 Class PH30, BS 84341:2003 30min & BS 5839-1:2002 Clause 26.2d

Pyrofil Standard Fire Safety


Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5 Core Construction (excluding drainwire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendment No.1) Complies Complies Complies
(1)

BS 6387

BS EN 50200

BS 84341

BS 5839-1 Clause 26.2 Standard Standard


(3)

LPCB Ref. No.

(1)

(1)

C, W, Z C, W, Z C, W, Z

Class PH30 Class PH30 Class PH30

30min 30min

(2)

172b/01

(2)

(3)

30min

(2)

Standard

(3)

Uo/U 300/500V

214

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES


Notes: 1) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendment No. 1), the Pyrofil Fire Safety cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCI on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1:1999. 2) The duration of 30min when tested in accordance with BS 8434-1:2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 3) The Pyrofil Fire Safety cables listed conform to BS 7629-1:1997 (Incorporating Amendment No. 1), met class PH30 when tested in accordance with BS EN 50200:2000 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.

Doncaster Cables
Millfields Industrial Estate, Arksey Lane, Bentley, Doncaster, South Yorkshire DN5 0SJ UK Tel: +44 (0)1302 821700 Fax: +44 (0)1302 821701
Certificate No: 338a to BS 7629-1: 1997 (Inc. Amd. No.1), BS EN 50200:2000 Class PH30, BS 8434-1:2003 30min & BS 58391:2002 Clause 26.2d

Firesure
Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5 4.0 Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendment No.1) the Firesure cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements C, W, Z in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCI on the (outer covering, binding tape & insulation) when tested in accordance with BS EN 50267-2-1:1999. 2) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d of BS 5839-1:2002. 3) The Firesure cables listed conform to BS 7629-1: 1977 (Incorporating Amendment No 1) met Class PH30 when tested in accordance with BS EN 50200:2000 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirement for a standard fire resistant cable described in Clause 26.2 of BS 5839-1:2002. Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 BS 7629-1 (Incorporating Amendment No.1) (1) Complies (1) Complies (1) Complies (1) Complies BS EN 50200 Class PH30 Class PH30 Class PH30 Class PH30 BS 84341 30min (2) 30min (2) 30min (2) 30min
(2)

BS 5839-1 Clause 26.2 Standard (3) Standard (3) Standard (3) Standard
(3)

LPCB Ref. No. 338a/01

Certificate No: 338b to BS 7629-1: 1997 (Inc. Amd. Nos. 1 & 2), BS 6387: 1994, IEC 60331-21: 1999, IEC 60332-3-24: 2000, BS EN 50200: 2000 Class PH120, BS 8434-2: 2003 120min and BS 5839-1: 2002 Clause 26.2e

FIRESURE PLUS
Nominal csa of conductor 1.0 1.5 2.5 4.0 Core construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendments Nos. and 2) Complies Complies Complies Complies BS 6387 IEC 60331-21 IEC 60332-324 Complies Complies Complies Complies BS EN 50200 BS84342 BS 58391 LPCB Ref. No.

C,W,Z C,W,Z C,W,Z C,W,Z

Complies Complies Complies Complies

Class PH120 Class PH120 Class PH120 Class PH120

120min 120min 120min 120min

Enhanced Enhanced Enhanced Enhanced

338b/01

Uo/U 300/500V Note 1: Note 2: Solid conductor only Stranded conductor only

January 2009

215

PART 3: SECTION 8
FIRE RESISTANT CABLES
Note 3: Note 4: Note 5: Note 6: In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), the FIRESURE PLUS cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1:1999. These cables met the requirements of IEC 60331-21:1999 when tested at a temperature of 950C (which is not recognised by IEC 60331). The duration of 120min when tested in accordance with BS 8434-2:2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2e) of BS 5839-1:2002. The FIRESURE PLUS cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), met Class PH120 when tested in accordance with BS EN 50200:2000 and met a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2e of BS 5839-1:2002.

Dongguan Keystone Electric Wire & Cable Company Ltd


Ye Sha Management District, Shatin, Dongguan City, Guangdong, Peoples Republic of China Tel: +86 769 886 1814 Fax: +86 769 886 1696 E-mail: jessey@keystonecable.com
Certificate No: 663a to BS 7846: 2000 This certificate is to a withdrawn version of the BS 7846: 2000. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU).

KEYSTONE Fire Resistance Armoured Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 75 95 120 150 185 240 300 400 Uo/U 600/1000V Note: 1) In meeting the requirements of BS 7846: 2000, the KEYSTONE Fire Resistance Armoured cables listed met the requirements of BS 6387:1994 Clause 11.1 Category C, W & Z. 2) BS 7846: 2000 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 663c covers cables certified in accordance with BS 7846: 2000 (Incorporating Amendments Nos. 1 & 2) Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7846 F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2
(1)

LPCB Ref. No. 663a/01

Certificate No: 663b to BS 6387: 1994, BS EN 50267-2-1: 1999, BS EN 50268-2: 2000 and IEC 60331-21: 1999

KEYSTONE FR 7211 Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 Core Construction (see note 1) (3,4) One (4,5,6) One (4,5,6) One BS 6387 C,W,Z C,W,Z C,W,Z BS EN 50267-2-1 (Insulation & Binder tape) <0.5% HCI <0.5% HCI <0.5% HCI BS EN 50268-2 >60% >60% >60% IEC 60331-21 Complies Complies Complies LPCB Ref. No. 663b/01

216

January 2009

SECTION 8: PART
Nominal csa of 2 conductor (mm ) 6.0 10 16 25 35 50 70 95 120 150 185 240 300 Uo/U 450/750V Core Construction (see note 1) (4,5,6) One (4,5,6) One (4,5,6) One (4,5,6) One (4,5,6) One (2,6) One (2,6) One (2,6) One (2,6) One (2,6) One (2,6) One (2,6) One (2,6) One BS 6387 BS EN 50267-2-1 (Insulation & Binder tape) <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI BS EN 50268-2 IEC 60331-21 LPCB Ref. No.

FIRE RESISTANT CABLES

C,W,Z C,W,Z C,W,Z C,W,Z C,W,Z C C C C C C C C

>60% >60% >60% >60% >60% -

Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies

Notes: 1) Clauses 8 (Bending) and 9.1 & 9.2 (Impact) cannot be conducted due to the cable having only one core. 2) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. 3) To satisfy the requirement of BS 6387, testing for C & W categories was conducted using a 20mm steel conduit as the other metallic element. 4) To satisfy the requirement of BS 6387, testing for Z category was conducted using a 20mm steel conduit as the other metallic element. 5) To satisfy the requirement of BS 6387, testing for W category was conducted using a 38mm steel conduit as the other metallic element. 6) To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm steel conduit as the other metallic element.

Certificate No: 663c to BS 7846: 2000 (Incorporating Amendments Nos. 1 & 2)

KEYSTONE Fire Resistance Armoured Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 BS 7846 (Incorporating Amendments Nos. 1 & 2) (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 (1) F2 LPCB Ref. No. 663c/01

Uo/U 600/1000 V Note: 1) In meeting the requirements of BS 7846: 2000 (Incorporating Amendments Nos. 1 & 2), the KEYSTONE Fire Resistance Armoured Cables listed met the requirements of BS 6387: 1994 Clause 11.1 Category C, W & Z.

January 2009

217

PART 3: SECTION 8
FIRE RESISTANT CABLES

Draka UK Limited
Alfreton Road, Derby DE21 4AE UK Tel: +44 (0)1332 345431 Fax: +44 (0)1332 331237 E-mail: firetuf@drakauk.com Website: www.drakauk.com
Certificate No: 361a to IEC 331:1970 and BS EN 50267-2-1:1999

Sifer 950i Single Core Fire Resistant OHLS Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10.0 16 25 35 50 70 95 120 150 185 240 300 400 500 630 Uo/U 600/1000V Notes: 1) The Sifer 950i cables also met IEC 331 when tested at 950C 2 2.) The Sifer 950i cables (up to and including 25mm ) also met IEC 331 when tested in conduit at 750C and 950C which is not recognised by the standard. Core Construction One One One One One One One One One One One One One One One One One One One IEC 331 (see notes 1 & 2) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies BS EN 50267-2-1 (outer covering) <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI LPCB Ref. No. 361a/01

Certificate No: 361a to IEC 331:1970 and BS EN 50267-2-1:1999

Sifer 950S Single Core Fire Resistant OHLS Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 Core Construction One One One One One One One One One One One One One One One One One One One One One IEC 331 (see notes 1 & 2) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies BS EN 50267-2-1 (outer covering) <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI LPCB Ref. No. 361a/02

218

January 2009

SECTION 8: PART
Uo/U 600/1000V Notes: 1) The Sifer cables also met IEC 331 when tested at 950C. 2 2) The Sifer 950s cables (up to and including 25mm ) also met IEC 331 when tested in conduit at 750C and 950C which is not recognised by the standard.

FIRE RESISTANT CABLES

Certificate No: 361b to BS 6387:1994 and BS EN 50267-2-1:1999

Firetuf Power OHLS cable


Nominal csa of 2 conductor (mm ) Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 (see notes 1 & 2) BS EN 50267-2-1 (outer covering) LPCB Ref. No.

1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo/U 450/750V

C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z

<0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI <0.5% HCI

361b/01

Notes: 1) The Firetuf Power OHLS cable also met category C, W, Z when tested for voltage rating 600/1000V which is not recognised by BS 6387. 2) For cables with an outside diameter in excess of 20mm, the Category Z tests were conducted in accordance with guidance from the manufacturer.

Certificate No: 361c to BS EN 50267-2-1: 1999

Firetuf FTPU 950 Fire Resistant Mifer OHLS cable


Nominal csa of 2 conductor (mm ) 1.5 1.5 2.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 4000 120/70 Core Construction (excluding drain wire & earth) 2, 3, 4 & 5 7,10,12,16,20,21 & 30 2, 3, 4 & 5 7,10,12,16,20,21 & 30 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 2, 3, 4 & 5 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 4+ Concentric Earth BS 6387 (see notes 1 & 2) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl LPCB Ref. No.

361c/01

January 2009

219

PART 3: SECTION 8
FIRE RESISTANT CABLES
Nominal csa of 2 conductor (mm ) 150/70 185/95 240/120 50/25 70/35 95/50 Uo/U 450/750V Notes: 1) The Firetuf FTPU 950 fire resistant Mifer OHLS cable also met category C,W,Z when tested for voltage rating 600/1000V which is not recognised by BS 6387. 2) For cable with an outside diameter of in excess of 20mm, the category Z tests were conducted in accordance with guidance from the manufacturer. Core Construction (excluding drain wire & earth) 4+ Concentric Earth 4+ Concentric Earth 4+ Concentric Earth 4+ Concentric Earth 4+ Concentric Earth 4+ Concentric Earth BS 6387 (see notes 1 & 2) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl LPCB Ref. No.

Certificate No: 361d to BS7629-1:1997 (Incorporating Amendments Nos. 1 & 2), BS6387:1994, BS 5839-1: 2002 Clause 26.2d, BS 8434-1: 2003 30 min & BS EN 50200: 2000 Class PH30

Firetuf Easystrip Multicore


Nominal csa of conductor 2 (mm ) 1.5 2.5 4.0 Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendments Nos.1 & 2) Complies Complies (1) Complies
(1)

BS 6387

BS EN 50200

BS 84341

BS 5839-1 Clause 26.2 Standard Standard (3) Standard


(3)

LPCB Ref. No.

C, W, Z C, W, Z C, W, Z

Class PH30 Class PH30 Class PH30

30min 30min (2) 30min

(2)

361d/01

Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), the Firetuf Easystrip Multicore cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 2) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1: 2002. 3) The Firetuf Easystrip Multicore cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), met Class PH30 when tested in accordance with BS EN 50200: 2000 and met a duration of 30min when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 361e to BS 7629-1: 1997 (Incorporating Amendment No.1), BS 5839-1: 2002 Clause 26.2d, BS 8434-1: 2003 30min & BS EN 50200: 2000 Class PH30

Firetuf EMC
Nominal csa of 2 conductor (mm ) Core Construction (excluding drain wire & earth) 2 2 BS 7629-1 (Incorporating Amendment No.1) Complies (1) Complies
(1)

BS EN 50200

BS 8434-1

BS 5839-1 Clause 26.2


(3)

LPCB Ref. No.

1.5 2.5 Uo/U 300/500V

Class PH30 Class PH30

30min (2) 30min

(2)

Standard (3) Standard

361e/01

Notes: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendment No.1), the Firetuf EMC cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation & outer covering) when tested in accordance with BS EN 50267-2-1: 1999 . 2) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2 d) of BS 5839-1: 2002.

220

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES


3) The Firetuf EMC cables listed conform to BS 7629-1: 1997 (Incorporating Amendment No.1), met Class PH30 when tested in accordance with EN 50200: 2000 and met a duration of 30min when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 361f to BS 7629-1: 1997 (Incorporating Amendment No. 1), BS 6387: 1994, BS EN 50200: 2000 Class PH120, BS 8434-2: 2003 120min and BS 5839-1: 2002 Clause 26.2e

Firetuf Plus
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendment No.1), the Firetuf Plus cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1: 1999. 2) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1: 2002. 3) The Firetuf Plus cables listed conform to BS 7629-1: 1997 (Incorporating Amendment No.1), met Class PH120 when tested in accordance with EN 50200: 2000 and met the 120min duration when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002. Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendment No.1) (1) Complies (1) Complies (1) Complies BS 6387 BS EN 50200 BS 8434-2
(2)

BS 5839-1 Clause 26.2 Enhanced (3) Enhanced (3) Enhanced


(3)

LPCB Ref. No.

C,W,Z C,W,Z C,W,Z

Class PH120 Class PH120 Class PH120

120min (2) 120min (2) 120min

361f/01

Certificate No: 361g to BS 7346-6:2005

Firetuf Powerplus
Nominal csa ofconductor (mm ) 10 (1) 120 (1) 150 (1) 16 (1) 185 (1) 2.5 1) 240 (1) 25 (1) 300 (1) 35 (1) 400 (1) 50 (1) 70 (1) 95 Uo/U 600/1000V Note: 1) Stranded conductor only
(1) 2

CoreConstructiondrainwire & earth) 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 7 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 4 4 4 4 4 4 4 4 4

BS 7346-6 (fire survival time) 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min

LPCB Ref. No. 361g/01

Certificate No: 361h to BS 6387: 1994

Sifer 950i - Single Core Fire Resistant OHLS Cable


Nominal csa of conductor 2) (mm 1.5 2.5 4.0 6.0 10 16 Core construction (see note 1) One One One One One One BS 6387 (see notes 2-4) C,W,Z (5) C,W,Z (5) C,W,Z (5) C,W,Z (5) C,W,Z (5) C,W,Z
(5)

IEC 60331-21 (see note 8) Complies Complies Complies Complies Complies Complies

BS EN 502672-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI

LPCB Ref. No. 361h/01

January 2009

221

PART 3: SECTION 8
FIRE RESISTANT CABLES
Nominal csa of conductor 2) (mm 25 35 50 70 95 120 150 185 240 300 400 500 630 Uo/U 600/1000V Note 1: Stranded conductor only. Note 2: Clauses 8 (Bending) and 9.1 & 9.2 (Impact) cannot be conducted due to the cable having only one core. Note 3: These cables also met category C, W, Z when tested for voltage rating 600/1000V which is not recognised by BS 6387. Note 4: Where a single cable is fitted in a conduit, only phase to earth voltage was applied. Note 5: To satisfy the requirement of BS 6387, testing for C, W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element. Note 6: To satisfy the requirement of BS 6387, testing for W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element. Note 7: To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element. Note 8: The Sifer 950i cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950C and at a voltage rating of 600V. Core construction (see note 1) One One One One One One One One One One One One One BS 6387 (see notes 2-4) C,W,Z (6,7) C,W,Z (6,7) C,W,Z (6,7) C,W,Z (6,7)

IEC 60331-21 (see note 8) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies

BS EN 502672-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI

LPCB Ref. No.

Certificate No: 361h/02 to BS 6387

Sifer 950s - Single Core Fire Resistant OHLS Cable


Nominal case of 2 conductor ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 Uo/U 600/1000V Note 1: Stranded conductor only. Note 2: Clauses 8 (Bending) and 9.1 & 9.2 (Impact) cannot be conducted due to the cable having only one core. Note 3: These cables also met category C,W,Z when tested for voltage rating 600/1000V which is not recognised by BS 6387. Note 4: Where a single cable is fitted in a conduit, only phase to earth voltage was applied. Note 5: To satisfy the requirement of BS 6387, testing for C, W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element. Note 6: To satisy the requirement of BS 6387, testing for W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element. Core construction (see note 1) One One One One One One One One One One One One One One One One One One One One One BS 6387 (see notes 2-4) C,W,Z (5) C,W,Z (5) C,W,Z (6,7) C,W,Z (6,7) C,W,Z (6,7) C,W,Z (6,7) C,W,Z (7) C (7) C (7) C (5)

IEC 60331-21 (see note 8) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies

BS EN 502672-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI

LPCB Ref. No. 361h/02

222

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES


Note 7: To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element. Note 8: The Sifer 950s cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950C and at a voltage rating of 600V.

Dubai Cable Company (Private) Limited, Trading as Ducab


Old Abu Dhabi Road, Jebel Ali, Dubai, UAE Tel: +9714 808 2500 Fax: +9714 808 2622 E-mail: ducab@ducab.com Website: www.ducab.com

Certificate No: 781a to BS 7846: 2000 (Incorporating Amendments Nos 1 and 2)

Ducab - FR
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 Uo/U 600/1000V Notes: 1) Stranded conductor only 2) In meeting the requirements of BS 7846: 2000 (incorporating Amendments Nos. 1 & 2) Category F2, the Ducab - FR cables met the requirements for fire resistance characteristics category CWZ specified in Clause 11 of BS 6387: 1994 Core Construction (see note 1) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7846 (Incorporating Amendments Nos. 1 and 2) F2 F2 F2 F2 F2 F2 F2 F2 LPCB Ref. No. 781a/01

Certificate No: 781b to BS 7846: 2000 This certificate is to a withdrawn version of the BS 7846: 2000. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU)

Ducab - FR
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 Uo/U 600/1000 V Notes: 1) Stranded conductors only 2) In meeting the requirements of BS 7846: 2000 Category F2, the Ducab - FR cables met the requirements for fire resistance characteristics category CWZ specified in Clause 11 of BS 6387: 1994 3) BS 7846: 2000 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 781a covers cables certified in accordance with BS 7846: 2000 (Incorporating Amendments Nos. 1 & 2) Core Construction (see Note 1) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7846 (see Notes 2 & 3) F2 F2 F2 F2 F2 F2 F2 F2 LPCB Ref. No. 781b/01

January 2009

223

PART 3: SECTION 8
FIRE RESISTANT CABLES

Certificate No: 781c to BS 6387: 1994, BS EN 50267-2-1: 1999, BS EN 50268-2: 2000 and IEC 60331-21: 1999

Ducab - FR SC
Nominal csa of conductor 2 (mm 1.5 2.5 4.0 6.0 10 Uo/U 600/1000V Notes: 1) Stranded conductor only. 2) Clause 8 (Bending) and 9.1 & 9.2 (Impact) cannot be conducted due to the cable having only one core. 3) To satisfy the requirement of BS 6387, testing for C, W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element. 4) These cables also met category C,W,Z when tested for voltage rating 600/1000V which is not recognised by BS 6387. 5) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. 6) These cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950C (which is not recognised by IEC 60331-21: 1999) and at a voltage rating of 600V. Core Construction (see note 1) One One One One One BS 6387 (see notes 2 5) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-21 <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl BS EN 502682 >60% >60% >60% >60% >60% IEC 6033121 (see note 6) Complies Complies Complies Complies Complies LPCB Ref. No. 781c/01

Dubai Cable Company (Private) Limited, Trading as Ducab


Industrial City, Abu Dhabi, Mussafah, Abu Dhabi, UAE Tel: +9714 808 2500 Fax: +9714 808 2622 E-mail: ducab@ducab.com Website: www.ducab.com Sales office: PO Box 11529, Dubai, UAE

Certificate No: 782a to BS 7846: 2000 (Incorporating Amendments Nos 1 and 2)

Ducab - FR
Nominal csa of 2 conductor (mm ) 50 70 95 120 150 185 240 300 400 Uo/U 600/1000V Notes: 1) Stranded conductors only 2) In meeting the requirements of BS 7846: 2000 Incorporating Amendments Nos. 1 & 2) Category F2, the Ducab - FR cables met the requirements for fire resistance characteristics category CWZ specified in Clause 11 of BS 6387:1994. Core Construction (see note 1) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7846 (Incorporating Amendments Nos. 1 and 2 F2 F2 F2 F2 F2 F2 F2 F2 F2 LPCB Ref. No. 782a/01

Certificate No: 782b to BS 7846: 2000 This certificate is to a withdrawn version of the BS 7846: 2000. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU)

224

January 2009

SECTION 8: PART
Ducab - FR
Nominal csa of 2 conductor (mm ) 50 70 95 120 150 185 240 300 400 Uo/U 600/1000 V Core Construction (see note 1) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7846 (see notes 2 & 3) F2 F2 F2 F2 F2 F2 F2 F2 F2 LPCB Ref. No. 782b/01

FIRE RESISTANT CABLES

Notes: 1) Stranded conductors only 2) In meeting the requirements of BS 7846: 2000 Category F2, the Ducab - FR cables met the requirements for fire resistance characteristics category CWZ specified in Clause 11 of BS 6387: 1994 3) BS 7846: 2000 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 782a covers cables certified in accordance with BS 7846: 2000 (Incorporating Amendments Nos. 1 & 2)

Eland Cables
120 Highgate Studios, 53-79 Highgate Road, London NW5 1TL UK Tel: +44 (0)20 7241 8787 Fax: +44 (0)20 7241 8700 E-mail: sales@eland.co.uk Website: www.eland.co.uk
Certificate No: 568c to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), BS EN 50200: 2000, BS 8434-1: 2003 30min and BS 5839-1: 2002 Clause 26.2d

FireForce
Nominal csa of conductor (mm) 1.0 (1) 1.5 (1) 2.5 (2) 4.0
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendments Nos. 1 & 2) (3) Complies (3) Complies (3) Complies (3) Complies

BS EN 50200 Class PH30 Class PH30 Class PH30 Class PH30

BS 84341 30min (4) 30min (4) 30min (4) 30min


(4)

BS 5839-1 Clause 26.2 Standard (5) Standard (5) Standard (5) Standard
(5)

LPCB Ref. No. 568c/01

Notes: 1) Solid and Stranded conductors. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), the FireForce cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 4) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2 d) of BS 5839-1: 2002. 5) The FireForce cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), met Class PH30 when tested in accordance with EN 50200: 2000 and met a duration of 30min when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

January 2009

225

PART 3: SECTION 8
FIRE RESISTANT CABLES

Emirates Fire Fighting Equipment Factory (FIREX)


Industrial Area 13, P.O.Box 22436, Sharjah, UAE Tel: +971 6 5340300 Fax: +971 6 5340090 E-mail: firex@emirates.net.ae Website: www.firexuae.com
Certificate No: 568a to BS 6387:1994 and BS EN 50267-2-1: 1999

FIREX
Nominal csa of conductors (mm) (1) 1.0 (1) 1.5 (1) 2.5 (2) 4.0 Uo/U 300/500 V Notes: 1) Solid and stranded conductors. 2) Stranded conductor only. Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI LPCB Ref. No. 568a/01

Certificate No: 568a to BS 6387:1994 and BS EN 50267-2-1: 1999

FIREX-UK
Nominal csa of conductors (mm) (1) 1.0 (1) 1.5 (1) 2.5 (2) 4.0 Uo/U 300/500 V Notes: 1) Solid and stranded conductors. 2) Stranded conductor only. Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI LPCB Ref. No. 568a/01

Fireshield Cable Systems Ltd


Unit 2, The Crossings Business Park, Riparian Way, Cross Hills, Keighley BD20 7BW UK Tel: +44 (0)1535 639619 Fax: +44 (0)1535 639618 E-mail: sales@fireshieldcables.co.uk Website: www.fireshieldcables.co.uk
Certificate No: 741a to BS 8434-2: 2003 120min

Fireshield Enhanced
Nominal csa of 2 conductor (mm ) (1) 1.0 (1) 1.5 (1) 2.5 Uo/U 300/500V Notes: 1) Solid conductor only. Core construction 2&4 2&4 2 BS 8434-2 120min (2) 120min (2) 120min
(2)

LPCB Ref. No. 741a/01

226

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES


2) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase.

Global System Technology Plc


Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire LE65 1RT UK Tel: +44 (0)1283 225 478 Fax: +44 (0)1283 222 039 E-mail: info@gst.uk.com Website: www.gst.uk.com
Certificate No: 568a to BS 6387:1994 and BS EN 50267-2-1: 1999 Nominal csa of conductors (mm) (1) 1.0 (1) 1.5 (1) 2.5 (1) 4.0 Uo/U 300/500 V Notes: 1) Solid and stranded conductors. 2) Stranded conductor only. Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI LPCB Ref. No. 568a/01

GLT Exports Limited


Detection House, 72-78 Morfa Road, Swansea SA1 2EN UK Tel: +44 (0)1792 455175 Fax: +44 (0)1792 455176 E-mail: ghassan@gltexports.com Website: www.gltexports.com
Certificate No: 330h to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), BS EN 50200:2006 Class PH120

Fire Defence
Nominal csa of conductor (mm) 1.0 (1) 1.5 (1) 2.5 2) 4.0 Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), the Fire Defence cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-21:1999. 4) The duration of 30min when tested in accordance with BS 8434-1:2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 5) The Fire Defence cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), met Class PH120 when tested in accordance with BS EN 50200:2006 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.
(1)

Core construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2

BS 7629-1 Amendments No.1 and 2) Complies (3) Complies (3) Complies (3) Complies
(3)

BS EN 50200

BS 84341
(4)

BS 5839-1 Clause 26.2 Standard (5) Standard (5) Standard (5) Standard
(5)

LPCB Ref. No.

Class PH120 Class PH120 Class PH120 Class PH120

30min (4) 30min (4) 30min (4) 30min

330h/01

January 2009

227

PART 3: SECTION 8
FIRE RESISTANT CABLES

Grupo General Cable Sistemas, S.A.


CTRA. Rusinol, 63., 08560, Manlleu, Spain Tel: +34 93 852 02 00 Fax: +34 93 852 02 22 E-mail: info@generalcable.es Website: www.generalcable.es
Certificate No: 722a to BS 6387: 1994, BS EN 50267-2-1: 1999, BS EN 50268-2: 2000 and IEC 60331-21:1999

SEGURFOC FR 950 07Z-R-M


Nominal csa of conductor 2 (mm ) 1.5 2.5 4.0 6.0 10.0 16.0 25.0 35.0 50.0 70.0 95.0 120.0 150.0 185.0 240.0 300.0 400.0 500.0 Uo/U 450/750V Notes: 1) Clause 8 (Bending) and 9.1 & 9.2 (Impact) can not be conducted due to the cable having only one core. 2) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. 3) To satisfy the requirement of BS 6387, testing for C & W categories was conducted using a 20mm stainless steel conduit as the other metallic element. 4) To satisfy the requirement of BS 6387, testing for Z category was conducted using a 20mm stainless steel conduit as the other metallic element. 5) To satisfy the requirement of BS 6387, testing for W category was conducted using a 38mm stainless steel conduit as the other metallic element. 6) To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element. 7) Testing to IEC 60331-21: 1999 was conducted at 450V Core Construction (see note 1) (3,4) one (4,5,6) one (4,5,6) one (4,5,6) one (4,5,6) one (4,5,6) one (2,5,6) one (2,5,6) one (2,5,6) one (2,5,6) one (2,5,6) one (2,5,6) one (2,5,6) one (2,6) one (2,6) one (2,6) one (2,6) one (2,6) one BS 6387 (insulation & Binder tape) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W C, W C, W C, W C, W C, W C, W C C C C C BS EN 50267-21 >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI >0.5%HCI BS EN 502682 >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% >60% IEC 6033121 (see note 7) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 722a/01

Grupo General Cable Sistemas, S.A.


CTRA. DE RIBAS KM 13.250, Montcada I Reixac, 08110, Barcelona, Spain Tel: +34 93 227 95 00 Fax: +34 93 227 95 22 E-mail: info@generalcable.es Website: www.generalcable.es
Certificate No: 730a to BS 7846: 2000 (Incorporating Amendment Nos 1 and 2)

SEGURFOC FRA 950


Nominal csa of 2 conductor (mm ) (1) 1.5 (1) 2.5 (1) 4.0 (1) 6.0 (1) 10.0 (1) 16.0 Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7846 (see note 2) F2 F2 F2 F2 F2 F2 LPCB Ref. No. 730a/01

228

January 2009

SECTION 8: PART
Nominal csa of 2 conductor (mm ) (1) 25.0 (1) 35.0 (1) 50.0 (1) 70.0 (1) 95.0 (1) 120.0 (1) 150.0 (1) 185.0 Uo/U 600/1000V Notes: 1) Stranded conductor only. 2) In meeting the requirements of BS 7846 category F2, the SEGURFOC FRA 950 cable met the requirements for fire resistance characteristics category CWZ specified in Clause 11 of BS 6387. Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7846 (see note 2) F2 F2 F2 F2 F2 F2 F2 F2 LPCB Ref. No.

FIRE RESISTANT CABLES

Certificate No: 730a to BS 7846: 2000 (Incorporating Amendment Nos 1 and 2)

SEGURFOC FRA-1 950


Nominal csa of 2 conductor (mm ) (1) 240.0 (1) 300.0 (1) 400.0 Uo/U 600/1000V Notes: 1) Stranded conductor only 2) In meeting the requirements of BS 7846 category F2, the SEGURFOC FRA-1 950 cable met the requirements for fire resistance characteristics category CWZ specified in Clause 11 of BS 6387 Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7846 (see note 2) F2 F2 F2 LPCB Ref. No. 730a/02

Haani Cables Limited


Tofts Farm Industrial Estate, Brenda Road, Hartlepool TS25 2BS UK Tel: +44 (0) 870 389 3400 Fax: +44 (0) 870 389 3402 E-mail: cables@haanicables.co.uk Website: www.haanicables.co.uk
Certificate No: 716a to BS 7629-1: 1997 (Incorporating Amendment No.1), BS 6387: 1994, BS EN 50200: 2000 Class PH30, BS 8434-1: 2003 30min and BS 5839-1: 2002 Clause 26.2d

FIRECOOL
Nominal csa of conductor 2 (mm ) 1.0 (2) 1.5 (2) 2.5 (3) 4.0 Uo/U 300/500V Notes 1) Solid conductor only 2) Solid and Stranded conductors 3) Stranded conductor only 4) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos.1 & 2), the FIRECOOL cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999.
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendments Nos.1 & 2) Complies Complies Complies Complies

BS 6387

BS EN 50200

BS 84341

BS 5839-1 Clause 26.2 Standard (6) Standard (6) Standard (6) Standard
(6)

LPCB Ref. No.

C, W, Z C, W, Z C, W, Z C, W, Z

Class PH30 Class PH30 Class PH30 Class PH30

30min (5) 30min (5) 30min (5) 30min

(5)

716a/01

January 2009

229

PART 3: SECTION 8
FIRE RESISTANT CABLES
5) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2 d) of BS 5839-1: 2002. 6) The FIRECOOL cables listed conform to BS 7629-1: 1997 (Incorporating Amendments No.1 & 2), met Class PH30 when tested in accordance with BS EN 50200: 2000 and met a duration of 30min when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Irish Driver-Harris Company Limited


Millbanks, New Ross, Co. Wexford, Ireland Tel: +353 51 421 405 Fax: +353 51 422 983 E-mail: sales@idh.ie Website: www.idh.ie
Certificate No: 408a to BS 7629-1:1997 (Incorporating Amendments Nos. 1 & 2), BS EN 50200:2000 Class PH30 and BS 58391:2002 Clause 26.2d

Kilflam 2000
Nominal csa of 2 conductor (mm ) 1.0 (2,3) 1.5 (4) 2.5 (4) 4.0 Uo/U 300/500V Notes: 1) Solid conductor only. 2) Solid conductor at 3 & 4 cores only. 3) Stranded conductor at 2 core only. 4) Stranded conductor only. 5) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), the Kilflam 2000 cables met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCI on the (outer covering, insulation and binder tape) when tested in accordance with BS EN 50267-2-1: 1999. 6) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 7) The Kilflam 2000 cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), met Class PH30 when tested in accordance with BS EN 50200:2000 and met the 30min duration when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendments Nos.1 & 2) (5) Complies (5) Complies (5) Complies (5) Complies

BS EN 50200

BS 8434-1

BS 5839-1 Clause 26.2 Standard (7) Standard (7) Standard (7) Standard
(7)

LPCB Ref. No.

Class PH30 Class PH30 Class PH30 Class PH30

30min (6) 30min (6) 30min (6) 30min

(6)

408a/01

Certificate No: 408b to BS 6387:1994

Kilflam 1000
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10.0 16.0 Uo/U 450/750V Notes: 1) Clauses 8 (Bending) and 9.1 & 9.2 (Impact) can not be conducted due to the cable only having one core. 2.) To satisfy the requirements of BS 6387, testing for C, W and Z categories was conducted using 20mm steel conduit as the other metallic element. Core Construction One One One One One One BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z LPCB Ref. No. 408b/01

230

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES

Certificate No: 408c to BS 7629-1:1997 (Inc. Amendment No.1), BS EN 50200:2000 Class PH120, BS 8434-2:2003 120min & BS 5839-1:2002 Clause 26.2e

Kilflam 3000
Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1:1997 (Inc. Amd. No.1), the Kilflam 3000 cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1:1999. 2) The duration of 120min when tested in accordance with BS 8434-2:2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2e) of BS 5839-1:2002. 3) The Kilflam 3000 cables listed conform to BS 7629-1:1997 (Incorporating Amendment No.1), met Class PH120 when tested in accordance with BS EN 50200:2000 and met the 120min duration when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1:2002. Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 BS 7629-1 (Incorporating Amendment No. 1) (1) Complies (1) Complies (1) Complies (1) Complies BS EN 50200 BS 8434-2 BS 5839-1 Clause 26.2 Enhanced (3) Enhanced (3) Enhanced (3) Enhanced
(3)

LPCB Ref. No.

Class PH120 Class PH120 Class PH120 Class PH120

120min (2) 120min (2) 120min (2) 120min

(2)

408c/01

Certificate No: 408d to BS 6387: 1994 and BS EN 50267-2-1: 1999

Kilflam 1200
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10.0 Uo/U 600/1000V Notes: 1) Stranded conductor only. 2) Clause 8 (Bending) and 9.1 & 9.2 (Impact) can not be conducted due to the cable having only one core. 3) The Kilflam 1200 cable also met category C,W,Z when tested for voltage rating 600/1000V which is not recognised by BS 6387. 4) To satisfy the requirement of BS 6387, testing for C category was conducted using a 20mm steel conduit as the other metallic element. 5) To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm steel conduit as the other metallic element. 6) To satisfy the requirement of BS 6387, testing for W and Z categories was conducted using a 20mm steel conduit as the other metallic element. 7) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. Core Construction (see note 1) (4,6) One (4,6) One (4,6) One (5,6) One (5,6) One BS 6387 (see notes 2, 3 & 7) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl LPCB Ref. No.

408d/01

Certificate No: 408e to BS 7629-1: 1997, BS EN 50200: 2000, BS 8434-1: 2003 30min and BS 5839-1: 2002 Clause 26.2d

Kilflam 2000
Nominal csa of 2 conductor (mm 1.0 (2,3) 1.5 (4) 2.5 (4) 4.0
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (see note 8) Complies (5) Complies (5) Complies (5) Complies
(5)

BS EN 50200

BS 8434-1

BS 5839-1 Clause 26.2 Standard (7) Standard (7) Standard (7) Standard
(7)

LPCB Ref. No.

Class PH30 Class PH30 Class PH30 Class PH30

30min (6) 30min (6) 30min (6) 30min

(6)

408e/01

January 2009

231

PART 3: SECTION 8
FIRE RESISTANT CABLES
Uo/U 300/500V Notes: 1) Solid conductor only 2) Solid conductor at 3 & 4 cores only. 3) Stranded conductor at 2 core only. 4) Stranded conductor only 5) In meeting the requirements of BS 7629-1: 1997, the Kilflam 2000 cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1: 1999. 6) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1: 2002. 7) The Kilflam 2000 cables listed conform to BS 7629-1: 1997, met Class PH30 when tested in accordance with BS EN 50200: 2000 and met the 30min duration when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002. 8) BS 7629-1: 1997 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 408e covers cables certified in accordance with BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2)

Certificate No: 408b/01 to BS 6387: 1994

Fumeguard FR
Nominal csa of 2 conductors (mm 1.5 2.5 4.0 6.0 10.0 16.0 Core construction One One One One One One BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z LPCB Ref. No. 408b/01

Uo/U450/750V Notes: 1) Clauses 8 (Bending) and 9.1 & 9.2 (Impact) can not be conducted due to the cable having only one core. 2) To satisfy the requirement of BS 6387, testing for C, W, and Z categories was conducted using 20mm steel conduit as the other metallic element.

Jaylow Supplies Ltd


Jaylow House, Leyton Link Estate, Argall Avenue, Leyton, London E10 7FD UK Tel: +44 (0)870 444 6890 Fax: +44 (0)870 444 6891 Website: www.jaylowcables.com
Certificate No: 682a to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), BS EN 50200:2006 Class PH120 BS 8434-1:2003 30min and BS 5839-1:2002 Clause 26.2d

Jayflame
Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5 4.0 Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2 BS 7629-1 (Incorporating Amendments No. 1 & 2) Complies Complies Complies Complies
(3)

BS EN 50200

BS 84341

BS 5839-1 Clause 26.2 Standard Standard


(5)

LPCB Ref. No.

(3)

(3)

(3)

Class PH120 Class PH120 Class PH120 Class PH120

30min 30min

(4)

682a/01

(4)

(5)

30min

(4)

Standard

(5)

30min

(4)

Standard

(5)

232

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), the Jayflame cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-21:1999. 4) The duration of 30min when tested in accordance with BS 8434-1:2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 5) The Jayflame cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), met Class PH120 when tested in accordance with BS EN 50200:2006 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.

Certificate No: 682b to BS 7629-1: 1997 (Incorporating Amendment No.1), BS EN 50200:2000 Class PH120, BS 8434-2: 2003 120min, BS 6387: 1994 and BS 5839-1: 2002 Clause 26.2e

Jayflame Plus
csa of conductor 2 (mm 1.0 1.5 2.5 Core Construction (excluding drain wire and earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendments Nos. 1 & 2) (2) Complies Complies Complies
(2)

BS 6387 C,W,Z C,W,Z C,W,Z

BS EN 50200 Class PH120 Class PH120 Class PH120

BS 8434-2 120min 120min 120min

BS 5839-1 Clause 26.2 Enhanced Enhanced Enhanced Enhanced Enhanced

LPCB Ref. No. 682b/01

(2)

Uo/U 300/500V Notes: 1) Solid conductor only 2) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos.1 & 2), the Jayflame Plus cables listed met the requirements of smoke density of BS EN 50268-2:2000 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1:1999. 3) The duration of 120min when tested in accordance with BS 8434-2:2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2e) of BS 5839-1:2002. 4) The Jayflame Plus cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos.1 & 2), met Class PH120 when tested in accordance with BS EN 50200:2000 and met a duration of 120min when tested in accordance with BS 8434-2:2003 and hence met the requirements for an enhanced fire resistant cable as described in clause 26.2 of BS 5839-1:2002.

Johnson Controls Hong Kong Limited


20/F Tower 1, 2 & 3, Enterprise I, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong Tel: +852 2590 0012 Fax: +852 2516 5648 Website: www.johnsoncontrols.com
Certificate No: 827a-(cl-1) to BS 6387: 1994 and BS EN 50267-2-1: 1999 (outer covering)

Firepro
Nominal csa of conductor (mm) (1) 1.5 (1) 16 (1) 10 (1) 2.5 (1) 4.0 (1) 6.0 Core construction One (4, 5) One (4, 5) One (3) One (3) One (3) One
(3)

BS 6387 (see note 2 & 6) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z

BS EN 50267-2-1 covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl

LPCB Ref. No. 827a/01

January 2009

233

PART 3: SECTION 8
FIRE RESISTANT CABLES
Uo/U 450/750V Notes: 1) Stranded conductor only 2) Clause 8 (Bending) and 9.1 & 9.2 (Impact) can not be conducted due to the cable having only one core. 3) To satisfy the requirement of BS 6387, testing for C, W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element. 4) To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element. 5) To satisfy the requirement of BS 6387, testing for W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element. 6) Where a single cable is fitted in a conduit, only phase to earth voltage was applied.

KME Italy SpA


Via Della Repubblica 257, 55051 Fornaci Di Barga, Lucca, Italy Tel: +39 0583 701.1 Fax: +39 0583 701623 E-mail: massimo.banfi@kme.com Website: www.kme-italy.com
Certificate No: 427a to BS 6387: 1994 and BS EN 60702-1: 2002

MICO - KME Light Duty Mineral Insulated Cable


Nominal csa 2 of conductor (mm ) 1.0 1.5 2.5 4.0 Uo/U 300/500V Note: 1) The above range is certified in both bare and covered constructions. Core Construction 2, 3, 4 & 7 2, 3, 4 & 7 2, 3, 4 & 7 2 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z BS EN 60702-1 Complies Complies Complies Complies LPCB Ref. No. 427a/01

Certificate No: 427a to BS 6387:1994 and BS EN 60702-1:2002

MICO - KME Single Core Heavy Duty Mineral Insulated Cables


Nominal csa 2 of conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo/U 450/750V Notes: 1) The above range is certified in both bare and covered constructions. 2) For cable with an outside diameter in excess of 20mm, the category Z tests were conducted in accordance with guidance from the manufacturer. Core Construction One One One One One One One One One One One One One One One One One BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 427a/02

234

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES

Certificate No: 427a to BS 6387:1994 and BS EN 60702-1:2002

MICO - KME Multi-core Heavy Duty Mineral Insulated Cables


Nominal csa 2 of conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 Uo/U 450/750V Notes: 1) The above range is certified in both bare and covered constructions. 2) For cable with an outside diameter in excess of 20mm, the category Z tests were conducted in accordance with guidance from the manufacturer. Core Construction 2, 3, 4, 7, 12 & 19 2, 3, 4, 7 & 12 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 427a/03

Nexans France S A - Lyon Plant


170 Avenue Jean Jaures, 69353 Lyon, Cedex 07, France Tel: +33 472 72 24 24 Fax: +33 478 72 13 19
Certificate No: 253a to BS 6387:1994 and BS 6425-1:1990

Pyrolyon E Fire Resistant Cable


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 Uo/U 300/500V Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 BS 6425-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl LPCB Ref. No.

C, W, Z C, W, Z C, W, Z

253a/01

Certificate No: 253f to BS 7629-1: 1997 (Inc. Amd. No.1), BS 6387: 1994, BS EN 50200: 2000 Class PH30, BS 8434-1: 2003 30min and BS 5839-1: 2002 Clause 26.2d

Alsecure-NX200
Nominal csa of conductor 2 (mm ) 1.0 (1) 1.5 (1) 2.5 (2) 4.0 Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendment No.1), the Alsecure-NX200 cables listed met the requirements of smoke density of BS EN 50268-: 2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999.
(1)

Core Construction (excluding drain wire & earth) 2,3 & 4 2,3 & 4 2,3 & 4 2,3 & 4

BS 7629-1 (Incorporating Amendment No.1) Complies (3) Complies (3) Complies (3) Complies
(3)

BS 6387

BS EN 50200

BS 84341

BS 5839-1 Clause 26.2 Standard (5) Standard (5) Standard (5) Standard
(5)

LPCB Ref. No.

C,W,Z C,W,Z C,W,Z C,W,Z

Class PH30 Class PH30 Class PH30 Class PH30

30min (4) 30min (4) 30min (4) 30min

(4)

253f/01

January 2009

235

PART 3: SECTION 8
FIRE RESISTANT CABLES
4) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2 d) of BS 5839-1: 2002. 5) The Alsecure-NX200 cables listed conform to BS 7629-1: 1997 (Incorporating Amendment No.1), met Class PH30 when tested in accordance with EN 50200: 2000 and met a duration of 30min when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 253g to BS 7629-1: 1997 (Inc. Amd. Nos. 1 and 2), BS 6387: 1994, BS EN 50200: 2000 Class PH120, BS 8434-2: 2003 120min and BS 5839-1: 2002 Clause 26.2e

ALSECURE NX 200 PLUS


Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendments Nos.1 & 2) Complies Complies Complies


(2)

BS 6387

BS EN 50200

BS 84342

BS 5839-1 Clause 26.2 Enhanced


(4)

LPCB Ref. No.

C,W,Z C,W,Z C,W,Z

(1)

(2)

(1)

(2)

Class PH120 Class PH120 Class PH120

120min 120min 120min

(3)

253g/01

(3)

Enhanced
(4)

(3)

Enhanced
(4)

Uo/U 300/500V Notes: 1) Solid conductor only. 2) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), the ALSECURE NX 200 PLUS cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 3) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1: 2002. 4) The ALSECURE NX 200 PLUS cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), met Class PH120 when tested in accordance with BS EN 50200: 2000 and met a duration of 120min when tested in accordance with BS 84342: 2003 and hence met the requirements for an Enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

OSL Group Limited (trading as CQR Security)


125 Pasture Road, Tarran Way Industrial Estate, Moreton, Wirral, Merseyside CH46 4TH UK Tel: +44 (0)151 606 9595 Fax: +44 (0)151 606 1122 E-mail: tinot@cqr.co.uk Website: www.cqr.co.uk
Certificate No: 815a to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), BS EN 50200: 2000, BS 8434-1: 2003 30min and BS 5839-1: 2002 Clause 26.2d

CQR FireBrand 30
Nominal csa of Conductor 2 (mm ) 1.0 (2,3) 1.5 (4) 2.5 (4) 4.0 Uo/U 300/500V Notes: 1) Solid conductor only 2) Solid conductor at 3 & 4 cores only. 3) Stranded conductor at 2 core only. 4) Stranded conductor only 5) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), the CQR FireBrand 30 cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1: 1999.
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendments Nos. 1 and 2) (5) Complies (5) Complies (5) Complies (5) Complies

BS EN 50200

BS 84341
(6)

BS 5839-1 Clause 26.2 Standard (7) Standard (7) Standard (7) Standard
(7)

LPCB Ref. No.

Class PH30 Class PH30 Class PH30 Class PH30

30min (6) 30min (6) 30min (6) 30min

815a/01

236

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES


6) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1: 2002. 7) The CQR FireBrand 30 cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), met Class PH30 when tested in accordance with BS EN 50200: 2000 and met the 30min duration when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Prysmian Cables & Systems Ltd (formerly Pirelli Cables Ltd)


Energy Cables, Chickenhall Lane, Bishopstoke, Eastleigh, Hants SO50 6YU UK Tel: +44 (0)8457 678345 Fax: +44 (0)2380 295465 E-mail: cables.marketing.uk@prysmian.com Website: www.prysmain.co.uk
Certificate No: 077a to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2)

FP200 Gold LSOH


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 Uo/U 300/500V Note: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), the FP200 Gold LSOH cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1: 1999. Core Construction (excluding drain wire & earth) 7 7, 12 & 19 7 & 12 BS 7629-1 (Incorporating Amendments Nos. 1 and 2) (1) Complies (1) Complies (1) Complies LPCB Ref. No. 077a/02

Certificate No: 077a to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2)

FP200 Flex
Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 Uo/U 300/500V Note: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), the FP200 Flex cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1: 1999. Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendments Nos. 1 and 2) (1) Complies (1) Complies (1) Complies LPCB Ref. No. 077a/03

Certificate No: 077b to BS 6387:1994 and BS EN 50267-2-1:1999

FP300 Fire Resistant Cable LSOH Outer Covering


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 6.0 10 16 Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl LPCB Ref. No. 077b/01

January 2009

237

PART 3: SECTION 8
FIRE RESISTANT CABLES
Uo/U 450/750V Note: 1) The FP300 LSOH cable also met Category C,W,Z when tested for voltage rating 600/1000V which is not recognised by BS 6387.

Certificate No: 077b to BS 6387:1994 and BS EN 50267-2-1

FP400 Fire Resistant Cable LSOH Outer Covering


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo/U 450/750V Notes : 1) The FP400 cable also met category C, W, Z when tested for voltage rating 600/1000 V which is not recognised by BS 6387. 2) The FP400 cable approved with insulation type XLPE(GP8). 3) The FP400 cable approved with insulation type EPR(GP6). Core Construction 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 BS 6387 (see note 1) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl LPCB Ref. No. 077b/02

Certificate No: 077b to BS 6387:1994 and BS EN 50267-2-1

FP200 Gold LSOH


Nominal csa of 2 conductor (mm ) 2.5 Uo/U 300/500V Core Construction (excluding drain wire & earth) 19 BS 6387 C&W BS EN 50267-2-1 (binder tape & outer covering) <0.5% HCl LPCB Ref. No. 077b/03

Certificate No: 077c to BS 6387: 1994, BS EN 50267-2-1: 1999 and IEC 60331-21: 1999

FP100 Fire Resistant Single Core Cable For Installation In Conduit


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 6.0 10 16 25 35 50 70 Core Construction One One One One One One One One One One One BS 6387 (see notes 1 - 4) C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl IEC 60331-21 (see Note 5) Complies Complies Complies Complies Complies LPCB Ref. No. 077c/01

238

January 2009

SECTION 8: PART
Nominal csa of 2 conductor (mm ) 95 120 150 185 240 300 400 500 630 Uo/U 450/750V Notes: 1) Testing was conducted using 20mm steel conduit. 2) To satisfy the requirement of BS 6387 the conduit was considered as the other metallic element. 3) Clauses 8 (Bending) and 9.1 & 9.2 (Impact) cannot be conducted due to the cable having only one core. 4) Only a single cable is fitted in conduit, hence only phase to earth voltage was applied. O 5) Testing to IEC 60331 was conducted at voltage rating of 600/1000V and at 95 C which is not recognised by the standard. Core Construction One One One One One One One One One BS 6387 (see notes 1 - 4) C, W, Z C C BS EN 50267-2-1 (outer covering) IEC 60331-21 (see Note 5) Complies Complies Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No.

FIRE RESISTANT CABLES

Certificate No: 077d to BS 6387:1994, BS EN 50267-2-1:1999 and BS EN 50268-2:2000

FP150 LS0H
Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 Uo/U 300/500V Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl BS EN 50268-2 >60% >60% >60% LPCB Ref. No. 077d/01

Certificate No: 077e to BS 6387: 1994, BS EN 50267-2-1: 1999 and IEC 60331-21: 1999

FP300 Single Core Cable


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 Uo/U 450/750V Notes: 1) Clause 8 (Bending) and 9.1 & 9.2 (Impact) of the BS 6387 standard cannot be conducted due to the cable having only one core. 2) The single core cable also met category C, W, Z when tested for voltage rating 600/1000 V which is not recognised by BS 6387. 3) To satisfy the requirement of BS 6387, testing for C, W and Z categories was conducted using a 20mm steel conduit as the other metallic element. Core Construction One One One One One One One One One One One One One One One One One One One One BS 6387 (see notes 1,2, & 5) (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (4) C (4) C (4) C (4) C (4) C (4) C (4) C (6) Complies (6) Complies (6) Complies (6) Complies BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl IEC 60331-21 (see Note 7) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 077e/01

January 2009

239

PART 3: SECTION 8
FIRE RESISTANT CABLES
4) To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm steel conduit as the other metallic element. 5) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. 6) Only clause 10 of BS 6387 was conducted. o 7) Testing to IEC 60331 was conducted at voltage rating of 600/1000V and at 950 C which is not recognised by the standard

Certificate No: 077e to BS 6387:1994, BS EN 50267-2-1 and IEC 60331-21

FP300MI Single Core Cable


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 Uo/U 450/750V Notes: 1) Clause 8 (Bending) and 9.1 & 9.2 (Impact) of the BS 6387 standard cannot be conducted due to the cable having only one core. 2) The single core cable also met category C, W, Z when tested for voltage rating 600/1000 V which is not recognised by BS 6387. 3) To satisfy the requirement of BS 6387, testing for C,W, and Z categories was conducted using a 20mm steel conduit as the other metallic element. 4) To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm steel conduit as the other metallic element. 5) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. 6) Only clause 10 of BS 6387 was conducted. 7) Testing to IEC 331 was conducted at voltage rating of 600/1000V and at 950C which is not recognised by the standard. Core Construction One One One One One One One One One One One One One One One One One One One One BS 6387 (see notes 1, 2 & 5) (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (4) C (4) C (4) C (4) C (4) C (4) C (4) C (6) Complies (6) Complies (6) Complies (6) Complies BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl IEC 60331-21 (see note 7) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 077e/02

Certificate No: 077f to BS 7629-1: 1997 (Inc. Amd. Nos. 1 & 2) and BS 5839-1:2002 Clause 26.2d

FP200 Gold LSOH


Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5 4.0 Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendment Nos. 1 & 2) (1) Complies (1) Complies Complies Complies
(1)

BS EN 50200

BS 5839-1 Clause 26.2 Standard (2) Standard Standard


(2) (2)

LPCB Ref. No. 077f/01

(1)

Class PH30 Class PH30 & PH60 Class PH30 & PH60 Class PH30 & PH60

Standard

(2)

Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), the FP200 Gold LSOH cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11

240

January 2009

SECTION 8: PART
of BS 6387: 1994 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 2) The FP200 Gold LSOH cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), met Class PH30 when tested in accordance with BS EN 50200: 2000 and met the requirements of the additional fire, mechanical shock and water tests described in Clause 26.2 d) of BS 5839-1: 2002 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

FIRE RESISTANT CABLES

Certificate No: 077g to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), BS EN 50200:2000 Class PH120, BS 84342:2003 120min & BS 5839-1:2002 Clause 26.2e

FP Plus
Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1: 1997 (Inc. Amd. Nos. 1 & 2), the FP Plus cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 2) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1: 2002. 3) The FP Plus cables listed conform to BS 7629-1: 1997, meet Class PH120 when tested in accordance with EN 50200: 2000 and meet a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence meet the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002. Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendment Nos.1 & 2) (1) Complies (1) Complies (1) Complies BS EN 50200 BS 8434-2 BS 5839-1 Clause 26.2 Enhanced (3) Enhanced (3) Enhanced
(3)

LPCB Ref. No.

Class PH120 Class PH120 Class PH120

120min 120min 120min

077g/01

Certificate No: 077h to BS 7629-1:1997 (Inc.Amd.No.1), BS EN 50200:2000 Class PH120, BS 8434-2:2003 120min BS 5839-1: Clause 26.2e

FP Plus Flex
Nominal csa of conductor 2 (mm ) Core Construction (excluding drain wire & earth) 2,3 & 4 2,3 & 4 2,3 & 4 2,3 & 4 BS 7629-1 (Incorporating Amendment No.1)
(1)

BS EN 50200

BS 84342

BS 5839-1 Clause 26.2


(3)

LPCB Ref. No.

1.0 1.5 2.5 4.0

Complies Complies Complies Complies

(1)

(1)

(1)

Class PH120 Class PH120 Class PH120 Class PH120

120min 120min 120min

(2)

Enhanced Enhanced

077h/01

(2)

(3)

(2)

Enhanced

(3)

120min

(2)

Enhanced

(3)

Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendment No.1), the FP Plus Flex cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1: 1999. 2) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1: 2002. 3) The FP Plus Flex cables listed conform to BS 7629-1: 1997 (Incorporating Amendment No.1), met Class PH120 when tested in accordance with EN 50200: 2000 and met a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 077j to BS 7629-1: 1997 This certificate is to a withdrawn version of the BS 7629-1: 1997. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU).

January 2009

241

PART 3: SECTION 8
FIRE RESISTANT CABLES FP200 Gold LSOH
Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1: 1997, the FP200 Gold LSOH cables listed met the requirements of smoke density of BS 7622-2: 1993, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS 6425-1: 1990. 2) BS 7629-1: 1997 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being. to satisfy the requirements of these regulators. Certificate 077a covers cables certified in accordance with BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2) Core Construction (excluding drain wire & earth) 7 7, 12 & 19 7 & 12 BS 7629-1 (see Note 2) Complies (1) Complies (1) Complies
(1)

LPCB Ref. No.

077j/01

Certificate No: 077j to BS 7629-1: 1997 This certificate is to a withdrawn version of the BS 7629-1: 1997. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU).

FP200 Flex
Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 Uo/U 300/500V Notes: 1) In meeting the requirements of BS 7629-1: 1997, the FP200 Flex cables listed met the requirements of smoke density of BS 7622-2: 1993, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS 6425-1: 1990. 2) BS 7629-1: 1997 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with st the CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 077a covers cables certified in accordance with BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2) Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (see Note 2) Complies (1) Complies (1) Complies
(1)

LPCB Ref. No. 077j/02

Certificate No: 077k to BS 7629-1: 1997 This certificate is to a withdrawn version of the BS 7629-1: 1997. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU), BS EN 50200: 2000 & BS 5839-1:2002 Clause 26.2d

FP200 Gold LSOH


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4.0 Uo/U 300/500V Notes: Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (see Note 3) Complies (1) Complies (1) Complies (1) Complies
(1)

BS EN 50200

BS 5839-1 Clause 26.2 Standard (2) Standard (2) Standard (2) Standard
(2)

LPCB Ref. No.

Class PH30 Class PH30 & PH60 Class PH30 & PH60 Class PH30 & PH60

077k/01

242

January 2009

SECTION 8: PART
1) In meeting the requirements of BS 7629-1: 1997, the FP200 Gold LSOH cables listed met the requirements of smoke density of BS 7622-2: 1993, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS 6425-1: 1990. 2) The FP200 Gold LSOH cables listed conform to BS 7629-1: 1997, met Class PH30 when tested in accordance with BS EN 50200: 2000 and met the requirements of the additional fire, mechanical shock and water tests described in Clause 26.2 d) of BS 5839-1: 2002 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002. 3) BS 7629-1: 1997 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on st 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 077f covers cables certified in accordance with BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2)

FIRE RESISTANT CABLES

Certificate No: 077g

FP Plus
Nominal csa of conductor 2 (mm 1.5 2.5 Core Construction (excluding drain wire & earth) 2 2 BS 7629-1 (Incoporating Amendments Nos. 1 & 2) (2) Complies Complies
(2)

BS EN 50200 Class PH120 Class PH120

BS 84342 120min 120min

BS 5839-1 Clause 26.2 Enhanced Enhanced

LPCB Ref. No. 077g/02

Uo/U 300/500V Notes: 1) Solid conductor only 2) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), the FP Plus cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-2-1: 1999. 3) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2e) of BS 5839-1: 2002. 4) The FP Plus cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), met Class PH120 when tested in accordance with BS EN 50200: 2000 and met the 120min duration when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 077m to BS 7346-6: 2005, BS EN 50267-2-1: 1999 and BS 61034-2: 2005

FP600
Nominal csa of conductor 2 (mm ) (1) 10 16 (1) 25 (1) 35 (1) 50 (1) 70 Uo/U 600/1000V Note: 1) Stranded conductor only. 2) In achieving 120min fire survival time in accordance with BS 7346-6: 2005, the FP600 cables listed also achieved a 120min fire survival time in accordance with BS 6491:2008. The test method given in BS 8491: 2008 is technically identical to the test method given in BS 7346: 2005 Annex B.
(1)

Core construction earth wire) 2, 3 & 4 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 4

BS 7346-6 survival time) 120min 120min 120min 120min 120min 120min

BS 8491 (fire survival time see note 2) 120min 120min 120min 120min 120min 120min

BS EN 50267-21 <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl

BS EN 610342 >60% >60% >60% >60% >60% >60%

LPCB Ref. No. 077m/01

January 2009

243

PART 3: SECTION 8
FIRE RESISTANT CABLES

Prysmian Cables & Systems Ltd (formerly Pirelli Cables Ltd)


Energy Cables Unit, Wrexham Industrial Estate, Wrexham LL13 9PH UK Tel: +44 (0)1978 662345 Fax: +44 (0)1978 662292 E-mail: cables.marketing.uk@prysmian.com Website: www.prysmian.co.uk
Certificate No: 517a to BS 6387: 1994, BS EN 50267-2-1: 1999 and IEC 60331-21: 1999

FP300 Single Core LSZH Cable


Nominal csa of 2 conductor (mm ) 50 70 95 120 185 240 300 400 630 800 1000 Uo/U 450/750 Notes: 1) These cables also met category C when tested for voltage rating 600/1000V which is not recognised by BS 6387. 2) Clause 8 (bending) and 9.1 & 9.2 (impact) can not be conducted due to the cable having only one core. 3) To satisfy the requirement of BS 6387, testing for category C was conducted using 38mm steel conduit as the other metallic element. 4) Where single cable is fitted in conduit, only phase to earth voltage was applied. 5) Only clause 10 of BS 6387 was conducted. 6) These cables met the requirements of IEC 60331 when tested at a temperature of 950C (which is not recognised by IEC 60331) and at a voltage rating of 600/1000V. Core Construction One One One One One One One One One One One BS 6387 (see notes 1 to 4) C C C C C C Complies (5) Complies (5) Complies (5) Complies (5) Complies (5) BS EN 50267-2-1 (outer covering) <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI IEC 60331-21 (see note 6) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies LPCB Ref. No. 517a/01

Certificate No: 517b to BS 6387:1994

FP400 Fire Resistant Cable


Nominal csa of 2 conductor (mm ) 50 70 95 120 185 240 300 400 Uo/U 450/750 Note: 1) The FP400 cable also met categories C, W, and Z when tested for voltage rating of 600/1000V which is not recognised by BS 6387. Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z LPCB Ref. No. 517b/01

Certificate No: 517c to BS 7346-6: 2005, BS 8491: 2008, BS EN 50267-2-1: 1999 and BS EN 61034-2: 2005

244

January 2009

SECTION 8: PART
FP600S
Nominal csa of conductor (mm 2 ) 120 150 185 240 300 400 70 (1) 95
(1)

FIRE RESISTANT CABLES

Core construction (excluding earth wire) 4 4 4 4 4 4 4 4

BS 7346-6 (fire survival time) 120min 120min 120min 120min 120min 120min 120min 120min

BS 8491 (fire survival time see note 2) 120min 120min 120min 120min 120min 120min 120min 120min

BS EN 502672-1 <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl

BS EN 61034-2 >60% >60% >60% >60% >60% >60% >60% >60%

LPCB Ref. No. 517c/01

Uo/U 600/1000V Notes: 1) Stranded conductor only. 2) In achieving a 120min fire survival time in accordance with BS 7346-6: 2005, the FP600S cables listed also achieved a 120min fire survival time in accordance with BS 8491: 2008. The test method given in BS 8491: 2008 is technically identical to the test method given in BS 7346-6: 2005, Annex B.

Prysmian Power Cables & Systems Australia Pty Limited


1 Heathcote Road, Liverpool, Sydney, New South Wales 2170, Australia Tel: +61 2 9600 0777 Fax: +61 2 9600 0303 Website: www.pirelli.com
Certificate No: 422a to BS 6387:1994 and BS EN 50267-2-1:1999

FIRESTOP FS-90 Single Core Cable


Nominal csa of 2 conductor (mm ) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Uo/U 450/750 V Notes : 1) Approved for the CEC01QGR series construction. 2) Approved for the CEC01QAZ series construction. 3) Clause 8 (Bending) and 9.1 & 9.2 (Impact) of the BS 6387 standard cannot be conducted due to the cable having only one core. 4) To satisfy the requirement of BS 6387, testing for C category was conducted using a 20mm and 38mm steel conduit as the other metallic element. 5) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. Core Construction 1.2 One 1.2 One 1.2 One 1 One 1 One 1 One 1 One 1 One 1 One 1 One 1 One 1 One 1 One 1 One 1 One 1 One BS 6387 (See notes 4, 5 & 6) C C C C C C C C C C C C C C C C BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl LPCB Ref. No. 422a/01

Certificate No: 422b to BS 6387:1994 and BS EN 50267-2-1:1999

January 2009

245

PART 3: SECTION 8
FIRE RESISTANT CABLES FIRESTOP FS-90 Multicore Cable
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo/U 450/750 V Notes: 1) Approved for CEC04QMR series construction. 2) Approved for REC04QMR series construction. Core Construction (See notes 1, 2) (1) 4 (1) 4 (1) 4 (1) 4 (1) 4 (1) 4 (1) 4 (1) 4 (1)(2) 4 (1)(2) 4 (1)(2) 4 (1)(2) 4 (1)(2) 4 (1)(2) 4 (1)(2) 4 (1)(2) 4 (2) 4 BS 6387 BS EN 50267-2-1 (outer covering) <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl <0.5% HCl LPCB Ref. No.

C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z

422b/01

RAMCRO S.p.A
V. Tanaro, 19, 20010 Villastanza di Parabiago, Milan, Italy Tel: +39 0331 406550 Fax: +39 0331 406559
Certificate No: 568a to BS 6387:1994 and BS EN 50267-2-1:1999

Ramfirecro-F3
Nominal csa of 2 conductor (mm ) (1) 1.0 (1) 1.5 (1) 2.5 (2) 4.0 Uo/U 300/500 V Notes: 1) Solid and stranded conductors. 2) Stranded conductor only. Core Construction 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 (outer covering) <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI LPCB Ref. No. 568a/01

Certificate No: 568b to BS 7629-1: 1997 This certificate is to a withdrawn version of the BS 7629-1: 1997. Cables conforming to this version of the standard may not be suitable for use within the jurisdiction of the European Union (EU), BS EN 50200: 2000 Class PH30, BS 8434-1:2003 30min & BS 5839-1:2002 Clause 26.2d

Ramfirecro-F3 Standard
Nominal csa of conductor (mm) 1.0 (1) 1.5 (1) 2.5 (2) 4.0 Uo/U 300/500V
(1)

Core Construction (excluding drain wire & earth) 2 ,3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (see note 6) Complies (3) Complies (3) Complies (3) Complies
(3)

BS EN 50200

BS 8434-1

BS 5839-1 Clause 26.2 Standard (5) Standard (5) Standard (5) Standard
(5)

LPCB Ref. No.

Class PH30 Class PH30 Class PH30 Class PH30

30min (4) 30min (4) 30min (4) 30min

(4)

568b/01

246

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES


Notes: 1) Solid and Stranded conductors. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1: 1997, the Ramfirecro-F3 Standard cables listed met the requirements of smoke density of BS 7622-2: 1993 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS 6425-1: 1990. 4) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2 d) of BS 5839-1: 2002. 5) The Ramfirecro-F3 Standard cables listed conform to BS 7629-1: 1997, met Class PH30 when tested in accordance with EN 50200: 2000 and met a duration of 30min when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002. 6) BS 7629-1: 1997 was amended in 2004 to implement the changes to the identification of cores by colours, in accordance with the st CENELEC Harmonisation Document HD 308 S2. The un-amended version of the standard was withdrawn on 31 March 2006. However, cables with the old identification colours, meeting the withdrawn version of the standard, are still requested by some regulators outside of the EU. Certification to the un-amended version of the standard has therefore been maintained, for the time being, to satisfy the requirements of these regulators. Certificate 568c covers cables certified in accordance with BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2)

Certificate No: 568c to BS 7629-1:1997 (Incorporating Amendments Nos. 1 & 2), BS EN 50200: 2000, BS 8434-1: 2003 30min and BS 5839-1: 2002 Clause 26.2d

Ramfirecro-F3 Standard
Nominal csa of conductor (mm) 1.0 (1) 1.5 (1) 2.5 (2) 4.0 Uo/U 300/500V Notes: 1) Solid and Stranded conductors. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), the Ramfirecro-F3 Standard cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 4) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2 d) of BS 5839-1: 2002. 5) The Ramfirecro-F3 Standard cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), met Class PH30 when tested in accordance with EN 50200: 2000 and met a duration of 30min when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendments Nos. 1 and 2) Complies (3) Complies (3) Complies (3) Complies
(3)

BS EN 50200

BS 84341

BS 5839-1 Clause 26.2 Standard (5) Standard (5) Standard (5) Standard
(5)

LPCB Ref. No.

Class PH30 Class PH30 Class PH30 Class PH30

30min (4) 30min (4) 30min (4) 30min

(4)

568c/01

TELE-FONIKA Kable Sp. z o.o., S.K.A.


ul.Wielicka 114, 30-663 Krakow, Poland Tel: +48 12 652 50 00 Fax: +48 12 652 51 56 E-mail: iso@tfkable.pl Website: www.tfkable.pl
Certificate No: 814c to BS 6387: 1994, BS EN 50267-2-1: 1999 and IEC 60331-21: 1999

Flame-X 950 Single


Nominal csa of conductor 2 (mm (1) 1.5 (1) 2.5 (1) 4.0 (1) 6.0 Core Construction One One One One BS 6387 (See Notes 2, 6 & 7) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z
(3)

BS EN 50267-2-1 (outer covering) <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl

IEC 60331-21 (See Note 8) Complies Complies Complies Complies

LPCB Ref. No.

814c/01

January 2009

247

PART 3: SECTION 8
FIRE RESISTANT CABLES
Nominal csa of conductor 2 (mm (1) 10 (1) 16 25 35 50 70 95 120 150 185 240 300 400 500 Uo/U 600/1000V Notes: 1) Stranded conductor only 2) Clause 8 (Bending) and 9.1 & 9.2 (Impact) cannot be conducted due to the cable having only one core. 3) To satisfy the requirement of BS 6387, testing for C, W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element. 4) To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element. 5) To satisfy the requirement of BS 6387, testing for W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element. 6) These cables also met category C,W,Z when tested for voltage rating 600/1000V which is not recognised by BS 6387. 7) Where a single cable is fitted in a conduit, only phase to earth voltage was applied. 8) These cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950C (which is not recognised by IEC 60331-21: 1999) and at a voltage rating of 600V. Core Construction One One One One One One One One One One One One One One BS 6387 (See Notes 2, 6 & 7) C, W, Z (4,5) C, W, Z (4,5) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (3) C, W, Z (4) C (4) C (4) C (4) C (4) C (4) C (4,5)

BS EN 50267-2-1 (outer covering) <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl

IEC 60331-21 (See Note 8) Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies

LPCB Ref. No.

Certificate No: 814a to BS 7629-1: 1997 (Inc. Amd. Nos. 1 and 2), BS 6387: 1994, BS EN 50200: 2000 Class PH30, BS 8434-1: 2003 30min and BS 5839-1: 2002 Clause 26.2

FLAME-X 950
Nominal csa of conductor (mm) Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendments Nos. 1 & 2) Complies Complies Complies Complies
(3)

BS 6387

BS EN 50200

BS 8434-1

BS 5839-1 Clause 26.2 Standard Standard


(5)

LPCB Ref. No.

1.0 1.5

(1)

C,W,Z C,W,Z C,W,Z C,W,Z

(1)

(3)

2.5

(1)

(3)

4.0

(2)

(3)

Class PH30 Class PH30 Class PH30 Class PH30

30min 30min

(4)

814a/01

(4)

(5)

30min

(4)

Standard

(5)

30min

(4)

Standard

(5)

Uo/U 300/500V Notes: 1) Solid conductor only 2) Stranded conductor only 3) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), the FLAME-X 950 cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 4) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1: 2002. 5) The FLAME-X 950 cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), met Class PH30 when tested in accordance with BS EN 50200: 2000 and met a duration of 30min when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

248

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES

Certificate No: 814b to BS 7629-1: 1997 (Inc. Amd. Nos. 1 and 2), BS 6387: 1994, BS EN 50200: 2000 Class PH120, BS 8434-2: 2003 120min and BS 5839-1: 2002 Clause 26.2

FLAME-X 950 Enhanced


Nominal csa of conductor (mm) 1.0 1.5
(1)

Core Construction drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendments Nos. 1 and 2) (3) Complies Complies Complies Complies
(3)

BS6387

BS EN 50200 Class PH120 Class PH120 Class PH120 Class PH120

BS 84342 120min 120min 120min 120min


(4)

BS 5839-1 Clause 26.2 Enhanced Enhanced Enhanced Enhanced


(5)

LPCB Ref. No. 814b/01

C,W,Z C,W,Z C,W,Z C,W,Z

(1)

(4)

(5)

2.5 4.0

(1)

(3)

(4)

(5)

(2)

(3)

(4)

(5)

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), the FLAME-X 950 Enhanced cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 4) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2e) of BS 5839-1: 2002. 5) The FLAME-X 950 Enhanced cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), met Class PH120 when tested in accordance with BS EN 50200: 2000 and met a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 814d to BS 7846: 2000 (Incorporating Amendments Nos. 1 and 2)

FLAME-X 950 Power


Nominal csa of conductor (mm) 1.5 (1) 2.5 (1) 4.0 (1) 6.0 (1) 10 (1) 16 (1) 25 (1) 35 (1) 50 (1) 70 (1) 95 (1) 120 (1) 150 (1) 185 (1) 240 (1) 300 Uo/U 600/1000V Notes: 1) Stranded conductor only 2) In meeting the requirements of BS 7846: 2000 (Incorporating Amendments Nos. 1 and 2) Category F2, the FLAME-X Power cables listed met the requirements for fire resistance characteristics Category CWZ specified in Clause 11 of BS 6387: 1994
(1)

Core Construction 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2, 3 & 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

BS 7846: 2000 (Incorporating Amendments Nos. 1 and 2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2 (2) F2

LPCB Ref. No. 814d/01

January 2009

249

PART 3: SECTION 8
FIRE RESISTANT CABLES

Tratos Cavi SpA


Via Stadio 2, Pieve S. Stefano 52036, Arezzo, Italy Tel: +39 0575 7941 Fax: +39 0575 798026 E-mail: direzione@tratos.it Website: www.tratos.it
Certificate No: 222a to BS 7629-1:1997, BS EN 50200:2000 Class PH30, BS 8434-1:2003 30min & BS 5839-1:2002 Clause 26.2d

FIRE-Safe TW950 Fire Resistant Cable


Nominal csa of conductor 2 (mm ) Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendments Nos. 1 and 2) BS EN 50200 BS 8434-1 BS 5839-1 Clause 26.2 LPCB Ref. No.

1.0 1.5 2.5 4.0

Complies Complies Complies Complies

Class PH30 Class PH30 Class PH30 Class PH30

30min 30min 30min 30min

Standard Standard Standard Standard

222a/01

Uo/U 300/500V Notes: 1) Solid conductor only 2) Stranded conductor only 3) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), the FIRE-safe TW950 Fire Resistant Cables listed met the requirements of smoke density of BS 7622-2: 1993, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS 6425-1: 1990. 4) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1: 2002. 5) The FIRE-safe TW950 Fire Resistant Cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 and 2), met Class PH30 when tested in accordance with BS EN 50200: 2000 and met the 30min duration when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Certificate No: 222b to BS 7629-1: 1997 (Incorporating Amendments Nos. 1 & 2), BS EN 50200: 2000 Class PH120, BS 8434-2: 2003 120min & BS 5839-1: 2002 Clause 26.2e

Firesafe Enhanced
Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5 4.0
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendments Nos. 1 and 2) Complies Complies Complies Complies


(3)

BS EN 50200

BS 84342

BS 5839-1 Clause 26.2 Enhanced


(5)

LPCB Ref. No.

(1)

(3)

(2)

(3)

(2)

(3)

Class PH120 Class PH120 Class PH120 Class PH120

120min 120min 120min 120min

(4)

222b/01

(4)

Enhanced
(5)

(4)

Enhanced
(5)

(4)

Enhanced
(5)

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos.1 & 2), the Firesafe Enhanced cables listed met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and

250

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES


achieved less than 0.5%HCl on the (insulation, binder tape & outer covering) when tested in accordance with BS EN 50267-2-1: 1999. 4) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1: 2002. 5) The Firesafe Enhanced cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos.1 & 2), met Class PH120 when tested in accordance with EN 50200: 2000 and met a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Tyco Thermal Control Huzhou Co Limited


Shuanglin Industrial Zone, Nanxun District, Huzhou, Zhejiang Province 313012, Peoples Republic of China Tel: +86 572 7362100 Fax: +86 572 7362166
Certificate No: 841a to BS EN 60702-1:2002 and BS 6387:1994

Pyrotenax Pyro MI Bare Mineral Insulated Cables (Heavy Duty)


Nominal csa of 2 conductor ) 1.5 10 16 2.5 25 4.0 6.0 Uo/U 450/750V Notes: 1) Solid conductor only. 2) The above cables are certified in bare construction only. Core Construction 2 2 2 2 2 2 2 BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies BS 6387 C,W,Z C,W,Z C,W,Z C,W,Z C,W,Z C,W,Z C,W,Z LPCB Ref. No. 841a/01

Certificate No: 841b to BS EN 60702-1:2002, BS 6387:1994, BS EN 50200:2000 Class PH120, BS 8434-2:2003, BS 5839-1:2002 Clause 26.2e and BS EN 50267-2-1:1999

Pyrotenax Pyro MI Served Mineral Insulated Cables (Heavy Duty)


Nominal csa of 2 conductor ) 1.5 10 16 2.5 25 4.0 6.0 Core Construction 2 2 2 2 2 2 2 BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies BS 6387 C,W,Z C,W,Z C,W,Z C,W,Z C,W,Z C,W,Z C,W,Z BS EN 50200 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 BS 8434-2 Clause 26.2 (3) 120min 120min 120min 120min 120min 120min 120min
(3)

BS 5839-1 (outer covering) (4) Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced
(4)

BS EN 50267-2-1 <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl <0.5%HCl

LPCB Ref. No. 841b/01

(3)

(4)

(3)

(4)

(3)

(4)

(3)

(4)

(3)

(4)

Uo/U 450/750V Notes: 1) Solid conductor only. 2) The above cables are certified in served construction only. 3) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2e) of BS 5839-1: 2002.

January 2009

251

PART 3: SECTION 8
FIRE RESISTANT CABLES
4) The Pyrotenax Pyro MI Served Mineral Insulated Cables (Heavy Duty) listed conform to BS EN 60702-1: 2002, met Class PH120 when tested in accordance with BS EN 50200: 2000 and met a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an Enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Tyco Thermal Controls Canada Limited


250 West Street, Trenton, Ontario K8V 5S2, Canada Tel: +613 392 6571 Fax: +613 394 3711 Website: www.tycothermal.com
Certificate No: 676a to BS EN 60702-1:2002, BS 6387:1994 and BS EN 50267-2-1:1999

Pyrotenax Bare Mineral Insulated Cable (light duty)


Nominal csa of 2 conductor (mm ) 1.0T 1.0 1.5T 1.5 2.5T 2.5 4.0 Uo/U=300/500V T = Twisted light duty Note: 1) The above range is certified in bare construction only. Core Construction (see note 1) 2 2, 3, 4 & 7 2, 3, 4 2, 3, 4 & 7 2, 3, 4 2, 3, 4 & 7 2 BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI LPCB Ref. No. 676a/01

Certificate No: 676a to BS EN 60702-1:2002, BS 6387:1994 and BS EN 50267-2-1:1999

Pyrotenax Bare Mineral Insulated Cable (single core heavy duty)


Nominal csa of 2 conductor (mm ) 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 Uo 450V Note: 1) The above range is certified in bare construction only. 2) For single core cables, only phase to earth voltage was applied. Core Construction (see note 1) One One One One One One One One One One One One One One One BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI LPCB Ref. No. 676a/02

Certificate No: 676a to BS EN 60702-1:2002, BS 6387:1994 and BS EN 50267-2-1:1999

252

January 2009

SECTION 8: PART
Pyrotenax Bare Mineral Insulated Cable (heavy duty)
Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 Uo/U 450/750V Note: 1) The above range is certified in bare construction only. Core Construction (see note 1) 2, 3, 4, 7, 12 & 19 2, 3, 4, 7 & 12 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50267-2-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI LPCB Ref. No. 676a/03

FIRE RESISTANT CABLES

Tyco Thermal Controls UK Limited


3 Rutherford Road, Stephenson Industrial Estate, Washington, Tyne & Wear NE37 3HX UK Tel: +44 (0)191 419 8200 Fax: +44 (0)191 419 8201 E-mail: mbaker@tycothermal.com Website: www.tycothermal.com
Certificate No: 063d to BS EN 60702-1:2002 and BS 6387:1994

Pyrotenax Bare Mineral Insulated Cable


Nominal csa of 2 conductor (mm ) (1) 1.0T (1) 1.0 (1) 1.5 (2) 1.5 (1) 1.5T (1) 2.5T (1) 2.5 (2) 2.5 (1) 4.0 (1) 4.0T (2) 4.0 (2) 6.0 (2) 10.0 T = Twisted light duty Notes: 1) The voltage of the mineral insulated light duty cables is at 500V. 2) The voltage of the mineral heavy duty cables is at 750V. 3) The above range is certified in bare construction only. Core Construction (see note 1) 2 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2 2, 3 & 2, 3 & 2 2 2, 3 & 2, 3 & 2 4 4 4 4 4 4 4 4 BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z LPCB Ref. No. 333a/01

Certificate No: 427a to BS EN 60702-1:2002 and BS 6387:1994

Pyrotenax Bare Mineral Insulated Cable (light duty)


Nominal csa of 2 conductor (mm ) 1.0 1.5 2.5 4 Uo=500V Note: Core Construction (see note 1) 2, 3, 4 & 7 2, 3, 4 & 7 2, 3, 4 & 7 2 BS EN 60702-1 Complies Complies Complies Complies BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z LPCB Ref. No. 427a/01

January 2009

253

PART 3: SECTION 8
FIRE RESISTANT CABLES
1) The above range is certified in bare construction only.

Certificate No: 063e/02 to BS EN 60702-1:2002 and BS 6387:1994

Pyrotenax Bare Mineral Insulated Cable (single core)


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 400 Uo=750V Notes: 1) The above range is certified in bare construction only 2) For cable with an outside diameter in excess of 20mm, the category Z tests were conducted in accordance with guidance from the manufacturer. Core Construction (see note 1) One One One One One One One One One One One One One One One One One BS EN 60702-1 BS 6387 LPCB Ref. No.

Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies

C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z

427a/02

Certificate No: 063e/03 to BS EN 60702-1:2002 and BS 6387:1994

Pyrotenax Bare Mineral Insulated Cable (heavy duty)


Nominal csa of 2 conductor (mm ) 1.5 2.5 4.0 6.0 10 16 25 Uo=750V Notes: 1) The above range is certified in bare construction only. 2) For cable with an outside diameter in excess of 20mm, the category Z tests were conducted in accordance with guidance from the manufacturer. Core Construction (see note 3) 2, 3, 4, 7, 12 & 19 2, 3, 4, 7, & 12 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 2, 3, & 4 BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z LPCB Ref. No. 427a/03

Certificate No: 063f/01 to BS EN 60702-1:2002, BS 6387:1994, BS EN 50200:2000, BS 8434-2:2003 120min, BS 5839-1:2002 Clause 26.2e and BS EN 50267-2-1:1999

Pyrotenax Served Mineral Insulated Cable (light duty)


Nominal csa of conductor 2 (mm ) 1.0T Core Construction (see note 3) 2 BS EN 60702-1 Complies BS 6387 C, W, Z BS EN 50200 Class PH120 BS 84342 120min
(1)

BS 5839-1 Clause 26.2 Enhanced


(2)

BS EN 50257-2-1 <0.5%HCI

LPCB Ref. No. 063f/01

254

January 2009

SECTION 8: PART
Nominal csa of conductor 2 (mm ) 1.0 1.5T 1.5 2.5T 2.5 4.0 Core Construction (see note 3) 2, 3, 4 & 7 2, 3, 4 2, 3, 4 & 7 2, 3, 4 2, 3, 4 & 7 2 BS EN 60702-1 Complies Complies Complies Complies Complies Complies BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50200 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 BS 84342 120min 120min 120min 120min 120min 120min
(1)

FIRE RESISTANT CABLES


BS 5839-1 Clause 26.2 Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced
(2)

BS EN 50257-2-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI

LPCB Ref. No.

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

Uo=500V T = Twisted light duty Notes: 1) The duration of 120min when tested in accordance with BS 8434-2:2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1:2002. 2) The served Pyrotenax MI cable listed conform to BS EN 60702-1:2002, meet Class PH120 when tested in accordance with BS EN 50200:2000 and meet the requirements for the additional fire, mechanical shock and water test described in Clause 26.2 e) of BS 5839-1:2002, and hence meet the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1:2002. 3) The above range is certified in served construction only.

Certificate No: 063f/02 to BS EN 60702-1:2002, BS 6387:1994, BS EN 50200:2000, BS 8434-2:2003, BS 5839-1:2002 and BS EN 50267-2-1:1999

Pyrotenax Served Mineral Insulated Cable (single core heavy duty)


Nominal csa of conductor 2 (mm ) 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 300 Core Construction (see note 3) One One One One One One One One One One One One One One One One BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies Complies BS 6387 C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z C, W, Z BS EN 50200 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 BS 84342 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min 120min
(1)

BS 5839-1 Clause 26.2 Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced
(2)

BS EN 50267-2-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI

LPCB Ref. No. 063f/02

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

January 2009

255

PART 3: SECTION 8
FIRE RESISTANT CABLES
Nominal csa of conductor 2 (mm ) 400 Core Construction (see note 3) One BS EN 60702-1 Complies BS 6387 C, W, Z BS EN 50200 Class PH120 BS 84342 120min
(1)

BS 5839-1 Clause 26.2 Enhanced


(2)

BS EN 50267-2-1 <0.5%HCI

LPCB Ref. No.

Uo 750V Notes: 1) The duration of 120min when tested in accordance with BS 8434-2:2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1:2002. 2) The served Pyrotenax MI cable listed conform to BS EN 60702-1:2002, meet Class PH120 when tested in accordance with BS EN 50200:2000 and meet the requirements for the additional fire, mechanical shock and water test described in Clause 26.2 e) of BS 5839-1:2002, and hence meet the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1:2002. 3) The above range is certified in served construction only.

Certificate No: 063f/03 to BS EN 60702-1:2002, BS 6387:1994, BS EN 50200:2000, BS 8434-2:2003, BS 5839-1:2002 and BS EN 50267-2-1:1999

Pyrotenax Served Mineral Insulated Cable (heavy duty)


Nominal csa of conductor 2 (mm ) 1.5 2.5 4.0 6.0 10 16 25 Core Construction (see note 3) 2, 3, 4, 7, 12 & 19 2, 3, 4, 7 & 12 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4 BS EN 60702-1 Complies Complies Complies Complies Complies Complies Complies BS 6387 C. W. Z C. W. Z C. W. Z C. W. Z C. W. Z C. W. Z C. W. Z BS EN 50200 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 Class PH120 BS 84342 120min 120min 120min 120min 120min 120min 120min
(1)

BS 5839-1 Clause 26.2 Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced
(2)

BS EN 50257-2-1 <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI <0.5%HCI

LPCB Ref. No. 063f/03

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

(1)

(2)

Uo 750V Notes: 1) The duration of 120min when tested in accordance with BS 8434-2:2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1:2002. 2) The served Pyrotenax MI cable listed conform to BS EN 60702-1:2002, meet Class PH120 when tested in accordance with BS EN 50200:2000 and meet the requirements for the additional fire, mechanical shock and water test described in Clause 26.2 e) of BS 5839-1:2002, and hence meet the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 58391:2002. 3) The above range is certified in served construction only.

Certificate No: 063c to BS 7629-1:1997 (Incorporating Amendment No.1), BS EN 50200:2000 Class PH30 & BS 5839-1:2002d

Pyro S
Nominal csa of conductor (mm) (1) 1.0 1.5
(2,3)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2, 3 & 4

BS 7629-1 (Incorporating Amendment Nos.1 and 2) (5) Complies Complies Complies Complies
(5)

BS EN 50200 Class PH30 Class PH30 Class PH30 Class PH30

BS 84341 30min 30min


(6)

BS 5839-1 Clause 26.2 Standard Standard


(7)

LPCB Ref. No. 063c/01

(6)

(7)

2.5

(4)

(5)

30min

(6)

Standard

(7)

4.0

(4)

(5)

30min

(6)

Standard

(7)

256

January 2009

SECTION 8: PART

FIRE RESISTANT CABLES

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Solid conductor at 3 & 4 cores only. 3) Stranded conductor at 2 core only. 4) Stranded conductor only. 5) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), the Pyro S cables met the requirements of smoke density of BS EN 50268-2: 2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCI on the (outer covering, insulation and binder tape) when tested in accordance with BS EN 50267-2-1: 1999. 6) The duration of 30min when tested in accordance with BS 8434-1: 2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 7) The Pyro S cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), met Class PH30 when tested in accordance with BS EN 50200:2000 and met the 30min duration when tested in accordance with BS 8434-1: 2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.

Union Cable Company Ltd


Unit 15, Goddard Road, Astmoor Industrial Estate, Runcorn, Cheshire WA7 1QF UK Tel: +44 (0)1928 577 418 Fax: +44 (0)1928 581 099jim@unioncable.co.uk E-mail: sales@unioncable.co.uk Website: www.unioncable.co.uk
Certificate No: 682a to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), BS EN 50200:2006 Class PH120, BS 8434-1:2003 30min and BS 5839-1:2002 Clause 26.2

Firetrax Gold
Nominal csaof 2 conductor ) 1.0 1.5 2.5 4.0
(1)

CoreConstructiondrainwire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2

BS 7629-1 Amendments No.1 & 2) (3) Complies Complies Complies Complies


(3)

BS EN 50200 Class PH120 Class PH120 Class PH120 Class PH120

BS 8434-1 30min 30min 30min 30min


(4)

BS 58391Clause 26.2 Standard Standard Standard Standard


(5)

LPCB Ref. No. 682a/01

(1)

(4)

(5)

(1)

(3)

(4)

(5)

(2)

(3)

(4)

(5)

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), the Firetrax Gold cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-21:1999. 4) The duration of 30min when tested in accordance with BS 8434-1:2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 5) The Firetrax Gold cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), met Class PH120 when tested in accordance with BS EN 50200:2006 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.

Certificate No: 682b-(cl-2) to BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), BS EN 50200:2000 Class PH120, BS 8434-2:2003 120min and BS 5839-1:2002 Clause 26.2

Firetrax Plus
Nominal csa of conductor (mm) 1.0 Core construction (excluding drain wire & earth) 2, 3 & 4 BS 7629-1 (Incorporating Amendments Nos. 1 and 2) (2) Complies BS 6387 C, W, Z BS EN 50200 Class PH120 BS 84342 120min
(3)

BS 5839-1

LPCB Ref. No. 682b/01

Enhanced

(4)

January 2009

257

PART 3: SECTION 8
FIRE RESISTANT CABLES
Nominal csa of conductor (mm) 1.5 2.5 Core construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 BS 7629-1 (Incorporating Amendments Nos. 1 and 2) (2) Complies Complies
(2)

BS 6387 C, W, Z C, W, Z

BS EN 50200 Class PH 120 Class PH120

BS 84342 120min 120min


(3)

BS 5839-1

LPCB Ref. No.

Enhanced Enhanced

(4)

(3)

(4)

Uo/U 300/500V Note 1: Solid conductor only Note 2: Note 3: Note 4: In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), the Firetrax Plus cables listed met the requirements of smoke density of BS EN 50268-2:2000 and achieved less than 0.5%HCl on the (outer covering & insulation) when tested in accordance with BS EN 50267-2-1:1999. The duration of 120min when tested in accordance with BS 8434-2:2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1:2002. The Firetrax Plus cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos. 1 and 2), met Class PH120 when tested in accordance with BS EN 50200:2000 and met a duration of 120min when tested in accordance with BS 8434-2:2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.

Ventcroft Limited
Goddard Road, Astmoor Industrial Estate, Runcorn, Cheshire WA7 1NQ UK Tel: +44 (0)1928 581098 Fax: +44 (0)1928 581099 E-mail: sales@ventcroft.co.uk Website: www.ventcroft.co.uk
Certificate No: 682a to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), BS EN 50200: 2000 Class PH30, BS 84341:2003 30min & BS 5839-1:2002 Clause 26.2d

NoBurn Platinum
Nominal csa of conductor 2 (mm ) (1) 1.0 1.5
(1)

Core Construction (excluding drain wire & earth) 2, 3 & 4 2, 3 & 4 2, 3 & 4 2

BS 7629-1 (Incorporating Amendments No.1 & 2) Complies Complies Complies Complies


(3)

BS EN 50200

BS 84342

BS 5839-1 Clause 26.2 Standard Standard Standard Standard


(5)

26.2

LPCB Ref. No.

(3)

2.5 4.0

(1)

(3)

(2)

(3)

Class PH120 Class PH120 Class PH120 Class PH120

120min 120min 30min

(4)

682a/01

(4)

(5)

(4)

(5)

120min

(4)

(5)

Uo/U 300/500V Notes: 1) Solid conductor only. 2) Stranded conductor only. 3) In meeting the requirements of BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), the NoBurn Platinum cables listed met the requirements of smoke density of BS EN 50268-2:2000, fire resistance requirements CWZ in Clause 11 of BS 6387:1994 and achieved less than 0.5%HCl on the (outer covering, binder tape & insulation) when tested in accordance with BS EN 50267-21:1999. 4) The duration of 30min when tested in accordance with BS 8434-1:2003 is achieved by 15min for the fire and impact phase and an additional 15min for the fire, impact and water phase as described in Clause 26.2d) of BS 5839-1:2002. 5) The NoBurn Platinum cables listed conform to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), met Class PH120 when tested in accordance with BS EN 50200:2006 and met the 30min duration when tested in accordance with BS 8434-1:2003 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2002.

Certificate No: 682b to BS 7629-1:1997 (Incorporating Amendments Nos.1 and 2), BS 6387:1994, BS EN 50200:2000 Class PH120, BS 8434-2: 2003 120min & BS 5839-1:2002 Clause 26.2e

258

January 2009

SECTION 8: PART
NoBurn Diamond
Nominal csa of conductor 2 (mm ) 1.0 1.5 2.5 Core Construction (excluding drain wire & earth) 2, 3 & 4 2,3 & 4 2,3 & 4 BS 7629-1 (Incorporating Amendment Nos.1 and 2) Complies Complies Complies BS 6387 BS EN 50200 BS 84342 BS 5839-1 Clause 26.2 Enhanced Enhanced
(4)

FIRE RESISTANT CABLES

LPCB Ref. No.

C,W,Z C,W,Z C,W,Z

Class PH120 Class PH120 Class PH120

120min 120min

(3)

682b/01

(3)

(4)

120min

(3)

Enhanced

(4)

Uo/U 300/500V Notes: 1) Solid conductor only. 2) In meeting the requirements of BS 7629-1: 1997 (Incorporating Amendments Nos.1 and 2), the NoBurn Diamond cables listed met the requirements of smoke density of BS EN 50268-2: 2000 and achieved less than 0.5%HCl on the (outer covering & insulation) when tested in accordance with BS EN 50267-2-1: 1999. 3) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1: 2002. 4) The NoBurn Diamond cables listed conform to BS 7629-1: 1997 (Incorporating Amendments Nos.1 and 2), met Class PH120 when tested in accordance with EN 50200: 2000 and met a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence met the requirements for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.

Wrexham Mineral Cables


Wynnstay Technology Park, Ruabon, Wrexham, Clwyd LL14 6EN UK Tel: +44 (0)1978 810789 Fax: +44 (0)1978 821502 E-mail: wrexhammineral@teeco.com Website: www.teeco.com
Certificate No: 333a to BS EN 60702-1:2002, BS EN 50200:2000 Class PH120, BS 8434-2:2003 120min and BS 5839-1:2002 Clause 26.2

Wrexham Mineral Insulated Cable


Nominal csa of conductor 2 (mm ) 1.0T (1) 1.0 (1) 1.5 (2) 1.5 (1) 1.5T (1) 2.5T (1) 2.5 (2) 2.5 (1) 4.0 (1) 4.0T (2) 4.0 (2) 6.0 (2) 10 T=Twisted light duty Notes: 1) The voltage of the mineral insulated light duty cables is at 300/500V. 2) The voltage of the mineral insulated Heavy duty cables is at 450/750V. 3) In meeting the requirements of BS EN 60702-1: 2002, the WMI cables listed met the requirements of fire resistance requirements CWZ in Clause 11 of BS 6387: 1994 and achieved less than 0.5%HCl on the (outer covering) when tested in accordance with BS 6425-1: 1990. 4) The duration of 120min when tested in accordance with BS 8434-2: 2003 is achieved by 60min for the fire and impact phase and an additional 60min for the fire, impact and water phase as described in Clause 26.2 e) of BS 5839-1: 2002. 5) Only the served WMI cables listed conform to BS EN 60702-1: 2002, meet Class PH120 when tested in accordance with BS EN 50200: 2000 and meet a duration of 120min when tested in accordance with BS 8434-2: 2003 and hence meet the requirement for an enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2002.
(1)

Core Construction 2 2, 3 & 2, 3 & 2, 3 & 2, 3 & 2 2, 3 & 2, 3 & 2 2 2, 3 & 2, 3 & 2 4 4 4 4 4 4 4 4

BS EN 607021 Complies (3) Complies (3) Complies (3) Complies (3) Complies (3) Complies (3) Complies (3) Complies (3) Complies (3) Complies (3) Complies (3) Complies (3) Complies
(3)

BS EN 50200 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120 ClassPH120

BS 8434-2 Clause 26.2 (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min (4) 120min

BS 5839-1 Clause 26.2 (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced (5) Enhanced

LPCB Ref. No. 333a/01

January 2009

259

PART 3: SECTION 8
FIRE RESISTANT CABLES

260

January 2009

SECTION 9: PART

PLENUM RATED CABLES

This section lists cables that are certificated by LPCB as complying with NFPA 262 Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces. NFPA 262 presents a test procedure for evaluating the potential for fire spread along cables and wires housed in a plenum or other environmental space. Notes: 1) Since LPCB uses national and international standards for the listing of products, in some instances the requirements of these standards may conflict with the recommendations of local codes of practice. We recommend that specifiers seek advice from the relevant local authorities and amend their specifications accordingly.

January 2009

261

PART 3: SECTION 10
ALARM RECEIVING CENTRES This section lists Alarm Receiving Centres approved to LPS 1020 Requirements for Alarm Receiving Centres and those certified to the requirements of BS 5979 Code of Practice for Remote Centres Receiving Signals from Security Systems. The Fire Services 'Model Agreement' between the Fire and Rescue authorities and users of remotely monitored fire alarm systems calls for third party certification of both the installer and the Alarm Receiving Centre (ARC). The LPCB approval scheme based on the criteria of LPS 1020 when used in conjunction with BS 5979 provides the means to achieve the alarm receiving centre requirement of the model agreement. Third party certification of the installer can be achieved via the LPCBs scheme for installers based, on the requirements of LPS 1014 Requirements for certificated fire detection and alarm systems firms. For further details of this agreement see the CFOA website. Since the Alarm receiving centres must have links to the appropriate fire brigade mobilisation centres, the list includes details of the fire authority areas for which they are approved.

Banham Alarms (Prop: Banham Patent Locks Limited)


10 Pascal Street, London SW8 4SH UK Tel: +44 (0)207 622 5151 Fax: +44 (0)207 498 2461 Website: www.banham.com
Certificate No. CSFA006 to LPS 1020 Alarm receiving equipment: Telecom Red CARE System. Approved Fire Authority areas of operation: Bedfordshire, Berkshire, Buckinghamshire, East Sussex, Essex, Hampshire, Hertfordshire, Kent, Greater London, Surrey West Sussex.

East Midlands Central Station Limited


Waterside House, Tissington Close, Chilwell, Nottingham NG9 6QG UK Tel: +44 (0)870 90 30 999 Fax: +44 (0)870 90 32 999 E-mail: admin@emcs.co.uk Website: www.emcs.co.uk
Certificate No. CFSA 017 to LPS 1020 Issue 2.1 Alarm receiving equipment: BT Redcare (Incorporating Classic,GSM,AGILE and ASSURE), CSL Dualcom, Emizon21, Webway One Digital Communicators, (Point Id and SIA communication Protocols) CCTV - Adpro, DM and VDT. Approved fire authority areas of operation: Avon, Bedfordshire, Berkshire, Buckinghamshire, Cambridgeshire, Central Scotland, Cheshire, Cleveland, Cornwall, Cumbria, Derbyshire, Devon, Dorset, Dumfries & Galloway, Durham, Dyfed, East Sussex, Essex, Fife, Gloucestershire, Grampian, Guernsey, Hampshire, Hereford & Worcester, Hertfordshire, Highlands & Islands, Humberside, Isle Of Man, Isle Of Wight, Kent, Lancashire, Leicester, Lincolnshire, London, Lothian & Borders, Manchester, Merseyside, Mid/West Wales, Norfolk, North Wales, North Yorkshire, Northants, Northern Ireland, Northumberland, Oxfordshire, Powys, Shropshire, Somerset, South Wales, South Yorkshire, Staffordshire, Strathclyde, Suffolk, Surrey, West Sussex, Tayside, Tyne & Wear, Warwickshire, West Midlands, West Yorkshire, Wiltshire.

National Monitoring (Prop. AVR Group Limited)


Units 16/24, Attenburys Park Estate, Attenburys Lane, Timperley, Cheshire WA14 5QN UK Tel: +44 (0)870 4009998 Fax: +44 (0)870 4009988
Certificate No. CSFA008 to LPS 1020 Alarm receiving equipment: Telecom Red CARE System.

262

January 2009

SECTION 10: PART

ALARM RECEIVING CENTRES

Approved fire authority areas of operation: Avon, Bedfordshire, Berkshire, Cambridgeshire, Cheshire, Clwyd, Cumbria, Derbyshire, Devon, Dorset, Essex, Gloucestershire, Hampshire, Hereford & Worcester, Humberside, Lancashire, Leicestershire, Lincolnshire, London, Greater Manchester, Merseyside, Norfolk, Northamptonshire, Northern Ireland, Nottinghamshire, North Yorkshire, Shropshire, South Yorkshire, Staffordshire, Suffolk, Surrey, Tyne and Wear Warwickshire, West Glamorgan, West Midlands, West Yorkshire, Strathclyde.

Security Services (Prop: Bryan Enterprises Ltd.)


2 Berry Street, Stoke on Trent ST4 1AY UK Tel: +44 (0)1782 416308 Fax: +44 (0)1782 849522
Certificate No. CSFA007 to LPS 1020 Alarm receiving equipment: Telecom Red CARE System. Approved fire authority areas of operation: Cheshire, Clwyd, Greater Manchester, Gwynedd, Shropshire, Staffordshire, West Midlands

Southern Monitoring Services Limited


Security House, 212-218, London Road, Waterlooville, Hampshire PO7 7AJ UK Tel: +44 (0)870 242 220 Fax: +44 (0)870 243 330
Certificate No. CSFA003 to LPS 1020 Alarm receiving equipment: Telecom Red CARE System. Approved fire authority areas of operation: Avon, Bedfordshire, Berkshire, Buckinghamshire, Cambridgeshire, Cheshire, Cleveland, Clwyd, Cornwall, Cumbria, Derbyshire, Devon, Dorset, East Sussex, Essex, Gloucestershire, Grampian, Greater London, Gwent, Hampshire, Hereford & Worcester, Hertfordshire, Humberside, Isle of Wight, Kent, Lancashire, Leicestershire, Lincolnshire, Lothian, Greater Manchester, Merseyside, Mid Glamorgan, Norfolk, Northamptonshire, North Yorkshire, Nottinghamshire, Oxfordshire, Powys, Shropshire, Somerset, South Glamorgan, South Yorkshire, Staffordshire, Strathclyde, Suffolk, Surrey, Tyne & Wear, Warwickshire, West Glamorgan, West Midlands, West Sussex, West Yorkshire, Wiltshire.

January 2009

263

PART 3: SECTION 11
ALARM TRANSMISSION AND FAULT MONITORING EQUIPMENT AND SIGNALLING SYSTEMS Introduction This section of the Red Book lists alarm transmission and fault routing equipment suitable for use with fire alarm systems as defined by Figure 1 of EN 54-1:1996 Fire detection and fire alarm systems Part 1. Alarm transmission equipment suitable for use with intruder alarm and hold-up systems is listed in Part 6:Section 1.2 of the Red Book. Where alarm transmission equipment may be suitable for use with both fire alarm systems and intruder alarm and hold-up systems the entry for the approved equipment will appear in Part 3 and Part 6 of the Red Book. Where appropriate, reference is made to published standards and the following standards are currently used for the approval schemes: EN 54-21:2006 Fire detection and fire alarm systems - Part 21: Alarm transmission and fault warning routing equipment LPS 1277 Requirements for LPCB Approval and listing of Alarm Transmission Systems and Equipment

EN 54-21:2006 is a harmonised standard for the Construction Products Directive and CE marking will be required for most of the European market by May 2009. ANNEX ZA of EN 54-21 states that for CE marking purposes it is not necessary to test the alarm transmission and fault routing equipment performance characteristics in conjunction with the transmission networks to confirm the claimed transmission parameters D, M, T, A ,S and I. These parameters are however described in the EN 54-21 normative ANNEX A and may be tested as an option. Unless otherwise stated LPCB approval to EN 54-21 confirms that the routing equipment meets only those requirements of ANNEX ZA relating to the operational and environmental reliability of the item(s) located within the protected premises. Whereas LPS 1277 includes criteria for both fire and security systems that specifically requires the alarm transmission and fault routing equipment to be tested in conjunction with the appropriate transmission networks. Particular emphasis is placed on the verification of manufacturers claims by measuring alarm transmission times over the transmission path(s) between the equipment under test and the corresponding alarm receiving centre. The response to the reporting of fault conditions is measured in a similar way. The results of these measurements are expressed in terms of alarm transmission system (ATS) performance criteria classification, using the parameters D, M, T and where applicable S and I. Where, D = Transmission time classification M = Transmission time maximum values T = Reporting time classification S = Substitution Security ( LPS category A only) I = Information Security ( LPS category A only) Availability is considered a key parameter under LPCB approval and is therefore included within the requirements of LPS 1277 and the resultant performance is expressed using the parameter A for Availability. The measured values associated with each performance criteria classification are used to determine the category of the alarm transmission equipment. Two categories of alarm transmission equipment are defined in LPS 1277; Category A: Components and associated networks meeting system Category A requirements are suitable for use in fire protection applications classified as being very high risk, i.e. where arson attempts are expected or where fire is expected to spread very rapidly. Category B: Components and associated networks meeting system Category B requirements are suitable for all other fire protection applications.

264

January 2009

SECTION 11: PART

ALARM TRANSMISSION AND FAULT MONITORING EQUIPMENT AND SIGNALLING SYSTEMS Products approved to LPS 1277 encompass all of the requirements of EN 54-21 and products tested and approved by the LPCB will have automatically met the compliance criteria of EN 54-21 in full. It is therefore recommended that alarm transmission and fault routing equipment be approved to LPS 1277 where possible. Compliance with relevant safety standards and applicable mandatory directives is a pre-requisite of LPCB approval and listing. Regular product auditing and regular factory inspections are carried out by LPCB ensuring high manufacturing standards and continued compliance with the applicable product standard. Notes: Since the LPCB uses national and international standards for the listing of products, in some instances the requirements of these standards may conflict with the recommendations of local codes of practice. We recommend that specifiers seek advice from the relevant local authorities and amend their specifications accordingly.

January 2009

265

PART 3: SECTION 11.1


ALARM TRANSMISSION AND FAULT ROUTING EQUIPMENT Alarm transmission and fault monitoring equipment approved to the requirements of EN 54-21:2006 Fire detection and fire alarm systems - Part 21: Alarm transmission and fault warning routing equipment. Unless stated otherwise the performance of those components of the alarm transmission and fault monitoring system normally located in the protected premises have been tested and assessed for compliance without connection to the associated alarm transmission networks as prescribed by ANNEX ZA of EN 54-21.

266

January 2009

SECTION 11.2: PART

ALARM TRANSMISSION AND FAULT ROUTING EQUIPMENT AND SYSTEMS

Alarm transmission equipment approved to LPS 1277 Requirements for LPCB Approval and listing of Alarm Transmission Systems and Equipment Requirements and tests are included in the Loss Prevention Standard that enables the assessment of the performance of those components of the alarm transmission system normally located in the protected premises when used in conjunction with the appropriate transmission networks.

BT redcare
Monument TE, 11-13 Great Tower Street, London EC3R 5EA UK Tel: +44 (0) 800 800 828 Fax: +44 (0)20 7929 6490 Website: www.redcare.bt.com
Certificate No: 775a to LPS 1277: Issue 2.2 Product Name UC-372G-UK ASSURE STAR Fire Category B Security Grade 3 Primary Transmission Path Asynchronous digital subscriber line (ASDL) operated by BT Broadband Secondary Transmission Path General packet radio service (GRPS) on a BT mobile network LPCB Ref. No. 775a/01

Performance Parameters Transmission Transmission Path Time Classification Primary D4 Secondary Combined
1

Transmission Time Max. Values M3 M3 M3


2 2 2

Reporting Time Classification T5 T3 T5


3 4

Substitution Security S2 S2 S2

Information Security I3 I3 I3

Network Availability5 A3 A1 A3

D4 D4

Approved Ancillaries AO100 External base antenna (short) BA900-5 High gain antenna (long) CAB0106 10m low loss extension cable UltraCapture8 Video Card UltraCapture4 Video Card Notes: 1) The combined performance parameters are shown for the ASSURE STAR as a whole, i.e. with both primary and secondary transmission paths operational. The alarm transmission performance parameters of the ASSURE STAR are consistent with those of ATS 5. 2) During a planned maintenance procedure the ASSURE STAR will achieve performance classification D4 at a maximum transmission time classification M2. The maintenance procedure will be operated approximately four times per year and will be of approximately 5 minutes duration. 3) The loss of the secondary path following a previous failure of the primary path results in a reporting time classification of T4. 4) The simultaneous loss of the primary and secondary transmission paths results in a reporting time classification of T5. 5) Network availability classifications have been based on the limited availability data. At the time of the initial evaluation only a limited number of ASSURE STAR alarm transmission equipment were in service and these were subject to interruption due to engineering trials whilst the data was being recorded. The monitoring of network availability continues and the classification will be updated when available. When operating with both transmission paths functioning correctly the combined system availability will meet classification A3.

CSL DualCom Limited


Salamander Quay West, Park Lane, Harefield, Middlesex UB8 6NZ UK Tel: +44 (0)1895 474474 Fax: +44 (0)1895 474440 E-mail: sales@csldual.com Website: www.csldual.com
Certificate No: 723a to LPS 1277: Issue 2.2

January 2009

267

PART 3: SECTION 11.2


ALARM TRANSMISSION AND FAULT ROUTING EQUIPMENT AND SYSTEMS
Certificated Products CS 1400 DualCom Fire Alarm Transmission Equipment (Ancillaries CS 1050, CS1053) LPCB Ref. No. 723a/01

Note: Meets the requirements of LPS 1277 for Category B fire alarm transmission equipment. The DualCom Fire has two transmission paths, a primary path signalling over the Packet Data Radio Network operated by Vodafone Ltd., and a secondary path operating over the Public Switched Telephone Network

Alarm transmission system performance parameters Transmission Transmission time Transmission Reporting time Path classification time classification Max. values M3 1 <90s

Network availability

Primary Secondary

D4 D3

T3 2 T5

A4 A4

Notes: 1) Equivalent to M2 of EN 50136-1-1:1998 2) The simultaneous loss of the primary and secondary transmission paths results in a reporting time classification of T3 Approved with the following Ancillaries CS 1050 DualCom 8 Channel Expander CS 1053 DualCom High gain aerial

268

January 2009

SECTION 11.3: PART

SIGNALLING SYSTEMS

In previous editions of the Red Book this section listed alarm signalling systems approved to special requirements developed by LPCB, prior to the publication of LPS 1277 and EN-54-21. The approval of these products has now expired and has been replaced by approval of products to LPS 1277 and EN-54-21. Please refer to Part 3:Section 11.1 'Alarm Transmission and fault routing equipment' for a list of equipment approved to EN 54-21or Part 3:Section 11.2 'Alarm Transmission and fault routing equipment and systems' for a list of equipment approved to LPS 1277.

BT redcare
Monument TE, 11-13 Great Tower Street, London EC3R 5EA UK Tel: +44 (0) 800 800 828 Fax: +44 (0)20 7929 6490 Website: www.redcare.bt.com
Certificate No: 099a Certificated Products 3GSTU-12V 3GSTU-24V LPCB Ref. No. n/a n/a

Note to Specifiers In January 2008 Red Book entries for the BT Redcare 3GSTU-12V and 3GSTU-24V alarm transmission equipment were removed because the scheme against which these products were approved had been superseded by LPS 1277. LPCB assessment of the quality management system associated with production of the 3GSTU-12V and 3GSTU-24V has been maintained and both products, now referred to as 'Classic STU' and 'Fire STU', are currently being evaluated to LPS 1277. Red Book listing will be reinstated once compliance with the requirements of LPS 1277 has been successfully demonstrated.

January 2009

269