RC Ordering Information
Input Module
Isolation Photocoupler Indicator Yes No 4 to 32 VDC Logic level Supply voltage Supply current 25 mA 100 to 240 VAC 5 to 24 VDC 4 to 24 VDC G3TA-IAZR02S-US G3TA-IDZR02S-US G3TA-IDZR02SM-US Rated input voltage Model
Output Module
Isolation Phototriac Zero cross function Yes Indicator Yes Rated output load (applicable output load) 2 A at 100 to 240 VAC (2 A at 75 to 264 VAC) Rated input voltage 12 VDC 24 VDC No Photocoupler --2 A at 5 to 48 VDC (2 A at 4 to 60 VDC) 1 A at 48 to 200 VDC (1 A at 40 to 200 VDC) 12 VDC 24 VDC 12 VDC 24 VDC 12 VDC 24 VDC G3TA-OD201S-US G3TA-ODX02S-US G3TA-OA202SL-US Model G3TA-OA202SZ-US
I/O Indication
I/O module classification and AC/DC use are indicated on the mark affixed to the top of the product. Mark indication AC IN DC IN AC OUT DC OUT Specification Input module, AC input Input module, DC input Output module, AC output Output module, DC output
Mark attached to the top of product
180
G3TA
Specifications
Ratings
Input Module
Input Model Rated voltage Operating voltage Input current Voltage level Must operate voltage G3TA-IAZR02S-US G3TA-IDZR02S-US G3TA-IDZR02SM-US Output Model G3TA-IAZR02S-US G3TA-IDZR02S-US G3TA-IDZR02SM-US Logic level supply voltage 4 to 32 VDC Output breakdown voltage 32 VDC max. Output current 25 mA max. Output current (load current) 0.1 to 25 mA 100 to 240 VAC 5 to 24 VDC 4 to 24 VDC 80 to 264 VDC 4 to 32 VDC 3 to 32 VDC 5 mA max. 80 VAC max. 4 VDC max. 3 VDC max. Must release voltage 10 VAC min. 1 VDC min.
Output Module
Input Model Rated voltage Operating voltage Input pu impedance i d 0.9 k20% 1.7 k20% 0.9 k20% 1.7 k20% 3.5 k20% 6.5 k20% 3.6 k20% 6.4 k20% Voltage level Must operate voltage 9.6 VDC max. 19.2 VDC max. 9.6 VDC max. 19.2 VDC max. 9.6 VDC max. 19.2 VDC max. 9.6 VDC max. 19.2 VDC max. Must release voltage 2 VDC min.
9.6 to 13.2 VDC 19.2 to 26.4 VDC 9.6 to 13.2 VDC 19.2 to 26.4 VDC 9.6 to 13.2 VDC 19.2 to 26.4 VDC 9.6 to 13.2 VDC 19.2 to 26.4 VDC
181
G3TA
Output Model Rated load voltage G3TA-OA202SZ-US G3TA-OA202SL-US G3TA-ODX02S-US G3TA-OD201S-US Note: 100 to 240 VAC 100 to 240 VAC 5 to 48 VDC 48 to 200 VDC 75 to 264 VAC 75 to 264 VAC 4 to 60 VDC 40 to 200 VDC 0.01 to 2 A 0.01 to 1 A 12 A (10 ms) 6 A (10 ms) Applicable load Load voltage Load current (see note) 0.05 to 2 A
G3TA
Characteristics
Input Module
Item Operate time Release time Output ON voltage drop Leakage current Insulation resistance Dielectric strength Vibration resistance Shock resistance Ambient temperature Ambient humidity Approved standards Weight G3TA-IAZR02S-US 20 ms max. 20 ms max. 1.6 V max. 5 A max. 100 M min. (at 500 VDC) 4,000 VAC, 50/60 Hz for 1 min between input and output Malfunction: 10 to 55 Hz, 1.5-mm double amplitude Malfunction: 1,000 m/s2 Operating: 30C to 80C (with no icing or condensation) Storage: 30C to 100C (with no icing or condensation) Operating: 45% to 85% UL508 file No. E64562/CSA C22.2 (No. 0, No. 14) file No. LR35535 Approx. 16 g G3TA-IDZR02S-US 0.5 ms max. 0.5 ms max. G3TA-IDZR02SM-US
Output Module
Item Operate time Release time Output ON voltage drop Leakage current Insulation resistance Dielectric strength Vibration resistance Shock resistance Ambient temperature Ambient humidity Approved standards Weight G3TA-OA202SZ-US 1/2 of load power source cycle + 1 ms max. 1.6 V max. 5 mA max. (at 200 VAC) 100 M min. (at 500 VDC) 4,000 VAC, 50/60 Hz for 1 min between input and output Malfunction: 10 to 55 Hz, 1.5-mm double amplitude Malfunction: 1,000 m/s2 Operating: 30C to 80C (with no icing or condensation) Storage: 30C to 100C (with no icing or condensation) Operating: 45% to 85% UL508 file No. E64562, CSA C22.2 (No. 14) file No. LR3553 Approx. 23 g With up to four G3TA SSRs mounted before G7T Relays, switching is possible at the rated load current for each Relay. With G3TA SSRs mounted before every other G7T Relays, switching is possible at the rated load current for each Relay. 1 mA max. G3TA-OA202SL-US 1 ms max. G3TA-ODX02S-US 0.5 ms max. 2 ms max. G3TA-OD201S-US 2 ms max. 2 ms max. 2.5 V max.
G3TA
G7T
G3TA
G7T
182
G3TA
G3TA
Engineering Data
Load Current vs. Ambient Temperature Characteristics
G3TA-OA202SZ/OA202SL/ODX02S-US G3TA-OD201S-US
Single-point mounting
16-point mounting
Operation
Circuit Configuration
Type AC output Model G3TA-OA202SZ (with zero cross function) G3TA-OA202SL (without zero cross function) G3TA-ODX02S G3TA-OD201S G3TA-IAZR02S Case color Black Indicator Yes
Constant-current circuit Zero cross circuit Drive circuit
Circuit
DC output
Black
Yes
Constant-current circuit Amplification circuit
AC input
Red
Yes
Rectification circuit Constant-current circuit Amplification circuit
DC input
G3TA-IDZR02S G3TA-IDZR02SM
Green
Yes No
Constant-current circuit Amplification circuit
183
G3TA
G3TA-IDZR02S/IDZR02SM
Output
+ 3
5 1
+ 3
5 1
G3TA-OA
Load power supply
G3TA-OD
Load power supply
Load 3 4 + 1 5
Load + 3 4 + 1 5
Dimensions
Note: All units are in millimeters unless otherwise indicated.
10 max.
31.7 39 max. 24
7.1 7.5
85
M3.5
35.3 0
+0.2
26
34
10
21 32.5
184
G3TA
For Output (NPN, + Common) P7TF-OS16
G3TA
182
68
85
M3.5
35.3 0
+0.2
10
21 32.5
102
68
85
M3.5
35.3 0
+0.2
10
21 32.5
P7TF-O5
19 max. Five, M3.5 x 8 Square washer faced screw
71.5 max
59 max.
185
G3TA
G3TA
Precautions
Refer to pages 11 to 19 for general precautions.
Connection
With the SSR for DC switching, the load can be connected to either positive or negative output terminal of the SSR.
Protective Component
Since the SSR does not incorporate an overvoltage absorption component, be sure to connect an overvoltage absorption component when using the SSR under an inductive load.
186