FEEDER
BRANCH CIRCUIT BREAKER NF Available Ampacities: 125A, 250A, 400A, 600A, 800A NQOD Available Ampacities: 100A, 225A, 400A, 600A
Alternatively, the upstream panelboard may be an I-Line section incorporated into a QED-2 switchboard.
Listing Of Tables
Downstream Panelboard Type 208Y/120V 0.1 - 1000s NF NQOD Table IIA Table IIIA 0.01 - 1000s Table IIB Table IIIB 0.1 - 1000s Table IA N/A Upstream Panelboard Type: I-Line 480Y/277V 0.01 - 1000s Table IB N/A
To find the table which applies to your application: Select a downstream panelboard type in the left-hand column. Read across the row to find the table which is listed under the appropriate voltage level and selectivity specification. For example, if the downstream panelboard is an NF panelboard, the appropriate table for selectivity from 0.01 1000s at 480Y/277V is Table IB.
Assumptions
All thermal-magnetic circuit breakers with adjustable instantaneous trip settings are assumed to have their instantaneous settings at maximum Electronic-trip circuit breakers are assumed to have the smallest sensor/rating plug size which meets or exceeds the ampacity requirements of the given circuit. The long-time trip/delay must be set to the appropriate level to give the breaker trip setting shown. The instantaneous function is assumed to be turned off, if possible for the breakers under consideration, or otherwise set to maximum. Electronic-trip circuit breakers are assumed to have a short-time function and the short-time pickup and delay settings are assumed to be set at maximum All circuit breakers are shown with their maximum available ampacity ranges. For most circuit breakers, these apply for 2- or 3-pole configurations, although this is not always the case. The availability of a given circuit breaker ampacity for a given model and configuration must be double-checked
6. If results do not yield a branch circuit breaker size which is large enough, repeat steps 4 and 5 using a different Upstream Panelboard Feeder Circuit Breaker Type 7. If results do not yield a branch circuit breaker size which is large enough (or an acceptable level of fault current at the downstream panelboard), a larger feeder will be required. Go to the next larger Feeder Size/Upstream Panelboard Circuit Breaker Size and repeat steps 1 through 6 8. Repeat steps 1 through 7 until the desired branch circuit breaker size is obtained
Table IA
I-Line/NF Panelboard Selective Coordination At 480Y/277V 0.1s 1000s
FEEDER SIZE / UPSTREAM (I-LINE) PANELBOARD CIRCUIT BREAKER SIZE (A) REQUIRED DOWNSTREAM (NF) PANELBOARD AMPACITY (A) MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 18 25 100 125 35 65 110 125 18 35 65 18 30 35 65 UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE FA, HD, LX PG FH HG LX PG HJ, LX PJ HD HG HJ HD, LA, LX PG LA HG, LH, LX PG HJ, LX PJ HD JD, LA LX PG LA HG JG, LH LX PG HJ JJ LX PJ JD, LA LX, PG LA JG, LH LX, PG JJ LX, PJ JD, LA, LX, PG LA-MC LA LA-MC JG, LH, LX PG LH-MC JJ, LX PJ JD, LA, LX PG LA-MC LA LA-MC JG, LH, LX PG LH-MC JJ, LX PJ JD, LA LA-MC LX, PG LA LA-MC JG, LH LH-MC LX, PG JJ LX, PJ DOWNSTREAM (NF) PANELBOARD BRANCH CIRCUIT BREAKER TYPE ED ED EG EG EG EG EJ EJ ED EG EJ ED ED EG EG EG EJ EJ ED ED ED ED EG EG EG EG EG EJ EJ EJ EJ ED ED EG EG EG EJ EJ ED ED ED EG EG EG EG EG EJ EJ ED ED ED EG EG EG EG EG EJ EJ ED ED ED EG EG EG EG EG EJ EJ LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 30 50 30 30 30 50 30 50 30 30 30 30 50 30 30 50 30 50 30 35 40 70 35 30 35 40 70 30 35 40 70 40 70 40 40 70 40 70 70 80 125 70 125 70 80 125 70 80 70 110 125 70 125 70 110 125 70 110 70 125 125 70 125 70 125 125 70 125
125
125
18 30 150 250 35
65 18 30 35 65 18 30 35 65 18 30 225 250 35 65 18 30 35 65
175
250
200
250
250
250
FEEDER SIZE / UPSTREAM (I-LINE) PANELBOARD CIRCUIT BREAKER SIZE (A) 300
MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 18 30 35 65 18 30 35 65 18 30 35 65 18 35 65 18 35 65 18 35 65 18 35 65 18 35 65
UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE LA, MG, LX, PG3 LA LH, MG, LX, PG3 LC, MJ, LX, PJ3 LA, MG, LX LA LH, MG, LX LC, MJ, LX LA, LA-MC, MG, LX, PG LA, LA-MC LH, LH-MC, MG, LX, PG LC, MJ, LX, PJ LC, MG, LX, PG3 LC, MG, LX, PG3 LC, MJ, LX, PJ3 LC, MG, LX, PG3 LC, MG, LX, PG3 LC, MJ, LX, PJ3 LC, MG, LX, PG (ET1.0)2, PG2 LC, MG, LX, PG (ET1.0)2, PG2 LC, MJ, LX, PJ (ET1.0)2, PJ2 MG, PG2,3 MG, PG2,3 MJ, PJ2,3 MG, PG (ET1.0)2, PG2 MG, PG (ET1.0)2, PG2 MJ, PJ (ET1.0)2, PJ2
LARGEST POSSIBLE BRANCH CIRCUIT BREAKER 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
350
400
400
400
450
600
500
600
600
600
700
800
800
800
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory note below for additional information 2 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range PG (ET1.0) = ET1.0 trip unit PG = Micrologic 5.0/6.0 trip unit 3 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45, 800A: 1000A w/LTPU=0.625, 700A: 1000A w/LTPU= 0.7)
X/R Ratio Adjustment: All available fault currents are given in RMS symmetrical amperes. For a system X/R ratio larger than the test X/R ratio of the circuit breaker in question, the available fault current equivalent RMS symmetrical duty for comparison with the values in the tables must be adjusted by a multiplying factor. See IEEE Std. 242-2001 (Buff Book), IEEE Std. 1015-1997 (Blue Book) or NEMA AB 3-2001 for details.
Molded Case Circuit Breaker Interrupting Rating Greater than 20kA 10kA - 20kA Less than 10kA Test X/R 4.9 3.2 1.7
Note that this is a consideration for breaker fault duty rather than for selective coordination.
Table IB
I-Line/NF Panelboard Selective Coordination At 480Y/277V 0.01s 1000s
FEEDER SIZE / UPSTREAM (I-LINE) PANELBOARD CIRCUIT BREAKER SIZE (A) 100 REQUIRED DOWNSTREAM (NF) PANELBOARD AMPACITY (A) 125 MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 18 35 65 18 35 65 18 35 65 18 35 65 18 UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE PG PG PJ PG PG PJ PG PG PJ PG PG PJ PG LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC PG LH-MC LH-MC LH-MC PJ PG LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC PG LH-MC LH-MC LH-MC LH-MC PJ LA-MC LA-MC LA-MC PG LA-MC LA-MC LA-MC LH-MC LH-MC LH-MC PG PJ PG4 PG4 PJ4 LA-MC LA-MC PG LA-MC LA-MC LH-MC LH-MC PG PJ PG4 PG4 PJ4 PG4 PG4 PJ4 PG (ET1.0)2, PG2 DOWNSTREAM (NF) PANELBOARD BRANCH CIRCUIT BREAKER TYPE ED EG EJ ED EG EJ ED EG EJ ED EG EJ ED ED ED ED EG EG EG EG EG EG EG EJ ED ED ED ED ED EG EG EG EG EG EG EG EG EG EJ ED ED ED ED EG EG EG EG EG EG EG EJ ED EG EJ ED ED ED EG EG EG EG EG EJ ED EG EJ ED EG EJ ED MAXIMUM AVAILABLE FAULT CURRENT AT DOWNSTREAM (NF) PANELBOARD (kA RMS Sym.)1,3 18 35 65 18 35 65 18 35 65 18 35 65 18 18 10 6 18 10 6 35 18 10 6 65 18 18 14 8 7 18 14 8 7 35 18 14 8 7 65 18 10 8 18 18 10 8 18 10 8 35 65 18 35 65 18 6 18 18 6 18 6 35 65 18 21.6 9 18 21.6 9 18
LARGEST POSSIBLE BRANCH CIRCUIT BREAKER 50 50 50 50 50 50 70 70 70 70 70 70 80 15 20 100 15 20 100 80 15 20 100 80 110 15 20 30 100 15 20 30 100 110 15 20 30 100 110 30 40 100 125 30 40 100 30 40 100 125 125 125 125 125 100 125 125 100 125 100 125 125 125 125 125 125 125 125 125 125
125
125
150
250
175
250
200
250
30
35
65
18
225
250
30
35
65 18
250
250
30
35
300
300
65 18 35 65 18
400
400
30
35 65 18 35 65 18 35 65 18
450
600
500 600
600 600
MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 35 65 18 35 65 18 35 65
UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE PG (ET1.0)2, PG2 PJ (ET1.0)2, PJ2 PG2,4 PG2,4 PJ2,4 PG (ET1.0)2, PG2 PG (ET1.0)2, PG2 PJ (ET1.0)2, PJ2
MAXIMUM AVAILABLE FAULT CURRENT AT DOWNSTREAM (NF) PANELBOARD (kA RMS Sym.)1,3 35 65 18 21.6 9 18 21.6 9
LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 125 125 125 125 125 125 125 125
700
800
800
800
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory note below for additional information 2 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range PG (ET1.0) = ET1.0 trip unit PG = Micrologic 5.0/6.0 trip unit 3 Values in red are taken from data bulletin 0100DB0501; all other values in this column generated via TCC comparison 4 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45, 800A: 1000A w/LTPU=0.625, 700A: 1000A w/LTPU= 0.7)
X/R Ratio Adjustment: All available fault currents are given in RMS symmetrical amperes. For a system X/R ratio larger than the test X/R ratio of the circuit breaker in question, the available fault current equivalent RMS symmetrical duty for comparison with the values in the tables must be adjusted by a multiplying factor. See IEEE Std. 242-2001 (Buff Book), IEEE Std. 1015-1997 (Blue Book) or NEMA AB 3-2001 for details.
Molded Case Circuit Breaker Interrupting Rating Greater than 20kA 10kA - 20kA Less than 10kA Test X/R 4.9 3.2 1.7
Note that this is a consideration for breaker fault duty rather than for selective coordination.
Table IIA
I-Line/NF Panelboard Selective Coordination At 208Y/120V 0.1s 1000s
FEEDER SIZE / UPSTREAM (I-LINE) PANELBOARD CIRCUIT BREAKER SIZE (A) REQUIRED DOWNSTREAM (NF) PANELBOARD AMPACITY (A) MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 25 100 125 65 100 25 65 100 25 42 65 100 UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE FA2, HD, LX PG FH, HG, LX PG HJ, LX PJ HD HG HJ HD, LA, LX PG LA HG, LH, LX PG HJ, LX PJ HD JD, LA LX PG LA HG JG, LH LX PG HJ JJ LX PJ JD, LA LX, PG LA JG, LH LX, PG JJ LX, PJ JD, LA, LX, PG LA-MC LA LA-MC JG, LH, LX PG LH-MC JJ, LX PJ JD, LA, LX PG LA-MC LA LA-MC JG, LH, LX PG LH-MC JJ, LX PJ JD, LA LA-MC LX, PG LA LA-MC JG, LH LH-MC LX, PG JJ LX, PJ LA, MG, LX, PG5 LA LH, MG, LX, PG5 LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 30 50 30 50 30 50 30 30 30 30 50 30 30 50 30 50 30 35 40 70 35 30 35 40 70 30 35 40 70 40 70 40 40 70 40 70 70 80 125 70 125 70 80 125 70 80 70 110 125 70 125 70 110 125 70 110 70 125 125 70 125 70 125 125 70 125 125 125 125
DOWNSTREAM (NF) PANELBOARD BRANCH CIRCUIT BREAKER TYPE ED ED EG3 EG3 EJ3 EJ3 ED EG3 EJ3 ED ED EG3 EG3 EG3 EJ3 EJ3 ED ED ED ED EG3 EG3 EG3 EG3 EG3 EJ3 EJ3 EJ3 EJ3 ED ED EG3 EG3 EG3 EJ3 EJ3 ED ED ED EG3 EG3 EG3 EG3 EG3 EJ3 EJ3 ED ED ED EG3 EG3 EG3 EG3 EG3 EJ3 EJ3 ED ED ED EG3 EG3 EG3 EG3 EG3 EJ3 EJ3 ED EG3 EG3
110
125
125
125
25
42 150 250 65
100
25 42 65 100
175
250
300
400
MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 100 25 42 65 100 25 42 65 100 25 65 100 25 65 100 25 65 100 25 65 100 25 65 100
UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE LC, MJ, LX, PJ5 LA, MG, LX LA LH, MG, LX LC, MJ, LX LA, LA-MC, MG, LX, PG LA, LA-MC LH, LH-MC, MG, LX, PG LC, MJ, LX, PJ LC, MG, LX, PG5 LC, MG, LX, PG5 LC, MJ, LX, PJ5 LC, MG, LX, PG5 LC, MG, LX, PG5 LC, MJ, LX, PJ5 LC, MG, LX, PG (ET1.0)4, PG4 LC, MG, LX, PG (ET1.0)4, PG4 LC, MJ, LX, PJ (ET1.0)4, PJ4 MG, PG4,5 MG, PG4,5 MJ, PJ4,5 MG, PG (ET1.0)4, PG4 MG, PG (ET1.0)4, PG4 MJ, PJ (ET1.0)4, PJ4
DOWNSTREAM (NF) PANELBOARD BRANCH CIRCUIT BREAKER TYPE EJ3 ED EG3 EG3 EJ3 ED EG3 EG3 EJ3 ED EG3 EJ3 ED EG3 EJ3 ED EG
3 3
LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
350
400
400
400
450
600
500
600
600
600
700
800
800
800
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory note below for additional information 2 480V-rated 3 2 Pole or 3 Pole 15 125A only. 1 Pole is available from 15 70A and has an AIR of 35kA for EG, 65kA for EJ 4 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range PG (ET1.0) = ET1.0 trip unit PG = Micrologic 5.0/6.0 trip unit 5 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45, 800A: 1000A w/LTPU=0.625, 700A: 1000A w/LTPU= 0.7)
X/R Ratio Adjustment: All available fault currents are given in RMS symmetrical amperes. For a system X/R ratio larger than the test X/R ratio of the circuit breaker in question, the available fault current equivalent RMS symmetrical duty for comparison with the values in the tables must be adjusted by a multiplying factor. See IEEE Std. 242-2001 (Buff Book), IEEE Std. 1015-1997 (Blue Book) or NEMA AB 3-2001 for details.
Molded Case Circuit Breaker Interrupting Rating Greater than 20kA 10kA - 20kA Less than 10kA Test X/R 4.9 3.2 1.7
Note that this is a consideration for breaker fault duty rather than for selective coordination.
TABLE IIB
I-Line/NF Panelboard Selective Coordination At 208Y/120V 0.01s 1000s
FEEDER SIZE / UPSTREAM (I-LINE) PANELBOARD CIRCUIT BREAKER SIZE (A) 100 REQUIRED DOWNSTREAM (NF) PANELBOARD AMPACITY (A) 125 MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 25 65 100 25 65 100 25 65 100 25 65 100 25 UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE PG PG PJ PG PG PJ PG PG PJ PG PG PJ PG LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC PG LH-MC LH-MC LH-MC PJ PG LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC PG LH-MC LH-MC LH-MC LH-MC PJ LA-MC LA-MC LA-MC PG LA-MC LA-MC LA-MC LH-MC LH-MC LH-MC PG PJ PG6 PG6 PJ6 LA-MC LA-MC PG LA-MC LA-MC LH-MC LH-MC PG PJ PG6 PG6 PJ6 PG6 PG6 PJ6 PG (ET1.0)4, PG4 MAXIMUM AVAILABLE FAULT CURRENT AT DOWNSTREAM (NF) PANELBOARD (kA RMS Sym.)1,5 21.6 65 100 21.6 65 100 21.6 65 100 21.6 65 100 21.6 18 10 6 18 10 6 65 18 10 6 100 21.6 18 14 8 7 18 14 8 7 65 18 14 8 7 100 18 10 8 21.6 18 10 8 18 10 8 65 100 21.6 65 100 18 6 21.6 18 6 18 6 65 100 21.6 21.6 9 21.6 65 100 21.6 LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 50 50 50 50 50 50 70 70 70 70 70 70 80 15 20 100 15 20 100 80 15 20 100 80 110 15 20 30 100 15 20 30 100 110 15 20 30 100 110 30 40 100 125 30 40 100 30 40 100 125 125 125 125 125 100 125 125 100 125 100 125 125 125 125 125 125 125 125 125 125
DOWNSTREAM (NF) PANELBOARD BRANCH CIRCUIT BREAKER TYPE ED EG3 EJ3 ED EG3 EJ3 ED EG3 EJ3 ED EG3 EJ3 ED ED ED ED EG3 EG3 EG3 EG3 EG3 EG3 EG3 EJ3 ED ED ED ED ED EG3 EG3 EG3 EG3 EG3 EG3 EG3 EG3 EG3 EJ3 ED ED ED ED EG3 EG3 EG3 EG3 EG3 EG3 EG3 EJ3 ED EG3 EJ3 ED ED ED EG3 EG3 EG3 EG3 EG3 EJ3 ED EG3 EJ3 ED EG3 EJ3 ED
125
125
150
250
175
250
200
250
42
65
100
25
42 225 250
65
100 25
250
250
42
65
300
300
100 25 65 100 25 42
400
450
600
500 600
600 600
10
MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 65 100 25 65 100
UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE PG (ET1.0)4, PG4 PJ (ET1.0)4, PJ4 PG4 6 PG4,6 MG PJ4,6 MJ PG (ET1.0)4, PG4 MG, PG (ET1.0)4, PG4 MJ, PJ (ET1.0)4, PJ4
DOWNSTREAM (NF) PANELBOARD BRANCH CIRCUIT BREAKER TYPE EG3 EJ3 ED EG3 EG3 EJ3 EJ3 ED EG3 EJ3
MAXIMUM AVAILABLE FAULT CURRENT AT DOWNSTREAM (NF) PANELBOARD (kA RMS Sym.)1,5 65 100 21.6 21.6 65 9 100 21.6 65 100
LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 125 125 125 125 125 125 125 125 125 125
700
800
800
800
25 65 100
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory notes below for additional information 2 480V-rated 3 2 Pole or 3 Pole 15 125A only. 1 Pole is available from 15 70A and has an AIR of 35kA for EG, 65kA for EJ 4 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range PG (ET1.0) = ET1.0 trip unit PG = Micrologic 5.0/6.0 trip unit 5 Values in red are taken from data bulletin 0100DB0501; all other values in this column generated via TCC comparison 6 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45, 800A: 1000A w/LTPU=0.625, 700A: 1000A w/LTPU= 0.7)
X/R Ratio Adjustment: All available fault currents are given in RMS symmetrical amperes. For a system X/R ratio larger than the test X/R ratio of the circuit breaker in question, the available fault current equivalent RMS symmetrical duty for comparison with the values in the tables must be adjusted by a multiplying factor. See IEEE Std. 242-2001 (Buff Book), IEEE Std. 1015-1997 (Blue Book) or NEMA AB 3-2001 for details.
Molded Case Circuit Breaker Interrupting Rating Greater than 20kA 10kA - 20kA Less than 10kA Test X/R 4.9 3.2 1.7
Note that this is a consideration for breaker fault duty rather than for selective coordination.
11
TABLE IIIA
I-Line/NQOD Panelboard Selective Coordination At 208Y/120V 0.1s 1000s
FEEDER SIZE / UPSTREAM (I-LINE) PANELBOARD CIRCUIT BREAKER SIZE (A) REQUIRED DOWNSTREAM (NF) PANELBOARD AMPACITY (A) MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 10 100 100 22 UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE HD FA, LX PG HD FA2, LX PG HG FH, LX PG HD HD HG HD, LA LX PG HD, LA LX PG LA HG, LH LX, PG HD JD, LA, LX, PG HD JD, LA LX PG LA HG JG, LH, LX, PG JD, LA, LX, PG JD, LA LX PG LA JG, LH, LX, PG JD, LA, LX LA-MC, PG JD, LA, LX, PG LA-MC LA, LA-MC JG, LH, LH-MC, LX, PG JD, LA, LX, PG LA-MC JD, LA LX PG LA-MC LA, LA-MC JG, LH, LH-MC, LX, PG JD, LA, LX, PG LA-MC JD, LA LX PG LA-MC LA, LA-MC JG, LH, LH-MC, LX, PG LA, MG, LX PG5 LA MG, LX PG5 LA LH, MG, LX, PG5 LA DOWNSTREAM (NF) PANELBOARD BRANCH CIRCUIT BREAKER TYPE QO QO QO QO-VH QO-VH QO-VH QH QH QH QO QO-VH QH QO QO QO QO-VH QO-VH QO-VH QH QH QH QO QO QO-VH QO-VH QO-VH QO-VH QH QH QH QO QO-VH QO-VH QO-VH QH QH QO QO QO QO-VH QO-VH QO-VH QH QH QO QO QO-VH QO-VH QO-VH QO-VH QH QH QO QO QO-VH QO-VH QO-VH QO-VH QH QH QO QO QO-VH QO-VH QO-VH QH QH QO LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 20 25 40 20 25 403 20 25 30 25 25 25 25 40 70 25 30 603 25 25 30 25 70 25 30 403 703 30 25 30 70 403 503 703 30 30 70 806 1006 503 803 1003 30 30 1006 1257 503 603 803 1253 30 30 1006 1257 603 803 1103 1503 30 30 1006 1257 903 1003 1253 30 30 1006
65 10 22 65 10
110
225
125
225
22 42 65 10
150
225
22
225
225
22
42 65 10
250
400
22
42 65 10
300
400
22 42 65 10
350
400
12
FEEDER SIZE / UPSTREAM (I-LINE) PANELBOARD CIRCUIT BREAKER SIZE (A) 350
MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 22 42 65 10 22 42 65 10 22 65 10 22 65 10 22 65
UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE MG, LX LA, MG, LX LA LH, MG, LX LA, LA-MC, MG, LX, PG LA, LA-MC, MG, LX, PG LA, LA-MC LH, LH-MC, MG, LX, PG LC, MG, LX, PG5 LC, MG, LX, PG5 LC, MG, LX, PG5 LC, MG, LX, PG5 LC, MG, LX, PG5 LC, MG, LX, PG5 LC, MG, LX, PG (ET1.0)4, PG4 LC, MG, LX, PG (ET1.0)4, PG4 LC, MG, LX, PG (ET1.0)4, PG4
DOWNSTREAM (NQOD) PANELBOARD BRANCH CIRCUIT BREAKER TYPE QO QO-VH QH QH QO QO-VH QH QH QO QO-VH QH QO QO-VH QH QO QO-VH QH
LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 1257 1503 30 30 1257 1503 30 30 1257 1503 30 1257 1503 30 1257 1503 30
400
400
450
600
500
600
600
600
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory note below for additional information 2 480V-rated 3 2 Pole or 3 Pole only. QO-VH 1 Pole is available up to 30A (and coordinates up to 30A) 4 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range PG (ET1.0) = ET1.0 trip unit PG = Micrologic 5.0/6.0 trip unit 5 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45, 800A: 1000A w/LTPU=0.625) 6 2 Pole or 3 Pole only. QO 1 Pole is available up to 70A (and coordinates up to 70A) 7 2p only. QO 1P is available up to 70A (and coordinates up to 70A), QO 3 Pole is available up to 100A (and coordinates up to 100A)
X/R Ratio Adjustment: All available fault currents are given in RMS symmetrical amperes. For a system X/R ratio larger than the test X/R ratio of the circuit breaker in question, the available fault current equivalent RMS symmetrical duty for comparison with the values in the tables must be adjusted by a multiplying factor. See IEEE Std. 242-2001 (Buff Book), IEEE Std. 1015-1997 (Blue Book) or NEMA AB 3-2001 for details.
Molded Case Circuit Breaker Interrupting Rating Greater than 20kA 10kA - 20kA Less than 10kA
Note that this is a consideration for breaker fault duty rather than for selective coordination.
13
Table IIIB
I-Line/NQOD Panelboard Selective Coordination At 208Y/120V 0.01s 1000s
FEEDER SIZE / REQUIRED UPSTREAM (I-LINE) DOWNSTREAM (NQOD) PANELBOARD CIRCUIT PANELBOARD AMPACITY BREAKER SIZE (A) (A) MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1 10 UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE HD PG HD PG PJ HG FH PG HD HD HG HD PG HD LA PG PJ HG LH PG HD JD PG HD JD LA PG PJ HG JG LH PG JD PG JD LA PG PJ JG LH PG JD LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC PG JD LA PG PJ LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC JG LH LH-MC PG JD DOWNSTREAM (NQOD) PANELBOARD BRANCH CIRCUIT BREAKER TYPE QO QO QO-VH QO-VH QO-VH QH QH QH QO QO-VH QH QO QO QO-VH QO-VH QO-VH QO-VH QH QH QH QO QO QO QO-VH QO-VH QO-VH QO-VH QO-VH QH QH QH QH QO QO QO-VH QO-VH QO-VH QO-VH QH QH QH QO QO QO QO QO QO QO QO QO QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QH QH QH QH QH QO MAXIMUM AVAILABLE FAULT CURRENT AT DOWNSTREAM (NQOD) PANELBOARD1.8 1.3 10 1.3 21.6 22 1.3 0.9 65 1.3 1.3 1.3 1.3 10 1.3 3.2 (2P ONLY) 21.6 22 1.3 65 (1P), 3.2 (2P, 3P) 65 1.3 2.3 10 1.3 2.3 3.2 (2P ONLY) 21.6 22 1.3 2.4 65 (1P), 3.2 (2P, 3P) 65 2.3 10 2.3 3.2 (2P ONLY) 21.6 22 2.4 65 (1P), 3.2 (2P, 3P) 65 2.3 18 (1P, 2P), 16 (3P) 18 (1P, 2P), 10 (3P) 7 (1P), 10 (2P), 6.5 (3P) 7 (1P, 2P), 6 (3P) 6 (1P, 2P), 5.5 (3P) 5 (1P, 3P), 6 (2P) 5 10 2.3 3.2 (2P ONLY) 21.6 22 22 (1P, 2P), 16 (3P) 22 (1P, 2P), 10 (3P) 7 (1P), 10 (2P), 6.5 (3P) 7 (2P), 6 (3P) 6 (2P), 5.5 (3P) 6 (2P), 5 (3P) 5 3.4 2.4 65 (1P), 3.2 (2P, 3P) 3.4 65 2.3 LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 20 40 20 403 403 20 25 30 25 25 25 25 70 25 25 603 603 25 25 30 25 70 70 25 30 30 703 703 25 30 30 30 70 70 403 403 703 703 30 30 30 70 15 20 30 40 50 70 1006 1006 503 503 803 803 15 20 30 403 503 703 1003 30 30 30 30 30 1006
100
100
22
65 10 22 65 10
110
225
125
225
22
65
10
150
225
22
65
10
22 175 225
65
10
200
225
22
42 65
225
225
10
14
FEEDER SIZE / REQUIRED UPSTREAM (I-LINE) DOWNSTREAM (NQOD) PANELBOARD CIRCUIT PANELBOARD AMPACITY BREAKER SIZE (A) (A)
MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1
UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE PG LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC JD LA PG PJ LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC JG LH LH-MC PG JD PG LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC JD LA PG PJ LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC LA-MC JG LH LH-MC PG PG5 LA MG PG5 LH MG PG5 LA MG LH MG LA-MC LA-MC LA-MC PG
DOWNSTREAM (NQOD) PANELBOARD BRANCH CIRCUIT BREAKER TYPE QO QO QO QO QO QO QO QO QO QO QO QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QH QH QH QH QH QO QO QO QO QO QO QO QO QO QO QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QH QH QH QH QH QO QO-VH QO-VH QO-VH QH QH QH QO-VH QO-VH QH QH QO QO QO QO
MAXIMUM AVAILABLE FAULT CURRENT AT DOWNSTREAM (NQOD) 1,8 PANELBOARD 10 18 18 (1P, 2P), 16 (3P) 11 (1P), 18 (2P), 8 (3P) 10 (1P, 2P), 7.5 (3P) 10 (1P, 2P), 7 (3P) 8 (1P), 10 (2P), 6.5 (3P) 7 (1P), 10 (2P), 6 (3P) 8 (2P), 6 (3P) 6 3.825 2.3 3.2 (2P ONLY) 21.6 22 22 (1P, 2P), 18 (3P) 22 (1P, 2P), 16 (3P) 11 (1P), 22 (2P), 8 (3P) 18 (2P), 7.5 (3P) 18 (2P), 7 (3P) 13 (2P), 6.5 (3P) 10 (2P), 6 (3P) 8 (2P), 6 (3P) 6 3.825 3.825 2.4 65 (1P), 3.2 (2P, 3P) 3.825 65 2.3 10 18 18 (1P, 2P), 14 (3P) 10 10 (1P, 2P), 9 (3P) 10 (1P, 2P), 8 (3P) 10 (1P, 2P), 7.5 (3P) 10 (2P), 7.5 (3P) 4.25 2.3 3.2 (2P ONLY) 21.6 22 22 (1P, 2P), 18 (3P) 22 (1P, 2P), 14 (3P) 18 (2P), 10 (3P) 18 (2P), 9 (3P) 13 (2P), 8 (3P) 11 (2P), 7.5 (3P) 10 (2P), 7.5 (3P) 4.25 4.25 2.4 65 (1P), 3.2 (2P, 3P) 4.25 65 10 3.2 (2P ONLY) 3.6 (3P ONLY) 21.6 65 (1P), 3.2 (2P, 3P) 65 (1P), 3.6 (2P, 3P) 65 3.2 (2P ONLY) 3.6 (3P ONLY) 65 (1P), 3.2 (2P, 3P) 65 (1P), 3.6 (2P, 3P) 18 10 6 10
LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 1006 15 20 30 40 50 60 70 806 1006 1257 503 503 803 803 15 20 30 403 503 603 703 803 1003 1253 30 30 30 30 30 1006 1006 20 30 40 50 60 70 1006 1257 603 603 1103 1103 20 30 403 503 603 803 1003 1503 30 30 30 30 30 1257 903 1003 1253 30 30 30 1503 1503 30 30 30 1006 1257 1257
10
225
225
22
42 65
10
250
400
22
42 65
400
400
10
15
FEEDER SIZE / REQUIRED UPSTREAM (I-LINE) DOWNSTREAM (NQOD) PANELBOARD CIRCUIT PANELBOARD AMPACITY BREAKER SIZE (A) (A)
MAXIMUM AVAILABLE FAULT CURRENT AT UPSTREAM (I-LINE) PANELBOARD (kA RMS Sym.)1
UPSTREAM (I-LINE) PANELBOARD FEEDER CIRCUIT BREAKER TYPE LA LA-MC LA-MC LA-MC MG PG LA-MC LH LH-MC MG PG PG5 MG PG5 MG PG5 PG5 MG PG5 MG PG5 PG (ET1.0)4, PG4 MG PG (ET1.0)4, PG4 MG PG (ET1.0)4, PG4
MAXIMUM AVAILABLE FAULT CURRENT AT DOWNSTREAM (NQOD) PANELBOARD BRANCH DOWNSTREAM (NQOD) PANELBOARD CIRCUIT BREAKER TYPE (kA RMS Sym.)1,8 QO-VH QO-VH QO-VH QO-VH QO-VH QO-VH QH QH QH QH QH QO QO-VH QO-VH QH QH QO QO-VH QO-VH QH QH QO QO-VH QO-VH QH QH 3.2 (2P ONLY) 22 (1P, 2P), 18 (3P) 22 (2P), 18 (3P) 6 3.6 (3P ONLY) 21.6 6 65 (1P), 3.2 (2P, 3P) 6 65 (1P), 3.6 (2P, 3P) 65 10 3.6 (3P ONLY) 21.6 65 (1P), 3.6 (2P, 3P) 65 10 3.6 (3P ONLY) 21.6 65 (1P), 3.6 (2P, 3P) 65 10 5.4 (3P ONLY) 21.6 65 (1P), 5.4 (2P, 3P) 65
LARGEST POSSIBLE BRANCH CIRCUIT BREAKER (A) 1503 30 1003 1503 1503 1503 30 30 30 30 30 1257 1503 1503 30 30 1257 1503 1503 30 30 1257 1503 1503 30 30
22
400
400 42 65
1 Available fault currents are based upon system X/R ratios less than or equal to the circuit breaker test X/R ratio. See the explanatory note below for additional information 2 480V-rated 3 2 Pole or 3 Pole only. QO-VH 1 Pole is available up to 30A (and coordinates up to 30A) 4 The P-Frame Powerpact circuit breaker is available with ET1.0 or Micrologic 5.0/6.0 trip units in this size range PG (ET1.0) = ET1.0 trip unit PG = Micrologic 5.0/6.0 trip unit 5 Requires larger sensor size if standard rating plug is used (300A: 600A w/ LTPU=0.5, 450A: 1000A w/LTPU=0.45, 800A: 1000A w/LTPU=0.625) 6 2 Pole or 3 Pole only. QO 1 Pole is available up to 70A (and coordinates up to 70A) 7 2 Pole only. QO 1 Pole is available up to 70A (and coordinates up to 70A), QO 3 Pole is available up to 100A (and coordinates up to 100A) 8 Values in red are taken from data bulletin 0100DB0501; all other values in this column generated via TCC comparison
X/R Ratio Adjustment: All available fault currents are given in RMS symmetrical amperes. For a system X/R ratio larger than the test X/R ratio of the circuit breaker in question, the available fault current equivalent RMS symmetrical duty for comparison with the values in the tables must be adjusted by a multiplying factor. See IEEE Std. 242-2001 (Buff Book), IEEE Std. 1015-1997 (Blue Book) or NEMA AB 3-2001 for details.
Molded Case Circuit Breaker Interrupting Rating Greater than 20kA 10kA - 20kA Less than 10kA
Note that this is a consideration for breaker fault duty rather than for selective coordination.
16