Professional Documents
Culture Documents
Revised: 6 Sep 06
Afternoon Agenda
Supply and Distribution Systems. Exhaust Systems and Devices. Controls and Commissioning. Lighting.
Right-Sizing
In the past, mechanical plants have been sized for 100% of peak load at 99% climatic tolerance with an additional 20-50% "startup factor" and another 20-30% "safety factor." Those days are over!
Apply realistic diversity factors. "Right-sizing" a labs mechanical plant reduces first costs and operational energy costs. It can reduce energy waste by 10-50% compared to conventional design practices.
10
12
13
0%
20%
40%
60%
80%
100%
Percent Load
Data provided by York International Corporation for chillers running at 42 deg F CHWS and 65 deg F CWS.
kW/ton
MDL Plant
Best Practice
Difference
17
Efficiency (kW/ton)
Tons
Data provided by York International Corporation.
System Efficiencies Under Different Conditions 85F Condenser Water Water F 60 55 50 48 46 45 44 42 40 kW/Ton 0.70 0.75 0.81 0.83 0.85 0.86 0.88 0.90 0.92 Tons 128.9 118.5 108.3 104.5 100.7 98.8 96.8 93.2 89.7 75F Condenser Water kW/Ton 0.59 0.64 0.70 0.72 0.74 0.75 0.77 0.79 0.82 Tons 135.5 124.4 113.8 109.7 105.7 103.8 101.8 98.0 94.2
20
22
25
Standard
500 2.5 in. w.g. 1.00 in. w.g. Constant Volume, N/A
Good
400 1.5 in. w.g. 0.60 in. w.g. Flow Measurement Devices, 0.60 - 0.30 in. w.g. 0.30 in. w.g. 2.25 in. w.g. 0.7 w.g. full design flow through fan and stack only, VAV System with bypass 0.25 w.g. 6.2 w.g. 1.2
Better
300 0.75 in.w.g. 0.35 in. w.g. Pressure Differential Measurement and Control, 0.10 in. w.g. 0.05 in. w.g. 1.2 in. w.g. 0.75 w.g. averaging half the design flow, VAV System with multiple stacks 0.0 w.g. 3.2 w.g. 0.6
Zone Temperature Control Coils Total Supply and Return Ductwork Exhaust Stack CFM and
0.5 in. w.g. 4.0 in. w.g. 0.7 w.g. full design flow through entire exhaust system, Constant Volume 1.0 w.g. 9.7 w.g. 1.8
Source: J. Weale, P. Rumsey, D. Sartor, L. E. Lock, Laboratory Low-Pressure Drop Design, ASHRAE Journal, August 2002.
University of Leeds 20 September 2006 27
28
29
VAV systems for labs must control supply and exhaust air together.
30
VAV Advantages
VAV systems have other advantages:
Monitors and controls pressurization in laboratories for increased safety. Provides constant face velocity that improves fume hood safety. Adapts to adding or moving fume hoods during remodeling more readily than CV.
31
33
Selecting Fans
Use the most efficient fan for the application. Consider fan curves, especially for lowspeed operation. Refer to ASHRAE HVAC Systems and Equipment Chapter on Fans.
34
Economizer Cycles
Appreciate that a 100% outside air (O.A.) lab is always in economizer mode. Consider the use of economizers in all applications with non-lab spaces such as offices, meeting rooms or librariesapplications where cooling is required & outside air temperature is below space temperature. Specify enthalpy controls.
36
37
Energy Recovery
Energy Recovery
Factors that improve energy recovery economics include:
Colder climates (e.g. more than 3,000 heating degreedays) High exhaust rates Long service life High utility rates Low discount (or interest) rate
Consider impact of increase pressure drop due to energy recovery devices. Evaporative cooling in exhaust stream can increase cooling energy recovery without adding moisture to supply air.
University of Leeds 20 September 2006 39
Energy Recovery,
continued
Run-around systems
Simple piping loop connecting a coil in the exhaust plenum with a coil in the make-up air plenum or AHU. Supply and exhaust ducts do not need to be adjacent.
Heat pipes
Transfer energy using phase change of a fluid within a pipe. Requires adjacent supply and exhaust ducts. Bypass on supply side recommended to prevent unwanted recovery.
University of Leeds 20 September 2006 40
Energy Recovery,
continued
End of Session