FireShield Technical Reference Manual

P/N 3100353 Rev 3.0 12MAY03

DEVELOPED BY

Content
Phone: (941) 739-4200 Copyright 20022003 IMPORTANT INFORMATION Limitation of liability This product has been designed to meet the requirements of the standards listed in Compliance statement below. Installation in accordance with this manual, applicable codes, and the instructions of the Authority Having Jurisdiction is mandatory. The manufacturer shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of products beyond the cost of repair or replacement of any defective products. The manufacturer reserves the right to make product improvements and change product specifications at any time. While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, the manufacturer assumes no responsibility for errors or omissions. FCC warning This equipment can generate and radiate radio frequency energy. If this equipment is not installed in accordance with this manual, it may cause interference to radio communications. This equipment has been tested and found to comply within the limits for Class A digital devices pursuant to Subpart B of Part 15 of the FCC Rules. These rules are designed to provide reasonable protection against such interference when this equipment is operated in a commercial environment. Operation of this equipment is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference. Compliance statement FireShield, when properly installed, operates as a Local Protected Premises Fire Alarm System in accordance with the following standards: NFPA Standard 72, 1999 Edition NFPA 70 National Electrical Code Underwriters Laboratories Standard 864, 8th Edition Underwriters Laboratories of Canada Standard ULC S527-99 Canadian Electrical Code Part I Standard for Installation of Fire Alarm Systems ULC S524 Standard for the Inspection and Testing of Fire Alarm Systems ULC S536

Chapter 1

System overview and operation 1.1 System overview 1.1 Operations overview 1.1 Controls and indicators 1.1 Component descriptions 1.3 Operating the panel 1.4 FSDACT LCD messages 1.7 Installation 2.1 Installation checklist 2.1 Installing the cabinet 2.1 Installing the Remote System Indicator 2.2 Installing the Remote Zone Indicator 2.3 Installing the Remote Relay Module 2.5 Installing the Power Expander Transformer 2.7 Installing the FSDACT 2.8 Connecting an RPM module 2.10 Connecting a CTM module 2.11 Connecting an auxiliary power supply 2.12 Installing the terminal shield 2.12 Programming 3.1 Overview 3.1 Using the factory default settings 3.2 Using an FSDACT 3.2 Custom programming the panel 3.2 FSDACT programming 3.8 Maintenance 4.1 Preventive maintenance 4.1 Calculations A.1 Battery calculation worksheet A.1 Notification appliance voltage drop calculation A.3 Notification appliance circuit maximum wire length calculation A.4 Programming templates B.1 Panel programming worksheet B.1 FSDACT programming worksheet B.2 Jumper settings and wiring diagrams C.1 Panel specifications D.1 Default event codes E.1 Default Contact ID event codes E.1 Default (4/2) event codes E.2 Index Z.1 FireShield Fire Alarm Control Panel Operating Instructions 1

Chapter 2

Chapter 3

Chapter 4

Appendix A

Appendix B

Appendix C Appendix D Appendix E

FireShield also complies with Local Protective Signaling (type L) - manual (M), automatic (A), waterflow (WF), and sprinkler supervisory (SS) for: Coded (C) and non-coded signaling (NC) Remote Station (type RS) - with RPM or FSDACT Auxiliary (type A) - with CTM4.7 (this may include Local with Shunt type connection to Master Box - type LS) Central Station (Type CS) - with FSDACT

Chapter 1

If the optional FSDACT is installed, the panel: Sends a record of the event to the FSDACT LCD and to the history log Uses the FSDACT to transmit event messages to a monitoring station as programmed

System overview and operation


System overview
FireShield is available in three models: three-zone, five-zone, and ten-zone. Each model is similar except for the number of initiating device circuits (IDCs) and notification appliance circuits (NACs), as shown in the following table.
Model FS302 (three-zone) FS502 (five-zone) FS1004 (ten-zone) IDCs 3 5 10 NACs 2 2 4

Controls and indicators


REMOTE DISCONNECT WALK TEST ALARM TROUBLE SUP POWER DISABLE

LAMP TEST

1 2

RESET

SIGNAL SILENCE & DRILL PANEL SILENCE

ANNUN TROUBLE

BATT TROUBLE

GND FAULT

WALK TEST

SIGNAL SILENCED

Model numbers may have the following suffixes: G or R indicates gray or red enclosure, GD or RD indicates panel with FSDACT, GC indicates ULC panel with terminal shield, GF indicates a French ULC panel with terminal shield, and G-2 indicates 230 Vac input. Each panel is configured for Class B operation. All models except for the three-zone can be easily converted to Class A by using two Class B circuits to make one Class A circuit. FireShield has the following optional components: Remote System Indicator (FSRSI) Remote Zone Indicator (FSRZI-A) Remote Relay Module (FSRRM) Power Expander Transformer (XTR3A120, XTR3A230) (ten-zone only) DACT (Dialer)/Modem (FSDACT) City Tie Module (CTM4.7) Reverse Polarity Module (RPM) Battery Cabinet (BC-2)

ALARM DISABLE

TROUBLE

SUP/MON

1 2 3 NAC 1 NAC 2

DISABLE

DISABLE

DISABLE

4
DISABLE

Front panel display (1) Lamp test Buttons


REMOTE DISCONNECT WALK TEST

Description Press the Remote Disconnect and Walk Test buttons simultaneously to initiate a panel lamp test. This lets you verify proper operation of the LEDs on the panel and the remote annunciators.

Refer to Chapter 2 Installation for optional module details.

Operations overview
The panel operates in normal mode in the absence of any alarm, supervisory, trouble, or monitor events. In normal mode, the control panel monitors the system. The panel operates in off-normal mode any time an event is introduced into the system. When this happens, the panel: Changes contact positions on appropriate common relays Activates alarm outputs (for alarm events only) Turns on the appropriate LEDs and the panel buzzer Executes the appropriate programmed output response for the input that signaled the event Communicates event information to appropriate optional components (FSRSI, FSRZI-A, CTM4.7, or RPM)

(2) Control buttons Button


REMOTE DISCONNECT

Description Operating mode with FSDACT: Disables or enables FSDACT. Has no effect on alarm relay. Operating mode without FSDACT: Disables or enables the common alarm relay. Programming mode: Selects the next option.

WALK TEST

Operating mode: Places the panel in walk test mode. The Walk Test LED is on when the panel is in walk test mode. Programming mode: Selects the previous option.

FireShield Technical Reference Manual

1.1

System overview and operation (4) Notification Appliance Circuits (NACs) LEDs and controls LED/button Trouble LED Description On steady when there's a wiring fault on circuit. Double-flashes when circuit is disabled. Operating mode: Used to render an NAC inoperative. A disabled NAC trouble LED double-flashes. If pressed when an NAC is active, notification appliances remain active. Once silenced, a disabled NAC does not resound unless enabled. Disabled NACs remain disabled after a system reset. Programming mode: Selects an NAC so that settings can be viewed or changed. (5) Common system LEDs LED Alarm Trouble Description On steady when there is an active alarm event on any IDC. Flashes when there's a fault with a monitored circuit or system component, when a circuit is disabled, or when panel is in walk test mode. On steady when there is an active supervisory event on any IDC. On when the panel has AC power. Double-flashes when there is a disabled circuit, FSRRM, alarm relay, or FSDACT. Pressing Disable also places the panel in the trouble state. On steady when there is a communication failure between the panel and a remote annunciator. Also places the panel in the trouble state. Flashes for voltage supervisory or charger trouble. Steady means placement trouble. Also places the panel in the trouble state. On steady during an active ground fault. Also places the panel in the trouble state. Flashes when performing an audible walk test. Steady indicates a silent walk test. Also places the panel in the trouble state. On steady indicates that NAC circuits are turned off but the panel is still in alarm.

Operating mode: Initiates a panel reset.


RESET

Programming mode: Selects the next setting for the current option. Alarm mode: Silences active notification appliances. Pressing Signal Silence a second time turns NACs back on. The Signal Silenced LED indicates when the panel is in alarm and operating with notification appliances turned off. Visual appliances may or may not turn off when Signal Silence is pressed depending on panel programming. Normal mode: Activates the drill function. Turns notification appliances on according to the panel programming but does not place the panel in alarm or activate the alarm relay. Pressing Drill a second time turns off the drill function. Programming mode: Selects the previous setting of the current program option.

SIGNAL SILENCE & DRILL

DISABLE

PANEL SILENCE

Operating mode: Silences the panel and FSRSI sounders during an active trouble, supervisory, or alarm event. Programming mode: Saves the program setting.

Supervisory (3) Indicating Device Circuits (IDCs) LEDs and controls LED/button Alarm LED Trouble LED Description On steady when an alarm input device is activated. On steady when there is a wiring fault on the circuit. Double-flashes when the circuit is disabled. Fast-flashes, during walk test, when the IDC is resetting. On steady when a supervisory input device is activated. Stays on until panel is reset. Also flashes when active if programmed as a monitor zone. Monitor zone programming option is not approved for use in Canada. Operating mode: Renders an IDC inoperative. A disabled circuit can not initiate a change in panel state. A disabled IDCs Trouble LED double-flashes. If pressed when an IDC is active, it has no effect on the panels current state but no further activity on that IDC will be reported. Disabled IDCs remain disabled after a system reset. Walk test mode: Selects an IDC to place it into or remove it from walk test mode. Programming mode: Selects an IDC so that settings can be viewed or changed. Power Disable

Annunciator Trouble

Supervisory / Monitor LED (SUP/MON)

Battery Trouble Ground Fault Walk Test

DISABLE

Signal Silenced

(6) LCD display when FSDACT is installed Notes on LEDs: During an alarm condition, all flashing

LEDs, regardless of their function, go steady. When NAC or IDC pairs are configured for Class A operation, trouble conditions may be indicated by the Trouble LED on either NAC or IDC in the pair.

1.2

FireShield Technical Reference Manual

System overview and operation

Component descriptions
1 2 3 4 5 6 7 8

PRG

10

11

12

13

(1) Main AC wiring block and fuse holder: Provides connections for 120 or 230 volt AC (primary power) from dedicated service. Includes a primary power fuse (5 A). (2) Dual Transformer AC wiring block: Ten-zone panel only. Provides connections between primary side of both main and expander transformer and 120 or 230 volt AC (fused primary power). (3) Transformer: Changes 120 or 230 volt AC supply voltage

(8) Cabinet enclosure: Houses the panel electronics and

standby batteries. In some cases the batteries may be housed in an external battery cabinet (BC-2).
(9) FSDACT: Optional. Digital alarm communicator

to 24 volt AC.
(4) Power expander transformer (XTR3A120, XTR3A230):

transmitter. Provides LCD display for status messages and programming menus. Provides two telephone line connections for sending system messages to a compatible digital alarm communicator receiver (DACR). Includes an event history log of panel and FSDACT events.
(10) Program jumper PRG: Used to place the panel in

Optional. Available for the ten-zone panel only. Provides additional primary power to increase the available NAC current for the ten-zone panel.
(5) Main circuit board: Provides connections for all circuits.

programming mode.
(11) Tie wrap mounts: Nonpower-limited. Used to secure

wires and to help maintain proper separation between powerlimited and nonpower-limited conductors.
(12) Tie wrap mounts: Power-limited. Used to secure wires

Also includes the operator interface.


(6) FSDACT plug: Used to connect the FSDACT to the circuit

board.
(7) Operator Interface: Includes operator controls, LED

and to help maintain proper separation between power-limited and nonpower-limited conductors.
(13) Standby batteries: Provide secondary/standby power to

indicators, and circuit identification labels.

the panel electronics in the absence of primary power.

FireShield Technical Reference Manual

1.3

System overview and operation To silence an FSRSI buzzer:

Operating the panel


Resetting the panel
Pressing Reset places the panel in the reset state. The panel should not be reset until the appropriate authority has determined that the hazard is no longer present. When you reset the panel: All LEDs on the panel light for five seconds The trouble and power lights remain on for an additional 15 seconds When reset is complete, the buzzer sounds (then turns off) and the trouble LED turns off All panel indicators are temporarily cleared All notification appliances are turned off All latched IDCs are cleared Alarm, trouble, and supervisory relays are returned to the inactive state Auxiliary power (if programmed as resettable) momentarily turns off

1. 2. 3.

Press the Silence button on the FSRSI. Determine the type of condition that caused the buzzer to sound: alarm, trouble, supervisory, or monitor. Determine the cause of the condition.

Silencing notification appliances


Pressing the Signal Silence & Drill button turns off all audible devices. Visual devices or NAC circuits may or may not turn off, depending on panel programming. When you silence the signals, the Signal Silenced LED lights, indicating that the notification appliances are off. The panel does not indicate a trouble condition. If GENESIS, horn/strobe, or horn-only devices are used on NACs programmed for GENESIS operation, Signal Silence & Drill silences only the horns.
WARNING: The notification appliances should not be silenced

In this state:

until the building is fully evacuated and the cause of the alarm has been determined.
To silence notification appliances:

At the conclusion of the reset, if an IDC is in an off-normal state, the panel treats the event as a new event and activates the programmed responses. Pressing Disable for the active IDC within 30 seconds after the panel has reset turns off the NACs and disables the IDC. If one or more IDCs are disabled prior to initiation of the reset, those IDCs remain disabled. If signal silence inhibit or reset inhibit is enabled, system reset is inhibited during the silence or reset inhibit period.
To reset the panel:

1.

Press the Signal Silence & Drill button.

When the auto signal silence timer is programmed

When an event activates the notification appliances, the 20minute auto signal silence timer is activated. The notification appliances are activated for the 20-minute period. When the timer expires, any NACs that are programmed as silenceable are deactivated, and the Signal Silenced LED is illuminated. If another event takes place that activates the previously silenced notification appliances, the Signal Silenced LED turns off. At any time, you can deactivate silenceable NACs by pressing Signal Silence & Drill.
Note: NACs activated by IDCs programmed as waterflow

1.

Press the Reset button.

Silencing panel and FSRSI buzzers


Both the panel and the optional FSRSI module have buzzer silence buttons. Pressing the Panel Silence button silences the buzzer on the panel and on remote FSRSIs. Pressing the FSRSI Silence button silences the buzzer on the FSRSI only.
To silence the panel buzzer:

cannot be silenced until the activated devices are restored to normal. After the devices restore, the Signal Silence & Drill button or the auto signal silence timer can silence the NACs.

Resounding an alarm condition


Pressing the Signal Silence & Drill button again turns the audible devices back on if they were silenced.
To resound notification appliances:

1. 2. 3.

Press the Panel Silence button on the panel. Determine the type of condition that caused the buzzer to sound: alarm, trouble, supervisory, or monitor. Determine the cause of the condition.

1.

Press the Signal Silence & Drill button.

Note: NACs resound automatically if a new alarm (from

another IDC) is received.

1.4

FireShield Technical Reference Manual

System overview and operation

Disabling an IDC
Pressing an IDC Disable button prevents the panel from responding to any status change from that IDC. When you disable an IDC: The common Disable LED double-flashes The IDC Trouble LED double-flashes The common Trouble LED lights and the panel goes into a trouble state The common trouble relay changes state

To re-enable an IDC or NAC:

1.

Press the Disable button for the IDC or NAC you want to re-enable.

Using the drill command


You can use the drill command to activate all of the notification appliance circuits. Pressing Drill activates all audibles and visuals according to the panel programming, but does not activate the Alarm relay. The FSDACT can be programmed to transmit a drill condition, but it will never report the drill as an alarm. Drill will not operate with an active alarm or supervisory event at the panel.
To perform a fire drill:

Resetting the panel has no effect on a disabled IDC, but removing all power from the panel clears the disable and enables the IDC.
Note: During an alarm condition, all flashing LEDs go steady. To disable an IDC:

1. 2.

Press and hold the Signal Silence & Drill button for one second. To stop the drill, press and hold the Signal Silence & Drill button for one second.

1.

Press the Disable button for the IDC that you want to disable.

Disabling a NAC
When you disable an NAC: The common Disable LED double-flashes The NAC Trouble LED double-flashes The common Trouble LED lights and the panel goes into a trouble state The common trouble relay changes state

Using the walk test command


A walk test lets you test IDC zones without having to create an actual alarm condition. You can conduct a walk test in silent or audible mode. In silent mode the audible devices (NACs) do not sound. Walk test will not operate with an active alarm or supervisory event at the panel. Zones should be placed in walk test one at a time. This allows the balance of the system to remain in service. In a walk test, the panel responds to the first signal it receives and ignores all others on that IDC until it clears that signal or the panel is reset. The input must be restored to the normal state before the next input is tested. When the input is restored, the panel automatically resets the circuit being tested. The automatic reset takes eight seconds. After the circuit is reset the next device can be tested. The panel terminates the walk test if any of the following occur: The panel enters an alarm or supervisory state There are 30 minutes of inactivity on the zone being tested The panel is reset Walk Test is pressed The Walk Test LED flashes for an audible walk test and is steady for a silent walk test The panel enters a trouble state. There is no fire protection for the IDC in walk test. If an unselected IDC goes into alarm or trouble, all programmed outputs operate as programmed.

Resetting the panel has no effect on a disabled NAC, but removing all power from the panel clears the disable and enables the NAC.
To disable a NAC:

1.

Press the Disable button for the NAC that you want to disable.

Re-enabling an IDC or NAC


You can re-enable a disabled IDC or NAC. When you reenable an IDC or NAC: The common Disable LED turns off The IDC or NAC trouble LED turns off The common Trouble LED turns off and the panel returns to normal The IDC or NAC LEDs are updated to show current status (e.g. if the IDC or NAC is in trouble, the Trouble LED lights). After enabling an IDC, alarms from that IDC are inhibited for 30 seconds. During this time the IDC can be disabled to avoid an unwanted alarm.

When you press Walk Test:

FireShield Technical Reference Manual

1.5

System overview and operation

The IDC you are testing behaves as follows: For alarm events, the appropriate panel, FSRSI, and FSRZI-A LEDs and buzzers are turned on In the audible test mode the notification appliances sound for a number of times equal to the zone number (e.g. three rings for zone three) After activation, the panel resets the IDC. This will take eight seconds. During the reset period, the IDC trouble LED fast-flashes. If the device being tested is not restored, the IDC does not reset. If the device is restored (no alarm is present) the panel is ready to test another device or detector. If auxiliary power is programmed as resettable, the auxiliary power is deactivated while the zone is reset Input zones programmed as waterflow with retard require 10 to 15 seconds of activation to initiate the test signals For trouble events, the appropriate LEDs and the buzzers are turned on. In the audible (NAC) test mode a onesecond pulse sounds on the audible devices. After sounding, the zone resets in preparation for continued testing. For ground fault events, the appropriate LEDs and the buzzers are turned on. In the audible (NAC) test mode a one-second pulse sounds on the audible devices. After sounding, the zone resets in preparation for continued testing.

Conducting lamp tests


Panel lamp test

A panel lamp test lights all the LEDs on the panel, FSRSIs, and FSRZI-As so you can verify proper operation.
To test panel lamps:

1. 2.

Press and hold the Remote Disconnect and Walk Test buttons simultaneously. Verify proper operation of all LEDs on the panel.

During lamp tests the LCD displays: DB# xx P: x.yy.zz D: x.yy.zz Where: DB# is the database revision number P: x.yy.zz is the main panel version D: x.yy.zz is the FSDACT version
FSRSI and FSRZI-A lamp test

FSRSI and FSRZI-A modules can be installed individually or in groups to create a complete remote annunciator. You can perform a local lamp test on the FSRSI and FSRZI-A. An FSRSI is required to initiate this function.
To do an FSRSI and FSRZI-A lamp test:

1. 2.

Press and hold the FSRSI Silence button for five seconds. Verify proper operation of all LEDs on the FSRSI and FSRZI-As.

To conduct an audible walk test:

1. 2. 3. 4. 5.

Press the Walk Test button once. Press the Disable button for the IDC you want to test. Conduct your walk test for the IDC. When you are finished testing an IDC, press the Disable button to turn off the walk test for that IDC. Select another IDC to walk test (steps 2 through 4) or exit from the walk test by pressing the Walk Test button.

To conduct a silent walk test:

1. 2. 3. 4. 5.

Press the Walk Test button two times. Press the Disable button for the IDC you want to test. Conduct your walk test for the IDC. When you are finished testing an IDC, press the Disable button to turn off the walk test for that IDC. Select another IDC to walk test (steps 2 through 4) or exit from the walk test by pressing the Walk Test button.

1.6

FireShield Technical Reference Manual

System overview and operation

FSDACT LCD messages


Message Peripheral trouble Battery Bad Battery Missing AC Failure Charger Trouble Description The panel lost communications with the peripherals The battery is bad and needs to be replaced The battery is no longer connected The panel lost AC power The panel detected a battery charger trouble condition. The charger may not be able to charge the batteries. The panel detected a ground fault The panel detected a trouble condition in the Power Expander Transformer The panel detected a trouble condition in the AUX power circuit. Panel-to-FSDACT communication fault One or more FSRRMs are disabled The FSDACT is dialing a DACR FSDACT is not programmed or has unverified changes FSDACT failed to deliver a message to the receiver or CMS A ground fault or line fault has been detected on Line 1 of the FSDACT A ground fault or line fault has been detected on Line 2 of the FSDACT

Ground Fault Transformer 2 TR AUX Power Troub Internal Comm TR RRM(s) disabled Dialing... DACT Configuration TRBL DACT Delivery TR DACT Line 1 Trbl DACT Line 2 Trbl

FireShield Technical Reference Manual

1.7

System overview and operation

1.8

FireShield Technical Reference Manual

Chapter 2

Panel dimensions Model D1 [1] D2 3.75 in (9.5 cm) 3.75 in (9.5 cm) D3 9.13 in (23.2 cm) 7.75 in (19.7 cm) D4 10.5 in (26.67 cm) 21.27 in (54.0 cm) D5 [1] 14.23 in (36.14 cm) 16.25 in (41.27 cm)

Installation
Installation checklist
Prepare the site: Make sure the installation location is free from construction dust and debris and extreme temperature ranges and humidity. Unpack the equipment Install the cabinet: See Installing the cabinet for cabinet dimensions. Remove the clear protective plastic from the front panel display Install optional components (FSRSI, FSDACT, etc.): See module installation instructions in this chapter. Set the panel jumpers: See Appendix C or the panel label. Review wire routing: See Appendix C or the panel label. Connect the field wiring: See Appendix C or the panel label. Meter for opens, grounds, and shorts before connecting. Connect AC power and ground: See Appendix C or the panel label. Panel can not be started on batteries only. WARNING: Make sure that the AC power circuit breaker is off before connecting wires to the terminal block. Connect batteries: See Appendix C or the panel label. Program the panel: Refer to Chapter 3. Test for proper operation

16.5 in Threeand five- (41.9 cm) zone Tenzone 23.65 in (60 cm)

[1] Add 1-1/2 in (3.81 cm) to D1 and D5 dimensions for trim kit.

D2

D3

Semi-flush mounting holes

D1

Surface mounting holes

D4

D5

Installing the cabinet


Cabinets can be surfaced mounted or semi-flush mounted. See the Panel dimensions figure and table for framing and mounting dimensions.
To surface mount the cabinet:

1. 2.

Position the cabinet on the finished wall surface. Fasten the cabinet to the wall surface where indicated.

To semi-flush mount the cabinet:

1. 2. 3.

Frame the interior wall as required to support the full weight of the cabinet and standby batteries. Install (optional) semi-flush trim to cabinet. Fasten the cabinet to the framing studs where indicated.

FireShield Technical Reference Manual

2.1

Installation LED Supervisory (yellow) Ground fault (yellow) Buzzer State On Description Active supervisory device System trouble System ground fault System trouble Alarm condition Supervisory condition AC fail Normal or silenced

Installing the Remote System Indicator


The Remote System Indicator (FSRSI) is a supervised remote annunciator that provides remote LED indication of power, alarm, supervisory, trouble, and ground fault conditions. A sounder gives audible indication during a trouble, alarm, or supervisory condition. The sounder can be silenced with the FSRSI Silence switch.
Note: You must run the Find Annunciators program option

Trouble (yellow) On On On On (temporal) On (slow pulse) On (intermittent) Off

after adding or removing a remote annunciator. The remote annunciators will not operate properly until the panel detects them. For more information see Chapter 3 Programming.

Jumper setup
Jumper J2 Name Group jumper Description Allows two FSRSIs to be connected to the same panel. Install the jumper on only one of the two FSRSIs. Note: For jumper location, refer to the FSRSI wiring diagram.

Installation instructions
A single FSRSI can be mounted in a standard, single gang electrical box (ANSI/NEMA OS1-1996) using the single gang cover plate that is included. Up to three FSRZI-As with or without an FSRSI can be mounted in an approved multiple gang electrical box (ANSI/NEMA OS1-1996) with appropriate two, three, or four gang cover plates (model numbers FSAT-2, FSAT-3, or FSAT-4).
Caution: Make sure all power is disconnected from the panel

Specifications
Max. per system: 2 Voltage range Minimum: 21 Vdc Maximum: 25 Vdc Current requirements Standby: 12 mA Alarm: 48 mA Max. circuit capacitance: 0.03 F Max. circuit resistance: 13 ohms Wire size Minimum: 18 AWG (0.75 sq mm) Maximum: 12 AWG (2.5 sq mm) Compatible electric box: ANSI/NEMA OS1-1996 1-3 gang electrical box Operating environment Temperature: 32 to 120 F (0 to 49 C) Humidity: 93% RH, noncondensing

before installing. Observe static-sensitive handling practices.


To install the FSRSI:

1. 2. 3.

Verify that all field wiring is free of opens, shorts, and ground faults. Connect wires to the FSRSI as shown (see wiring diagram). Using the two plain machine screws provided, mount the module to the electrical box.
Note: If you are using a surface mounting box, you must

install washers (provided) between the FSRSI and the surface mounting box. 4. Using the white machine screws provided with the faceplate, mount the faceplate to the module. Connect the wires to the terminals in the control panel. Program the FSRSI using the Find Annunciators program option. Refer to Chapter 3 Programming.

LEDs and buzzer


LED Power (green) Alarm (red) State On On Description AC power present Active alarm state

5. 6.

2.2

FireShield Technical Reference Manual

Installation

Installing the Remote Zone Indicator


Compatible electrical box

The Remote Zone Indicator (FSRZI-A) is a supervised remote annunciator that provides remote LED indication of IDCs in alarm state. The FSRZI-A indicates conditions for five IDCs. The IDC groups are set by jumpers to indicate zones 15 or zones 610. Paper inserts are provided for labeling the LEDs.
Note: You must run the Find Annunciators program option

after adding or removing a remote annunciator. The remote annunciators will not operate properly until the panel detects them. For more information see Chapter 3 Programming.

Installing the FSRSI in an electrical box

Wiring diagram
From control panel or previous device Communication in Communication in + 24 V in + 24 V in Group J2

Specifications
Max. per system FS302 (three-zone): 2 FS502 (five-zone): 2 FS1004 (ten-zone): 4 Voltage range Minimum: 21 Vdc Maximum: 25 Vdc Current requirements Standby: 8 mA Alarm: 35 mA Max. circuit capacitance: 0.03 F Max. circuit resistance: 13 ohms Wire size Minimum: 18 AWG (0.75 sq mm) Maximum: 12 AWG (2.5 sq mm) Compatible electric box: ANSI/NEMA OS1-1996 1-3 gang electrical box Operating environment Temperature: 32 to 120 F (0 to 49 C) Humidity: 93% RH, noncondensing

24V IN C IN - + + 24V OUT C OUT - + + -

24 V out + 24 V out Communication out Communication out + To next device

Notes

1. 2.

All wiring is supervised and power limited. 24 V out (aux power) must be programmed as nonresettable.

FireShield Technical Reference Manual

2.3

Installation

Jumper setup
Jumper J2 Name Reserved for future use Zone 6 10 jumper Zone 1- 5 jumper Group jumper Description N/A
Compatible electrical box

J3

Sets the five LEDs to report alarms in zones 6 - 10. [1] Sets the five LEDs to report alarms in zones 1 - 5. [1] Allows two FSRZI-As to be connected to the same panel and set to the same zone output option. Install the jumper on FSRZI-As in only one of the two groups.

J4 J5

[1] Install only one zone jumper on J3 or J4. Note: For jumper location, refer to the FSRZI-A wiring diagram. Installing the FSRZI-A in an electrical box

Installation instructions
A single FSRZI-A can be mounted in a standard, single gang electrical box (ANSI/NEMA OS1-1996) using the single gang cover plate that is included. Up to three FSRZI-As with or without an FSRSI can be mounted in an approved multiple gang electrical box (ANSI/NEMA OS1-1996) with appropriate two, three, or four gang cover plates (model numbers FSAT-2, FSAT-3, or FSAT-4).
Caution: Make sure all power is disconnected from the panel

Wiring diagram
Communication in Communication in + 24 V in + 24 V in From control panel or previous device

before installing. Observe static-sensitive handling practices.


To install the FSRZI-A:

J5 J4 J3 J2

24V IN C IN - + + 24V OUT C OUT - + + -

1. 2. 3.

Verify that all field wiring is free of opens, shorts, and ground faults. Connect wires to the FSRZI-A as shown (see wiring diagram). Using the two plain machine screws provided, mount the module to the electrical box.
Note: If you are surface mounting the FSRZI-A, you must
24 V out + 24 V out Communication out Communication out + To next device

install washers (provided) between the FSRZI-A and the surface mount box. 4. 5. 6. Using the two white machine screws provided with the faceplate, mount the faceplate to the module. Connect the wires to the terminals in the control panel. Program the FSRZI-A using the Find Annunciators program option. Refer to Chapter 3 Programming.
Notes

1. 2.

All wiring is supervised and power limited. 24 V out (aux power) must be programmed as nonresettable.

2.4

FireShield Technical Reference Manual

Installation

Installing the Remote Relay Module


The Remote Relay Module (FSRRM) provides five dry contact relay outputs. The outputs can be wired as both normally open and normally closed. The outputs can be set to common or zone notifications (see the Command options table below). Installing the appropriate jumper (JP3 - JP5) configures the dry contact relay output options. Five diagnostic LEDs provide visual indication of the status of each relay. If the LED is lit, the relay is energized. If the LED is off, the relay is de-energized. If configured for common operation the trouble relay and the power relay will be energized when the system is normal.
Note: You must run the Find Annunciators program option

Common operation current requirements Standby: 30 mA Alarm: 41 mA Max. circuit capacitance: 0.03 F Max. circuit resistance: 13 ohms Relay ratings: 30 Vdc @ 1 A (resistive load) Wire size Minimum: 18 AWG (0.75 sq mm) Maximum: 12 AWG (2.5 sq mm) Mounting: MFC-A cabinet or listed fire alarm enclosure Operating environment Temperature: 32 to 120 F (0 to 49 C) Humidity: 93% RH, noncondensing

Jumper setup
Jumper JP1 Name Disable jumper Description Disables all outputs. This allows the installer to test the system while the FSRRM is disabled. Removing the jumper reactivates the FSRRM. The disable jumper is supervised. With the disable jumper in place, the panel displays Trouble, Annunciator Trouble, Disable, sounds the panel buzzer, and de-energizes any energized relay. JP2 Reserved for future use. Zone 6 10 jumper Zone 1- 5 jumper Common jumper Group jumper Sets the five dry contacts to report events on zones 6 through 10. See Command options table. [1] Sets the five dry contacts to report events on zones 1 through 5. See Command options table. [1] Sets the five dry contacts to report common events. See Command options table. [1] The group jumper (JP6) allows two FSRRMs to be connected to the same panel and set to the same output option. Install the jumper (JP6) to only one of the two grouped FSRRMs.

after adding or removing a remote annunciator. The remote annunciators will not operate properly until the panel detects them. For more information see Chapter 3 Programming.

ACTIVE
DS4

DISABLE JP1 OUTPUTS JP1 IN


MODULE TYPE JP2 ZONE 11-15 JP3 ZONE 6-10 JP4 ZONE 1-5 JP5 COMMON

OUT 1
DS5

DS2

OUT 3

OUT 4
DS1

OUT 5

TB1

TB2

DS3

TB3

OUT 2

TB4

GROUP #1 JP6 IN JP6 #2 JP6 OUT

JP3

JP4

Specifications
Max. per system FS302 (three-zone): 4 FS502 (five-zone): 4 FS1004 (ten-zone): 6 Voltage range Minimum: 21 Vdc Maximum: 25 Vdc Zoned operation current requirements Standby: 8 mA Alarm: 65 mA
JP5

JP6

[1] Install only one zone jumper on J3 or J4 or J5.

Command options
Module type Common Zone 1 - 5 Zone 6 - 10 Jumper JP5 JP4 JP3 Output 1 Alarm Zone 1 Zone 6 Output 2 Trouble [1] Zone 2 Zone 7 Output 3 Supervisory Zone 3 Zone 8 Output 4 Monitor Zone 4 Zone 9 Output 5 Power [1] Zone 5 Zone 10

[1] Under normal conditions the relay is energized (the internal LED is lit). Loss of power de-energizes the relay.

FireShield Technical Reference Manual

2.5

Installation

Installation instructions
The FSRRM snaps into a snap track (shipped with the FSRRM), which mounts inside a listed fire alarm enclosure. The FSRRM can be positioned in the snap track with the terminal block facing vertically or horizontally.
Caution: Make sure all power is disconnected from the panel

5. 6. 7. 8.

Verify that all wiring is free of opens, shorts, and ground faults. Connect the FSRRM to the panel or other peripheral devices. Power up the panel and confirm that all relays are in the correct state before connecting the field wiring. Connect field wires to the FSRRM as shown in the wiring diagram. Be sure connection will not adversely affect controlled devices (e.g. elevators, fans, etc.). Connect wiring to the controlled devices.

before installing. Observe static-sensitive handling practices.


To install the FSRRM:

9.

1. 2.

Mount the MFC-A cabinet using the installation sheet provided (P/N 387453). Drill mounting holes in the snap track using the template provided (P/N 3100463). These holes will align to the mounting holes on the MFC-A. An optional extended track (P/N FSRRM-S11) is available for mounting two to four FSRRM modules. Mount the snap track to the MFC-A cabinet.
MFC-A

10. Program the FSRRM using the Find Annunciators program option. Refer to Chapter 3 Programming.

Wiring diagram
From control panel or previous device Communication in + Communication in [1] [1] To next device Communication out Communication out +

3.

24 V in 24 V in +

[1]

[2]

[2]

Snap track

Snap track
OUT 1 24V IN C IN C OUT OUT 3 + - - + - + NO C NC NO C NC [2] [2] [2]

MFC-A Snap track Snap track


24V OUT

OUT 2 OUT 5 OUT 4 NO C NC NO C NC NO C NC


24 V out [1] 24 V out + To next device

Notes

4.

Insert one side of the FSRRM into the first snap track slot and snap in the opposite side.

[1] Supervised and power limited. [2] Must be connected to a power limited source. 3. 24 V out (aux power) must be programmed as nonresettable.

Mount in first slot only

Service and troubleshooting


If the Disabled and Annunc Trouble LED are lit but no IDC or NAC is disabled then the FSRRM output is disabled.

RRM Snap track

2.6

FireShield Technical Reference Manual

Installation

Installing the Power Expander Transformer


The Power Expander Transformer (XTR3A120, XTR3A230) provides additional primary AC power to increase the NAC capacity for the ten-zone panel. It provides an additional 2.5 amps of NAC current. The Power Expander Transformer installs in the cabinet with four nuts (provided). The input side of the Power Expander Transformer connects to 120 Vac or 230 Vac through the Dual Transformer AC Wiring Block. Its output connects to the circuit board (J4) with the attached cable harness. One Power Expander Transformer can be installed in the 10-zone panel.
Note: The Power Expander Transformer does not work with

3. 4. 5.

Connect the cable harness to J4 on the circuit board. Push the cable harness until the connector clicks into place. Connect the incoming power wires to the dual transformer AC wiring block above the existing transformer. Secure the incoming power wires to the side of the control panel with the tie strap provided.
From 120 Vac, 15 A, 60 Hz Dedicated branch circuit OR From 230 Vac, 15 A, 50/60 Hz Dedicated branch circuit

L
Cabinet

the three-zone or five-zone panels.


Main AC wiring block and fuse holder

Fuse Dual transformer AC wiring block N2 L2

Specifications
Power input 120 Vac @ 60 Hz (P/N XTR3A120) 230 Vac @ 50/60 Hz (P/N XTR3A230) Operating environment Temperature: 32 to 120 F (0 to 49 C) Humidity: 93% RH, noncondensing Fuse: Primary winding has thermal current protection and is not field serviceable
Note: Input current rating is included with the overall ten-zone

Tie wrap mounts

Main transformer

Main controller board


TB1

ratings.

Installation instructions
Caution: Make sure all power is disconnected from the panel
XTR (optional transformer)

Mounting studs

before installing. Observe static-sensitive handling practices.


To install the Power Expander Transformer:

J4

1.

Position the Power Expander Transformer so that the mounting holes align with the four mounting studs on the control panel cabinet. Secure the transformer to the panel using the four nuts provided.

Plug connector

Power Expander Transformer installation and wiring

2.

FireShield Technical Reference Manual

2.7

Installation

Installing the FSDACT


The FSDACT is a digital alarm communicator transmitter (DACT) that transmits panel events to a compatible digital alarm communicator receiver (DACR). Messages are transmitted over standard loop-start telephone lines. The dialer is capable of split reporting to two different account and telephone numbers. In addition to the DACT functions, this module includes: An alphanumeric LCD to display system messages and programming prompts An event history log of panel and DACT events, viewable through compatible software A modem for uploading and downloading panel configuration, history, and current status to a PC running compatible software

changes shall be 100 percent tested. In addition, 10 percent of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, also shall be tested, and correct system operation shall be verified. A revised record of completion in accordance with 1-6.2.1 shall be prepared to reflect any changes. For additional download security, the FSDACT can be programmed to perform a call back function. This call back option applies whether the FSDACT is configured for attended or unattended downloading.

Note: The FSDACT modem is only rated for 2400 baud

communication. Some PC modems may not be compatible with this baud rate. The FSDACT can be programmed to operate as a single or dual line DACT/Modem/LCD display, a Modem/LCD display, or an LCD display only. For the FSDACT to be NFPA 72 CS compliant, the following is required: 1. 2. 3. 4. The factory installed warning label must be removed from the FSDACT's line two phone jack. A second phone line, independent of that used for line one must be connected to phone jack two. The FSDACT must be programmed for dual line operation. The FSDACT must be programmed for a daily transmission test frequency.

Specifications
Current requirements Standby: 40 mA Alarm: 60 mA Operating environment Temperature: 32 to 120 F (0 to 49 C) Humidity: 93% RH, noncondensing Phone line type: one or two loop-start lines on a public, switched network Phone line connector: RJ31/38X (C31/38X). Two 7 ft plug cords are shipped with the FSDACT. FCC registration number: US: EDWAL01BFSDACT Ringer equivalence number: 0.1 Industry Canada Registration number: IC: 3944-FSDACT Connection between panel and FSDACT: 6-pin connector Communication formats: Contact ID (SIA DC-05) and EST 4/2 (SIA DC-02 P3 with hexadecimal event codes)

UL 864 compliance requires the dual line setting. The FSDACT can be configured for attended or unattended downloading. JP1 is a wire loop (located near the top of the FSDACT) that controls which download method is used. Leaving the JP1 wire loop intact configures the FSDACT for attended downloading. The panel will not allow changes to the panel or dialer configuration unless the program jumper is inserted. It will allow changes to receiver information (account code, telephone numbers, etc.). UL requires the red wire loop to be intact for all remote station systems. Cutting the JP1 wire loop configures the FSDACT for unattended downloading. This means that the program jumper need not be inserted to accept any panel or dialer configuration changes. NFPA 72 1999 edition states in 7-1.6.2.1 that reacceptance testing shall be performed after any change to site-specific software. "All components, circuits, systems operations, or site-specific software functions known to be affected by the change or identified by a means that indicates the system operational

Installation instructions
Note: It is not necessary to remove the main panel board from

the cabinet to install the dialer.


Caution: Make sure all power is disconnected from the panel

before removing or installing an FSDACT. Failure to disconnect power will damage the panel and the FSDACT. Observe static-sensitive handling practices.
To install the FSDACT:

1. 2.

Remove the blank insert from the display window. Remove the clear protective plastic film from the FSDACT LCD display.

2.8

FireShield Technical Reference Manual

Installation

3.

Use JP1 to configure the FSDACT for attended or unattended downloading: Attended: leave the JP1 wire intact Unattended: cut the JP1 wire

FCC Information 1. The dialer complies with Part 68 of the FCC rules. The dialers FCC certification number and Ringer Equivalence Number (REN) is displayed on the panels programming label and in this manual. This information must be provided to the telephone company if requested. Two FCC compliant telephone cords with 8-pin modular plugs at both ends are supplied with the FSDACT. The dialer is designed to be connected to the telephone network using the supplied cord and an RJ31X or RJ38X jack, which must also comply with FCC Part 68 rules. The REN is used to determine the maximum number of devices that may be connected to a single telephone circuit. All telephone devices are assigned a REN. The sum of the RENs for all connected devices may not exceed five. The maximum REN may vary in some areas. Contact the local telephone provider for more information. If the dialer causes harm to the telephone network, the telephone company will notify you an advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with the FCC, if you believe it is necessary. The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the dialer. If this happens, the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service. If trouble is experienced with the dialer, for repair or warranty information, contact the manufacturer at: (941) 739-4200. If the dialer is causing harm to the telephone network, the telephone company may request you disconnect the dialer until the problem is resolved. No repairs may be performed on the dialer by the user. The dialer can not be used on public coin phones or party line service provided by the telephone company.

4. 5. 6. 7. 8.

Install the dialer to the back of the circuit board. Align the LCD display with the opening in the circuit board. Secure the dialer to the circuit board with the two machine screws provided. Connect the power cable to J2 on the control panel. Connect RJ31X/C31X jacks to the supplied cables. Connect the telephone circuits as required.
Line 1 Line 2 Phone cables (supplied) To wall phone jack

2.

3.

4.

5.

RJ31 jacks

6.

JP1 jumper wire

7. 8.

Industry Canada Information NOTICE: This equipment meets the applicable Industry Canada Terminal Equipment Technical Specifications. This is confirmed by the registration number. The abbreviation, IC, before the registration number signifies that registration was performed based on a Declaration of Conformity indicating that Industry Canada technical specifications were met. It does not imply that Industry Canada approved the equipment.
Circuit board

Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas. Caution: Users should not attempt to make connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate. NOTICE: The Ringer Equivalence Number (REN) for this terminal equipment is 0.1. The REN assigned to each terminal equipment provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed five.

FSDACT installation and telephone circuit connection The FSDACT is listed for use with the following DACRs
Receiver Ademco FBII Osborne-Hoffman Radionics Silent Knight Sur-Gard Models 685 CP220 OH 2000 D6500 9000 MLR1, MLR2, MCDI TLR, TLR+ Formats EST 4/2*, Contact ID EST 4/2*, Contact ID EST 4/2*, Contact ID EST 4/2* EST 4/2* EST 4/2*, Contact ID

* EST 4/2 is SIA DCS-02 P3 with the ability to transmit hexadecimal event codes.

FireShield Technical Reference Manual

2.9

Installation Alarm and trouble transmitted on a single circuit Note: JP1 on the RPM must be OUT.

Connecting an RPM module


The Reverse Polarity Module (RPM) is an interface between FireShield and a reverse polarity receiver. It provides offpremises signal transmission for systems that must comply with NFPA requirements. When used as a reverse polarity remote station transmitter, it can be connected to either a single circuit (alarm or alarm and trouble) or up to three circuits (alarm, supervisory, and trouble).
Note: For detailed information and wiring, refer to the RPM

FireShield TB3 NO TRBL C NC NO SUP NO ALM CC+ 24VOUT + From COM on RPM (black wire) From +24 on RPM (red wire) From ALRM on RPM (brown wire) From TRBL on RPM (yellow wire)

installation sheet P/N 3100430. Below are application diagrams for using the RPM.
Note: The RPM must be mounted in an MFC-A enclosure

immediately adjacent to the panel and in conduit.


Alarm transmitted only

FireShield TB3 NO TRBL C NC NO SUP NO ALM CC+ 24VOUT + From COM on RPM (black wire) From +24 on RPM (red wire) From ALRM on RPM (brown wire)

Alarm, supervisory, and trouble transmitted on separate circuits Note: JP1 on the RPM must be IN.

FireShield TB3 NO TRBL C NC NO SUP NO ALM CC+ 24VOUT + From COM on RPM (black wire) From +24 on RPM (red wire) From SUPV on RPM (orange wire) From ALRM on RPM (brown wire) From TRBL on RPM (yellow wire)

2.10

FireShield Technical Reference Manual

Installation Panel in alarm condition

Connecting a CTM module


The CTM4.7 City Tie Module is an interface between the control panel notification appliance circuit and a master box. It provides off-premises signal transmission for systems that must comply with NFPA requirements for Auxiliary Protective Systems. The CTM4.7 activates a local energy fire alarm box, which provides a 24 Vdc alarm signal (current limited at 200 mA). The 4.7 K end of line resistor required by the NAC is built in to the CTM4.7.

Alarm condition CTM4.7 + _ _ 2 1 1 2 Master box + [1] [2] +


_ _

Requirements
When connecting a CTM to the panel, the following hardware and programming requirements must be met: The NAC used must be dedicated to CTM use only All alarm zones must be programmed to activate the dedicated NAC The NAC used must not be programmed for Signal Silence

+ [3] [5] [4] Notification appliance circuit

Municipal circuit

Notes

[1] 200 mA into a 14.5 trip coil max., loop resistance = 25 [2] This circuit is nonpower-limited and is supervised for grounds and opens, but not shorts [3] Supervised and power-limited [4] NAC must be programmed for continuous signal [5] CTM4.7 must be mounted in the same room as the panel

Specifications
Power: Nominal 24 Vdc @ 200 mA Municipal box operation: Nominal 24 Vdc Maximum wiring resistance: 25 Trip current: 200 mA into 14.5 coil Maximum current: 300 mA Standby current: 20 mA Mounting: Single gang box Operating environment Temperature: 32 to 120 F (0 to 49 C) Humidity: 93% RH, noncondensing The following are wiring diagrams showing how the polarity switches during an alarm condition.
Panel in normal condition

Normal condition CTM4.7 _ + [4] + _ 2 1 1 2 Master box


_

[1] [2] _ + Municipal circuit

[3] [5] Notification appliance circuit

FireShield Technical Reference Manual

2.11

Installation

Connecting an auxiliary power supply


Aux power supplied by the panel cannot exceed 0.5 A. If more than 0.5 A is required, you must use a compatible UL/ULC listed fire alarm power supply. When using an auxiliary power supply, you must connect the -24 Vdc auxiliary terminal at the panel to the -24 Vdc output terminal of the listed auxiliary power supply used to power FireShield devices.
Note: For detailed wiring information, refer to the installation

Installing the terminal shield


The terminal shields for the three, five, and ten zone panels (model numbers ending in GC or GF) required for Canadian installation, cover and protect the wire connections at the terminal blocks.
To install the terminal shield:

1. 2. 3.

Remove the four corner mounting screws from the circuit board. Refer to the diagram below for location. Mount the supplied standoffs to the four corner locations where you removed the screws. Mount the terminal shield to the standoffs using the screws you removed in step 1. Refer to the diagram below.
Standoff

instructions that came with the auxiliary power supply.

Aux. Power

+
To Devices 24 Vdc @ 0.5 A Max.

FireShield FACP

+
UL Listed Aux. Power Source
To Devices Requiring Additional Power

2.12

FireShield Technical Reference Manual

Chapter 3

Programming
Overview
Program options and settings
The features and functions of FireShield can be customized through programming. To customize the panel, you choose a program option, then choose a setting for that option. This chapter shows you how to program the panel.

ANNUN TROUBLE 16

BATT TROUBLE 8

GND FAULT 4 Binary numbers

WALK TEST 2

SIGNAL SILENCED 1

Bottom row of LEDs

FSDACT display
If you are using the optional FSDACT to program the panel, each option and setting is displayed on the LCD display. The top row of the LCD displays the program option, and the bottom row displays the setting for that option. You can use the programming buttons to step through the options and select the settings you want.

Programming methods
FireShield panels can be programmed using either of two methods. First, you can use the panels LEDs and switches, with or without an FSDACT installed. Second, you can use a PC with an FSDACT installed. PC programming requires an optional software package, the FireShield Configuration Utility (model number FSCU). Refer to the FSCU online help system for complete programming instructions.

Programming buttons
The panel buttons take on a different function when the panel is in programming mode. The following table shows the buttons and describes what they do in programming mode.
Button
REMOTE DISCONNECT WALK TEST

Description Selects the next program option. The top row of LEDs and the FSDACT LCD change to show the option selected. Selects the previous program option. The top row of LEDs and the FSDACT LCD change to show the option selected. Selects the next setting for the current option. The bottom row of LEDs and the FSDACT LCD change to show the setting selected. Selects the previous setting for the current option. The bottom row of LEDs and the FSDACT LCD change to show the setting selected. Saves the setting you selected for the current program option.

Programming LEDs
In programming mode, the top row of panel LEDs indicates which program option is selected. Each LED is assigned a binary number, and the total value of the top row equals the option number. If you are not familiar with binary numbers, you can simply match the pattern of the LEDs with the programming instructions.
ALARM 16 TROUBLE 8 SUP 4 Binary numbers POWER 2 DISABLE 1
PANEL SILENCE

RESET

SIGNAL SILENCE & DRILL

Top row of LEDs

Each option has a number of possible settings. The bottom row of panel LEDs indicates which setting is selected for the current option. The settings are detailed below in Custom programming the panel. Again, each LED is assigned a binary number, and the total value of the bottom row equals the setting number. The values of all LEDs lit on a single row are added to determine the option or setting number. For example, if the Gnd Fault, Walk Test, and Signal Silenced LEDs are lit, the value is 7 (4+2+1). This means that setting seven for the current option is selected.

FireShield Technical Reference Manual

3.1

Programming

Using the factory default settings


The panel comes from the factory programmed with a predefined set of defaults. The default settings are:
Option Find annunciators Auto signal silence timer Aux power reset Signal silence/reset inhibit timer IDC zone types IDC class NAC class NAC output (NAC1 NAC4) NAC silenceable Default setting None found None No None Alarm (unverified) All IDCs activate all NACs Class B Class B GENESIS Silenceable

2. 3. 4. 5.

Press Remote Disconnect to select the Load Defaults program option. Press Reset to select Yes, the setting to reload the factory default settings. Press Panel Silence to perform the reload. The trouble buzzer sounds a long beep as confirmation. Exit program mode by removing the program jumper or continue to the next topic to custom program the panel. Refer to Custom programming the panel for more information.

Using an FSDACT
If you have an FSDACT connected to your system, it must be recognized by the panel before programming. Also, if you remove an FSDACT from your system, it must be removed from the panels memory. To do this, install the program jumper (PRG), then remove the program jumper. This allows the panel to recognize that an FSDACT was installed or removed from the system.

For a more detailed list of defaults, see Appendix B, Programming templates. If you want to use the factory programmed settings as they are, you do not need to perform any programming. If you do not want to use the panels default settings, refer to Custom programming the panel.
Note: You must run the Find Annunciators program option

Custom programming the panel


FireShield functionality can be custom programmed when the factory defaults do not meet your needs. The following options can be custom programmed: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Load defaults Find annunciators Auto signal silence timer Aux power reset Signal silence/reset inhibit timer IDC zone types (and NACs that activate) IDC class NAC class NAC output NAC silenceable Program FSDACT (if installed)

after adding or removing a remote annunciator. The remote annunciators will not operate properly until the panel detects them. These include the FSRSI, FSRZI-A, and FSRRM.

Reloading the factory default settings


When you reload defaults, you return the panel to the factoryprogrammed settings. The primary purpose for loading the defaults is to return the panel to its original settings if the need arises. You can then start fresh by using these settings or custom program one or more options.
Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description Do not load default settings Load default settings Yes Key: = OFF, = ON

Load Defaults

No

Tip: We recommend that you program the options in the order

To reload the default settings:

they are listed. This matches the order of the LEDs as you increment through each option. The lighting pattern of the LEDs corresponds to the program option you are programming and follows the binary number pattern associated with each row of LEDs.

1.

Install program jumper PRG. The panel common LEDs flash and the panel enters a trouble state. The trouble buzzer sounds.

3.2

FireShield Technical Reference Manual

Programming

Getting started
You should complete the programming templates found in Appendix B before you program the panel. NFPA 72 requires that you keep a copy of these sheets on file. The following table and procedures prepare the panel for custom programming.
1. Program load defaults

next option or Walk Test to return to the previous option. To save your changes, you must press Panel Silence before advancing to the next option.
2. Program find annunciators

Description: Verifies and logs each remote annunciator (FSRSI, FSRZI-A, and FSRRM) connected to your system.
Notes

In this topic, you do not need to load the defaults. To load the default settings, see the topic Reloading the factory default settings, above.
Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description Does not load default settings Loads the default settings Yes Key: = OFF, = ON

This process may take up to 40 seconds. During this time do not remove the program jumper. If the program jumper is removed, you must power down and power up the panel to get back into the programming mode. The Find Annunciators program option must be performed if you are using remote annunciators (FSRSI, FSRZI-A, or FSRRM) or if you add or remove a remote annunciator from your system.
Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description Does not look for devices. Find Annunc xx now on bus Logs all devices connected to the panel.

Load Defaults

No

To get started:

1.

Install program jumper PRG. The top rows of LEDs flash and the panel enters a trouble state. The trouble buzzer sounds.

Find devices

To find remote annunciators:

2.

Press Remote Disconnect to advance to the first programming option (Load Defaults). The LEDs stop flashing, the Disable LED (binary value 1) lights, and Load Defaults is displayed on the FSDACT LCD display (if installed). The trouble buzzer turns off; however, the panel is still in a trouble state. The Signal Silenced LED is on, showing that setting No is selected.

1.

Press Remote Disconnect to select the program option. If an FSDACT is installed, the lower line of the LCD displays xx now on bus where xx is the number of devices (between 0 and 12).

2. 3.

Press Reset to select Find devices. Press Panel Silence to begin finding devices. The bottom row of LEDs flashes and the second line of the LCD displays Finding devices while the panel searches for all remote annunciators. When the search is complete, the bottom row of LEDs shows (in binary) the number of devices found. The second line of the LCD displays was xx now yy. The number of devices found (now) should equal the number of devices installed. If not, there is a wiring or device problem.

3.

You can press Reset to step through the settings available for this option (No or Yes). Notice how the Signal Silenced and Walk Test LEDs switch to indicate the different options. You are now ready to program your panel.

Notes

You can exit program mode at any time by removing the program jumper. All saved program selections remain intact. When the jumper is removed, the panel resets. If no buttons are pressed for 90 seconds, the system returns to the initial program start state with the top row of LEDs flashing and the buzzer sounding.

4.

To end programming now, remove the program jumper. Otherwise, continue with Program auto signal silence timer, below.

3. Program auto signal silence timer

To program the panel


If no programming is required for a particular option, it can be skipped. You can use Remote Disconnect to advance to the

Description: A timer that, when programmed, automatically silences the NAC circuits 20 minutes after the last alarm event.

FireShield Technical Reference Manual

3.3

Programming To program the signal silence/reset inhibit timer:

Program option Top LEDs/LCD

Setting Bottom LEDs/LCD

Description NACs stay on until Signal Silence is pressed NACs automatically turn off after twenty minutes

1. 2. 3.

Press Remote Disconnect to select the program option. Press Reset to select your setting. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation.

Auto Sig Sil

None

Sil aft 20 mins

To program the auto signal silence timer:

6. Program IDC zone types

1. 2. 3.

Press Remote Disconnect to select the program option. Press Reset to select your setting. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation.

Description: Selects the type and functionality of each IDC.


Note: See the FireShield ULI and ULC compatibility lists P/N

3100468 for restrictions. Default: Alarm - unverified, with all NACs active
Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description Alarm-unverified: For circuits with smoke detectors and contact devices. All activations are immediately considered as alarms. Circuit can not be restored until devices are restored to normal and panel is reset. Alarm-verified: For circuits with smoke detectors and contact devices. 2-wire smoke detector activations are verified (delayed and confirmed) before activating an alarm. 4-wire smoke detectors and contact devices are not verified and immediately considered as alarms. Circuit can not be restored until devices are restored to normal and panel is reset. Waterflow (retard): For connection of both vane type and pressure flow switches. Device activation must be maintained for at least 15 seconds before being considered an alarm. NACs activated by waterflow IDCs can not be silenced until activated devices restore to normal (panel reset not required). Circuit can not be restored until devices are restored to normal and panel is reset.

4. Program aux power reset

Description: Causes a temporary interruption of aux power when Reset is pressed. This is so that four-wire smoke detectors can be reset. If this is not programmed, pressing Reset has no effect on the aux power output.
Caution: This option must be set to No (continuous) if remote

Program IDC

Alarm-unverified

annunciators or relays are being used.


Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description Continuous 24 Vdc on AUX PWR terminals Resettable 24 Vdc on AUX PWR terminals

Alarm-verified

Aux Power Reset

No

Yes

To program aux power reset:

1. 2. 3.

Press Remote Disconnect to select the program option. Press Reset to select your setting. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation.
Retard-waterflow

5. Program signal silence/reset inhibit timer

Description: Programs all NACs with a one-minute silence inhibit. This means that, the NACs cannot be silenced and the panel cannot be reset during their first minute of activation.
Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description Signal Silence/Reset operational immediately after NACs turn on Signal Silence/Reset operational one minute after NACs turn on

Sig Sil Inhibit

None

Inhibit one min

3.4

FireShield Technical Reference Manual

Programming To program IDC zone types:

Waterflow

Waterflow (no retard): For connection of both vane type and pressure flow switches. Activations are immediately considered as alarms. NACs activated by waterflow IDCs can not be silenced until activated devices restore to normal (panel reset not required). Circuit can not be restored until devices are restored to normal and panel is reset. Waterflow (retard) / supervisory (latching): Special IDC that allows connection of both waterflow and supervisory devices on the same 2wire circuit. Requires the use of two resistors (3.6 k and 1.1 k). The waterflow portion of the circuit functions the same as IDC Type 3 Waterflow (retard) and the supervisory portion functions the same as IDC Type 7 Supervisory (latching). Waterflow (no retard) / supervisory (latching): Special IDC that allows the connection of both waterflow and supervisory devices on the same 2wire circuit. Requires the use of two resistors (3.6 k and 1.1 k). See Waterflow (no retard) and Supervisory (latching) settings for additional information. Supervisory (latching): For the connection of supervisory devices. Momentary activation of normally open devices immediately places the panel in a supervisory state and turns on supervisory LEDs and relays. Circuit can not be restored until devices are restored to normal and panel is reset. Monitor: Monitoring of normally open switches for other functions (fire door position, etc.). Not approved for use under ULC 527 in Canada.

1.

Press Remote Disconnect to select the program option. For new panels, the Trouble LED of IDC 1 lights. Otherwise, the Trouble LED of the last IDC programmed lights. To select an IDC for programming, press the IDC Disable button.

2.

Press Reset to select the desired IDC zone type.


Note: If you program an IDC as a waterflow/supervisory,

a supervisory activation will not turn on the outputs (NACs and relays). Only a waterflow activation will turn on the outputs. 3. Program which NAC activates for the IDC. The Trouble LED for the NAC lights to indicate which NAC is associated with the IDC. Press the NAC Disable button to deselect (or reselect) it for activation. The default is that each alarm or waterflow IDC activates all NACs. Only alarm, waterflow, and supervisory can operate NACs. Alarm and supervisory IDCs should not be assigned to the same NACs. Monitor zones can not be assigned to NACs. 4. 5. Press Panel Silence to save your selection for the IDC. The trouble buzzer sounds a long beep as confirmation. Select the next IDC for programming by pressing its Disable button. The corresponding Trouble LED lights to indicate your selection. 6. Program the IDC by repeating steps 2 through 4, above. Complete this procedure for each IDC before moving on to the next program option.
7. Program IDC classes

Ret-wf/superv

Wf-supervisory

Supervisory

Description: Programs the IDCs as either Class B or Class A. This option only appears for panels that can be configured as Class A. All IDC types except the two combination waterflow/ supervisory options can be configured as Class A For Class A operation, you need to configure a pair of IDCs, one odd and one even. When you change the class of an IDC, you must change the class of both IDCs in the pair.
Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description IDC wired as Class B IDC Class Class B IDC wired as Class A Class A

Monitor

FireShield Technical Reference Manual

3.5

Programming To program IDC classes:

1. 2. 3. 4.

Press Remote Disconnect to select the program option. The last programmed IDC Trouble LED stays lit. Press Reset to select Class A or Class B. Press Panel Silence to save your selection. The trouble buzzer sounds a long beep as confirmation. Program each IDC class by pressing the IDC Disable button to light the IDC Trouble LED. When the Trouble LED is lit, you can program the IDC class by repeating steps 2 and 3 above.

Program option Top LEDs/LCD

Setting Bottom LEDs/LCD

Description NAC outputs continuous signal: For strobes and notification appliances that selfgenerate a temporal pattern. NAC outputs temporal (3-3-3) signal: Universal 3-3-3 pattern required for evacuation signals by NFPA 72. Used when notification appliances are not capable of selfgenerating a temporal pattern. GENESIS sync/silence: Used with Genesis and Enhanced Integrity horns and strobes. Genesis and Enhanced Integrity appliances maintain synchronization per UL 1971. For Genesis devices, it allows connected horns to be silenced while strobes on the same 2-wire circuit continue to flash until the panel is reset.

NAC Output

Continuous

Temporal

Note: Make sure you set the IDC jumpers to match the class

for which you program the IDC.


8. Program NAC classes
GENESIS

Description: Programs the NACs as either Class B or Class A. For Class A operation, you need to configure a pair of NACs, one odd and one even. When you change the class of an NAC, you must change the class of both NACs in the pair.
Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description NAC wired as Class B NAC Class Class B NAC wired as Class A Class A

To program NAC outputs:

1. 2. 3. 4.

Press Remote Disconnect to select the program option. The last programmed NAC Trouble LED stays lit. Press Reset to select your setting. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation. Program the output for each NAC by pressing the NAC Disable button to light the Trouble LED for that NAC. When the Trouble LED is lit, you can program the NAC by repeating steps 2 and 3 above.
Note: Whenever NAC pairs are programmed for Class A,

To program NAC classes:

1.

Press Remote Disconnect to select the program option. For new panels, the Trouble LED of NAC 1 lights. Otherwise, the Trouble LED of the last NAC programmed lights. To select a NAC for programming, press the NAC Disable button.

2.

Press Reset to select Class A or Class B.


Note: Whenever NAC pairs are programmed for Class A,

output pairs must be programmed for the same output types. 3. 4. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation. Program each NAC class by pressing the NAC Disable button to light the NAC Trouble LED. When the Trouble LED is lit, you can program the NAC class by repeating steps 2 and 3 above.

output pairs must be programmed for the same output types.


10. Program NAC as Silenceable

Description: Programs the NAC as silenceable. If set to No, the NAC, when activated, cannot be silenced using the Signal Silence & Drill button or the auto signal silence feature. It can only be silenced with a panel reset.

Note: Make sure you set the NAC jumpers to match the class

for which you program the NAC.


9. Program NAC outputs

Description: Programs the output of each NAC.

3.6

FireShield Technical Reference Manual

Programming

Program option Top LEDs/LCD

Setting Bottom LEDs/LCD

Description NAC does not turn off when Signal Silence is pressed NAC turns off when Signal Silence is pressed

NAC Silenceable

No

If you selected Yes, the panel automatically switches to FSDACT programming mode and DACT Programming is displayed on the LCD. Refer the next topic FSDACT programming for complete programming instructions. If you selected No, proceed to Finishing up, below. You can return to FSDACT programming at any time.
Tip: If no panel programming is needed, you can go directly to

Yes

Note: It is not necessary to select this option for waterflow

this program option by following these steps: 1. Insert the program jumper. 2. Press Remote Disconnect. 3. Press Walk Test.
Finishing up To finish up:

IDCs. NACs assigned to waterflow IDCs can not be silenced as long as the IDC has an active input. The IDC remains in the alarm state until the panel is reset. If the auto signal silence feature is programmed, the panel silences the associated NAC when the waterflow switch is no longer active and the timer has expired. If Signal Silence & Drill is pressed when a waterflow circuit is active, the associated NAC circuit does not silence until the waterflow condition is no longer active.
To program the NACs as silenceable:

1. 2. 3.

Remove the program jumper PRG. You can store the suitcase jumper on one pin. Panel programming is complete. The panel will reset. At the conclusion of the reset, make sure the panel is free of troubles. If IDC or NAC trouble LEDs are on, check to see that the jumper settings match the program options selected. Test all circuits and panel functions to make sure that the panel was programmed correctly.

1. 2. 3. 4.

Press Remote Disconnect to select the program option. The last programmed NAC Trouble LED stays lit. Press Reset to select your setting. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation. Program each NAC by pressing the NAC Disable button to light the Trouble LED for that NAC. When the Trouble LED is lit, you can program the zone by repeating steps 2 and 3 above.

4.

11. Programming the FSDACT

Description: Initiates the FSDACT for programming. This option is not displayed if you do not have a FSDACT; you can proceed to Finishing up, below.
Program option Top LEDs/LCD Setting Bottom LEDs/LCD Description Does not switch to FSDACT programming mode. Automatically switches the panel to FSDACT programming mode.

Program DACT

No

Yes

To program the FSDACT:

1. 2. 3.

Press Remote Disconnect to select the program option. Press Reset to select Yes or No. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation.

FireShield Technical Reference Manual

3.7

Programming

FSDACT programming
Programming the FSDACT sets up the dialer for communication with the central monitoring station. It also sets a number of other options such as date, time, phone numbers, etc. Many of the options have default settings, which are detailed below. These settings can be changed if desired.

Digit D E F * # ,

Telephone number

4.2 event codes Hexadecimal D (13) Hexadecimal E (14)

Terminator (indicates last digit) DTMF * DTMF # DTMF , (used for a pause between digits)

Hexadecimal F (15)

Programming buttons
The panel buttons function in the following way when in FSDACT programming mode.
Button descriptions Button
REMOTE DISCONNECT WALK TEST

Getting started
You should complete the programming templates found in Appendix B before you program the panel. NFPA 72 requires that you keep a copy of these sheets on file. Follow the steps below to prepare the panel for FSDACT programming. If you are already in programming mode, skip the first three steps and start at number four below.
To get started:

Description Selects the next program option

Selects the previous program option

Selects the next setting for the current option.


RESET

1.

Install program jumper PRG. Panel common LEDs flash and the panel enters a trouble state. The trouble buzzer sounds.

Also increments through the digits of numeric entries such as telephone numbers Selects the previous setting for the current option Also decrements through the digits of numeric entries such as telephone numbers Saves the setting you selected for the current program option Advances cursor to the next digit of a field (e.g. entering a phone number) Note: When pressed in the last digit of a field, the information is saved and the next program option is displayed

SIGNAL SILENCE & DRILL

2.

Press Remote Disconnect to advance to the first programming option (Load Defaults). The LEDs stop flashing, the Disable LED (binary 1) lights, and Load Defaults is displayed on the LCD. The trouble buzzer turns off; however, the panel is still in a trouble state.

PANEL SILENCE

3. 4. 5.

Do not load defaults. Press Walk Test until DACT Programming is displayed. Press Reset until Yes is selected. Press Panel Silence to begin FSDACT programming. The panel automatically switches to FSDACT programming mode and DACT Programming is displayed on the LCD.

Tip: In this chapter we tell you to press Reset to scroll through

each list of settings. However, to enter a setting thats near the end of the list, it may be faster to press Signal Silence & Drill to move backwards through the list of selections.

6.

Digit descriptions
The following table describes the function of each digit that can be entered in FSDACT programming fields.
Digit 0 to 9 A B C Telephone number Numeric digits DTMF A DTMF B 4.2 event codes Numeric digits Hexadecimal A (10) Hexadecimal B (11) Hexadecimal C (12)

Enter your password. Refer to Programming the FSDACT below.

Note: You can exit from programming mode at any time by

removing the program jumper. All saved program selections will remain intact.

3.8

FireShield Technical Reference Manual

Programming

Programming the FSDACT


When you program the FSDACT, youll follow these general steps: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. Enter your passcode Load default settings Edit your passcode Enter the date Enter the time Select the FSDACT mode Enter the (DACR1) primary phone number Enter the (DACR1) secondary phone number Enter the (DACR1) account code Select the DACR1 alarm format Select the restore option for CMS one Enter retry count one Enter retry time one Enter the (DACR2) primary phone number Enter the (DACR2) secondary phone number Enter the (DACR2) account code Select the DACR2 alarm format Select the restore option for CMS two Enter retry count two Enter retry time two Select tone or pulse dialing Select AC fail delay time Enter the transmission test time Select the transmission test frequency Enter the number of rings to answer Select the ring type Enable (disable) call back Enter the call back phone number

3. 4. 5. 6.

Press Reset (or Signal Silence & Drill) until the next digit of your passcode is displayed. Press Panel Silence to save and advance to the next digit. Repeat steps 3 and 4 until all digits are entered. When you press Reset at the last digit, the system automatically advances you to the next program option.

2. Load default settings

Description: Loads the factory default settings for each program option. Settings: Yes = Loads the default settings No = Does not load the default settings Default: No
To load default settings:

1. 2.

Press Reset to select Yes or No. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

3. Edit your passcode

Description: You have the option to change your passcode or continue with programming. Format: 7 digits Default: No default
To skip changing your passcode:

Tip: If you save an incorrect digit, press Walk Test then

Remote Disconnect. This returns the cursor to the first digit. Press Panel Silence until the cursor is at the incorrect digit. Enter the correct digit, then press Panel Silence to save and advance to the next digit.
1. Enter your passcode

1.

Press Remote Disconnect to advance to the next program option.

To change your passcode:

1. 2. 3. 4. 5. 6.

Description: Access to dialer programming is passcode restricted. For security, the default passcode should be changed as part of the installation. (To change the passcode, refer to Edit passcode, below.) Format: 7 digits Default: 1111111
To enter your passcode:

Press Reset until the first digit of your new passcode is displayed. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset until the next digit is displayed. Press Panel Silence to save and advance to the next digit. Repeat steps 3 and 4 until all digits are entered. When you press Panel Silence at the last digit, the system automatically advances you to the next program option.

1.

Press Reset (or Signal Silence & Drill) to scroll through the setting list until the first digit of your passcode is displayed. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation.

4. Enter the date

2.

Description: Sets the current date. Format: MMDDYYYY Default: 01012002

FireShield Technical Reference Manual

3.9

Programming Tip: Dont forget that you can press Reset or Signal Silence &

The trouble buzzer sounds a long beep as confirmation.


Note: If Single Line DACT is selected, dual line programming

Drill to scroll through the list of settings. It may be faster to press Signal Silence & Drill to scroll backwards through the settings.
To enter the current date:

is skipped. If Modem/LCD only is selected, all account and receiver related programming is skipped. If LCD only is selected, all account, receiver, and telephone related programming is skipped.
7. Enter the (DACR1) primary phone number Note: If a DACR1 primary phone number is not entered, skip

1. 2.

Press Reset until the correct month is displayed. Press Panel Silence to save the month setting and advance to the day setting. The trouble buzzer sounds a long beep as confirmation. Press Reset until the correct day is displayed. Press Panel Silence to save the day setting and advance to the year setting. The trouble buzzer sounds a long beep as confirmation. Press Reset until the correct year is displayed. Press Panel Silence to save the year setting and advance to the next option. The trouble buzzer sounds a long beep as confirmation.

Enter the (DACR1) secondary phone number through Enter retry count one, inclusive. Description: Specifies the primary phone number that is used to contact the central monitoring station. Format: Up to 20 digits Default: Blank
Tip: If you save an incorrect digit, press Walk Test then

3. 4.

5. 6.

Remote Disconnect. This returns the cursor to the first digit. Press Panel Silence until the cursor is at the incorrect digit. Enter the correct digit, then press Panel Silence to save and advance to the next digit.
To enter the primary phone number:

5. Enter the time

Description: Sets the current time. Format: HHMM Default: 0000


To enter the current time:

1. 2. 3. 4. 5.

Press Reset until the first digit of the phone number is displayed. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset until the next digit is displayed. Press Panel Silence to save and advance to the next digit. Repeat steps 3 and 4 until all digits are entered.
Note: If less than 20 digits are entered, press Panel

1. 2.

Press Reset until the correct hour is displayed. Press Panel Silence to save the hour setting and advance to the minute setting. The trouble buzzer sounds a long beep as confirmation. Press Reset until the correct minute is displayed. Press Panel Silence to save the minute setting and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

3. 4.

Silence again or Remote Disconnect to advance to the next program option. 6. When you press Panel Silence at the last digit (20th digit), the system automatically advances you to the next program option.

6. Select the FSDACT mode

8. Enter the (DACR1) secondary phone number

Description: Determines how the FSDACT operates. Settings: Single Line DACT Dual Line DACT (required by UL 864) Modem/LCD only LCD only Default: Dual Line DACT
To select the desired FSDACT mode:

Description: Specifies the secondary phone number that is used to contact the central monitoring station. Format: Up to 20 digits Default: Blank To enter the secondary phone number, follow the same steps you used to enter the primary phone number. (See Enter the (DACR1) primary phone number above.)

1. 2.

Press Reset to select the desired format. Press Panel Silence to save and advance to the next step.

3.10

FireShield Technical Reference Manual

Programming 9. Enter the (DACR1) account code 12. Enter retry count one

Description: Sets the account code for DACR1. This is the code that is used by the monitoring facilities receiver to identify the panel location and response information. Use a leading zero to enter a three-digit account code as four digits. Format: 4 digits Default: FFFF
To enter the account code:

Description: Sets the maximum number of failed attempts to deliver an alarm to a DACR. Settings: 5 10 retries Default: 5 (retries)
To enter retry count one:

1. 2.

Press Reset to change the retry count. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

1. 2. 3. 4. 5. 6.

Press Reset until the first digit of the account code is displayed. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset until the next digit is displayed. Press Panel Silence to save and advance to the next digit. Repeat steps 3 and 4 until all digits are entered. When you press Panel Silence at the last digit, the system automatically advances you to the next program option.

13. Enter retry time one

Description: Sets the delay time before trying to resend an alarm to a DACR. Format: 2 digits max (5 10 seconds) Default: 5 (seconds)
To enter retry time one:

10. Select the DACR1 alarm format

1. 2.

Press Reset to enter the retry time. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

Description: Specifies the type of alarm format the monitoring facility (DACR) will accept. Selecting either Contact ID or 4/2 loads default event codes (see Appendix E for more information). Settings: Contact ID EST 4/2 (SIA DC-02 P3 with hexadecimal event codes) Default: Contact ID
To select the DACR1 alarm format:

14. Enter the (DACR2) primary phone number Note: If a DACR2 primary phone number is not entered, skip

Enter the (DACR2) secondary phone number through Enter retry count two, inclusive. Description: Specifies the primary phone number that is used to contact the central monitoring station. Format: Up to 20 digits Default: Blank
To enter the primary phone number:

1. 2.

Press Reset to select the desired format. Press Panel Silence to save and advance to the next step. The trouble buzzer sounds a long beep as confirmation.

11. Select the restore option for CMS one

Description: Determines whether or not restoration events are sent to the first central monitoring station. Settings: Send restores No restores Default: Send restores
To select the restore option:

1. 2. 3. 4. 5.

Press Reset until the first digit of the phone number is displayed. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset until the next digit is displayed. Press Panel Silence to save and advance to the next digit. Repeat steps 3 and 4 until all digits are entered.
Note: If less than 20 digits are entered, press Panel

1. 2.

Press Reset to select the restore option for CMS one. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation.

Silence again or Remote Disconnect to advance to the next program option.

FireShield Technical Reference Manual

3.11

Programming

6.

When you press Reset at the last digit (20th digit), the system automatically advances you to the next program option.

Settings: Send restores No restores Default: Send restores


To select the restore option:

15. Enter the (DACR2) secondary phone number

Description: Specifies the secondary phone number that is used to contact the central monitoring station. Format: Up to 20 digits Default: Blank To enter the secondary phone number, follow the same steps you used to enter the primary phone number. (See Enter the (DACR2) primary phone number above.)
16. Enter the (DACR2) account code

1. 2.

Press Reset to select the restore option for CMS two. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation.

19. Enter retry count two

Description: Sets the maximum number of failed attempts to deliver an alarm to a DACR. Settings: 5 10 retries Default: 5 (retries)
To enter retry count two:

Description: Sets the account code for DACR2. This is the code that is used by the monitoring facilities receiver to identify the panel location and response information. Format: 4 digits Default: FFFF
To enter the account code:

1. 2.

Press Reset to change the retry count. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

1. 2. 3. 4. 5. 6.

Press Reset until the first digit of the account code is displayed. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset until the next digit is displayed. Press Panel Silence to save and advance to the next digit. Repeat steps 3 and 4 until all digits are entered. When you press Reset at the last digit, the system automatically advances you to the next program option.

20. Enter retry time two

Description: Sets the delay time before trying to resend an alarm to a DACR. Format: 2 digits max (5 10 seconds) Default: 5 (seconds)
To enter retry time two:

1. 2.

Press Reset to change the retry time. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

17. Select the DACR2 alarm format

Description: Specifies the type of alarm protocol the DACR will accept. Settings: Contact ID EST 4/2 (SIA DC-02 P3 with hexadecimal event codes) Default: Contact ID
To select the DACR2 alarm format:

21. Select tone or pulse dialing

Description: Specifies whether the phone line is set up for tone dialing or pulse dialing. Settings: Tone Pulse Default: Pulse
Note: Touch tone is recommended where available. To select tone or pulse dialing:

1. 2.

Press Reset to select the desired format. Press Panel Silence to save and advance to the next step. The trouble buzzer sounds a long beep as confirmation.

18. Select the restore option

1. 2.

Press Reset to select tone or pulse dialing for line 1. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation.

Description: Determines whether or not restoration events are sent to the second central monitoring station.

3.12

FireShield Technical Reference Manual

Programming

3. 4.

Press Reset to select tone or pulse dialing for line 2. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

2.

Press Panel Silence to save and advance to the next step. The trouble buzzer sounds a long beep as confirmation.

25. Enter the number of rings to answer

22. Select AC fail delay time

Description: Sets the number of rings that are ignored before answering an incoming modem call. Settings: 0 15 rings Default: 5 (rings)
To enter the number of rings:

Description: The AC fail delay lets you set the amount of time before the panel signals that it is operating with insufficient or no AC power. Settings: 6 hours (central station) 15 hours (remote station) Default: 6 hours
To select the AC fail delay time:

1. 2.

Press Reset to change the number of rings to answer. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

1. 2.

Press Reset to select the desired AC fail delay time. Press Panel Silence to save and advance to the next step. The trouble buzzer sounds a long beep as confirmation.

26. Select the ring type

Description: Specifies the type of ring expected when an incoming call is received. Default: Ring type (additional options to be added in future release). DACT answers any ring type after programmed ring count.
To select the ring type:

23. Enter the transmission test time

Description: Specifies the time of day the transmission test message is sent to the CMS. Values are in 24-hour time. Format: 0000 2359 Default: 0217
To enter the transmission test time:

1. 2.

Press Reset to select ring type. Press Panel Silence to save and advance to the next step. The trouble buzzer sounds a long beep as confirmation.

1. 2. 3. 4.

Press Reset to enter the hour. Press Panel Silence to save. The trouble buzzer sounds a long beep as confirmation. Press Reset to enter the minutes. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

27. Enable (disable) call back

24. Select the transmission test frequency

Description: Call back adds increased security when uploading or downloading. When an incoming call is received on line one, the panel establishes a connection and waits for a valid password. If call back is not enabled, uploading or downloading begins. If call back is enabled, the panel disconnects the incoming call and dials the programmed call back number. Once the connection is reestablished, uploading or downloading can begin. Settings: No Yes Default: No
To enable (disable) call back:

Description: Specifies the number of days between sending a transmission test message to the CMS.
Note: NFPA 72 and UL 864 require daily tests for commercial

systems. Settings: 0 = None 1 = Daily 2 = 30 days Default: 1 (daily)


To select the transmission test frequency:

1. 2.

Press Reset to select enable (disable) call back. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

1.

Press Reset to select the transmission test frequency.

FireShield Technical Reference Manual

3.13

Programming 28. Enter the call back phone number

Description: Specifies the phone number that is used for call back. Format: Up to 20 digits Default: Blank
To enter the call back phone number:

1. 2. 3. 4. 5.

Press Reset until the first digit of the phone number is displayed. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset until the next digit is displayed. Press Panel Silence to save and advance to the next digit. Repeat steps 3 and 4 until all digits are entered.
Note: If less than 20 digits are entered, press Panel

Low Batt Rcvr Mis Batt Rcvr Int Comm Tr Rcvr AC Fail Rcvr Charger Tr Rcvr Xfrmr 2 Tr Rcvr Aux Pwr Tr Rcvr Periph Trb Rcvr Line 1 Trb Rcvr Line 2 Trb Rcvr Delivery Tr Rcvr After programming the receiver locations, continue with the steps described under Enter the system trouble restore code.
1. Select CMS locations for event reporting

Description: Specifies which CMS receives each event. Settings: None CS 1 CS 2 CS 1 and 2 Default: CS 1
To select the CMS locations for event reporting:

Silence again or Remote Disconnect to advance to the next program option. 6. When you press Reset at the last digit (20th digit), the system automatically advances you to the next program option.

1. 2.

Press Reset to select the desired CMS location. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation. Repeat steps 1 and 2 to set the CMS location for each option. When you reach the last option, proceed to "Enter the system trouble restore code" below.

Event notification programming


Event notification programming determines where events are sent. Events can be sent to the primary, secondary, or both central monitoring stations (CMS), or you can choose not to send the event at all. To program event notification, follow these general steps: 1. 2. Select CMS locations for event reporting Enter the system trouble restore code

3. 4.

Note: If you are only using one central monitoring station and

2. Enter the system trouble restore code

are using the default settings, no further programming is required. You can exit from programming by removing the program jumper. The first event notification programming option after completing Select the restore option is Panel Tst Rcvr. Twenty-one event receiver locations must be programmed using steps described below, under Select CMS locations for event reporting. CS Tst Rcvr CS AB Tst Rcvr Walk Tst Rcvr Drill Rcvr Reset Rcvr Program Mode Rcvr DACT Disab Rcvr Panel Sil Rcvr Signal Sil Rcvr Grd Fault Rcvr

Description: Sets the code that is transmitted to the CMS with trouble restoral events. Format: 1 digit (0 9 and A F) Default: See Appendix E Default event codes. This can be changed if needed.
To enter the system trouble restore code:

1. 2.

Press Reset to increment the restore code if it needs to be changed. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

3.14

FireShield Technical Reference Manual

Programming

Circuit programming
Circuit programming defines the routes and codes used to report IDC and NAC events. Unless the options described below are changed, the factory default event codes are sent to CS 1 only. If the default selections are acceptable, you can skip to End programming below.
Note: IDC disabled and NAC disabled events are

To select the receiver for each IDC event:

1. 2.

Select an IDC for programming by pressing the Disable button for that IDC. Determine the zone type assigned to the selected IDC. Refer to the Panel programming worksheet you completed. Use the table shown above to determine which event types need to be configured. Press Remote Disconnect or Walk Test to select the desired event type. Press Reset to select the desired receiver. Press Panel Silence to save the setting. The trouble buzzer sounds a long beep as confirmation. Repeat steps 4 and 5 for each event type you need to configure. Repeat steps 1 through 7 for each IDC you want to program. When the required IDCs have been programmed, press Remote Disconnect to advance to the next program option.

automatically routed to the receiver you select for the IDC trouble activation and NAC trouble activation events. To program the circuits, youll follow these general steps: 1. 2. 3. 4. 5. 6. 7. 8. Select the receiver for each IDC event Select the receiver for each NAC trouble event Set up or change system event codes Set up or change IDC event codes Set up or change the IDC zone restoration code Set up or change the NAC trouble code Set up or change the NAC trouble restoration code End programming

3. 4. 5. 6. 7. 8. 9.

1. Select the receiver for each IDC event

Description: Determines where alarm, waterflow, trouble, supervisory, and monitor IDC events are reported. An IDC has five possible events. You only need to program those events that apply to the zone type of the selected IDC. For example, if the IDC is configured as alarm-verified (or alarm-unverified) you only need to configure the alarm and trouble events. You dont need to select a receiver for the waterflow, supervisory, or monitor events for that IDC. The following table lists the events that apply to each zone type.
Event types Zone type Alarm Waterflow Waterflow / Supervisory Supervisory Monitor Alarm X X X Waterflow Trouble X X X X X X X X Supervisory Monitor

2. Select the receiver for each NAC trouble event

Description: Determines where an NAC trouble event is reported.


Note: You must program each NAC during this step.

Settings: None CS 1 CS 2 CS 1 and 2 Default: CS 1


To select the receiver for each NAC trouble event:

1. 2. 3. 4. 5.

Select an NAC for programming by pressing the Disable button for that NAC. Press Reset to select the desired receivers. Press Panel Silence to save the setting. The trouble buzzer sounds a long beep as confirmation. Repeat steps 1 through 3 for each NAC you want to program. When all NACs have been programmed, press Remote Disconnect to advance to the next program option.

Settings: None CS 1 CS 2 CS 1 and 2 Default: CS 1

3. Set up or change system event codes

Description: Defines the 4/2 event codes (reset, drill, trouble silence, etc.) that are sent to the CMS for system level events.

FireShield Technical Reference Manual

3.15

Programming

Format: 2 digits (0 9 and A F) Default: See Appendix E Default event codes. These can be changed if needed.
Note: If you are using Contact ID or the default 4/2 codes, you

To change the IDC zone restoration code:

1. 2.

Press Reset to change the IDC zone restoration code. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

can skip ahead to End programming now.


To change system event codes:

6. Set up or change the NAC trouble code

1. 2. 3. 4. 5. 6.

Press Reset or Signal Silence & Drill to scroll to the event code that you want to change. Press Reset to change the first digit of the code. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset to change the second digit. Press Panel Silence to save. Press Reset to advance to the next event code.

Description: Sets the 4/2 event code that is transmitted to the CMS for a NAC trouble event. Format: 2 digits (0 9 and A F) Default: See Appendix E Default event codes. This can be changed if needed.
To change the NAC trouble code:

1. 2. 3. 4. 5. 6. 7.

Select an NAC for programming by pressing the Disable button for that NAC. Press Reset to change the first digit of the code. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset to change the second digit. Press Panel Silence to save. Repeat steps 1 through 5 for each NAC you want to program. Press Reset to advance to the next program option.

4. Set up or change IDC event codes

Description: Defines the 4/2 event codes (alarm, sup, trouble, etc.) that are sent to the CMS for IDC events. Format: 2 digits (0 9 and A F) Default: See Appendix E Default event codes. These can be changed if needed.
To change IDC event codes:

1. 2. 3. 4. 5. 6. 7. 8.

Select an IDC for programming by pressing the Disable button for that IDC. Press Reset or Signal Silence & Drill to scroll to the event code that you want to change. Press Reset to change the first digit of the code. Press Panel Silence to save and advance to the next digit. The trouble buzzer sounds a long beep as confirmation. Press Reset to change the second digit. Press Panel Silence to save. Repeat steps 1 through 6 for each IDC you want to program. Press Reset to advance to the next event code.

7. Set up or change the NAC trouble restoration code

Description: Sets the 4/2 event code that is transmitted to the CMS for a NAC restoral event. Format: 1 digit (0 9 and A F) Default: See Appendix E Default event codes. This can be changed if needed.
To change the NAC trouble restoration code:

1. 2.

Press Reset to change the NAC trouble restoration code. Press Panel Silence to save and advance to the next program option. The trouble buzzer sounds a long beep as confirmation.

5. Set up or change the IDC zone restoration code

Description: Sets the 4/2 event code that is transmitted to the CMS for an IDC restoral event. Format: 1 digit (0 9 and A F) Default: See Appendix E Default event codes. This can be changed if needed.

8. End programming

Programming is complete.
To end programming:

1.

Press Panel Silence.

3.16

FireShield Technical Reference Manual

Programming

The system takes you back to the beginning of FSDACT programming (Program DACT). 2. Remove the program jumper PRG. You can store the jumper on one pin of the jumper.

Editing previously programmed information


You may find it necessary to change information that you previously programmed (e.g. if a phone number changes).
To edit previously programmed information:

1. 2. 3. 4. 5. 6.

Install program jumper PRG. Press Remote Disconnect until DACT Programming is displayed. Press Reset until Yes selected. Press Panel Silence to save. Enter your passcode. Press Remote Disconnect to advance to the programming option you want to change. The currently stored data is displayed. Edit the program option with the desired setting. Use the program buttons to enter the information. Press Panel Silence to save. Edit other program options as needed.

7. 8. 9.

10. Exit from program mode by removing jumper PRG.

Other FSDACT options


The following options can only be changed using the FireShield Configuration Utility. Refer to the FireShield Configuration Utility online help system for details on programming these options.
Swinger shutdown

Description: Automatically inhibits transmission of a single event more consecutive times than the value entered. Format: 0 255 Default: 0 (none)
Contact ID

Contact ID codes can only be changed when using the configuration utility.

FireShield Technical Reference Manual

3.17

Programming

3.18

FireShield Technical Reference Manual

Chapter 4

Canadian tests for grounds, opens, and shorts


ULC requires that you test ground fault, open circuit, and short circuit indications. For ground fault tests, directly short one leg of the circuit to chassis ground. The Ground Fault and Trouble LEDs must light.

Maintenance

Preventive maintenance
Before commencing testing, notify all areas where the alarm sounds and off-premises locations that receive alarm and trouble transmissions that testing is in progress. Records of all testing and maintenance shall be kept as required by the authority having jurisdiction. Required tools: -Slotted screwdriver, insulated -Digital multimeter -1.1 k, 1 W resistor -12 in (30.5 cm) jumper lead with alligator clips -Panel door key -Sound level meter A complete check of installed field wiring and devices should be made at regular intervals in accordance with NFPA 72, Canadian Electrical Code Part I, ULC S524, and S536 requirements. This includes testing all alarm and supervisory initiating devices and circuits and any off-premises connections. Panel operation should be verified in the alarm, supervisory, and trouble modes. To ensure that the panel can be powered when primary power is lost, the batteries should be periodically inspected, tested, and replaced (at a minimum) every four years.

For NAC and IDC open circuit tests, remove the EOL resistor from the last device on the circuit. The Trouble LED must light. For NAC short circuit testing, place a short across each NAC output individually. The individual NAC LED must light as well as the common LED. For AUX power short circuit testing, place a short across the +24 V and -24 V at the panel. The common trouble LED must light. For communications testing, place a short across C+ and C-. The annunciator trouble LED must light.

Preventive maintenance schedule


Refer to NFPA 72, Chapter 7 Inspection, Testing, and Maintenance, Canadian Electrical Code Part I, ULCS524, or ULCS536 for more information on required inspection and testing methods and frequency of fire alarm systems and devices. For detector sensitivity and functionality testing, refer to the detector manufacturer's installation instructions.

FireShield Technical Reference Manual

4.1

Maintenance

4.2

FireShield Technical Reference Manual

Appendix A

Standby current: three-zone - 110 mA, five-zone - 120 mA, ten-zone - 145 mA Alarm current: three-zone - 145 mA, five-zone - 170 mA, ten-zone - 250 mA) [2] The maximum battery size the panel can charge is 18 Ah (Power-Sonic P/N PS-12180-NB or equivalent). Refer to "Panel specifications" in Chapter 2 for more information. If batteries over 7 Ah are required for the three- and fivezone panels, you must use the BC-2 battery cabinet. Refer to installation sheet P/N 3100027. [3] Use maximum value or actual calculated value from Form B. The IDC alarm current is included in the panel alarm current.

Calculations

Battery calculation worksheet


Use this worksheet to determine the minimum amperage capacity required for the panel's standby battery. You can obtain operating current requirements for notification appliances from their respective installation sheets.
Notes

[1] Base panel includes the main controller board with no load, only EOL resistors.
Standby Current (mA) Base panel [1] FSDACT (optional) Aux current (see Form A) IDC detector current [see Form B] NAC 1 load [see page A.3] NAC 2 load [see page A.3] NAC 3 load [see page A.3] NAC 4 load [see page A.3] 0 0 0 0 [3] (40) (60) Alarm Current (mA)

Total current Required standby and alarm time Standby time 24 or 60 hour Alarm time 5 min = 0.083 hr 10 min = 0.167 hr 15 min = 0.250 hr 30 min = 0.500 hr mAh 1000 Battery amp hour total = 1.2 Minimum battery size [2] = Ah Ah

mAh

mAh

FireShield Technical Reference Manual

A.1

Calculations

Form A
Module Quantity Standby current (mA) 12 8 30 8 Qty Standby current (mA) Alarm current (mA) 48 35 41 65 Qty Alarm current (mA)

FSRSI [1] FSRZI-A [1] FSRRM common [1] FSRRM zone [1] Other AUX Total AUX [5] [6]

Form B (Note: Calculate IDC detector load or use maximum load.)


IDC IDC1 IDC2 IDC3 IDC4 IDC5 IDC6 IDC7 IDC8 IDC9 IDC10 Total current for all IDCs = Max IDC standby current: FS302 = 4.5 mA, FS502 = 7.5 mA, and FS1004 = 15.0 mA Quantity of detectors [2] Detector current (mA) [3] Total standby current [4] (quantity x current in mA)

Notes [1] Use of FSRSI, FSRZI-A, and FSRRM is limited as follows: Three- and five-zone panels support 2 FSRSIs, 2 FSRZI-As, and 4 FSRRMs, ten-zone panels support 2 FSRSIs, 4 FSRZI-As, and 6 FSRRMs. [2] See the FireShield UL and ULC Compatibility List (P/N 3100468) for the maximum number of detectors per IDC. [3] See FireShield UL and ULC Compatibility List (P/N 3100468) for detector current ratings. [4] Maximum current per IDC may not exceed 1.5 mA. [5] Aux power supplied by panel cannot exceed 0.5 A. If more than 0.5 A is required, you must use a compatible UL/ULC listed fire alarm power supply. [6] When using an auxiliary power supply, you must connect the -24 OUT connection on the panel to the negative connection on the auxiliary power supply. Refer to the installation section for more information.

A.2

FireShield Technical Reference Manual

Calculations

Notification appliance voltage drop calculation


NAC 1 voltage drop calculations Circuit length feet Panel voltage [4] x Total circuit current [2] amps End of line voltage [3] = x Voltage drop Wire resistance per 1000 ft [1] 1000 = Panel voltage [4] = Voltage drop % Voltage drop

Voltage drop

NAC 2 voltage drop calculations Circuit length feet Panel voltage [4] x Total circuit current [2] amps End of line voltage [3] = x Voltage drop Wire resistance per 1000 ft [1] 1000 = Panel voltage [4] = Voltage drop % Voltage drop

Voltage drop

NAC 3 voltage drop calculations Circuit length feet Panel voltage [4] x Total circuit current [2] amps End of line voltage [3] = x Voltage drop Wire resistance per 1000 ft [1] 1000 = Panel voltage [4] = Voltage drop % Voltage drop

Voltage drop

NAC 4 voltage drop calculations Circuit length feet Panel voltage [4] Notes [1] Use 3.5 for 12 AWG and 2.5 sq mm wire, 5.2 for 14 AWG and 1.5 sq mm wire, 8.0 for 16 AWG and 1.0 sq mm wire, and 13.0 for 18 AWG and 0.75 sq mm wire. [2] Use the filtered 20 Vdc Average Operating Current ratings found on the installation or catalog sheet of each device. [3] Cannot drop below 17 Vdc. [4] 18.6 V for 230 V at 50 Hz, 18.8 V for 230 V 60 at Hz, 18.9 V for 120 V at 60 Hz x Total circuit current [2] amps End of line voltage [3] = x Voltage drop Wire resistance per 1000 ft [1] 1000 = Panel voltage [4] = Voltage drop % Voltage drop

Voltage drop

FireShield Technical Reference Manual

A.3

Calculations

Notification appliance circuit maximum wire length calculation


Use this worksheet to determine the maximum wire length of a notification appliance circuit. Fill in one worksheet for each NAC connected to the panel.
Wire length matrix

Maximum wire length Current required 0.25 0.50 0.75 1.00 1.25 1.50 18 AWG 584 292 194 146 116 92 16 AWG 950 474 316 236 190 158 14 AWG 1460 730 486 364 292 242 12 AWG 2170 1084 722 542 434 362

Wire lengths in the following table are based on a voltage drop of 1.9 volts or 10% and total load at the end of the line.

Maximum signal loss allowed [1] 1000

Wire resistance per 1000 ft/pair [2]

Total operating current required [3] Maximum circuit length

A ft

Notes [1] 1.6 V for 230 V at 50 Hz 1.8 V for 230 V at 60 Hz 1.9 V for 120 V at 60 Hz [2] Use 3.5 for 12 AWG and 2.5 sq mm wire, 5.2 for 14 AWG and 1.5 sq mm wire, 8.0 for 16 AWG and 1.0 sq mm wire, and 13.0 for 18 AWG and 0.75 sq mm wire. [3] Use the filtered 20 Vdc Average Operating Current ratings found on the installation or catalog sheet of each device.

A.4

FireShield Technical Reference Manual

Appendix B

Programming templates
Panel programming worksheet
Project name _____________________________ Project address ___________________________________________________________ Programmed by __________________________ Date ____________ Tested by ____________________________ Date ____________ [1] Load defaults [2] Find annunciators No (1) Yes (2)
ALARM 16

Panel LEDs and binary number values


TROUBLE 8 SUP 4 Binary values GND FAULT POWER 2 DISABLE 1

Peripherals installed Peripherals found

[3] Auto NAC silence timer [4] Aux power reset [5] Signal silence inhibit timer [6] IDC zone types Alarm-unverified (1) Alarm-verified (2) Waterflow (retard) (3) Waterflow (no retard) (4) Waterflow (retard) / supervisory(latching) (5) Waterflow (no retard) / supervisory(latching) (6) Supervisory (latching) (7) Monitor (8) NAC Assignment NAC1 NAC2 NAC3 NAC4 [7] IDC class Class B (1) Class A (2) [8] NAC classes Class B (1) Class A (2) [9] NAC outputs Continuous (1) Temporal (3-3-3) (2) GENESIS synch/silence (3) [10] NAC silenceable NAC1 IDC1 IDC1

None (1) No (1) None (1) IDC2

20 minutes (2) Yes (2)

ANNUN TROUBLE

BATT TROUBLE

WALK TEST

SIGNAL SILENCED

16

1 minute (2) IDC3 IDC4 IDC5 IDC6 IDC7

4 Binary values

IDC8

IDC9

IDC10

IDC2

IDC3

IDC4

IDC5

IDC6

IDC7

IDC8

IDC9

IDC10

NAC2

NAC3

NAC4

[ ] ( )

= Top row of LEDs binary number value = Bottom row of LEDs binary number value = Factory default settings

No (1) Yes (2)

No (1) Yes (2)

No (1) Yes (2)

No (1) Yes (2)

Button definitions (programming mode) Remote disconnect - Selects next option Walk test - Selects previous option Reset - Selects next setting Signal Silence & Drill - Selects previous setting Panel Silence - Saves program setting

FireShield Technical Reference Manual

B.1

Programming templates

FSDACT programming worksheet


DACT setup Access passcode Load defaults Edit passcode Date Time DACT mode Receiver 1 (DACR1) Setup Phone 1 Phone 2 Account Format Restores Retry Count Retry Time Contact ID Send Restores (05 10) 05 (05 10) 05 (0 9, A F) FFFF EST 4/2 No Restores Ex. 19415551212 Ex. 19415551212 (HHMM) 0000 Single line DACT Dual line DACT Modem/LCD LCD only Yes No (0 9, A F) (MMDDYYYY) 01012002 (0 9, A F) 1111111

Receiver 2 (DACR2) Setup Phone 1 Phone 2 Account Format Restores Retry Count Retry Time Contact ID Send Restores (05 10) 05 (05 10) 05 (0 9, A F) FFFF EST 4/2 No Restores Ex. 19415551212 Ex. 19415551212

DACT Dialing Properties Setup Tone/Pulse Line 1 Tone/Pulse Line 2 AC Fail Delay Transmission Test Time Transmission Test Freq. Rings to Answer Ring Type Callback Enable Callback Number Tone Tone 6 Hours Pulse Pulse 15 Hours (0000 2359) 0217 (00 02) 01 (00 15) 05 Ring type No DACT answers any ring type after programmed ring count Yes

Note: Default settings are shown in boldface type.

B.2

FireShield Technical Reference Manual

Programming templates
System event reporting setup Event Panel test Panel abnormal test Walk test Drill Reset Program mode DACT Disabled Panel silence Signal silence Ground fault Low battery Missing battery Internal comm trouble AC fail Charger trouble Transformer 2 trouble Aux power trouble Peripheral trouble DACT line 1 trouble DACT line 2 trouble DACT delivery trouble Where to report the event None None None None None None None None None None None None None None None None None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 CS 1 (0 F) D CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code DF 6F AF AD AB C1 AE CA AC 66 6C 6C AA 69 6B 6A 65 6D 68 6E 67

System trouble restoral (4/2 code) Zone settings - IDC 1

Note: For IDCs, program only those events that apply to the IDC zone type you specified on the Panel programming worksheet. Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Zone settings - IDC 2 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Zone settings - IDC 3 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 13 23 73 33 53 Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 12 22 72 32 52 Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 11 21 71 31 51

Note: Default settings are shown in boldface type.

FireShield Technical Reference Manual

B.3

Programming templates
Zone settings - IDC 4 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Zone settings - IDC 5 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Zone settings - IDC 6 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Zone settings - IDC 7 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Zone settings - IDC 8 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Zone settings - IDC 9 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 19 29 79 39 59 Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 18 28 78 38 58 Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 17 27 77 37 57 Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 16 26 76 36 56 Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 15 25 75 35 55 Where to report the event None None None None None CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 14 24 74 34 54

Note: Default settings are shown in boldface type.

B.4

FireShield Technical Reference Manual

Programming templates
Zone settings - IDC 10 Event Alarm activation Waterflow activation Trouble activation Supervisory activation Monitor activation Zone restoral (4/2 code) NAC settings - NAC 1 Event Trouble activation NAC settings - NAC 2 Event Trouble activation NAC settings - NAC 3 Event Trouble activation NAC settings - NAC 4 Event Trouble activation Where to report the event None (0 F) D CS 1 CS 2 CS 1 & 2 4/2 event code 64 Where to report the event None CS 1 CS 2 CS 1 & 2 4/2 Event code 63 Where to report the event None CS 1 CS 2 CS 1 & 2 4/2 event code 62 Where to report the event None CS 1 CS 2 CS 1 & 2 4/2 event code 61 Where to report the event None None None None None (0 F) E CS 1 CS 1 CS 1 CS 1 CS 1 CS 2 CS 2 CS 2 CS 2 CS 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 CS 1 & 2 4/2 event code 1A 2A 7A 3A 5A

NAC Trouble restoral (4/2 code) Other FSDACT options

Note: These options can only be changed using the FireShield Configuration Utility. Swinger shutdown Contact ID codes Code Description Code Description (0 255) 000

Note: Default settings are shown in boldface type.

FireShield Technical Reference Manual

B.5

Programming templates

Contact ID codes Code Description Code Description

B.6

FireShield Technical Reference Manual

Appendix C

Three-zone panel

LINE WARNING: Never replace fuse while circuit is energized. Replacement fuse must be of equivalent size and type. CAUTION: The middle connection on the terminal block makes a mechanical connection to the chassis even with the ground wire removed. 5 A, 250 V, SLO-BLO (Littlefuse P/N 218005) DACT/Dialer (optional) DACT connector J2 NAC1 NAC1+ NAC2 NAC2+ PRG IDC1+ C C+ 24VOUT PRG Programming mode 24VOUT+ Normal mode Jumper Setting Description IDC1 IDC2+ IDC2 IDC3+ IDC3 RECHARGEABLE BATTERY CIRCUIT Voltage: 24 Vdc Amp-hour capacity: 18 Ah maximum sealed lead acid batteries only Note: Standby batteries larger than 7 Ah must be installed in a BC-2 battery cabinet. BLACK JP1 wire loop [12]

EARTH GND

NEUTRAL

EGND

FireShield Technical Reference Manual


NOTIFICATION APPLIANCE CIRCUITS [2] [3] [5] [11] Class B (Style Y) Operating voltage: 24 Vfwr Operating current: 1.5 A/circuit, 1.5 A total Circuit impedance: 13, 0.03 F, max EOLR: 4.7 k, 1/2 W (P/N EOL4.7)

DETAIL A

COMMON TROUBLE RELAY [10] 1 A @ 30 Vdc, resistive Nonsupervised

+ +

+ +

EOLR

Jumper settings and wiring diagrams

See COMMON SUPERVISORY RELAY [10] DETAIL A 1 A @ 30 Vdc, resistive Nonsupervised COMMON ALARM RELAY [10] 1 A @ 30 Vdc, resistive Nonsupervised REMOTE MODULE COMMUNICATION BUS 13 , 0.03 F, max

AUXILIARY/SMOKE POWER OUTPUT 24 Vdc, nominal @ 500 mA

+ + +

+ + +

EOLR

MAIN SUPPLY CIRCUIT 120 V, 60 Hz, 0.8 A or 230 V, 50/60 Hz, 0.4 A from dedicated branch supply 24VAC IN E1 E2 RED

INITIATING DEVICE CIRCUITS [2] [3] [9] [11] Class B (Style B) Operating voltage: 16.3 - 25.7 Vdc Operating current: 1.5 mA/circuit, max Circuit impedance: 13, 0.03 F, max EOLR: 4.7 k, 1/2 W (P/N EOL4.7) CAUTION: Break the wire run at each field device to provide proper connection supervision. Do not loop wires under terminals.

12 Vdc Battery

12 Vdc Battery

C.1

Jumper settings and wiring diagrams


REMOTE MODULE AND REMOTE RELAY WIRING [6]

C C+ 24VDC+ 24VDC

POWER ALARM SUP TBL GND FLT


SILENCE LMPTST

REMOTE RELAY MODULE (RRM)

TYPICAL FOUR-WIRE SMOKE DETECTOR CIRCUIT [2] [3] [7] IDC1+ 24VDC+ 24VDC IDC1 4.7 k WATERFLOW / SUPERVISORY COMBINATION CIRCUIT [4] [8] IDC1+ IDC1 NOTES 1 [2] [3] [4] All wiring is power-limited except for AC power and battery wiring. All wiring is supervised unless noted otherwise. Class A wiring not supported Listed EOLRs must be installed as shown for proper supervision For UL installations use EOLR P/N EOL3.6-1.1 which includes one 1.1 k (P/N EOL1.1) and one 3.6 k (P/N EOL3.6) resistor. For ULC installations use EOL-P1 and select the 1.1 k and 3.6 k resistors. Marking indicates output signal polarity when the circuit is active. Polarity reverses when the circuit is not active. Wire notification appliances accordingly. Notification appliance polarity shown in active state. 1.1 k 3.6 k [7] UL/ULC LISTED EOL RELAY (shown energized) [6]

Keep power-limited wiring in the shaded area and nonpower-limited wiring in the unshaded area at all times.

Requires continuous 24 Vdc from the AUX Power terminals or a power-limited UL/ULC listed compatible fire signaling power supply IDC circuits do not support alarm verification using fourwire smokes. Requires resettable 24 Vdc from AUX Power terminals. Combination circuits consist of waterflow switches (WF) and their associated valve tampers (SS). Automatic and manually activated alarm initiating devices can be installed on the same IDC circuit regardless of circuit type except for combination circuits (option 6, setting 5 and 6)

WF

WF

SS

SS

[8] [9]

[10] Relay circuits can only be connected to power-limited sources [11] Installation limits under jurisdiction of local authority [12] Refer to the FireShield Technical Reference Manual (P/N 3100353) for the topic "Installing the FSDACT."

[5]

C.2

FireShield Technical Reference Manual

Five-zone panel

LINE WARNING: Never replace fuse while circuit is energized. Replacement fuse must be of equivalent size and type. CAUTION: The middle connection on the terminal block makes a mechanical connection to the chassis even with the ground wire removed. 5 A, 250 V, SLO-BLO (Littlefuse P/N 218005) DACT/Dialer (optional) DACT connector J2 TB2 Jumper PRG Programming mode NAC1 and NAC2 = Class B JP1A &JP6A NAC1 = Class A Out NAC2 = Class A Return IDC1 and IDC2 = Class B JP3A &JP2A IDC1 = Class A Out IDC2 = Class A Return IDC3 and IDC4 = Class B JP4A &JP5A IDC3 = Class A Out IDC4 = Class A Return JP4A & JP5A JP3A & JP2A PRG TB3 IDC1+ IDC1 IDC2+ IDC2 IDC3+ IDC3 IDC4+ IDC4 IDC5+ IDC5 Normal mode JP6A JP1A Setting Description JP1 wire loop [12] CAUTION: The panel does not indicate when JP6A is missing. A shorted NAC circuit may damage the equipment if NAC jumpers are missing or set incorrectly.

EARTH GND

NEUTRAL

CAUTION: Break the wire run at each field device to provide proper connection supervision. Do not loop wires under terminals.

EGND

FireShield Technical Reference Manual


TB5 NOTIFICATION APPLIANCE CIRCUITS [2] [3] [5 [11] Class B (Style Y) or Class A (Style Z) Operating voltage: 24 Vfwr Operating current: 1.5 A /circuit, 2.5 A total Circuit impedance: 13 , 0.03 F, max EOLR: 4.7 k, 1/2 W (P/N EOL4.7) NAC1 NAC1+ NAC2 NAC2+

DETAIL A

COMMON TROUBLE RELAY [10] 1 A @ 30 Vdc, resistive Nonsupervised

+ +

+ +

EOLR

EOLR

C C+ 24VOUT 24VOUT+

See COMMON SUPERVISORY RELAY [10] DETAIL A 1 A @ 30 Vdc, resistive Nonsupervised COMMON ALARM RELAY [10] 1 A @ 30 Vdc, resistive Nonsupervised REMOTE MODULE COMMUNICATION BUS 13 , 0.03 F, max AUXILIARY/SMOKE POWER OUTPUT 24 Vdc,nominal @ 500 mA MAIN SUPPLY CIRCUIT 120 V, 60 Hz, 0.8 A or 230 V, 50/60 Hz, 0.4 A from dedicated branch supply

24VAC IN E1 E2 TB1 12 Vdc Battery BLACK RED

RECHARGEABLE BATTERY CIRCUIT Voltage: 24 Vdc Amp-hour capacity: 18 Ah maximum sealed lead acid batteries only

+ + + + +

+ + + + +
INITIATING DEVICE CIRCUITS [2] [3] [9] [11] Class B (Style B) or Class A (Style D) Operating voltage: 16.3 - 25.7 Vdc Operating current: 1.5 mA/circuit, max Circuit impedance: 13 , 0.03 F, max EOLR: 4.7 k, 1/2 W (P/N EOL4.7) 12 Vdc Battery Note: Standby batteries larger than 7 Ah must be installed in a BC-2 battery cabinet.

Jumper settings and wiring diagrams

C.3

Jumper settings and wiring diagrams


REMOTE MODULE AND REMOTE RELAY WIRING [6]

C C+ 24VDC+ 24VDC

POWER ALARM SUP TBL GND FLT


SILENCE LMPTST

REMOTE RELAY MODULE (RRM)

TYPICAL FOUR-WIRE SMOKE DETECTOR CIRCUIT [2] [3] [7] IDC1+ 24VDC+ 24VDC IDC1 4.7 k WATERFLOW / SUPERVISORY COMBINATION CIRCUIT [4] [8] IDC1+ IDC1 NOTES 1 [2] [3] [4] All wiring is power-limited except for AC power and battery wiring. All wiring is supervised unless noted otherwise. Class A wiring not supported Listed EOLRs must be installed as shown for proper supervision For UL installations use EOLR P/N EOL3.6-1.1 which includes one 1.1 k (P/N EOL1.1) and one 3.6 k (P/N EOL3.6) resistor. For ULC installations use EOL-P1 and select the 1.1 k and 3.6 k resistors. Marking indicates output signal polarity when the circuit is active. Polarity reverses when the circuit is not active. Wire notification appliances accordingly. Notification appliance polarity shown in active state. 1.1 k 3.6 k [7] UL/ULC LISTED EOL RELAY (shown energized) [6]

Keep power-limited wiring in the shaded area and nonpower-limited wiring in the unshaded area at all times.

Requires continuous 24 Vdc from the AUX Power terminals or a power-limited UL/ULC listed compatible fire signaling power supply IDC circuits do not support alarm verification using fourwire smokes. Requires resettable 24 Vdc from AUX Power terminals. Combination circuits consist of waterflow switches (WF) and their associated valve tampers (SS). Automatic and manually activated alarm initiating devices can be installed on the same IDC circuit regardless of circuit type except for combination circuits (option 6, setting 5 and 6)

WF

WF

SS

SS

[8] [9]

[10] Relay circuits can only be connected to power-limited sources [11] Installation limits under jurisdiction of local authority [12] Refer to the FireShield Technical Reference Manual (P/N 3100353) for the topic "Installing the FSDACT."

[5]

C.4

FireShield Technical Reference Manual

JP1 wire loop [13] DACT/Dialer (optional) DACT connector J2 TB2 NAC1 NAC1+ NAC2 NAC2+ TB4 NAC3 NAC3+ NAC4

Ten-zone panel

TB3 COMMON TROUBLE RELAY [11] 1 A @ 30 Vdc, resistive Nonsupervised

NOTIFICATION APPLIANCE CIRCUITS [2] [3] [5] [8] [12] Class B (Style Y) or Class A (Style Z) Operating voltage: 24 Vfwr Operating current: 1.5 A/circuit, 2.5 A total Circuit impedance: 13 , 0.03 F, max EOLR: 4.7 k, 1/2 W (P/N EOL4.7)
EOLR

MAIN SUPPLY CIRCUIT 120 V, 60 Hz, 1.6 A 230 V, 50/60 Hz, 0.8 A from dedicated branch supply CAUTION: The panel does not indicate when JP13 or JP14 are missing. A shorted NAC circuit may damage the equipment if NAC jumpers are JP14 missing or set incorrectly. =B JP1
Jumper PRG C C+ 24VOUT 24VOUT+ JP6 & JP14 A JP2 & JP3 A JP4 & JP5 A JP7 & JP8 B A TB1 EGND 24VAC IN A JP11 & JP12 A B JP9 & JP10 B IDC5 and IDC6 = Class B IDC5 = Class A out IDC6 = Class A return IDC7 and IDC8 = Class B IDC7 = Class A out IDC8 = Class A return IDC9 and IDC10 = Class B IDC3 = Class A out IDC4 = Class A return TB6 B IDC3 and IDC4 = Class B IDC1 = Class A out IDC2 = Class A return B IDC1 and IDC2 = Class B NAC3 = Class A out NAC4 = Class A return B NAC3 and NAC4 = Class B A NAC1 = Class A out NAC2 = Class A return JP1 & JP13 B NAC1 and NAC2 = Class B ON Programming mode OFF Normal mode Position Description

SEE DETAIL A =A

FireShield Technical Reference Manual


+ + + +
COMMON SUPERVISORY RELAY [11] 1 A @ 30 Vdc, resistive Nonsupervised COMMON ALARM RELAY [11] 1 A @ 30 Vdc, resistive Nonsupervised REMOTE MODULE COMMUNICATION BUS 13 , 0.03 F, max

PRG JP13 JP6


TB5 NAC4+

AUXILIARY/SMOKE POWER OUTPUT 24 Vdc,nominal @ 500 mA

+ +
IDC1+ IDC1 IDC2+ IDC2

+ +
EOLR

CAUTION: The middle connection on the terminal block makes a mechanical connection to the chassis even with the ground wire removed.
L

JP3 & JP2

IDC3+ IDC3 IDC4+ IDC4

LINE N

EARTH GND

5A, 250V, SLO-BLO (Littlefuse P/N 218005)

NEUTRAL

JP4 & JP5

IDC5+ IDC5

WARNING: Never replace fuse while circuit is energized. Replacement fuse must be of equivalent size and type.

+ + + + +
IDC6+

+ + + + +

DETAIL A

JP7 & JP8

IDC6 IDC7+ IDC7 IDC8+ IDC8 IDC9+

JP9 & JP10


IDC9 = Class A out IDC10 = Class A return

IDC9 IDC10+

XTR3A120 or XTR3A230 (OPTIONAL) E1 E2 RED

RECHARGEABLE BATTERY CIRCUIT Voltage: 24 Vdc Amp-hour capacity: 18 Ah maximum sealed lead acid batteries only JP11 & JP12
BLACK

IDC10

+ + + + +

+ + + + +
INITIATING DEVICE CIRCUITS [2] [3] [9] [12] Class B (Style B) or Class A (Style D) Operating voltage: 16.3 - 25.7 Vdc Operating current: 1.5 mA/circuit, max Circuit impedance: 13 , 0.03 F EOLR: 4.7 k, 1/2 W (P/N EOL4.7)
12 Vdc Battery 12 Vdc Battery

Jumper settings and wiring diagrams

CAUTION: Break the wire run at each field device to provide proper connection supervision. Do not loop wires under terminals.

C.5

Jumper settings and wiring diagrams

REMOTE MODULE AND REMOTE RELAY WIRING [6]

C C+ 24VDC+ 24VDC

POWER ALARM SUP TBL GND FLT


SILENCE LMPTST

REMOTE RELAY MODULE (RRM)

TYPICAL FOUR-WIRE SMOKE DETECTOR CIRCUIT [2] [3] [7] IDC1+ 24VDC+ 24VDC IDC1 IDC2+ IDC2 4.7 k UL/ULC LISTED EOL RELAY (shown energized)

WATERFLOW / SUPERVISORY COMBINATION CIRCUIT [4] [10] (Only Class B allowed)


IDC1+ IDC1 1.1 k 3.6 k

WF

WF

SS

SS

[6] Requires continuous 24 Vdc from the AUX Power terminals or a power-limited UL/ULC listed compatible fire signaling power supply [7] IDC circuits do not support alarm verification using four-wire smokes. Requires resettable 24 Vdc from AUX Power terminals. [8] 5.0 A total with optional transformer (P/N XTR3A120 or XTR3A230 [9] Automatic and manually activated alarm initiating devices can be installed on the same IDC circuit regardless of circuit type except for combination circuits (option 6, setting 5 and 6) [10] Combination circuits consist of waterflow switches (WF) and their associated valve tampers (SS) [11] Relay circuits can only be connected to power-limited sources [12] Installation limits under jurisdiction of local authority [13] Refer to the FireShield Technical Reference Manual (P/N 3100353) for the topic "Installing the FSDACT."

NOTES 1. All wiring is power-limited except for AC power and battery wiring. All wiring is supervised unless otherwise noted.

[2] Dashed lines show Class A wiring [3] Listed EOLRs must be installed as shown for proper supervision. EOLRs are not required for Class A operation. [4] For UL installations use EOLR P/N EOL3.6-1.1 which includes one 1.1 k (P/N EOL1.1) and one 3.6 k (P/N EOL3.6) resistor. For ULC installations use EOL-P1 and select the 1.1 k and 3.6 k resistors. [5] Marking indicates output signal polarity when the circuit is active. Polarity reverses when the circuit is not active. Wire notification appliances accordingly. Notification appliance polarity shown in active state.

C.6

FireShield Technical Reference Manual

Appendix D

Panel specifications
FS302 three-zone panel Initiating device circuits (IDCs) Notification appliance circuits (NACs) Power supply NAC voltage rating Maximum NAC current 1.5 amps each 1.5 amps total Class B Class A Class B Class A 3 0 2 0 2.0 amps total FS502 five-zone panel 5 0 2 0 3 1 0 1 24 Vfwr 1.5 amps each 2.5 amps total 1.5 amps each - 2.5 amps total for NAC1 + NAC2 or NAC3 + NAC4 5.0 amps with optional expander transformer AC input 120 Vac 60 Hz 230 Vac 50/60 Hz 0.8 amps 0.4 amps 110 mA 145 mA 0.8 amps 0.4 amps 120 mA 170 mA 1.6 amps - incl. optional exp. transformer 0.8 - incl. optional exp. transformer 145 mA 250 mA Up to two 18 Ah batteries will fit in the panel. 1 2 FS1004 ten-zone panel 10 0 4 0 8 1 6 2 2 1 4 3 2 4 0 2 0 5

3.0 amps total

3.0 amps (expandable to 5.5 amps)

Base panel current draw (standby) Base panel current draw (alarm) Battery placement Maximum auxiliary current Auxiliary output IDC max. detector standby current IDC circuit IDC operating voltage Compatibility ID Alarm contact Trouble contact Supervisory contact Environmental Terminal rating Serial communications Batteries

Up to two 7 Ah batteries will fit in the panel. Note: If batteries greater than 7 Ah are required, you must use the BC-2 battery cabinet. Refer to installation sheet P/N 3100027.

0.5 amps (may be programmed as resetable) 19 to 25.7 Vdc 1.5 mA (See FireShield UL and ULC Compatibility List (P/N 3100468) for maximum quantity of detectors per circuit.) Maximum loop resistance: 13 Maximum loop capacitance: 0.03 F 16.3 to 25.7 Vdc 100 Form A N.O. 30 Vdc @ 1 A (resistive load) Form C 30 Vdc @ 1 A (resistive load) Form A N.O. 30 Vdc @ 1 A (resistive load) Temperature: 0 to 49 C (32 to 120 F) Humidity: 5 to 93% RH, noncondensing All terminals rated for 12 to18 AWG (0.75 to 2.5 sq mm) Asynchronous communications maximum resistance: 13 Maximum capacitance: 0.03 F Batteries must be sealed lead acid type only. Maximum charging capacity = 18 Ah.

FireShield Technical Reference Manual

D.1

Panel specifications

D.2

FireShield Technical Reference Manual

Appendix E

Default event codes


Default Contact ID event codes
Code Description Fire alarm general Fire IDC 1 11000001 Fire IDC 2 11000002 Fire IDC 3 11000003 Fire IDC 4 11000004 Fire IDC 5 11000005 Fire IDC 6 11000006 Fire IDC 7 11000007 Fire IDC 8 11000008 Fire IDC 9 11000009 Fire IDC10 11000010 Fire alarm waterflow (sprinkler) Waterflow IDC 1 11300001 Waterflow IDC 2 11300002 Waterflow IDC 3 11300003 Waterflow IDC 4 11300004 Waterflow IDC 5 11300005 Waterflow IDC 6 11300006 Waterflow IDC 7 11300007 Waterflow IDC 8 11300008 Waterflow IDC 9 11300009 Waterflow IDC 10 11300010 Fire alarm bypass Fire bypass IDC 1 57000001 Fire bypass IDC 2 57000002 Fire bypass IDC 3 57000003 Fire bypass IDC 4 57000004 Fire bypass IDC 5 57000005 Fire bypass IDC 6 57000006 Fire bypass IDC 7 57000007 Fire bypass IDC 8 57000008 Fire bypass IDC 9 57000009 Fire bypass IDC 10 57000010 Supervisory general Fire supervisory IDC 1 20000001 Fire supervisory IDC 2 20000002 Fire supervisory IDC 3 20000003 Fire supervisory IDC 4 20000004 Fire supervisory IDC 5 20000005 Fire supervisory IDC 6 20000006 Fire supervisory IDC 7 20000007 Fire supervisory IDC 8 20000008 Fire supervisory IDC 9 20000009 Fire supervisory IDC 10 20000010

Trouble zone Fire trouble (380 Sensor trouble) IDC 1 37300001 Fire trouble (380 Sensor trouble) IDC 2 37300002 Fire trouble (380 Sensor trouble) IDC 3 37300003 Fire trouble (380 Sensor trouble) IDC 4 37300004 Fire trouble (380 Sensor trouble) IDC 5 37300005 Fire trouble (380 Sensor trouble) IDC 6 37300006 Fire trouble (380 Sensor trouble) IDC 7 37300007 Fire trouble (380 Sensor trouble) IDC 8 37300008 Fire trouble (380 Sensor trouble) IDC 9 37300009 Fire trouble (380 Sensor trouble) IDC 10 37300010 Monitor point/zone active General alarm IDC 1 14000001 General alarm IDC 2 14000002 General alarm IDC 3 14000003 General alarm IDC 4 14000004 General alarm IDC 5 14000005 General alarm IDC 6 14000006 General alarm IDC 7 14000007 General alarm IDC 8 14000008 General alarm IDC 9 14000009 General alarm IDC 10 14000010 NAC trouble 32000001 Trouble NAC 1 32000002 Trouble NAC 2 32000003 Trouble NAC 3 32000004 Trouble NAC 4 NAC bypass 52000001 Bypass NAC 1 52000002 Bypass NAC 2 52000003 Bypass NAC 3 52000004 Bypass NAC 4 System events AC failure 30100000 Transformer 2 trouble 30100000 Battery bad 30200000 Reset 30500000 Internal communications fault 30800000 Charger trouble 30900000 Ground fault 31000000 Battery missing 31100000 Auxiliary power trouble 31200000 Panel silence 31500000 Signal silence 32800000 Peripheral trouble 33000000 DACT line 1 trouble 35100000 DACT line 2 trouble 35200000 DACT delivery trouble 35400000 RRM bypass 53000000 DACT disabled 55100000 Drill 60100000 Panel test 60200000 Walk test 60700000 Panel abnormal test 60800000 Program mode entry 62700000 Program mode exit 62800000

FireShield Technical Reference Manual

E.1

Default event codes


Code Description E<N> Supervisory restoration E<N> Monitor restoration F<N> IDC trouble restoration Note: N is the circuit number.

Default (4/2) event codes


Code 1<N> 2<N> 3<N> 4 5<N> 6<N:1-4> 65 66 67 68 69 6A 6B 6C 6D 6E 6F 7<N> 8<N> 9<N> A<N:1-4> A5 AA AB AC AD AE AF B<N:1-4> B5 BB BC BD BE BF C1 C2 CA D<N:1-4> D5 D6 D7 D8 D9 DA DB DC DD DE DF E<N> E<N> Description Fire alarm activation events Waterflow alarm activation events Supervisory signal activation events Not used Monitor signal activation events NAC trouble activation events Aux power trouble activation Ground fault activation DACT delivery trouble DACT line 1fail AC loss Transformer 2 trouble Charger trouble Battery missing/Battery bad FSRSI, FSRZI, FSRRM trouble DACT line 2 fail DACT abnormal test IDC trouble activation IDC disabled (not configurable) IDC enabled (not configurable) NAC disabled (not configurable) FSRRM outputs disabled (not configurable) Internal communication trouble Panel reset Signal silence activated Drill activated DACT disabled Walk test activated NAC enabled (not configurable) FSRRM outputs enabled (not configurable) Panel reset restore (not configurable) Signal silence ended (not configurable) Drill ended (not configurable) DACT enabled (not configurable) Walk test ended (not configurable) Program mode entry Program mode exit (not configurable) Panel silence activated NAC trouble restoration Aux power trouble restoration Ground fault restoration DACT delivery trouble restore DACT line 1 restoration AC loss restoration Transformer 2 restoration Charger trouble restoration Battery missing/Battery bad restore FSRSI, FSRZI, FSRRM restoration DACT line 2 restoration DACT normal test Fire alarm restoration Waterflow alarm restoration

E.2

FireShield Technical Reference Manual

Index
4
4/2 event codes E.2

D
default event codes FSDACT E.1 defaults factory defaults 3.2 reloading the factory defaults 3.2 disable IDC 1.2, 1.5 LED 1.2 NAC 1.2, 1.5 disabled events 3.15 drill drill button 1.2 using the drill command 1.5

A
alarm IDC zone type 3.4 LED 1.2 resounding an alarm condition 1.4 signal silenced LED 1.2 annunciator trouble LED 1.2 auto NAC silence timer description 3.3 operation 1.4 programming 3.3 aux power reset description 3.4 programming 3.4 auxiliary power supply installing 2.12

E
enable re-enable IDC or NAC 1.5 enclosure See cabinet event notification programming FSDACT 3.14

B
battery calculation A.1 battery trouble LED 1.2 binary numbers LEDs 3.1 buttons disable IDC 1.2 disable NAC 1.2 operating mode 1.1 programming mode 1.1, 3.1 buzzer FSRSI 2.2 silencing FSRSI buzzer 1.4 silencing panel buzzer 1.4

F
find peripherals description 3.3 programming 3.3 FireShield Configuration Utility 3.1 FSCU 3.1 FSDACT 1.3 4/2 event codes E.2 changing password 3.9 contact ID E.1 default event codes E.1 description 2.8 digit descriptions 3.8 display 3.1 editing programed information 3.17 event notification programming 3.14 getting started (programming) 3.8 installing 2.8 panel programming 3.2 password 3.9 programming 3.7, 3.8, 3.9 programming buttons 3.8 FSRPM description 2.10 installing 2.10 wiring 2.10 FSRRM command options 2.5 description 2.5 installation instructions 2.6 jumper setup 2.5 MFC-A 2.6 service and troubleshooting 2.6 specifications 2.5 wiring 2.6 FSRSI buzzer 1.4, 2.2 description 2.2 installation instructions 2.2 jumper setup 2.2 lamp test 1.6

C
cabinet dimensions 2.1 installing 2.1 MFC-A 2.6 semi-flush mount 2.1 surface mount 2.1 calculations battery A.1 NAC maximum wire length A.4 NAC voltage drop A.3 checklist installation checklist 2.1 class A programming 3.5, 3.6 wiring C.1, C.3, C.5 class B programming 3.5, 3.6 wiring C.1, C.3, C.5 command options FSRRM 2.5 component descriptions 1.3 contact ID codes E.1 CTM description 2.11 installing 2.11 wiring 2.11

FireShield Technical Reference Manual

Z.1

Index
LEDs 2.2 specifications 2.2 wiring 2.3 FSRZI-A description 2.3 installation instructions 2.4 jumper setup 2.4 lamp test 1.6 LEDs 2.3 specifications 2.3 wiring 2.4

M
maintenance 4.1 metal dead front installing 2.12 MFC-A FSRRM 2.6 monitor IDC zone type 3.4 LED 1.2

N G
ground and open tests 4.1 ground fault LED 1.2 NAC disable 1.5 disable button 1.2 maximum wire length A.4 programming class A or class B 3.6 programming outputs 3.6 programming silence inhibit timer 3.4 programming silenceable 3.6 re-enabling 1.5 silencing 1.4 trouble LED 1.2 voltage drop calculation A.3 NAC disabled event 3.15 notification appliance circuit See NAC

I
IDC alarm LED 1.2 disable 1.5 disable button 1.2 programming class A or class B 3.5 programming zone types 3.4 re-enabling 1.5 supervisory/monitor LED 1.2 IDC disabled event 3.15 IDC trouble LED 1.2 initiating device circuit See IDC inputs IDC zone types 3.4 installation checklist 2.1 installing auxiliary power supply 2.12 cabinet 2.1 CTM 2.11 FSDACT 2.8 FSRPM 2.10 FSRRM 2.5 FSRSI 2.2 FSRZI-A 2.3 metal dead front 2.12 power expander transformer 2.7

O
open and ground tests 4.1 operation operating the panel 1.4 overview 1.1 outputs NAC outputs 3.6 overview operation 1.1 system 1.1

P
panel silencing buzzer 1.4 panel silence button operating mode 1.2 programming mode 3.1 password changing FSDACT 3.9 FSDACT 3.9 power expander transformer 1.3 description 2.7 installation instructions 2.7 specifications 2.7 wiring 2.7 power LED 1.2 program jumper 1.3, C.1, C.3, C.5 program mode exiting 3.2 programming auto NAC silence timer 3.3 aux power reset 3.4 buttons 3.1 find peripherals 3.3 FSCU 3.1 FSDACT 3.8, 3.9 IDC class 3.5 IDC zone types 3.4 installing jumper 3.2 load defaults 3.3, 3.9 NAC class 3.6

J
jumper 10-zone panel settings C.5 3-zone panel settings C.1 5-zone panel settings C.3 FSRRM 2.5 FSRSI 2.2 FSRZI-A 2.4 program jumper 1.3, C.1, C.3, C.5

L
lamp test 1.1 conducting a panel lamp test 1.6 conducting an FSRSI and FSRZI-A lamp test 1.6 LEDs binary number value 3.1 FSRSI 2.2 FSRZI-A 2.3 programming 3.1 system 1.2 load defaults description 3.3, 3.9 programming 3.3, 3.9

Z.2

FireShield Technical Reference Manual

Index
NAC output 3.6 NAC silence inhibit timer 3.4 NAC silenceable 3.6 options 3.2 overview 3.1 templates B.1 programming methods 3.1 LED 1.2 surface mount cabinet 2.1

T
tie wrap mounts 1.3 trouble LED 1.2 trouble silence button programming mode 1.2

R
remote disconnect button operating mode 1.1 programming mode 1.1, 3.1 remote relay module See FSRRM remote system indicator See FSRSI remote zone indicator See FSRZI-A reset button operating mode 1.2 programming mode 1.2, 3.1 resetting the panel 1.4

U
ULC tests 4.1

W
walk test audible 1.6 LED 1.2 overview 1.5 silent 1.6 using the walk test command 1.5 walk test button operating mode 1.1 programming mode 1.1, 3.1 waterflow IDC zone type 3.4 wiring 10-zone panel C.5 3-zone panel C.1 5-zone panel C.3 class A C.1, C.3, C.5 class B C.1, C.3, C.5 CTM 2.11 FSRPM 2.10 FSRRM 2.6 FSRSI 2.3 FSRZI-A 2.4 NAC maximum wire length A.4 power expander transformer 2.7

S
semi-flush mount cabinet 2.1 service and troubleshooting FSRRM 2.6 signal silence & drill button alarm mode 1.2 normal mode 1.2 programming mode 1.2, 3.1 silencing FSRSI buzzer 1.4 notification appliances 1.4 panel buzzer 1.4 specifications FSRRM 2.5 FSRSI 2.2 FSRZI-A 2.3 panel D.1 power expander transformer 2.7 supervisory IDC zone type 3.4

FireShield Technical Reference Manual

Z.3

Index

Z.4

FireShield Technical Reference Manual

Frame these instructions and mount on the wall next to the control panel.

FireShield Fire Alarm Control Panel Operating Instructions


For additional information, refer to the FireShield Technical Reference Manual P/N 3100353. RESPONDING TO ALARM SIGNALS 1. 2. 3. Evacuate the area. Notify the proper authorities immediately and state the nature and location of the emergency. Be prepared to provide directions to firefighters when they arrive. TO SILENCE THE PANEL BUZZER 1. Press Panel Silence. The buzzer turns off. Any new events turn the buzzer back on. Trouble conditions not cleared resound the buzzer after a predetermined time. WARNING! Trouble conditions may affect the panel's ability to provide early detection and indication of a fire. Clear trouble conditions immediately. RESPONDING TO SUPERVISORY SIGNALS 1. 2. Silence the panel buzzer. Investigate the cause of the supervisory signal and notify the authorized service personnel immediately. Silence the panel buzzer. Investigate the cause of the monitor signal and notify the authorized service personnel immediately.

TO SILENCE ALARM NOTIFICATION SIGNALS WARNING! Alarm notification signals should not be silenced until after all occupants have been evacuated. 1. Press Signal Silence & Drill. The Signal Silenced LED turns on and all audible notification circuits turn off. New alarm events turn the notification circuits back on. Note: Panel programming may delay alarm silence for up to one minute, may prevent alarm silencing when water flows through the sprinkler system, and may not turn off visible notification circuits. TO RETURN THE SYSTEM TO NORMAL AFTER AN ALARM OR SUPERVISORY EVENT 1. 2. Make sure all smoke detectors are free from smoke and all manual pull stations are reset. Press Reset.

RESPONDING TO MONITOR SIGNALS 1. 2.

PERIODIC TEST RECOMMENDATIONS See Maintenance, in the FireShield Technical Reference Manual for test instructions and references. Installed by Name: Company: Address: Phone: Per NFPA 72 Protected Premises Fire Alarm System, Local Auxiliary Fire Alarm System Remote Supervising Station Fire Alarm System Central Station Date: For service contact Company: Address: Phone: Acceptance Inspection by

Note: Panel programming may delay panel reset for up to one minute after alarm notification circuits turn on. TO INITIATE A FIRE DRILL 1. Press Signal Silence & Drill. All audible notification circuits turn on. This function will not automatically notify the fire department. TO PERFORM A LAMP TEST (panel and remote annunciators) 1.

Press and hold the Remote Disconnect and Walk Test buttons simultaneously.

TO PERFORM A REMOTE ANNUNCIATOR LAMP TEST 1. 2.

Press and hold the Silence button on the RSI for five seconds. LEDs on remote annunciators will remain on until silence button is released.
Silence the panel buzzer. Investigate the cause of the trouble and notify the authorized service personnel immediately.

RESPONDING TO TROUBLE SIGNALS 1. 2.

Date:

Operating Instruction Placard FireShield - Fire Alarm Control Panel

P/N: 3100470 REV: 2.0 1/1