lateral Pressures for Formwork Design

A review of the formulas to determine the pressure of fresh concrete


By M.K. Hurd

resh concrete exerts pressure on vertical form surfaces, and an assessment of that pressure is needed for designing forms. In the simplest theory, fresh concrete acts as a fluid exerting pressure equally in all directions at whatever point the measurement is madeessentially assuming a hydrostatic pressure effect. This is reasonable because the fresh concrete behaves much like a fluid at least briefly during vibration, or for a longer time if flowability of the mixture has been enhanced through use of admixtures or special proportioning and materials selection. But concrete is not a true fluid, and some method of evaluating the concretes actual pressure is needed. Evaluating pressure has been a significant part of the work of ACI Committee 347, Formwork for Concrete. As early as 1958, Committee 347 (then Committee 622) studied available field measurements of lateral pressure on formwork and used the data to develop pressure formulas that could be safely used for form design. A report was published in 1958,1 and the formulas, with some modifications, were included in ACIs first formwork

standard, ACI 347-63.2 In the days before the advent of the personal computer, the committee considered it important to keep the equations simple, reasoning that this would encourage their use and minimize mathematical errors. These formulas were carried forward through successive ACI standards until 2001, when accumulating data3 on lateral pressures enabled the committee to introduce new coefficients for unit weight and chemistry of the mixture, expanding coverage of the formulas to mixtures with cement replacements, admixtures, or both. I wrote about those changes for CI readers in October 2002.4 Further modifications were issued in ACI 347-04,5 however, and clarification of the present status may be needed. To avoid possible confusion, the formulas presented here are given the same identifying numbers as in ACI 347-04.

BasiC Formula

Although the pressure at any given point within the form varies over time, the designer usually doesnt need
Concrete international

/ june 2007

31

Table 1: Unit weight coefficient Cw Used in form pressUre eqUations


Unit weight (density) of concrete Less than 140 lb/ft3 (2240 kg/m3) 140 to 150 lb/ft3 (2240 to 2400 kg/m3) More than 150 lb/ft3 (2400 kg/m3)
Note: w = unit weight (density) of concrete, in lb/ft3 (kg/m3)

Cw (in.-lb version)

Cw (SI version)

Cw = 0.5[1 + (w/145)] but not less than 0.80 Cw = 0.5[1 + (w/2320)] but not less than 0.80 1.0 Cw = w/145 1.0 Cw = w/2320

Table 2: chemistry coefficient CC Used in form pressUre eqUations


Cement type or blend Types I, II, and III cements without retarders* Types I, II, and III cements with a retarder Other types or blends containing less than 70% slag or 40% fly ash without retarders* Other types or blends containing less than 70% slag or 40% fly ash with a retarder* Blends containing more than 70% slag or 40% fly ash Cc 1.0 1.2 1.2 1.4 1.4

to know the variation in detail. Hence, the equations for lateral formwork pressure provide only the maximum to be used for design. The basic formula is: p = wh p = gh (2.1a), in.-lb units (2.1b), SI units

*Retarders include any admixture, such as a retarder, retarding water-reducer, retarding mid-range water-reducing admixture, or high-range water-reducing admixture, that delays setting of concrete

For the equation in in.-lb units, p is the lateral pressure, in lb/ft2; w is unit weight of the fresh concrete, in lb/ft3; and h is the depth in feet of fluid or plastic concrete from the top of a placement to the point under consideration in the form. For the equation in SI units, p is the lateral pressure, in kPa; is the concrete density, in kg/m3; g is the gravitational constant of 9.81 N/kg; and h is the depth of fluid or plastic concrete in meters from the top of a placement to the point under consideration in the form. If a form is filled rapidly before any stiffening of the concrete takes place, h should be taken as the full height of the freshly placed concrete. If multiple placements are to be made, h should be taken as the distance between construction joints. This formula is applicable for all conditions other than those specifically defined for the use of Eq. (2.2), (2.3), and (2.4).

Column Form Pressure

Heavy-duty steel formwork resists concrete pressure in a 16 ft (5 m) high retaining wall. Custom form assembly permitted the contractor to place the wall and projecting corbels monolithically
(Photo courtesy of EFCO Corp.)

For the purpose of pressure determination, Committee 347 defines columns as elements with no plan dimension exceeding 6.5 ft (2 m). For concrete with a slump of 7 in. (175 mm) or less and placed in column forms with normal internal vibration to a depth of 4 ft (1.2 m) or less, ACI 347-04 recommends the following equation for calculating the maximum pressure pmax in lb/ft2 (kPa) to be used for column form design:

pmax = Cw Cc [150 + 9000 R T ]

(2.2), in.-lb units

32

june 2007

/ Concrete international

785 R p max = C w C c 7.2 + T + 17.8

(2.2), SI units

aDDitional inFormation

with a minimum of 600Cw lb/ft2 (30Cw kPa), but in no case greater than Eq. (2.1). Cw and Cc are the unit weight and chemistry coefficients shown in Tables 1 and 2, respectively; R is the rate of placement, in ft/h (m/h); and T is the temperature of the concrete during placement, in F (C). With rapid placement and intensive vibration or with self-consolidating concrete, it is possible to have concrete remaining in a fluid condition for the full duration of the placement, in which case the only theoretical pressure limit will be as in Eq. (2.1). Committee 347 didnt have sufficient test data to develop separate provisions for self-consolidating concrete. A number of studies have been or are being conductedfor example, Reference 6 but definitive results have yet to be found.

For examples showing how to apply these formulas, refer to the 7th Edition of ACI SP-4, Formwork for Concrete.7 Lateral pressure calculations are also presented in the interactive spreadsheet program made available to ACI by William C. Epstein, formerly a Professor of Construction Management at California State Polytechnic University, San Luis Obispo, CA. To use the spreadsheets, visit the Concrete Knowledge Center at www.concrete.org, click on the Construction button, and click on the Form Design Spreadsheet button. Then go down to the bottom of the page and select Walls.

references
1. ACI Committee 622, Pressures on Formwork, ACI JOURNAL, Proceedings V. 55, Aug. 1958, pp. 173-190. 2. ACI Committee 347, ACI Standard Recommended Practice for Concrete Formwork (ACI 347-63), American Concrete Institute, Farmington Hills, MI, 1963, 52 pp. 3. Barnes, J.M., and Johnston, D.W., Modification Factors for Improved Prediction of Fresh Concrete Lateral Pressures on Formwork, Institute of Construction, Department of Civil Engineering, North Carolina State University, Raleigh, NC, Oct. 1999, 90 pp. 4. Hurd, M.K., Putting the Pressure on Formwork, Concrete International, V. 24, No. 10, Oct. 2002, pp. 49-55. 5. ACI Committee 347, Guide to Formwork for Concrete (ACI 347-04), American Concrete Institute, Farmington Hills, MI, 2004, 32 pp. 6. Billberg, P.; Silfwerbrand, J.; and sterberg, T., Form Pressures Generated by Self-Consolidating Concrete, Concrete International, V. 27, No. 10, Oct. 2005, pp. 35-42. 7. Hurd, M.K., Formwork for Concrete (SP-4), 7th Edition, American Concrete Institute, Farmington Hills, MI, 2005, 516 pp. Selected for reader interest by the editors.

Wall Form Pressure

For purposes of pressure determination, ACI 347-04 defines a wall as a vertical structural element with at least one plan dimension greater than 6.5 ft (2 m). ACI 347-04 gives two equations for wall form pressure. As in the case of the column formula, both are applicable to concrete with a slump of 7 in. (175 mm) or less and vibration to a depth of 4 ft (1.2 m) or less. The first, Eq. (2.3), applies to walls with a rate of placement less than 7 ft/h (2.1 m/h) and a placement height of 14 ft (4.2 m) or less:

p max = C w C c [ + 9000 R T ] 150


785 R p max = C w C c 7.2 + T + 17.8

(2.3), in.-lb units

(2.3), SI units

The second equation, Eq. (2.4), applies to all walls with a placement rate of 7 to 15 ft/h (2.1 to 4.5 m/h), and to walls placed at less than 7 ft/h (2.2 m/h), but having a placement height greater than 14 ft (4.2 m).

p max = C w C c [ + 43,400 T + 2800 R T ] (2.4), in.-lb units 150


1156 244 R p max = C w C c 7.2 + + T + 17.8 T + 17.8
(2.4), SI units

For both Eq. (2.3) and (2.4), pmax should be a minimum of 600Cw lb/ft2 (30Cw kPa), but not greater than Eq. (2.1). Because Committee 347 has insufficient data on observed pressure at higher rates, Eq. (2.4) does not apply for rates of placement greater than 15 ft/h (4.5 m/h).

ACI Honorary Member M.K. Hurd is a member of ACI Committees 124, Concrete Aesthetics, and 347, Formwork for Concrete. She has received numerous awards for her service and contributions to ACI, including the ACI Construction Award (1982 and 1988), the delmar L. Bloem Award for distinguished Service (1990 and 2006), and the Henry C. Turner Medal (1995). The author of seven editions of ACI SP-4, Formwork for Concrete, Hurd is the first female recipient of the Marston Medal, the highest award bestowed by the College of engineering at Iowa State university.